36C24620R0007-0006005.pdf
PDF Posted
- Attached to
- Inpatient Privacy Renovate 5B
- Solicitation number
- 36C24620R0007
About this file
This presolicitation notice announces an upcoming solicitation for commercial and institutional building construction services. The Department of Veterans Affairs requires renovating approximately 8,000 square feet of space on the fifth floor of the Durham VA Medical Center into twelve private patient rooms and ancillary spaces. The estimated construction value is between $1 million and $5 million. The solicitation will be a total service-disabled veteran-owned small business set-aside and is anticipated to publish around November 7, 2019, with proposals due approximately 45 days later. Interested parties should monitor the website for additional details.
36C24620R0007 0006 07-ELECRICAL_100_BD.1.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24620R0007-0011001.pdf | ||
| 36C24620R0007-0011002.pdf | ||
| 36C24620R0007-0011000.docx | DOCX document | |
| 36C24620R0007-0010000.docx | DOCX document | |
| 36C24620R0007-0009000.docx | DOCX document | |
| 36C24620R0007-0008001.pdf | ||
| 36C24620R0007-0008000.docx | DOCX document | |
| 36C24620R0007-0007000.docx | DOCX document | |
| 36C24620R0007-0006004.pdf | ||
| 36C24620R0007-0006006.pdf | ||
| 36C24620R0007-0006000.docx | DOCX document | |
| 36C24620R0007-0006003.pdf | ||
| 36C24620R0007-0006001.pdf | ||
| 36C24620R0007-0006002.pdf | ||
| 36C24620R0007-0005000.docx | DOCX document | |
| 36C24620R0007-0005001.pdf | ||
| 36C24620R0007-0005005.pdf | ||
| 36C24620R0007-0005004.pdf | ||
| 36C24620R0007-0005002.pdf | ||
| 36C24620R0007-0005003.pdf | ||
| 36C24620R0007-0004000.docx | DOCX document | |
| 36C24620R0007-0003000.docx | DOCX document | |
| 36C24620R0007-0003001.pdf | ||
| 36C24620R0007-0002002.pdf | ||
| 36C24620R0007-0002001.docx | DOCX document | |
| 36C24620R0007-0001001.pdf | ||
| 36C24620R0007-023.pdf | ||
| 36C24620R0007-022.docx | DOCX document |
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIAL PURPOSE RECEPTACLE - MOUNTED 18" AFF
QUADRUPLEX RECEPTACLE (HOSPITAL GRADE) - MOUNTED 18" AFF
LIGHTING CONTACTOR
a
PHOTOCELL
UTILITY KILOWATT-HOUR METER
DUPLEX RECEPTACLE (HOSPITAL GRADE) - EMERGENCY POWER -
MOUNTED 18" AFF
DUPLEX RECEPTACLE (HOSPITAL GRADE) - CEILING MOUNTED
QUADRUPLEX RECEPTACLE (HOSPITAL GRADE) - EMERGENCY
POWER - MOUNTED 18" AFF
MAGNETIC STARTER
SAFETY SWITCH - FUSIBLE
SAFETY SWITCH - NON-FUSIBLE
EQUIPMENT CONNECTION
EXIT SIGN - DUAL FACE, WALL MOUNTED
EXIT SIGN - DUAL FACE, CEILING MOUNTED
EXIT SIGN - SINGLE FACE, WALL MOUNTED
EXIT SIGN - SINGLE FACE, CEILING MOUNTED
ARROW INDICATES DIRECTION OF EXIT
BRANCH CIRCUIT PANELBOARD - FLUSH MOUNTED
DISTRIBUTION PANELBOARD OR SWITCHBOARD
MOTOR CONTROL CENTER
BRANCH CIRCUIT PANELBOARD - SURFACE MOUNTED
CONTROL PANEL
TRANSFORMER
POWER SYMBOLS LIGHTING SYMBOLS
AUTOMATIC TRANSFER SWITCH
CIRCUIT BREAKER
GROUND
ONE-LINE DIAGRAM SYMBOLS
GENERATOR
DELTA-WYE TRANSFORMER
HAND DRYER
CONDUIT - CAPPED
CABLE TRAY
SEALING FITTING
EXPANSION FITTING
CONDUIT FITTING (CONDULET)
JUNCTION BOX
CONDUIT - FLEXIBLE
CONDUIT - CONTINUED
CONDUIT - CONCEALED BELOW
SLAB OR GRADE
CONDUIT - UP AND DOWN
(CHANGE IN ELEVATION)
CONDUIT - TURNING UP
CONDUIT - EXPOSED
CONDUIT - CONCEALED IN
SUSPENDED CEILING OR WALL
CONDUIT - TURNING DOWN
REVISION CALL-OUT
ROOM NUMBER
FEEDER CALL-OUT
MECHANICAL EQUIPMENT CALL-OUT: REFER TO
THE EQUIPMENT DATA SCHEDULE FOR DETAILS
GENERAL SYMBOLS
WIRING AND CONDUITS
NEW EQUIPMENT (TYPICAL)
EXISTING EQUIPMENT (TYPICAL)
DEMOLITION EQUIPMENT (TYPICAL)
PUSH BUTTON
WALL MOUNT BRACKET (TYPICAL)
LUMINAIRE - SURFACE MOUNTED
OPEN INDUSTRIAL LUMINAIRE
RECESSED LUMINAIRE CONNECTED TO THE
EMERGENCY POWER SYSTEM
OPEN INDUSTRIAL LUMINAIRE
EMERGENCY POWER SYSTEM OR
BALLAST/DRIVER
LUMINAIRE TYPE
PANEL NAME
LUMINAIRE - RECESSED (REFER TO LUMINAIRE SCHEDULE)
CONNECTED FOR NIGHT LIGHT USE
1LP-1a NL
CIRCUIT NUMBER AND SWITCH LEG
(LUMINAIRES ARE CONTROLLED BY LOCAL
SWITCH UNLESS DESIGNATION GIVEN)
A a
WALL MOUNTED LUMINAIRE
a
T-1
45KVA 3Ø
480V-208Y/120VAC
# AF
# AT
PANELBOARD
QUADRUPLEX RECEPTACLE (HOSPITAL GRADE) -
MOUNTED 8" ABOVE COUNTER
LINEAR PENDANT
PENDANT
LRP LIGHTING RELAY PANEL
INV INVERTER
RECESSED DOWNLIGHT
EMERGENCY LIGHT
EXIT SIGN WITH EMERGENCY LIGHT
ARROW INDICATES DIRECTION OF EXIT
Room name 101A
PLUMBING EQUIPMENT CALL-OUT: REFER TO
THE EQUIPMENT DATA SCHEDULE FOR DETAILS
J
G
# A
# POLES
VOLTS
PANEL
M
F
VFD
T
POLE MOUNTED TRANSFORMERT
J
H
B
DUPLEX RECEPTACLE (NEMA 5-20R) (HOSPITAL GRADE) -
MOUNTED 18" AFF
GFI GROUND FAULT CIRCUIT INTERRUPTER
SS SURGE SUPPRESSOR (ISOLATED GROUND TYPE)
WP WEATHERPROOF
TP TAMPER PROOF
DED DEDICATED
AC MOUNT 8" ABOVE COUNTER
FLOOR BOX - SEE SPECS OR KEYED NOTES ON
PLAN FOR DETAILS
COMBINATION STARTER
VFD VARIABLE FREQUENCY DRIVE WITH INTEGRAL
DISCONNECTING DEVICE
PC
LC1
TOGGLE SWITCH - MOUNTED 48" AFF
b LOWER CASE LETTER DENOTES LTG. SWITCH GROUP
2 DOUBLE-POLE SINGLE-THROW (DPST)
3 3-WAY
4 4-WAY
B PUSHBUTTON
D DIMMER (WALL BOX TYPE)
K KEY OPERATED
M MANUAL MOTOR STARTER
P PILOT LIGHT
T TIMER
TT THERMAL TRIP SWITCH
WP WEATHERPROOF
OS WALL BOX OCCUPANCY SENSOR
OS2 WALL BOX OCCUPANCY SENSOR FOR TWO LEVEL
SWITCHING
VS WALL BOX VACANCY SENSOR
LV LOW VOLTAGE SWITCH
LVD LINE VOLTAGE DIMMER
LVDS LINE VOLTAGE DIMMER WITH INTEGRAL VACANCY SENSOR
OS
DL
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
a LOWER CASE LETTER DENOTES LTG. SWITCH GROUP
CEILING MOUNTED DAYLIGHT SENSOR
a LOWER CASE LETTER DENOTES LTG. SWITCH GROUP a
VS CEILING MOUNTED DUAL TECHNOLOGY VACANCY SENSOR
a LOWER CASE LETTER DENOTES LTG. SWITCH GROUP
GROUND BAR
100A4G
# KVA/KW
480Y/277V, 3Ø, 4W
CLNG
AC
AHU-1
GWH1
E
ELECTRICAL ABBREVIATIONS LIST
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UNO UNLESS NOTED OTHERWISE
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
N NEW, THIS PROJECT
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORDCOORDINATE
COR CONTRACTING OFFICER
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
L
L
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED
PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND
WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE
BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL
PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE
WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND
THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED
MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO
AVOID CONFLICT DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE. ALL DEVICES/EQUIPMENT LOCATIONS SHALL BE LABELLED IDENTIFYING FEEDER
AND ELECTRICAL CIRCUIT DESIGNATION.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO
INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR
MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE
ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR
EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE
DEVICE'S SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT
UNLESS NOTED OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON
VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET).
