36C24218B0572-0004001.docx

DOCX document 14 KB Posted

Attached to
528A8-18-805 RENOVATE ONCOLGY LAB FOR USP 800
Solicitation number
36C24218B0572
Issued by

About this file

36C24218B0572 0004 Responses to RFI 3.docx

View the file

Other files

File Type Posted
36C24219C0026-000.docx DOCX document
36C24218B0572-0005000.docx DOCX document
36C24218B0572-0005001.docx DOCX document
36C24218B0572-0005002.pdf PDF
36C24218B0572-0004000.docx DOCX document
36C24218B0572-0004002.pdf PDF
36C24218B0572-0004003.pdf PDF
36C24218B0572-0003002.pdf PDF
36C24218B0572-0003001.docx DOCX document
36C24218B0572-0003000.docx DOCX document
36C24218B0572-0003003.pdf PDF
36C24218B0572-0002001.docx DOCX document
36C24218B0572-0002003.pdf PDF
36C24218B0572-0002002.pdf PDF
36C24218B0572-0002000.docx DOCX document
36C24218B0572-0002004.pdf PDF
36C24218B0572-0001000.docx DOCX document
36C24218B0572-005.pdf PDF
36C24218B0572-003.pdf PDF
36C24218B0572-001.docx DOCX document
36C24218B0572-002.docx DOCX document
36C24218B0572-004.zip ZIP file
36C24218B0572-000.docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Request for Information (RFI)

Project Name: Renovate Oncology Project #: 528A8-18-805 Solicitation#: 36C24218B0572

Monday, October 15, 2018

Stratton VA Medical Center Response

Q8: The Oncology project is calling for a temp clean room to be set up in room 1106b. The temp enclosure overall height is 102” and calls for finished ceilings to be 6” above that, making our new ceiling height for 1106b over the enclosure to be 108”, or 9feet. Has there been an above ceiling inspection done to ensure existing finished walls go up that height or will there be additional work needed on walls to finish before painting and ceiling work?

A8: The temporary clean room will be set up in room A1105b (not 1106b). During design we did investigate above the existing ceiling in this room. The existing ceiling measures 8’-8 ¼” +/-. The wall adjoining A1105a is gypsum and extends to the deck. The other three walls are either plaster on blocks or lath and plaster. The lowest top of these walls is approximately 7” above ceiling level. It appears that all of the walls extend to at least 9’ AFF.

Q9: In response to RFI 2 – Q7, did you mean Additional Information on Drawing M-002?

A9: Correct, please refer to Drawing M-002 as there is no M-005.