Fire Dampers Repairs and Installation Federal contract opportunity
Solicitation number
36C24220R0038
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This document outlines a federal contract solicitation for fire damper repairs, testing, and new installation at the Department of Veterans Affairs Medical Center in Northport, New York. The solicitation seeks bids for inspection, testing, repair, and tagging of existing fire dampers as well as installation of new fire dampers. Bidders must be currently registered as a Veteran-Owned Small Business in SAM.gov and VIP.vetbiz.gov. The total project duration is 180 days with work coordinated through the Contracting Officer's Representative. Bids are due by the date specified in the solicitation to be released on or about January 30, 2020. The winning bidder must provide bonding, insurance, and a one-year warranty on parts and labor.

36C24220R0038 Exhibit 2 Fire Smoke Dampers to be Tested Rev 2 as of 12-26-19.xlsx

View the file

Other files for this federal contract opportunity

Other files attached to Fire Dampers Repairs and Installation, newest first.
File Type Posted
36C24220R0038-003.docx DOCX document
36C24220R0038-002.txt TXT text file
36C24220R0038-004.pdf PDF
36C24220R0038-006.xlsx XLSX spreadsheet
36C24220R0038-005.xlsx XLSX spreadsheet
36C24220R0038-007.pdf PDF
36C24220R0038-001.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Building 200 Exhibit 2

LocationDamper Number (Report)Damper ID (Plans)Damper LocationDamper TypeCurrent StatusVA Required? (Y/N)VA Comments / NotesVA Walkthrough CommentsProject ScopeContractor Final Report
Attic / PenthouseA-FD-16-0011Inside of the Elevator RoomFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0022Inside of Room # P5-1FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-0088Inside of the Women's Wellness CenterFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-0099Inside of the Women's Wellness CenterFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-01010Inside of Room #B43FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-01212Inside of Room #B43FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-01515Inside of the Mechanical Room Near Room # B4-24FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-01616Inside of the Mechanical Room Near Room # B4-24FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-01717Inside of the Mechanical Room Near Room # B4-24FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-01818Outside of Room # B4-05FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-01919Inside of Room # B4-05FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-02020Inside of Room # B4-05FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-02121Inside of Room # B4-05FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-02222Inside of Mechanical Room # B4-60FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-02323Inside of Mechanical Room # B4-60FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-02424Inside of Mechanical Room # B4-60FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-02626Inside of the Engineering Air Conditioning Equipment Room # A4-26FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-02727Inside of the Engineering Air Conditioning Equipment Room # A4-26FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-02828Inside of the Engineering Air Conditioning Equipment Room # A4-26FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-02929Inside of the Storage Room # A1-25FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Forth Floor4-FD-16-03030Inside of the Housekeeping Room # A4-61BFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-01414At Room # B3-5FireRetestYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-01616Across from Room # B3-37 Unit ManagerFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-01717Inside of Room # B3-60FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-01919Inside of Room # B3-25FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-02121Inside of Room B3-3FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-02222See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-02323See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-02424See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-02525See Exhibit 2FireUnknownYAdd 16 x 16 access door to ductAdd 16" x 16" access door to duct. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-02626See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-02727See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-02828See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-02929See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Third Floor3-FD-16-03030See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second FloorUnknownUnknownSee Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor Unit 222-FD-16-003A6Above the Clinical Nurse Specialist Room # A2-57FireUnknownYExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Sheetrock celling W/access door. Damper located in Room A2-59 bathroom. Damper is accessible. Retest damper.Supply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor2-FD-16-01218Across from Room # B2-35FirePASSYExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor2-FD-16-01420Inside of Room # B2-26FirePASSYExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor2-FD-16-01521In the Office Inside of the Rehab Therapy RoomFirePASSYExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second floor Unit 242-FD-16-01622Inside Room B2-62FireUnknownYExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor Unit 212-FD-16-01723Above Room # B2-35 DoorFireUnknownYExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Sheetrock celling W/access door @ Room B2-35 Hall.Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor Unit 212-FD-16-004A24Outside of Room # A2-62FireUnknownYExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Sheetrock celling. Add 12 x 12 access door approximately 3' North of existing 2 x 2 access door to sheetrock celling. Retest damper.Add 12 x 12 access door approximately 3' North of existing 2 x 2 access door to sheetrock celling. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-03434See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-03535See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-03636See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-03737See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-03838See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-03939See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04040See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04141See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04242See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04343See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04444See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04545See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04646See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04747See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04848See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-04949See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-05050See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-05151See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-05252See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-05353See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-05454See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-05555See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementUnknownUnknownSee Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0011Outside of Electrical RoomFireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0022Outside of Electrical RoomFireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0033Outside of Electrical RoomFireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0044Outside of Electrical RoomFireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0055See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0066See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0077See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0088See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0099See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01010See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01111See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01212See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01313See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01414See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01515See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01616See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01717See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01818See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-01919See Exhibit 2FireUnknownYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.

Basement

&"-,Bold"&24Exhibit 2. Building 200 Dampers. Compliance to NFPA 101

Building 200-N Exhibit 2

LocationDamper Number (Report)Damper ID (Plans)Damper LocationDamper TypeCurrent StatusVA Required? (Y/N)VA Comments / NotesVA Walkthrough CommentsProject ScopeContractor Final Report
Attic / PenthouseA-FD-16-0011Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0022Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0033Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0044Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0055Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0066Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0077Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0088Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0099Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01010Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01111Inside of the AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01212Inside of the East AtticFireUnknownYAdd 12 x 12 door on vertical section of duct below existing door, then retest damper.Add 12" x 12" access door onto vertical section of duct. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01313Inside of the East AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01414Inside of the East AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01515Inside of the East AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01616Inside of the East AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01717Inside of the East AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01818Inside of the East AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01919Inside of the East AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02020Inside of the East AtticFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02121Inside of the East AtticFireFAILYDamper consists of 44 x 24 vertical penetration through attic floor.Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor2-FD-16-0044Outside of the Housekeeping Closet # D2-56FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor2-FD-16-0055Inside of the Housekeeping Closet # D2-22FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor2-FD-16-0066Inside of House Keeping Room D2-22FireUnknownYInstall additional 12 x 12 access door as required on duct @ East wall duct size 34 x 16.Add 12" x 12" access door onto duct. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor2-FD-16-0077Inside of the Hatch in Room # D2-22FireUnknownYInstall additional 12 x 102access door East of existing access door on duct 12 x 12Add 12" 12" access door East of existing access door. Add 12" x 12"acess door onto duct. Supply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Second Floor2-FD-16-0088Inside of the Hatch in Room # D2-22FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0011Inside of the Electrical Room # D0-30FirePASSYNo Exhibit for referenceSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-006ERROR:#REF!Inside of Elevator Mechanical Room # D0-1FirePASSYNo Exhibit for referenceSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-007ERROR:#REF!Inside of Elevator Mechanical Room # D0-1FirePASSYNo Exhibit for referenceSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-018ERROR:#REF!Inside of Room # E0-65FirePASSYNo Exhibit for referenceSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-019ERROR:#REF!Inside of Room # E0-65FirePASSYNo Exhibit for referenceSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-020ERROR:#REF!Inside of Room # E0-60FireUnknownYNo Exhibit for referenceSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-021ERROR:#REF!Inside of Room # E0-60FirePASSYNo Exhibit for referenceSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.

&"-,Bold"&24Exhibit 2. Building 200 North Compliance to NFPA 101

Building 8 Exhibit 2

LocationDamper Number (Report)Damper ID (Plans)Damper LocationDamper TypeCurrent StatusVA Required? (Y/N)VA Comments/NotesVA Walkthrough CommentsProject ScopeContractor Final Report
AtticA-FD-16-001130 Feet in Room On the RightFirePASSYExhibit 2 is for reference onlySupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-0022Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-0033Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-0044Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-0055Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-0066Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-0077Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-0088Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-0099Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01010Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01111Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01212Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01313Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01414Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01515Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01616Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01717Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01818Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-01919Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02020Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02121Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02222At the Elevator ShaftFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02323Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02424Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02525Inside of the Attic Quad 3FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02626Inside of the Attic Quad 3FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02727Inside of the Attic Quad 3FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02828Inside of the Attic Quad 3FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-02929Inside of the AtticFireNON-ACCESSIBLEYNeed 2 x 2 access door in sheet-rock celling of room 223 bathroom. No fire stopping sleeve installed. 12 x 12 duct through concrete floor in attic.Add 2' x 2' access door in celling of bathroom of room 223. Provide approved fire stopping at concrete floor. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-03030Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-03131Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-03232Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-03333Inside of the AtticFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
AtticA-FD-16-03434Inside of the Attic Quad 2FirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-0011Inside of the Vestibule Entrance of the BuildingFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-0022Above the Room Door # 134 EAP CoordinatorFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-0033Inside of the Hatch in Room # 145EFirePASSYSupply and attach damper ID tag. Retest damper repair if required then retest. Affix signed and dated test sticker to space provided on damper ID tag.

&"-,Bold"&24Exhibit 2. Building 8 Dampers. Compliance to NFPA 101

Building 9 No Exhibit 2

LocationDamper Number (Report)Damper ID (Plans)Damper LocationDamper TypeCurrent StatusVA Required? (Y/N)VA Comments / NotesVA Walkthrough CommentsProject ScopeContractor Final Report
Attic / PenthouseA-FD-16-001130 Feet in Room On the RightFirePASSY12 x 14 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0022Inside of the AtticFirePASSY20 x 18 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0033Inside of the AtticFirePASSY16 x 20 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0044Inside of the AtticFirePASSY10 x 10 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0055Inside of the AtticFirePASSY24 x 16 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0066Inside of the AtticFirePASSY20 x 12 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0077Inside of the AtticFirePASSY12 x 10 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0088Inside of the AtticFirePASSY10 x 10 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-0099Inside of the AtticFirePASSY24 x 12 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01010Inside of the AtticFirePASSY15 x 15 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01111Inside of the AtticFirePASSY30 x 14 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01212Inside of the AtticFirePASSY30 x 14 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01313Inside of the AtticFirePASSY24 x 14 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01414Inside of the AtticFirePASSY10 x 10 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01515Inside of the AtticFirePASSY12 x 10 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01616Inside of the AtticFirePASSY12 x 10 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01717Inside of the Attic Quad 2FirePASSY26 x 16 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01818Inside of the Attic Quad 2FirePASSY30 x 16 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-01919Inside of the Attic Quad 2FirePASSY40 x 14 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02020Inside of the Attic Quad 2FirePASSY36 x 20 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02121Inside of the Attic Quad 2FirePASSY36 x 20 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02222At the Elevator ShaftFirePASSY36 x 36 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02323Inside of the Attic Quad 2FirePASSY12 x 10 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02424Inside of the Attic Quad 2FirePASSY14 x 12 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02525Inside of the Attic Quad 3FirePASSY10 x 12 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02626Inside of the Attic Quad 3FirePASSY12 x 18 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02727Inside of the Attic Quad 3FirePASSY10 x 1 0 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02828Inside of the Attic Quad 3FirePASSY19 x 12 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-02929Inside of the Attic Quad 3FirePASSY10 x 10 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03030Inside of the Attic Quad 2FirePASSY24 x 14 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03131Inside of the Attic Quad 2FirePASSY24 x 19 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03232Inside of the Attic Quad 2FirePASSY22 x 12 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03333Inside of the Attic Quad 3FirePASSY10 x 10 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03434Inside of the Attic Quad 2FirePASSY20 x 18 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03535Inside of the Attic Quad 2FirePASSY18 x 20 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03636Inside of the Attic Quad 2FirePASSY10 x 12 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03737Inside of the Attic Quad 2FirePASSY22 x 12 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03838Inside of the Attic Quad 2FirePASSY21 x 19 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
Attic / PenthouseA-FD-16-03939Inside of the Attic Quad 1FirePASSY20 x 18 Duct vertical penetration through concrete floorSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-0011Inside of the Vestibule Entrance of the BuildingFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-0022Above the Room Door # 134 EAP CoordinatorFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-0033Inside of the Hatch in Room # 145EFirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
First Floor1-FD-16-0044Outside of Room # 121FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0011Inside of Room # 19FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.
BasementB-FD-16-0022Inside of Room # 19FirePASSYSupply and attach damper ID tag. Verify damper compliance to NFPA 101. Affix signed and dated test sticker to space provided on damper ID tag.

&"-,Bold"&24Exhibit 2. Building 9 Dampers. Compliance to NFPA 101