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN
APPROVED THIRD PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE
SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC
PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE
MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT
BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE
BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS
DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:4
P
M
E-001
ELECTRICAL GENERAL INFORMATION
1 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
ELECTRICAL SYMBOL LEGEND
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
C5010A
C5012
SURG RISK
ASSESSMENT NURSE
HOUSE
KEEPING
ELEVATOR
ELEVATOR
G
FI
G
FI
G
FI
GFIGFI
GFI GFI
G
FI
G
FI
G
FI
J
G
FI
J J J J
J
J J
J
J J
J
J
J J
J
J
J
J
J
JJJ
J
J
J
J
J
JJ
J
GFI
G
FI G
FI
J J
JJ J
J
J
J
J
J J
J J
J
J
J
J
J
JJ
J
J
J
J
J
J
J
JJ
J
G
FI
J
J
J
J
GFI
LI
M
IT
O
F P
R O
JE
C
T S
C O
P E
L L
M M
N N
P P
Q Q
R R
R.1 R.1
5.1
5.1
8 9
13 14
14 15
SS
TT
TYP.
TYP. TYP.01
(EX)
MATV
CABINET
01 01
(EX)
FA TERMINAL
CABINET
TYP.
TYP.
TYP.
TYP.01
TYP.01
TYP.01
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:1
P
M
ED101
FIFTH FLOOR ELECTRICAL
DEMOLITION PLAN
2 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
0 4 8 16
NORTH
TRUE
Scale: 1/8" = 1'-0"
FIFTH FLOOR ELECTRICAL DEMOLITION PLAN
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
1. CONTRACTOR SHALL BE RESPONSIBLE FOR
TRACING AND IDENTIFYING ALL CIRCUITS AND
CONDUITS THAT ORIGINATE, PASS THROUGH,
OR TERMINATE IN THE AREA OF WORK.
DEMONLISH ALL CIRCUITS THAT ARE NO
LONGER IN USE. MAINTAIN CIRCUIT
CONTINUITY TO ALL CIRCUITS WHICH ARE
NOT COMPLETELY REMOVED.
2. CONTRACTOR TO DISCONNECT AND REMOVE
ELECTRICAL CONNECTION TO OUTLETS,
RECEPTACLES, HVAC EQUIPMENT AND
OTHER ELECTRICAL DEVICES. REMOVE
CONDUCTORS AND CONDUIT BACK TO
PANELBOARD SERVING EQUIPMENT OR TO
THE POINT WHERE OTHER REMAINING LOADS
ARE CONNNECTED. MARK ANY ABANDONED
OVERCURRENT PROTECTION DEVICE AS
"SPARE (UNUSED)".
3. ABANDONED CONDUIT/BOXES SHALL HAVE
ALL ELECTRICAL WIRING REMOVED
COMPLETELY AND NOT JUST MADE "SAFE".
CONDUIT/BOXES SHALL BE REMOVED WHERE
PRACTICAL WITHOUT CREATING ADDITIONAL
DEMOLITION WORK FOR OTHER TRADES.
CIRCUITS SUPPLYING EQUIPMENT WHICH IS
REMOVED UNDER THE CONTRACT
DOCUMENTS FOR ANY DIVISION SHALL, FOR
THE PURPOSES OF THIS NOTE, BE
CONSIDERED "ABANDONED".
4. WHERE CONDUIT IS REMOVED FROM AN
EXISTING RATED ASSEMBLY NOT SUBJECT TO
DEMOLITION, THE REMAINING PENETRATION
SHALL BE PATCHED/REPAIRED TO MAINTAIN
THE RATING OF THE ASSEMBLY.
5. DEMOLITIONS SHALL INCLUDE BUT NOT BE
LIMITED TO THOSE DEVICES AND OR
SYSTEMS NOTED. COORDINATE WITH
ARCHITECTURAL AND MECHANICAL
DEMOLITION PLANS FOR WORK SCOPE. FIELD
VERIFY EXISTING CIRCUITING. HEAVIER LINE
WEIGHT AND INDICATES DEMOLITION WORK.
LIGHTER LINE WEIGHT INDICATES EXISTING
TO REMAIN, VERIFY IN FIELD.
6. OWNER HAS FIRST RIGHT OF REFUSAL TO ALL
DEMOLITION ITEMS INCLUDING BUT NOT
LIMITED TO SMOKE/FIRE ALARM DEVICES, ALL
LIGHT FIXTURES AND, LAMPS OR RELATED
ASSEMBLIES. ANY ITEMS NOT IDENTIFIED BY
OWNER TO BE SAVED SHALL BE LEGALLY
DISPOSED OF IN ACCORDANCE WITH STATE
AND FEDERAL REGULATIONS.
01 (TYP) LED RETROFIT FIXTURE TO BE
REMOVED AND TURNED OVER TO VA
DURHAM. COORDINATE WITH COR.
