28_31_00-0002_-_Fire_Detection_Alarm_and_Mass_Notification__.pdf

PDF 4 MB Posted

Attached to
Z1DA--Construction -Repair Villa Water Damage Project Number 540-24-101
Solicitation number
36C24524B0004
Issued by

About this file

This federal contract opportunity notice is for construction and repair services at the Villa Water Damage Project located at Veterans Health Administration Veterans Integrated Service Network 5. The solicitation number is 36C24524B0004 and calls for repair work at Project Number 540-24-101. The required services include construction and repair to address water damage. The contracting agency is the Department of Veterans Affairs. The response due date and award date are not specified. Pricing terms, set asides, and incumbent information are also not included in this brief description.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Features Master Controller (top) bay:

32-Bit Master Controller with color-coded operator interface including raised switches for high confidence feedback

Dual configuration program CPU, convenient service port access, and capacity for up to 2500 addressable points

CPU assembly includes 2 GB dedicated compact flash memory for on-site system programming and information storage

System power supply (SPS) and charger (9 A total) with on-board: NACs, IDNet addressable device interface, programmable auxiliary output and alarm relay

Available with InfoAlarm Command Center expanded content user interface (see data sheet S4100-0045)

Upgrade kits are available for existing control panels Standard addressable interfaces include:

IDNet addressable device interface with 250 points that support TrueAlarm analog sensing and operate with either shielded or unshielded twisted pair wiring

Remote annunciator module support via RUI (remote unit interface) communications port

Optional modules include:

Building Network Interface Module (BNIC) for Ethernet connectivity options (see data sheet S4100-0061) Electrically isolated output IDNet 2 (two loop) and

IDNet 2+2 (four loop) modules with short circuit isolation output loops allowing use with either shielded or unshielded, twisted or untwisted single pair wiring

Fire Alarm Network Interfaces, DACTs, city connections, and up to five (5) RS-232 ports for printers and terminals

IP communicator compatibility MAPNET II addressable device modules and

MAPNET II quad isolator modules Alarm relays, auxiliary relays, additional power supplies, IDC modules, NAC expansion modules Service modems, VESDA Air Aspiration Systems interface, ASHRAE BACnet Interface, TCP/IP Bridges LED/switch modules and panel mount printers Emergency communications systems (ECS) equipment;

8 channel digital audio or 2 channel analog audio Battery brackets for seismic area protection (see page 2)

Compatible with Simplex® remotely located 4009 IDNet NAC Extenders, up to ten per IDNet

SLC

4100ES and upgrade kits are UL Listed to:

UL 864, Fire Detection and Control (UOJZ), and Smoke

Control Service (UUKL) UL 2017, Process Management Equipment (QVAX) UL 1076, Proprietary Alarm Units-Burglar (APOU) UL 1730, Smoke Detector Monitor (UULH) UL 2572, Mass Notification Systems (PGWM) ); refer to data sheet S4100-0034 for audio equipment ULC S527, Control Units for Fire Alarm Systems

Press ACK l ocated under fl ashin g indicator.

Repeat operation unti l al l events are acknowledged.

Local tone wil l silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP ' ( ) , 0 :

S T U V W X Y Z /

ALARMS

Fire Alarm Priority 2 Alarm

SYSTEM WARNINGS

Supervisory Trouble Ala rm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building Signals System ind icator flashing. Tone On. Press Alarm Silence.

How to Reset System Press System Reset.

Press Ack to si lence tone device.

ZONE

SI G

A UX

FB

IO

I DNet

P

A

L

N ET ADDR

0 DE L

Enter C/Exit

Fire Alarm Ack

Priority 2 Ack

Supv Ack

Trouble Ack

Alarm Silence

System Reset

Event Time

Enable On Arm

Disable Off Disarm Auto Lamp

Test

More Info

Menu Previous

Next

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

Press ACK located under flashing indicator.

Repeat operation until all events are acknowledged.

Lo cal to ne will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /

ALARMS

Fire Alarm Priority 2 Ala rm

SYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building Signals System indicator flashing. Tone On. Press Alarm Silence.

How to Reset System Press System Reset.

Press Ack to si lence tone device.

ZONE

SI G

A UX

FB

IO

I DNet

P

A

L

NET ADDR

0 DEL

Enter C/Exit

Fire Alarm Ack

Priority 2 Ack

Supv Ack

Trouble Ack

Alarm Silence

System Reset

Event Time

Enable On Arm

Disable Off Disarm Auto Lamp

Test

More Info

Menu Previous

Next

4100ES Cabinets are Available with One, Two or Three Bays

Software Feature Summary CPU provides dual configuration programs:

Two programs allow for optimal system protection and commissioning efficiency with one active program and one reserve

Downtime is reduced because the system stays running during download

PC based programmer features:

Convenient front panel accessed Ethernet port for quick and easy download of site-specific programming Modifications can be uploaded as well as downloaded for greater service flexibility AND, firmware enhancements are made via software downloads to the on-board flash memory

Introduction

4100ES Series Fire Detection and Control Panels provide extensive installation, operator, and service features with point and module capacities suitable for a wide range of system applications. An on-board Ethernet port provides fast external system communications to expedite installation and service activity. Dedicated compact flash memory archiving provides secure on-site system information storage of electronic job configuration files to meet NFPA 72 (National Fire Alarm and Signaling Code) requirements.

Modular design. A wide variety of functional modules are available to meet specific system requirements.

Selections allow panels to be configured for either Stand-Alone or Networked fire control operation. InfoAlarm Command Center options provide convenient expanded display content (detailed on data sheet S4100-0045).

* See pages 5 and 6 for product that is UL or ULC listed and additional listing information.

