About this file

This pre-solicitation notice is for a firm-fixed price construction contract to build a hospice unit at the Loch Raven Veterans Affairs Medical Center (VAMC) in Baltimore, Maryland. The project scope includes approximately 20,000 square feet of new construction and renovations to existing facilities, including a new second story addition, stair/elevator tower, and pedestrian walkway. The work is 100% set aside for service-disabled veteran-owned small businesses. The solicitation is expected to be issued on June 4, 2020 via the Government Point of Entry system. Bids are due by July 8, 2020 and contract performance must be completed within 540 days of award. The construction value is estimated between $10-20 million. Questions regarding the pre-solicitation notice should be directed via email to the specified contract specialists by July 10, 2020.

View the file

Other files

File Type Posted
36C24520B0001 0005.docx DOCX document
RFI No - 69.docx DOCX document
RFI No - 60.docx DOCX document
I103 MECH PENTHOUSE _ PED WALKWAY LEVEL - FLOOR FINISH PLANS.pdf PDF
321723 Pavement Markings (rev 8-20).pdf PDF
RFI No - 20.pdf PDF
RFI No - 26.docx DOCX document
RFI No - 61.docx DOCX document
RFI No - 59.docx DOCX document
RFI No - 1.pdf PDF
RFI No - 86.pdf PDF
RFI No - 85.pdf PDF
RFI No - 87_VA Response.pdf PDF
RFI No - 12.pdf PDF
312319 Dewatering (rev 8-20).pdf PDF
RFI No - 90.pdf PDF
RFI No - 7.pdf PDF
RFI No - 31.docx DOCX document
RFI No - 63_VA Response.docx DOCX document
RFI No - 10_VA Response.pdf PDF
331000 Water Utilities - (rev 8-20).pdf PDF
RFI No - 37.docx DOCX document
RFI No - 43.docx DOCX document
RFI No - 48.docx DOCX document
RFI No - 50.docx DOCX document
A501 INTERIOR DETAILS.pdf PDF
RFI No - 24.docx DOCX document
312000 Earthwork1 (rev 8-20).pdf PDF
RFI No - 71.docx DOCX document
RFI No - 17.pdf PDF
RFI No - 53.docx DOCX document
RFI No - 66.docx DOCX document
RFI No - 84.pdf PDF
RFI No - 76.docx DOCX document
RFI No - 67.docx DOCX document
RFI No - 45.docx DOCX document
Virtual Bid Opening Updated.pdf PDF
RFI No - 15.pdf PDF
RFI No - 78.docx DOCX document
RFI No - 13.pdf PDF
36C24520B0001 0004.docx DOCX document
A406 ENLARGED RESTROOM PLANS AND ELEVATIONS.pdf PDF
RFI No - 8.pdf PDF
078123 - Intumescent Fireproofing.pdf PDF
RFI No - 41.docx DOCX document
RFI No - 2.pdf PDF
RFI No - 54.docx DOCX document
RFI No - 52.docx DOCX document
A408 ENLARGED PLANS AND CASEWORKS ELEVATIONS.pdf PDF
RFI No - 42.docx DOCX document
Show 40 more

Latest 50 of 147 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Veterans Administration Medical Center 03-19

Baltimore, Maryland REV. 08-20

Expand Loch Raven Hospice Unit

512-532 08 80 00-1

SECTION 08 80 00

GLAZING

PART 1 - GENERAL

1.1 DESCRIPTION

This section specifies glass, related glazing materials and accessories. Glazing products specified apply to factory or field glazed items. Exterior glazing shall match existing.

1.2 RELATED WORK

A. Factory glazed by manufacturer in following units:

1. Sound resistant doors: Section 08 11 13, HOLLOW METAL DOORS AND

FRAMES, and Section 08 14 00, WOOD DOORS.

2. Mirrors: Section 10 28 00, TOILET, BATH, AND LAUNDRY ACCESSORIES.

1.3 LABELS

A. Temporary labels:

1. Provide temporary label on each light of glass identifying manufacturer or brand and glass type, quality and nominal thickness.

2. Label in accordance with NFRC (National Fenestration Rating Council) label requirements.

3. Temporary labels shall remain intact until glass is approved by

Contracting Officers Representative (COR).

B. Permanent labels:

1. Locate in corner for each pane.

2. Label in accordance with ANSI Z97.1 and SGCC (Safety Glass

Certification Council) label requirements.

a. Tempered glass.

b. Laminated glass or have certificate for panes without permanent label.

c. Organic coated glass.