02 EXISTING PANEL LF. REMOVE AND RELOCATE
TO NEW ELECTRICAL CLOSET B5017A. FIELD
VERIFY ANY EXISTING CIRCUITS NOT
REMOVED UNDER DEMOLITION FOR (5B),
EXTEND AND RELOCATE CIRCUITS TO NEW
PANEL LOCATION. SEE DETAIL 6 SHEET E-401.
kgenther Model
D E
D
AC
GFI
A C
G
FI
A C
G
FI
A C
G
FI
U S
B A
C
J
J J J
E
J
U S
B A
C
PATIENT RM
B5008
CARE STATION
B5009
PATIENT RM
B5010
PATIENT RM
B5011
PATIENT RM, BARIATRIC
B5012
LOCKER
B5014
PATIENT RM
B5016
SOILED UTILITY
B5018
STAFF LOUNGE
B5015
CLEAN SUPPLY
B5019
ALCOVE
B5020
PATIENT RM
B5021
PATIENT RM
B5022
PATIENT RM
B5024
PATIENT RM
B5025
PASSAGE
B5041
NOUR
B5026
MEDS
B5027
CORRIDOR
B5040
STAIR
B5050
STAFF TLT
B5014A
PATIENT RM, ISOLATION
B5028
BATH
B5028A
ANTE
B5028B
PATIENT RM, ISOLATION
B5029
BATH
B5029A
ANTE
B5029B
PATIENT RM, BARIATRIC
B5007
CARE STATION
B5005
EQUIP
B5004
CARE STATION
B5013
CARE STATION
B5023
NURSE MGR OFFICE
B5030EQUIP
B5017
TEAM WORK ROOM
B5031
ELEC
B5017A
OIT
B5003A
E-401
E-401
3 _____ E-401
E-401
4_____ E-401
E-401
E-401
L L
M M
N N
P P
Q Q
R R
R.1 R.1
5.1
5.1
8 9
13 14
14 15
SS
TT
(19) (21)
(21)
(19)
(19)
LF-17
LF-19,21
LF-31
ESCE-2
(GS1) LF-14
(GS2) LF-12
(EC) 5CE-13
(G51) LF-20
(GS2) LF-18
(EC) 5CE-7
(GS1) LF-10
(GS2) LF-12
(EC) 5CE-13
ESCE-2
(GS1) LF-16
(GS1) LF-18
(EC) 5CE-7
(GS1) LF-8
(GS2) LF-10
(EC) 5CE-5
LF-8
5CE-11
E5CD-7,9
LF-8
(GS1) LF-6
(GS2) LF-2
(EC) 5CE-3
(GS1) LF-4
(GS2) LF-2
(EC) 5CE-3
LF-2
LF-7
LF-9
B1-E5CE-1
(GS1) LF-3
(GS2) LF-5
(EC) 5CE-5
(GS1) LF-23
(GS2) LF-25
(EC) 5CE-10
(GS1) LF-27
(GS2) LF-25
(EC) 5CE-10
LF-27
5CE-1
(GS1) LF-32
(GS2) LF-30
(GS1) LF-28
(GS2) LF-30
(EC) 5CE-18
5CE-1
LF-1
LF-1
LF-13
LF-15
5CE-6
E5CE-1
BIO
B5003
LF-39
LF-11
02 (TYP)
02 (TYP)
02 (TYP)
(EC) 5CE-18
PNL-E5CT
LF-1
EWC
E5CE-9 E5CE-11
LF-8
LF-13
ESCE-22
R R
R.1 R.1
5.1
5.1
8 9
SS
TT
JJ
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1
/2
:3
:1
A
M
EP101
FIFTH FLOOR POWER PLAN
3 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
0 4 8 16
NORTH
TRUE
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
FIFTH FLOOR POWER PLAN
A. PROVIDE 2 CRITICAL BRANCH E1 NORMAL
BRANCH 20A CIRCUITS FOR PATIENT
HEADWALL.
B. SEE -E401 FOR ELECTRICAL ROOM AND
CLOSET ENLARGEMENTS.
C. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12
AWG EG IN 3/4" CONDUIT UNLESS NOTED
OTHERWISE:
20-AMP CIRCUITS LESS THAN 150'
SHALL BE MINIMUM 2-12 AWG, 1-12 AWG
EG IN 3/4" C.
20-AMP CIRCUITS 150'-250' SHALL BE
MINIMUM 2-10AWG, 1-10 AWG EG IN
3/4" C.
20-AMP CIRCUITS GREATER THAN 250'
SHALL BE MINIMUM 2-8 AWG, 1-8 AWG
EG IN 3/4" C.
D. COORDINATE LOCATION AND ELECTRICAL
REQUIREMENTS OF MECHANICAL AND
PLUMBING EQUIPMENT WITH MECHANICAL AND
PLUMBING CONTRACTORS.
E. COORDINATE EQUIPMENT WITH
ARCHITECTURAL EQUIPMENT PLANS AND
SCHEDULES.
F. ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/ TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
G. ALL RECEPTACLES SHALL HAVE THEIR
SOURCE PANEL AND CIRCUIT NUMBER
INDICATED ON THEIR FACEPLATE.
H. SEE ENLARGED SCALE DETAIL PLANS SHEET
E-401 FOR DEVICE LOCATIONS IN PATIENT
ROOMS.
01 SEE SHEET GC001 FOR WORK SCOPE
RELATED TO ALTERNATE DEDUCT 1.
02 CIRCUITING FOR PATIENT ROOMS (TYP), SEE
DETAIL PLANS SHEET E-401.
03 SEE ARCHITECTURAL ELEVATIONS AND
DETAILS FOR DEVICE LOCATIONS.
04 POWER AT WALL JUNCTION BOX FOR
CONNECTION TO SYSTEMS FURNITURE.
PROVIDE CIRCUITS AS NOTED. COORDINATE
WITH VA FURNISHED SYSTEMS FURNITURE
AND PROVIDE COVER PLATE AT JUNCTION
BOX.
05 POWER FOR AUTOMATIC DOOR OPENER.
COORDINATE INTERCONNECTION WITH DOOR
CONTROL HARDWARE AND AETHON ROBOT
SYSTEM CONTROLS.
Scale: 1/8" = 1'-0"
FIFTH FLOOR POWER PLAN ALTERNATE DEDUCT 1 0 4 8 16
NORTH
TRUE
TO PNL LF
(B5017A)
1" C
TO PNL 5CE
(B5017A)
3/4" C
AETHON ROBOT DOOR INTERCONNECTIONS REVISION 08/15/2019
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
FG144A
EG017A
GENERAL
LAB
STORAGE
TO CRAWL
SPACE
TO CRAWL
RAMP
RAMP
BG000
BG001
AG002A
AG000A
AG002
CG008
S4
S5 P3
P2
P1 P7
P6
P5
AG005
AG009
AG011AG012
AG009A
AG008
AG015A
AG015B
AG003
CG009
CG007
CG010
BG003
FG145
FG146A
EG006
EG013
EG015
EG017
EG007
EG011
EG009
EG018
EG010
EG014
EG012
EG008
EG004
EG005
EG002
EG003
FG156
FG155
FG154
FG143
FG137A
FG147FG146 FG147A
FG142
FG148
FG149
FG157
FG158
FG104
FG160
FG160A
FG159
AG017
AG015
AG010
EG005A
EG007A
EG001
FG43
FG141
FG104A
FG156A
FG151
BG001A
AG001
EG003A EG003B
EG012A
EG018A
EG017A
FG1000
CG003
ROLLING
SHUTTER
UP
DN
STAIR-1
CANTEEN STORAGE
OFFICE
MORGUE
OFFICE
FREEZER
OFFICE
VENDING RM
KEEPING
CPR EQUIP
CANTEEN CANTEEN
OFFICE
FREEZER
STAIR-12
FIRE PROTECTION
HOUSE
ELECTRICAL RM
TELEPHONE
CLOSET
ISO OFFICE
KEEPING
OFFICE
LAB
OFFICE
OFFICE
OFFICE
STORAGE
STORAGE
STORAGE
RESEARCH
AFGE
AFGE
DECEDENT
AFFAIRS OFFICE ISO OFFICE
IRM OFFICE
CLOSET TOILET
SERVER RM
TELECOM
TELECOM
OFFICE
CLOSET
ELEVATOR
ELECTRICAL
HOUSE
LAB
FIRE PROTECTION
STORAGE
IRM OFFICE
STORAGE
CANTEEN
STAIR-10
HAC
DUMB WAITER
DUMB WAITER
GREEN
ELEVATOR
GREEN
ELEVATOR
GREEN
ELEVATOR
OFFICE
DUMB WAITER
FIRE PROTECTION
FIRE
CANTEEN
STORAGE
LINEN
CHUTE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ELEVATOR
CAFETERIA
CAFETERIA
LINEN
CHUTE LINEN
CHUTE
SHAFT
MENS TOILET
TRASH RM
FEMALE TOILET
FEMALE TOILET
CORRIDOR
CORRIDOR
CORRIDOR
RETAIL STORE
MECH
RETAIL STORE
RECORDS RM
OFFICE, PRIVACY
CANTEEN DINING
CANTEEN DINING
CANTEEN DINING
KITCHEN
CANTEEN DINING
OFFICE
CORRIDOR
OFFICE, NURSING UNION ISO OFFICE
CORRIDOR
CORRIDOR
MECH RM
CORRIDOR
CORRIDOR
ELECTRICAL
ELECTRICAL
PROTECTION
446. 3969
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:2
P
M
EP102
PARTIAL GROUND FLOOR ELECTRICAL
ROUTING PLANS
4 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
Scale: 3/32" = 1'-0"
PARTIAL GROUND FLOOR ELECTRICAL ROUTING PLAN
01 EXISTING PANEL 'EED'. REFERENCE SINGLE
LINE SHEET E-601.
