36C24226Q0023_1.docx

DOCX document 688 KB Posted

Attached to
J059--BK/SA Electrical ITM Service Federal contract opportunity
Solicitation number
36C24226Q0023
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This is a Request for Quotation (RFQ) for electrical system inspection, testing, and maintenance services for the Department of Veterans Affairs at the Brooklyn VA Medical Center and St. Albans Community Living Center. The solicitation (36C24226Q0023) is a total set-aside for certified Service-Disabled Veteran-Owned Small Businesses (SDVOSB) with a base period from December 1, 2025, to November 30, 2026, and four one-year option periods through November 30, 2030. The contract covers comprehensive electrical maintenance services including inspections, testing, and maintenance of electrical equipment such as switchgear, transformers, circuit breakers, automatic transfer switches, and fifteen generators across multiple buildings.

Key requirements include performing detailed electrical system testing in compliance with NFPA and Joint Commission standards, conducting annual load bank testing for generators, infrared scanning, and providing comprehensive reporting. Contractors must have at least five years of continuous experience in electrical maintenance within healthcare or equivalent industrial settings, possess NETA or NICET certifications, and demonstrate expertise with electrical power distribution systems. Quotes are due by 4:30 PM ET on November 12, 2025, and must include a technical capability statement, pricing details, past performance information, and required representations and certifications. The estimated contract value is up to $19 million, with services to be performed at the Brooklyn and St. Albans VA facilities in New York.

View the file

Other files for this federal contract opportunity

Other files attached to J059--BK/SA Electrical ITM Service, newest first.
File Type Posted
Brooklyn Breakers .docx DOCX document
36C24226Q0023 0003.docx DOCX document
36C24226Q0023 0002.docx DOCX document
36C24226Q0023 0001.docx DOCX document
Attachment A.docx DOCX document
WD 2015-4187 Rev. 33.pdf PDF
Attachment B.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

36C24226Q0023

PAGE 1 OF

1. REQUISITION NO.

2. CONTRACT NO.

3. AWARD/EFFECTIVE DATE

4. ORDER NO.

5. SOLICITATION NUMBER

6. SOLICITATION ISSUE DATE

a. NAME

b. TELEPHONE NO. (No Collect Calls)

8. OFFER DUE DATE/LOCAL

TIME

9. ISSUED BY

CODE

10. THIS ACQUISITION IS

UNRESTRICTED OR

SET ASIDE:

% FOR:

SMALL BUSINESS

HUBZONE SMALL

BUSINESS

SERVICE-DISABLED

VETERAN-OWNED

SMALL BUSINESS

WOMEN-OWNED SMALL BUSINESS

(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED

SMALL BUSINESS PROGRAM

EDWOSB

8(A)

NAICS:

SIZE STANDARD:

11. DELIVERY FOR FOB DESTINA-

TION UNLESS BLOCK IS

MARKED

SEE SCHEDULE

12. DISCOUNT TERMS

13a. THIS CONTRACT IS A

RATED ORDER UNDER

DPAS (15 CFR 700)

13b. RATING

14. METHOD OF SOLICITATION

RFQ

IFB

RFP

15. DELIVER TO

CODE

16. ADMINISTERED BY

CODE

17a. CONTRACTOR/OFFEROR

CODE

FACILITY CODE

18a. PAYMENT WILL BE MADE BY

CODE

TELEPHONE NO.

UEI:

EFT:

PHONE:

FAX:

17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER 18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW IS CHECKED

SEE ADDENDUM

19.

20.

21.

22.

23.

24.

ITEM NO.

SCHEDULE OF SUPPLIES/SERVICES

QUANTITY

UNIT

UNIT PRICE

AMOUNT

(Use Reverse and/or Attach Additional Sheets as Necessary)

25. ACCOUNTING AND APPROPRIATION DATA

26. TOTAL AWARD AMOUNT (For Govt. Use Only) 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED.

27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA

ARE

ARE NOT ATTACHED

28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN _______________

29. AWARD OF CONTRACT: REF. ___________________________________ OFFER

COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND

DATED ________________________________. YOUR OFFER ON SOLICITATION

DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY

(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE

ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED

SET FORTH HEREIN IS ACCEPTED AS TO ITEMS:

30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER) 30b. NAME AND TITLE OF SIGNER (TYPE OR PRINT) 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (TYPE OR PRINT) 31c. DATE SIGNED

AUTHORIZED FOR LOCAL REPRODUCTION

(REV. NOV 2021)

PREVIOUS EDITION IS NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.212

7. FOR SOLICITATION

INFORMATION CALL:

STANDARD FORM 1449

SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES

OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30

36C24226Q0023 10-31-2025 Chris Weider | Christopher.Weider@va.gov 716-862-7461 x22470 11-12-2025 4:30pm

EST

36C528 Department of Veterans Affairs Network Contracting Office (NCO) 2 3495 Bailey Avenue Building 3, 2nd floor Buffalo NY 14215 X X 238210 $19 Million N/A X Department of Veterans Affairs New York Harbor Healthcare System Brooklyn and St Albans 800 Poly Place Brooklyn NY 11209 36C528 Department of Veterans Affairs Network Contracting Office (NCO) 2 3495 Bailey Avenue Building 3, 2nd floor Buffalo NY 14215

Tungsten Network https://www.tungsten-network.com/ customer-campaigns/veteransaffairs/

See CONTINUATION Page This requirement is for electrical system inspection, testing and maintenance.

