36C24220R0038-006.xlsx
XLSX spreadsheet Posted
- Attached to
- Fire Dampers Repairs and Installation Federal contract opportunity
- Solicitation number
- 36C24220R0038
About this file
This solicitation is for fire damper repairs, testing, and new installations at the Northport VA Medical Center in Northport, New York. The Department of Veterans Affairs is seeking a Veteran-Owned Small Business to inspect, prepare repair reports for, decommission, test, and replace fire dampers as needed across multiple buildings on site. The estimated cost range for the project is $200,000 to $500,000 and work must be completed within 180 days of receiving a notice to proceed. The contractor will be responsible for verifying duct sizes, locking and tagging unneeded dampers, installing new dampers, testing all dampers and submitting reports on compliance and repairs. The solicitation response deadline and award date will be included in the full solicitation document to be posted on January 30, 2020. Bonding will be required and only hard copy submissions accepted in response to this solicitation.
36C24220R0038 Exhibit 1 Fire Smoke Dampers to be decommishioned Rev 2 as of 12-26-19.xlsx
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24220R0038-005.xlsx | XLSX spreadsheet | |
| 36C24220R0038-007.pdf | ||
| 36C24220R0038-008.xlsx | XLSX spreadsheet | |
| 36C24220R0038-001.docx | DOCX document | |
| 36C24220R0038-004.pdf | ||
| 36C24220R0038-003.docx | DOCX document | |
| 36C24220R0038-002.txt | TXT text file |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building 200 Exhibit 1
| Location | Damper Number (Report) | Damper ID (Plans) | Damper Location | Damper Type | Current Status | Required? (Y/N) | Comments / Notes | Walkthrough Comments | Project Scope |
| Attic / Penthouse | A-FD-16-003 | 3 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Attic / Penthouse | A-FD-16-004 | 4 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Attic / Penthouse | A-FD-16-005 | 5 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Attic / Penthouse | A-FD-16-006 | 6 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Attic / Penthouse | A-FD-16-007 | 7 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-001 | 1 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-002 | 2 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-003 | 3 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-004 | 4 | At the Double Doors Near Room # A4-4 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-005 | 5 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-006 | 6 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-007 | 7 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-011 | 11 | Inside of Room #B43 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-013 | 13 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-014 | 14 | At the Door Leading to the Clinical Research Center | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-025 | 25 | Inside of the Linen and Waste Disposal Room # A4-4 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-031 | 31 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-032 | 32 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-033 | 33 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-034 | 34 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-035 | 35 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-036 | 36 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-037 | 37 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-038 | 38 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-039 | 39 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-040 | 40 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-041 | 41 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-042 | 42 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-043 | 43 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-044 | 44 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-045 | 45 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-046 | 46 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Forth Floor | 4-FD-16-047 | 47 (NEW) | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-001 | 1 | Above the Double Doors near Room # A333 Medicine Service Resident Coordinator | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-002 | 2 | Inside of Office # A333 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-004 | 4 | Above the Door to Room # A333 | Fire | FAIL | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-005 | 5 | Above the Medical Conference Room # A335 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-007 | 7 | At the Double Doors Outside of Room # A330 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-008 | 8 | Inside of the Linen and Waste Disposal Room # A3-4 | Fire | Retest | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-009 | 9 | Above the Double Doors Near the Pharmacy Office Room # A3-2 | Fire | FAIL | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-011 | 11 | Inside of Room # A32A | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-012 | 12 | Above the Door to Room # A32A | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-013 | 13 | At the Double Doors Near Unit # 33 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-015 | 15 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-018 | 18 | Inside of Room # B3-60 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Third Floor | 3-FD-16-020 | 20 | See Exhibit 2 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| second Floor | 2-FD-16-001 | 1 | Inside of the Waste Disposal Room # A24 | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| second Floor | 2-FD-16-002 | 3 | At the Double Doors Near Elevator # P-3 | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| second Floor | 2-FD-16-003 | 5 | At the Double Doors Near Room # A23 | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| second Floor | 2-FD-16-004 | ERROR:#REF! | Above Room # A22B Door | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Second Floor | 2-FD-16-005 | 9 | Near Room # B237 | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Second Floor | 2-FD-16-006 | 11 | At the Double Doors Near Room # B2-C2B | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Second Floor | 2-FD-16-006A | 12 | Above the Exit Sign Next to Room # A2-53 | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Second Floor | 2-FD-16-007 | 13 | At the Double Doors Near Room # B2-C2B | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Second Floor | 2-FD-16-008 | 14 | At the Double Doors Near Room # B2-C2B | Fire | FAIL | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Second Floor | 2-FD-16-009 | 15 | Outside of Door of Unit # 21 in the Mental Health Department | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Second Floor | 2-FD-16-010 | 16 | Outside of Door of Unit # 22 in the Mental Health Department | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Second Floor | 2-FD-16-011 | 17 | Outside of Room # A22B | Fire | PASS | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Second Floor | 2-FD-16-013 | 19 | Across from Room # B2-35 | Fire | NON-ACCESSIBLE | N | Exhibit 2 for 2nd floor of building 200 is for reference only. Use Exhibit 1 for bidding. | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| First Floor | 1-FD-16-001 | 1 | Above the Women's Staff Restroom # B1-8 | Fire | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |||
| First Floor | 1-SD-16-002 | 2 | Above the Double Doors Near the Service Elevators # B134 | Smoke | FAIL | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-003 | 3 | At the Service Elevators Above Elevator # F4 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-004 | 4 | Above Elevator F5 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-005 | 5 | Above the Double Doors Near Room # B1-32 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-006 | 6 | Inside of the Climate Control Room # B1-29 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-007 | 7 | Above the Double Doors Near the EMS Room # B1-24 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-008 | 8 | Above the Double Doors Near the EMS Room # B1-24 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-009 | 9 | Above the Lab Blood Drawing Room/Waiting Room Near Room # C1-76 | Fire | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |||
| First Floor | 1-FD-16-010 | 10 | Above the Lab Blood Drawing Room/Waiting Room Near Room # C1-76 | Fire | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |||
| First Floor | 1-FD-16-011 | 11 | Inside of the Histology Room # B1-28 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-012 | 12 | Inside of the Histology Room Above the Histology Storage | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-013 | 13 | Inside of the Histology Storage Room | Fire | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |||
| First Floor | 1-FD-16-014 | 14 | Inside of the Histology Storage Room | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-015 | 15 | Inside of the Histology Storage Room | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-016 | 16 | Inside of the Histology Storage Room | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-017 | 17 | Near the Histology Storage Room | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-018 | 18 | Near the Histology Room Above the Computers | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FSD-16-019 | 19 | Inside of the Room # C1-72 Above the Receptionist Desk | Combination | FAIL | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FSD-16-020 | 20 | Inside of the Room # C1-72 Above the Receptionist Desk | Combination | FAIL | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-021 | 21 | Above the Double Doors Near Room # B1-13G Stress Lab | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-022 | 22 | Above the Double Doors Near Room # B1-13G Stress Lab | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-023 | 23 | Above the Double Doors Near Room # B1-13G Stress Lab | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-024 | 24 | Above the Surgery SAC Administration Office # C1-45 | Fire | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |||
| First Floor | 1-FD-16-025 | 25 | Above the Men's Restroom # C1-39 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-026 | 26 | Above the Surgery SAC Administration Office # C1-45 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-027 | 27 | Above the Surgery SAC Administration Office # C1-45 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-028 | 28 | Above the Double Doors Near Room # C1-27 | Fire | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |||
| First Floor | 1-FD-16-029 | 29 | Above the Double Doors Near Room # C1-27 | Fire | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |||
| First Floor | 1-FD-16-030 | 30 | Above the Double Doors Near Room # C1-27 | Fire | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |||
| First Floor | 1-FD-16-031 | 31 | Above the Double Doors Near Room # C1-6 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-032 | 32 | Above the Double Doors Near Room # C1-6 | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-033 | 33 | Above the Double Doors Near the EMS Room # B1-24 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. |
Basement
&"-,Bold"&24Exhibit 1. Building 200 Dampers to be Decommissioned
Building 200-N Exhibit 1
| Location | Damper Number (Report) | Damper ID (Plans) | Damper Location | Damper Type | Current Status | Required? (Y/N) | Comments / Notes | Walkthrough Comments | Project Scope |
| Second Floor | 2-FD-16-001 | 1 | At the Double Doors Near the Service Elevator | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Second Floor | 2-FD-16-002 | 2 | At the Double Doors Near the Service Elevator | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Second Floor | 2-FD-16-003 | 3 | At the Double Doors Near the Primary Care Quad 2G | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First floor | 1-FD-16-001 | 1 | Outside of # D1-9B | Fire | PASS | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First floor | 1-FD-16-002 | 2 | Inside of # E1-1 | Fire | N/A | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| Basement | B-FD-16-002 | 2 | ERROR:#REF! | Fire | PASS | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-003 | 3 | Outside of the Electrical Room # D0-30 | Fire | N/A | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-004 | 4 | Inside of the Mechanical Room # D0-39 | Fire | PASS | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FSD-16-005 | 5 | Inside of the Room E0-5 | Combination | FAIL | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-008 | 8 | Inside of Mechanical Room # E0-19 | Fire | N/A | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FSD-16-009 | 9 | Inside of Mechanical Room # E0-19 | Combination | FAIL | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-010 | 10 | Inside of Mechanical Room # E0-19 | Fire | FAIL | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FSD-16-011 | 11 | Inside of Mechanical Room # E0-19 | Combination | PASS | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FSD-16-012 | 12 | Inside of Mechanical Room # E0-19 | Combination | FAIL | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FSD-16-013 | 13 | Inside of Mechanical Room # E0-19 | Combination | PASS | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-014 | 14 | Inside of the Retail Store | Fire | N/A | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-015 | 15 | Inside of the Convenience Store | Fire | PASS | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-016 | 16 | Inside of the Convenience Store | Fire | PASS | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-017 | 17 | Inside of the Retail Store | Fire | PASS | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-022 | 22 | Inside of Retail Store Stockroom | Fire | PASS | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | |
| Basement | B-FD-16-023 | 23 | Inside of Retail Store Stockroom | Fire | N/A | N | No Exhibit for reference | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. |
&"-,Bold"&24Exhibit 1. Building 200 North Dampers to be Decommissioned
Building 92 Exhibit 1
| Location | Damper Number (Report) | Damper ID (Plans) | Damper Location | Damper Type | Current Status | Required? (Y/N) | Comments/Notes | Walkthrough Comments | Project Scope |
| First Floor | 1-FD-16-001 | 1 | Above the Double Doors Near Room # 145 | Fire | FAIL | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-002 | 2 | Inside of Room # 144 | Fire | FAIL | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. | ||
| First Floor | 1-FD-16-003 | 3 | At the Double Doors Near Room # 169 | Fire | FAIL | N | Supply and attach damper decommissioned tag. Permantely disable damper in the open position. |
&"-,Bold"&24Exhibit 1. Building 92 Dampers to be Decommissioned