1.4 PERFORMANCE REQUIREMENTS

A. Building Enclosure Vapor Retarder and Air Barrier:

1. Utilize the inner pane of multiple pane sealed units for the continuity of the air barrier and vapor retarder seal.

2. Maintain a continuous air barrier and vapor retarder throughout the glazed assembly from glass pane to heel bead of glazing sealant.

Veterans Administration Medical Center 09-17

08 80 00-2

B. Glass Thickness:

1. Select thickness of exterior glass to withstand dead loads and wind loads acting normal to plane of glass at design pressures calculated in accordance with applicable code.

2. Test in accordance with ASTM E 1300.

3. Thicknesses listed are minimum. Coordinate thicknesses with framing system manufacturers.

1.5 SUBMITTALS

A. In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND

SAMPLES.

B. Manufacturer's Certificates:

1. Certificates stating that wire glass, meets requirements for safety glazing material as specified in ANSI Z97.1.

2. Certificate on shading coefficient.

3. Certificate on "R" value when value is specified.

4. Certificate test reports confirming compliance’s with specified bullet resistive rating.

C. Warranty: Submit written guaranty, conforming to General Condition requirements, and to “Warranty of Construction” Article in this

Section.

D. Manufacturer's Literature and Data:

1. Glass, each kind required.

2. Insulating glass units.

3. Transparent (one-way vision glass) mirrors.

4. Elastic compound for metal sash glazing.

5. Glazing cushion.

6. Sealing compound.

E. Samples:

1. Size: 150 mm by 150 mm (6 inches by 6 inches).

2. Tinted glass.

F. Preconstruction Adhesion and Compatibility Test Report: Submit glazing sealant manufacturer’s test report indicating glazing sealants were tested for adhesion to glass and glazing channel substrates and for compatibility with glass and other glazing materials.

08 80 00-3

1.6 DELIVERY, STORAGE AND HANDLING

A. Delivery: Schedule delivery to coincide with glazing schedules so minimum handling of crates is required. Do not open crates except as required for inspection for shipping damage.

B. Storage: Store cases according to printed instructions on case, in areas least subject to traffic or falling objects. Keep storage area clean and dry.

C. Handling: Unpack cases following printed instructions on case. Stack individual windows on edge leaned slightly against upright supports with separators between each.

D. Protect laminated security glazing units against face and edge damage during entire sequence of fabrication, handling, and delivery to installation location. Provide protective covering on exposed faces of glazing plastics, and mark inside as "INTERIOR FACE" or "PROTECTED

FACE":

1. Treat security glazing as fragile merchandise, and packaged and shipped in export wood cases with width end in upright position and blocked together in a mass. Storage and handling shall comply with

Manufacturer's directions and as required to prevent edge damage or other damage to glazing resulting from effects of moisture, condensation, temperature changes, direct exposure to sun, other environmental conditions, and contact with chemical solvents.

2. Protect sealed-air-space insulating glazing units from exposure to abnormal pressure changes, as could result from substantial changes in altitude during delivery by air freight. Provide temporary breather tubes which do not nullify applicable warranties on hermetic seals.

3. Temporary protections: The glass front and polycarbonate back of glazing shall be temporarily protected with compatible, peelable, heat-resistant film which will be peeled for inspections and re-applied and finally removed after doors and windows are installed at destination. Since many adhesives will attack polycarbonate, the film used on exposed polycarbonate surfaces shall be approved and applied by manufacturer.

4. Edge protection: To cushion and protect glass clad, polycarbonate, and Noviflex edges from contamination or foreign matter, the four

08 80 00-4 edges shall be sealed the depth of glazing with continuous standard-thickness Santoprene tape. Alternatively, continuous channel shaped extrusion of Santoprene shall be used, with flanges extending into face sides of glazing.

5. Protect "Constant Temperature" units including every unit where glass sheet is directly laminated to or directly sealed with metal-tube type spacer bar to polycarbonate sheet, from exposures to ambient temperatures outside the range of 16 to 24 C, during the fabricating, handling, shipping, storing, installation, and subsequent protection of glazing.

1.7 PROJECT CONDITIONS

Field Measurements: Field measure openings before ordering tempered glass products. Be responsible for proper fit of field measured products.

