1ST FLOOR
0"
2ND FLOOR
12'-0"
ROOF BEARING
24'-0"
A B C D E F G H I J K
TOP OF ROOF
40'-0"
LIGHT GAUGE
METAL TRUSSES
AE322
Sim
AE322
Sim
AE113
1ST FLOOR
0"
2ND FLOOR
12'-0"
ROOF BEARING
24'-0"
A B C D E F G H I J K
WORKSTATIONS
WORKSTATIONS
BREAK
ROOM
BREAK
ROOM
LOBBY/ATRIUM
WORKSTATIONS
WORKSTATIONS
TOP OF ROOF
40'-0"
LIGHT GAUGE
METAL TRUSSES
MODIFY TRUSSES
TO ACCOMODATE
ELEVATOR SHAFT,
TYP.
AE621
GENERAL NOTES
1. STRUCTURAL ITEMS ARE IDENTIFIED
FOR GRAPHICAL PURPOSES ONLY.
REFER TO STRUCTURAL DRAWINGS
FOR INFORMATION AND COORDINATION.
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE313
ARCHITECTURAL
BUILDING SECTION
REPLACE BUILDING 71
03.28.2018 AR RR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1/8" = 1'-0"1 BUILDING SECTION THROUGH HALL
1/8" = 1'-0"2
BUILDING SECTION THROUGH
ELEVATOR SHAFT
No. DESCRIPTION DATE
2ND FLOOR
12'-0"
ROOF BEARING
24'-0"
TYPICAL BRICK FACED WALL ASSEMBLY: W1
• 3 5/8" x 2 1/4" x 7 5/8" BRICK MASONRY
• AIRSPACE
• 1" CAVITY MORTAR NET
• 2.5" CONTINUOUS MINERAL WOOL INSULATION BOARD
MECHANICALLY FASTENED
• SELF ADHERED VAPOR PERMEABLE AIR/WATER BARRIER
• 5/8" EXT. GYPSUM BOARD
• 6" NOMINAL STEEL STUDS @ 16" O.C.
W/ HORIZONTAL BLOCKING AT MID-HEIGHT
• MINERAL WOOL INSULATION (FULL CAVITY)
• 5/8" TYPE X GYPSUM WALL BOARD, PAINTED
CAST IN PLACE CONCRETE
FOUNDATION
(REFER TO STRUCTURAL)
FULL SPANNING PRECAST
CONCRETE HEADER
PRECAST CONCRETE SILL
W/ DRIP (TYP.)
ALUMINUM STOREFRONT WITH SHADES.
REFER TO SCHEDULES FOR SIZES
GALVANIZED LOOSE LINTEL
(REFER TO STRUCTURAL
FOR SIZES)
TRANSITION MEMBRANE
FLASHING INCL TERM BAR
(TYP.)
PRECAST CONCRETE SILL
SLOPED AWAY FROM
BUILDING (TYP.)
SOLID SURF. INTERIOR
WINDOW STOOL AND
APRON (TYP.)
BRICK RETURNS AT JAMB
BACKER ROD AND SEALANT PROVIDE BREAK FORM SUB SILL PAN
FLASHING TO MATCH STOREFRONT ON
CONTINUOUS BEAD OF SEALANT WITH
CONTINUOUS SEALANT BETWEEN SILL
AND PRECAST (TYP.)
WRAP TRANSITION MEMBRANE INTO
OPENING FULL DEPTH OF WALL FRAMING
AT HEAD, SILL, AND JAMB (TYP.)
THROUGH WALL FLASHING
WITH WEEPS IN MASONRY
ABOVE. COMPLETE WITH
TRANSITION MEMBRANE
AND TERM BAR.
PROVIDE HEAD FLASHING
TIED INTO WRB
PROVIDE MASONRY TIES AT 16"
O.C. HORIZONTAL AND VERTICAL
UNLESS OTHERWISE NOTED. SEE
STRUCTURAL (TYP.)
REFER TO STRUCTRUAL
DRAWINGS FOR
STRUCTURAL STEEL SIZES,
LOCATIONS AND BRACING
THROUGH WALL FLASHING
WITH WEEPS
TYPICAL ROOFING ASSEMBLY: RF:1
• 25 YEAR ARCHITECTURAL ASPHALT SHINGLE
• ROOFING UNDERLAYMENT W/ ICE AND WATER MEMBRANE
FOR FIRST 2' UP EAVES AND VALLEYS (TYP.)
• VENTED NAILBOARD
• 2 LAYERS OF 2.5" POLY ISO INSULATION (STAGGERED)
• 5/8" EXTERIOR GYPSUM BOARD
• METAL DECK
• PREFABRICATED LIGHT GAUGE TRUSSES
• 7/8" FURRING HAT CHANNELS
• 2 LAYERS OF 5/8" TYPE X GWB (WHERE INDICATED)
• SUSPENDED CEILING SUPPORTS AS REQ'D
• SOFFIT AND RIDGE VENTS
TRANSITION MEMBRANE
FLASHING
PROVIDE STRUCTURAL LINTEL AND
REINFORCING AT OPENING. REFER
TO STRUCTURAL AND SHEETS AE721,
AE722 .
THROUGH WALL FLASHING
WITH WEEPS IN MASONRY
GWB
TYPICAL SECOND FLOOR ASSEMBLY: FL-
• FINISH FLOORING. SEE FINISH SCHEDULE
• CONCRETE SLAB (SEE STRUCTURAL)
PROVIDE SLIP CHANNELS
DESIGNED BY COLD FORM
FRAMING MANUFACTURER
(TYP.)
THROUGH WALL FLASHING
WITH WEEPS IN MASONRY
BACKER ROD
AND SEALANT
FULLY GROUT BELOW SLAB W/
2.5" EPS INSULATION BACKUP
1' -0
6"
POLYASH FASCIA
BRICK SOLDIER COURSE
EDGE OF SLAB
11 1/2"
INSIDE FACE OF FRAMING
1'-2" FACE OF BRICK TO
SLOP
PREFABRICATED MTL
TRUSSES (TYP.)
SUSPENDED
CEILING
SUPPORTS
SLOP
SOLID SURF. INTERIOR
WINDOW STOOL AND
APRON (TYP.)
BEADED MTL SOFFIT W/ J-
HALF ROUND EAVESTROUGH COMPLETE
WITH DOWNSPOUTS HANGERS AND
SUPPORT (TYP.)
PREFINISHED MTL DRIP EDGE
SOFFIT VENT (TYP.)
PRESSURE TREATED FASCIA WRAPPED IN ROOF
MEMBRANE
WRAPPED IN PREFINISHED METAL (TYP.)
5/8" TYPE X GWB WRAPPED W/ SELF
ADHERING MEMBRANE AND COVERED
WITH PREFINISHED MTL (TYP.)
INSULATED SOFFIT
ASPHALT SHINGLE STARTER COURSE
DRIP EDGE AND SOFFIT
CONTINUOUS BEAD OF SEALANT BETWEEN
FOOTING AND CONCRETE WALL
4"
4" DOUBLE LAYER OF WATERPROOFING
MEMBRANE AT INSIDE CORNER
(TYP.)
WRAP FOOTING, FOUNDATION AND
SLAB EDGE IN WATERPROOFING
MEMBRANE AND TIE INTO SUB-
SLAB POLY BARRIER (TYP.)
TRANSITION MEMBRANE W/ TERM BAR LAPPED
OVER THROUGH WALL FLASHING WITH WEEPS
IN MASONRY. RUN WATERPROOFING
MEMBRANE UP WALL SHEATHING BEHIND
THROUGH WALL FLASHING. TRANSITION TO AIR
BARRIER MEMBRANE ABOVE THROUGH WALL
FLASHING. (TYP.)
DESIGN OF COLD
FORM STUDS BY
OTHERS. SHOWN
FOR GRAPHIC
PURPOSES ONLY
PROVIDE METAL FRAMING
INCLUDING ALL KICKERS,
LINTELS, AND ACCESSORIES
TO SUPPORT EXTERIOR
MASONRY ELEMENTS.