02 3" CONDUIT UP. REFERENCE SINGLE LINE
SHEET E-601.
03 FEEDER UP TO 5TH FLOOR. PROVIDE
FIRE/SMOKE RATED PENETRATIONS AS
REQUIRED BY CODE.
04 EXISTING SUBSTATION 120/208V, 3 PHASE, 4
WIRE.
05 ROUTING OF NEW RACEWAYS TO BE
COORDINATED WITH EXISTING CONDITIONS.
NO NEW RACEWAYS TO BE LOCATED BELOW
7'-6" ABOVE FINISHED FLOOR. REVIEW AND
NOTIFY COR OF CONFLICTS PRIOR TO
INSTALLATION FOR RESOLUTION.
A. COORDINATE ALL WORK WITH COR.
B. FOLLOW ALL ICRA GUIDELINES WHEN
PERFORMING WORK OUTSIDE PRIMARY AREA
OF WORK. COORDINATE WITH COR.
C. ELECTRICAL CONTRACTOR SHALL FOLLOW ALL
SITE LOCK-OUT/ TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
0 84 16
NORTH
TRUE
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
B1005
B1007 B1005A
B1003
A1009 A1011
C1010
C1024
C1014
C1012
C1008
C1018
C1006
B1001
C1030
B1001A
ELEVATOR
ELEVATOR
STAIR-1
ELEVATOR
ELEVATOR ELEVATOR
C10000
C1001
A1005
A1007
A1005A
A1005C
C1005
C1003
OFFICE
COFFE SHOP
WEAPON
OFFICE
ROOM
POLICE
RM
TRASH
CHUTE
OFFICE
IRB
TO PARKING GARAGE
OFFICE
TELEPHONE
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
GENERAL
DUMB
OFFICE
OFFICE
HAC
LINEN
CHUTE
P5
GREEN
ELEVATOR
P6
GREEN
ELEVATOR
P7
GREEN
ELEVATOR
LINEN/
BREAK
POLICE
A1005D
ROOM
HOLDING
KEEPING
HOUSE
CO-ORDR
FIRE PROTECTION
OFFICE
WAITER
DUMB
WAITER
C1008A
SVC
CUSTOMER
GENERAL
EVIDENCE
STORAGE
C1005A
ALCOVE
OIT
GENERAL
POLICE
STORAGE
STORAGE
A1007
B1003A
1CW4C
O
R R
ID
O
R
C O
R R
ID
O
R
C O
R R
ID
O
R
C W
C
W
1AW1CORRIDOR
C
W
C
W
CORRIDOR
C O
R R
ID
O
R
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:2
P
M
EP103
PARTIAL FIRST FLOOR ELECTRICAL
ROUTING PLANS
5 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
01 3" CONDUIT UP/DN. REFERENCE SINGLE LINE
ON SHEET E-601, AND ELECTRICAL ROUTING
PLANS.
Scale: 1/8" = 1'-0"
PARTIAL FIRST FLOOR ELECTRICAL ROUTING PLAN
A. COORDINATE ALL WORK WITH COR.
B. FOLLOW ALL ICRA GUIDELINES WHEN
PERFORMING WORK OUTSIDE PRIMARY AREA
OF WORK. COORDINATE WITH COR.
C. ELECTRICAL CONTRACTOR SHALL FOLLOW ALL
SITE LOCK-OUT/ TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
0 4 8 16
NORTH
TRUE
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
COOLER
SPD CLEAN STORAGE
STORAGE RM
STERILISATION
IMR OFFICEOFFICE
TOILET
TOILET
SPD STORAGE
CLOSET
OFFICE
OFFICE/LAB
OFFICE/LAB
LINEN /
LINEN CHUTE
SHAFT
DUMB WAITER
BREAKOUT
FIRE PROTECTION
MENS
WOMENS
LINEN
CORRIDOR
CORRIDOR
CORRIDOR
ANTE RM
CORRIDOR
RECEIVING AND
PROSTHETICS
OFFICE
TELEPHONE
TRASH CHUTE
CHUTE
CORRIDOR
CORRIDOR
CART STORAGE
SURGICAL SUPPLY AND
CLEAN
C2000
B2005A
B2003B
C2010
C2002
A2001
C2005
A2003
C2015
A2007
C2011
C2009
C2004
A2005
C2005B
C2007
A2007AA2005A
C2005A
A2005B
A
A
A2000B
DN
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:2
P
M
EP104
PARTIAL SECOND FLOOR ELECTRICAL
ROUTING PLANS
6 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
01 3" CONDUIT UP/DN. REFERENCE SINGLE LINE
ON SHEET E-601, AND ELECTRICAL ROUTING
PLANS.
Scale: 1/8" = 1'-0"
PARTIAL SECOND FLOOR ELECTRICAL ROUTING PLAN
A. COORDINATE ALL WORK WITH COR.
B. FOLLOW ALL ICRA GUIDELINES WHEN
PERFORMING WORK OUTSIDE PRIMARY AREA
OF WORK. COORDINATE WITH COR.
C. ELECTRICAL CONTRACTOR SHALL FOLLOW ALL
SITE LOCK-OUT/ TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
0 4 8 16
NORTH
TRUE
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
ANESTHESIOLOGY
CHECK-IN
CORRIDOR
OFFICE
COMPOSITE
DATA
OFFICE OFFICE
OFFICE
NURSING
EDUCATION
CLASS RM
STORAGE CONFERENCE RM
ELEVATOR
ELEVATOR ELEVATOR
ELEVATOR ELEVATOR
STAIR -1
CHAPEL
MEN
WOMENS
HOUSE
KEEPING
WAITING RM OFFICE OFFICE
ELEVATOR
ELEVATOR
ELEVATOR
DUMB WAITER
DUMB WAITER
LINEN CHUTE
STORAGE
DUMB WAITER
DUMB WAITER
STORAGE
OFFICE
ANESTHESIOLOGY
OFFICE
ANESTHESIOLOGY
OFFICE
OFFICE
OFFICE
OFFICE
TRASH CHUTE
LINEN
C3002
A3001A
C3011
A3011A3009A3007A3005
A3001
A3003
C3011A
C3003
C3007C3005
C3014
C3010
C3012C3008
C3006B
C3006A
C3004
C3000B3001
B3003D
B3003C
C3013A
C3013
A3000A
C3009
DN
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:3
P
M
EP105
PARTIAL THIRD FLOOR ELECTRICAL
ROUTING PLANS
7 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
01 3" CONDUIT UP. REFERENCE SINGLE LINE
ON SHEET E-601, AND ELECTRICAL ROUTING
PLANS.