Please annotate pricing in the Price/Cost Schedule.

Period of Performance:

Base: December 1, 2025 - November 30, 2026 Option 1: December 1, 2026 - November 30, 2027 Option 2: December 1, 2027 - November 30, 2028 Option 3: December 1, 2028 - November 30, 2029 Option 4: December 1, 2029 - November 30, 2030 Send quote via email to POC by 4:30pm ET, November 12, 2025.

Submission requirements are outlined in Section E.1.

POC: Chris Weider | Christopher.Weider@va.gov See CONTINUATION Page X X X

ONE

Christopher Weider Contracting Officer Table of Contents

SECTION A1
A.1 SF 1449 SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES1
SECTION B - CONTINUATION OF SF 1449 BLOCKS3
B.1 CONTRACT ADMINISTRATION DATA3
B.2 STATEMENT OF WORK4
B.3 PRICE/COST SCHEDULE18
ITEM INFORMATION18
SECTION C - CONTRACT CLAUSES53
C.1 52.212-4 CONTRACT TERMS AND CONDITIONS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (NOV 2023)53
C.2 52.217-9 OPTION TO EXTEND THE TERM OF THE CONTRACT (MAR 2000)59
C.3 SUPPLEMENTAL INSURANCE REQUIREMENTS59
C.4 VAAR 852.219-73 VA NOTICE OF TOTAL SET-ASIDE FOR CERTIFIED SERVICE-DISABLED VETERAN-OWNED SMALL BUSINESSES (JAN 2023) (DEVIATION)59
C.5 VAAR 852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING—CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION (JAN 2023) (DEVIATION)62
C.6 VAAR 852.242-71 ADMINISTRATIVE CONTRACTING OFFICER (OCT 2020)64
C.7 52.252-2 CLAUSES INCORPORATED BY REFERENCE (FEB 1998)64
C.8 52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR EXECUTIVE ORDERS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (OCT 2025) (DEVIATION FEB 2025)65
SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS74
SECTION E - SOLICITATION PROVISIONS75
E.1 52.212-1 INSTRUCTIONS TO OFFERORS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (SEP 2023)75
E.2 52.204-24 REPRESENTATION REGARDING CERTAIN TELECOMMUNICATIONS AND VIDEO SURVEILLANCE SERVICES OR EQUIPMENT (NOV 2021)79
E.3 52.209-7 INFORMATION REGARDING RESPONSIBILITY MATTERS (OCT 2018)81
E.4 52.233-2 SERVICE OF PROTEST (SEP 2006)83
E.5 52.252-1 SOLICITATION PROVISIONS INCORPORATED BY REFERENCE (FEB 1998)83
E.6 52.212-2 EVALUATION—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (NOV 2021)84
E.7 52.212-3 OFFEROR REPRESENTATIONS AND CERTIFICATIONS—COMMERCIAL PRODUCTS AND COMMERCIAL SERVICES (OCT 2025) (DEVIATION FEB 2025)85

SECTION B - CONTINUATION OF SF 1449 BLOCKS

B.1 CONTRACT ADMINISTRATION DATA

1. Contract Administration: All contract administration matters will be handled by the following individuals:

a. CONTRACTOR:

b. GOVERNMENT: Contracting Officer 36C242 Chris Weider Department of Veterans Affairs Network Contracting Office (NCO) 2 3495 Bailey Avenue Building 3, 2nd floor Buffalo NY 14215

2. CONTRACTOR REMITTANCE ADDRESS: All payments by the Government to the contractor will be made in accordance with:

[X]
52.232-33, Payment by Electronic Funds Transfer—System For Award Management, or
[]
52.232-36, Payment by Third Party

3. INVOICES: Invoices shall be submitted in arrears:

a. Quarterly[]
b. Semi-Annually[]
c. Other[X] Per Schedule

4. GOVERNMENT INVOICE ADDRESS: All Invoices from the contractor shall be submitted electronically in accordance with VAAR Clause 852.232-72 Electronic Submission of Payment Requests.

Tungsten Network https://www.tungsten-network.com/customer-campaigns/veteransaffairs/ ACKNOWLEDGMENT OF AMENDMENTS: The offeror acknowledges receipt of amendments to the Solicitation numbered and dated as follows:

AMENDMENT NO
DATE

36C24226Q0023

Page 1 of Page 1 of

B.2 STATEMENT OF WORK

1. Title: Electrical System Inspection, Testing and Maintenance

2. Background The Department of Veterans Affairs, New York Harbor Healthcare System Engineering Service at the Brooklyn and St. Albans healthcare facilities are required to perform regular maintenance on their electrical equipment including, but not limited to, transfer switches and fifteen (15) generators (including load bank testing). The Brooklyn campus and St. Albans CLC generators are designed to provide back-up electrical power during an unforeseen outage of the primary electrical source and minimize additional disruptions to critical services.

3. Introduction:

A. The VA is dedicated to optimizing its physical environment and ensuring the seamless operation of our medical facility. A major objective is the prevention of engineering related safety hazards. This project details requirements to support the mission above.