REFER TO STRUCTURAL
(ITEMS INDICATED FOR
GRAPHIC PURPOSES ONLY)
1'-8"
1'-0" MIN
2 LAYERS OF 5/8" TYPE X
GWB AT UNDERSIDE OF
TRUSSES
/6 AE321
/6 AE321
/7 AE321
TYPICAL SLAB ON GRADE FLOOR ASSEMBLY: FL-
2 LAYERS THERMALLY INSULATIVE TAPE
BETWEEN STEEL ANGLES AND WRAPPED
INTO OPENING FULL DEPTH OF ANGLE.
3"
3' MINIMUM BETWEEN GRADE
AND BOTTOM OF FOOTING
P.T. FRTW
NAILER
AROUND
STOREFRONT
OPENINGS ALL
SIDES (TYP.)
EDGE OF SLAB
1'-0"
P.T. FRTW TO
UNDERSIDE OF DECK
M
IN6"
C
O U
R
SE
S
/2
THROUGH WALL FLASHING
MEMBRANE
DRAINAGE TILE
DRAINAGE MAT
1.5" EPS INSULATION
AND DRAINAGE MAT
APPLIED
FILTER FABRIC
FREE DRAINING
FILL
1ST FLOOR
0"
2ND FLOOR
12'-0"
ROOF BEARING
24'-0"
DOOR THRESHOLD INSTALLED ON
CONTINUOUS BEAD OF SEALANT.
PROVIDE SELF ADHERED WATERPROOFING
/SILL FLASHING CONTINUOUS WITH FOOTING.
CAST IN PLACE
CONCRETE FOUNDATION
(REFER TO STRUCTURAL)
TYPICAL SLAB ON GRADE FLOOR ASSEMBLY: FL-1
• FINISH FLOORING. SEE FINISH SCHEDULE
• CONCRETE SLAB ON GRADE (SEE STRUCTURAL)
• POLYETHYLENE SHEET VAPOR BARRIER
• 2 1/2" R10 CONTINUOUS EPS INSULATION (24" MIN TO THE INTERIOR)
• COMPACTED GRANULAR AS PER STRUCTURAL
TYPICAL EXTERIOR PAVING SLAB ASSEMBLY: FL-
• CONCRETE SLAB ON GRADE (SEE STRUCTURAL)
TYPICAL ROOFING ASSEMBLY: RF-1
TRANSITION MEMBRANE W/ TERM BAR LAPPED
OVER THROUGH WALL FLASHING
THROUGH WALL FLASHING
POLYURETHANE SIMULATED
WOOD TRIM
EXTRUDED ALUMINUM SILL BY BY
STOREFRONT MANUFACTURER
WEEPS IN
PROVIDE METAL FRAMING
INCLUDING ALL KICKERS,
LINTELS, AND ACCESSORIES
TO SUPPORT EXTERIOR
MASONRY ELEMENTS.
REFER TO STRUCTURAL
(ITEMS INDICATED FOR
GRAPHIC PURPOSES ONLY)
PRE-ENGINEERED
ALUMINUM
POLYURETHANE SIMULATED
WOOD TRIM (TYP.)
/5 AE212
/4 AE212
REFER TO
STRUCTURAL
TYPICAL WALL ASSEMBLY: W-4
• 3 5/8" GLAZED BRICK
• AIRSPACE
• 1" CAVITY MORTAR NET
• 2.5" CONTINUOUS MINERAL WOOL
INSULATION BOARD
MECHANICALLY FASTENED
• SELF ADHERED VAPOR PERMEABLE
AIR/WATER BARRIER
• 5/8" EXT. GYPSUM BOARD
• 6" NOMINAL STEEL STUDS @ 16" O.C.
W/ HORIZONTAL BLOCKING AT MID-HEIGHT
• MINERAL WOOL INSULATION (FULL CAVITY)
• 5/8" TYPE X GYPSUM WALL BOARD, PAINTED
ALIGN BULKHEAD
WITH TOP OF
WINDOW AND
COLUMN BEYOND
PROVIDE REGLET EMBEDDED IN
CONTINUOUS BEAD OF SEALANT.
BREAK FORMED FLASHING WITH SLIP
JOINT BETWEEN WALL AND CANOPY
COMPLETE WITH CLIPS AND FASTENERS
2 LAYERS OF 5/8" TYPE
X GWB AT UNDERSIDE
OF TRUSSES
PREFABRICATED
LIGHT GAUGE
TRUSSES (TYP.)
REFER TO STRUCTRUAL
DRAWINGS FOR
STRUCTURAL STEEL SIZES
AND BRACING
SLOPE
2 LAYERS THERMALLY INSULATIVE TAPE
AROUND STEEL ANGLE AND FULL DEPTH
OF OPENING.
WRAP WRB OVER MEMBRANE COVERED
ANGLE AND PROVIDE HEAD FLASHING TO
WRAP INTO OPENING. FINISH TO MATCH
STORE FRONT.
PROVIDE TRANSITION MEMBRANE W/
TERM BAR FLASHING OVER THROUGH
WALL FLASHING WITH WEEPS IN
MASONRY.
PROVIDE P.T. FRTW NAILER
AT PERIMETER OF OPENINGS
(TYP.)
ALIGN BLKHD W/
OPENING
2 LAYERS THERMALLY INSULATIVE TAPE
BETWEEN STEEL ANGLES AND WRAPPED
INTO OPENING FULL DEPTH OF ANGLE.
PROVIDE HEAD FLASHING TIED INTO WRB
SLOPE
PROVIDE REGLET AND PREFINISHED
METAL FLASHING OVER SIMULATED
TRIM. FINISH TO MATCH TRIM
CONTINUOUS P.T. BLOCKING BENEATH
METAL SILL WRAPPED IN SELF ADHERED
MEMBRANE.
BULKHEAD: 5/8" TYPE X GWB
ON MTL STUDS. 2-1/2" MTL
STUDS AT UNDERSIDE OF
BEAM
1" OFFSET 10" +/-
OVERHANG
1'-4" +/-
EDGE OF SLAB
1'-0"
PROVIDE BOND BREAK BETWEEN
CONCRETE SLABS AND APPLY
THERMALLY
INSULATIVE TAPE BETWEEN EXTERIOR
SLAB AND INTERIOR SLAB/FOUNDATION
BACKER ROD AND SEALANT
GWB RETURN AT BASE
OF
WRAP FOOTING IN
WATERPROOFING MEMBRANE
AND TIE INTO BELOW SLAB
POLY BARRIER (TYP.)
AE321
Sim
1'-8"
MATCH COLUMN ENCLOSURE WIDTH
1" 1/
2"
PAINT REVEAL BLACK
1/2" 1/2"
6"
TOP OF CUBICLE
ONE SIDE GYP.
BD. ON STUD
FRAMING
NOTE:
HEIGHT TO BE
DETERMINED PL-1
P-3
2ND FLOOR
12'-0"
CL
CENTER LINE OF
STEEL
AND FACE OF
FRAMING ABOVE
3 5/8"
ALIGN F.F. OF
GWB.
3" EDGE OF SLAB
9'-4"
ATRIUM
HEA
SILL
VIF
FACE OF
SHEATHING
FACE OF
BRICK
5/
8"
5/ 8"
1" OVERHANG
FACE OF
SHEATHING
FACE OF
BRICK
OVERHANG
2"
1" OVERHANG
8" 8"7"
VIF
SILL
E
5/8" GYP. BD.
1.5" MTL
STEEL BEAM. SEE
STRUCT. DWGS.
ALIGN WITH BLKHD
OVER STOREFRONT
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE321
ARCHITECTURAL
TYPICAL WALL SECTIONS
REPLACE BUILDING 71
03.28.2018 AR RR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1 1/2" = 1'-0"1 TYPICAL BRICK FACED WALL
1 1/2" = 1'-0"2 TYPICAL GABLE END DETAIL.
