Mission Critical Roofs Phase I Responses RFI.xlsx

XLSX spreadsheet 97 KB Posted

Attached to
Y1DZ--620-20-201 Replace Mission Critical Roofs Phase I (Buildings 3, 6, 13, 14, 17 and 36)
Solicitation number
36C24224B0014
Issued by

About this file

This document is a Request for Information (RFI) related to a federal contract opportunity to replace mission critical roofs on several buildings at the Department of Veterans Affairs (VA) Montrose campus. The RFI includes questions and responses covering various aspects of the project, such as asbestos and lead-based paint abatement, fall protection requirements, roofing materials, site access, temporary power, and scheduling. Key details include:

  • The project will replace roofs on buildings 3, 6, 13, 14, 17, and 36 at the VA Montrose campus.
  • Asbestos-containing materials and lead-based paint were identified and must be properly abated by licensed contractors.
  • Permanent fall protection systems will be required on the new roofs.
  • The project is expected to start in Summer/Fall 2024 and must be completed within 12 months.
  • Contractors can work on up to two buildings concurrently, subject to VA approval.
  • Prevailing wage rates for Westchester County, NY will apply.
  • The solicitation number is 36C24224B0014 and the opportunity is for the "Replace Mission Critical Roofs Phase I" project.

View the file

Other files

File Type Posted
36C24224B0014 0010.docx DOCX document
36C24224B0014 0009.docx DOCX document
36C24224B0014 0008.docx DOCX document
240612 VMON-001 Detail Revisions.pdf PDF
36C24224B0014 0007.docx DOCX document
36C24224B0014 0006.docx DOCX document
RFI Responses Contd.docx DOCX document
36C24224B0014 0005.docx DOCX document
36C24224B0014 0004.docx DOCX document
VMON-002-Haz_Mat_Testing_Report-01.07.22.pdf PDF
36C24224B0014 0003.docx DOCX document
36C24224B0014 0002.docx DOCX document
36C24224B0014 0001.docx DOCX document
P07 - Wage Determination Dutchess County NY.txt TXT text file
52-225-2-Buy-American-Certificate.pdf PDF
620-20-201 Drawings Phase 1.pdf PDF
620-20-201 Specifications Phase 1 (2).pdf PDF
36C24224B0014.docx DOCX document
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

RFI #DISCIPLINEQUESTION:RESPONSERESPONSE DATE:
49ENVIRO/ABATEMENTThe plans and specifications state to remove “felt paper under clay tile associated with the pitched roof”. The process of removing the slate tile will likely disturb the ACM felt contaminating the roof tiles. Additionally, wherever there is roofers cement, flashing, or tar, the tiles are also contaminated. Please confirm if the existing clay or slate roof tiles need to be treated as ACM when removed. (The weight of the tile being removed on this project is estimated to be close to 1million lbs, the costs of removing ACM versus regular construction debris is vastly different.)If the materials can be separated without disturbing underlying asbestos-containing materials, then the non-ACM building materials may be disposed of as regular construction debris. Conversely, if the materials cannot be separated without disturbing ACM, then the entire assembly, including roof tiles or sheathing, must be disposed of as ACM.4/30/24
50ENVIRO/ABATEMENTSimilarly, the plans call for removing and replacing some sheathing. Is the sheathing to be treated as ACM as well?If the materials can be separated without disturbing underlying asbestos-containing materials, then the non-ACM building materials may be disposed of as regular construction debris. Conversely, if the materials cannot be separated without disturbing ACM, then the entire assembly, including roof tiles or sheathing, must be disposed of as ACM.4/30/24
51ENVIRO/ABATEMENTWe could find no asbestos survey/report in the project documents. Please advise if one is available.Hazardous Materials Testing Report, 1/7/2022, is attached.4/30/24
45ARCHITECTURALSpec section 030130 page no.1, para 1.4 states UNIT PRICES. Work of this Section is affected by unit prices specified in Section 012200 "Unit Prices." --- There is NO Section 012200 in the bid document. Requesting agency to provide/list Unit Prices along with the description and quantity in the bid form.Unit Prices are not included in this project. Specification will be amended to reflect this. Please disregard for bidding purposes.4/29/24
46ARCHITECTURALSpec section 030130 page no.1, para 1.3 states ALLOWANCES. Field quality-control testing is part of testing and inspecting allowance. --- There is NO allowance amount provided in the bid document for this work. Requesting agency to provide allowance amount in the bid form.Allowances are not included in this project. Specifications will be amended to reflect this. Please disregard for bidding purposes.4/29/24
47ENVIRO/ABATEMENTSpec section 02 82 13, the total quantities of “felt paper under clay tile” listed for

each building appear to not coincide with the actual total square footage of the pitched roofs on these buildings. For example, it states buildings 3, 7 and 12 have 12,750 sf of felt paper, and the larger buildings 13 and 14 have the same 12,750 square footage, while we are seeing building 14 for example is closer to 22,000 sf. Please advise whether the contractor is responsible for actual quantities or if the quantities stated in the asbestos

scope should be used.It's the contractor's responsibility during the bidding process to quantify identified ACM. Our numbers are estimates and may not factor in rise/ run of roofing systems etc.4/29/24
48ENVIRO/ABATEMENTSpecification section 02 82 13 for Asbestos Abatement calls for abatement on buildings

5, 12 and 27, however those buildings could not be found on the drawings or anywhere

else in scope of work. Please confirm if those buildings are omitted from scope of work.Buildings 5, 12 and 27 will be included in the Phase II portion of this overall roof replacement, and should be disregarded for bidding purposes of this project (Phase I).4/29/24
1VA CLIENTFor the Ludowici tiles and roofing system, the lead time 6 months according to the supplier after receiving the order and a lengthy submittal process before. Is the VA expecting the physical work to start Spring of 2025?The VA is expecting work to start in the Summer/Fall 2024 Timeframe but is fully aware that the project schedule might be affected by the lead time of the approved product selection. The selected GC will provide that updated product availability and lead time.4/22/24
2FALL PROTECTIONThe drawings show the safety pole and lanyard system that needs to be installed but doesn't provide specifications, post layout, or manufacturer. Can this be added to the specification?Please clarify what system you are referring to.4/22/24
3VA CLIENTWe would like to put together a phasing plan and believe we can do more than one building at once. Is there any requirement that would prevent us from doing that provided we had the safety and oversight to do so? If not, would the VA extend the Period of Performance?The VA is open to two (2) buildings being worked on concurrently, but the VA may limit which buildings are phased.4/22/24
4VA CLIENTAre there any VA requirements for overhead protection other than at the doorways? If we elect to scaffold the buildings for safety, are there any specific VA requirements that we should be aware of?Overhead protection is required for all egree routes and maintenance areas.4/22/24
5VA CLIENTWhere is the job trailer location for the project going to be located? Will it need to be at the laydown area next to building 6 or can we use a more centralized location?Refer to sheet G002 for suggested location. Alternative locations can be suggested by contractor for review by VA. Construction Job Trailer should be located in the Storage/Parking area near Building 6 where other trailers have been located in the past.4/22/24
6VA CLIENTCan the VA extend the deadline for bids due to the size and complexity of this project to ensure proper proposals? (CO here – I can extend with approval from Engineering)Bid deadline can be extended.4/22/24
7FALL PROTECTIONSAFETY l SECTION 05 52 00 l HANDRAILS AND RAILINGS l MANUFACTURERS Acceptable Manufacturer: Tractel Ltd., which is located at: 1615 Warden Ave.; Scarborough, ON, Canada M1R 2T3; Tel: 416-298-8822; ; Bluewater; 952-448-2935; ; Fabenco; 713-686-6620; ; Email:request info (marketing.swingstage@tractel.com); Web:http://www.tractel.com|https://www.tractel.com/us; The warranty is for two years by the manufacturer for the guardrail system. Is there an associated charge for inspection/s of the system by the manufacturer beyond the initial inspection?Warranty charges will be manufacturer-specific and will be provided by the manufacturer.4/22/24
8VA CLIENTPREPARATION FOR RE-ROOFING - 07 01 50.19 – 5 - 1.8 WARRANTY: Construction Warranty: FAR clause 52.246-21, "Warranty of Construction." Existing Warranties: Perform work to maintain existing roof warranty. in effect. Can the VA provide the copies of the existing warranties in place for the roofs associated with this project prior to bid time? What if a warranty exists on a roof beyond the roofer certifications?Warranties will be provided to the selected Bidder4/22/24
9ARCHITECTURALCOLD ADHESIVE STYRENE-BUTADIENE-STYRENE MODIFIED BITUMINOUS MEMBRANE ROOFING l 07 52 16.11 – 7 “Warranty Period: 2010 years.” What is the actual required Manufacturer’s warranty, there is a typo showing 2010 years?20 years4/22/24
10ARCHITECTURALSpecification 01 45 00 3.4B lists the qualifications for the CQC Manager and Alternate CQC manager. Are the education requirements mandatory or would past experience and current CQM training certification be sufficient?follow the requirements listing in Quality Control specification.4/22/24
11ENVIRO/ABATEMENTSpecification 02 83 33.13 3.4 mentions Lead Abatement and Lead Based Paint Removal and calls for the removal of lead based paint within the areas indicated on the drawings but after review there isn’t anything on the drawings calling out for lead based paint removal. Is there any lead abatement or lead based paint removal in the project scope?Lead based paint was identified on the roofs of buildings 12, 14, 3, and 36. Lead safe work practices must be followed and disturbance of components coated with lead based paint must comply with Federal, State, and local regulations.4/22/24
12ARCHITECTURALDrawing Demolition Keynote D3 mentions fascia board removal on all buildings but there are no Construction Keynotes referring to either the reinstallation of existing or replacement and install new fascia anywhere in the drawings or specifications. Can you please provide clarification as to the scope for fascia removal and replacement?Refer to detail 9 on sheet A401. The note refers to the board to be removed and replaced at the rear side of the concealed gutters of the sloped roofs.4/22/24
13ARCHITECTURALThe drawings and specifications are not very clear regarding the Cast Stone Cap replacement. Are buildings 17 and 36 the only Buildings getting Cast Stone Repairs or Replacement or do the other Buildings have repairs or replacement as well?Correct, only Buildings 17 and 36 have stone cap replacements at the parapets, as indicated on drawings.4/22/24
14ARCHITECTURALSpecification 03 01 30-10 3.7E1 mentions the need for a manufacturers representative to perform 2 separate inspections for both joint filler applications as well as crack injection adhesive. Are these inspections a requirement?Yes4/22/24
15VA CLIENTPlease clarify if any phasing is required for this project? Can contractor simultaneously work on multiple buildings at one time?The VA is open to (2) buildings being worked on concurrently but the VA may limit which buildings are phased. Contractor has to ensure that proper staffing & materials availability as to not negatively affect the buildings4/22/24
16VA CLIENTBased on our experience time limit of 365 calendar days is very low for these six buildings. Please increase the time limit minimum to 15 months.The project is scheduled to be completed in twelve months to allow for coordination of other construction activities ongoing and planned to follow completion.4/22/24
17ARCHITECTURALThere is an extensive spec section for Quality Control. Para 3.4 has extensive requirements for personnel requirements. Please clarify what are the full-time supervision requirements for this project. As this will have a big impact on our bid price.Part-time supervision will be adequate ffor the project.4/22/24
18ARCHITECTURALSpec section 01 35 26 states to have SSHO. Please confirm contractor’s supervisor can simultaneously perform the duties of this SSHO.If person meets OSHA requirements as specified4/22/24
19ARCHITECTURALThere is a spec section for Testing Lab Services. Please advise what testing needs to be done and if contractor has to hire and pat for these services.no testing of materials is required for project.4/22/24
20ARCHITECTURALThere is spec section for General Commissioning Requirements. Please advise what does contractor has to commission and the commission agent will be hired by VA.No commissioning will be required.4/22/24
21ENVIRO/ABATEMENTSpec section 02 82 13.21, provides quantities for ACM roofing. Please confirm all this work of asbestos roofing abatement must be performed by a licensed asbestos abatement subcontractor or roofing contractor can remove all ACM?Per Part 56 of Title 12 of the Official Compilation of Codes, Rules and Regulations of the State of New York all asbestos abatement shall be performed by a licensed abatement contractor4/22/24
22ENVIRO/ABATEMENTPlease clarify if air monitoring is responsibility of VA or contractor must hire an independent agency.Air monitoring is contracted by the VA and not the General Contractor. GC to abatement subcontractor to file for NYSDOL Notification. The Contractor is responsible for their Employee monitoring.4/22/24
23ENVIRO/ABATEMENTThere is a spec section for Lead-Based Paint Removal and Disposal. Para 2.1 states Chemical Strippers. Please advise what is the correct scope of the work? Are safe lead practices to be followed or it requires lead-paint abatement? Also specify correct and exact quantities for the lead paint removal work. Response will impact our bid offer price.Safe lead practices must be followed. Lead based paint was identified on the roofs of buildings 12, 14, 3, and 36. Disturbance of components coated with lead based paint must comply with Federal, State, and local regulations.4/22/24
24ARCHITECTURALPlease confirm at all the buildings proper access is available for the construction vehicles to reach close to the building.Refer to G002 for site plan. Note there are loading dock areas at most building. Clearance at entrances through the connecting corridors may limit the size of some vehicles. (VA: The GC will be permitted access to the Building sites for local staging & placement of materials & debris roll off containers. All ACM debris roll off containers MUST adhere to NYSDOL and other abatement guidelines)4/22/24
25FALL PROTECTIONSpec section 11 81 29 para 1.1C states Maximum number of workers on system at one time: 2. Please clarify what does this mean?It refers to the number of workers allowed on the system at any one time.4/22/24
26ELECTRICSpec section 11 81 29 on all pages on the top it states, ‘Buildings 3,5,6,12,13,14,17,27,36’. --- Please confirm that this fall protection is only for the six specified bldg. numbers and the rest of the building nos. are typo and should be removed/deleted from the spec section.Fall protection is only for the six specified building numbers. The building numbers are part of the header which encompasses the entirety of the project.4/22/24
27ARCHITECTURALPlease specify the temporary power requirements, can contractor get temporary power from any closest building location, or does he have to hire temporary generator?Refer to specification section 01 00 00 1.14 Temporary use of mechanical and electrical equipment. (VA: VA Montrose has limited power for the project sites and GC should anticipate the use of a separate generator for this project)4/22/24
28ARCHITECTURALDoes contractor need to erect stair tower to access individual bldg. roofs?Method of access to the roofs is part of the contractor's means and method. Note that there are interior access ladders/hatch to the penthouse roof on Buildings 3, 6, 12, 13, and 14. There are interior stairs to door onto main roof at Building 5 and Building 17. There is exterior ladder access at Building 36. (VA: This item is a choice by the GC but there are roof hatch access via the attics to the sloping roofs and at the GC's descretion, they can utilize scaffold stair towers or motorized Man-lifts (Lull) to access roof locations. All damaged landscaping to be restored by GC.)4/22/24
29VA CLIENTDoes contractor need to erect pipe scaffold from grade level to roof level throughout the perimeter of each building to do the roof replacement work?Refer to response for #28 (VA: Building ground level shrubbery also require protection.)4/22/24
30VA CLIENTPlease advise the work hours for all the scaffold erection including the sidewalk bridge. Document states to erect scaffold during off hours, what about Saturday and Sunday hours, regular of off hours as well?VA will permit the assembly of sidewalk bridge during normal duty hours (8:00 am - 4:30 PM M-F) and to be coordinated with VA Engineering Office4/22/24
31ELECTRICPower Plan Keynote #1 on Drawings E101-E103 indicate installation of a surge protector on each building’s main switchboard. Switchboard information for each building is required to properly size the surge protectors and to provide the proper breakers to connect the surge protectors to the switchboards. For each building, please provide the following: Main switchboard/panelboard make and model.: 1. Main switchboard/panelboard branch breaker type; 2. Confirm main switchboard/panelboard has either spare 3P breaker or space for new breaker to connect SPD; 3. If main switchboard/panelboard is at capacity or obsolete, advise if SPDs can be connected via external disconnecte tapped directly to switchboard bus (would require a temporary shutdown.)A field investigation will be required by contractor to determine how lightning protection is connected to switchboard.4/22/24
32ENVIRO/ABATEMENTPlease advise if the existing roof tiles needs to be removed and dispose of as asbestos containing material (ACM). The existing tile bottom surface which sticks to the underlayment can contain ACM. Please clarify as this will have big impact on our bid offer.Refer to Spec Section 02 82 13 for asbestos abatement scope and the Hazardous Materials Testing Report dated January 7, 2022 for asbestos survey results.4/22/24
33VA CLIENTVA Montrose falls under Westchester County, the prevailing wage rates issued are for Dutchess County. Please issue prevailing wage rates for the correct county.Westchester County Rates shall apply. Please note: DVA publishes wage rates but it is up to the Contractor to ensure they are referencing the most recent version of wage rates. SAM.gov4/22/24
34ARCHITECTURALIs there any roofing material below the asbestos felt paper. If there is any, then please specify the quantities.Ice and water shield as indicated (ie 2' from edges and ridges, 3' from valley) below the new underlayment.4/22/24
35FALL PROTECTIONPlease clarify if the new fall protection system is temporary or will remain permanent on roofs.The systems are permanent.4/22/24
36ARCHITECTURALThere is a possibility that large areas of existing landscaping/grass may be damaged by the construction work, does contractor need to restore these areas?Damaged areas should be restored.4/22/24
37ARCHITECTURALSheet 1/A136 – Keynote 5.07 refers to a new metal catwalk. Please provide details and specifications.Refer to sheet FP-136 for catwalk details and further information4/22/24
38STRUCTSheet S502 Sections and Details – please identify which repair details apply to concrete deck repair scope, and at what locations.Concrete repair details on Sheet S502 are typical details to be used by the contractor when cracking, deterioriating or unsound concrete is encountered during construction. Concrete floor exists at the attic floor, penthouse floor and penthouse roof. Concrete repair must be in accordance with Sec tion M on Sheet S001, Details on Sheet S502 and Specification Section 030130 Maintenance of Cast-in-Place Concrete.4/22/24
39FALL PROTECTIONDetails 4&5/FP604 Fall Protection Anchor Details indicate “flashing/detailing at anchor posts by others.” Please provide clay tile roofing detail at FP end anchor and intermediate anchors at roof slope.Please see Detail 5/A4044/22/24
40ELECTRICPlease provide an attachment detail for lightning protection terminals at clay tile roofing.Use a typical ridge mount base with air terminal. See Detail 7 below.4/22/24
41ARCHITECTURALA114 Roof Plan Keynote 6.01 “Replace damaged 6” T&G sheathing. Assume 5% of area to be replaced.” This keynote appears at roof sections and does not define an area. Should 5% of all sloped roofs be figured? Please clarify.Correct, this should be assumed for all sloped roofs.4/22/24
42ARCHITECTURALA114 Roof Plan Keynote 7.01 suggests insulation is to be replaced, does this apply to all sloped roofs? Please clarify.Sloped roofs do not currently have insulation. The drawings indicate for batt insulation to be added on the interior/attic side between roof joists.4/22/24
43FALL PROTECTIONThe fall protection system specification calls for a horizontal lifeline system with a system design that allows users to walk the entire length of the system without having to disconnect from the system to pass through intermediate supports. This type of system is extremely expensive, and typical for areas that expect to incur a lot of daily use, like platforms in a factory. The use on this project appears to be for an occasional occurrence such as maintenance. A system that would make the user use two carabiners so they always attached to the lifeline even when having to connect past an intermediate support would greatly reduce the costs for the VA. Please advise.VA will permit the use of a Fall Protection System that would allow the roof worker the user use two carabiners so that they always attach one of their lifelines to a fixed roof surface connection point in lieu of a continuous cable. This type of fall protection system must comply with all OSHA guidelines.4/22/24
44ENVIRO/ABATEMENTThere are quantities provided in the "General Abatement Notes" for all abatement building plans. If we scale the drawings then there is a big difference between the scaled quantities and the quantities listed on the plans. Can the agency please clarify which quantities are to be used for the bidding purpose as this will have an impact on our bid price.Suspect asbestos-containing materials were measured in the field during our hazardous building materials survey that occurred on 11/23/21 and 11/24/21 (report attached for reference). Quantities of confirmed ACM were used to generate the specifications and the drawing Abatement Notes. (Report attached).4/22/24

RFI 39/Detail 5/A404

RFI 40/Detail image1.PNG image2.png