02 3" CONDUIT DOWN. REFERENCE SINGLE
LINE ON SHEET E-601, AND ELECTRICAL
ROUTING PLANS.
Scale: 1/8" = 1'-0"
PARTIAL THIRD FLOOR ELECTRICAL ROUTING PLAN
A. COORDINATE ALL WORK WITH COR.
B. FOLLOW ALL ICRA GUIDELINES WHEN
PERFORMING WORK OUTSIDE PRIMARY AREA
OF WORK. COORDINATE WITH COR.
C. ELECTRICAL CONTRACTOR SHALL FOLLOW ALL
SITE LOCK-OUT/ TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
0 4 8 16
NORTH
TRUE
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
REC 9
REC 8 REC 7
A4001
C4009
C4005
C4001
C4016
C4007
C4014
C4012
C4010
C4004
C4008
C4002
B4001
B4003B4005
C4003
C4019
C4001B
C4001A
C4001C
C4012A
C4000
STAIR-1
NURSE OFFICE
ISOLATION RM
MACHINE
OR-1
OR-9 ANTE RM
ELEVATOR
ELEVATOR
ELEVATOR
ICE
PROTECTION
FIRE
DUMB WAITER DUMB WAITER
TOILET
MENS
STORAGE
HOUSE
KEEPING
DUMB WAITER
TOILET
GAS STORAGE
SHAFT
STORAGE
DUMB WAITER
PGM SUPPORT ASST
FIRE PROTECTION CLOSET
OR-8
LINEN/
TRASH CHUTE
LINEN CHUTE
HOUSE KEEPING
STAFF LOUNGE
ELEVATOR ELEVATOR
ELEVATOR ELEVATOR
ELEVATOR
CORRIDOR
TOILET
CORRIDOR
PACU
DUMB WAITER
DUMB WAITER
HOUSEKEEPING
EQUIPMENT
CLOS
C4006
ELECTRICAL
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:3
P
M
EP106
PARTIAL FOURTH FLOOR ELECTRICAL
ROUTING PLANS
8 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
01 EXISTING PANEL 'ELS4C'. ADD 40A, 3 POLE
BREAKER. REFERENCE SINGLE LINE SHEET
E-601.
02 3-6 AWG, 1-6 AWG NEUTRAL, 1-10 AWG EGC IN
1" CONDUIT. REFERENCE SINGLE LINE SHEET
E-601. PROVIDE FIRE-RATED PENETRATIONS
WHERE REQUIRED BY CODE.
03 3" CONDUIT. REFERENCE EP102-EP105.
Scale: 1/8" = 1'-0"
PARTIAL FOURTH FLOOR ELECTRICAL ROUTING PLAN
A. COORDINATE ALL WORK WITH COR.
B. FOLLOW ALL ICRA GUIDELINES WHEN
PERFORMING WORK OUTSIDE PRIMARY AREA
OF WORK. COORDINATE WITH COR.
C. ELECTRICAL CONTRACTOR SHALL FOLLOW ALL
SITE LOCK-OUT/ TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
0 4 8 16
NORTH
TRUE
OFFICE
STORAGE
OFFICE
DUMB WAITER
SURG RISK
ASSESSMENT NURSE
WORK RM
CHIEF
PLASTIC
SURGY
CHIEF
OTOLARYNGOLOGY
OFFICE
OFFICE
WOMENS
MALE
DUMP WAITER
CONFERENCE RM
SHAFT
FIRE PROTECTION CLOSET
HOUSE
KEEPING
GENERAL
STORAGE
STORAGE
CLOSET
DUMB WAITER ELEVATOR ELEVATOR
ELEVATOR ELEVATOR
OFFICE
CORRIDORSURG
OFFICE
EQUIPMENT
BEDS &
OFFICE
OFFICE
TO AREA
OF WORK
TO AREA
OF WORK B5002
A5002A
C5008
C5006
C5004
C5002
C5026
C5018
C5016
A5002B
C5010A
A5000
C5012
C5010
C5022
C5014A
3'-9 1 4"
C5028
C5014
A5001A
C5000
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
04 03
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:3
P
M
EP107
PARTIAL FIFTH FLOOR ELECTRICAL
ROUTING PLANS
9 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
Scale: 1/8" = 1'-0"
PARTIAL FIFTH FLOOR ELECTRICAL ROUTING PLAN
01 DOWN CONDUIT TO 4TH FLOOR. FEEDS NEW
PANEL 'LS'. REFERENCE SINGLE LINE SHEET
E-601.
02 DOWN CONDUIT. REFERENCE EP102-EP106.
03 3-6 AWG, 1-6 AWG NEUTRAL, 1-10 AWG EGC IN
1" CONDUIT. REFERENCE SINGLE LINE SHEET
E-601. (ELS5C)
04 3-4/0 AWG, 1-4/0 AWG NEUTRAL, 1-2 AWG EGC
IN 3" CONDUIT. REFERENCE SINGLE LINE
SHEET E-601. (E5CD, E5CE).
05 FEEDERS TO ELECTRICAL B5017A.
REFERENCE EP101, AND E-401
ENLARGEMENT 6.
06 EXISTING FA TERMINAL CABINET AND
WIREWAY.
A. COORDINATE ALL WORK WITH COR.
B. FOLLOW ALL ICRA GUIDELINES WHEN
PERFORMING WORK OUTSIDE PRIMARY AREA
OF WORK. COORDINATE WITH COR.