1.8 WARRANTY

A. Warranty: Conform to terms of "Warranty of Construction", FAR clause

52.246-21, except extend warranty period for the following:

1. Bullet resistive plastic material to remain visibly clear without discoloration for 10 years.

2. Insulating glass units to remain sealed for 10 years.

3. Laminated glass units to remain laminated for 5 years.

4. Polycarbonate to remain clear and ultraviolet light stabilized for 5 years.

5. Insulating plastic to not have more than 6 percent decrease in light transmission and be ultraviolet light stabilized for 10 years.

1.9 APPLICABLE PUBLICATIONS

A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.

B. American National Standards Institute (ANSI):

Z97.1-09................Safety Glazing Material Used in Building -

Safety Performance Specifications and Methods of Test.

C. American Society for Testing and Materials (ASTM):

C542-05.................Lock-Strip Gaskets

08 80 00-5

C716-06.................Installing Lock-Strip Gaskets and Infill

Glazing Materials.

C794-10.................Adhesion-in-Peel of Elastomeric Joint Sealants

C864-05.................Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers

C920-11.................Elastomeric Joint Sealants

C964-07.................Standard Guide for Lock-Strip Gasket Glazing

C1036-06................Flat Glass

C1048-12................Heat-Treated Flat Glass-Kind HS, Kind FT Coated and Uncoated Glass.

C1376-10................Pyrolytic and Vacuum Deposition Coatings on

Flat Glass

D635-10.................Rate of Burning and/or Extent and Time of

Burning of Self-Supporting Plastic in a

Horizontal Position

D4802-10................Poly (Methyl Methacrylate) Acrylic Plastic

Sheet

E84-10..................Surface Burning Characteristics of Building

Materials

E119-10.................Standard Test Methods for Fire Test of Building

Construction and Material

E2190-10................Insulating Glass Unit

D. Commercial Item Description (CID):

A-A-59502...............Plastic Sheet, Polycarbonate

E. Code of Federal Regulations (CFR):

16 CFR 1201 - Safety Standard for Architectural Glazing Materials; 2010

F. National Fire Protection Association (NFPA):

80-13...................Fire Doors and Windows.

252-12..................Standard Method of Fire Test of Door Assemblies

257-12..................Standard on Fire Test for Window and Glass

Block Assemblies

G. National Fenestration Rating Council (NFRC)

H. Safety Glazing Certification Council (SGCC) 2012:

Certified Products Directory (Issued Semi-Annually).

I. Underwriters Laboratories, Inc. (UL):

752-11..................Bullet-Resisting Equipment.

08 80 00-6

J. Unified Facilities Criteria (UFC):

4-010-01-2012...........DOD Minimum Antiterrorism Standards for

Buildings

K. Glass Association of North America (GANA):

Glazing Manual (Latest Edition)

Sealant Manual (2009)

L. American Society of Civil Engineers (ASCE):

ASCE 7-10...............Wind Load Provisions

PART 2 - PRODUCT

2.1 GLASS

A. Use thickness stated unless specified otherwise in assemblies.

B. Clear Glass:

1. ASTM C1036, Type I, Class 1, Qualityq3.

2. Thickness, 6 mm (1/4 inch) unless indicated otherwise.

C. Tinted Heat reflective and low emissivity coated glass:

1. ASTM C1036, Type I, Class 2, Quality q3.

2. Color: To Match Existing First Floor

3. Thickness,6 mm (1/4 inch) unless indicated otherwise.

C. Clear Tempered Glass:

1. ASTM C1048, Kind FT, Condition A, Type I, Class 1, Quality q3.

2. Thickness, 6 mm (1/4 inch).

D. Tinted Tempered Glass.

1. ASTM C1048, Kind FT, Condition A, Type I, Class 2, Quality q3.

2. Color: Bronze

3. Thickness, 6 mm (1/4 inch).

2.2 COATED GLASS

A. Spandrel Glass:

1. ASTM C1048, Kind HS, Condition B, Type I.

2. Thickness, 6 mm (1/4 inch).

08 80 00-7

B. Low-E Tempered Glass:

1. ASTM C1048, Kind FT, Condition C, Type I, Class 1, Quality q3 with low emissivity pyrolytic coating having an E of 0.15.

2. Apply coating to third surface of insulating glass units.

3. Thickness, 4.8 mm (3/16 inch).

C. Ceramic Coated Spandrel Glass:

1. ASTM C1048, Kind HS, Condition B, Type I, Class 1, Quality q3 with ceramic coating applied over and fused into glass surface.

2. Pattern as indicated in drawings.

3. Apply coating to second surface.

4. Thickness, 6 mm (1/4 inch).

2.3 INSULATING GLASS UNITS

A. Provide factory fabricated, hermetically sealed glass unit consisting of two panes of glass separated by a dehydrated air space and comply with ASTM E2190.

B. Assemble units using glass types specified:

C. Sealed Edge Units (SEU):

1. Insulating Glass Unit Makeup

a. Outboard Lite

1. Glass type: Pilkington Optifloat or Equal meeting performance requirements.

2. Glass Tint: To Match Existing First Floor

3. Nominal Thickness: 6 mm (1/4”)

4. Glass Strength: (Tempered)

b. Spacer

1. Nominal Thickness: 13 mm (1/2”)

2. Gas Fill: (Argon)

c. Inboard Lite

1. Glass Type: Pilkington Energy Advantage or equal meeting performance requirements.

2. Glass Tint: Clear

3. Nominal Thickness: 6 mm (1/4”)

4. Glass Strength: (Tempered)

08 80 00-8

5. Coating Orientation: (N/A, Surface #3)

2. Performance Characteristics (Center of Glass)

a. Visible Transmittance: 42%

b. Visible Reflectance: Exterior 8%, Interior 14%

c. Winter U-factor (U-value): 0.29 degree F

d. Shading Coefficient (SC): 0.51

e. Solar heat Gain Coefficient (SHGC): 0.45

3. Glass shall be annealed, heat strengthened or tempered as required by codes, or as required to meet thermal stress and wind loads.

4. Glass heat-treated by horizontal (roller hearth) process with inherent roller wave distortion parallel to the bottom edge of the glass as installed when specified.

D. Fused Edge Units, (FEU):

1. Glass to glass sealed edges electrically fused.

2. Air space not less than 4.8 mm (3/16 inch) wide up to 6 mm (1/4 inch) wide.

3. R value not less than 1.5.

E. FEU Clear Glass.

1. Interior and exterior panes, ASTM C1036, Type I, Class 1, Quality q3, 3 mm (1/8 inch) thick.

2. Thickness, 11 mm (7/16 inch) minimum.

2.4 FIRE RESISTANT GLASS WITHOUT WIRE MESH

A. Type 1 (Transparent float glass), Class 1 (Clear).

B. Fire-protective glass products used to protect against smoke and flames only shall be rated for [20] [45] minutes as required by local building code and shall be tested in accordance with NFPA 252 (Standard Methods of Fire Tests of Door Assemblies) and NFPA 257 (Standard on Fire Test for Window and Glass Block Assemblies)

C. Fire-resistive products used to protect against smoke, flame, and the transmission of radiant heat shall be rated for [60] [90] [120] minutes and shall be tested in accordance with NFPA 252, NFPA 257, and ASTM

E119 (Standard Test Methods for Fire Tests of Building Construction and

Materials).

D. Fire-rated glass or glass assembly shall be classified by Underwriters

Laboratory (UL), Intertek Testing Services- Warnock Hersey (ITS-WHI) or any other OSHA certified testing laboratory. All glass shall bear a

08 80 00-9 permanent mark of classification in accordance with local building code.

E. Maximum size is per the manufacturer’s test agency listing for doors, transoms, side lights, borrowed lights, and windows.

F. Where safety glazing is required by local building code, fire-rated glass shall be tested in accordance with CPSC 16 CFR 1201 Category I or

II and bear a permanent mark of classification.

1. Category I products are limited to 0.84 m2 – 9 ft2 and tested to no less than 203 Nm-150 ft-lbs impact loading.

2. Category II products are greater than 0.84 m2 – 9 ft2 and tested to no less than 542 Nm-400 ft-lbs impact loading. Category II products can be used in lieu of Category I products.

2.5 LAMINATED GLASS:

A. Laminated Glass: ASTM C1172. Two or more lites of glass bonded with polyvinyl butyral, ionomeric polymer, or cast-in-place and cured-transparent-resin interlayer complying with interlayer manufacturer's written instructions.

B. Interlayer: Use min. 0.75 mm (0.030 inch) thick interlayer for vertical glazing unless otherwise indicated in construction documents.

E. Interlayer Color: Clear, unless otherwise indicated in construction documents.

2.6 GLAZING ACCESSORIES

A. As required to supplement the accessories provided with the items to be glazed and to provide a complete installation. Ferrous metal accessories exposed in the finished work shall have a finish that will not corrode or stain while in service.

