36C24220R0038-006.xlsx

XLSX spreadsheet Posted

Attached to
Fire Dampers Repairs and Installation Federal contract opportunity
Solicitation number
36C24220R0038
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This solicitation is for fire damper repairs, testing, and new installations at the Northport VA Medical Center in Northport, New York. The Department of Veterans Affairs is seeking a Veteran-Owned Small Business to inspect, prepare repair reports for, decommission, test, and replace fire dampers as needed across multiple buildings on site. The estimated cost range for the project is $200,000 to $500,000 and work must be completed within 180 days of receiving a notice to proceed. The contractor will be responsible for verifying duct sizes, locking and tagging unneeded dampers, installing new dampers, testing all dampers and submitting reports on compliance and repairs. The solicitation response deadline and award date will be included in the full solicitation document to be posted on January 30, 2020. Bonding will be required and only hard copy submissions accepted in response to this solicitation.

36C24220R0038 Exhibit 1 Fire Smoke Dampers to be decommishioned Rev 2 as of 12-26-19.xlsx

View the file

Other files for this federal contract opportunity

Other files attached to Fire Dampers Repairs and Installation, newest first.
File Type Posted
36C24220R0038-005.xlsx XLSX spreadsheet
36C24220R0038-007.pdf PDF
36C24220R0038-008.xlsx XLSX spreadsheet
36C24220R0038-001.docx DOCX document
36C24220R0038-004.pdf PDF
36C24220R0038-003.docx DOCX document
36C24220R0038-002.txt TXT text file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Building 200 Exhibit 1

LocationDamper Number (Report)Damper ID (Plans)Damper LocationDamper TypeCurrent StatusRequired? (Y/N)Comments / NotesWalkthrough CommentsProject Scope
Attic / PenthouseA-FD-16-0033See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Attic / PenthouseA-FD-16-0044See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Attic / PenthouseA-FD-16-0055See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Attic / PenthouseA-FD-16-0066See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Attic / PenthouseA-FD-16-0077See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-0011See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-0022See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-0033See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-0044At the Double Doors Near Room # A4-4FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-0055See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-0066See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-0077See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-01111Inside of Room #B43FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-01313See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-01414At the Door Leading to the Clinical Research CenterFireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-02525Inside of the Linen and Waste Disposal Room # A4-4FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-03131See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-03232See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-03333See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-03434See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-03535See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-03636See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-03737See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-03838See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-03939See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-04040See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-04141See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-04242See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-04343See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-04444See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-04545See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-04646See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Forth Floor4-FD-16-04747 (NEW)See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-0011Above the Double Doors near Room # A333 Medicine Service Resident CoordinatorFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-0022Inside of Office # A333FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-0044Above the Door to Room # A333FireFAILNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-0055Above the Medical Conference Room # A335FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-0077At the Double Doors Outside of Room # A330FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-0088Inside of the Linen and Waste Disposal Room # A3-4FireRetestNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-0099Above the Double Doors Near the Pharmacy Office Room # A3-2FireFAILNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-01111Inside of Room # A32AFireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-01212Above the Door to Room # A32AFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-01313At the Double Doors Near Unit # 33FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-01515See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-01818Inside of Room # B3-60FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Third Floor3-FD-16-02020See Exhibit 2FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
second Floor2-FD-16-0011Inside of the Waste Disposal Room # A24FirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
second Floor2-FD-16-0023At the Double Doors Near Elevator # P-3FirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
second Floor2-FD-16-0035At the Double Doors Near Room # A23FirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
second Floor2-FD-16-004ERROR:#REF!Above Room # A22B DoorFirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-0059Near Room # B237FirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-00611At the Double Doors Near Room # B2-C2BFirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-006A12Above the Exit Sign Next to Room # A2-53FirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-00713At the Double Doors Near Room # B2-C2BFirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-00814At the Double Doors Near Room # B2-C2BFireFAILNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-00915Outside of Door of Unit # 21 in the Mental Health DepartmentFirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-01016Outside of Door of Unit # 22 in the Mental Health DepartmentFirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-01117Outside of Room # A22BFirePASSNExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-01319Across from Room # B2-35FireNON-ACCESSIBLENExhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding.Supply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0011Above the Women's Staff Restroom # B1-8FireNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-SD-16-0022Above the Double Doors Near the Service Elevators # B134SmokeFAILNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0033At the Service Elevators Above Elevator # F4FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0044Above Elevator F5FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0055Above the Double Doors Near Room # B1-32FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0066Inside of the Climate Control Room # B1-29FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0077Above the Double Doors Near the EMS Room # B1-24FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0088Above the Double Doors Near the EMS Room # B1-24FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0099Above the Lab Blood Drawing Room/Waiting Room Near Room # C1-76FireNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-01010Above the Lab Blood Drawing Room/Waiting Room Near Room # C1-76FireNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-01111Inside of the Histology Room # B1-28FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-01212Inside of the Histology Room Above the Histology StorageFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-01313Inside of the Histology Storage RoomFireNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-01414Inside of the Histology Storage RoomFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-01515Inside of the Histology Storage RoomFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-01616Inside of the Histology Storage RoomFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-01717Near the Histology Storage RoomFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-01818Near the Histology Room Above the ComputersFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FSD-16-01919Inside of the Room # C1-72 Above the Receptionist DeskCombinationFAILNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FSD-16-02020Inside of the Room # C1-72 Above the Receptionist DeskCombinationFAILNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-02121Above the Double Doors Near Room # B1-13G Stress LabFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-02222Above the Double Doors Near Room # B1-13G Stress LabFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-02323Above the Double Doors Near Room # B1-13G Stress LabFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-02424Above the Surgery SAC Administration Office # C1-45FireNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-02525Above the Men's Restroom # C1-39FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-02626Above the Surgery SAC Administration Office # C1-45FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-02727Above the Surgery SAC Administration Office # C1-45FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-02828Above the Double Doors Near Room # C1-27FireNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-02929Above the Double Doors Near Room # C1-27FireNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-03030Above the Double Doors Near Room # C1-27FireNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-03131Above the Double Doors Near Room # C1-6FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-03232Above the Double Doors Near Room # C1-6FirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-03333Above the Double Doors Near the EMS Room # B1-24FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.

Basement

&"-,Bold"&24Exhibit 1. Building 200 Dampers to be Decommissioned

Building 200-N Exhibit 1

LocationDamper Number (Report)Damper ID (Plans)Damper LocationDamper TypeCurrent StatusRequired? (Y/N)Comments / NotesWalkthrough CommentsProject Scope
Second Floor2-FD-16-0011At the Double Doors Near the Service ElevatorFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-0022At the Double Doors Near the Service ElevatorFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
Second Floor2-FD-16-0033At the Double Doors Near the Primary Care Quad 2GFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First floor1-FD-16-0011Outside of # D1-9BFirePASSNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First floor1-FD-16-0022Inside of # E1-1FireN/ANSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-0022ERROR:#REF!FirePASSNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-0033Outside of the Electrical Room # D0-30FireN/ANNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-0044Inside of the Mechanical Room # D0-39FirePASSNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FSD-16-0055Inside of the Room E0-5CombinationFAILNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-0088Inside of Mechanical Room # E0-19FireN/ANNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FSD-16-0099Inside of Mechanical Room # E0-19CombinationFAILNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-01010Inside of Mechanical Room # E0-19FireFAILNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FSD-16-01111Inside of Mechanical Room # E0-19CombinationPASSNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FSD-16-01212Inside of Mechanical Room # E0-19CombinationFAILNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FSD-16-01313Inside of Mechanical Room # E0-19CombinationPASSNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-01414Inside of the Retail StoreFireN/ANNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-01515Inside of the Convenience StoreFirePASSNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-01616Inside of the Convenience StoreFirePASSNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-01717Inside of the Retail StoreFirePASSNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-02222Inside of Retail Store StockroomFirePASSNNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
BasementB-FD-16-02323Inside of Retail Store StockroomFireN/ANNo Exhibit for referenceSupply and attach damper decommissioned tag. Permantely disable damper in the open position.

&"-,Bold"&24Exhibit 1. Building 200 North Dampers to be Decommissioned

Building 92 Exhibit 1

LocationDamper Number (Report)Damper ID (Plans)Damper LocationDamper TypeCurrent StatusRequired? (Y/N)Comments/NotesWalkthrough CommentsProject Scope
First Floor1-FD-16-0011Above the Double Doors Near Room # 145FireFAILNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0022Inside of Room # 144FireFAILNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.
First Floor1-FD-16-0033At the Double Doors Near Room # 169FireFAILNSupply and attach damper decommissioned tag. Permantely disable damper in the open position.

&"-,Bold"&24Exhibit 1. Building 92 Dampers to be Decommissioned