M502 - Detail 1.pdf

PDF 4 MB Posted

Attached to
Y1DA--Replace Fan Coil Units Federal contract opportunity
Solicitation number
36C24623B0014
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

This document contains mechanical drawings and details for replacing fan coil units at a Department of Veterans Affairs medical center. Key details include drawings showing required piping configurations for two heat exchangers in parallel, with notes specifying saddle supports, adjustable mounting heights to facilitate condensate return, control valve sizing, instrument details, and drain line routing. Additional drawings illustrate connections for inline pumps, inverted bucket steam traps, pipe hangers, securing hanger rods, small pipe anchors, steam line drip pockets and traps, steam pressure reducing stations, supply air duct takeoffs, terminal unit water coils, volume dampers, and general water coil connections. The related federal contract opportunity is solicitation number 36C24623B0014 to replace fan coil units at the Veterans Affairs Medical Center in Fayetteville, North Carolina, issued by the Veterans Health Administration VISN 6.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--Replace Fan Coil Units, newest first.
File Type Posted
SD232113-10. DWG - Dual Heat Exchanger Controls (Heating System).pdf PDF
36C24623B0014 0002.docx DOCX document
36C24623B0014 0001.docx DOCX document
Site Visit Attendance.pdf PDF
SD232213-06 Flash Tank Sizing.pdf PDF
MP203B - MECHANICAL PIPING PLANS -AREA B.pdf PDF
Specifications Replace 3rd Floor FCUs.pdf PDF
Wage Determination.pdf PDF
Issued For Construction Drawings Replace 3rd Floor FCUs.pdf PDF
36C24623B0014_1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

[6 "M

IN

(T Y P m m

D

NOTES:

1. THE ABOVE DETAIL SHOWS REQUIRED PIPING FOR TWO HEAT EXCHANGERS IN PARALLEL. INDICATE IF 100% REDUNDANT OR NOT.

2. PROVIDE SADDLE SUPPORTS AND LEGS OR HANGERS FOR HEAT EXCHANGER. MOUNTING HEIGHT SHALL BE ADJUSTED TO FACILITATE GRAVITY

RETURN OF STEAM CONDENSATE.

3. MAKE THE BYPASS THE SAME SIZE AS THE CONNECTIONS TO THE CONTROL VALVES.

4. CONTROL VALVES SHALL BE IN A 1_

AND 2_

SIZE ARRANGEMENT.

TEST PLUG

(TYP.)

THERMOMETER (TYP.)

HPS STEAM

SUPPLY

HEAT

EXCHANGER

(TYP.)

RUN DRAIN LINE FROM RELIEF VALVE

TO NEAREST FLOOR DRAIN. (TYP.)HW

R

HW

S

15mm [1/2"] CHECK

VALVE VACUUM

BREAKER (TYP.)DDC TEMPERATURE

SENSORS (TYP.)

SEE SCHEDULES FOR RELIEF

VALVE SETTING

TT

PI

PI

BY

PA

SS

IF INSTALLED

LOWER THAN

MAIN HPS LINE,

PROVIDE ANOTHER

SCALE

POCKET/TRAP

HERE.

TT

IF THE SECOND HEAT

EXCHANGER IS NOT A

REDUNDANT 100%

BACK UP UNIT, THEN

PROVIDE A

MOTORIZED ISOLATION

VALVE HERE.

NC

DDC PRESSURE

SENSORS (TYP.)

SCALE POCKET

(TYP.)

HP

R T

O F

LAS

H

TAN

K O R T

O

HP

R

MAI

N L

INE

(T

YP.

CO

NTR

OL

VAL

VES

IN

2/

3 & 1_

SI

ZE

ARR

ANG

EME

NT,

TY

P.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

ENGINEER:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ARCHITECT:

Atriax, PLLC 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254

ISSUED FOR

CONSTRUCTION

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project: 20215.001

B

IM

/2

.0

V

A F a y e tt e v ill e R e p la c e F a n

C o ils rd F lo o r/

.0

V A

F a y e tt e v ill e F a n

C o ils rd F lo o r_ S

E S

.r v t

/1

/2

:0

:1

P

M

M502

MECHANICAL DETAILS REPLACE FAN COIL UNITS - 3RD

FLOOR FAYETTEVILLE VAMC,

FAYETTEVILLE, NC

2300 Ramsey St, Fayetteville, NC 28301

08/12/2022 GWB NLC

565-21-104

100% FINAL

1/8" = 1'-0"

IN-LINE PUMPS - CONNECTIONS

1/8" = 1'-0"

INVERTED BUCKET STEAM TRAP ASSEMBLY

1/8" = 1'-0"

PIPE HANGERS

1/8" = 1'-0"

SECURING HANGER RODS IN CONCRETE

1/8" = 1'-0"

SMALL PIPE ANCHOR (1 1/2" - 4")

1/8" = 1'-0"

STEAM LINE DRIP POCKET AND STEAM TRAP ASSEMBLY

1/8" = 1'-0"

STEAM PRESSURE REDUCING STATION DOUBLE VAVLE (1/3 AND 2/3)

1/8" = 1'-0"

SUPPLY DUCTWORK TAKE-OFFS

1/8" = 1'-0"

TERMINAL UNIT WATER COILS - PIPING CONNECTIONS

1/8" = 1'-0"

VOLUME DAMPER DETAIL

1/8" = 1'-0"

WATER COILS - PIPING CONNECTIONS

1/8" = 1'-0"

HEAT EXCHANGER - STEAM TO HOT WATER

08/12/2022 20215.001

Revisions: Date:

Revision 0 August 12, 2022

File details come from the government source that posted it. Updated .