This document appears to be a 100% bid set for the renovation of the VA's MHT Lab in Manchester, VAMC. The related federal contract opportunity is Solicitation Number 36C24124B0052, titled "Z1DA--608-23-133, Third Floor Lab Construction." This is an invitation for bids for the third floor lab construction project. The contracting agency is the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 1. The document includes detailed construction plans and specifications for the renovation work. The solicitation requires bidders to submit their proposals by the bid due date, with the contract award anticipated at a later date. Pricing terms, set-asides, incumbents, and other key details are not explicitly provided in this document.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
CFR ENGINEERING
20251 CENTURY BLVD.
SUITE 120
GERMANTOWN, MD 20874
877-871-4229
CONSULTANT:
IMEG CORP.
101 NORTH SEVENTH STREET
SUITE 404
LOUISVILLE, KY 40202
440-262-3063
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
08-20-2024
608-23-133
OLKJ
3RD FLOOR LABORATORY
CONSTRUCTION
100% CD SUBMISSION
COVER SHEET
GI100
-2
-1
G I1
.p d f
Department of Veterans Affairs
3RD FLOOR LABORATORY CONSTRUCTION
Manchester VAMC 718 Smyth Road
Manchester, NH 03104
Manchester VAMC 718 Smyth Road Manchester, NH 03104
100% CD SUBMISSION
LOCATION MAP DRAWING LIST PROJECT DIRECTORY
Medical Center Director
Director of Facility Management Service
Medical Director
Project COR
Project CO
Infection Control
Safety Officer
CONTRACTING OFFICER REPRESENTATIVE (COR)
Keith Lacasse
VA Medical Center - Manchester 718 Smyth Road, BST Suite 105 Manchester, NH 03104 PHONE: (603) 624-4366 x 1106 keith.lacasse@va.gov
ARCHITECT
Ken Jones
CB DESIGN GROUP, INC
421 King St., Suite 301
PHONE: (443) 388-7351
kjones@cbdg-ae.com
STRUCTURAL
Katie Goldberg
IMEG Corp 15 Sunnen Drive Suite 104 St. Louis, MO 63143
PHONE: (314) 951-2538
katie.m.goldberg@imegcorp.com
CONTRACTING OFFICER (CO)
Casey Pridham
Contracting Officer Construction Team 1 718 Smyth Road, BST Suite 105 Manchester, NH 03104
PHONE: (781) 687-7343
Casey.Pridham@va.gov
APPROVALS
FIRE PROTECTION
Lenny Hendrix
IMEG Corp 101 North Seventh Street | Suite 404 | Louisville, KY 40202
PHONE: (440) 262-3063
leonard.d.hendrix@imegcorp.com
LIFE SAFETY
David McCoy
Compass Consulting Group 3401 Enterprise Parkway Beachwood, OH 44122
PHONE: (619) 925-1647
COST ESTIMATE
Sarita Kandel
OCMI
PHONE: (202) 299-0530
skandel@ocmi.com
GENERAL
GI100 COVER SHEET
GI200 SYMBOLS, ABBREVIATIONS & NOTES
GI300 GENERAL NOTES
GI301 TYPICAL MOUNTING HEIGHTS
GC200 EXISTING CONDITIONS PLAN
LIFE SAFETY
LS100 LIFE SAFETY ANALYSIS AND 3RD LEVEL PLAN
ARCHITECTURAL
AD100 DEMOLITION PLAN
AD101 DEMOLITION DETAILS
AE100 FLOOR PLAN
AE101 DIMENSION PLAN
AE300 DOOR / WINDOW SCHEDULES
AE301 FLOOR FINISH PLAN AND SCHEDULE
AE302 WALL PROTECTION PLAN
AE303 MATERIAL COLORS
AE304 WALL TYPES
AE305 SIGN TYPES
AE400 BUILDING & WALL SECTIONS
AE401 PNEUMATIC TUBE STATION & DUMBWAITER DETAILS
AE402 WALL SECTIONS