B. This Statement of Work (SOW) describes the requirements for the inspection, testing, maintenance, and/or calibration of the Electrical Power Distribution System at the Brooklyn VAMC, and St. Albans CLC.

4. Equipment A. Brooklyn electrical equipment (including transformers and ATS) - Attachment A B. St Albans electrical equipment (including transformers and ATS) - Attachment B C. Generators – See Section 11.C.

5. Contractor Qualifications:

A. The Contractor shall have resources (employees, supervisors, material and equipment) explicitly dedicated to the performance of this contract. A point of contact shall be on site during the full performance of each task.

B. Contractors shall be experienced electrical contractors, having properly trained, certified and licensed permanent staff to perform the proposed work. Electrical contracting (i.e. the construction, repair, testing and maintenance of industrial and commercial electrical distribution systems) shall be the primary interest/specialty of the Contractor’s business.

C. Contractor personnel doing testing shall be certified by the International Electrical Testing Association (NETA) or NICET as Certified Technicians with no exceptions.

D. Contractors shall have technical training and a minimum of five (5) continuous years of experience working in maintenance, inspection, and testing of the relevant electrical power distribution systems and related components in a healthcare setting or equivalent in industrial, educational, and commercial facilities. Electrical components on which the Contractors shall have experience include but are not be limited to switchboards & switchgear (low and medium voltage); generators; low voltage controls; motor control centers, wiring, transformers, meters, and other electrical appurtenances.

E. The Contractor shall have technical training and a track record of proven experience with generator operations, load banking and annual service for a minimum of five (5) continuous years.

F. Contractors shall have ready access to the latest versions of the following references:

1. NFPA 70, National Electrical Code

2. NFPA 70B, Recommended Practice for Electrical Equipment Maintenance

3. NFPA 70E, Standard for Electrical Safety for the Workplace

4. NFPA 110, Standard for Emergency and Standby Power System

5. OSHA Standard 29 CFR 1910, Subparts I & S

6. International Electrical Testing Association, Inc. (NETA) – Maintenance and Testing Specifications

7. VHA Directive 1028, Electrical Power Distribution System G. Contractors shall have and provide all necessary tools, equipment, and Personal Protective Equipment (PPE) to perform the work safely, effectively, and timely.

1. Tools, equipment, and PPE shall comply with the requirements of OSHA Standard 29 CFR 1910, Subpart I, and NFPA 70E.

2. Prior to initiating work, Contractor shall provide documentation that all instruments, test equipment, tools and PPE have current calibration.

3. Dated calibration labels shall be visible on all instruments, test equipment, tools, and PPE as appropriate.

6. General Administration:

A. If the contractor requires a specific source of power, for any test equipment, details of power requirements must be submitted with solicitation response.

B. The Contractor Program Manager shall be required to visit the site at least twice annually and meet with the COR or their representative(s) to discuss and develop mutual understanding relative to work status, safety, quality, and other contractual requirements. This requirement can be cancelled at the discretion of the COR. The Government reserves the right to schedule meetings to discuss or resolve issues/problems it deems to be critical.

7. Safety A. Contractors shall have safety training, either on-the-job or class-room type. Training certifications shall be submitted to the COR prior to work. If no training certifications are available, the contractor’s employer shall certify that he/she has met this requirement in writing and submit it to the COR for approval prior to work.

1. OSHA Standard 29 Code of Federal Regulations (CFR) 1910 Subpart S – Electrical

2. NFPA 70E – Standard for Electrical Safety in the Workplace.

3. Occupational Safety & Health Administration (OSHA) approved 10-hour construction safety training.

8. Period of Performance Performance shall be for a period of one year with four option years.

Base Period:December 1, 2025 – November 30, 2026
Option Period 1:December 1, 2026 – November 30, 2027
Option Period 2:December 1, 2027 – November 30, 2028
Option Period 3:December 1, 2028 – November 30, 2029
Option Period 4:December 1, 2029 – November 30, 2030

9. Schedule A. Unless otherwise noted, regular working hours are defined as Monday-Friday between 7:00AM-3:30PM.

B. See Requirements sections below for requirement specific scheduling considerations.

C. Services shall not be required during federal holidays. Federal holidays include any holiday declared by the President of the United States, including:

Page 1 of New Year’s Day Martin Luther King, Jr. Day Washington’s Birthday Memorial Day Juneteenth Independence Day Labor Day Columbus Day Veterans Day Thanksgiving Day Christmas Day

As well as any other day declared as a holiday by the President of the United States

10. Place of Performance:

Department of Veterans Affairs New York Harbor Healthcare System – Brooklyn Campus 800 Poly Place Brooklyn, NY 11209

Department of Veterans Affairs New York Harbor Healthcare System – St. Albans Community Living Center 179-00 Linden Blvd.

Jamaica, NY 11425

11. Requirements A. Electrical Equipment Inspection, Testing and Maintenance

1. Testing shall be performed in compliance with manufacturers’ recommendations and per the applicable procedures as outlined in the latest edition of the ANSI/NETA Standard for Maintenance Testing Specifications and/or as noted in this document.

2. Contractor shall provide maintenance of low voltage air circuit breakers. Testing and maintenance of the breakers is required under this contract to include infrared scanning to detect any electrical deficiencies.

3. Contractor shall affix label on all equipment tested, documenting at a minimum the date of test, equipment tested, name of testing firm, and name or initials of testing technician.

4. Unless specified elsewhere in this document, any test labeled as “optional” by NETA is not required.

5. Visually inspect for sign(s) of overheating, misaligned contacts, damaged insulation, or loose lugs.

6. Equipment shall be cleaned of accumulated dust and dirt.

7. Contractor shall use a vacuum cleaner to remove large debris; compressed air is not to be used for this purpose.

8. Lubricate all moving parts as recommended by the manufacturer with manufacturer approved lubricants.

9. Contractor shall replace the backup battery and switchgear PLC battery, types ½ AA 3.6v Lithium, once per 2 calendar years.

10. Testing shall be completed in the following sequential phases:

a. Infra-Red Scanning/Thermography Survey

i. Scanning shall be performed on the electrical equipment, automatic transfer switches and generators. Contractor shall advise the facility in advance where and if panel covers need to be removed.

ii. Contractor shall use an infra-red scanning camera to detect hot spots in the emergency power distribution system. The objective of this work is to detect any loose, broken, or corroded connections in the system.

iii. Problem connections shall be replaced with new connectors, and/or tightened with torque wrench to meet the equipment manufacturers’ specifications. This work should be done first before any of the hands-on testing is conducted.

iv. Contractor shall provide a thermographic survey report as specified in ANSI/NETA MTS.

v. Note that since this work item must be done while the electrical power distribution system is energized, appropriate safety precautions must be taken before, during and after scanning the system.

vi. Emergency side of transfer switches, emergency paralleling switchgear, emergency busways and emergency generator breakers must be scanned during regularly scheduled generator tests. (second Thursday of each month between 4:00AM and 7:00AM for A & B board generators. From 9:00AM to 10:00AM for Building 14 generator.)

b. Visual inspection, physical maintenance, mechanical and electrical testing of all electrical power equipment, in accordance with NFPA and Joint Commission requirements.

11. Dry Type Transformers shall be cleaned exteriorly and inspected for signs of overheating with infrared thermal detecting equipment. No other maintenance is required.

12. Switchgear and Switchboard Assemblies (Conducted Year 1 & 4 of this contract)

a. Visual and Mechanical Inspection

i. Inspect and note the general condition of each section and document equipment nameplate information.

ii. Inspect physical and mechanical condition.

iii. Inspect anchorage, alignment, grounding, and required area clearances.

iv. Verify the unit is clean.

b. Electrical Tests

i. Perform insulation-resistance tests on each bus section, phase-to-phase and phase-to-ground.

ii. Perform a dielectric withstand voltage test (Hipot Test) on each bus section.

iii. Perform secondary current-injection tests on the entire current circuit in each section of switchgear.

iv. Perform system function test.

v. Verify Operation of cubicle switchgear/switchboard space heaters.

vi. Provide service on switchgear battery bank per NETA 7.18.1.2, including optional load test per 7.18.1.2.B.5

vii. Test breakers using secondary injection utilizing the appropriate EATON test kit. Note, that EATON might be considered proprietary by the manufacturer and that test kit and service might need to be supplied from an authorized service technician.

Drawing E-304 Switchgear A & B, 480V, 4000A EATON CB.

Drawout EATON Circuit Breaker, 17 CB for SWGR-A, 20 CB for SWGR-B (1)-double ended incoming switchgear lineup with 37 Drawout EATON breakers (incl mains and tie).

Direct-Current Systems: (Main Primary Switchgear)

13. Transformers, Dry Type, Air-Cooled, Large (Conducted Year 1 & 4 of this contract)

a. Visual and Mechanical Inspection

i. Verify and document equipment nameplate data.

ii. Inspect physical and mechanical condition.

iii. Verify anchorage and alignment.

iv. Verify unit is clean.

v. Verify that as-left tap connections are specified.

vi. Verify presence of surge arresters.

vii. Verify that cooling fans operate, and fan motors have the correct overcurrent protection.

viii. Inspect bolted electrical connections for high resistance using a low- resistance ohmmeter

b. Electrical Tests

i. Perform an insulation resistance test on each winding and winding to ground.

ii. Verify correct secondary voltage phase-to-phase and phase-to-neutral after energization and prior to loading.

iii. Perform resistance measurements through bolted connections with a low- resistance ohmmeter.

iv. Perform a turns-ratio test at all tap positions.

v. Perform an excitation-current test on each phase.

vi. Measure core insulation resistance at 500 volts dc if the core is insulated and the core ground strap is removable.

vii. Test surge arresters in accordance with the "Surge Arresters" Testing Section.

14. Three-year Circuit Breaker Maintenance in compliance with NETA regulations, per specific circuit breaker type.

(Conducted Year 1 & 4 of this contract)

a. Document equipment nameplate data.

b. Inspect physical and mechanical condition.

c. Coordinate phased shutdown for each main breaker.

d. Rack out main breakers, individually, and clean and apply lubrication to contacts.

e. Operate circuit breaker to ensure smooth operation.

f. Replace the main breaker if defective, with a spare that the facility should have on hand.

15. Circuit Breaker, Medium-Voltage (Conducted Year 2, 3 & 5 of this contract)

a. Visual and Mechanical Inspection

i. Document equipment nameplate data.

ii. Inspect physical and mechanical condition

iii. Verify anchorage and alignment.

iv. Verify unit is clean, arc chutes are intact, and appropriate lubrication of contacts.

v. Manually close/open breaker to check for binding, friction, contact alignment, and penetration.

b. Electrical Tests

i. Perform an insulation resistance test on each pole to ground, between poles and across the open poles.

ii. Perform a contact resistance test on each pole in the closed position.

iii. Perform manual operation checks: manual tripping, electrically tripping, and operating protective relay.

iv. Perform dielectric withstand voltage test (high potential test) on each vacuum interrupter.

16. Circuit Breakers, Air, Low-Voltage Power (Conducted Year 2, 3 & 5 of this contract)

a. Visual and Mechanical Inspection

i. Document equipment nameplate data.

ii. Inspect physical and mechanical condition

iii. Verify anchorage and alignment.

iv. Verify unit is clean and appropriate lubrication of contacts.

v. Operate circuit breaker to ensure smooth operation.

b. Electrical Tests

i. Perform an insulation resistance test on each pole to ground, between poles and across the open poles.

ii. Perform a contact resistance test on each pole in the closed position.

iii. Test functions of the trip unit by means of primary current injection testing.

17. Switches, Air, Medium-Voltage, Metal Enclosed (Conducted Annually)

a. Visual and Mechanical Inspection

i. Verify and document equipment nameplate data.

ii. Inspect physical and mechanical condition

iii. Verify anchorage and alignment.

iv. Verify unit is clean and appropriate lubrication of contacts.

v. Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.

b. Electrical Tests

i. Perform contact resistance across each switchblade and fuse holder.

ii. Perform insulation-resistance tests on each pole, phase-to-phase and phase- to-ground.

iii. Perform a dielectric withstand voltage test on each pole.

18. Circuit Breakers, Air, Insulated-Case/Molded-Case (Conducted Year 2, 3 & 5 of this contract)

a. Visual and Mechanical Inspection

i. Verify and document equipment nameplate data.

ii. Inspect physical and mechanical condition.

iii. Verify anchorage and alignment.

iv. Verify unit is clean and appropriate lubrication of contacts.

v. Operate circuit breaker to ensure smooth operation.

b. Electrical Tests

i. Perform an insulation resistance test on each pole to ground, between poles and across the open poles.

ii. Perform a contact resistance test on each pole in the closed position.

iii. Test functions of the trip unit by means of secondary current injection testing.

19. Protective Relays, microprocessor-based (Conducted Annually)

a. Visual and Mechanical Inspection

i. Verify and document equipment nameplate data.

ii. Inspect physical and mechanical condition.

iii. Verify unit is clean.

iv. Check tightness of connections.

b. Electrical Tests

i. Perform an insulation resistance test on each phase to ground and between phases.

ii. Apply voltage or current to all analog inputs and verify correct registration of the relay meter.

iii. Perform mechanical and functional operation checks.

iv. Perform inspection and calibration of the protective relays in accordance with manufacturer recommendations.

v. Verify the protective relays trip their associated main circuit breaker.

20. Schedule for Electrical Equipment Inspection, Testing and Maintenance

a. Contractor shall provide a proposed schedule with their quote. The schedule shall be in the form of a progress chart of suitable scale to indicate the work scheduled for completion. Show individual phases and duration of each. The proposed schedule shall be reviewed by the COR and any required adjustments to the schedule shall be incorporated by the Contractor.

b. Contractor shall start and finish at one site, prior to moving on to the next site.

c. Contractor shall submit work plans and/or check lists of the testing to be performed prior to start of work.

d. All outages shall be scheduled in advance. Outages will be scheduled only at night and/or on weekends unless noted elsewhere in this document. Contractor shall verify all scheduled shutdowns and testing with the COR, who will verify all scheduled times in writing.

e. Complete Shutdown on switchgear must be approved and coordinated by Engineering. The left side of switchgear can be shut down one evening (if coordinated w/ Fire Pump Xfmr shutdown). The right side of the switchgear can be shut down during a separate evening.

21. Reporting for Electrical Equipment Inspection, Testing and Maintenance:

a. Contractors shall report deficiencies that are deemed critical or catastrophic immediately to the COR.

b. All work performed shall be fully documented by the Contractor. A complete written report of the work performed shall be provided to the VA within seven (7) days of completion. Contractor shall submit two (2) hard copies of the written report, and two (2) CD-ROM or DVD of the electronic version of the report in Microsoft Word or PDF format to the COR. All reference materials shall be included in the electronic version of the report, either through scanning or other means of electronic text import methods.

c. Information shown in the report shall include:

i. Company’s name, addresses, telephone, & fax numbers.

ii. Name and signature of contractor(s) that performed the work

iii. VA Project Number, name and number of VA COR.

iv. Date and time of work.

v. Copies of contractors’ valid licenses, professional and training certificates.

vi. Descriptions and model number of specialized tools and equipment used such as torque wrench or infra-red scanning camera.

vii. Location, Type, Name, and nameplate information of electrical equipment to be maintained and tested.

viii. Descriptions of work items.

ix. Test data.

x. Reference materials such as equipment manufacturer’s specifications, coordination study, etc.

xi. Remarks on the condition of electrical equipment. List all deficiencies, if any.

xii. Recommended corrective actions, if any.

d. All work items, definitions, and references shall comply with the latest edition of the NETA – Maintenance Testing Specifications (MTS) and with the VHA Directive, Electrical Power Distribution System.