B. Setting Blocks: ASTM C864:

1. Channel shape; having 6 mm (1/4 inch) internal depth.

2. Shore a hardness of 80 to 90 Durometer.

3. Block lengths: 50 mm (two inches) except 100 to 150 mm (four to six inches) for insulating glass.

4. Block width: Approximately 1.6 mm (1/16 inch) less than the full width of the rabbet.

08 80 00-10

5. Block thickness: Minimum 4.8 mm (3/16 inch). Thickness sized for rabbet depth as required.

C. Spacers: ASTM C864:

1. Channel shape having a 6 mm (1/4 inch) internal depth.

2. Flanges not less 2.4 mm (3/32 inch) thick and web 3 mm (1/8 inch) thick.

3. Lengths: One to 25 to 76 mm (one to three inches).

4. Shore a hardness of 40 to 50 Durometer.

D. Sealing Tapes:

1. Semi-solid polymeric based material exhibiting pressure-sensitive adhesion and withstanding exposure to sunlight, moisture, heat, cold, and aging.

2. Shape, size and degree of softness and strength suitable for use in glazing application to prevent water infiltration.

E. Spring Steel Spacer: Galvanized steel wire or strip designed to position glazing in channel or rabbeted sash with stops.

F. Glazing Gaskets: ASTM C864:

1. Firm dense wedge shape for locking in sash.

2. Soft, closed cell with locking key for sash key.

3. Flanges may terminate above the glazing-beads or terminate flush with top of beads.

G. Lock-Strip Glazing Gaskets: ASTM C542, shape, size, and mounting as indicated.

H. Glazing Sealants: ASTM C920, silicone neutral cure:

1. Type S.

2. Class 25

3. Grade NS.

4. Shore A hardness of 25 to 30 Durometer.

I. Structural Sealant: ASTM C920, silicone acetoxy cure:

1. Type S.

2. Class 25.

3. Grade NS.

08 80 00-11

4. Shore a hardness of 25 to 30 Durometer.

J. Neoprene, EPDM, or Vinyl Glazing Gasket: ASTM C864.

1. Channel shape; flanges may terminate above the glazing channel or flush with the top of the channel.

2. Designed for dry glazing.

K. Color:

1. Color of glazing compounds, gaskets, and sealants used for aluminum color frames shall match color of the finished aluminum and be nonstaining.

2. Color of other glazing compounds, gaskets, and sealants which will be exposed in the finished work and unpainted shall be black, gray, or neutral color.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Verification of Conditions:

1. Examine openings for glass and glazing units; determine they are proper size; plumb; square; and level before installation is started.

2. Verify that glazing openings conform with details, dimensions and tolerances indicated on manufacturer’s approved shop drawings.

B. Advise Contractor of conditions which may adversely affect glass and glazing unit installation, prior to commencement of installation: Do not proceed with installation until unsatisfactory conditions have been corrected.

C. Verify that wash down of adjacent masonry is completed prior to erection of glass and glazing units to prevent damage to glass and glazing units by cleaning materials.

3.2 PREPARATION

A. For sealant glazing, prepare glazing surfaces in accordance with GANA-

02 Sealant Manual.

B. Determine glazing unit size and edge clearances by measuring the actual unit to receive the glazing.

C. Shop fabricate and cut glass with smooth, straight edges of full size required by openings to provide GANA recommended edge clearances.

D. Verify that components used are compatible.

E. Clean and dry glazing surfaces.

08 80 00-12

F. Prime surfaces scheduled to receive sealants, as determined by preconstruction sealant-substrate testing.

3.3 INSTALLATION - GENERAL

A. Install in accordance with GANA-01 Glazing Manual and GANA-02 Sealant

Manual unless specified otherwise.

B. Glaze in accordance with recommendations of glazing and framing manufacturers, and as required to meet the Performance Test

Requirements specified in other applicable sections of specifications.

C. Set glazing without bending, twisting, or forcing of units.

D. Do not allow glass to rest on or contact any framing member.

E. Glaze doors and operable sash, in a securely fixed or closed and locked position, until sealant, glazing compound, or putty has thoroughly set.

F. Tempered Glass: Install with roller distortions in horizontal position unless otherwise directed.

G. Insulating Glass Units:

1. Glaze in compliance with glass manufacturer's written instructions.

2. When glazing gaskets are used, they shall be of sufficient size and depth to cover glass seal or metal channel frame completely.