AE700 REFLECTED CEILING PLAN / DETAILS
AE900 OVERALL EQUIPMENT PLAN
AE901 ENLARGED 3RD FLOOR EQUIPMENT PLAN - AREA A
AE902 ENLARGED 3RD FLOOR EQUIPMENT PLAN - AREA B
AE903 METAL / WOOD CASEWORK PLAN AND ELEVATIONS
AE904 WOOD CASEWORK SECTIONS
AE905 3D PERSPECTIVES & INTERIOR ELEVATIONS
AE906 3D PERSPECTIVES & INTERIOR ELEVATIONS
AE907 3D PERSPECTIVES & INTERIOR ELEVATIONS
AE908 DETAILS
QV101 PNEUMATIC TUBE SYSTEM VENDOR DRAWING
STRUCTURAL
S000 GENERAL NOTES
S200 PARTIAL FLOOR FRAMING PLANS AND DETAILS
MECHANICAL
M001 NOTES, ABBREVIATIONS & SYMBOLS - MECHANICAL
MD101 PARTIAL 3RD FLOOR PLAN - DEMOLITION - MECHANICAL
MD102 PARTIAL 7TH FLOOR PLAN - DEMOLITION - MECHANICAL
M100 OVERALL 3RD FLOOR PLAN - NEW WORK - MECHANICAL DUCTWORK
M101 PARTIAL 3RD & 7TH FLOOR PLAN - NEW WORK - MECHANICAL DUCTWORK
M102 PARTIAL 3RD FLOOR PLAN - NEW WORK - MECHANICAL DUCTWORK
M200 OVERALL 3RD FLOOR PLAN - NEW WORK - MECHANICAL PIPING
M201 PARTIAL 3RD FLOOR PLAN - NEW WORK - MECHANICAL PIPING
M202 PARTIAL 3RD FLOOR PLAN - NEW WORK - MECHANICAL PIPING
M203 PARTIAL BASEMENT FLOOR PLAN - NEW WORK - MECHANICAL PIPING
M301 PARTIAL 3RD FLOOR RCP - NEW WORK - MECHANICAL
M302 PARTIAL 3RD FLOOR - NEW WORK - PRESSURIZATION PLAN
M401 SECTIONS - MECHANICAL
M402 SECTIONS - MECHANICAL
M501 DETAILS - MECHANICAL
M502 DETAILS - MECHANICAL
M503 DETAILS - MECHANICAL
M504 DETAILS - MECHANICAL
M505 DETAILS - MECHANICAL
M511 HYDRONIC RISERS - MECHANICAL
M512 AIR RISERS - MECHANICAL
M601 SCHEDULES - MECHANICAL
M602 SCHEDULES - MECHANICAL
M701 CONTROLS - MECHANICAL
M702 CONTROLS - MECHANICAL
M703 CONTROLS - MECHANICAL
M704 CONTROLS - MECHANICAL
M705 CONTROLS - MECHANICAL
PLUMBING
P001 NOTES, ABBREVIATIONS & SYMBOLS - PLUMBING
PD101 PARTIAL 3RD FLOOR PLAN - DEMOLITION - PLUMBING
PD102 PARTIAL BASEMENT FLOOR PLAN - DEMOLITION - PLUMBING
P101 PARTIAL 3RD FLOOR PLAN - NEW WORK - PLUMBING WATER & GAS
P102 PARTIAL 3RD FLOOR PLAN - NEW WORK - PLUMBING WATER & GAS
P103 PARTIAL BASEMENT FLOOR PLAN - NEW WORK - PLUMBING WATER
P201 PARTIAL 3RD FLOOR PLAN - NEW WORK - PLUMBING WASTE
P202 PARTIAL 3RD FLOOR PLAN - NEW WORK - PLUMBING WASTE
P501 RISER DIAGRAMS - PLUMBING WATER
P502 RISER DIAGRAMS - SANITARY AND VENT
P503 DETAILS - PLUMBING
P504 DETAILS - PLUMBING
P601 SCHEDULES - PLUMBING
FIRE PROTECTION
F000 FIRE PROTECTION COVERSHEET
F103 FIRE PROTECTION LEVEL 03 DEMOLITION PLAN
F203 FIRE PROTECTION LEVEL 03 PLAN
F400 FIRE PROTECTION DETAILS
ELECTRICAL
E001 GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS - ELECTRICAL
ED101 PARTIAL THIRD FLOOR PLAN - DEMOLITION - POWER AND TELECOMMUNICATION
ED102 PARTIAL ROOF PLAN - DEMOLITION - POWER
ED201 PARTIAL THIRD FLOOR PLAN - DEMOLITION - LIGHTING
E101 PARTIAL THIRD FLOOR PLAN - NEW WORK - POWER
E102 PARTIAL ROOF PLAN - NEW WORK - POWER
E103 PARTIAL THIRD FLOOR PLAN - TELECOMMUNICATIONS AND SECURITY - NEW WORK
E201 PARTIAL THIRD FLOOR PLAN - NEW WORK - LIGHTING
E501 DETAILS AND SCHEDULES - ELECTRICAL
E502 DETAILS - ELECTRICAL
E601 PARTIAL SIGNLE LINE DIAGRAM