1 1/2" = 1'-0"4 SECTION DETAIL - LOW WALL
1 1/2" = 1'-0"5 BEAM DETAIL AT STAIR IN ATRIUM
1 1/2" = 1'-0"6 SECTION AT PRECAST FIRST FLOOR
1 1/2" = 1'-0"7 SECTION AT PRECAST SECOND FLOOR
1 1/2" = 1'-0"3 BEAM DETAIL AT ATRIUM
2ND FLOOR
12'-0"
ROOF BEARING
24'-0"
BACKER ROD AND SEALANT (VENTED TO
EXTERIOR) TRANSITION MEMBRANE
WRAPPED INTO ROUGH
OPENING AT HEAD, SILL,
AND JAMB (TYP.)
SILL FLASHING SLOPED TO EXTERIOR
SEALANT UNDER FLASHING
WRAP INSULATION EDGE WITH MESH-
REINFORCED BASE COAT (TYP.)
EIFS INSULATION COMPONENT
SLOPE GRADE
AWAY
DRAINAGE TRACK AND FLASHING
WRAP INSULATION EDGE WITH
REINFORCING MESH, TERMINATE BASE
COAT AT DRAINAGE TRACK
BACKER ROD AND SEALANT (VENTED TO
EXTERIOR)
HEAD FLASHING TO MATCH STOREFRONT
WINDOW
WRAP INSULATION EDGE WITH
REINFORCING MESH (TYP.)
SELF-FLASHING VENTING AND DRAINAGE
TRACK
PROVIDE EXPANSION JOINT AT FLOOR
LEVEL TRANSITION AND AS FURTHER
REQUIRED BY MANUFACTURER OF EIFS
SYSTEM
CAST IN PLACE
CONCRETE FOUNDATION
(REFER TO STRUCTURAL)
OUTLINE OF COLUMN
FOOTING BEYOND
(REFER TO STRUCTURAL)
TYPICAL EIFS FACED WALL ASSEMBLY: W3
• 2 1/2" VENTED AND FREE DRAINING EIFS SYSTEM
COMPLETE WITH TRANSITIONS, WEEPS, FLASHINGS,
VAPOR PERMEABLE AIR BARRIERS AND ADHESIVE
SYSTEM BY SELECTED MANUFACTURER
• 5/8" EXTERIOR GYPSUM BOARD
• 6" NOMINAL COLD FORM STEEL STUDS @ 16" O.C.
W/ HORIZONTAL BLOCKING AT MID-HEIGHT
• MINERAL WOOL INSULATION (FULL CAVITY)
• 5/8" GYPSUM WALBOARD, PAINTED
TYPICAL ROOFING ASSEMBLY: RF-1
1'-0"
ALIGN FACE OF
SHEATING WITH SLAB
EDGEREINF. PARGING OVER 1.5" EPS INSULATION
RATED FOR GROUND CONTACT.
WRAP FOOTING AND
FOUNDATION WALL WITH
WATERPROOFING MEMBRANE.
TIE INTO SUB-SLAB VAPOR
BARRIER
11" EDGE OF SLAB
TYPICAL SLAB ON GRADE
FLOOR ASSEMBLY: FL-1
SEALANT UNDER FLASHING
STOREFRONT. REFER TO SCHEDULES FOR
SIZES (TYP.)
AE321
Sim
FACE OF BRICK BEYOND
PROVIDE P.T. FRTW WOOD NAILER AROUND
EXTERIOR OPENINGS (TYP.)
WATERPROOFING MEMBRANE
8"
FREE DRAINING FILL
AROUND PERIMETER OF
FOUNDATION (TYP.)
DRAINAGE TILE (TYP.)
FILTER FABRIC (TYP.)
1ST FLOOR
0"
ROOF BEARING
24'-0"
TYPICAL ROOFING ASSEMBLY: RF-1
TYPICAL SLAB ON GRADE FLOOR ASSEMBLY: FL-1
• FINISH FLOORING. SEE FINISH SCHEDULE
• CONCRETE SLAB ON GRADE (SEE STRUCTURAL)
• POLYETHYLENE SHEET VAPOR BARRIER
• 2 1/2" R10 CONTINUOUS EPS INSULATION
(24" MIN TO THE INTERIOR)
• COMPACTED GRANULAR AS PER STRUCTURAL
1'-8"
CAST IN PLACE
CONCRETE FOUNDATION
(REFER TO STRUCTURAL)
TYPICAL BRICK FACED CMU WALL ASSEMBLY: W2
• 3 5/8" x 2 1/4" x 7 5/8" BRICK MASONRY WITH RACKING COURSES AS INDICATED
• AIRSPACE
• 1" CAVITY MORTAR NET
• 2.5" CONTINUOUS CAVITY ROCK INSULATION
MECHANICALLY FASTENED
• SELF ADHERED VAPOR PERMEABLE AIR/WATER BARRIER
• 7 5/8" X 7 5/8" X 15 5/8" CMU
TRANSITION MEMBRANE
W/ TERM BAR LAPPED
OVER THROUGH WALL
FLASHING (TYP.)
FULLY GROUT BELOW
SLAB W/ 2.5" EPS
INSULATION BACKUP
4"
EDGE OF SLAB
11 1/2"
2 LAYERS 5/8"
TYPE X GWB OVER
7/8" HAT
CHANNELS
1'-4" MIN.
DRAINAGE MAT
1.5" EPS INSULATION
WATERPROOFING MEMBRANE.
OVER FOUNDATION WALL
AE321
Sim
WEEPS IN
MASONRY (TYP.)
MASONRY TIES @
16" O.C. BOTH
VERTICALLY AND
HORIZONTALLY
UNLESS
OTHERWISE
NOTED. REFER
ALSO TO
STRUCTURAL.
1" X 10" POLYASH
FASICA BOARD
PROVIDE CONTINUOUS P.T. FRTW
BLOCKING AT PERIMETER WALLS
TO UNDERSIDE OF DECK.
WRAP FOOTING AND
FOUNDATION WALL WITH
WATERPROOFING MEMBRANE.
TIE INTO SUB-SLAB VAPOR
BARRIER
1'-4" MIN.
INSIDE FACE OF CMU
1'-4" FACE OF BRICK TO
CONTINUOUS BEAD OF SEALANT BETWEEN
FOOTING AND CONCRETE WALL (TYP.)
DOUBLE LAYER OF WATERPROOFING
MEMBRANE AT INSIDE CORNER
(TYP.)
WRAP SELF ADHERING MEMBRANE UP UNDERSIDE OF MTL
DECK AND SEAL ALL OPENINGS WITH FIRE RATED FOAM
TYPE SEALANT. (TYP.)
M
IN
6"
C
O U
R
SE
S
/2
FILTER FABRIC
FREE DRAINING FILL
DRAINAGE TILE (TYP.)
WRAP WATERPROOFING
MEMBRANE UP SLAB EDGE .
TRANSITION BETWEEN
WATERPROOFING AND AIR
BARRIER SYSTEM ABOVE
THROUGH WALL FLASHING
(TYP.)
THROUGH WALL
FLASHING
1ST FLOOR
0"
2ND FLOOR
12'-0"
ROOF BEARING
24'-0"
TYPICAL ROOFING ASSEMBLY : RF-
REFER TO STRUCTRUAL
DRAWINGS FOR STRUCTURAL
STEEL SIZES
TRANSITION MEMBRANE WRAPPED
OVER THROUGH WALL FLASHING
THROUGH WALL FLASHING WITH WEEPS
IN MASONRY
PROVIDE STRUCTURAL LINTEL AND REINFORCING AT
OPENING.
