This document provides details for a federal solicitation seeking replacement of domestic hot water systems at three buildings on the Castle Point VA Medical Center campus. The solicitation is for a service-disabled veteran-owned small business set-aside and seeks to remove existing systems and install new steam-fired water heaters utilizing an in-house steam supply. The scope of work includes phased removal and replacement to maintain domestic hot water, along with associated electrical, mechanical, and general construction work. The response due date is March 26, 2021 and the period of performance is 270 calendar days. The cost estimate range for the project is $500,000 to $1 million.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AIRTEK ENVIRONMENTAL CORP.
39 – 37 29th Street, Long Island City, New York, 11101 Phone (718) 937-3720 Fax (718) 937-3721 www.airtekenv.com
Lead-Based Paint Testing Report
Conducted At:
VA Hudson Valley Health Care System
41 Castle Point Rd
Building 19, 20, and 21
Wappingers Falls, NY 12590
Prepared For:
Watson Engineering, PC
1112 State Route 434
Owego, New York 13827
Prepared by:
Airtek Environmental Corp.
39-37 29 th
Street
Long Island City, NY 11101
Airtek Project No: 20-0257
May 27 th
, 2020
Lead Based Paint Testing Report – Watson Engineering - VA Castle Point Page 2 of 7
Airtek Project #:20-0257 May 27 th
Table of Contents
I. Executive Summary
II. Background
III. File Search Data
IV.Testing Procedures/Analytical Methodology
V. Results
VI. Conclusions
VII. Report Certifications
Attachments:
Attachment A. XRF Results
Attachment B: Positive Lead Shots Diagram
Attachment C: Lead Inspector/Risk Assessor, Company Certifications
Lead Based Paint Testing Report – Watson Engineering - VA Castle Point Page 3 of 7 th
I. Executive Summary
Airtek Environmental Corp. performed a lead-based paint inspection at the VA Hudson Valley Health Care
System - 41 Castle Point Road, Wappingers Falls, NY (the Property). The inspection was performed by
EPA Certified Lead Risk Assessor Anthony Dhanpat of Airtek Environmental Corp., who has been trained and certified in accordance with 40 CFR Part 745. All fieldwork associated with this inspection was performed on May 15
, 2020.
The intent of the inspection was to ascertain if the surface coatings on building components have a lead
Concentration greater than or equal to 1.0 mg/cm2 or 0.5 percent by weight.
According to the inspection, thirteen (13) of the tested components/surfaces contain lead-based paint above current regulatory thresholds. Please refer to Attachment A for detailed test results.
The report shows all the readings that were taken by Room and Wall sequence. As noted on the result
Spreadsheet, Wall 1 in each room is the wall where the door opening is. Going clockwise, Wall 2 will be
On your left, Wall 3 is straight ahead of you and Wall 4 is always on the right.
This report represents field data, observations and findings relating to the single testing performed at the property. The results and findings stated in this report are representative of the conditions observed at this property at the time of inspection. Airtek Environmental Corp. assumes no responsibility for any change in the conditions or circumstances that occurred subsequent to our performance of single testing.
Lead Based Paint Testing Report – Watson Engineering - VA Castle Point Page 4 of 7 th
II. Background
A. Property
VA Hudson Valley Health Care System - 41 Castle Point Road, Wappingers Falls, NY is a Public facility (Hospital).
B. Owner
Owner’s information was not provided to Airtek.
C. Lead Inspection Firm
Airtek Environmental Corp. USEPA # NY 1661-1
39-37 29 th
Street
Long Island City, NY 11101
Contact: Mike S. Zouak
Telephone: (718) 937-3720
D. Lead Inspectors (Certifications/Licenses)
Anthony Dhanpat
E. XRF Instruments/Serial Numbers
Heuresis Pb200i Serial # 2477
III. File Search Data
No prior documentation related to lead paint was provided by the client.
IV. Testing Procedures/Analytical Methodology
The primary lead detection technique utilized for this work was X-ray fluorescence analysis (XRF). The
XRF analysis was conducted on site, using a portable Pb200i XRF Lead Analyzer manufactured by Heuresis
Corporation. The Pb200i was utilized in accordance with the procedures specified by the manufacturer, Performance Characteristic Sheet (PCS), dated December 1, 2015 and Chapter 7 of the HUD Guidelines for the Evaluation and Control of Lead Based Paint Hazards in Housing.
Lead Based Paint Testing Report – Watson Engineering - VA Castle Point Page 5 of 7
V. Results
The data provided as Attachment A consists of data downloaded from the XRF to Microsoft Excel.
VI. Conclusions
According to the inspection, thirteen (13) of the tested components/surfaces contain lead-based paint above current regulatory thresholds.
Table 1: Positive Components
Shot # Component Color Location
9 Wall 1 Gray C-001
10 Wall 2 Gray C-001
12 Wall 4 Gray C-001
15 Wall 1 White Outside wall (C-001)
33 Wall 1 White B-001
34 Wall 2 White B-001
35 Wall 3 White B-001
36 Wall 4 White B-001
51 Wall 2 White A-001
52 Wall 3 White A-001
52 Wall 4 White A-001
56 Wall 1 White A-001
59 Wall 4 White A-001
Please refer to Attachment A for detailed test results and Attachment B for the location diagram.
The readings that are labeled “CALIBRATION” are the calibration readings only and they do not indicate a lead positive component in the subject space.
VII. Report Certifications:
Airtek certifies that the information contained herein is based on the physical and visual inspections conducted by Airtek and data collected during the inspection survey on the date noted.
Prepared by:
Airtek Environmental Corp.
EPA Certified Lead Risk Assessor
Attachement A:
XRF Results
Company Heuresis Corp.
Model Pb200i
Type XRF Lead Paint Analyzer
Serial Num. 2219
App Version Pb200i-4.1-11
Job Id Reading # ConcentrationUnits Result Date Time Analytic Mode Structure ComponentWall Substrate Color Paint ConditionRoom Site Address Floor/Apt # Room Inspector
1 1 mg/cm2 Positive 5/15/2020 10:32:47 Lead Paint Calibrate Metal White Poor VA Castle Point Anthony Dhanpat
2 1.1 mg/cm2 Positive 5/15/2020 10:33:01 Lead Paint Calibrate Metal White Poor VA Castle Point Anthony Dhanpat
3 1 mg/cm2 Positive 5/15/2020 10:33:16 Lead Paint Calibrate Metal White Poor VA Castle Point Anthony Dhanpat
4 0.1 mg/cm2 Negative 5/15/2020 10:33:33 Lead Paint Calibrate Metal White Poor VA Castle Point Anthony Dhanpat
5 0.1 mg/cm2 Negative 5/15/2020 10:33:40 Lead Paint Calibrate Metal White Poor VA Castle Point Anthony Dhanpat
6 0.1 mg/cm2 Negative 5/15/2020 10:33:47 Lead Paint Calibrate Metal White Poor VA Castle Point Anthony Dhanpat
7 0.2 mg/cm2 Negative 5/15/2020 10:34:20 Lead Paint Door Door Wall 1 Metal Gray Poor VA Castle Point Bldg 19 C-001 Anthony Dhanpat
8 0.7 mg/cm2 Negative 5/15/2020 10:34:37 Lead Paint Door Door Buck Wall 1 Metal Gray Poor VA Castle Point Bldg 19 C-001 Anthony Dhanpat
9 7.2 mg/cm2 Positive 5/15/2020 10:35:25 Lead Paint Room Wall Wall 1 Concrete Gray Poor VA Castle Point Bldg 19 C-001 Anthony Dhanpat
10 2.8 mg/cm2 Positive 5/15/2020 10:36:04 Lead Paint Room Wall Wall 2 Concrete Gray Poor VA Castle Point Bldg 19 C-001 Anthony Dhanpat
11 0.7 mg/cm2 Negative 5/15/2020 10:36:42 Lead Paint Room Wall Wall 3 Concrete Gray Poor VA Castle Point Bldg 19 C-001 Anthony Dhanpat
12 2.2 mg/cm2 Positive 5/15/2020 10:37:16 Lead Paint Room Wall Wall 4 Concrete Gray Poor VA Castle Point Bldg 19 C-001 Anthony Dhanpat
13 0.5 mg/cm2 Negative 5/15/2020 10:41:01 Lead Paint Angle Iron Angle Iron Floor Metal White Poor VA Castle Point Bldg 19 C-001 Anthony Dhanpat
14 0.7 mg/cm2 Negative 5/15/2020 10:44:37 Lead Paint Room Ceiling Ceiling Concrete White Poor Common AreaVA Castle Point Bldg 19 Anthony Dhanpat
15 1.9 mg/cm2 Positive 5/15/2020 10:45:23 Lead Paint Room Wall Wall 1 Concrete White Poor Common AreaVA Castle Point Bldg 19 Anthony Dhanpat
16 0.6 mg/cm2 Negative 5/15/2020 10:45:42 Lead Paint Room Wall Wall 2 Concrete White Poor Common AreaVA Castle Point Bldg 19 Anthony Dhanpat
17 0.1 mg/cm2 Negative 5/15/2020 10:45:56 Lead Paint Room Wall Wall 3 Concrete White Poor Common AreaVA Castle Point Bldg 19 Anthony Dhanpat
18 0.6 mg/cm2 Negative 5/15/2020 10:46:11 Lead Paint Room Wall Wall 4 Concrete White Poor Common AreaVA Castle Point Bldg 19 Anthony Dhanpat
19 0.2 mg/cm2 Negative 5/15/2020 10:48:32 Lead Paint Door Door Wall 1 Metal Blue Poor VA Castle Point 20 B-005 Anthony Dhanpat
20 0.2 mg/cm2 Negative 5/15/2020 10:48:47 Lead Paint Door Door Buck Wall 1 Metal Blue Poor VA Castle Point 20 B-005 Anthony Dhanpat
21 0.3 mg/cm2 Negative 5/15/2020 10:49:24 Lead Paint Room Wall Wall 1 Concrete Blue Poor VA Castle Point 20 B-005 Anthony Dhanpat
22 0.3 mg/cm2 Negative 5/15/2020 10:50:34 Lead Paint Room Wall Wall 2 Concrete Blue Poor VA Castle Point B-005 Anthony Dhanpat
23 0.3 mg/cm2 Negative 5/15/2020 10:50:49 Lead Paint Room Wall Wall 3 Concrete Blue Poor VA Castle Point B-005 Anthony Dhanpat
24 0.1 mg/cm2 Negative 5/15/2020 10:51:03 Lead Paint Room Wall Wall 4 Concrete Blue Poor VA Castle Point B-005 Anthony Dhanpat
25 0.2 mg/cm2 Negative 5/15/2020 10:52:39 Lead Paint Room Wall Wall 1 Concrete White Poor VA Castle Point 20 corridor Anthony Dhanpat
26 0 mg/cm2 Negative 5/15/2020 10:52:52 Lead Paint Room Wall Wall 2 Concrete White Poor VA Castle Point 20 corridor Anthony Dhanpat
27 0.1 mg/cm2 Negative 5/15/2020 10:53:13 Lead Paint Room Wall Wall 3 Concrete White Poor VA Castle Point 20 corridor Anthony Dhanpat
28 0.5 mg/cm2 Negative 5/15/2020 10:53:30 Lead Paint Room Wall Wall 4 Concrete White Poor VA Castle Point 20 corridor Anthony Dhanpat
29 0.5 mg/cm2 Negative 5/15/2020 10:53:48 Lead Paint Room Wall Wall 3 Concrete White Poor VA Castle Point 20 corridor Anthony Dhanpat
30 0.2 mg/cm2 Negative 5/15/2020 10:55:11 Lead Paint Door Door Wall 1 Metal Blue Poor VA Castle Point b001 bldg 20 B-001 Anthony Dhanpat
31 0.6 mg/cm2 Negative 5/15/2020 10:55:26 Lead Paint Door Door Buck Wall 1 Metal Blue Poor VA Castle Point b001 bldg 20 B-001 Anthony Dhanpat
32 0.1 mg/cm2 Negative 5/15/2020 10:55:54 Lead Paint Room Wall Wall 1 Concrete White Poor VA Castle Point b001 bldg 20 B-001 Anthony Dhanpat
33 2 mg/cm2 Positive 5/15/2020 10:56:04 Lead Paint Room Wall Wall 1 Concrete White Poor VA Castle Point b001 bldg 20 B-001 Anthony Dhanpat
34 1.9 mg/cm2 Positive 5/15/2020 10:56:19 Lead Paint Room Wall Wall 2 Concrete White Poor VA Castle Point b001 bldg 20 B-001 Anthony Dhanpat
35 2 mg/cm2 Positive 5/15/2020 10:56:39 Lead Paint Room Wall Wall 3 Concrete White Poor VA Castle Point b001 bldg 20 B-001 Anthony Dhanpat
36 2.8 mg/cm2 Positive 5/15/2020 10:57:05 Lead Paint Room Wall Wall 4 Concrete White Poor VA Castle Point b001 bldg 20 B-001 Anthony Dhanpat
37 0.2 mg/cm2 Negative 5/15/2020 10:59:18 Lead Paint Door Door Wall 1 Metal Blue Poor VA Castle Point a005 bldg 21 A-005 Anthony Dhanpat
38 0.3 mg/cm2 Negative 5/15/2020 10:59:32 Lead Paint Door Door Buck Wall 1 Metal Blue Poor VA Castle Point a005 bldg 21 A-005 Anthony Dhanpat
39 0.2 mg/cm2 Negative 5/15/2020 11:00:10 Lead Paint Room Wall Wall 1 Concrete White Poor VA Castle Point a005 bldg 21 A-005 Anthony Dhanpat
40 0.3 mg/cm2 Negative 5/15/2020 11:00:31 Lead Paint Room Wall Wall 2 Concrete White Poor VA Castle Point a005 bldg 21 A-005 Anthony Dhanpat
41 0.2 mg/cm2 Negative 5/15/2020 11:00:48 Lead Paint Room Wall Wall 3 Concrete White Poor VA Castle Point a005 bldg 21 A-005 Anthony Dhanpat
42 0.3 mg/cm2 Negative 5/15/2020 11:01:14 Lead Paint Room Wall Wall 4 Concrete White Poor VA Castle Point a005 bldg 21 A-005 Anthony Dhanpat
43 0.5 mg/cm2 Negative 5/15/2020 11:03:12 Lead Paint Room Wall Wall 1 Concrete White Poor Common AreaVA Castle Point bldg 21 Anthony Dhanpat
44 0.2 mg/cm2 Negative 5/15/2020 11:03:30 Lead Paint Room Wall Wall 2 Concrete White Poor Common AreaVA Castle Point bldg 21 Anthony Dhanpat
45 0.6 mg/cm2 Negative 5/15/2020 11:03:43 Lead Paint Room Wall Wall 3 Concrete White Poor Common AreaVA Castle Point bldg 21 Anthony Dhanpat
46 0.2 mg/cm2 Negative 5/15/2020 11:04:00 Lead Paint Room Wall Wall 4 Concrete White Poor Common AreaVA Castle Point bldg 21 Anthony Dhanpat
47 0.6 mg/cm2 Negative 5/15/2020 11:05:17 Lead Paint Door Door Wall 1 Metal Blue Poor Common AreaVA Castle Point bldg 21 a001 A001 Anthony Dhanpat
48 0.1 mg/cm2 Negative 5/15/2020 11:05:33 Lead Paint Door Door Buck Wall 1 Metal Blue Poor Common AreaVA Castle Point bldg 21 a001 A001 Anthony Dhanpat
49 0.2 mg/cm2 Negative 5/15/2020 11:06:07 Lead Paint Room Wall Wall 1 Concrete White Poor Common AreaVA Castle Point bldg 21 a001 A001 Anthony Dhanpat
50 -0.3 mg/cm2 Negative 5/15/2020 11:06:24 Lead Paint Room Wall Wall 1 Concrete White Poor Common AreaVA Castle Point bldg 21 a001 A001 Anthony Dhanpat
51 4.3 mg/cm2 Positive 5/15/2020 11:06:59 Lead Paint Room Wall Wall 2 Concrete White Poor Common AreaVA Castle Point bldg 21 a001 A001 Anthony Dhanpat
52 1.2 mg/cm2 Positive 5/15/2020 11:08:24 Lead Paint Room Wall Wall 3 Concrete White Poor Common AreaVA Castle Point A001 Anthony Dhanpat
53 3.9 mg/cm2 Positive 5/15/2020 11:08:55 Lead Paint Room Wall Wall 4 Concrete White Poor Common AreaVA Castle Point A001 Anthony Dhanpat
54 0.2 mg/cm2 Negative 5/15/2020 11:10:09 Lead Paint Door Door Wall 1 Metal Blue Poor Common AreaVA Castle Point A002 Anthony Dhanpat
55 0.4 mg/cm2 Negative 5/15/2020 11:10:21 Lead Paint Door Door Buck Wall 1 Metal Blue Poor Common AreaVA Castle Point A002 Anthony Dhanpat
56 3 mg/cm2 Positive 5/15/2020 11:10:59 Lead Paint Room Wall Wall 1 Concrete White Poor Common AreaVA Castle Point A002 Anthony Dhanpat
57 0.2 mg/cm2 Negative 5/15/2020 11:11:19 Lead Paint Room Wall Wall 2 Concrete White Poor Common AreaVA Castle Point A002 Anthony Dhanpat
58 0.1 mg/cm2 Negative 5/15/2020 11:11:33 Lead Paint Room Wall Wall 3 Concrete White Poor Common AreaVA Castle Point A002 Anthony Dhanpat
59 2.7 mg/cm2 Positive 5/15/2020 11:11:51 Lead Paint Room Wall Wall 4 Concrete White Poor Common AreaVA Castle Point A002 Anthony Dhanpat
60 0.4 mg/cm2 Negative 5/15/2020 11:13:08 Lead Paint Angle Iron Floor Metal Gray Poor Common AreaVA Castle Point A002 Anthony Dhanpat
61 1 mg/cm2 Positive 5/15/2020 11:15:42 Lead Paint Calibrate Metal Gray Poor Common AreaVA Castle Point Anthony Dhanpat
62 1.1 mg/cm2 Positive 5/15/2020 11:15:57 Lead Paint Calibrate Metal Gray Poor Common AreaVA Castle Point Anthony Dhanpat
63 1 mg/cm2 Positive 5/15/2020 11:16:12 Lead Paint Calibrate Metal Gray Poor Common AreaVA Castle Point Anthony Dhanpat
64 0.1 mg/cm2 Negative 5/15/2020 11:16:31 Lead Paint Calibrate Metal Gray Poor Common AreaVA Castle Point Anthony Dhanpat
65 0.1 mg/cm2 Negative 5/15/2020 11:16:41 Lead Paint Calibrate Metal Gray Poor Common AreaVA Castle Point Anthony Dhanpat
66 0 mg/cm2 Negative 5/15/2020 11:16:48 Lead Paint Calibrate Metal Gray Poor Common AreaVA Castle Point Anthony Dhanpat
Appendix B:
Positive Lead Shots Diagram
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
DESIGN DEVELOPMENT
Office of
Construction and Facilities
Management U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEER
WATSON ENGINEERING
1112 STATE ROUTE 434
OWEGO NY, 13827
(607)-223-4334
REPLACE DOMESTIC HOT
WATER SYSTEMS
CASTLE POINT VA CAMPUS
620A4-19-122
19 - 20 - 21 Project Director
04/30/2020 EMW CDPRevisions: Date:
BUILDING 19, 20, 21
ARCHITECTURAL PLAN
A-101
KEYED NOTES
SCALE: 3/8" = 1'-0"
BUILDING 19 ARCHITECTURAL PLAN
F1
SCALE: 1" = 100'-0"
KEY PLAN
SCALE: 3/8" = 1'-0"
BUILDING 20 ARCHITECTURAL PLAN
F5
SCALE: 3/8" = 1'-0"
BUILDING 21 ARCHITECTURAL PLAN
C5
REPLACE EXISTING DOOR AND FRAME. SEE
DOOR SCHEDULE.
EXISTING FLOORS SHALL BE REFINISHED WITH
STONHARD STONGARD MR OR EQUIVALENT
3 EXISTING WALLS IN ROOM SHALL BE PAINTED.
REFER TO SCHEDULES FOR DETAILS.
SCALE: 3/8" = 1'-0"
BUILDING 20 ARCHITECTURAL PLAN
F8
2 3
DOOR HARDWARE SCHEDULE
SET NO. HINGES LOCK SERIES
PUSH
PLATES CLOSERS HOLDERS PLATES REMARKS
11C
A8111
/A5111 F07 J302
C02011/
C02021 L02121 J102
MECHANICAL ROOM - REFER TO
SPECIFICATION
DOOR SCHEDULE
NO. ROOM SIZE MATERIAL TYPE FRAME LABEL HARDWARE REMARKS
1 A-001 4'-0" X 7'-0" X 1 3/4" HOLLOW METAL HOLLOW METAL 1-HR 11C
2 A-002 3'-6" X 7'-0" X 1 3/4" HOLLOW METAL HOLLOW METAL 1-HR 11C
3 B-001 3'-6" X 7'-0" X 1 3/4"
HOLLOW METAL HOLLOW METAL 1-HR 11C
4 B-005 3'-6" X 7'-0" X 1 3/4" HOLLOW METAL HOLLOW METAL 1-HR 11C
5 C-001 3'-6" X 7'-0" X 1 3/4" HOLLOW METAL HOLLOW METAL 1-HR 11C
ROOM FINISH SCHEDULE
RO
O
M N
U M
BE
R
ROOM NAME FL
O
O R
FI
N
IS
H
WALL FINISH CEILINGS
RE
M
AR
KS
PL
AN
N O
RT
H
PL
AN
E
AS
T
PL
AN
S O
U
TH
PL
AN
W
ES
T
C O
V E
B
A S
E
A
L L
W
A L L S
FI
N
IS
H
A-001 TANK RM
STONGARD MR
PEWTER WHITE WHITE WHITE WHITE
S T
O N
G A
R D
O
V E
R L A
Y M
E N
T
P E
W T
E R
EXISTING
A-002 MECHANICAL
STONGARD MR
PEWTER WHITE WHITE WHITE WHITE EXISTING
B-001 TANK RM
STONGARD MR
PEWTER WHITE WHITE WHITE WHITE EXISTING
B-005 MECHANICAL
STONGARD MR
PEWTER WHITE WHITE WHITE WHITE EXISTING
C-001 TANK RM
STONGARD MR
PEWTER WHITE WHITE WHITE WHITE EXISTING
4 INSTALL NEW EQUIPMENT PADS. REFER TO
DETAIL 7/P-501. L & W DIMENSIONS SHALL BE 6"
GREATER THAN THE EQUIPMENT BASE PLATE.
F1
F5
F8
C5
AutoCAD SHX Text
UP
AutoCAD SHX Text
TANK
AutoCAD SHX Text
TUNNEL
AutoCAD SHX Text C-001
AutoCAD SHX Text
MECH ROOM
AutoCAD SHX Text C-002
AutoCAD SHX Text
ELECT.
AutoCAD SHX Text B-005
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text B-006
AutoCAD SHX Text
UP
AutoCAD SHX Text
TANK
AutoCAD SHX Text B-001
AutoCAD SHX Text
STEAM RM
AutoCAD SHX Text B-002
AutoCAD SHX Text
TUNNEL
AutoCAD SHX Text
TANK RM
AutoCAD SHX Text A-001
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text A-002
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text A-003
AutoCAD SHX Text A-003
AutoCAD SHX Text A-003
AutoCAD SHX Text A-003
AutoCAD SHX Text A-003 mrive Rectangle mrive Rectangle mrive Rectangle mrive Callout mrive Callout mrive Callout mrive Callout mrive Rectangle mrive Callout mrive Callout mrive Callout mrive Callout mrive Rectangle mrive Rectangle mrive Rectangle mrive Callout mrive Callout mrive Callout mrive Rectangle mrive Rectangle mrive Callout mrive Callout mrive Text Box Building 19, 20, and 21 Positive Lead Shot Locations
Appendix C:
Lead Inspector/Risk Assessor, Company Certifications
| Lead Shot Locations.pdf |
| Replace Domestic Hot Water-T-001 |
| Sheets and Views |
| Replace Domestic Hot Water-T-001 |
| Replace Domestic Hot Water-G-001 |
| Sheets and Views |
| Replace Domestic Hot Water-G-001 |
| Replace Domestic Hot Water-A-001 |
| Sheets and Views |
| Replace Domestic Hot Water-A-001 |
| Replace Domestic Hot Water-A-101 |
| Sheets and Views |
| Replace Domestic Hot Water-A-101 |
| Replace Domestic Hot Water-P-001 |
| Sheets and Views |
| Replace Domestic Hot Water-P-001 |
| Replace Domestic Hot Water-PD101 |
| Sheets and Views |
| Replace Domestic Hot Water-PD101 |
| Replace Domestic Hot Water-PD102 |
| Sheets and Views |
| Replace Domestic Hot Water-PD102 |
| Replace Domestic Hot Water-PD103 |
| Sheets and Views |
| Replace Domestic Hot Water-PD103 |
| Replace Domestic Hot Water-P-101 |
| Sheets and Views |
| P-101 |
| Replace Domestic Hot Water-P-102 |
| Sheets and Views |
| P-102 |
| Replace Domestic Hot Water-P-103 |
| Sheets and Views |
| P-103 |
| Replace Domestic Hot Water-P-501 |
| Sheets and Views |
| Replace Domestic Hot Water-P-501 |
| Replace Domestic Hot Water-P-601 |
| Sheets and Views |
| Replace Domestic Hot Water-P-601 |
| Replace Domestic Hot Water-E-001 |
| Sheets and Views |
| Replace Domestic Hot Water-E-001 |
| Replace Domestic Hot Water-E-101 |
| Sheets and Views |
| Replace Domestic Hot Water-E-101 |
| Replace Domestic Hot Water-E-201 |
| Sheets and Views |
| Replace Domestic Hot Water-E-201 |
| Replace Domestic Hot Water-E-501 |
| Sheets and Views |
| Replace Domestic Hot Water-E-501 |
File details come from the government source that posted it. Updated .