22. Reference Images

a. Low Voltage Motor Control Center, General Electric, 480V, 1200A

b. Fire Pump Transformer

B. Maintenance of Automatic Transfer Switch (ATS) (Conducted annually over 1 weekend)

1. Infra-red scanning shall be performed on all automatic transfer switches.

2. Thermal scan for ATS-G1 and breaker injection testing, GE Switch 800V 1200A.

3. Generator ATS and Main Breaker, Building 4 – Generator Room

C. Generator Service and Annual Testing

1. All generator service will be performed in compliance with Joint Commission (JTC) and National Fire Protection Association (NFPA) 110 requirements.

2. Annual service for generators (load bank, fluids, filters, leak checks, belt checks, etc).

3. The Contractor shall provide qualified maintenance labor, equipment, tools, materials, parts, supplies, transportation, supervision, any other items, and non-personal services deemed necessary to perform load bank testing services on the following fifteen generators:

BROOKLYN CAMPUS

Equipment
Location
Make/Rating
Model
Serial No.
PM

Frequency

Outside Bldg 1 Switchgear Room
Main Generator Caterpillar 2025KW
3516B
YAT00416
Annual
Bldg. 4 (Engineering)
A-Board Generator Caterpillar 2200KW

3516B

1HN00551

Annual

Outpatient Clinic
OPC Generator
Emergency
Generator
Caterpillar
3508
23Z06777
Annual

Diesel

600KW

Generators
Building 14 (Data Center)
Bldg. 14 Data Center Generator Caterpillar 400KW

CER00472

Bldg. 13 Critical Care

Building 13
Generator MTU

Onsite 6R1600

DS250

16301004459
Annual

Energy 250KW

ST ALBANS CLC

Equipment
Location
Make
Model
Serial No.
PM

Frequency

Emergency Diesel Generators Bldg. 64 Boiler Plant Upper Level

Caterpillar 300KW

C9

CAT000C9E NGP00992

Bldg. 64 Boiler Plant Lower Level
Caterpillar 1000KW
C32
JSJ03348
Annual
Bldg. 174 (serves Bldg. 173 - Laundry)
Caterpillar 750KW
C27
2A300225
Annual

Bldg. 167 (serves Bldgs. 85-87)

Caterpillar 150KW
D150-10
CAT00C71LL 7C00429
Annual

Bldg. 88 (serves Commissary)

Caterpillar 500KW

C15

CAT00C15K NAP0599

Bldg. 88 (serves Domiciliary area)

Caterpillar 200KW

D200-2

CAT00C71CE TG00540

Bldg. 89 Basement
Caterpillar 150KW
D150-10
CAT00C71V L7C00430
Annual

Bldg. 168 (serves Bldgs. 91-93)

Caterpillar 150KW
D150-10
CAT00C71A L7C00428
Annual
Emergency Gas Generators
Guard Shack (Police)
Caterpillar 150KW
DG 30-2
CAT00G30A NB W00138
Annual
Pump Station
Caterpillar 300KW
G300LG 6
GXJ04856- OLY00000
Annual

4. Generator Service and Testing Tasks:

a. The Annual load banking shall meet the Joint Commission’s requirements, tested as follows:

i. 30% of nameplate rating for 2 hours, followed by

ii. 50% of nameplate rating for 1 hour, followed by

iii. 75% of nameplate ratings for 1 hour, plus warm up and cool down time for a total continuous run of 4 hours.

b. Annual oil quality testing is required.

5. General Requirements for Generator Service and Testing:

a. A post-award site visit will be required to determine parking, pathways, and proper connections to the generator units.

b. The Contractor will be required to furnish the load bank and make the necessary cable connections from the generator to the load bank. This may require parallel runs of cabling. In some locations, this may require barricades, safety cones or both.

c. Prior to starting the generators, Contractor shall perform a pre-run inspection to include checking the oil level, coolant level and a visual inspection of the motor/generator.

d. The work performed on generators shall not interrupt any power to the buildings identified in this Statement of Work.

6. Schedule for Generator Service and Testing:

a. Work shall be conducted on weekdays (Monday through Friday), between 6:00 a.m. to 4:00p.m. Work shall not occur on Government holidays.

7. Reporting for Generator Service and Testing:

a. Contractor shall provide a report, to the COR, that details each generator run.

b. At 15-minute intervals, the following readings Shall be recorded:

iv. Lube Oil Pressure

v. Water Temperature

vi. Exhaust Temperature

vii. Amperes

viii. Volts

ix. Frequency

x. Coolant Temperature

xi. Power Factor

xii. Ambient Temperature

xiii. Load Percentage

c. The report shall contain certification statements that each generator was load bank tested in accordance with manufacturer’s requirements.

d. The report shall be provided in paper and electronic pdf form.

8. Acceptance of Generator Service and Testing:

a. VA personnel and Contractor personnel shall inspect the generators prior to the Contractor personnel leaving the facility. No invoices will be processed for payment prior to the completion of the POC inspection.

b. The Contractor shall provide a complete written report of the load banking for each generator. The information in the report shall have the following data:

i. Company’s name, address, telephone number and fax number.

ii. Name and signature of Contractors who performed the load bank.

iii. VA purchase order number or contract number.

iv. Date and time of work.

v. Generator building number.

vi. Generator model, Engine model, Nameplate rating.

vii. The fifteen-minute interval log that was recorded during the load bank.

viii. Description of generator condition and any deficiencies, if any.

12. Temporary Power Generation A. Temporary power generation services may be necessary to accomplish certain maintenance. Such temporary services will be coordinated with the COR and will be accomplished using methods to avoid service interruptions, where possible, or to minimize system downtime where such interruptions of service are unavoidable.

B. Temporary power generation services shall be funded only upon a written contract modification from the CO.

13. Corrective Maintenance C. The Contractor shall immediately notify the COR of any repairs deemed necessary that are not included in Section 11, above. If requested, the contractor shall provide a repair quote within 10 calendar days that itemizes parts and labor hours. The Government will review the recommended repairs and decide on a timeline and mechanism for completing the repair.

D. Corrective maintenance/repairs required for equipment to meet the regulated limits and/or standards (NFPA, NETA, VHA Directives) may be conducted only after a written contract modification is issued by the CO.

E. One-time repairs that exceed $2,000.00 and require 32 hours or more of on-site work to complete shall be covered under the Davis Bacon Act (DBA) instead of the Service Contract Act (SCA). The DBA repair(s) shall be subject to applicable construction clauses and DBA wage determinations which will be provided by the CO.

14. Warranty Enforcement.

A. The on-site COR shall be responsible for tracking and Contractor compliance with manufacturers and contract warranties and shall maintain on-site records of equipment bearing warranties in addition to ensuring the Contractor provides fully completed worksheets to the facility management. The Contractor will annotate equipment O&M records showing warranted items and warranty expiration dates on all equipment. The Contractor shall provide supporting documentation for any warranty claims to the on-site COR. The Government will provide the Contractor with all existing warranty documentation at the start of the purchase order.

B. Warranty Service Response. The Contractor shall normally conduct first look, with response based on the “Response and Completion” Table below, for all infrastructure systems under warranty, without voiding the warranty. The Contractor shall utilize a warranty response priority system for bringing the appropriate warranty outside Contractor (Manufacturer or their qualified warranty responder) based on the priority system below.

a. Priority Code 1. Emergency Warranty Response Required.

i. The facility maintenance Contractor shall determine the EMERGENCY nature, based on criteria noted in the “Response Definitions” table below, of the warranty service call, with confirmation by the on-site COR, where the warranty outside Contractor shall respond on-site within 4 hours to conduct evaluation and determine course of action and initiate work within 2 hours following the on-site response time.

ii. Work shall continue until the problem is repaired/ resolved.

b. Priority Code 2. Urgent Warranty Response Required.

i. The facility maintenance Contractor shall determine the URGENT nature, based on criteria noted in the “Response Definitions” table below, of the warranty service call, with confirmation by the on-site COR, where the warranty outside Contractor shall respond on-site within 8 hours to conduct evaluation and determine course of action and initiate work within 2 hours following the on-site response time. Work shall continue until the problem is repaired/ resolved.

c. Priority Code 3. Routine Warranty Response Required.

i. The facility maintenance Contractor shall determine the ROUTINE nature, based on criteria noted in the “Response Definitions” table, of the warranty service call, with confirmation by the on-site COR, where the warranty outside Contractor shall respond on-site within 5 days to conduct evaluation and determine course of action and initiate work within 2 hours following the on-site response time. Work shall continue until the problem is repaired/ resolved.

Response and completion times will be required as follows:

A.

Classification
Normal Duty Hours
Other Than Normal Duty Hours
Response time
Completion
Response Time
Completion
Emergency
4 hours
Continuous Until Safe / Complete
5 hours
Continuous Until Safe / Complete
Urgent
8 hours
Downgrade to Routine
10 hours
Downgrade to Routine
Routine
5 Days
30 Calendar Days
5 Days
30 Calendar Days

15. Expired Equipment:

When equipment surpasses life expectancy and is determined to no longer be economically repairable, Contractors shall notify the CO and COR. The Government retains the right to decide whether to replace the equipment or keep it in service. If the COR determines that equipment is to be replaced, COR and the CO will review and decide on the appropriate timeline and mechanism for replacing the equipment. In the event the facility cannot or does not replace identified equipment, coverage for that equipment will cease and contract pricing will be reduced accordingly. Note: the contracting officer shall make the final scope determination. As this is a maintenance contract, replacements should be procured separately and competitively.

B.3 PRICE/COST SCHEDULE

ITEM INFORMATION

ITEM NUMBER
DESCRIPTION OF SUPPLIES/SERVICES
QUANTITY
UNIT
UNIT PRICE
AMOUNT

0.00

__________________
__________________

Brooklyn Electrical Equipment Inspection, Testing and Maintenance Contract Period: Base POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components CLIN has no set price (NSP). Price each SLIN.

0001AA

1.00
JB
__________________
__________________

Switchgear and Switchboard Assemblies

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0001AB

1.00
JB
__________________
__________________

Transformers, Dry Type, Air-Cooled, Large

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0001AC

1.00
JB
__________________
__________________

Three-year Circuit Breaker Maintenance

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0001AD

1.00
JB
__________________
__________________

Switches, Air, Medium-Voltage, Metal Enclosed

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0001AE

1.00
JB
__________________
__________________

Protective Relays

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0.00

__________________
__________________

St Albans Electrical Equipment Inspection, Testing and Maintenance

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0002AA

1.00
JB
__________________
__________________

Switchgear and Switchboard Assemblies

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0002AB

1.00
JB
__________________
__________________

Transformers, Dry Type, Air-Cooled, Large

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0002AC

1.00
JB
__________________
__________________

Three-year Circuit Breaker Maintenance

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0002AD

1.00
JB
__________________
__________________

Switches, Air, Medium-Voltage, Metal Enclosed

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0002AE

1.00
JB
__________________
__________________

Protective Relays

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1.00
JB
__________________
__________________

Brooklyn Automatic Transfer Switch Maintenance

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1.00
JB
__________________
__________________

St Albans Automatic Transfer Switch Maintenance

POP Begin: 12-01-2025 POP End: 11-30-2026

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0.00

__________________
__________________

Brooklyn Generator Service and Annual Testing

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0005AA

1.00
JB
__________________
__________________

Main Generator Caterpillar 2025KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model 3516B SN YAT00416

0005AB

1.00
JB
__________________
__________________

A-Board Generator Caterpillar 2200KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model 3516B SN 1HN00551

0005AC

1.00
JB
__________________
__________________

OPC Generator Caterpillar 600KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model 3508 SN 23Z06777

0005AD

1.00
JB
__________________
__________________

Bldg. 14 Data Center Generator Caterpillar 400KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model 3456 SN CER00472

0005AE

1.00
JB
__________________
__________________

Bldg. 13 Critical Care Generator MTU Onsite Energy 250KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model 6R1600 DS250 SN 16301004459

0.00

__________________
__________________

St Albans Generator Service and Annual Testing

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0006AA

1.00
JB
__________________
__________________

Bldg. 64 Boiler Plant Caterpillar 300KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model C9 SN CAT000C9E NGP00992

0006AB

1.00
JB
__________________
__________________

Bldg. 64 Boiler Plant Caterpillar 1000KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model C32 SN JSJ03348

0006AC

1.00
JB
__________________
__________________

Bldg. 174 Caterpillar 750KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model C27 SN 2A300225

0006AD

1.00
JB
__________________
__________________

Bldg. 167 Caterpillar 150KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model D150-10 SN CAT00C71LL 7C00429

0006AE

1.00
JB
__________________
__________________

Bldg. 88 Caterpillar 500KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model C15 SN CAT00C15K NAP0599

0006AF

1.00
JB
__________________
__________________

Bldg. 88 Caterpillar 200KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model D200-2 SN CAT00C71CE TG00540

0006AG

1.00
JB
__________________
__________________

Bldg. 89 Basement Caterpillar 150KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model D150-10 SN CAT00C71V L7C00430

0006AH

1.00
JB
__________________
__________________

Bldg. 168 Caterpillar 150KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model D150-10 SN CAT00C71A L7C00428

0006AI

1.00
JB
__________________
__________________

Guard Shack Caterpillar 150KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model DG 30-2 SN CAT00G30A NB W00138

0006AJ

1.00
JB
__________________
__________________

Pump Station Caterpillar 300KW

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Model G300LG 6 SN GXJ04856- OLY00000

1.00
HR
__________________
__________________

Corrective Maintenance/Repair services hourly rate - Electrical Equipment and ATS

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components Only upon approved contract modification by CO

1.00
HR
__________________
__________________

Corrective Maintenance/Repair services hourly rate - Generators

POP Begin: 12-01-2025 POP End: 11-30-2026 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0.00

__________________
__________________

Brooklyn Electrical Equipment Inspection, Testing and Maintenance Contract Period: Option 1 POP Begin: 12-01-2026 POP End: 11-30-2027 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1001AA

1.00
JB
__________________
__________________

Circuit Breaker, Medium-Voltage

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1001AB

1.00
JB
__________________
__________________

Circuit Breakers, Air, Low-Voltage Power

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1001AC

1.00
JB
__________________
__________________

Switches, Air, Medium-Voltage, Metal Enclosed

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1001AD

1.00
JB
__________________
__________________

Circuit Breakers, Air, Insulated-Case/Molded-Case

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1001AE

1.00
JB
__________________
__________________

Protective Relays

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

0.00

__________________
__________________

St Albans Electrical Equipment Inspection, Testing and Maintenance

POP Begin: 12-01-2026 POP End: 11-30-2027 PRINCIPAL NAICS CODE: 238210 - Electrical Contractors and Other Wiring Installation Contractors PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1002AA

1.00
JB
__________________
__________________

Circuit Breaker, Medium-Voltage

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1002AB

1.00
JB
__________________
__________________

Circuit Breakers, Air, Low-Voltage Power

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1002AC

1.00
JB
__________________
__________________

Switches, Air, Medium-Voltage, Metal Enclosed

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1002AD

1.00
JB
__________________
__________________

Circuit Breakers, Air, Insulated-Case/Molded-Case

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment - Electrical and Electronic Equipment Components

1002AE

1.00
JB
__________________
__________________

Protective Relays

POP Begin: 12-01-2026 POP End: 11-30-2027

PRODUCT/SERVICE CODE: J059 - Maintenance, Repair, and Rebuilding of Equipment -…

This is the start of the file's text. The full file is on GovTribe.