PROVIDE HEAD FLASHING TIED INTO WRB
BACKER ROD AND SEALANT
GWB RETURN AT
HEIGHT OF WINDOW
WRAP TRANSITION
MEMBRANE FULL DEPTH
OF OPENING AT HEAD,
JAMB, AND SILL (TYP)
TYPICAL SECOND FLOOR ASSEMBLY : FL-2
ALUMINUM CURTAIN WALL
COORDINATE SUPPORTS AND
REINFORCEMENT WITH
MANUFACTURER AND
STRUCTURAL
WRAP TRANSITION MEMBRANE
AND SILL FLASHING INTO
CURTAIN WALL ASSEMBLY AT
PRESSURE PLATE (TYP.)
TRANSITION MEMBRANE
LAPPED OVER THROUGH WALL
FLASHING WITH WEEPS IN
MASONRY
CAST IN PLACE
CONCRETE
FOUNDATION
(REFER TO
STRUCTURAL)
DOWNSPOUT TYP.
BRICK SOLDIER COURSE
SLAB
6" EDGE OF
1'-6"
OFFSET FROM SLAB
1" CURTAIN WALL
1'-0" MIN.
TYPICAL SLAB ON GRADE FLOOR ASSEMBLY: FL-1
AE321
Sim
LINE OF BRICK BEYOND
CURTAIN WALL
REFER TO SCHEDULES FOR
SIZES (TYP.)
1" x 10" POLY ASH FASCIA
ALIGN FACE OF
BULKHEAD WITH
COLUMN BEYOND
2 LAYERS OF 5/8" TYPE X GWB AT
UNDERSIDE OF TRUSSES (TYP.)
TYPICAL BRICK FACED WALL ASSEMBLY:
W1
SUSPENDED CEILING
SUPPORTS
P.T. FRTW NAILER AROUND
CURTAIN WALL ALL SIDES
(TYP.)
2 LAYERS THERMALLY INSULATIVE TAPE BETWEEN
STEEL ANGLES AND WRAPPED INTO OPENING FULL
DEPTH OF ANGLE
SOLID SURF. SILL AND
STOOL. (TYP.)
AE321
Sim
M U
LL
IO
N
A
LI
G N
W
THROUGH WALL FLASHING WITH WEEPS
IN MASONRY
TYPICAL BRICK FACED WALL ASSEMBLY:
W1
WRAP TRANSITION MEMBRANE
OVER THROUGH WALL
MEMBRANE
EDGE OF SLAB
10"
WRAP SELF ADHERING MEMBRANE UP
UNDERSIDE OF MTL DECK AND SEAL ALL
OPENINGS WITH FIRE RATED FOAM TYPE
SEALANT. (TYP.)
M
IN
6"
C
O U
R
SE
S
/2
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE322
ARCHITECTURAL
TYPICAL WALL SECTIONS
REPLACE BUILDING 71
03.28.2018 AR RR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1 1/2" = 1'-0"2 TYPICAL EIFS SECTION
1 1/2" = 1'-0"1
TYPICAL BRICK FACED WALL SECTION
WITH CMU BACKUP 1 1/2" = 1'-0"3 TYPICAL CURTAIN WALL SECTION
2ND FLOOR
12'-0"
PRECAST MASONRY CAP
ELEMENT W/ DRIP EDGE
TYPICAL MASONRY BASE AT CANOPY
• 3 5/8" x 2 1/4" x 7 5/8" BRICK MASONRY
CONCRETE PIER - REFER TO STRUCTURAL
FULLY GROUT BETWEEN PIER AND MASONRY
PRECAST BASE ELEMENT.
REFER ALSO TO
TYPICAL PREFAB ROOF ASSEMBLY: RF-2
PRE-ENGINEERED
ALUMINUM
PRE-ENGINEERED ALUMINUM
POST SUPPORTED CANOPY.
COORDINATE
ANCHORING REQUIREMENTS WITH
STRUCTURAL
/2 AE212.
REFER TO THE FOLLOWING
DRAWING FOR
/2 AE212
SLOPE SLOPE
CAST IN PLACE
CONCRETE FOUNDATION
(REFER TO STRUCTURAL)
OVERHANG (TYP.)
1 1/2"
1 1/2" OFFSET
1/ 2"
CHAMFER CORNER
PROVIDE BOND
BREAK
BETWEEN CONCRETE
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE323
ARCHITECTURAL
TYPICAL WALL SECTIONS
REPLACE BUILDING 71
03.28.2018 AR RR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1 1/2" = 1'-0"1
CANOPY CROSS SECTION AT
PERIMETER COLUMN
D
CONFERENCE
A/V 120A
CHAIR RAIL
30" AFF
AI211
1.11.1
1'-0" 1'-0"
1' -0
4'
-0 " 1'
-0
1' -0
WALL MOUNTED TV MONITOR, N.I.C.
PROVIDE FIRE TREATED 24X36, 3/4"
PLYWOOD MOUNTED BETWEEN STUDS
COORDINATE HEIGHT WITH
INSTALLATION OF MONITOR
EQ EQ
D
D
E
E
TELECOM
BREAK
ROOM
REF.
REF.
CHAIR RAIL
30" AFF, TYP
CHAIR RAIL
AI211
AE521
Sim
AE521
SIM
AF1113
E
E
F
F
G
G
AE411 7
DOOR OPERATOR BUTTON
CARD READER
F
F
MEN
WOMEN
AI21110
AI211 9
1.11.1
WATER
FOUNTAINS
TOILET
PARTITION 5'
-3
3' -0
3'
-0
" URINAL
SCREEN
6' -0
6' -0
3'
-1
3' -1
5'
-3
1' -6
5'-0" 5'-0"
1' -6
1'
-6
1' -6
1'
-6
1' -6
O.H.
FDFD
G
G
CONFERENCE
A/V 134A
CHAIR RAIL, TYP.
30" AFF
AI211
4 Sim
1.11.1
4' -0
1'
-0
1' -0
1'-0"
1' -0
1'-0"
WALL MOUNTED TV MONITOR, N.I.C.
PROVIDE FIRE TREATED 24X36, 3/4"
PLYWOOD MOUNTED BETWEEN STUDS
COORDINATE HEIGHT WITH
INSTALLATION OF MONITOR
EQ EQ
J
J
COPY
AREA
AE521
AE521
AI211
COPIER,
N.I.C.
WALL CABINET
BASE CABINET
RM 116 SIM. OPP HAND
1ST FLOOR
0"
2ND FLOOR
12'-0"
DOOR OPERATOR BUTTON
CARD READER
3' -0
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE411
ARCHITECTURAL
FIRST FLOOR 1/4" PLANS
REPLACE BUILDING 71
03.28.2018 AR RR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1/4" = 1'-0"1 CONFERENCE ROOM 120 FLOOR PLAN
1/4" = 1'-0"5 BREAK ROOM TYP.
1/4" = 1'-0"6 PUBLIC ENTRY FLOOR PLAN
1/4" = 1'-0"2 RESTROOMS TYP.
1/4" = 1'-0"3 CONFERENCE ROOM 134 FLOOR PLAN
1/4" = 1'-0"4 COPY AREA 139 FLOOR PLAN
REFER TO SHEET AG003 FOR ADA REQUIREMENTS
1/4" = 1'-0"7 PUBLIC ENTRY ELEVATION
GENERAL NOTES:
1. REFER TO DRAWINGS AE 112 AND AE 122 FOR PLAN
D
OFFICE
D E
TELECOM
BREAK
ROOM
AI211
CHAIR RAIL
CHAIR RAIL
REF.
REF.
Si m
7 Sim
4' -0
1' -0
1'-0"
D
CONFERENCE
A/V 215A
CHAIR RAIL
1.1
4' -0
1'
-0
1' -0
1'-0"1'-0"
1' -0
A
22 COPY
AREA
5'-2"
BASE CABINET
WALL CABINET
COPIER
N.I.C.
AI211
F
MEN
WOMEN
CORRIDOR
AI211 9
Si m
AI21110
Si m
1.1
5' -3
3'
-0
3' -0
3' -1
3'
-1
5' -3
5'-0" 5'-0"
FDFD
G H
CONFERENCE
A/V 231A
AI211
4 Sim
CHAIR RAIL
AI2112
COPY
N.I.C.