C. ELECTRICAL CONTRACTOR SHALL FOLLOW ALL
SITE LOCK-OUT/ TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
0 4 8 16
NORTH
TRUE
LVD
LV
D S
VSVS
LVD
LVD LVD LVDLVD
LVD
LVDS
LVD
LVDLVD
LVDLVD
LVD LVD
LVD
LVDLVD LVDLVD
LVD LVD
LVD
VS
LVDLVD
LVDLVD
LVDS
LVD
LVDS
LVD
LVD
LVD LVD
LVDS
LVDS
LVDS
LVDS
LVDS
LV
D
S
LV
D
S
LV
D
S
LV
D
S
LV
D
LV
D
LV
D
LV
D
LV
D
VS VS
V S
VS
LVD LVD LVD LVD
LVD
LVD
LVD
LVD
LVD
LVD
LVD
LV
D
SLV
D
J J
LI
M
IT
O
F P
R O
JE
C
T S
C O
P E
PATIENT RM
B5008
CARE STATION
B5009
PATIENT RM
B5010
PATIENT RM
B5011
PATIENT RM, BARIATRIC
B5012
LOCKER
B5014
PATIENT RM
B5016
SOILED UTILITY
B5018STAFF LOUNGE
B5015
CLEAN SUPPLY
B5019
ALCOVE
B5020
PATIENT RM
B5021
PATIENT RM
B5022
PATIENT RM
B5024
PATIENT RM
B5025
PASSAGE
B5041
NOUR
B5026 MEDS
B5027
BATH
B5007A
CORRIDOR
B5040
BATH
B5008A
BATH
B5010A
BATH
B5011A
BATH
B5016A
BATH
B5024A
BATH
B5025A
BATH
B5021A
STAIR
B5050
STAFF TLT
B5014A
PATIENT RM, ISOLATION
B5028
BATH
B5028A
ANTE
B5028B
PATIENT RM, ISOLATION
B5029
BATH
B5029A
PATIENT RM, BARIATRIC
B5007
CARE STATION
B5005
EQUIP
B5004
BATH
B5012A
CARE STATION
B5013
CARE STATION
B5023
NURSE MGR OFFICE
B5030
EQUIP
B5017 TEAM WORK ROOM
B5031
ELEC
B5017A
OIT
B5003A
E1
E1 E1
D1
D1
D1
D1
D1
D1
B1
B2
D1 D1 D1D1
D1 D1
D1 D1
D1
D1 D1
D1
D1 D1
D1 D1D1 D1D1 D1
D1
D1
D1 D1D1
B2
B2 B2
B1
B2 B2
B2B2
A1
A1
A1
A1
B1
B2
B2 B2 B2
B1 B1
D1
D1
D1
D1 D1
D2D2
D1D1
D1
D1
D1D1
D1
D1 D1
D1
D1
D1D1
D1
D1 D1
D1
D1
D2 D2
D1
D1D1
D2 D2
D1 D1
D1
D1D1D1 D1 D1
D1
D1 D1
D1
D2 D2 D2 D1
D1
D1
G G G G GC
NL/EM
G G G G
G
G
G
L L
M M
N N
P P
Q Q
R R
R.1 R.1
5.1
5.1
8 9
13 14
14 15
SS
TT
a a c aa
EM/NL
c b c cNL/EM
'ELS5C'-1
d d d d b e e e
EM/NL
NL/EM
'ELS5C'-1
EXISTING
STAIRWELL
LIGHTING
(EMERGENCY
LIGHTING
CIRCUIT)
NL/EM
'ELS5C'-1
NL/EM
'ELS5C'-1
NL/EM
'ELS5C'-1
'LF'-33 'LF'-33
'ELS5C'-2
'5CE'-3
C2 C1
C2
C2
C2 C2
C2
'5CE'-10
'5CE'-18
'5CE'-18
'5CE'-10
C2 C2
C2
'ELS5C'-2
D1
'LF'-34
'ELS5C'-2
'LF'-34
'E5CE'-20
'E5CE'-20
C1 C1 C1
C1
'5CE'-13
'LF'-34
'LF'-34
'LF'-33
'5CE'-5'5CE'-3
'LF'-33
'E5CE'-20
C1 C1
C1
C1
C1
C1
'LF'-35
'LF'-35
'LF'-35
'5CE'-5
'LF'-33
'LF'-33
C2
'LF'-34
'LF'-34
'5CE'-7
5CE-7
'LF'-34C1
C2 C2
PNL-E5CT
a a a
'LF'-34
a
'LF'-33
'ELS5C'-1
'LF'-33
a a a a
'ELS5C'-1
a a a a a a
'LF'-33
a a
'E5CE'-20
'LF'-34
'LF'-35
a a a
'LF'-33
a a a a
'E5CE'-20
a
B1
'ELS5C'-2
'LF'-37
'LF'-37
'LF'-37
'LF'-37
'LF'-37 'LF'-37'LF'-37'LF'-37
'5CE'-13
A1 A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1
A1 A1A1
E1
E1
R
R.1
5 5.1 6 7 8 9 10
SS
TT
'LF'-35 'ELS5C'-1
TO PNL 'LF'
(B5017A)
3/4" C
TO PNL 'ELS5C'/ 'E5CE'
(B5017A)
(2) 3/4" C
'E5C8'-10, 18
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:1
P
M
EL101
FIFTH FLOOR LIGHTING PLAN
10 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
0 4 8 16
NORTH
TRUE
Scale: 1/8" = 1'-0"
FIFTH FLOOR LIGHTING PLAN
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
A. ALL LIGHTING CONDUCTORS SHALL BE 2-12
AWG, 1-12 AWG EG IN 3/4" CONDUIT UNLESS
NOTED OTHERWISE:
20-AMP CIRCUITS LESS THAN 150'
SHALL BE MINIMUM 2-12 AWG, 1-12 AWG
EG IN 3/4" C.
20-AMP CIRCUITS 150'-250' SHALL BE
MINIMUM 2-10AWG, 1-10 AWG EG IN
3/4" C.
20-AMP CIRCUITS GREATER THAN 250'
SHALL BE MINIMUM 2-8 AWG, 1-8 AWG
EG IN 3/4" C.
B. ALL UN-SWITCHED EXIT SIGNS, EMERGENCY
NIGHT LIGHTS (EM NL), AND EMERGENCY
LIGHTING UNITS SHALL BE CIRCUITED FROM
LIGHTING CIRCUIT 'LS5C'-1, BUT AHEAD OF ANY
CONTROLS OR SWITCHES.
C. ALL SWITCHED EMERGENCY LIGHTS (EM)
SHALL HAVE BOTH NORMAL AND EMERGENCY
POWER. DURING EMERGENCY CONDITION THE
GENERATOR TRANSFER DEVICE SHALL
DETECT NORMAL POWER VOLTAGE LOSS,
TRANSFER TO EMERGENCY POWER AND
EMERGENCY LIGHT SHALL RETURN TO FULL-
OUTPUT. DURING NORMAL NON-EMERGENCY
CONDITION LIGHT FIXTURES SHALL BE
SWITCHED WITH NORMAL LIGHTING AS
SHOWN. SEE DETAIL 5/E-501 NORMAL POWER
CIRCUIT AS SHOWN ON PLAN. EMERGENCY
POWER CIRCUIT IS ON NEW PANEL 'S1H2'.
D. LOCATION AND QUANTITY OF OCCUPANCY
SENSORS IS APPROXIMATE. CONTRACTOR
SHALL FOLLOW MANUFACTURER'S
RECOMMENDED PLACEMENT AND INSTALL PER
MANUFACTURER'S INSTRUCTION..
E. CONTRACTOR SHALL VERIFY COMPATIBILITY
OF ALL LIGHTING CONTROLS WITH THE LED
DRIVERS TO BE CONTROLLED.
F. COORDINATE ALL TIME DELAY, AUTO DIM,
PRESET DIMMING LEVELS, SENSOR
SENSITIVITY AND CONFIGURATIONS WITH THE
COR.
01 (TYP) PROVIDE SWITCH IN CONJUNCTION
WITH PATIENT EXAM/READING LIGHT.
COORDINATE INTERCONNECTION WITH BED
CONTROLS. COORDINATE WITH
MANUFACTURER AND COR.
02 UNDERCABINET LIGHT (TYPE “H”) WITH
ROUND, FROSTED ACRYLIC LENS. (48”L x
2-5/8”W). CIRCUIT TO LIGHTS IN NURSE AREA.
SEE DETAILS AI431.
03 SEE SHEET GC001 FOR WORK SCOPE
RELATED TO ALTERNATE DEDUCT 1.
