This document contains a solicitation for fire damper repairs, testing, and new installation services at the Northport Veterans Affairs Medical Center in Northport, New York. The solicitation seeks a Veteran-Owned Small Business contractor to inspect existing fire dampers, prepare repair reports, decommission outdated units, install new fire damper labels, install out-of-airstream fire dampers where needed, and perform testing and inspection services to verify compliance with NFPA 80 standards. The total project duration is 180 days, with potential off-hours work to minimize disruption to patient care areas. The cost estimate range for the project is $200,000 to $500,000. Responses are due on or around January 30, 2020 and must be submitted in hard copy to the address provided in the full solicitation.
36C24220R0038 Exhibit 6 Test form Rev 1 as of 12-26-19.docx
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24220R0038-002.txt | TXT text file | |
| 36C24220R0038-004.pdf | ||
| 36C24220R0038-006.xlsx | XLSX spreadsheet | |
| 36C24220R0038-005.xlsx | XLSX spreadsheet | |
| 36C24220R0038-007.pdf | ||
| 36C24220R0038-008.xlsx | XLSX spreadsheet | |
| 36C24220R0038-001.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE AND SMOKE DAMPERS
Form 17-C
Inspection and Maintenance
| Year | System | |
| Location | Date | Inspector |
| 1. | Full unobstructed access to dampers is provided. |
| 2. | Smoke damper needs to be cycled through its closure and opening in accordance with NFPA 72. |
| 3. | Fusible link, if provided, is removed and damper closes completely and latches closed (where latch provided). |
| 4. | No interference with damper operation by rusted, bent, or misaligned parts, damaged blades, or defective hinges. |
| 5. | Damper frame not penetrated by foreign objects to prevent proper operation. |
| 6. | Fusible link is not damaged or painted. If damaged, it should be replaced. |
| 7. | All exposed moving parts to be dry lubricated per manufacturer’s instructions. |
| 8. | Note deficiencies and how they were corrected. After any repairs, the damper should be retested for proper operation. |
Y = Satisfactory N = Unsatisfactory (explain below) N/A = Not applicable
| Fire Damper Number or Location |
| 1 |
| 2 |
| 3 |
| 4 |
| 5 |
| 6 |
| 7 |
| 8 |
Note: Use reverse side for comments.
Note: Dampers must be tested and inspected 1 year after installation and then every 4 years, except in a hospital, where they can be inspected every 6 years.