BASE CABINET
WALL CABINET
1.1
1' -0
1'
-0
1'-0" 1'-0"
1' -0
4' -0
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE421
ARCHITECTURAL
SECOND FLOOR 1/4" PLANS
REPLACE BUILDING 71
03.28.2018 AR RR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1/4" = 1'-0"5 OFFICE 218 DETAIL PLAN
1/4" = 1'-0"6 SECOND FLOOR BREAK ROOM
1/4" = 1'-0"2 CONFERENCE ROOM 215 FLOOR PLAN
1/4" = 1'-0"1 COPY AREA 211 FLOOR PLAN
1/4" = 1'-0"3 SECOND FLOOR RESTROOMS
1/4" = 1'-0"4
CONFERENCE ROOM 231 AND COPY
AREA 232 FLOOR PLAN
REFER TO SHEET AG003 FOR ADA REQUIREMENTS
GENERAL NOTES:
A
1/
2"
BOX OUT COLUMN WITH LIGHT
GAUGE MTL FRAMING
PROVIDE 1/2" MIN CLEARANCE
BETWEEN STRUCTURAL STEEL
AND LIGHT GAUGE FRAMING MTL
REFER TO
TYPICAL WALL ASSEMBLY W1
TYPICAL WALL ASSEMBLY W1
2 1/2"
1'-1" +/-
1' -1
PROVIDE 1/2" CLEARANCE MIN
BETWEEN STRUCTURAL STL
AND LIGHT GAUGE FRAMING
AE321
Sim
ALIGN WALL CAP, LOW
WALL WITH COLUMN
ENCLOSURE, (TYP.)
PAINT ALL 4 SIDES OF COLUMNS,
FLOOR TO CEILING. SEE FINISH
PLANS FOR ACCENT COLOR
PAINT WALL BELOW CAP ON
EITHER SIDE OF COLUMNS P-3
1' -5
2 1/2"
1/
2"
1/ 2"
1'-5"
2 1/2"
J
J
LIGHT GAUGE FRAMING SHOWN
FOR GRAPHIC PURPOSES ONLY.
DESIGN OF SYSTEM BY
MANUFACTURER OF SYSTEM (TYP)
REFER TO STRUCTURAL
FOR COLUMN SIZES
AND LOCATIONS
TYPICAL WALL ASSEMBLY W3
INTERIOR WALLS TO ABUT
EXTERIOR WALLS. INTERIOR FINISH
OF EXTERIOR WALLS GWB TO BE
CONTINUOUS AROUND PERIMETER
OF EXTERIOR WALLS INCLUDING
COLUMNS
REFER TO TYPICAL WALL ASSEMBLY W3
REFER TO TYPICAL WALL ASSEMBLY
BACKER ROD AND
WRAP TRANSITION
MEMBRANE INTO OPENING
FULL DEPTH OF FRAMING
PROVIDE ALUMINUM ANGLE
BETWEEN MASONRY AND CURTAIN WALL
SECURE INTO PRESSURE PLATE
FINISH TO MATCH CURTAIN WALL
A
A
ALIGN FACE OF
GYPSUM WITH
FACE OF CMU
TYPICAL WALL ASSEMBLY W3
TYPICAL WALL ASSEMBLY W3
REFER TO STRUCTURAL FOR
COLUMN SIZES AND LOCATIONS
BOX OUT COLUMN WITH LIGHT
GAUGE MTL FRAMING AROUND
COLUMN AND (1) LAYER OF
5/8" TYPE X GWB (TYP)
PROVIDE 1/2" CLEARANCE MIN
BETWEEN STRUCTURAL STL
AND LIGHT GAUGE FRAMING
PAINT ALL 4 SIDES OF FREE-
STANDING COLUMNS; SEE FINISH
PLANS FOR ACCENT COLOR
1'-5"
1' -5
B
B
REFER TO STRUCTURAL FOR
COLUMN SIZES AND LOCATIONS
PROVIDE 1/2" CLEARANCE BETWEEN
STRUCTURAL STL COLUMNS AND LIGHT
GAUGE FRAMING (TYP)
BOX OUT AROUND STRUCTURAL
COLUMNS WITH LIGHT GAUGE FRAMING
WITH 5/8" TYPE X GWB
PLAM SILL BELOW
GWB RETURN
BACKER ROD AND
SEALANT
WRAP TRANSITION
MEMBRANE INTO OPENING
FULL DEPTH OF FRAMING
BRICK MASONRY RETURN
AT WINDOWS, TYP.
PRECAST SILL BELOW
TYPICAL WALL ASSEMBLY W1
1'-2" +/-
B
B
ALIGN STL FRAMING WITH
EXTERIOR MASONRY
REFER TO STRUCTURAL FOR
COLUMN SIZES AND LOCATIONS
BOX OUT AROUND STRUCTURAL
COLUMNS WITH LIGHT GAUGE FRAMING
WITH 5/8" TYPE X GWB
PLAM SILL BELOW
GWB RETURN
BACKER ROD AND
SEALANT
WRAP TRANSITION
MEMBRANE INTO OPENING
FULL DEPTH OF FRAMING
BRICK MASONRY RETURN
AT WINDOWS, TYP.
PRECAST SILL BELOW
1'-4" +/-
ALUMINUM BRAKE METAL BY
WINDOW MANUFACTURER
LAPPED INTO PRESSURE CAP
AND COMPATIBLE WITH SYSTEM
FILL VOID WITH
CONTINUOUS
RIGID INSULATION ALIGN BRAKE METAL
AND PRESSURE CAP
PROVIDE PRE- FINISHED ALUMINUM BRAKE
METAL TRIM LAPPED INTO WINDOW SYSTEM
BACKER ROD AND SEALANT, TYP
- STRUCTURAL STL BY STRUCTURAL COLD
FORMED METAL FRAMING
- MINERAL WOOD BATT INSULATION
- 5/8" EXTERIOR GRADE GYPSUM
- TRANSITION MEMBRANE WRAPPED FULL
DEPTH OF FRAMING AND LAPPED ON TO
STRUCTURAL COLUMN
PAD OUT COLUMN AS REQUIRED FOR
CONTINOUS BACKUP BEHIND BRAKE METAL
PROVIDE MIN 1" CLEARANCE BETWEEN
CURTAIN WALL AND EDGE OF SLAB/
BEAM OF SECOND FLOOR ASSEMBLY
LINE OF WALL BELOW
EDGE OF SLAB AT SECOND FLOOR LEVEL
EDGE OF SLAB AT SECOND FLOOR LEVEL
1"
1"
ELEVATOR SHAFT
"TYPE B"
3 5/8" STUD PARTITION FILLED
W/ ACOUSTIC INSULATION
"TYPE D"
2 1/2" STUD ON 8" CMU
"TYPE A"
3 5/8" STUD PARTITION
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE521
ARCHITECTURAL
PLAN DETAILS / EXTERIOR DETAILS
REPLACE BUILDING 71
03.28.2018 AR RR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1 1/2" = 1'-0"10 DETAIL COLUMN A-4
1 1/2" = 1'-0"6 DETAIL COLUMN I-2
1 1/2" = 1'-0"2 DETAIL AT COLUMN J-1
1 1/2" = 1'-0"3
PLAN DETAIL AT INTEROR PARTITION
TERMINATING AT EXTERIOR
1 1/2" = 1'-0"5
STAIR 2 AND 3 (OPPOSITE HAND) -
FIRST FLOOR PLAN - Callout 1
1 1/2" = 1'-0"1
STAIR 2 AND 3 (OPPOSITE HAND) -
FIRST FLOOR PLAN - Callout 2
1 1/2" = 1'-0"7 GWB WRAPPED COLUMN (TYP.)