Scale: 1/8" = 1'-0"
FIFTH FLOOR LIGHTING PLAN ALTERNATE DEDUCT 1 0 4 8 16
NORTH
TRUE
M
M M
M
M
M M M
M
M
M
M
M
M
M
M M
M
M
M
M
M
E E E E E
EE
E
EE
E
E
E
E E
E E E
E
E
E E E
E
EE
EE
E
E
E
E
E
E
E
E
E
M
E
PATIENT RM
B5008
CARE STATION
B5009
PATIENT RM
B5010
PATIENT RM
B5011
PATIENT RM, BARIATRIC
B5012
LOCKER
B5014
PATIENT RM
B5016
SOILED UTILITY
B5018
STAFF LOUNGE
B5015
CLEAN SUPPLY
B5019
ALCOVE
B5020
PATIENT RM
B5021
PATIENT RM
B5022
PATIENT RM
B5024
PATIENT RM
B5025
PASSAGE
B5041
NOUR
B5026
MEDS
B5027
BATH
B5007A
CORRIDOR
B5040
BATH
B5008A
BATH
B5010A
BATH
B5011A
BATH
B5016A
BATH
B5024A
BATH
B5025A
BATH
B5021A
BATH
B5022A
STAIR
B5050
STAFF TLT
B5014A PATIENT RM, ISOLATION
B5028
BATH
B5028A
ANTE
B5028B
PATIENT RM, ISOLATION
B5029
BATH
B5029A
ANTE
B5029B
PATIENT RM, BARIATRIC
B5007
CARE STATION
B5005
EQUIP
B5004
BATH
B5012A
CARE STATION
B5023
NURSE MGR OFFICE
B5030
EQUIP
B5017
TEAM WORK ROOM
B5031
ELEC
B5017A
OIT
B5003A
5B-TU-35B-TU-4
5B-TU-5
5B-TU-65B-TU-75B-TU-8
5B-TU-10 5B-TU-11 5B-TU-12
5B-TU-13
5B-TU-14
5B-TU-16
5B-TU-17
5B-TU-9
5B-TU-18
5B-TU-19 5B-TU-20
5B-TU-15
5B-TU-21 5B-TU-22
5B-TU-23
5B-TU-24
L L
M M
N N
P P
Q Q
R R
R.1 R.1
5.1
5.1
8 9
14 15
SS
TT
5B-CU-1
5B-EF-X
5B-SS-1
0203 0302 02
5B-TU-EF-1
'LF'-41
'E5CD'-1
'LF'-41 'LF'-41 'LF'-41
'E5CD'-3
'LF'-40
'LF'-40
'LF'-40
'LF'-40
'LF'-42 'LF'-42
'LF'-42
'LF'-42
'E5CD'-4
'E5CD'-2
'E5CE'-13,15,17
'E5CD'-8,10
01'E5CD'-5
(ELS-5C)
(L-F)
(E5CD)
(E5CE)
(EX)
R R
R.1 R.1
5.1
5.1
8 9
SS
TT
JJ
E
M
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:2
P
M
EM101
FIFTH FLOOR MECHANICAL POWER
PLAN
11 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: 1/8" = 1'-0"
FIFTH FLOOR MECHANICAL POWER PLAN
01 POWER CONNECTION FOR MED GAS ALARM
SYSTEM. COORDINATE WITH PLUMBING AND
COR.
02 EQUIPMENT CONNECTION FOR PATIENT BED
LIFT. PROVIDE MOTOR RATED SWITCH.
COORDINATE PLACEMENT WITH COR AND
DEVICE MANUFACTURER.
03 EQUIPMENT CONNECTION FOR BARIATRIC
PATIENT BED LIFT. PROVIDE MOTOR RATED
SWITCH. COORDINATE PLACEMENT WITH COR
AND DEVICE MANUFACTURER.
04 MECHANICAL EQUIPMENT LOCATED AT
LOWER ROOF LEVEL. COORDINATE WITH
MECHANICAL TRADES.
05 PROVIDE 3/4"C FOR CONNECTION OF 5B-CU-1
TO 5B-SS-1. CONTROL/POWER CABLING BY
OTHERS.
06 REFERENCE MECHANICAL CONDUCTOR
SCHEDULE E-602.
08 SEE SHEET GC101 FOR WORK SCOPE
RELATED TO ALTERNATE 3.
A. SEE -E401 FOR ELECTRICAL ROOM AND
CLOSET ENLARGEMENTS.
B. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12
AWG EG IN 3/4" CONDUIT UNLESS NOTED
OTHERWISE:
20-AMP CIRCUITS LESS THAN 150'
SHALL BE MINIMUM 2-12 AWG, 1-12 AWG
EG IN 3/4" C.
20-AMP CIRCUITS 150'-250' SHALL BE
MINIMUM 2-10AWG, 1-10 AWG EG IN
3/4" C.
20-AMP CIRCUITS GREATER THAN 250'
SHALL BE MINIMUM 2-8 AWG, 1-8 AWG
EG IN 3/4" C.
C. COORDINATE LOCATION AND ELECTRICAL
REQUIREMENTS OF MECHANICAL AND
PLUMBING EQUIPMENT WITH MECHANICAL AND
PLUMBING CONTRACTORS.
D. COORDINATE EQUIPMENT WITH
ARCHITECTURAL EQUIPMENT PLANS AND
SCHEDULES.
E. ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/ TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
F. ALL EQUIPMENT CONNECTIONS SHALL HAVE
THEIR SOURCE PANEL AN CIRCUIT NUMBER
INDICATED ON LOCAL MOTOR RATED SWITCH
OR DISCONNECT.
Scale: 1/8" = 1'-0"
FIFTH FLOOR MECHANICAL POWER PLAN ALTERNATE
DEDUCT 1
0 4 8 16
NORTH
TRUE
0 4 8 16
NORTH
TRUE
TO PNL 'LF'
(B5017A
3/4" C
TO PNL 'E5CD'
(B5017A)
E5CD-4
J J
J
AC
GFI
AC
GFI
U
SB
USB
U
SB AC 72
J J
J
AC
GFI
AC
GFI
USB
U
SB
U
SB AC
AC
GFI
AC
GFI
USB
J J
J
U
SB AC
AC
GFI
AC
GFI
AC
GFI
AC
GFI
DEDDEDDED
AC
DED
AC
GFI
DED
AC J
J J
AC
GFI
AC
GFI
USB
U
SB
U
SB AC
PATIENT RM, BARIATRIC
B5012
BATH
B5012A
M
N
P
2 3 4
08PATIENT RM
B5008
BATH
B5008A
M
N
P
10 11
PATIENT RM
B5010
BATH
B5010A
M
N
P
5 5.1 6 7
NOUR
B5026
MEDS
B5027
Q
R
8 9 10
'LF'-26
'E5CE'-12
'LF'-22
'LF'-24
'LF'-29
'LF'-38
'E5CE'-14
'E5CE'-16
B1-PNL-ELS5C
B1-PNL-E5CD
B1-PNL-E5CE
B1-PNL-LF
Q
'LF'-1
OIT
B5003A
PNL-E5CT
M
N
P
'E5CT'-1
'E5CT'-3,5
'E5CT'- 2,4
BIO
B5003
'E5CT'-6,8
PATIENT RM, ISOLATION
B5028
BATH
B5028A
ANTE
B5028B
Q
R
R.1
10 11
05 06
(E5CE-2)
# SHEET KEY NOTES:
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:5
P
M
E-401
ENLARGED ELECTRICAL PLANS
12 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale: 1/4" = 1'-0"
PATIENT ROOM B5012
Scale: 1/4" = 1'-0"
PATIENT ROOM B5008
Scale: 1/4" = 1'-0"
PATIENT ROOM B5010
Scale: 1/4" = 1'-0"
MEDS B5027 & NOUR B5026 0 2 4 8
NORTH
TRUE
0 2 4 8
NORTH
TRUE
0 2 4 8
NORTH
TRUE
0 2 4 8
NORTH
TRUE
0 2 4 8
NORTH
TRUE
Scale: 1/4" = 1'-0"
ELECTRICAL B5017A
Scale: 1/4" = 1'-0"
OIT B5003A 0 2 4 8
NORTH
TRUE
0 2 4 8
NORTH
TRUE
A. ALL CONDUCTORS SHALL BE 2-12 AWG, 1-12
AWG EG IN 3/4" CONDUIT UNLESS NOTED
OTHERWISE:
20-AMP CIRCUITS LESS THAN 150'
SHALL BE MINIMUM 2-12 AWG, 1-12 AWG
EG IN 3/4" C.
