This document provides details for a federal construction contract opportunity to build a hospice unit at the Loch Raven Veterans Affairs Medical Center in Baltimore, Maryland. The Department of Veterans Affairs will solicit fixed-price bids to construct approximately 20,000 square feet of new buildings and associated renovations including a new second story addition, stair/elevator tower, and pedestrian walkway. The work must be completed by a service-disabled veteran-owned small business within 540 days in accordance with provided drawings and specifications. Bids are due by July 8, 2020 and contract award is restricted to eligible SDVOSBs. The construction value is estimated between $10-20 million. Interested parties should monitor the SAM.gov website for solicitation number 36C24520B0001.
View the file
Other files
Show 40 more
Latest 50 of 147 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Veterans Administration Medical Center 08-20 Baltimore, Maryland
Expand Loch Raven Hospice Unit
512-532
INTUMESCENT FIREPROOFING
07 81 23 - 1
SECTION 07 81 23
INTUMESCENT FIREPROOFING
PART 1 - GENERAL
1.1 QUALITY ASSURANCE
A. Mockups for each type of fireproofing, substrate, and finish.
1.2 PERFORMANCE REQUIREMENTS
A. Fire-Resistance Design: Tested according to ASTM E 119 or UL 263. Steel members are considered restrained. Assembly rating is 2 Hour Fire Rating.
1.3 MASTIC AND INTUMESCENT FIRE-RESISTIVE COATINGS
A. Mastic and Intumescent Fire-Resistive Coating: For exterior use.
1. Surface-Burning Characteristics: Flame-Spread Index of 25 or less and smoke-developed index of 50 or less.
2. Hardness: Not less than 67 or less, Type D durometer.
3. Finish: As selected by Architect from manufacturer's Spray-textured finish.
B. Auxiliary Materials: According to fire-resistance designs indicated.
1. Topcoat.
1.4 FIELD QUALITY CONTROL
A. Special Inspections: Contractor engaged special inspector.
- - - END - - -