3. Do not use putty or glazing compounds.

4. Do not grind, nip, cut, or otherwise alter edges and corners of fused glass units after shipping from factory.

5. Install with tape or gunnable sealant in wood sash.

H. Fire Resistant Glass:

1. Wire glass: Glaze in accordance with NFPA 80.

2. Other fire resistant glass: Glaze in accordance with UL design requirements.

3.5 INSTALLATION - WET/DRY METHOD (PREFORMED TAPE AND SEALANT)

A. Cut glazing tape to length and set against permanent stops, 5 mm (3/16 inch) below sight line. Seal corners by butting tape and dabbing with butyl sealant.

B. Apply heel bead of butyl sealant along intersection of permanent stop with frame ensuring full perimeter seal between glass and frame to complete the continuity of the air and vapor seal.

C. Place setting blocks at 1/4 points with edge block no more than 150 mm

(6 inches) from corners.

08 80 00-13

D. Rest glazing on setting blocks and push against tape and heel bead of sealant with sufficient pressure to achieve full contact at perimeter of pane or glass unit.

E. Install removable stops, with spacer strips inserted between glazing and applied stops, 6 mm (1/4 inch) below sight line. Place glazing tape on glazing pane or unit with tape flush with sight line.

F. Fill gap between glazing and stop with polyurethane type sealant to depth equal to bite of frame on glazing, but not more than 9 mm (3/8 inch) below sight line.

G. Apply cap bead of polyurethane/silicone type sealant along void between the stop and the glazing, to uniform line, flush with sight line. Tool or wipe sealant surface smooth.

3.6 INSTALLATION - INTERIOR WET/DRY METHOD (TAPE AND SEALANT)

A. Cut glazing tape to length and install against permanent stops, projecting 1.6 mm (1/16 inch) above sight line.

B. Place setting blocks at 1/4 points with edge block no more than 150 mm

(6 inches) from corners.

C. Rest glazing on setting blocks and push against tape to ensure full contact at perimeter of pane or unit.

D. Install removable stops, spacer shims inserted between glazing and applied stops at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.

E. Fill gaps between pane and applied stop with acrylic type sealant to depth equal to bite on glazing, to uniform and level line.

F. Trim protruding tape edge.

3.7 REPLACEMENT AND CLEANING

A. Clean new glass surfaces removing temporary labels, paint spots, and defacement after approval by Contracting Officers Representative (COR).

B. Replace cracked, broken, and imperfect glass, or glass which has been installed improperly.

C. Leave glass, putty, and other setting material in clean, whole, and acceptable condition.

3.8 PROTECTION

Protect finished surfaces from damage during erection, and after completion of work. Strippable plastic coatings on colored anodized finish are not acceptable.

08 80 00-14

3.9 GLAZING SCHEDULE

A. Fire Resistant Glass:

1. Use Fire Resistant Glass without wire mesh in all fire rated doors indicated to receive glazing.

B. Tempered Glass:

1. Install in full and half glazed doors unless indicated otherwise.

2. Install in storefront, windows, and door sidelights adjacent to doors.

3. Use clear tempered glass on interior side lights and doors, and on exterior doors and sidelights unless otherwise indicated or specified.

4. Use SEU clear tempered insulating glass on storefronts and sidelights.

5. Use SEU tinted tempered and clear tempered insulating glass on storefront and sidelights.

6. Use SEU Low E tempered and clear glass, G-41, on storefront and sidelights.

8. Use tinted tempered glass in exterior pane and clear tempered glass in interior pane unless specified otherwise of insulating glass units adjacent to door.

D. Clear Glass:

1. Interior observation windows not specified otherwise.

2. Interior pane of dual glazed windows not receiving tempered, laminated or organic coated glass, or other special glass indicated or specified.

E. Tinted Glass: Exterior pane of dual glazed windows not receiving tinted tempered glass.

F. Insulating Glass:

1. Install SEU clear tempered glass in windows, interior pane of dual glazed windows, storefronts, curtain walls and adjacent to entrances or walks.

2. Install SEU clear glass in windows, interior pane of dual glazed windows, storefronts, curtain walls and not adjacent to entrances or walks.

08 80 00-15

3. Install SEU tinted tempered and clear tempered glass in storefronts, curtain walls and adjacent to entrances or walks.

G. Spandrel Glass: Install specified spandrel glazing where indicated.

- - - E N D - - -