This document is a technical specification file for Air Handling Unit 16 (AHU16), detailing existing equipment and components required for a facility's HVAC system.
The AHU16 system comprises several key components: a Wall Fan (WF-12) rated at 2,130 CFM with 2,890 static pressure and 635 RPM, and an Exhaust Fan (EF-20) rated at 23,632 CFM with 2.25 static pressure and 879 RPM. The prefilter section contains a 1-combination filter (22 inches) with 30,000 CFM air volume, featuring a Throwaway MERV 7 prefilter and Varicel SH cartridge filter. The steam coil section includes 2 coils (12 inches) with model 8JA0801C, capacity of 2,900,906-3,299,896 Btu/h, 30 PSI steam pressure, and a condensate load of 3,229-3.5,512 lb/hr. Materials include aluminum (C-6066) and copper (C25) fins with copper tubes and galvanized steel casing. The humidifier section features a future coil setup with 2 coils and 2 rows, stainless steel drain pan on the drive side. Cabinet dimensions measure 132 inches wide by 88 inches high, with multiple connection points for steam inlets/outlets, cold water inlets/outlets, and condensate drains positioned at specified coordinates throughout the unit.
Supporting documentation includes piping details for freeze-proof steam preheat coil connections with dual steam traps and capacity control valves at 1/3 and 2/3 capacity, plus humidifier piping connections using short absorption tubes with manual shut-off valves and modulating control mechanisms. A 1,000 PPH clean steam generator (model CS-001111 MVVAB) produced by Advanced Steam Technology provides steam supply, featuring stainless steel construction, 150 PSI ASME stamp rating, and integrated level controllers with high and low alarms.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AHU16 Existing Equipment:
Wall Fan (WF-12)
Exhaust Fan (EF-20)
AHU 16 Prefilter Section
AHU 16 Steam Coil (Freeze-Proof Required)
AHU 16 Humidifier Section
AHU 16 Cabinet Dimensions
AHU 16 Steam Coil Piping Detail
AHU 16 Humidifier Piping Detail
AHU 16 Steam Generator