1 1/2" = 1'-0"8 FIRST FLOOR WINDOW AT COLUMN
1 1/2" = 1'-0"4 SECOND FLOOR WINDOW AT COLUMN
1 1/2" = 1'-0"9
STAIR 2 AND 3 (OPPOSITE HAND) -
FIRST FLOOR PLAN - Callout 3
1 1/2" = 1'-0"11 DETAIL ELEVATOR 1 CORNER
G
G
H
H
HOUSE
KEEPING
CLOSET
ELEV 1
AE611
AE611
AE611 1
MIN. 6'-9"
8'-1 3/4"
7'-0" MIN.
7'-2"
8' -4
" M
IN
8' -5
/2
AI211
REFER TO
STRUCTURAL
FOR SUMP PIT
LOCATION
ELEV
MECH
ELEV #2
(DEDUCT
ALTERNATE #1)
PIT LADDER
(TYP.)
1ST FLOOR
0"
2ND FLOOR
12'-0"
ROOF BEARING
24'-0"
G 4
AE611
4' -0
SHAFT DEPTH
7'-2"
NOTE: GC TO COORDINATE AND VERIFY ALL
REQUIRED SHAFT DIMENSIONS AND ELEVATOR
REQUIREMENT WITH SITE CONDITIONS AND
MANUFACTURER REQUIREMENTS
HOIST BEAM
PIT LADDER
(TYP.)
MIN.
1'-6"
1ST FLOOR
0"
2ND FLOOR
12'-0"
ROOF BEARING
24'-0"
4 3
AE611
AE312
PI
T
D
EP
TH
4'
-0
SHAFT WIDTH
8'-5 1/2"
TOP OF ROOF
40'-0"
PRE ENGINEERED METAL
MODIFY TRUSSES OVER ELEVATOR SHAFTS
TO ALLOW REQUIRED CLEARANCES.
PROVIDE CONCRETE SLAB OVER STEEL
DECK OVER SHAFT. (SEE STRUCTURAL)
HOIST BEAMS
REFER TO STRUCTURAL.
COORDINATE
CLEARANCES
WITH ELEVATOR
MANUFACTURER ALIGN
BEAM WITH CMU
COURSING
'-8
" M
IN
AE611
PIT LADDER (TYP.)
AE611
Sim
1ST FLOOR
0"
43 5
AE611
AE312
CONTROLSCONTROLS
G
G
AE611
AE611
AE312
HOUSEKEEPING
CLOSET
AI211 11
AE621
AE621
1ST FLOOR
0"
BENT PLATE 2 1/2"
X 3/8" WELD TO
STRINGERS AND
ATTACH TO WALL
W/ 3/4" EXP. BOLTS
SPACED @ 4'-0"
O.C. MAX VERT.
3/4" DIA STEEL
RUNGS WELD TO
STRINGERS
2 1/2" X 3/8" FLAT
BAR STRINGERS
2 1/2" X 2 1/2" X
1/4" CLIP ANGLE
WELD TO
STRINGER AND
BOLT TO FLOOR
1' -4
" M
AX
1' -0
TY
P.
4' -0
" T O
T O
P O
F
FL
O O
R
4 1/2" MIN
CL
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE611
ARCHITECTURAL
ELEVATOR
REPLACE BUILDING 71
03.28.2018 AR RR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1/4" = 1'-0"2 ELEVATORS - FIRST FLOOR PLAN
1/4" = 1'-0"5 ELEVATOR CABIN / SHAFT SECTION
1/4" = 1'-0"4 ELEVATOR SHAFTS SECTION
1/4" = 1'-0"1
FIRST FLOOR ELEVATION (SECOND
FLOOR SIMILAR)
1/4" = 1'-0"3 ELEVATORS - SECOND FLOOR PLAN
GENERAL NOTES:
1. REFER TO DRAWINGS AE112 AND AE 122 FOR PLAN
1" = 1'-0"6 TYPICAL PIT LADDER
F
F
AE621
AE621
AE621 7 AE6219
PROVIDE ACCESS DOOR IN
PERFORATED METAL PANEL
DOOR TO MATCH
PERFORATED PANELS
THICKENED SLAB
BELOW STAIR. SEE
STRUCT.
AE621
AE621
EXTENSIO
N TYP.
1'- 0"
HANDRAIL
AE621
AE621
Sim
UP
STEEL TUBE
SUPPORT BELOW.
BY STAIR MANUF.
12" DIAM MIN.
P-7
R
ISERS
9'-
2"
5'- 0"
6' -1
1/
2"
OF STRINGER
5'-4" TO OUTSIDE
O F
S T R
IN
G
ER
5' -4
" T O
O U
TS
ID
E
9 RISERS
8'-3" +/- 6'-6"
1ST FLOOR
0"
2ND FLOOR
12'-0"
F
" AE621
AE621
P-7
1ST FLOOR
0"
2ND FLOOR
12'-0"
AE621
TYP.
2'-11" +/-
AE621
AE621
ACCESS PANEL, LOCKABLE
+/- 30" WIDE. DOOR TO MATCH PERFORATED PANELS
HEIGHT TO BE DETERMINED BY CONTINUOUS REVEAL
IN PANEL BELOW STRINGER.
AE621
1ST FLOOR
0"
2ND FLOOR
12'-0"
3 3
AE621
BEND @ LANDING
STRINGER BEYOND
CANE GUARD
AE621
2' -3
AE621
1ST FLOOR
0"
2ND FLOOR
12'-0"
STAIR 1 AND MEZZANINE
GUARD AND HANDRAIL
PERFORATED METAL PANEL AT TOP
OF STAIR NOT SHOWN FOR CLARITY
BEND PERFORATED METAL PANEL
AT ALL TURNS AND CORNERS
AE621
Sim
F
F
AE621
AE621
AE621 7 AE6219
STAIR 1 AND
MEZZANINE RAILING
AE621
2" OFFSET FROM MEZ.
G U
AR
D
A N
D W
A
LL
2" O
FF
SE
T
BE
TW
EE
N
TYP.
1'-0" EXTENSION
TYP.
1'-0" EXTENSION
RETURN
HANDRAIL TO
WALL
AE621
ELEVATION
1" 1"
2" SQUARE POST
METAL STANDOFFS
MATCH FINISH OF POSTS
METAL STANDOFFS
MATCH FINISH OF POSTS
3"
ADA COMPLIANT RAILING,
BRACKET, AND SUPPORTS
P-8P-7 P-7
4"
3' -0
6"
2" X 2" SQUARE
METAL TUBE POSTS
RETURN HANDRAIL
AT POST
1"METAL STANDOFF
PANEL
PARALLEL TO
STRINGER.
DROPPED 4"
AE621
Sim
AE621
Sim
TYP.
AE621
C
AN
E G
U
AR
D
2' -3
POSTS TO EXTEND PAST
PERFORATED PANEL BY 2"
BOTH AT CANE GUARD
AND WHERE POST DROPS
BELOW STAIR (TYP.)
EXTENSION
1'-0"
.0
0°
P-8P-7 P-7P-8
TUBE STRINGER
2X2 SQUARE POST
OFFSET FROM
STRINGER BY 1/4" +/-
1/
2"
1.5" DIAM
HANDRAIL, PAINTED
STAIR TREADS
WITH TILE
FACE OF PERFORATED
MTL THIS SIDE
2"
MIN OFFSET
TO WALL
/6 AE621
/14 AE621
P-7
P-7
P-7
CAP
2X2 SQUARE MTL
POST
TILE FLOORING
PERFORATED METAL
PANEL TURNED OVER
AT EDGES SET IN
2" X 1/8" STEEL FRAME
2"
3' -6
" M
IN
CROSS SECTION
POST SUPPORT
AND CAP AS
REQ'D BY
SYSTEM
4"
/10 AE621
3' -0
/14 AE621
1.5" DIAM. WD
HANDRAIL
2"
1/
2"
P-7
P-8
P-7
1ST FLOOR
0"
2ND FLOOR
12'-0"
F
METAL PAN STAIRS
ABRASIVE EDGE
ALIGN T.O. TILE WITH
ABRASIVE EDGE
P-7
CT-F5
PERFORATED METAL
PANEL TURNED OVER
AT EDGES SET IN
2" X 1/8" STEEL FRAME
PERFORATED
METAL CRIMPED
ON EDGE. PROVIDE
SMOOTH EDGE
SMOOTH FASTENERS ON
ALL EXPOSED EDGES
P-8
P-7
2ND FLOOR
12'-0"
ANGLE FULL
DEPTH OF SLAB
AND MTL DECK
(REFER TO
1/4"
1 LAYER 5/8" TYPE X
GWB ON 3-5/8" MTL
REFR TO STRUCT FOR
BEAM SIZES AND
SCHLUTER
SCHIENE EDGE
FINISHED FLOORING
POST SUPPORT FOR
GUARD / HANDRAIL
REFER TO RCP FOR
CEILING HEIGHTS
FACE OF
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE621
ARCHITECTURAL
STAIRS
REPLACE BUILDING 71
03.28.2018 AR LP
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1/4" = 1'-0"5 STAIR 1 - FIRST FLOOR PLAN 1/4" = 1'-0"8 STAIR 1 ELEVATION FRONT
1/4" = 1'-0"7 STAIR 1 ELEVATION LEFT
1/4" = 1'-0"9 STAIR 1 ELEVATION RIGHT
1/4" = 1'-0"3 STAIR 1 SECTION
1/4" = 1'-0"4 STAIR 1 - SECOND FLOOR PLAN
1" = 1'-0"10
TYPICAL GUARD/HANDRAIL ELEVATION
AT SECOND FLOOR LOBBY/ ATRIUM
1" = 1'-0"11 STAIR 1 TYPICAL DETAILS
1 1/2" = 1'-0"12 TYP. SECTION AT STRINGER
1 1/2" = 1'-0"13 POST BASE
1" = 1'-0"1
TYPICAL GUARD/HANDRAIL SECTION AT
SECOND FLOOR LOBBY/ ATRIUM
1/4" = 1'-0"2 STAIR 1 SECTION1
1 1/2" = 1'-0"6 STAIR 1 TREAD DETAIL
6" = 1'-0"14 GUARD BORDER PROFILE
1 1/2" = 1'-0"15 BULKHEAD DETAIL AT ATRIUM
UP
DN
A
A
AE622
AE521
AE521
AE521
1.11.1
T
R
EA
D S
1"
'-0
4' -6
TR
EA
D S
1" 9'
-0
4'-5" 6" 4'-5"
3' HIGH
HANDRAIL
TO RETURN
AT WALL
AE622
A
A
AE622
AE313
1.11.1
42" HIGH
GUARD WITH
VERTICAL
BALLUSTERS
MATCHING
SIZE AND
SPACING AT
STAIR
1/
2" M
IN
2"
1/
2" M
IN
2"
1.5" DIAM
MTL
HANDRAILS
2" DIAM
MTL
GUARD
1.5" DIAM
MTL POSTS
WITH 3/4"
BALUSTERS
BETWEEN
POSTS
1.5" DIAM
MTL
BOTTOM
RAIL M
AX4"
TUBE
STRINGER
STAIR
TREADS
BEYOND
1ST FLOOR
0"
2ND FLOOR
12'-0"
ROOF BEARING
24'-0"
AE322
Sim
1.1
12"
TYP. HANDRAIL EXTENSION
FROM TOP TREAD
12"
" 42
E
Q U
AL
R
IS
ER
S
7/
'-0
4" MAX SPACING
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE622
ARCHITECTURAL
EXIT STAIR
REPLACE BUILDING 71
03.28.2018 DB AR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
1/4" = 1'-0"1
STAIR 2 AND 3 (OPPOSITE HAND) -
FIRST FLOOR PLAN
1/4" = 1'-0"2
STAIR 2 AND 3 (OPPOSITE HAND) -
SECOND FLOOR
1 1/2" = 1'-0"3 SECTION AT STAIR 2 AND 3 (TYP.)
1/4" = 1'-0"4 STAIR 2 AND 3 SECTION
1/ 2"
2"44
1/ 2"
FO
R
P
AR
TI
TI
O N
T
YP
E C
O O
R D
IN
AT
E W
/P
LA
N S
DOOR
4"
PARTITION,
COORDINATE
CONFIGURATION
W/PLAN
WIDTH
EQ EQ
WIDTH
A
SOLID CORE FLUSH DOOR
B
PAIR OF SOLID CORE FLUSH
DOOR
C
SOLID CORE FLUSH
DOOR w/ CLEAR
TEMPERED LIGHT
WIDTH
8" 8"
8"
T
D
PAIR OF SOLID CORE
FLUSH DOORS w/ CLEAR
TEMPERED LIGHT
H
EI
G H
T
H
EI
G H
T
H
EI
G H
T
H
EI
G H
T
3'-0" 3'-0"
WIDTH
8" TYP
8"
T T
E
PAIR OF ALUMINUM
STOREFRONT DOORS w/
CLEAR TEMPERED LIGHT
H
EI
G H
T
3'-0" 3'-0"
8" TYP
8"
T T
WIDTH WIDTH
F
INSULATED HOLLOW CORE
METAL DOOR
H
EI
G H
T
H
EI
G H
T
WIDTH WIDTH
H
EI
G H
T
METAL FRAME
SINGLE DOOR
METAL FRAME
DOUBLE DOOR
ALUMINUM INTERIOR
STOREFRONT ASSEMBLY
H
EI
G H
T 8'
-6
WIDTH
VARIES
T
5' -0
2'
-6
FROSTED PRIVACY
FILM APPLIED TO
OFFICE SIDE OF
GLAZING
6"
PREP FOR
POWER/DATA
SEE ELECTRICAL
MID MULION AS
REQUIRED
EQ EQ
TT
P
ER
W
AL
L
TY
PE
3 5
2"
2"
1/ 2"
2"
TRANSITION MEMBRANE WRAPPED
OVER THROUGH WALL FLASHING
THROUGH WALL FLASHING WITH WEEPS
GALVANIZED LOOSE LINTEL
BACKER ROD AND SEALANT
5 6
2"
2"1 1/2"2"
MSA, P.C.
Environmental Sciences Planning Surveying Civil & Environmental Engineering Landscape Architecture
5033 Rouse Drive, Virginia Beach, VA 23462 757-490-9264 (Ofc) 757-490-0634 (Fax) www.msaonline.com
M
AS
A Serv ic e
D is ab l e d Ve t e ran Owned Sma ll Bus iness
SDVOSB
CVE
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F o n e e ig h th in ch o n e f o o t o n e q u a rt e r in ch o n e f o o t th re e e ig h th s in ch o n e f o o t o n e h a lf in ch o n e f o o t th re e q u a rt e rs in ch o n e f o o t o n e in ch o n e f o o t o n e a n d o n e h a lf in ch o n e f o o t th re e in ch e s o n e f o o t
6"
6" 6"
6" 6"
Office of Construction and Facilities Management
Department of Veterans Affairs
Drawing Number
Building Number
Project Number
DrawnChecked
Location
Date
Project TitleDrawing Title
Approved: Project Director
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER PROFESSIONAL SEALCONSULTANTS:
Miller-Remick LLC M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856) 429-4000
FAX: (856) 429-5002
MR PROJECT NO: 0500-0006
FULLY SPRINKLERED
401 Woodbourne Ave Baltimore, Maryland 21212
T 410-435-6677 | F 410-435-6868 www.PenzaBailey.com
R :\R ev it
C en tra l F ile s\
- V
A Bu ild in g
\C 4-
1-
VA
- C op y_
LT
.rv t
AE711
ARCHITECTURAL
DOOR SCHEDULE
REPLACE BUILDING 71
03.28.2018 AR RR
BID DOCUMENTS
590-604
HAMPTON, VIRGINIA
PBA No. 16041
DOOR SCHEDULE
DOOR No. ROOM
DOOR FRAME
RATING HARDWARE STC COMMENTSTYPE MATERIAL FINISH WIDTH HEIGHT THICKNESS TYPE MATERIAL FINISH
1ST FLOOR
02A STAIR 2 A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 1
02B STAIR 2 F HM PTD 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 2
03A STAIR 3 A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 1
03B STAIR 3 F HM PTD 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 2
100A E ALUM CA 6'-0" 8'-4" 1 3/4" 2 ALUM CA 3 AUTO-OPENER & CARD READER
100B E ALUM CA 6'-0" 8'-4" 1 3/4" 2 ALUM CA 3.1 CARD READER
100C WORKSTATIONS D WD STAINED 6'-0" 7'-0" 1 3/4" 2 HM PTD 45 MIN 4 AUTO-OPENER
100D WORKSTATIONS D WD STAINED 6'-0" 7'-0" 1 3/4" 2 HM PTD 45 MIN 4 AUTO-OPENER
100E A WD STAINED 2'-8" 7'-0" 1 3/4" 1 HM PTD 8
100F A WD STAINED 2'-8" 7'-0" 1 3/4" 1 HM PTD 8
102 BREAK ROOM C WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 6
102A BREAK ROOM C WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 6
103 TELECOM A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 7 CARD READER
105 SPRINKLER MECH/PLUMB A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 9
105A ELEC A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 5
105B SPRINKLER MECH/PLUMB A HM PTD 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 10 CARD READER
106 MEN A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 11
107 WOMEN A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 11
108 HOUSE KEEPING CLOSET A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 8.1
111 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
112 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
113 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
114 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
115 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
117 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
118 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
119 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
120 CONFERENCE A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 13 45
120A A/V B WD STAINED 4'-0" 7'-0" 1 3/4" 2 HM PTD 14
121 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
122 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
123 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
131 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
132 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
133 ELEV MECH A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 9.1 45
134 CONFERENCE A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 13 45
134A A/V A WD STAINED 2'-6" 7'-0" 1 3/4" 1 HM PTD 15
135 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
136 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
137 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
138 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
140 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
141 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
142 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
143 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
144 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
151 TOILET A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 16 BUILDING 173
152 IT ROOM A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 7 BUILDING 173
E1.1 ELEV 1 ELEV 3'-0" 7'-6" 1 3/16" BY ELEVATOR MANUFACTURER
E2.1 ELEV #2 ELEV 3'-0" 7'-6" 1 3/16" BY ELEVATOR MANUFACTURER
2ND FLOOR
02C STAIR 2 A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 1
03C STAIR 3 A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 1
200A WORKSTATIONS D WD STAINED 6'-0" 7'-0" 1 3/4" 2 HM PTD 45 MIN 4 AUTO-OPENER
200B WORKSTATIONS D WD STAINED 6'-0" 7'-0" 1 3/4" 2 HM PTD 45 MIN 4 AUTO-OPENER
201 BREAK ROOM C WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 6
201A BREAK ROOM C WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 6
202 TELECOM A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 7 CARD READER
203 MECH/PLUMB A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 9
203A ELEC A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 5
204 MEN A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 11
205 WOMEN A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 11
206 HOUSEKEEPING CLOSET A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 45 MIN 8.1
212 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
213 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
214 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
215 CONFERENCE A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 13 45
215A A/V A WD STAINED 2'-6" 7'-0" 1 3/4" 1 HM PTD 15
216 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
217 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
218 WORKSTATIONS A WD 3'-0" 7'-0" 1 3/4" 3 ALUM
231 CONFERENCE A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 13 45
231A A/V A WD STAINED 2'-6" 7'-0" 1 3/4" 1 HM PTD 15
232 COPY AREA - - - 0" 0" -
233 POLICE OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 17 45 CARD READER
233A IT CLOSET A WD STAINED 3'-0" 7'-0" 1 3/4" 1 HM PTD 5.1
234 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
235 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
236 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
237 OFFICE A WD STAINED 3'-0" 7'-0" 1 3/4" 3 ALUM CA 12
E1.2 ELEV 1 ELEV 3'-0" 7'-6" 1 3/16" BY ELEVATOR MANUFACTURER
E2.2 ELEV #2 ELEV 3'-0" 7'-6" 1 3/16" BY ELEVATOR MANUFACTURER
3" = 1'-0"3 TYP. JAMB DETAIL (HEAD SIMILAR)
1/4" = 1'-0"
DOOR TYPES
1/4" = 1'-0"
FRAME TYPES
KEYNOTE LEGEND
1 5/8" GYPSUM WALLBOARD
2 3 5/8" METAL STUDS @ 16" O.C.
3 HOLLOW METAL DOOR FRAME
4 SEALANT
5 GROUT-FILL HOLLOW METAL FRAME
6 1 3/4" SOLID CORE DOOR
7 DOOR SILENCER
8 BACKER ROD W/ SEALANT
404 DOORS, DOORWAYS, AND GATES
1. DOORS, DOORWAYS, AND GATES THAT ARE PART OF AN ACCESSIBLE ROUTE SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS.
2. REVOLVING DOORS, REVOLVING GATES, AND TURNSTILES SHALL NOT BE PART OF AN ACCESSIBLE ROUTE.
3. AT LEAST ONE OF THE ACTIVE LEAVES OF DOORWAYS WITH TWO LEAVES SHALL COMPLY WITH REQUIRED CLEAR WIDTH AND MANEUVERING CLEARANCES. SEE FIGURE 404.2.4.1.
4. DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH
THE DOOR OPEN 90 DEGREES. SEE FIGURE 404.2.3. OPENINGS MORE THAN 24 INCHES DEEP SHALL PROVIDE A CLEAR OPENING OF 36 INCHES MINIMUM. THERE SHALL BE NO PROJECTIONS INTO THE REQUIRED CLEAR OPENING WIDTH LOWER THAN 34 INCHES ABOVE THE FINISH FLOOR OR GROUND. PROJECTIONS INTO THE CLEAR WIDTH BETWEEN 34 INCHES AND 80 INCHES ABOVE THE FINISH FLOOR OR GROUND SHALL
NOT EXCEED 4 INCHES.
A. EXCEPTIONS: 1. IN ALTERATION, A PROJECTION OF 5/8 INCH MAXIMUM INTO THE REQUIRED CLEAR WIDTH SHALL BE PERMITTED FOR THE LATCH SIDE STOP. 2. DOOR CLOSERS AND DOOR STOPS
SHALL BE PERMITTED TO BE 78 INCHES MINIMUM ABOVE THE FINISHED FLOOR OR GROUND.
5. MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY WITH FIGURE 404.2.4.1. MANEUVERING CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH
SIDE OR HINGE SIDE CLEARANCE.
6. SWINGING DOORS AND GATES SHALL HAVE MANEUVERING CLEARANCES COMPLYING WITH FIGURE 404.2.4.1.
7. DOORWAYS LESS THAN 36 INCHES WIDE WITHOUT DOORS OR GATES, SLIDING DOORS, OR FOLDING DOORS SHALL HAVE MANEUVERING CLEARANCES COMPLYING WITH FIGURE 404.2.4.2.
8. THRESHOLDS, IF PROVIDED, SHALL BE 1/2 INCH HIGH MAXIMUM.
9. DOORS IN SERIES AND GATES IN SERIES. THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES AND GATES IN SERIES SHALL BE 48 INCHES MINIMUM PLUS THE WIDTH OR THE DOORS OR GATES
SWINGING INTO THE SPACE. SEE FIGURE 404.2.6.
10. HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERABLE PARTS ON DOORS AND GATES SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST.
THE FORCE REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
11. MANEUVERING CLEARANCES FOR FORWARD APPROACH SHALL BE PROVIDED WHEN ANY OBSTRUCTION WITHIN 18 INCHES OF THE LATCH SIDE OF A DOORWAY PROJECTS MORE THAN 8 INCHES BEYOND THE FACE
OF THE DOOR,…