- Fire Dampers Repairs and Installation Federal contract opportunity
- Solicitation number
- 36C24220R0038
About this file
This document outlines a federal contract solicitation for fire damper repairs, testing, and new installation at the Department of Veterans Affairs Medical Center in Northport, New York. The solicitation seeks bids for inspection, testing, repair, and tagging of existing fire dampers as well as installation of new fire dampers. Bidders must be currently registered as a Veteran-Owned Small Business in SAM.gov and VIP.vetbiz.gov. The total project duration is 180 days with work coordinated through the Contracting Officer's Representative. Bids are due by the date specified in the solicitation to be released on or about January 30, 2020. The winning bidder must provide bonding, insurance, and a one-year warranty on parts and labor.
36C24220R0038 Exhibit 2 Fire Smoke Dampers to be Tested Rev 2 as of 12-26-19.xlsx
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24220R0038-003.docx | DOCX document | |
| 36C24220R0038-002.txt | TXT text file | |
| 36C24220R0038-004.pdf | ||
| 36C24220R0038-006.xlsx | XLSX spreadsheet | |
| 36C24220R0038-005.xlsx | XLSX spreadsheet | |
| 36C24220R0038-007.pdf | ||
| 36C24220R0038-001.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building 200 Exhibit 2
| Location | Damper Number (Report) | Damper ID (Plans) | Damper Location | Damper Type | Current Status | VA Required? (Y/N) | VA Comments / Notes | VA Walkthrough Comments | Project Scope | Contractor Final Report |
| Attic / Penthouse | A-FD-16-001 | 1 | Inside of the Elevator Room | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-002 | 2 | Inside of Room # P5-1 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-008 | 8 | Inside of the Women's Wellness Center | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-009 | 9 | Inside of the Women's Wellness Center | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-010 | 10 | Inside of Room #B43 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-012 | 12 | Inside of Room #B43 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-015 | 15 | Inside of the Mechanical Room Near Room # B4-24 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-016 | 16 | Inside of the Mechanical Room Near Room # B4-24 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-017 | 17 | Inside of the Mechanical Room Near Room # B4-24 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-018 | 18 | Outside of Room # B4-05 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-019 | 19 | Inside of Room # B4-05 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-020 | 20 | Inside of Room # B4-05 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-021 | 21 | Inside of Room # B4-05 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-022 | 22 | Inside of Mechanical Room # B4-60 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-023 | 23 | Inside of Mechanical Room # B4-60 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-024 | 24 | Inside of Mechanical Room # B4-60 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-026 | 26 | Inside of the Engineering Air Conditioning Equipment Room # A4-26 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-027 | 27 | Inside of the Engineering Air Conditioning Equipment Room # A4-26 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-028 | 28 | Inside of the Engineering Air Conditioning Equipment Room # A4-26 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-029 | 29 | Inside of the Storage Room # A1-25 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Forth Floor | 4-FD-16-030 | 30 | Inside of the Housekeeping Room # A4-61B | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-014 | 14 | At Room # B3-5 | Fire | Retest | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-016 | 16 | Across from Room # B3-37 Unit Manager | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-017 | 17 | Inside of Room # B3-60 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-019 | 19 | Inside of Room # B3-25 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-021 | 21 | Inside of Room B3-3 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-022 | 22 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-023 | 23 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-024 | 24 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-025 | 25 | See Exhibit 2 | Fire | Unknown | Y | Add 16 x 16 access door to duct | Add 16" x 16" access door to duct. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Third Floor | 3-FD-16-026 | 26 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-027 | 27 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-028 | 28 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-029 | 29 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Third Floor | 3-FD-16-030 | 30 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Second Floor | Unknown | Unknown | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Second Floor Unit 22 | 2-FD-16-003A | 6 | Above the Clinical Nurse Specialist Room # A2-57 | Fire | Unknown | Y | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Sheetrock celling W/access door. Damper located in Room A2-59 bathroom. Damper is accessible. Retest damper. | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |
| Second Floor | 2-FD-16-012 | 18 | Across from Room # B2-35 | Fire | PASS | Y | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Second Floor | 2-FD-16-014 | 20 | Inside of Room # B2-26 | Fire | PASS | Y | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Second Floor | 2-FD-16-015 | 21 | In the Office Inside of the Rehab Therapy Room | Fire | PASS | Y | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Second floor Unit 24 | 2-FD-16-016 | 22 | Inside Room B2-62 | Fire | Unknown | Y | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Second Floor Unit 21 | 2-FD-16-017 | 23 | Above Room # B2-35 Door | Fire | Unknown | Y | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Sheetrock celling W/access door @ Room B2-35 Hall. | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |
| Second Floor Unit 21 | 2-FD-16-004A | 24 | Outside of Room # A2-62 | Fire | Unknown | Y | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Sheetrock celling. Add 12 x 12 access door approximately 3' North of existing 2 x 2 access door to sheetrock celling. Retest damper. | Add 12 x 12 access door approximately 3' North of existing 2 x 2 access door to sheetrock celling. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |
| First Floor | 1-FD-16-034 | 34 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-035 | 35 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-036 | 36 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-037 | 37 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-038 | 38 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-039 | 39 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-040 | 40 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-041 | 41 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-042 | 42 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-043 | 43 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-044 | 44 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-045 | 45 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-046 | 46 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-047 | 47 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-048 | 48 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-049 | 49 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-050 | 50 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-051 | 51 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-052 | 52 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-053 | 53 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-054 | 54 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-055 | 55 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | Unknown | Unknown | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-001 | 1 | Outside of Electrical Room | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-002 | 2 | Outside of Electrical Room | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-003 | 3 | Outside of Electrical Room | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-004 | 4 | Outside of Electrical Room | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-005 | 5 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-006 | 6 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-007 | 7 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-008 | 8 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-009 | 9 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-010 | 10 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-011 | 11 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-012 | 12 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-013 | 13 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-014 | 14 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-015 | 15 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-016 | 16 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-017 | 17 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-018 | 18 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-019 | 19 | See Exhibit 2 | Fire | Unknown | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. |
Basement
&"-,Bold"&24Exhibit 2. Building 200 Dampers. Compliance to NFPA 101
Building 200-N Exhibit 2
| Location | Damper Number (Report) | Damper ID (Plans) | Damper Location | Damper Type | Current Status | VA Required? (Y/N) | VA Comments / Notes | VA Walkthrough Comments | Project Scope | Contractor Final Report |
| Attic / Penthouse | A-FD-16-001 | 1 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-002 | 2 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-003 | 3 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-004 | 4 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-005 | 5 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-006 | 6 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-007 | 7 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-008 | 8 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-009 | 9 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-010 | 10 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-011 | 11 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-012 | 12 | Inside of the East Attic | Fire | Unknown | Y | Add 12 x 12 door on vertical section of duct below existing door, then retest damper. | Add 12" x 12" access door onto vertical section of duct. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-013 | 13 | Inside of the East Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-014 | 14 | Inside of the East Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-015 | 15 | Inside of the East Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-016 | 16 | Inside of the East Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-017 | 17 | Inside of the East Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-018 | 18 | Inside of the East Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-019 | 19 | Inside of the East Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-020 | 20 | Inside of the East Attic | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic / Penthouse | A-FD-16-021 | 21 | Inside of the East Attic | Fire | FAIL | Y | Damper consists of 44 x 24 vertical penetration through attic floor. | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Second Floor | 2-FD-16-004 | 4 | Outside of the Housekeeping Closet # D2-56 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Second Floor | 2-FD-16-005 | 5 | Inside of the Housekeeping Closet # D2-22 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Second Floor | 2-FD-16-006 | 6 | Inside of House Keeping Room D2-22 | Fire | Unknown | Y | Install additional 12 x 12 access door as required on duct @ East wall duct size 34 x 16. | Add 12" x 12" access door onto duct. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Second Floor | 2-FD-16-007 | 7 | Inside of the Hatch in Room # D2-22 | Fire | Unknown | Y | Install additional 12 x 102access door East of existing access door on duct 12 x 12 | Add 12" 12" access door East of existing access door. Add 12" x 12"acess door onto duct. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Second Floor | 2-FD-16-008 | 8 | Inside of the Hatch in Room # D2-22 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-001 | 1 | Inside of the Electrical Room # D0-30 | Fire | PASS | Y | No Exhibit for reference | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Basement | B-FD-16-006 | ERROR:#REF! | Inside of Elevator Mechanical Room # D0-1 | Fire | PASS | Y | No Exhibit for reference | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Basement | B-FD-16-007 | ERROR:#REF! | Inside of Elevator Mechanical Room # D0-1 | Fire | PASS | Y | No Exhibit for reference | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Basement | B-FD-16-018 | ERROR:#REF! | Inside of Room # E0-65 | Fire | PASS | Y | No Exhibit for reference | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Basement | B-FD-16-019 | ERROR:#REF! | Inside of Room # E0-65 | Fire | PASS | Y | No Exhibit for reference | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Basement | B-FD-16-020 | ERROR:#REF! | Inside of Room # E0-60 | Fire | Unknown | Y | No Exhibit for reference | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Basement | B-FD-16-021 | ERROR:#REF! | Inside of Room # E0-60 | Fire | PASS | Y | No Exhibit for reference | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. |
&"-,Bold"&24Exhibit 2. Building 200 North Compliance to NFPA 101
Building 8 Exhibit 2
| Location | Damper Number (Report) | Damper ID (Plans) | Damper Location | Damper Type | Current Status | VA Required? (Y/N) | VA Comments/Notes | VA Walkthrough Comments | Project Scope | Contractor Final Report |
| Attic | A-FD-16-001 | 1 | 30 Feet in Room On the Right | Fire | PASS | Y | Exhibit 2 is for reference only | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic | A-FD-16-002 | 2 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-003 | 3 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-004 | 4 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-005 | 5 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-006 | 6 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-007 | 7 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-008 | 8 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-009 | 9 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-010 | 10 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-011 | 11 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-012 | 12 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-013 | 13 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-014 | 14 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-015 | 15 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-016 | 16 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-017 | 17 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-018 | 18 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-019 | 19 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-020 | 20 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-021 | 21 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-022 | 22 | At the Elevator Shaft | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-023 | 23 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-024 | 24 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-025 | 25 | Inside of the Attic Quad 3 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-026 | 26 | Inside of the Attic Quad 3 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-027 | 27 | Inside of the Attic Quad 3 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-028 | 28 | Inside of the Attic Quad 3 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-029 | 29 | Inside of the Attic | Fire | NON-ACCESSIBLE | Y | Need 2 x 2 access door in sheet-rock celling of room 223 bathroom. No fire stopping sleeve installed. 12 x 12 duct through concrete floor in attic. | Add 2' x 2' access door in celling of bathroom of room 223. Provide approved fire stopping at concrete floor. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic | A-FD-16-030 | 30 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-031 | 31 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-032 | 32 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-033 | 33 | Inside of the Attic | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Attic | A-FD-16-034 | 34 | Inside of the Attic Quad 2 | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-001 | 1 | Inside of the Vestibule Entrance of the Building | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-002 | 2 | Above the Room Door # 134 EAP Coordinator | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-003 | 3 | Inside of the Hatch in Room # 145E | Fire | PASS | Y | Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag. |
&"-,Bold"&24Exhibit 2. Building 8 Dampers. Compliance to NFPA 101
Building 9 No Exhibit 2
| Location | Damper Number (Report) | Damper ID (Plans) | Damper Location | Damper Type | Current Status | VA Required? (Y/N) | VA Comments / Notes | VA Walkthrough Comments | Project Scope | Contractor Final Report |
| Attic / Penthouse | A-FD-16-001 | 1 | 30 Feet in Room On the Right | Fire | PASS | Y | 12 x 14 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-002 | 2 | Inside of the Attic | Fire | PASS | Y | 20 x 18 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-003 | 3 | Inside of the Attic | Fire | PASS | Y | 16 x 20 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-004 | 4 | Inside of the Attic | Fire | PASS | Y | 10 x 10 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-005 | 5 | Inside of the Attic | Fire | PASS | Y | 24 x 16 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-006 | 6 | Inside of the Attic | Fire | PASS | Y | 20 x 12 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-007 | 7 | Inside of the Attic | Fire | PASS | Y | 12 x 10 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-008 | 8 | Inside of the Attic | Fire | PASS | Y | 10 x 10 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-009 | 9 | Inside of the Attic | Fire | PASS | Y | 24 x 12 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-010 | 10 | Inside of the Attic | Fire | PASS | Y | 15 x 15 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-011 | 11 | Inside of the Attic | Fire | PASS | Y | 30 x 14 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-012 | 12 | Inside of the Attic | Fire | PASS | Y | 30 x 14 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-013 | 13 | Inside of the Attic | Fire | PASS | Y | 24 x 14 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-014 | 14 | Inside of the Attic | Fire | PASS | Y | 10 x 10 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-015 | 15 | Inside of the Attic | Fire | PASS | Y | 12 x 10 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-016 | 16 | Inside of the Attic | Fire | PASS | Y | 12 x 10 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-017 | 17 | Inside of the Attic Quad 2 | Fire | PASS | Y | 26 x 16 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-018 | 18 | Inside of the Attic Quad 2 | Fire | PASS | Y | 30 x 16 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-019 | 19 | Inside of the Attic Quad 2 | Fire | PASS | Y | 40 x 14 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-020 | 20 | Inside of the Attic Quad 2 | Fire | PASS | Y | 36 x 20 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-021 | 21 | Inside of the Attic Quad 2 | Fire | PASS | Y | 36 x 20 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-022 | 22 | At the Elevator Shaft | Fire | PASS | Y | 36 x 36 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-023 | 23 | Inside of the Attic Quad 2 | Fire | PASS | Y | 12 x 10 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-024 | 24 | Inside of the Attic Quad 2 | Fire | PASS | Y | 14 x 12 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-025 | 25 | Inside of the Attic Quad 3 | Fire | PASS | Y | 10 x 12 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-026 | 26 | Inside of the Attic Quad 3 | Fire | PASS | Y | 12 x 18 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-027 | 27 | Inside of the Attic Quad 3 | Fire | PASS | Y | 10 x 1 0 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-028 | 28 | Inside of the Attic Quad 3 | Fire | PASS | Y | 19 x 12 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-029 | 29 | Inside of the Attic Quad 3 | Fire | PASS | Y | 10 x 10 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-030 | 30 | Inside of the Attic Quad 2 | Fire | PASS | Y | 24 x 14 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-031 | 31 | Inside of the Attic Quad 2 | Fire | PASS | Y | 24 x 19 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-032 | 32 | Inside of the Attic Quad 2 | Fire | PASS | Y | 22 x 12 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-033 | 33 | Inside of the Attic Quad 3 | Fire | PASS | Y | 10 x 10 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-034 | 34 | Inside of the Attic Quad 2 | Fire | PASS | Y | 20 x 18 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-035 | 35 | Inside of the Attic Quad 2 | Fire | PASS | Y | 18 x 20 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-036 | 36 | Inside of the Attic Quad 2 | Fire | PASS | Y | 10 x 12 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-037 | 37 | Inside of the Attic Quad 2 | Fire | PASS | Y | 22 x 12 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-038 | 38 | Inside of the Attic Quad 2 | Fire | PASS | Y | 21 x 19 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| Attic / Penthouse | A-FD-16-039 | 39 | Inside of the Attic Quad 1 | Fire | PASS | Y | 20 x 18 Duct vertical penetration through concrete floor | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | ||
| First Floor | 1-FD-16-001 | 1 | Inside of the Vestibule Entrance of the Building | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-002 | 2 | Above the Room Door # 134 EAP Coordinator | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-003 | 3 | Inside of the Hatch in Room # 145E | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| First Floor | 1-FD-16-004 | 4 | Outside of Room # 121 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-001 | 1 | Inside of Room # 19 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. | |||
| Basement | B-FD-16-002 | 2 | Inside of Room # 19 | Fire | PASS | Y | Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag. |
&"-,Bold"&24Exhibit 2. Building 9 Dampers. Compliance to NFPA 101