This product has been listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:251(4100ES) for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

Fire Control Panels UL, ULC, CSFM Listed; FM Approved; Addressable Fire Detection and Control MEA (NYC) Acceptance* Basic Panel Modules and Accessories

S4100-0031-31 3/2015

Module Bay Description

The Master Controller Bay (top) includes a standard multi-featured system power supply, the master controller board, and operator interface equipment.

The Expansion Bays include a Power Distribution Interface (PDI) for new 4” x 5” flat design option modules and also accommodate 4100-style modules.

The Battery Compartment (bottom) accepts two batteries, up to 50 Ah, to be mounted within the cabinet without interfering with module space.

The following illustration identifies bay locations using a three bay cabinet for reference.

PDI

4x5 Module

Expansion Power Supply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

O pt io n

O pt io n

O pt io n

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

System Power Supply

(SPS)

IDNet NACs 1, 2 & 3

Aux Pwr Aux Relay

Btry

M as te r C on tro lle r

B oa rd

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

Slot 1

Slot 2

Slot 4

Slot 3

PDI

4x5 Module

Expansion Power Supply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

O pt io n

O pt io n

O pt io n

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

Master Controller Bay

Expansion Bay 1

Battery Compartment

System power supply Master controller with dual slot motherboard

Expansion Bay 2

Typical bays with mixed module sizes

4100ES Module Bay Reference

Mechanical Description

Boxes can be close-nippled; each box provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting

Smooth box surfaces are provided for locally cutting conduit entrance holes exactly where required

Cabinet assembly design has been seismic tested and is certified to IBC and CBC standards as well as to ASCE 7 categories A through F, requires battery brackets as detailed on data sheet S2081-0019

Mechanical Description (Continued)

The latching dress panel (retainer) assembly easily lifts off for internal access

NACs are mounted directly on power supply assemblies providing minimized wiring loss, compact size, and readily accessible terminations

Packaging supports traditional 4100-style motherboard with daughter cards

Modules are power-limited (except as noted, such as relay modules)

The NEMA 1/IP30 box is ordered separately and available for early installation

Doors are available with tempered glass inserts or solid; boxes and doors are available in platinum or red

Boxes and door/retainer assemblies are ordered separately per system requirements; refer to data sheet S4100-0037 for details

Operator Interface Detail Reference

The following illustration identifies the primary functions of the operator interface.

Press ACK located under flashing indicator.

Repeat operation until all events are acknowledged.

Local tone will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /

ALARMS

Fire Alarm Priority 2 Alarm

SYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building Signals System indicator flashing. Tone On. Press Alarm Silence.

How to Reset System Press System Reset.

Press Ack to silence tone device.

ZONE

SIG

AUX

FB

IO

IDNet

P

A

L

NET ADDR

0 DEL

Enter C/Exit

Fire Alarm Ack

Priority 2 Ack

Supv Ack

Trouble Ack

Alarm Silence

System Reset

Event Time

Enable On Arm

Disable Off Disarm Auto Lamp

Test

More Info

Menu

Previous

Next

Upload/Download Ethernet port access (under sliding cover)

Basic operator instructions are printed on the interface mounting plate

Panel sounder

Operator interface panel is directly viewable and accessible (no access door)

Software Feature Summary

TrueAlarm individual analog sensing with front panel information and selection access

“Dirty” TrueAlarm sensor maintenance alerts, service and status reports including “almost dirty”

TrueAlarm magnet test indication appears as distinct “test abnormal” message on display when in test mode

TrueAlarm sensor peak value performance report “Install Mode” allows grouping of multiple troubles for uninstalled modules and devices into a single trouble condition (typical with future phased expansion); with future equipment and devices grouped into a single trouble, operators can more clearly identify events from the commissioned and occupied areas

Module level ground fault searching assists installation and service by locating and isolating modules with grounded wiring

“Recurring Trouble Filtering” allows the panel to recognize, process, and log recurring intermittent troubles (such as external wiring ground faults), but only sends a single outbound system trouble to avoid nuisance communications

WALKTEST silent or audible system test performs an automatic self-resetting test cycle

2 S4100-0031-31 3/2015

Operator Interface Convenient Status Information. With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches.

Features include a two-line by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in the illustration below.

LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door provides access to the control switches and allows further inquiry by scrolling the display for additional detail.

Operator Interface Features Convenient and extensive operator information is provided using a logical, menu-driven display

Multiple automatic and manual diagnostics for maintenance reduction

Alarm and Trouble History Logs (up to 1250 entries for each, 2500 total events) are available for viewing from the LCD, or capable of being printed to a connected printer, or downloaded to a service computer

Convenient PC programmer label editing

Password access control

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /

ALARMS

Fire Alarm Priority 2 Alarm

SYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

ZONE

SIG

AUX

FB

IO

IDNet

P

A

L

NET ADDR

0 DEL

Enter C/Exit

Fire Alarm Ack

Priority 2 Ack

Supv Ack

Trouble Ack

Alarm Silence

System Reset

Event Time

Enable On Arm

Disable Off Disarm Auto Lamp

Test

More Info

Menu

Previous

Next

SIX SYSTEM STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash to indicate the condition and then when acknowledged, remain on until reset :

Fire Alarm & Priority 2 Alarm, red LED Supervisory & Trouble, yellow LED Alarm Silenced, yellow LED AC Power, green LED (on for normal)

FIVE PROGRAMMABLE

FUNCTION SWITCHES,

each with a yellow LED indicator

POINT STATUS

CONTROL KEYS:

Point Enable and Disable Force On or Arm Force Off or Disarm Return On/Off or Arm/Disarm to Auto Mode