20-AMP CIRCUITS 150'-250' SHALL BE
MINIMUM 2-10AWG, 1-10 AWG EG IN
3/4" C.
20-AMP CIRCUITS GREATER THAN 250'
SHALL BE MINIMUM 2-8 AWG, 1-8 AWG
EG IN 3/4" C.
B. COORDINATE LOCATION AND ELECTRICAL
REQUIREMENTS OF MECHANICAL AND
PLUMBING EQUIPMENT WITH MECHANICAL AND
PLUMBING CONTRACTORS.
C. COORDINATE EQUIPMENT WITH
ARCHITECTURAL EQUIPMENT PLANS AND
SCHEDULES.
D. ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/ TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT.
E. ALL RECEPTACLES SHALL HAVE THEIR
SOURCE PANEL AND CIRCUIT NUMBER
INDICATED ON THEIR FACEPLATE.
01 TYP FOR BARIATRIC PATIENT ROOMS B5007
AND B5012.
02 TYP FOR ISOLATION PATIENT ROOMS B5028
AND B5029.
03 TYP FOR STANDARD PATIENT ROOMS.
04 FEED PANEL 'E5CT' FROM PANEL
'E5CE'-19,21,23. REFERENCE SINGLE LINE
SHEET E-601. LOCATE TVSS ADJACENT TO
PANEL.
05 RECEPTACLE WITH USB CHARGING PORT.
COMBINATION DEVICE WITH
TAMPER-RESISTANT OUTLET (5-15R) WITH
TYPE A AND TYPE C USB CHARGERS.
LEVITON T5632-HGW OR EQUAL.
06 SEE RESPECTIVE FLOOR PLAN. NORMAL
POWER GENERAL SERVICES CIRCUIT GS-1.
07 SEE RESPECTIVE FLOOR PLAN. NORMAL
POWER GENERAL SERVICES CIRCUIT GS-2.
08 SEE RESPECTIVE FLOOR PLAN. ESSENTIAL
POWER (CRITICAL EQUIPMENT) CIRCUIT EC.
09 3-10 AWG, 1-10 AWG N, 1-10 AWG EGC
IN 3/4" C.
10 30A 208V 1 PHASE RECEPTACLE.
COORDINATE TYPE WITH OWNER
EQUIPMENT.
11 STACKED CONTROL CABINETS FOR
PACS/NURSE CALL. COORDINATE LOCATION
IN FIELD.
12 AT PATIENT HEADWALL SYSTEM (SEE AI431)
AND SPECIFICATIONS. CIRCUIT
DESIGNATIONS E1, E3 ARE CONNECTED TO
(GS-2) SEE NOTE 7. CIRCUIT DESIGNATIONS
E2, E4 ARE CONNECTED TO (EC) SEE NOTE 8.
13 RELOCATED PANEL 'LF'. PROVIDE NEW
SURFACE MOUNTED TUB FOR PANEL
INTERIOR.
14 20A 208V 1 PHASE RECEPTACLE.
COORDINATE WITH USP PROVIDED AT BIO
MED RACK. SEE SHEET TK503.
010303
02 12
121212
Scale: 1/4" = 1'-0"
PATIENT ROOM B5028
CEILING
MAIN BEAM RECESSED CAN
LUMINAIRE
CEILING BEAM
GYPSUM BOARD (TYP)
LUMINAIRE
BAR HANGERSRECESSED CAN
LUMINAIRE
CEILING
CROSS BEAM
WIRE TIE OR SCREW
BAR HANGER TO
CROSS BEAM TYP.
CEILING HANGER
WIRE, TYP.
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING HARDWARE.
FIXTURE WHIP FROM
JUNCTION BOX (6' LONG MAX)
LUMINAIRE SUSPENSION
WIRE
CEILING HANGER
WIRE, TYP.
WIRE TIE OR
SCREW BAR
HANGER TO
ARCHITECTURAL
CEILING GRID TYP.
ARCHITECTURAL
CEILING GRID RECESSED CAN
LUMINAIRE
RECESSED CAN
LUMINAIRE
ARCHITECTURAL CEILING GRID
ACOUSTICAL
CEILING TILE
(TYP)
LUMINAIRE
BAR HANGERS
LUMINAIRE SUSPENSION
WIRE
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING HARDWARE.
FIXTURE WHIP FROM
JUNCTION BOX (6' LONG MAX)
CEILING HANGER WIRE
DRYWALL
CEILING CROSS
TEE, TYP.
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO
STRUCTURE
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
CEILING MAIN
BEAM
GYPSUM
BOARD
DRYWALL
CEILING CROSS
TEE, TYP. 1/4" SCREW
JUNCTION BOX
LOCKING
SQUARE
WASHER & NUT
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
FIXTURE WHIP FROM JUNCTION
BOX (6' LONG MAX.)
CEILING HANGER WIRE
ARCHITECTURAL
CEILING GRID
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO
STRUCTURE.
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
ARCHITECTURAL
CEILING GRID
ACOUSTICAL CEILING
TILE, TYP.
ARCHITECTURAL
CEILING GRID
1/4" SCREW
JUNCTION BOX
LOCKING SQUARE
WASHER & NUT
FIXTURE WHIP FROM JUNCTION
BOX (6' LONG MAX)
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING HARDWARE.
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERS. ATTACH
WITH SHEET METAL SCREW
FIXTURE WHIP
FROM JUNCTION
BOX
(6FT. LONG MAX.)
LUMINAIR. REFER TO
SCHEDULE
LUMINAIRE. REFER TO
SCHEDULE
DRYWALL BORDER
CEILING CROSS
BEAM
GYPSUM BOARD
CEILING MAIN BEAM
CEILING CROSS BEAM
GYPSUM BOARD
(TYP)
3 TWIST
MINIMUM (TYP)
LUMINAIRE
SUSPENSION WIRES
(#10 MIN)
ATTACHED TO
STRUCTURE
(TYP EA. CORNER)
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERS. ATTACH
WITH SHEET METAL SCREW
FIXTURE WHIP
FROM JUNCTION
BOX
(6FT. LONG MAX.)
LUMINAIRE. REFER TO
SCHEDULE
ARCHITECTURAL
CEILING GRID
LUMINAIRE. REFER
TO SCHEDULE
ACOUSTICAL CEILING
TILE (TYP)
3 TWIST
MINIMUM (TYP)
LUMINAIRE
SUSPENSION WIRES
(#10 MIN)
ATTACHED TO
STRUCTURE
(TYP EA. CORNER)
Revisions: Date
Drawing Title
Approved ANDREKA WATLINGTON
PROJECT ENGINEER
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/2
/2
:0
:5
P
M
E-501
ELECTRICAL DETAILS
13 16MAH JDM
IMPROVE INPATIENT
PRIVACY (RENOVATE 5B)
DURHAM VA MEDICAL CENTER
508 FULTON STREET
DURHAM, NC 27705 06/28/2019
BID DOCUMENTS
558-18-15018-048
Scale: N.T.S.
DOWNLIGHT MOUNTING - GYPBOARD CEILING
Scale: N.T.S.
DOWNLIGHT MOUNTING - LAY-IN CEILING
Scale: N.T.S.
EXIT SIGN MOUNTING - GYPBOARD CEILING
Scale: N.T.S.
EXIT SIGN MOUNTING - LAY-IN CEILING
Scale: N.T.S.
LUMINAIRE MOUNTING - GYPBOARD CEILING
Scale: N.T.S.
LUMINAIRE MOUNTING - LAY-IN CEILING
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE
CONSTRUCTED
OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION
DESIGNS
IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC
WITH
NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)
WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES.
THE
GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE
AS
SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .