240612 VMON-001 Detail Revisions.pdf
PDF 3 MB Posted
- Attached to
- Y1DZ--620-20-201 Replace Mission Critical Roofs Phase I (Buildings 3, 6, 13, 14, 17 and 36)
- Solicitation number
- 36C24224B0014
About this file
This document contains drawings and details for the roof replacement project at the Montrose, NY VA medical facility. The project, titled "Mission Critical Roofs, Montrose, Phase 1", will replace the roofs on Buildings 3, 6, 13, 14, 17, and 36. The work includes removing existing roofing materials, repairing or replacing roof decking and structure as needed, and installing new copper, terracotta tile, EPDM, and modified bitumen roofing systems. The drawings provide specifications for flashing, insulation, gutters, and other roofing components. This project is being solicited by the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 2 under Solicitation Number 36C24224B0014.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24224B0014 0010.docx | DOCX document | |
| 36C24224B0014 0009.docx | DOCX document | |
| 36C24224B0014 0008.docx | DOCX document | |
| 36C24224B0014 0007.docx | DOCX document | |
| 36C24224B0014 0006.docx | DOCX document | |
| RFI Responses Contd.docx | DOCX document | |
| 36C24224B0014 0005.docx | DOCX document | |
| Mission Critical Roofs Phase I Responses RFI.xlsx | XLSX spreadsheet | |
| 36C24224B0014 0004.docx | DOCX document | |
| VMON-002-Haz_Mat_Testing_Report-01.07.22.pdf | ||
| 36C24224B0014 0003.docx | DOCX document | |
| 36C24224B0014 0002.docx | DOCX document | |
| 36C24224B0014 0001.docx | DOCX document | |
| P07 - Wage Determination Dutchess County NY.txt | TXT text file | |
| 52-225-2-Buy-American-Certificate.pdf | ||
| 620-20-201 Drawings Phase 1.pdf | ||
| 620-20-201 Specifications Phase 1 (2).pdf | ||
| 36C24224B0014.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A113
7.01
7.03
7.08
7.02
7.10
7.06
7.07
7.12
7.03
7.01 7.01
7.01 7.01
7.017.01 7.01
7.05
A401
A401
A403
A401
A401
5.04
85' - 0" +/- 39' - 9" +/- 50' - 2 1/2" +/-
174' - 11 1/2" +/-
/4
/4
/4
5'
8'
/4
8'
45' - 0" +/-
FUTURE STAIR TOWER (NOT IN SCOPE)
FUTURE STAIR TOWER (NOT IN SCOPE)
FUTURE CHILLER
LOCATIONS
5.06
A402
A4025.04
A402
A401
A402
A402
7.15
A403
A401
A403
A403
8.01
TOP OF ATTIC SLAB
35' - 8"
7.01
6.01
6.03
7.08
A401
A403
H.P. OF PH ROOF SLAB (TYP)
51' - 8 1/2"
3'
/4
4'
/2
D1
D4
D3
D2
D12
D6
D8
D13
D1 D1
D1 D1
D1 D1D1
D22 D22 D22
D22 D22
D22 D22 D22
D24
FUTURE STAIR TOWER (NOT IN SCOPE)
FUTURE STAIR TOWER (NOT IN SCOPE)
D9
D9
D9
D9
D9
D26
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.ae-works.comAE WORKS®
A u to d e s k D o c s /V
M O
N -0
M o n tr o s e R o o f R e p la c e m e n t/ V
M O
N -0
M o n tr o s e
R o o f R e p la c e m e n t
P h a s e
.r v t
/1
/2
:2
:1
P
M
A113
BLDG 13 ROOF PLANS & SECTION MISSION CRITICAL ROOFS,
MONTROSE, PHASE 1
2094 ALBANY POST RD, MONTROSE, NY 10548
620-20-201
06.12.23 RS AC
BID DOCUMENTS
1/16" = 1'-0"
BUILDING 13 ROOF PLAN
1/8" = 1'-0"
BUILDING 13 ROOF SECTION
CONSTRUCTION KEYNOTES
03.01 KEYNOTE NOT USED.
03.02 5% CONCRETE ROOF SLAB AREA REPAIR.
03.03 KEYNOTE NOT USED.
03.04 100 SF OF CONCRETE ROOF SLAB REPAIR. NO REPAIR FOR NEWER ADDITION WITH METAL
DECKING.
4.01 CAST STONE CAP. MATCH EXISTING STONE CAP PROFILE AND COLOR. TYPICAL FOR ALL
PARAPETS ON BUILDING 5 ROOF.
4.02 CAST STONE CAP AT AREAS WHERE DAMAGED STONE CAPS HAVE BEEN REMOVED. MATCH
EXISTING STONE CAP PROFILE AND COLOR. ASSUME 5% OF STONE CAP TO BE REPLACED
ALONG PERIMETER.
4.07 CAST STONE CAP. MATCH EXISTING STONE CAP PROFILE AND COLOR.
5.01 ADJUSTABLE LADDER. REFER TO FALL PROTECTION DRAWINGS.
5.02 METAL GUTTER AND DOWNSPOUT TO SPLASHBLOCK.
5.03 KEYNOTE NOT USED.
5.04 METAL LADDER. REFER TO FALL PROTECTION DRAWINGS.
5.05 ROOF DRAIN (TYP)
5.06 FIXED HATCH RAILING SYSTEM WITH SELF-CLOSING AND LATCHING GATE.
5.07 NEW CATWALK TO REPLACE EXISTING
5.08 METAL GUARDRAIL. REFER TO FALL PROTECTION DRAWINGS.
6.01 REPLACE DAMAGED 6" T&G SHEATHING. ASSUME 10% OF AREA TO BE REPLACED AT BUILDING
13 AND 5% OF AREA TO BE REPLACED AT OTHER BUILDINGS.
6.02 KEYNOTE NOT USED.
6.03 STRUCTURAL REPAIR OF WOOD RAFTER FRAMING. 100' OF 2X10s TO BE REPLACED AS NEEDED
THROUGHOUT THE ROOF FRAMING FOR BUILDINGS 2, 6, 12, 13, & 14.
7.01 TERRACOTTA TILES WITH HEAVY FELT UNDERLAYMENT ON ICE & WATER SHIELD OVER
EXISTING ROOF SHEATHING. PATCH EXISTING ROOF SHEATHING PRIOR TO INSTALLATION.
NETTED BATT INSULATION BETWEEN JOISTS BELOW. PROVIDE NEW SNOW GUARDS.
TERRACOTTA TILES TO BE CUSTOM COLORS TO MATCH EXISTING TILE COLORS AT
PROPORTIONS OF 60% BROWN, 20% SLATE GRAY, AND 20% FOREST GREEN/EMPIRE GREEN.
TYPICAL AT ALL TERRACOTTA ROOFS.
7.02 COPPER ROOF ON UNDERLAYMENT ON ICE & WATER SHIELD OVER EXISTING SHEATHING.
PATCH EXISTING ROOF SHEATHING PRIOR TO INSTALLATION. NETTED BATT INSULATION
BETWEEN JOISTS BELOW.
7.03 COPPER FLASHING. TYPICAL AT ALL ROOF INTERSECTIONS, RIDGES, VALLEYS, STEPPED
FLASHINGS, AND DORMERS.
7.04 3 PLY MODIFIED BITUMEN ROOFING ON PROTECTION BOARD OVER 4" RIGID INSULATION ON AIR
& VAPOR CONTROL MEMBRANE. ADDITIONAL TAPERED INSULATION AS NEEDED FOR POSITIVE
SLOPE TO DRAINS. PATCH EXISTING SHEATHING AS NEEDED PRIOR TO INSTALLATION.
7.05 TERRACOTTA TILES AT DORMER ROOFS AND WALLS, TYP. HEAVY FELT UNDERLAYMENT ON ICE
& WATER SHIELD OVER EXISTING ROOF SHEATHING. PATCH EXISTING ROOF SHEATHING PRIOR
TO INSTALLATION. NETTED BATT INSULATION BETWEEN JOISTS BELOW ROOF & BETWEEN
WALL STUDS. TERRACOTTA TILES TO BE CUSTOM COLORS TO MATCH EXISTING TILE COLORS
AT PROPORTIONS OF 60% BROWN, 20% SLATE GRAY, AND 20% FOREST GREEN/EMPIRE GREEN.
TYPICAL AT ALL DORMER ROOFS AND WALL.
7.06 PROVIDE SHEET METAL FLASHING AT EXISTING HVAC EQUIPMENT CURBS AND PIPE
PENETRATIONS, TYPICAL.
7.07 PROVIDE SHEET METAL FLASHING AT PARAPETS, TYPICAL. MODIFIED BITUMEN ROOFING TO
EXTEND UP OVER CANT.
7.08 INSTALL COPPER GUTTER LINING OVER EXISTING GUTTER LINING. PROVIDE GUTTER GUARD, TYP. REPLACE ALL DRAIN BODIES INSIDE GUTTERS AND ON ROOF. SEE DETAIL 1/A401.
7.09 3 PLY MODIFIED BITUMEN ROOFING OVER 4" RIGID INSULATION ON AIR & VAPOR CONTROL
BARRIER. ADDITIONAL TAPERED INSULATION AS REQUIRED FOR POSITIVE SLOPE TO DRAINS.
7.10 EPDM ROOFING OVER 4" RIGID INSULATION ON AIR & VAPOR CONTROL BARRIER. ADDITIONAL
TAPERED INSULATION AS REQUIRED FOR POSITIVE SLOPE TO DRAINS. REINSTALL BALAST.
7.11 EPDM ROOF WALKWAY PADS, TYPICAL.
7.12 METAL ROOF HATCH.
7.14 METAL EDGE WITH DRIP EDGE AT ROOF EDGES.
7.15 COPPER FLASHING AT ALL EXISTING PIPE PENETRATIONS, TYP.
8.01 REINSTALL WINDOW. TYPICAL AT ALL DORMERS AT PITCHED ROOF BUILDINGS. COORDINATE
WITH VA FOR LOCATIONS WHERE LOUVER TO BE INSTALLED AT BUILDING 13.
DEMOLITION KEYNOTES
D1 REMOVE EXISTING CLAY TILE. REMOVE EXISTING FELT UNDERLAYMENT. REMOVE EXISTING
SNOW GUARDS. AREA OF WORK SHALL BE PROTECTED FROM WEATHER ONCE REMOVAL
OCCURS. TYPICAL AT ALL CLAY TILE ROOF.
D2 REMOVE METAL ROOF AND UNDERLAYMENT.
D3 REMOVE EXISTING ROOF DRAINS. CLEAR GUTTERS OF ALL DEBRIS. REMOVE EXISTING FASCIA
BOARD. TYPICAL AT ALL ROOF DRAINS AND GUTTERS.
D4 REMOVE EXISTING CLAY TILE AT GABLE WALL.
D5 REMOVE EXISTING MODIFIED BITUMEN ROOFING AND INSULATION.
D6 REMOVE FLASHING AT EXISTING HVAC EQUIPMENT CURBS AND PIPE PENETRATIONS, TYPICAL.
D7 REMOVE EXISTING METAL GUTTER AND DOWNSPOUT.
D8 REMOVE EXISTING FLASHING AT PARAPETS, TYPICAL.
D9 REMOVE EXISTING FLASHING, TYPICAL.
D10 KEYNOTE NOT USED.
D11 REMOVE EXISTING EPDM ROOFING AND INSULATION.
D12 REMOVE EXISTING EPDM ROOFING, UNDERLAYMENT AND BALAST. STORE BALAST ON SITE
FOR REUSE.
D13 REMOVE EXISTING ROOF HATCH.
D14 REMOVE EXISTING WALKWAY PADS, TYPICAL.
D15 REMOVE EXISTING WOODEN CATWALK, STAIRS AND RAMP.
D16 KEYNOTE NOT USED.
D17 KEYNOTE NOT USED.
D18 KEYNOTE NOT USED.
D19 KEYNOTE NOT USED.
D20 REMOVE EXISTING DAMAGED STONE CAPS AT PARAPET OF BUILDING 17. ASSUME 5% OF
STONE CAP TO BE REMOVED ALONG PERIMETER.
D21 KEYNOTE NOT USED.
D22 REMOVE DAMAGED 6" T&G WOOD DECKING. ASSUME 5% OF AREA TO BE REPLACED.
D23 KEYNOTE NOT USED.
D24 REMOVE EXISTING LIFELINE. REPAIR SHEATHING AS REQUIRED.
D25 REMOVE STONE CAP AT DIGESTER. REMOVE WEEDS AND DEBRIS AT DIGESTER PERIMETER
PRIOR TO STONE CAP REMOVAL.
D26 REMOVE EXISTING WINDOW. STORE FOR REINSTALLATION. TYPICAL AT ALL DORMERS AT
PITCHED ROOF BUILDINGS.
1/16" = 1'-0"
BUILDING 13 ROOF DEMO PLAN
N
# Revisions Date
ICE & WATER SHIELD
EXISTING T&G SHEATHING TO REMAIN U.N.O.; REPLACE
EXISTING T&G SHEATHING IF FOUND DAMAGED, TYP.
ASSUME 10% REPLACEMENT AT BLDG 13,
5% REPLACEMENT AT OTHER BUILDINGS
EXISTING STONE CORNICE TO
REMAIN; PATCH AND REPAIR AS
REQUIRED TO COMPLETE
GUTTER RELINING
EXISTING GALVANIZED LEADER
PIPE TO REMAIN U.N.O.
EXISTING ATTIC SLAB
TO REMAIN
COPPER GUTTER LINING
COPPER CLEATS AT 12" O.C.
12" +/-
EXISTING WOOD RAFTERS
TYPICALLY TO REMAIN -
ASSUME 100 FT ALLOWANCE
FOR REPLACEMENT OF
DAMAGED 2X10S
TERRA COTTA TILE OVER HEAVY FELT
UNDERLAYMENT
EXISTING REGLET GROOVE
SEALANT
6" BATT INSULATION
(R-21 MIN)
LEAF GUARD SCREEN
PT 1X WOOD BOARD
EXISTING GUTTER LINING TO REMAIN
COPPER FLASHING
ICE & WATER SHIELD
3/4" PLYWOOD
OVERHANG
3/4" MIN
3" MIN. HEADLAP (TYP)
2' - 0" MIN
CANT STRIP
EXISTING SILL PLATE
TYPICALLY TO REMAIN -
ASSUME 100 FT ALLOWANCE
FOR REPLACEMENT OF
DAMAGED SILL PLATES
COPPER CLEATS AT 12" O.C.
LAP LAYER OF UNDERLAYMENT
OVER FLASHING
COPPER
FLASHING
FOUNDATION GRADE WOOD NAILERS
EXISTING T&G SHEATHING
TO REMAIN U.N.O.;
REPLACE EXISTING T&G
SHEATHING IF FOUND
DAMAGED, TPY.
EXISTING STRUCTURE TO
REMAIN
PAINTED WOOD TRIM BOARD -
MATCH EXISTING COLOR
REPLACE EXISTING FASCIA BOARD
WITH NEW PT FASCIA BOARD -
REPAINT TO MATCH EXISTING
ICE & WATER SHIELD
TERRA COTTA TILE OVER HEAVY FELT
UNDERLAYMENT
MIN 3/4" M
AX 2"
EXISTING T&G SHEATHING
TO REMAIN U.N.O.;
REPLACE EXISTING T&G
SHEATHING IF FOUND
DAMAGED, TYP.
CANT STRIP
COPPER FORMED DRIP
EDGE WITH 1/2" HEM
TERRACOTTA / SYNTHETIC SLATE TILE
OVER HEAVY FELT UNDERLAYMENT
TERRA COTTA TILE
OVER HEAVY FELT
UNDERLAYMENT
ICE & WATER SHIELD
- EXTEND UP WALL
6" BATT INSULATION
(R-21 MIN)
7"
1'-0"
2' - 0 " M
IN
8" MIN
8" M
IN
SEALANT
PT WOOD BLOCKING
TERRA COTTA TILE OVER HEAVY FELT
UNDERLAYMENT
ANCHOR GABLE END
BAND TO SHEATHING
ICE & WATER SHIELD
REPLACE EXISTING FASCIA BOARD
WITH NEW PT FASCIA BOARD
- REPAINT TO MATCH EXISTING
REMOVE AND REPLACE BLOCKING
WITH PT WOOD BLOCKING
REMOVE AND REINSTALL EXISTING WINDOW
REMOVED FOR CONSTRUCTION.
COORDINATE WITH VA FOR LOCATIONS
WHERE LOUVER IS TO BE INSTALLED FOR
OTHER PROJECT.
EXISTING TRIM AT WINDOW HEAD TO
REMAIN. PATCH AND REPAIR ANY
DAMAGED OR DETERIORATED TRIM.
REPLACE / PROVIDE SEALANT AT ALL
EDGES BETWEEN TRIM
COPPER APRON - OVERLAP TILE
BY 8" MIN, TURN UP WALL BEHIND
BLOCKING
SEALANT
TERRA COTTA TILE OVER
HEAVY FELT UNDERLAYMENT
ICE & WATER SHIELD
EXISTING T&G SHEATHING TO
REMAIN U.N.O.; REPLACE EXISTING
T&G SHEATHING IF FOUND
DAMAGED, TYP.
6" BATT INSULATION
(R-21 MIN)
2' - 0" MIN
SEALANT AROUND FULL PERIMETER
OF WINDOW / LOUVER
SEALANT AROUND FULL PERIMETER
OF WINDOW / LOUVER
PT WOOD BLOCKING / SHIM AS
REQUIRED
PT WOOD BLOCKING / SHIM AS
REQUIRED
SEALANT AROUND FULL PERIMETER
OF WINDOW / LOUVER
REPLACE / PROVIDE SEALANT AT
EDGE BETWEEN VERTICAL TRIM AND
NEW METAL SILL
SEALANT AROUND FULL PERIMETER
OF WINDOW / LOUVER
SEALANT
REMOVE AND REPLACE METAL SILL -
MATCH EXISTING FINISH
EXISTING TRIM AT JAMBS TO REMAIN.
PATCH AND REPAIR ANY DAMAGED OR
DETERIORATED TRIM. REPLACE /
PROVIDE SEALANT AT ALL EDGES
BETWEEN TRIM
8" M
IN
COPPER CLEATS AT 12" O.C.
METAL FLASHING
REGLET WITH LEAD WEDGE
2 PIECE COPPER CAP
FLASHING
COPPER STEP
FLASHING
TERRACOTTA TILE OVER
HEAVY FELT UNDERLAYMENT
8" MIN.
ADHERED FLASHING STRIP PER
EPDM MANUFACTURER
COPPER COUNTER
FLASHING
EXISITNG CANT TO REMAIN
BALLAST
EPDM ROOFING
PROTECTION BOARD
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR POSITIVE
SLOPE TO DRAINS
AIR & VAPOR CONTROL MEMBRANE
MIN 4" RIGID INSULATION (R-26 MIN)
EXISTING SLAB
TO REMAIN
ICE & WATER SHIELD
EXISTING T&G SHEATHING TO
REMAIN U.N.O.; REPLACE
EXISTING T&G SHEATHING IF
FOUND DAMAGED, TYP.
6" BATT INSULATION (R-21 MIN)
EXISTING BRICK VENEER
TO REMAIN
2'-0" MIN
SEALANT
9" M
IN
9" M
IN
REGLET WITH LEAD WEDGE
4" M
IN
L
A P
COPPER CLEATS AT 12" O.C.
TERMINATION BAR
WITH SEALANT
6" M
IN
ROOF CEMENT OR SEALANT
COPPER FLASHING
TERRACOTTA TILE OVER
HEAVY FELT UNDERLAYMENT
ICE & WATER SHIELD
EXISTING T&G SHEATHING TO REMAIN U.N.O.;
REPLACE EXISTING T&G SHEATHING IF
FOUND DAMAGED, TYP.
6" BATT INSULATION (R-21 MIN)
EXISTING BRICK VENEER
TO REMAIN
COVER ROOF TILE 8" MINIMUM
WITH COPPER APRON FLASHING
ICE & WATERSHIELD
SEALANT
2' - 0" MIN
REGLET WITH LEAD WEDGE
8" MIN.
COPPER RECEIVER
8" M
IN
COPPER CLEATS AT 12" O.C.
TERRA COTTA TILE OVER HEAVY FELT
UNDERLAYMENT
ICE & WATER SHIELD
EXISTING CORNICE TO REMAIN
EXISTING T&G SHEATHING TO REMAIN U.N.O.;
REPLACE EXISTING T&G SHEATHING IF FOUND
DAMAGED, TYP.
COPPER FLASHING
COPPER CLEAT
2'-0" MIN
3"
8" MIN
HEMMED DRIP EDGE
COPPER COUNTER FLASHING
LIQUID-APPLIED FLASHING
SYSTEM, TYP.
EXISTING DIGESTER TO REMAIN
EXISTING CONCRETE WALL TO REMAIN
EXISTING CANT TO REMAIN
3 PLY MODIFIED
BITUMEN ROOFING
PROTECTION BOARD
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR
POSITIVE SLOPE TO DRAINS
MIN 4" RIGID
INSULATION (R-26 MIN)
AIR & VAPOR CONTROL
MEMBRANE
EXISTING SLAB TO REMAIN
9" M
IN
REGLET WITH LEAD WEDGE
4" M
IN
SEALANT
REGLET WITH LEAD WEDGE
TWO PIECE COPPER
CAP FLASHING
COPPER STEP FLASHING
10 1/8" TYP. EXPOSURE
8" MIN.
TERRA COTTA TILE
HEAVY FELT
UNDERLAYMENT
ICE & WATER SHIELD
EXISTING T&G SHEATHING TO
REMAIN U.N.O.; REPLACE
EXISTING T&G SHEATHING IF
FOUND DAMAGED, TYP.
REQUIRED FASTENERS
SEALANT
9" M
IN
COPPER CLEATS AT 12" O.C.
4" M
IN
L
A P
REGLET WITH SEALANT
COPPER FLASHING
- JOINTS LAPPED 6" IN THE
DIRECTION OF FLOW,
SOLDER AT COPPER APRON
TERRA COTTA TILE
HEAVY FELT
UNDERLAYMENT
ICE & WATER SHIELD
EXISTING T&G SHEATHING TO
REMAIN U.N.O.; REPLACE
EXISTING T&G SHEATHING IF
FOUND DAMAGED, TYP.
REQUIRED FASTENERS
10 1/8" TYP. EXPOSURE
8" MIN.
8" M
IN
COPPER CLEATS AT 12" O.C.
CLEAT AT 12" O.C.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.ae-works.comAE WORKS®
A u to d e s k D o c s /V
M O
N -0
M o n tr o s e R o o f R e p la c e m e n t/ V
M O
N -0
M o n tr o s e
R o o f R e p la c e m e n t
P h a s e
.r v t
/1
/2
:2
:2
P
M
A401
DETAILS MISSION CRITICAL ROOFS,
MONTROSE, PHASE 1
2094 ALBANY POST RD, MONTROSE, NY 10548
620-20-201
06.12.23 RS AC
BID DOCUMENTS
1 1/2" = 1'-0"
TYPICAL CONCEALED GUTTER DETAIL
1 1/2" = 1'-0"
DORMER SECTION DETAIL AT SIDE WALL
1 1/2" = 1'-0"
DORMER SECTION DETAIL AT WINDOW
1 1/2" = 1'-0"
SECTION DETAIL AT PENTHOUSE
# Revisions Date
1 1/2" = 1'-0"
SECTION DETAIL AT WALL BASE AND SLOPED ROOF
1 1/2" = 1'-0"
PEDIMENT SECTION DETAIL
1 1/2" = 1'-0"
SECTION DETAIL AT BLDG 36
3" = 1'-0"
TYPICAL DETAIL AT STEP FLASHING
3" = 1'-0"
TYPICAL DETAIL AT DORMER SIDE WALL
EXISTING CANT TO REMAIN
EXISTING STONE CAP TO
REMAIN
COPPER ROOFING
COPPER ROOFING
FLUID APPLIED FLASHING
SYSTEM AS SPECIFIED
ICE & WATER SHIELD
2' - 0" M
IN
REGLET WITH LEAD WEDGE
COPPER RECEIVER
SEALANT
8" M
IN
8" M
IN
COPPER RECEIVER
EXISTING BRICK VENEER TO REMAIN
EXISTING T&G SHEATHING TO REMAIN
U.N.O.; REPLACE EXISTING T&G
SHEATHING IF FOUND DAMAGED, TYP.
ICE & WATER SHIELD
COPPER ROOFING
COPPER FLASHING
EXISTING RAFTERS TO
REMAIN U.N.O.
6" BATT INSULATION
(R-21 MIN)
2' - 0
" MIN
SEALANT
REGLET WITH LEAD WEDGE
8" M
IN
8" MIN.
3/4" LOCK SOLDERED
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR
POSITIVE SLOPE TO DRAINS
PROTECTION BOARD
4" RIGID INSULATION
(R-26 MIN)
AIR & VAPOR CONTROL
MEMBRANE
3 PLY MODIFIED BITUMEN
ROOFING
SELF-ADHERING BASE
FLASHING SYSTEM PER MFR
METAL EDGE FLASHING
PT WOOD BLOCKING
METAL FLASHING
METAL GUTTER
EXISTING BRICK VENEER
TO REMAIN
CONTINUOUS CLEAT
TERRA COTTA SHINGLE TILE
EXISTING T&G SHEATHING TO REMAIN
U.N.O.; REPLACE EXISTING T&G
SHEATHING IF FOUND DAMAGED, TYP.
EXISTING RAFTERS TO
REMAIN U.N.O.
HEAVY FELT UNDERLAYMENT
ICE & WATER SHIELD
6" BATT INSULATION
(R-21 MIN)
COPPER ROOFING
COPPER FLASHING OVER PARAPET 2'-0"
END DAM BEYOND
EXISTING MASONRY WALL
TO REMAIN
2' - 0 " M
IN
SEALANT ALONG EDGE
2'-0" MIN
COPPER CLEAT
3/4" LOCK SOLDERED
LAP LAYER OF UNDERLAYMENT
OVER FLASHING
COPPER CLEATS AT 12" O.C.
CAST STONE CAP
-MATCH EXISTING SIZE, PROFILE
AND APPEARANCE
EXISTING DIGESTER COVER TO REMAIN
EXISTING WALL TO REMAIN
SELF-ADHERING BASE FLASHING SYSTEM PER MFR
EXISTING CANT TO REMAIN; REPLACE IF DAMAGED, TYP
3 PLY MODIFIED BITUMEN ROOFING
PROTECTION BOARD
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR POSITIVE
SLOPE TO DRAINS
MIN 3" RIGID INSULATION (R-19 MIN)
AIR & VAPOR CONTROL MEMBRANE
THRU-WALL FLASHING AND COUNTER-FLASHING
WITH SEALANT
8" MIN
COPPER ROOFING
TERRA COTTA ROOFING
TERRA COTTA SHINGLE TILE
EXISTING T&G SHEATHING TO REMAIN
U.N.O.; REPLACE EXISTING T&G
SHEATHING IF FOUND DAMAGED, TYP.
EXISTING RAFTERS TO
REMAIN U.N.O.
HEAVY FELT UNDERLAYMENT
6" BATT INSULATION
(R-21 MIN)
COPPER ROOFING
LAP LAYER OF UNDERLAYMENT
OVER FLASHING
8" M
IN
3/4" LOCK SOLDERED
COPPER CLEATS AT 12" O.C.
COPPER FLASHING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.ae-works.comAE WORKS®
A u to d e s k D o c s /V
M O
N -0
M o n tr o s e R o o f R e p la c e m e n t/ V
M O
N -0
M o n tr o s e
R o o f R e p la c e m e n t
P h a s e
.r v t
/1
/2
:2
:2
P
M
A402
DETAILS MISSION CRITICAL ROOFS,
MONTROSE, PHASE 1
2094 ALBANY POST RD, MONTROSE, NY 10548
620-20-201
06.12.23 RS AC
BID DOCUMENTS
# Revisions Date
1 1/2" = 1'-0"
SECTION DETAIL AT METAL ROOF AND PARAPET
1 1/2" = 1'-0"
SECTION AT WALL BASE AND METAL ROOF
1 1/2" = 1'-0"
BUILDING 17 PENTHOUSE DETAIL AT GUTTER
1 1/2" = 1'-0"
SECTION AT PARAPET AND METAL ROOF
1 1/2" = 1'-0"
SECTION DETAIL AT BLDG 36
AXONOMETRIC VIEW - METAL ROOFING AREA
1 1/2" = 1'-0"
SECTION DETAIL AT METAL ROOF AND TERRA COTTA TILES
6/ A4
1/ A4
3 PLY MODIFIED BITUMEN ROOFING
PROTECTION BOARD
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR
POSITIVE SLOPE
MIN 3" RIGID INSULATION (R-19 MIN)
AIR & VAPOR CONTROL
MEMBRANE
EXISTING SLAB TO REMAIN
PT WOOD BLOCKING
METAL EDGE DRIP EDGE
TWO-PLY STRIPPING, TYP.
EXISTING BRICK VENEER TO REMAIN
EXISTING CMU TO REMAIN
EXISTING OPEN WEB STEEL
JOISTS TO REMAIN
CONTINUOUS CLEAT
SEALANT PER MODIFIED BITUMEN MFR
SEALANT PER MOD BIT MFR
1/4" / 1'-0"
8" MIN
METAL FLASHING
SELF-ADHERING BASE FLASHING SYSTEM PER MFR
EXISTING CANT TO REMAIN
TAPERED RIGID INSULATION
- SLOPE 1/4" MIN PER FT FOR POSITIVE SLOPE TO DRAINS
PROTECTION BOARD
MIN 4" RIGID INSULATION (R-26 MIN)
AIR & VAPOR CONTROL MEMBRANE
3 PLY MODIFIED BITUMEN ROOFING
STONE COPING TO REMAIN EXCEPT
REPLACE WHERE DAMAGED WITH NEW
STONE COPING - MATCH COLOR AND
PROFILE (ASSUME 5% OF STONE CAP
ALONG PERIMETER TO BE REPLACED)
SEALANT
NOTE CONTRACTOR TO VERIFY
EXISTING WALL ASSEMBLY OF
PARAPET WHERE STONE
COPING TO BE REPLACED.
SEALANT
REGLET WITH LEAD WEDGE
9" M
IN
4" M
IN
L
A P
8" MIN
EXISTING STONE CAP TO REMAIN
COPPER RECEIVER
COPPER FLASHING
TERRA COTTA TILE OVER HEAVY FELT
UNDERLAYMENT
ICE & WATER SHIELD
EXISTING T&G SHEATHING TO REMAIN U.N.O.; REPLACE
EXISTING T&G SHEATHING IF FOUND DAMAGED, TYP.
2' - 0" MIN
REGLET WITH LEAD WEDGE
SEALANT
8" MIN.
CLEATS AT 12" O.C.
NOTE: REPOINT BRICK AT
END GABLES AS REQUIRED
TO REPAIR CONDITION
SHIP LAPPED V-RIDGE TILE, TYP
FOUNDATION GRADE
BLOCKING AS REQUIRED
BY TILE MFR
TERRA COTTA TILE OVER HEAVY FELT
UNDERLAYMENT
ICE & WATER SHIELD
EXISTING T&G SHEATHING TO REMAIN U.N.O.; REPLACE
EXISTING T&G SHEATHING IF FOUND DAMAGED, TYP.
SEALANT
EXISTING STRUCTURE
TO REMAIN
6" BATT INSULATION (R-21 MIN)
2' - 0" MIN
2' - 0
" M
IN
COPPER FLASHING
8" MIN
8" M
IN
COPPER RIDGE CAP
LOOSE LOCK SEAM
TERRA COTTA TILE OVER HEAVY FELT
UNDERLAYMENT
ICE & WATER SHIELD
EXISTING T&G SHEATHING TO REMAIN
U.N.O.; REPLACE EXISTING T&G
SHEATHING IF FOUND DAMAGED, TYP.
EXISTING STRUCTURE
TO REMAIN U.N.O.
COPPER VALLEY FLASHING
CLEAT AT 12" O.C.
6" BATT INSULATION (R-21 MIN)
VALLEY TO OPEN 1/8"
WIDER PER FOOT DOWN
SLOPE, TYP
3' - 0 " M
IN
3' - 0" MIN
AT TOP OF VALLEY
6" MIN. OPENING
8" M
IN.
COPPER CANT
SOLDERED TO FLASHING
8" MIN.
COPPER CANT
SOLDERED TO FLASHING
CLEAT AT 12" O.C.
COPPER CLEAT 12" O.C.
BEND OVER FASTENER
COPPER VALLEY FLASHING
ICE & WATER SHIELD
TERRA COTTA TILE
HEAVY FELT UNDERLAYMENT
8" MIN.
COPPER CANT SOLDERED
TO FLASHING
ADHERED FLASHING STRIP PER
EPDM MANUFACTURER
THROUGH-WALL
COPPER FLASHING
EXISITNG CANT TO REMAIN
BALLAST
EPDM ROOFING
PROTECTION BOARD
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR POSITIVE
SLOPE TO DRAINS
AIR & VAPOR CONTROL MEMBRANE
MIN 4" RIGID INSULATION (R-26 MIN)
EXISTING SLAB
TO REMAIN
4" M
IN
L
A P
REPLACE EXISTING DOUBLE WHYTHE
PARAPET WALL AT DAMAGED
NORTHEAST PENTHOUSE PARAPET
WALL OF BUILDING 13 PER STRUCTURAL
ENGINEERING REQUIREMENTS
REPLACE EXISTING STONE COPING AT
DAMAGED NORTHEAST PENTHOUSE
PARAPET WALL OF BUILDING 13
6" M
IN
9" M
IN
NOTE: WALL CONDITION AND
CONFIGURATION TO BE REVIEWED
BY STRUCTURAL ENGINEER PRIOR
TO CONSTRUCTION
TERMINATION BAR
WITH SEALANT
8" MIN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.ae-works.comAE WORKS®
A u to d e s k D o c s /V
M O
N -0
M o n tr o s e R o o f R e p la c e m e n t/ V
M O
N -0
M o n tr o s e
R o o f R e p la c e m e n t
P h a s e
.r v t
/1
/2
:2
:2
P
M
A403
DETAILS MISSION CRITICAL ROOFS,
MONTROSE, PHASE 1
2094 ALBANY POST RD, MONTROSE, NY 10548
620-20-201
06.12.23 RS AC
BID DOCUMENTS
1 1/2" = 1'-0"
SECTION DETAIL AT BLDG 36
1 1/2" = 1'-0"
SECTION DETAIL AT BLDG 17
# Revisions Date
1 1/2" = 1'-0"
END GABLE SECTION DETAIL
1 1/2" = 1'-0"
TYPICAL RIDGE DETAIL
1 1/2" = 1'-0"
TYPICAL VALLEY DETAIL
1 1/2" = 1'-0"
SECTION DETAIL AT BUILDING 13 PENTHOUSE - NE PARAPET
WATER CUT OFF MASTIC
PREMOLDED PIPE BOOT
EXISTING ROOF STRUCTURE TO REMAIN
CLAMPING RING
IN-SEAM SEALANT
MODIFIED BITUMEN SEALANT PER MANUF.
MIN 4" RIGID INSULATION (R-26 MIN)
FULLY ADHERED ROOF MEMBRANE
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR POSITIVE SLOPE TO DRAINS
EXISTING PIPE TO REMAIN
3 PLY MODIFIED BITUMEN ROOFING
SELF-ADHERING BASE FLASHING SYSTEM PER MFR
EXISTING ROOF MOUNTED MECHANICAL
EQUIPMENT TO REMAIN
3 PLY MODIFIED BITUMEN ROOFING
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR POSITIVE
SLOPE TO DRAINS
MIN 4" RIGID INSULATION (R-26 MIN)
EXISTING ROOF STRUCTURE TO REMAIN
EXISTING ROOF CURB
EXISTING WOOD BLOCKING (VIF)
EXISTING FRAMED OPENING
V A
R
IE
S
AIR & VAPOR CONTROL MEMBRANE
SELF-ADHERING BASE FLASHING SYSTEM PER MFR
METAL FLASHING
EXISTING EQUIPMENT TO REMAIN
3 PLY MODIFIED BITUMEN ROOFING
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR POSITIVE
SLOPE TO DRAINS
MIN 4" RIGID INSULATION (R-26 MIN)
EXISTING ROOF STRUCTURE TO REMAIN
EXISTING ROOF CURB (VIF)
EXISTING CANT (VIF)
EXISTING FRAMED OPENING
AIR & VAPOR CONTROL MEMBRANE
SELF-ADHERING BASE FLASHING SYSTEM PER MFR
SEALANT
METAL FLASHING
ROOF DRAIN
WATER CUT OFF MASTIC
EXISTING ROOF
STRUCTURE TO REMAIN
CLAMPING RING
3 PLY MODIFIED BITUMEN ROOFING
RAIN WATER CONDUCTOR
4" RIGID INSULATION (R-26 MIN)
- TAPER TO DRAIN
TAPERED RIGID INSULATION
- SLOPE 1/4" MIN PER FT FOR
POSITIVE SLOPE TO DRAINS
AIR & VAPOR BARRIER
ROLL TOP OF FLASHING INTO PIPE OR
CAP WITH FORMED SOFT METAL CAP
16" OZ. COPPER FLASHING EXTENDED
UPSLOPE TO ACHIEVE 3" HEAD LAP
SOLDERED FLASHING SLEEVE
24" x 24" ICE AND WATER SHIELD
EXISTING ROOF MOUNTED MECHANICAL
EQUIPMENT TO REMAIN
EPDM ROOFING
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR POSITIVE
SLOPE TO DRAINS
MIN 4" RIGID INSULATION (R-26 MIN)
EXISTING ROOF STRUCTURE TO REMAIN
EXISTING ROOF CURB
EXISTING WOOD BLOCKING (VIF)
EXISTING FRAMED OPENING
V A
R
IE
S
AIR & VAPOR CONTROL MEMBRANE
BONDING ADHESIVE AT CURB, TYP.
METAL FLASHING
8" MIN
EPDM ROOFING
TERMINATION BAR WITH SEALANT
WATER CUT OFF MASTIC
PREMOLDED PIPE BOOT
EXISTING ROOF STRUCTURE TO REMAIN
CLAMPING RING
IN-SEAM SEALANT
SEALANT PER EPDM MANUF.
MIN 4" RIGID INSULATION (R-26 MIN)
FULLY ADHERED ROOF MEMBRANE
TAPERED RIGID INSULATION
- SLOPE 1/4" PER FT FOR POSITIVE SLOPE TO DRAINS
EXISTING PIPE TO REMAIN
EPDM ROOFING
LIQUID-APPLIED FLASHING SYSTEM PER MFR, TYP.
ROOF DRAIN
WATER CUT OFF MASTIC
EXISTING ROOF
STRUCTURE TO REMAIN
CLAMPING RING
EPDM ROOFING
RAIN WATER CONDUCTOR
4" RIGID INSULATION (R-26 MIN)
- TAPER TO DRAIN
TAPERED RIGID INSULATION
- SLOPE 1/4" MIN PER FT FOR
POSITIVE SLOPE TO DRAINS
AIR & VAPOR BARRIER
CLEATS AT 12" O.C.
SINGLE PIECE COPPER
BASE FLASHING
REFER TO 8/A401 FOR
SECTION DETAIL AT
STEP FLASHING
TWO PIECE COPPER CAP
SOLDERED, TYPICAL
FORMED CANT STRIP IN
BASE FLASHING
COPPER FLASHING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.ae-works.comAE WORKS®
A u to d e s k D o c s /V
M O
N -0
M o n tr o s e R o o f R e p la c e m e n t/ V
M O
N -0
M o n tr o s e
R o o f R e p la c e m e n t
P h a s e
.r v t
/1
/2
:2
:2
P
M
A404
DETAILS MISSION CRITICAL ROOFS,
MONTROSE, PHASE 1
2094 ALBANY POST RD, MONTROSE, NY 10548
620-20-201
06.12.23 RS AC
BID DOCUMENTS
# Revisions Date
1 1/2" = 1'-0"
PIPE PENETRATION DETAIL AT MODIFIED BITUMEN ROOFING
1 1/2" = 1'-0"
MECHANICAL CURB DETAIL AT MODIFIED BITUMEN ROOFING
1 1/2" = 1'-0"
ROOF EXHAUST FLASHING DETAIL AT MODIFIED BITUMEN ROOFING
1 1/2" = 1'-0"
ROOF DRAIN DETAIL AT MODIFIED BITUMEN ROOFING
PIPE PENETRATION DETAIL AT TERRA COTTA TILE
1 1/2" = 1'-0"
MECHANICAL CURB DETAIL AT EPDM ROOFING
1 1/2" = 1'-0"
PIPE PENETRATION DETAIL AT EPDM ROOFING
1 1/2" = 1'-0"
ROOF DRAIN DETAIL AT EPDM ROOFING
STEP FLASHING DETAIL
| Sheets |
| A113 - BLDG 13 ROOF PLANS & SECTION |
| A401 - DETAILS |
| A402 - DETAILS |
| A403 - DETAILS |
| A404 - DETAILS |