NUMERIC KEYPAD for point category and point selection (alphabet characters are not used at this time)

ADDITIONAL FUNCTION

KEYS:

Event Time Request More Information Request Lamp Test

Elevator Recall

City Disconnect

Manual Evac

Ground Fault

Waterflow-West

Waterflow-East

Custom label insert

LCD NAVIGATION

CONTROL:

Menu selection Vertical and Horizontal position selection buttons

FIRE ALARM ACK acknowledges a Fire Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

PRIORITY 2 ACK acknowledges a Priority 2 Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

SUPV ACK acknowledges system supervisory conditions, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

TROUBLE ACK acknowledges system troubles, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

ALARM SILENCE causes audible notification appliances to be silenced (depending on panel programming) typically after evacuation is complete and while alarm source is being investigated; may allow visible notification to continue (strobes still flashing)

SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal

2 X 40 LCD READOUT, LED backlighted during normal conditions and abnormal operating conditions, provides up to 40 characters for custom label information

FIRST ALARM DISPLAY: Operation can be selected for maintained display of first alarm until acknowledged

THREE PROGRAMMABLE LEDs provide custom labeling, the top two LEDs are selectable as red or yellow, the bottom LED is selectable as green or yellow

ULC SYSTEMS

require designating a Ground Fault indicator

Almost Dirty

Ground Fault Latch

3 S4100-0031-31 3/2015

Compatible Peripheral Devices The 4100ES is compatible with an extensive list of remote peripheral devices including printers, CRT/keyboards (up to five total), and both conventional and addressable devices including TrueAlarm analog sensors.

Addressable Device Control Overview. The 4100ES provides standard addressable device communications for IDNet compatible devices and accepts optional modules for communications with MAPNET II compatible devices. Using a two wire communications circuit, individual devices such as manual fire alarm stations, TrueAlarm sensors, conventional IDC zones, and sprinkler waterflow switches can be interfaced to the addressable controller to communicate their identity and status.

Addressability allows the location and condition of the connected device to be displayed on the operator interface LCD and on remote system annunciators. Additionally, control circuits (fans, dampers, etc.) may be individually controlled and monitored with addressable devices.

Addressable Operation. Each addressable device on the communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Both Class B and Class A operation are available. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuit for Class B operation.

Devices with LEDs pulse the LED to indicate receipt of a communications poll and can be turned on steady from the panel.

IDNet Channel Capacity. The CPU bay system power supply (SPS) provides an IDNet signaling line circuit (SLC) that supports up to 250 addressable monitor and control points intermixed on the same pair of wires. Additional 250 point IDNet circuit modules are available, refer to IDNet 2 and IDNet 2+2 modules on page 7.

IDNet, MAPNET II, IDNet 2, and IDNet 2+2 SLC Wiring Common Specifications Maximum Distance from Control Panel per Device Load

1 to 125 4000 ft (1219 m); 50 ohms

126-250 2500 feet (762 m); 35 ohms

Connections Terminals for 18 to 12 AWG (0.82 mm2 to 3.31 mm2)

IDNet and MAPNET II Specifications

Wire Type Preferred Shielded twisted pair (STP)

Acceptable* Unshielded twisted pair (UTP)

IDNet and MAPNET II Wiring, Total Wire Length Allowed With “T” Taps for Class B Wiring

Up to 10,000 ft (3 km); 0.58 μF

IDNet 2 and IDNet 2+2 Wiring Specifications

Wire Type Shielded or unshielded, twisted or untwisted wire*

Total Wire Length Allowed With “T” Taps for Class B Wiring

Up to 12,500 ft (3.8 km);

0.60 μF

Maximum Capacitance Between IDNet 2 Channels 1 μF

IDNet 2 and IDNet 2+2 Module Compatibility: IDNet communicating devices and TrueAlarm sensors including QuickConnect and QuickConnect2 sensors

* Some applications may require shielded wiring. Review your system with your local Simplex product supplier.

TrueAlarm System Operation Addressable device communications include operation of TrueAlarm smoke and temperature sensors. Smoke sensors transmit an output value based on their smoke chamber condition and the CPU maintains a current value, peak value, and an average value for each sensor.

Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.

Programmable sensitivity of each sensor can be selected at the control panel for different levels of smoke obscuration (shown directly in percent) or for specific heat detection levels. To evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read and compared to the alarm threshold directly in percent.

CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one system address. The CO sensor can be enabled/disabled, used in LED/Switch modes and custom control, and can be made public for communication across a fire alarm Network.

(refer to data sheet S4098-0052 for details)

TrueAlarm heat sensors can be selected for fixed temperature detection, with or without rate-of-rise detection. Utility temperature sensing is also available, typically to provide freeze warnings or alert to HVAC system problems. Readings can selected as either Fahrenheit or Celsius.

TrueSense Early Fire Detection. Multi-sensor 4098-9754 provides photoelectric and heat sensor data using a single 4100ES IDNet address. The panel evaluates smoke activity, heat activity, and their combination, to provide TrueSense early detection. For more details on this operation, refer to data sheet S4098-0024.

Diagnostics and Default Device Type Sensor Status. TrueAlarm operation allows the control panel to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each sensor. CO Sensors track their 10 year active life status providing indicators to assist with service planning. Indicators occur at: 1 year, 6 months, and when end of life is reached.

Modular TrueAlarm sensors use the same base and different sensor types (smoke or heat sensor) and can be easily interchanged to meet specific location requirements.

This allows intentional sensor substitution during building construction when conditions are temporarily dusty.

Instead of covering smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. The control panel will indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.

4 S4100-0031-31 3/2015

CPU Bay Module Details Master Controller and Motherboard:

Mounts in Slot 4 of a two slot motherboard (Slots 3 and 4 of the Master Controller Bay) and provides one Class B or Class A, RUI communications channel, available at Slot 4

RUI communications controls up to 31 devices per master controller (on one or multiple RUI channels); devices include: MINIPLEX transponders, 4603-9101 LCD Annunciators, 4602-9101 Status Command Units (SCU), 4602-9102 Remote Command Units (RCU), 4602 Series LED Annunciator Panels, and 4100 Series 24 I/O and LED/Switch modules

Up to four RUI channels are supported; use up to three 4100-1291 RUI expansion modules as required

Optional Service Modem 4100-6030 mounts onto the master controller board with its own on-board connections

Slot 3 of the motherboard is primarily for the 4100-6078 Network Interface Board with media modules, and secondarily for the 4100-6038 Dual RS-232 Board (4100-6038 is required for 2120 System connections)

System Power Supply: (see page 9 for more detail) Rating is 9 A total with “Special Application” appliances;

4 A total for “Regulated 24 DC” appliance power Outputs are power-limited, except for the battery charger Provides system power, battery charging, auxiliary power, auxiliary relay, earth detection, on-board IDNet communications channel for 250 points, three on-board NACs, and provisions for either an optional City Connect Module or an optional Alarm Relay Module

IDNet SLC Output provides Class B or Class A communications for up to 250 addressable devices (as described on page 4)

System Power Supply (Continued):

Three, 3 A On-Board NACs, conventional reverse polarity operation; rated 3 A for Special Application appliances and 2 A for Regulated 24 DC power, with electronic control and overcurrent protection; selectable as Class B or Class A, and for synchronized strobe or SmartSync horn/strobe operation over two wires

NACs can be selected as auxiliary power outputs derated to 2 A for continuous duty; the total auxiliary power output per SPS is limited to 5 A

Battery Charger is dual rate, temperature compensated, and charges up to 50 Ah sealed lead-acid batteries mounted in the battery compartment (33 Ah for single bay cabinets); also is UL listed for charging up to 110 Ah batteries mounted in an external cabinet (see data sheet S2081-0012 for details)

Battery and Charger Monitoring includes battery charger status and low or depleted battery conditions;

status information provided to the master controller includes analog values for: battery voltage, charger voltage and current, actual system voltage and current, and individual NAC currents

2 A Auxiliary Power Output is selectable for detector reset, door holder, or coded output operation

Auxiliary Relay is selectable as N.O. or N.C., rated 2 A @ 32 VDC, and is programmable as a trouble relay, either normally energized or normally de-energized, or as an auxiliary control

Optional City Connect Module (4100-6031, with disconnect switches, or 4100-6032, without disconnect switches) can be selected for conventional dual circuit city connections

Optional Alarm Relay Module (4100-6033) provides three Form C relays that are used for Alarm, Trouble, and Supervisory, rated 2 A resistive @ 32 VDC

4100ES Master Controller and Expansion Bay Selection* (Canadian models have low battery cutout) Model Model Type and Listing Description Supv.** Alarm**

4100-9111 120 VAC Input UL 4100ES Master Controller Assembly with LCD and operator interface, 9 A system power supply/battery charger (SPS), 250 point IDNet interface, 3 NACs, auxiliary relay, and external RUI communications interface

373 mA 470 mA4100-9112 English 120 VAC, Canadian ULC 4100-9113 French 4100-9211 220-240 VAC Input UL 4100-9131 120 VAC Input UL 4100ES Master Controller Assembly, no display, no operator interface, 9 A system power supply/battery charger (SPS), 250 point IDNet interface, 3 NACs, auxiliary relay, and external RUI communications interface

363 mA 425 mA4100-9132 English, 120 VAC, Canadian ULC 4100-9230 220-240 VAC Input UL

4100-9121 (not ULC listed)

Redundant Master Controller with a two bay assembly, one for each of the primary and backup master controllers. Both bays have an LCD and operator interface, CPU card assembly, and 9 A system power supply (SPS) 120 VAC, 60 Hz input. Active SPS battery charger in Bay 1 only.

External RUI connections require 4100-1291 RUI expansion modules. Do not use circuit connections (IDNet, NACs, etc.) on primary and secondary SPS power supplies.

718 mA 937 mA

4100ES Master Controller Upgrades for Existing 4100 Series Fire Alarm Control Panels* Model Panel Type Includes

4100-7150 1000 pt 4100 (4100+) New Master Controller CPU card, 4100ES door assembly with LCD and user interface, and Ethernet connection

4100-7152 512 pt 4100 Same as 4100-7150 plus a Universal Power Supply

4100-7158

4100U or 1000 pt 4100 (4100+) previously upgraded to 4100U

New Master Controller CPU card with Ethernet Connection Upgrade Kit (door assembly with LCD and user interface are not included) for:

4100U with or without LCD and operator interface, or 4100+ without LCD and operator interface, or An existing 4100 (512 pt) or 4100+ (1000 pt) panel that was previously upgraded to a 4100U Master Controller and Display

* For InfoAlarm Command Center expanded content display products, refer to data sheet S4100-0045. (Continued on next page) ** Note: Master Controller current does not subtract from 9 A output rating.

5 S4100-0031-31 3/2015

Master Controller Selection Information

6 S4100-0031-31 3/2015

Communication Modules Model Description Size Supv. Alarm

4100-6078 For Master Controller; mounts in Slot 3 Modular Network Interface; each requires two media modules (below)

1 Slot 46 mA 46 mA

4100-6061 For Redundant Master Controller 1 Slot 46 mA 46 mA

4100-6056 Wired Media Module Select two media cards as required; mounts on 4100-6078 or 4100-6061; Class B or Class X operation

N.A. 55 mA 55 mA

4100-6057 Fiber Optic Media Module N.A. 25 mA 25 mA

4100-6047 Building Network Interface Card (BNIC), refer to data sheet S4100-0061 for details 2 Blocks 291 mA 291 mA

4100-6055 Network Access Dial-in Service Modem, mounts to 4100-6078 or 4100-6061 Network Interface Card, requires telephone line connection N.A. 60 mA 60 mA

4100-1291 Remote Unit Interface Module (RUI); up to three maximum per control panel 1 Slot 85 mA 85 mA

4100-6030 Service Port Modem, local panel access only, mounts to Master Controller Module, requires telephone line connection, accesses same information as front panel port N.A. 70 mA 70 mA

4100-6031 Select one per SPS (fits on SPS)

City Circuit, with disconnect switches For use with SPS only, not RPS

N.A. 20 mA 36 mA

4100-6032 City Circuit, w/o disconnect switches N.A. 20 mA 36 mA

4100-6033 Alarm Relay, 3 Form C relays, 2 A @ 32 VDC; for SPS or RPS N.A. 15 mA 37 mA

4100-6101 Physical Bridge, Class B, includes 1 modem module and 2 wired modules 1 Slot 210 mA 210 mA

4100-6102 Physical Bridge, Class X, includes 2 modem and 2 wired modules 2 Slots 300 mA 300 mA

4100-6038 Dual Port RS-232 with 2120 interface (slot module) 3 maximum of RS-232 type modules per panel

1 Slot 132 mA 132 mA

4100-6046 Dual Port RS-232 standard interface (4 x 5 module) 1 Block 60 mA 60 mA

4100-6045 Decoder Module 3 Slots 85 mA 163 mA

4100-6048 VESDA Aspiration System Interface 1 Slot 132 mA 132 mA

4100-6052 DACT, Point or Event Reporting; 1 shipped unless 4100-7908 is selected; 2 max. per system; includes 2, 2080-9047 cables, 14 ft (4.3 m) long, RJ45 plug and spade lugs 1 Slot 30 mA 40 mA

Expansion, System and Remote Power Supplies and Accessories (Canadian models have low battery cutout) Model Voltage/Listing Description Size Supv. Alarm

4100-5101 120 VAC UL Expansion Power Supply (XPS); 9 A output, 3 built-in Class A/B NACs; NAC operation is same as SPS, see page 5 for details

2 Blocks 50 mA 50 mA 4100-5103 120 VAC, Canadian ULC

4100-5102 220-240 VAC UL

4100-5115 NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only N.A. 25 mA 25 mA

4100-5111 120 VAC UL Additional System Power Supply (SPS); 9 A power supply/charger with 250 point IDNet channel, 3 Class A/B NACs, add IDNet device currents separately

4 Blocks 175 mA 185 mA 4100-5112 120 VAC, Canadian ULC

4100-5113 220-240 VAC UL

4100-5125 120 VAC UL Remote Power Supply (RPS); 9 A power supply/charger similar to SPS except no IDNet channel or City Circuits; will accept one 4100-6033

4 Blocks 150 mA 185 mA 4100-5126 120 VAC, Canadian ULC

4100-5127 220-240 VAC UL

Continued on next page

Master Controller Accessories 4100-2300 Expansion Bay Assembly; order for each required expansion bay (not required for 4100-9121)

4100-2303 Legacy Module Stabilizer Bracket, used when expansion bays have legacy slot style modules

4100-2301 Expansion Bay Upgrade Kit for mounting 4100ES style (4” x 5” modules) in existing 4100 style panels;

Note: When using this kit to upgrade a 4100+ transponder, a 4100-0620 Transponder Interface Card (TIC) is also required for communications to the 4100ES module

Master Controller Upgrades for Existing 4020 Series Fire Alarm Control Panel Model Description

4100-9833

4020 Master Controller Upgrade to 4100ES; Includes New Master Controller with LCD & operator interface assembly, 8 VDC Converter and RUI Interface in a single bay cabinet with locking glass door and retainer; mounts as an adjunct panel close-nippled to existing 4020 cabinet; also includes 8 VDC box-to-box power and communications harness and solid filler panel for the existing 4020 Master Controller bay

Module Selection Information

Master Controller Selection Information (Continued)

7 S4100-0031-31 3/2015

Expansion, System and Remote Power Supplies and Accessories (Continued) Model Description Size Current

4100-5152 12 VDC Power Option, 2 A maximum 1 Block 1.5 A maximum

4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block included w/loads

4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet 4100-0638 4100 Slot Module Additional 24 VDC Harness; need when 4100 Slot module requirements exceed 2 A from SPS

8 Zone Initiating Device Circuits* Expansion Signal Module and Options (1.5 A Class B except as noted) Model Type Supv. Alarm Model Description Supv. Alarm

4100-5005 Class B 75 mA 195 mA 4100-5116 Converts 1 NAC in to 3 NACs out; 1 Block size 18 mA 80 mA

4100-5015 Class A 75 mA 195 mA 4100-1266 Expands 3 NACs to 6 select one; mounts on 4100-5116

0.6 mA 60 mA

* IDC Modules are 1 Slot size 4100-1267 Converts 3 NACs to Class A 0.6 mA 30 mA

Addressable Interface Modules (refer to location reference on pages 8 and 9) Model Description Supv. Alarm

4100-3109*

IDNet 2 Module, 250 point capacity; electrically isolated output with two short circuit isolating Class B or Class A output loops, 1 block; standard on EPS with IDNet 2 Module; alarm currents for 50 and above devices includes 20 device LEDs in alarm no devices 50 mA 60 mA 50 devices 90 mA 150 mA

125 devices 150 mA 225 mA 250 devices 250 mA 350 mA

4100-3110*

IDNet 2+2 Module, 250 point capacity; electrically isolated output with four short circuit isolating Class B or Class A output loops, 1 block; mounts in expansion bay or available master controller bay module locations only, not applicable for EPS mounting; alarm currents for 50 and above devices includes 20 device LEDs in alarm no devices 50 mA 60 mA 50 devices 90 mA 150 mA

125 devices 150 mA 225 mA 250 devices 250 mA 350 mA

4100-3111* IDNet Short Circuit Isolating Loop Output Module; mount up to two on a 4100-3109 module; for use with 4100-3109 modules; this option is for aftermarket field installation only

*Note: Loading per IDNet device (no LEDs on) = 0.8 mA supervisory and 1 mA alarm.

Each IDNet 2 and IDNet 2+2 Short Circuit Isolating Loop Output can be individually controlled for system diagnostics and can be assigned a public point for Fire Alarm Network annunciation.

Model Description Supv. Alarm

4100-3102 MAPNET II Module, 127 point capacity, add devices separately; Module size = 2 Slots;

Loading per MAPNET II device = 1.7 mA

Module without devices 255 mA 275 mA

Fully loaded module, total 471 mA 491 mA

4100-3103

Isolator Module for MAPNET II communications; converts a single connected SLC into four isolated outputs selectable as Class A or Class B; up to two Isolator Modules can be connected to one SLC; Module size = 1 Slot;

NOTE: Compatible with MAPNET II Remote Isolators only

50 mA 50 mA

Relay Modules; Nonpower-limited (for mounting in expansion bay only, refer to location reference on pages 8 and 9)

Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm 4100-3202 4 DPDT w/feedback 10 A 250 VAC 10 A 250 VAC 2 Slots 15 mA 175 mA

4100-3204 4 DPDT w/feedback 2 A 30 VDC/VAC 1/2 A 30 VDC/120 VAC 1 Block 15 mA 60 mA 4100-3206 8 SPDT 3 A 30 VDC/120 VAC 1-1/2 A 30 VDC/120 VAC 1 Block 15 mA 190 mA

Current Calculation Notes:

1. To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered by panel power supplies.

2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC loads and all external loads powered from panel power supplies.

Continued on next page

Module Selection Information (Continued)

8 S4100-0031-31 3/2015

End User Programming Software (requires 4100-8802) Model Description

4100-8802 Programming Software (select)

End User Programming Software Selection (select maximum of one each from below) Model Description

4100-0292 Custom Labels Editing; allows editing of 40 Character Custom Labels for non-system user points

4100-0296 Access Level/Passcode Editing; allows user to re-assign Access Levels and Passcodes for each display function;

Acknowledge, Alarm Silence, System Reset, Point Enable/Disable, WALKTEST Enable/Disable, Clear History Logs, Change Time & Date, etc.

4100-0295 Port Vectoring Setup and Control; Allows vectoring of events to PC Annunciator, Printers, LCD Annunciators, etc.

4100-0298

WALKTEST Configuration Setup and Control; Allows user to create or edit WALKTEST groups used to test system initiating devices and signals by a single person, these groups allow an inspector to conduct a one-person WALKTEST in a specific area of a building (or different buildings), and limit the activation of the building signals to only the intended area; up to 8 WALKTEST groups are supported

Miscellaneous Accessories Model Description

4100-1279 Single blank 2” display cover; 4100-2302 provides a single plate for a full bay

4100-9856* 4100ES Canadian French Appliqué Kit; Simplex, 4100ES, Contrôle Incendie

4100-9857* 4100ES English Appliqué Kit; Simplex, 4100ES, Fire Control

4100-9858* 4100ES InfoAlarm Remote Display English Appliqué Kit; Simplex, Operator Interface, 4100ES

4100-9859* 4100ES InfoAlarm Remote Display Canadian French Appliqué Kit; Simplex, Interface de l’operateur, 4100ES

4100-9868 Special Purpose Appliqué Kit: Simplex, Elevator Recall Control and Supervisory Control Unit, 4100ES

4100-9869 Special Purpose Appliqué Kit: Simplex, Sprinkler Waterflow and Supervisory Station, 4100ES

4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules

4100-6029 Smoke Management Application Guide; required for UUKL listing

4100-6034 Tamper Switch, one per cabinet assembly if required; monitors solid door for panels with solid door; monitors the internal retainer panel for panels with glass door (not the glass door); has a built-in addressable IDNet IAM

2081-9031 Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 , 1 W, encapsulated, two 18 AWG leads (0.82 mm2 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)

* Note: 4100ES English Appliqués are included with 4100ES Upgrade and Retrofit Kits for mounting 4100ES in 4100, 2120, 2001, and Autocall back boxes so that upgrades can be easily identified as 4100ES. 4100ES Appliqué Kits are available for applications such as to update Remote InfoAlarm Displays connected to a panel that was upgraded to 4100ES or for an existing 4100U when the New Master Controller is upgraded to 4100ES and only a software upgrade is required. When required, French appliqués are ordered separately.

Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2

Expansion Bay Chassis

Block A

Block B

Block C

Block D

Block E

Block F

Block G

Block H

Size Definitions: Block = 4” W x 5” H (102 mm x 127 mm) card area Slot = 2” W x 8” H (51 mm x 203 mm) motherboard with daughter card

Module Selection Information (Continued)

Expansion Bay Module Loading Reference

Description Mounting IDNet 2, IDNet 2+2 Modules 1 Block 4, 2 A Relays

NON

Power-limited

1 block 4, 10 A Relays 4”, 2 slots 8, 3 A Relays 1 block VESDA Interface 2”, 1 Slot Class B IDC 2”, 1 Slot Class A IDC 2”, 1 Slot MAPNET II Module 4”, 2 Slots MAPNET II/IDNet Isolator 2”, 1 Slot Class B Physical Bridge 2”, 1 Slot Class X Physical Bridge 4”, 2 Slots Decoder Module 6”, 3 Slots

System or Remote Power Supply Blocks E, F, G & H

ONLY

Expansion Power Supply Blocks G & H ONLY NAC Expansion Module On XPS ONLY

9 S4100-0031-31 3/2015

PDI

4x5 Module

Expansion Power Supply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

System Power Supply

(SPS)

IDNet NACs 1, 2 & 3

Aux Pwr Aux Relay

Btry

City Circuit 4100-6031 4100-6032

Alarm Relay 4100-6033

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

*System power supply*Master controller with motherboard

Optional semi-flush trim kit

4100-6031 or 4100-6032 City Circuit or 4100-6033 Alarm Relay

4100-6030 Service Modem mounts only on master controller board

Slot 3, one 2" card: either 4100-6078 Network Module with media cards or 4100-6038 Dual RS-232

Slot 1

Slot 2

Slot 3

Cabinet height:

(2 bay shown for reference)

1 Bay = 22" (559 mm)

2 Bay = 40" (1016 mm)

3 Bay = 56" (1422 mm)

Stud alignment markers, each side

Knockout screw/nail holes (for semi-flush mounting)

4" stud

6" stud

Two, 2", or one, 4" slot for one or two modules installed per the following:

4100-6052 DACT, Slot 1 4100-6101 Physical Bridge, Slot 2 4100-6102 Physical Bridge (4" module) Slots 1 and 2 4100-6048 VESDA Interface, Slot 1 or 2 4100-5005/5015 IDC Modules, Slot 1 or 2 4100-6038 Dual RS-232, Slot 2, if Network Module is in Slot 3

Master Controller Bay

Typical Expansion Bay (showing mixed module sizes)

Battery Compartment

Door can be hung hinged left or right

Wall board reference for semi-flush mounting, 6" stud

Two bay cabinet shown without retainer

11-11/16" (296 mm)

6-29/32" (175 mm)

For semi-flush mounting provide 1/2" (12.7 mm) minimum extension beyond finished wall

24" (610 mm)

Door 4-3/4" (121 mm)

Input Power

System Power Supplies (SPS) Expansion Power Supplies (XPS)

Remote Power Supplies (RPS)

120 VAC Models 4 A maximum @ 102 to 132 VAC, 60 Hz

220-240 VAC

Models

2 A maximum @ 204 to 264 VAC, 50/60 Hz;

separate taps for 220/230/240 VAC

Power Supply Output Ratings for SPS, XPS, and RPS (nominal 28 VDC on AC; 24 VDC on battery backup)

Total Power Supply Output Rating

Including module currents and auxiliary power outputs;

9 A total for “Special Application” appliances; 4 A total for “Regulated 24 DC” power (see below for details)

Output switches to battery backup during mains AC failure or brownout conditions

Auxiliary Power Tap 2 A maximum Rated 19.1 to 31.1 VDC NACs Programmed for Auxiliary Power 2 A maximum per NAC;

5 A maximum total

Special Application Appliances

Simplex horns, strobes, and combination horn/strobes and speaker/strobes (contact your Simplex product representative for compatible appliances)

Regulated 24 DC Appliances Power for other UL listed appliances; use associated external synchronization modules where required

Battery Charger Ratings for SPS and RPS (sealed lead-acid batteries)

Battery capacity range UL listed for battery charging of 6.2 Ah up to 110 Ah (batteries larger than 50 Ah require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries

Charger characteristics and performance

Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527

Environmental Operating Temperature 32° to 120°F (0° to 49° C) Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum

Additional Technical Reference

Installation Instructions 574-848 Operating Instructions 579-197

NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.

Mounting and CPU Bay Module Reference (* indicates supplied modules)

General Specifications

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. Microsoft and Windows are trademarks of Microsoft Corporation. VESDA is a trademark of Xtralis Pty Ltd. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA).

ASHRAE and BACnet are trademarks of ASHRAE, American Society of Heating, Refrigeration, and Air Conditioning Engineers.

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4100-0031-31 3/2015 www.simplex-fire.com

© 2015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Subject Data Sheet Subject Data Sheet Introducing the 4100ES S4100-0060 SafeLINC Internet Interface S4100-0062 4100ES Enclosures S4100-0037 Agent Release Applications S4100-0040 4100ES Control Panels with EPS+ Power Supplies for TrueAlert Addressable Notification S4100-0100

Fire Alarm Network Overview S4100-0055 Network Communications S4100-0056

4100ES Audio and Firefighter Phone Modules S4100-0034 Network Display Unit (NDU) S4100-0036 LED/Switch Modules & Printer S4100-0032 Addressable Device Compatibility S4090-0011 Remote Annunciators S4100-0038 Remote Battery Charger S4081-0002 MINIPLEX Transponders S4100-0035 TFX Interface Module S4100-0042 Building Network Interface (BNIC) S4100-0061 Master Clock Interface S4100-0033 InfoAlarm Command Center S4100-0045 2120 BMUX Module S4100-0048 Graphic I/O Modules S4100-0005 TrueInsight Remote Service S4100-0063

Additional 4100ES Data Sheet Reference

Emergency voice/alarm communications provide:

Alarm/evacuation signal generation with multiple built-in tones Standard or customized digital message storage and message generation Automatic or manual operation Mass Notification operation

Multiple channels are available:

Analog audio systems provide dual channel operation Digital audio systems provide up to eight channels over a single wire pair

Communications features:

Up to five supervised remote microphone inputs Spoken voice coding from the digital message player Multiple digitally recorded human voice messages Spoken WALKTEST system testing Separate evacuation, drill, and optional “All Clear” voice messages and tones Ready-to-talk microphone indicator on front panel audio control module Local panel speaker for tone/message broadcast verification MINIPLEX Voice Transponders are available for distributed audio

Amplifiers are available with analog or digital input:

Flex-35 (35 W) and Flex-50 (50 W) amplifiers provide a dual channel design with configurable operation modes 100 W primary and backup, single channel amplifiers include a built-in power supply Amplifiers are available for 25 VRMS or 70.7 VRMS output with on-board, power-limited NACs (only one voltage choice per system) Built-in Temporal Pattern horn tone provides default backup signal operation Optional modules provide power-limited NAC expansion, convert Class B NACs to Class A operation, and provide Constant Supervision Operation for Non-Alarm Audio (NAA) applications (NAA requires additional hardware, and software revision 11.08 or higher)

Firefighter telephone systems:

Master telephone can simultaneously talk with up to 6 remote telephones and can be connected as an audio input for broadcast messages Ring signal on remote firefighter telephone indicates that a call request is initiated and a hold signal indicates that a connected line has been deselected Telephone circuits are supervised for open and short circuits, too many telephones connected, and the master telephone is supervised for cord integrity Degraded mode allows remote telephones to remain connected to each other in the event of a communications loss

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

Press ACK located under flashing indicator.

Repeat operation until all events are acknowledged.

Local tone will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /

ALARMS

Fire Alarm Priority 2 Alarm

SYSTEM WARNINGS

Supervisory Trouble Alarm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building Signals System indicator flashing. Tone On. Press Alarm Silence.

How to Reset System Press System Reset.

Press Ack to silence tone device.

ZONE

SIG

AUX

FB

IO

IDNet

P

A

L

NET ADDR

0 DEL

Enter C/Exit

Fire Alarm Ack

Priority 2 Ack

Supv Ack

Trouble Ack

Alarm Silence

System Reset

Event Time

Enable On Arm

Disable Off Disarm Auto Lamp

Test

More Info

Menu

Previous

Next

4100ES Fire Alarm Control Panel with Voice and Firefighter Telephone Options

Listed to:

UL 864, Fire Detection and Control (UOJZ), and Smoke Control Service (UUKL) UL 2017, Process Management Equipment (QVAX) UL 1076, Proprietary Alarm Units-Burglar (APOU) UL 2572, Mass Notification Systems (PGWM) ULC S527, Control Units for Fire Alarm Systems

Description 4100ES Audio Systems provide voice communication, alarm tones, and/or digitally prerecorded voice messages to alert occupants of fire or other emergency situations.

Evacuation signaling may be automatically generated via alarm initiated event programs or by firefighting personnel using the operator controls.

4100U Series Products Note. The audio system modules and features listed in this data sheet are both compatible with, and listed for use with 4100U series fire alarm control panels. Contact your local Simplex® product supplier for details.

* See page 5 for product that is listed as UL or ULC and additional product listing details.

This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:251 for allowable values and/or conditions concerning material presented in this document. Accepted for use – City of New York Department of Buildings – MEA35-93E.

Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

Fire Control Panels UL, ULC, CSFM Listed; FM Approved; Addressable Fire Detection and Control MEA (NYC) Acceptance* Emergency Voice/Alarm Communications Equipment

S4100-0034-16 5/2014

Audio Controller Module Description The Audio Controller Module provides digitized alarm tones and digitally recorded voice messages and message construction, and manages both microphone inputs and other auxiliary inputs connected to the optional Auxiliary Audio Input Module. Tones and voice messages are digitally recorded and stored in the audio control module’s message memory.

Two versions are available: Analog and Digital. Systems must be either analog or digital, not intermixed. One audio control module controls the entire audio system.

Common audio control board features:

On-board digital message memory provides up to 2 minutes at normal or 1 minute at high resolution Connects to optional 4-input audio input modules (two maximum) for a total of up to 6 microphones and 11 distinct audio inputs Memory expansion is available to provide up to 8 minutes or 32 minutes at normal resolution (4 minutes or 16 minutes at high resolution) Connections for a Master Microphone and one Remote Microphone, compatible with standard or noise-canceling microphones Master telephone to audio interface connection uses the audio bay’s Power Distribution Interface Module (PDI) Local panel speaker output with on-board volume control On-board download port for message loading The microphone ready-to-talk LED is located on the front panel audio control module (see p. 4) and requires connection to a 64 LED/64 switch controller Audio risers, either digital or analog, may be directly connected to 31 remote nodes; for applications requiring audio risers to more than 31 remote nodes, alternate connection methods are available, contact your Simplex product representative for details

Analog Audio Controller Modules Analog audio control modules are for systems that require one or two simultaneous channels of audio information per the following feature summary.

Built-in 10 VRMS riser output eliminates the need for separate riser amplifiers available as Class B or Class A Messages can play on one or both risers simultaneously, with the same or a different message Analog audio controllers are for connection to analog input audio amplifiers and audio risers only On-board status LEDs assist with setup and troubleshooting

Digital Audio Controller Modules Digital audio control modules are for systems that require more than two simultaneous channels of audio information per the following feature summary.

Up to 8 channels of information at normal resolution are available (4 channels at high resolution) on one twisted wire pair Primary 1 Digital Audio Riser (DAR) output can be either wired Style 4 or Style 7; Primary 2 DAR is an identical, separate output for Style 4 connections, typically to local MINIPLEX voice transponders Digital audio…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .