This notice solicits bids for a service-disabled veteran-owned small business set-aside contract to replace domestic hot water systems at three buildings at the Castle Point VA Medical Center in Wappingers Falls, New York. The scope of work includes removing existing systems, installing new steam-fired water heaters, and connecting them to steam supply, condensate return, and domestic water lines. The contract is classified under NAICS code 237110 with a size standard of $36.5 million. The cost estimate range is $500,000 to $1 million. The period of performance is 270 calendar days from notice to proceed. Bids are due by March 26, 2021. The solicitation will be posted on beta.SAM.gov on or around that date. Responses must be submitted in hard copy to the point of contact, Aletha Bourke at Aletha.Bourke@va.gov.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AIRTEK ENVIRONMENTAL CORP.

39 – 37 29th Street, Long Island City, New York, 11101 Phone (718) 937-3720 Fax (718) 937-3721 www.airtekenv.com

LIMITED ASBESTOS INSPECTION REPORT

Conducted At:

VA Hudson Valley Health Care System

41 Castle Point Rd Building 19, 20, and 21

Wappingers Falls, NY 12590

Prepared For:

Watson Engineering, PC 1112 State Route 434

Owego, New York 13827

Prepared by:

Airtek Environmental Corp.

39-37 29 th

Street Long Island City, NY 11101

Airtek Project No: 20-0257

May 27. 2020

TABLE OF CONTENTS

Page No.

1.0 BACKGROUND

2.0 SCOPE OF WORK

3.0 AIRTEK INSPECTION RESULTS

4.0 CONCLUSIONS AND RECOMMENDATIONS

5.0 AREAS NOT INSPECTED

6.0 REPORT CERTIFICATIONS

APPENDICES

APPENDIX A: ACM Location Diagram

APPENDIX B: Analytical Results and Chain of Custody

APPENDIX C: Accreditation

Limited Asbestos Inspection Report May 27 th

, 2020 Airtek Project #: 20-0257 Page 1

1.0 BACKGROUND

Airtek Environmental Corp. has conducted a limited asbestos inspection for the presence of Asbestos-Containing Materials (ACM) with the potential to be disturbed at the following:

Site: VA Hudson Valley Health Care System- 41 Castle Point Rd, Wappingers

Falls, NY 12590

Area Inspected: Basement – Building 19, 20, and 21

Scope of Work: Limited inspection of accessible areas for ACM, sampling and quantification of suspect materials.

The Investigator and Inspector responsible for this project were:

Keith Dalbon NYS DOL Asbestos Inspector #16-14838 Exp.: 06/2020

Michael Rivera NYS DOL Asbestos Inspector #14-18878 Exp.: 07/2020

Site Visit: 05/7/2020

Report Date: May 27, 2020

Field Procedures and Analysis Methodology:

Guidelines used for the inspection were established by the Environmental Protection Agency (EPA) in the Guidance for Controlling Asbestos Containing Materials in Buildings, Office of Pesticides and Toxic Substances, DOC #560/5-85-024 and 40 CFR Part 763.

Field information was organized as per the concept of homogenous material. A homogenous material is defined as a suspect material of similar age, appearance, function and texture. Each material was grouped together as a specific homogenous material, sampled and then assessed for condition.

Bulk samples of suspect ACM were analyzed by Polarized Light Microscopy (PLM) with dispersion staining, as described in 40 CFR Part 763 and the National Emissions Standard for Hazardous Air Pollutants (NESHAPS).

The New York State Department of Health has recently revised the PLM Stratified Point Counting Method. The new method, “Polarized Light Microscopy Methods for Identifying and Quantitating Asbestos in Bulk Samples” can be found as item 198.1 in the Environmental Laboratory Approval Program (ELAP) Certification manual.

The State of New York ELAP has determined that analysis of Non-friable, Organically Bound Materials (NOB) are not reliably performed by PLM. Therefore, if PLM analysis of a NOB yields a negative result, it must be further confirmed by Transmission Electron Microscopy (TEM).

All samples were initially analyzed by PLM. Samples which produced a negative PLM result and which are classified as a NOB were then re-analyzed utilizing the TEM methodology.

This report contains data which was produced by Airtek’s Laboratory ( 39-37 29th Street, LIC, NY 11101) accredited by ELAP #11040 & NVLAP #102011-0 for bulk asbestos fiber analysis

, 2020 Airtek Project #: 20-0257 Page 2

2.0 SCOPE OF WORK

At the following address, a limited asbestos inspection in support of the fire protection upgrade project was conducted to verify the quantities of ACM that are associated with the property:

VA Hudson Valley Health Care System- 41 Castle Point Rd, Building 19, 20, and 21, Wappingers Falls, NY 12590

The inspection was characterized by a close visual inspection of all accessible areas for suspect ACM. Suspect materials were sampled and inventoried for quantity, condition and friability.

3.0 AIRTEK INSPECTION RESULTS

The following table presents inspection results, by homogeneous materials, obtained during Airtek’s investigation:

TABLE 1

SUMMARY OF INSPECTION RESULTS

41 CASTLE POINT RD, BUILDING 19, 20, AND 21, WAPPINGERS FALLS, NY 12590

Suspect ACM That May Be Affected

Lab Result

Approximate

ACM

Quantity Notes/ Location

Building 19

Fiberglass Pipe Wrap NAD 0

Room C-001

Brick Mortar NAD 0

Wall Paint NAD 0

Red Fire Stop NAD 0

Wall Plaster (white and brown) NAD 0

Pipe Elbow NAD 0 Outside Room C-001

Building 20

Sheetrock NAD 0 Room B-005

Spray on Fireproofing NAD 0

Wall Plaster (white and brown) NAD 0

Room B-001

Wall Paint NAD 0

Brick Mortar NAD 0

Fiberglass Pipe Wrap NAD 0

Red Fire Stop NAD 0

Door Frame Grout NAD 0

Building 21

Pressure Regulator Gasket NAD 0

Room A-002

Hot Water Heater Gasket NAD 0

Wall Paint NAD 0

Concrete Floor Patch NAD 0

Brick Mortar NAD 0

Wall Plaster (brown only) NAD 0 Room A-001

Wall Paint NAD 0

NAD = No Asbestos Detected ACM = Asbestos Containing Material

, 2020 Airtek Project #: 20-0257 Page 3

4.0 CONCLUSIONS AND RECOMMENDATIONS

Asbestos-containing materials were not identified in the spaces accessible to Airtek during our site visit. Asbestos abatement is not required prior to demolition or renovation.

If additional materials are identified that are not listed in this report and have not been tested, they must be assumed to be ACM until tested.

5.0 AREAS NOT INSPECTED

Airtek inspected and sampled materials, which were observable and accessible to the survey team. If materials were not accessible and not sampled, they are assumed ACM unless tested to confirm that they are ACM or non-ACM by laboratory analysis.

6.0 REPORT CERTIFICATIONS

Airtek certifies that the information contained herein is based on the physical and visual inspections conducted by Airtek and data collected during the inspection survey and file review.

Sincerely yours, Michael Rivera

Michael Rivera Project Manager

Airtek Project #: 20-0257 Page 4

APPENDIX A

Sample Location Diagram

MPS

CR

MPS

CR

MPS

CR

MPS

CR

MPS

CR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

DESIGN DEVELOPMENT

Office of

Construction and Facilities

Management U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEER

WATSON ENGINEERING

1112 STATE ROUTE 434

OWEGO NY, 13827

(607)-223-4334

REPLACE DOMESTIC HOT

WATER SYSTEMS

CASTLE POINT VA CAMPUS

620A4-19-122

19 - 20 - 21 Project Director

04/30/2020 EMW CDPRevisions: Date:

BUILDING 19 DEMOLITION

PLAN

PD101

SCALE: 1" = 100'-0"

KEY PLAN

SCALE: 1/8" = 1'-0"

BUILDING 19 DEMOLITION PLAN

F1

SCALE: 3/8" = 1'-0"

ENLARGED TANK ROOM DEMOLITION PLAN

F7

KEYED NOTES

1 REMOVE ALL EXISTING PIPING INSULATION IN ROOM C-001 AND

REPAIR ANY DAMAGED PIPING. ASSUME 185' OF 3" OR SMALLER.

F7

PD101

2 DEMOLISH EXISTING HOT WATER PIPING (1-1/2") IN

TUNNEL (APPROX. 240')

3 DEMOLISH EXISTING HOT WATER RETURN PIPING (3/4") IN

TUNNEL (APPROX. 120')

SCALE: 1/2" = 1'-0"

EXISTING ROOM C-001 DOMESTIC PIPING

C1

3" DCW MAIN SUPPLY

3" DCW MAIN

SUPPLY

CLOSED

1" DHW

3/4" DHWR

2" DCW

1-1/2" DCW

1" DHW

4 DEMOLISH EXISTING HOT WATER PIPING (1-1/2") IN TANK

ROOM TO MANUAL VALVE (APPROX. 50')

5 DEMOLISH EXISTING HOT WATER RETURN PIPING (3/4") IN

TANK ROOM BACK TO MANUAL VALVE (APPROX. 50')

4 5

C1

PD101

18,19,20

14, 17

4, 9, 10

1,2, 3

7,8

5,12,15

13,16

Bulk Sample Locations Building 19

MPS

CR

MPS

CR

MPS

CR

MPS

CR

MPS

CR

MPS

CR

MPS

CR

MPS

CR

MPS

CR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

DESIGN DEVELOPMENT

Office of

Construction and Facilities

Management U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEER

WATSON ENGINEERING

1112 STATE ROUTE 434

OWEGO NY, 13827

(607)-223-4334

REPLACE DOMESTIC HOT

WATER SYSTEMS

CASTLE POINT VA CAMPUS

620A4-19-122

19 - 20 - 21 Project Director

04/30/2020 EMW CDPRevisions: Date:

BUILDING 20 DEMOLITION

PLAN

PD102

SCALE: 1/8" = 1'-0"

BUILDING 20 DEMOLITION PLAN

F1

SCALE: 3/8" = 1'-0"

ENLARGED MECHANICAL ROOM DEMOLITION PLAN

F8

KEYED NOTES

1 REMOVE ALL EXISTING PIPING INSULATION IN ROOM B-001 AND

REPAIR ANY DAMAGED PIPING. ASSUME 145' OF 4" OR SMALLER.

F8

PD102

SCALE: 1" = 100'-0"

KEY PLAN

2 DEMOLISH EXISTING HOT WATER PIPING (1-1/2") IN

TUNNEL (APPROX. 240').

3 DEMOLISH EXISTING HOT WATER RETURN (3/4")PIPING IN

TUNNEL (APPROX. 240')

SCALE: 1/2" = 1'-0"

EXISTING ROOM B-001 DOMESTIC PIPING

C1

3/4" DHWR

1-1/2" DHW

3/4" DHWR

1-1/2" DHW

4" DCW 3/4" DCW

3/4" DHWR

1-1/2" DHW

4 DEMOLISH EXISTING HOT WATER PIPING (1-1/2") IN ROOM

B-001 BACK TO MANUAL VALVE (APPROX. 20')

5 DEMOLISH EXISTING HOT WATER RETURN PIPING (3/4") IN

ROOM B-001 TO MANUAL VALVE (APPROX. 20')

C1

PD102

4 5

37, 38, 39

32,33, 34 28,31

40, 41, 42

27, 30

43, 44

26, 29

21- 25

35,36

Building 20

MPS

CR

MPS

CR

MPS

CR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

DESIGN DEVELOPMENT

Office of

Construction and Facilities

Management U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEER

WATSON ENGINEERING

1112 STATE ROUTE 434

OWEGO NY, 13827

(607)-223-4334

REPLACE DOMESTIC HOT

WATER SYSTEMS

CASTLE POINT VA CAMPUS

620A4-19-122

19 - 20 - 21 Project Director

04/30/2020 EMW CDPRevisions: Date:

BUILDING 21 DEMOLITION

PLAN

PD103

KEYED NOTES

DEMOLISH EXISTING SEMI-INSTANTANEOUS STEAM HOT

WATER HEATERS (3) AND ASSOCIATED PIPING. ASSUME

270' OF 4" OR SMALLER.

REMOVE ALL EXISTING PIPING INSULATION IN ROOM A-001 AND

REPAIR ANY DAMAGED PIPING. ASSUME 110' OF 1-1/2" OR SMALLER.

SCALE: 1" = 100'-0"

KEY PLAN

3 DEMOLISH EXISTING CONDENSATE PUMPS

SCALE: 3/4" = 1'-0"

TUNNEL PIPING SECTION

C5

CHILLED WATER RETURN

CHILLED WATER SUPPLY

1-1/2" DOM HOT WATER SUPPLY

3/4" DOM HOT WATER RETURN

3/4" DOM HOT WATER RETURN

4 DEMOLISH EXISTING HOT WATER PIPING (1-1/2") IN

TUNNEL (APPROX. 240')

5 DEMOLISH EXISTING HOT WATER RETURN PIPING (3/4") IN

TUNNEL (APPROX. 240')

1-1/2" DOM HOT WATER SUPPLY

4" DOM COLD WATER

1-1/2" DOM COLD WATER

1" DOM HOT WATER

7'-8"

8'-3"

SCALE: 1/8" = 1'-0"

BUILDING 21 DEMOLITION PLAN

F1

SCALE: 3/8" = 1'-0"

ENLARGED MECHANICAL ROOM DEMOLITION PLAN

F7

F7

P-103

3/4" DHWR RISER

1-1/2" DHW RISER

3/4" DHWR RISER

1-1/2" DHW RISER

2" DCW

1-1/2" DHW

1/2" DHWR

FIRE LINE

C5

PD103

48,49,50

54,55,56

45,46,47

57,58

51,52

59, 60, 61

Building 21

Airtek Project #: 20-0257 Page 5

APPENDIX B

Analytical Results and Chain of Custody

Test Report: Asbestos Analysis of Bulk Material

Airtek Project No.: 20-0257

Watson Engineering

Project Address: VA Medical Center

Castle Point

Attn:

Address:

Fax:

Phone:

Project Manager:

Sample Description / Test Fibrous Non-Fibrous Asbestos Comment Vermiculite

Company:

39-37 29th Street Long Island City, NY 11101

Phone: (718) 937-3720

Fax: (718) 937-3721

Sample 20-0228-1 Fiberglass pipe wrap

Building 19- room C-001

Layer 1 Tan Homogeneous Fibrous

28.00% Fiberglass None Detected /

Inconclusive

32.70% ResiduePLM NYS 198.6 NOB 5/21/2020 Fbglss=isotropicNone Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-2 Fiberglass pipe wrap

Building 19- room C-001

Layer 1 Tan Homogeneous Fibrous

25.00% Fiberglass None Detected /

Inconclusive

48.60% ResiduePLM NYS 198.6 NOB 5/21/2020 Fbglss=isotropicNone Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-3 Fiberglass pipe wrap

Building 19- room C-001

Layer 1 Tan Homogeneous Fibrous

None Detected /

Inconclusive

47.20% ResiduePLM NYS 198.6 NOB 5/21/2020 Fbglss=isotropicNone Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-4 Brick mortar

Building 19- room C-001

Layer 1 Gray Homogeneous Non-Fibrous

Friday, May 29, 2020 Page 1 of 12

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-5 Brick mortar

Building 19- room C-001

Layer 1 Gray Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-6 Wall paint

Building 19- room C-001

Layer 1 Tan Homogeneous Non-Fibrous

None Detected /

Inconclusive

28.20% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-7 Wall paint

Building 19- room C-001

Layer 1 Tan Homogeneous Non-Fibrous

None Detected /

Inconclusive

14.50% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-8 Wall paint

Building 19- room C-001

Layer 1 Tan Homogeneous Non-Fibrous

None Detected /

Inconclusive

39.60% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-9 Red fire stop

Building 19- room C-001

Layer 1 Red Homogeneous Non-Fibrous

None Detected /

Inconclusive

27.40% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Friday, May 29, 2020 Page 2 of 12

Sample 20-0228-10 Red fire stop

Building 19- room C-001

Layer 1 Red Homogeneous Non-Fibrous

None Detected /

Inconclusive

62.00% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-11 Red fire stop

Building 19- room C-001

Layer 1 Red Homogeneous Non-Fibrous

None Detected /

Inconclusive

71.50% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-12 Wall plaster- white

Building 19- room C-001

Layer 1 White Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-13 Wall plaster- white

Building 19- room C-001

Layer 1 White Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-14 Wall plaster- white

Building 19- room C-001

Layer 1 White Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-15 Wall plaster- brown

Building 19- room C-001

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-16 Wall plaster- brown

Building 19- room C-001

Friday, May 29, 2020 Page 3 of 12

Layer 1 Brown Homogeneous Non-Fibrous

Sample 20-0228-17 Wall plaster- brown

Building 19- room C-001

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-18 Pipe elbow

Building 19- room C-001

Layer 1 Brown Homogeneous Fibrous

19.00% Fiberglass None DetectedPLM NYS 198.1 Friable 5/21/2020 Fbglss=isotropicNone Detected

Sample 20-0228-19 Pipe elbow

Building 19- room C-001

Layer 1 Brown Homogeneous Fibrous

22.00% Fiberglass None DetectedPLM NYS 198.1 Friable 5/21/2020 Fbglss=isotropicNone Detected

Sample 20-0228-20 Pipe elbow

Building 19- room C-001

Layer 1 Brown Homogeneous Fibrous

21.00% Fiberglass None DetectedPLM NYS 198.1 Friable 5/21/2020 Fbglss=isotropicNone Detected

Sample 20-0228-21 Sheetrock

Building 20- room B-005

Layer 1 White/Brown Heterogeneous Fibrous

11.00% Cellullose

4.00% Fiberglass

None DetectedPLM NYS 198.1 Friable 5/21/2020 Cell=ribbons/Fbglss=isotropicNone Detected

Sample 20-0228-22 Sheetrock

Building 20- room B-005

Layer 1 White/Brown Heterogeneous Fibrous

12.00% Cellullose

4.00% Fiberglass

None DetectedPLM NYS 198.1 Friable 5/21/2020 Cell=ribbons/Fbglss=isotropicNone Detected

Sample 20-0228-23 Spray-on

Building 20- room B-005

Friday, May 29, 2020 Page 4 of 12

Layer 1 Tan Homogeneous Fibrous

9.00% Cellullose None DetectedPLM NYS 198.1 Friable 5/21/2020 Cell=ribbonsNone Detected

Sample 20-0228-24 Spray-on

Building 20- room B-005

Layer 1 Tan Homogeneous Fibrous

8.00% Cellullose None DetectedPLM NYS 198.1 Friable 5/21/2020 Cell=ribbonsNone Detected

Sample 20-0228-25 Spray-on

Building 20- room B-005

Layer 1 Tan Homogeneous Fibrous

9.00% Cellullose None DetectedPLM NYS 198.1 Friable 5/21/2020 Cell=ribbonsNone Detected

Sample 20-0228-26 Wall plaster- white

Building 20- room B-001

Layer 1 White Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-27 Wall plaster- white

Building 20- room B-001

Layer 1 White Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-28 Wall plaster- white

Building 20- room B-001

Layer 1 White Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-29 Wall plaster- brown

Building 20- room B-001

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-30 Wall plaster- brown

Building 20- room B-001

Friday, May 29, 2020 Page 5 of 12

Sample 20-0228-31 Wall plaster- brown

Building 20- room B-001

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-32 Wall paint

Building 20- room B-001

Layer 1 Tan Homogeneous Non-Fibrous

None Detected /

Inconclusive

36.40% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-33 Wall paint

Building 20- room B-001

Layer 1 Tan Homogeneous Non-Fibrous

None Detected /

Inconclusive

47.50% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-34 Wall paint

Building 20- room B-001

Layer 1 Tan Homogeneous Non-Fibrous

None Detected /

Inconclusive

22.10% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-35 Brick mortar

Building 20- room B-001

Layer 1 Gray Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-36 Brick mortar

Building 20- room B-001

Layer 1 Gray Homogeneous Non-Fibrous

Friday, May 29, 2020 Page 6 of 12

Sample 20-0228-37 Fiberglass pipe wrap

Building 20- room B-001

Layer 1 Tan Homogeneous Fibrous

16.00% Fiberglass None Detected /

Inconclusive

26.90% ResiduePLM NYS 198.6 NOB 5/21/2020 Fbglss=isotropicNone Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-38 Fiberglass pipe wrap

Building 20- room B-001

Layer 1 Tan Homogeneous Fibrous

18.00% Fiberglass None Detected /

Inconclusive

31.00% ResiduePLM NYS 198.6 NOB 5/21/2020 Fbglss=isotropicNone Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-39 Fiberglass pipe wrap

Building 20- room B-001

Layer 1 Tan Homogeneous Fibrous

17.00% Fiberglass None Detected /

Inconclusive

36.20% ResiduePLM NYS 198.6 NOB 5/21/2020 Fbglss=isotropicNone Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-40 Red fire stop

Building 20- room B-001

Layer 1 Red Homogeneous Non-Fibrous

None Detected /

Inconclusive

18.70% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-41 Red fire stop

Building 20- room B-001

Layer 1 Red Homogeneous Non-Fibrous

None Detected /

Inconclusive

19.10% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

Friday, May 29, 2020 Page 7 of 12

Sample 20-0228-42 Red fire stop

Building 20- room B-001

Layer 1 Red Homogeneous Non-Fibrous

None Detected /

Inconclusive

25.60% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-43 Door frame grout

Building 20- room B-001

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-44 Door frame grout

Building 20- room B-001

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-45 Pressure regulator gasket

Building 21- room A-002

Layer 1 Gray Homogeneous Non-Fibrous

None Detected0.45% ResiduePLM NYS 198.6 NOB 5/21/2020 * Res < 1%None Detected

Sample 20-0228-46 Pressure regulator gasket

Building 21- room A-002

Layer 1 Gray Homogeneous Non-Fibrous

None Detected /

Inconclusive

13.00% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-47 Pressure regulator gasket

Building 21- room A-002

Layer 1 Gray Homogeneous Non-Fibrous

None Detected /

Inconclusive

26.70% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

Friday, May 29, 2020 Page 8 of 12

Sample 20-0228-48 Hot water heater gasket

Building 21- room A-002

Layer 1 Green Homogeneous Non-Fibrous

None Detected /

Inconclusive

71.80% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-49 Hot water heater gasket

Building 21- room A-002

Layer 1 Green Homogeneous Non-Fibrous

None Detected /

Inconclusive

64.40% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-50 Hot water heater gasket

Building 21- room A-002

Layer 1 Green Homogeneous Non-Fibrous

None Detected /

Inconclusive

63.10% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-51 Wall paint

Building 21- room A-002

Layer 1 Gray Homogeneous Non-Fibrous

None Detected /

Inconclusive

4.50% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-52 Wall paint

Building 21- room A-002

Layer 1 Gray Homogeneous Non-Fibrous

None Detected /

Inconclusive

3.70% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

Friday, May 29, 2020 Page 9 of 12

Sample 20-0228-53 Wall paint

Building 21- room A-002

Layer 1 Gray Homogeneous Non-Fibrous

None Detected /

Inconclusive

10.70% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-54 Concrete floor patch

Building 21- room A-002

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-55 Concrete floor patch

Building 21- room A-002

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-56 Concrete floor patch

Building 21- room A-002

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-57 Brick mortar

Building 21- room A-002

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-58 Brick mortar

Building 21- room A-002

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-59 Wall plaster (brown)

Building 21- room A-001

Friday, May 29, 2020 Page 10 of 12

Sample 20-0228-60 Wall plaster (brown)

Building 21- room A-001

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-61 Wall plaster (brown)

Building 21- room A-001

Layer 1 Brown Homogeneous Non-Fibrous

None DetectedPLM NYS 198.1 Friable 5/21/2020 None Detected

Sample 20-0228-62 Wall paint

Building 21- room A-001

Layer 1 Gray Homogeneous Non-Fibrous

None Detected /

Inconclusive

15.30% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-63 Wall paint

Building 21- room A-001

Layer 1 Gray Homogeneous Non-Fibrous

None Detected /

Inconclusive

35.70% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

None DetectedTEM NYS 198.4 NOB 5/21/2020 Not Analyzed

Sample 20-0228-64 Wall paint

Building 21- room A-001

Layer 1 Gray Homogeneous Non-Fibrous

None Detected /

Inconclusive

19.70% ResiduePLM NYS 198.6 NOB 5/21/2020 None Detected

Friday, May 29, 2020 Page 11 of 12

Method: PLM with EPA 600/M4/82/020, ELAP 198.1 and ELAP 198.6; TEM by ELAP 198.4

Methods of stratified point-counting or negative scanning are used on at least 4 mounts, as per 198.1

Polarized light microscopy is not consistently reliable in detecting asbestos in floor covering/non-friable organically bound materials (NOB's).

NOB's should be analyzed by quantitative TEM. The above test report relates only to item tested.

Layered samples are analyzed by layer. Any positive layer will be reported separately.

Asbetos percentage is based on point-counting rules described in ELAP 198.1

*VERMICULTE NOTE DISCLAIMER: Samples that contain more than 10% vermiculite are re-analyzed by ELAP method 198.6. This method does not remove verimculite and may underestimate the level of asbestos containing greater than 10% vermiculite.

Attic fill, block fill or other loose bulk Vermiculite materials must be designated and treated as ACM per NYSDOH

All Surfacing Materials containing vermiculite must be analyzed by a laboratory approved for ELAP 198.8

Airtek collects samples in accordance with EPA 40 CFR Part 763.

This report should not be used to claim product certification, approval or endorsement by NVLAP, NIST or any agency of the federal government and may not be reproduced, except in full, without written approval by Airtek.

Currently approved by ELAP (11040) for Asbestos in Friable Material item 198.1 and EPA 600/M4/82/020, asbestos in Non Friable Materials 198.6 (NOB by PLM) and asbestos in Non Friable

Material 198.4 (TEM)

Currently accredited by the NVLAP lab code 102011-0 for Bulk Asbestos Analysis (PLM) EPA 600/M4/82/020.

This report relates only to the samples reported above and must not be reproduced except in full with the approval of the laboratory.

Efren Martinez, Lab Analyst

Analysts: Efren Martinez

Friday, May 29, 2020 Page 12 of 12

Airtek Project #: 20-0257 Page 6

APPENDIX C

Accreditation

New York State – Department of Labor Division of Safety and Health License and Certificate Unit State Campus, Building 12

Albany, NY 12240

ASBESTOS HANDLING LICENSE

39-37 29th Street

Long Island City, NY 11101

FILE NUMBER: 99-0589

LICENSE NUMBER: 28638

LICENSE CLASS: RESTRICTED

DATE OF ISSUE: 06/13/2019

EXPIRATION DATE: 06/30/2020

Duly Authorized Representative – Saad Zouak:

This license has been issued in accordance with applicable provisions of Article 30 of the Labor Law of New York State and of the New York State Codes, Rules and Regulations (12 NYCRR Part 56). It is subject to suspension or revocation for a (1) serious violation of state, federal or local laws with regard to the conduct of an asbestos project, or (2) demonstrated lack of responsibility in the conduct of any job involving asbestos or asbestos material.

This license is valid only for the contractor named above and this license or a photocopy must be prominently displayed at the asbestos project worksite. This license verifies that all persons employed by the licensee on an asbestos project in New York State have been issued an Asbestos Certificate, appropriate for the type of work they perform, by the New York State Department of Labor.