E602 PANEL SCHEDULES
FIRE ALARM
FA000 ELECTRICAL COVERSHEET
FA103 SYSTEMS LEVEL 03 DEMOLITION PLAN
FA203 SYSTEMS LEVEL 03 PLAN
SITE
MEP
Omar Malik
CFR Engineering 20251 Century Blvd. Suite 120 Germantown, MD 20874
PHONE: (267) 625-1259
omalik@cfrengineering.com
WOOD
ALUMINUM
STEEL
EARTH
CONCRETE MASONRY UNITS
RIGID INSULATION
CONCRETE
EXISTING CONSTRUCTION
TO REMAIN
EXISTING CONSTRUCTION
TO BE REMOVED
BRICK
WOOD-FINISHED
WOOD ROUGH
PLYWOOD
GYPSUM - PLASTER
ACOUSTIC TILE
CAST STONE
ALL METALS - SMALL SCALE
GLASS - LARGE SCALE
BATT INSULATION
CERAMIC TILE
CARPET
GRAVEL
CENTER LINE
DETAIL INDICATOR
DETAIL INDICATIOR
DIMENSION LINE
DRAWING BLOCK TITLE, TYPICAL
ELEVATION INDICATOR, EXTERIOR
ELEVATION INDICATOR, INTERIOR, MULTIPLE VIEW
ELEVATION INDICATOR, INTERIOR, SINGLE VIEW
SECTION INDICATOR
TYPICAL DETAIL INDICATOR
COLUMN GRID
KEYNOTE
NORTH ARROW
A
DETAIL NUMBER
SHEET WHERE
DRAWN
XXxxx
XXxxx
X
DRAWING TITLE
SCALE: 1 1/2" = 1'-0"
1 1/2"
XXxxx
XXxxx
XXxxx
REVISION
REVISION CLOUD
NORTH
BREAK LINE
DEMOLITION KEYNOTE
A
XXxxx
D
BC
COLUMN NUMBER
COLUMN LETTER
XXxxx
ELEVATION NUMBER
SHEET WHERE
DRAWN
ELEVATION NUMBER
SHEET WHERE
DRAWN
ELEVATION NUMBER
SHEET WHERE
DRAWN
DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL NUMBER
SHEET WHERE DRAWN
SHEET WHERE
DRAWN
ELEVATION NUMBER
DOOR / BORROWED LIGHT TAG
FURNITURE, FIXTURE, & EQUIPMENT TAG
WALL/PARTITION TAG
x'-x" VERTICAL HEIGHT INDICATOR
ROOM NAME
3333333333
A3
ROOM NUMBER
ROOM AREA
PROGRAM AREA
D100
FLR FLOOR
FLUOR FLUORESCENT
FM FLOOR MATS & FRAMES
FO __ FACE OF __
FOC FACE OF CONCRETE
FOS FACE OF STUD
FOW FACE OF WALL
FP FOLDING PANEL PARTITION
FPRF FIREPROOF(ING)
FR FIRE RATING, FRAME
FRMG FRAMING
FS FULL SIZE, FEATURE STRIPS
FT FOOT OR FEET, FLOOR TILE MOSAIC
FTCT CERAMIC MOSAIC TILE
FTG FOOTING
FUR FURRING
FUT FUTURE
GA GAUGE
GAL GALLON
GALV GALVANIZED
GALV STL GALVANIZED STEEL
GB GRAB BAR
GC GENERAL CONTRACTOR
GCMU GLAZED FACE CMU
GD GUARD
GL GLASS
GND GROUND
GR GRADE
GT GRANITE
GUMU GLASS MASONRY UNIT
GWB GYPSUM WALLBOARD
GYP BD GYPSUM WALLBOARD
HB HOSE BIBB
HC HOLLOW CORE
HD HEAD
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HNDRL HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HP HIGH POINT
HPDL PLASTIC LAMINATE
HR HANDRAIL, HOUR
HSPL HIGH STRENGTH PLASTER
HT HEIGHT
HVAC HEATING, VENTILATION, AIR
CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE DIAMETER /
DIMENSION
IN INCH
INCL INCLUDE(D)
INSUL INSULATION
INT INTERIOR
INV INVERT
JAN JANITOR
JST JOIST
JT JOINT
KC PLASTER KEENE CEMENT
KP KICK PLATE
KO KNOCKOUT
L LENGTH
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBS POUND
LED LIGHT EMITTING DIODE
LF LINEAR FEET
LG LONG
LH LEFT HAND
LIN LINEAR
LIQ LIQUID
LKR LOCKER
LL LEAD LINED
LLV LONG LEG VERTICAL
LM LATEX MASTIC FLOORING
LMC LINEAR METAL CEILING
LP LOW POINT
LRG LARGE
LT LIGHT
LT WT LIGHTWEIGHT
LVR LOUVER
LWC LINEAR WOOD CEILING
M MORTAR
MAS MASONRY
MAT MATERIAL
MAX MAXIMUM
MB MARBLE
MC MULTI-COLOR COATING
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MP MOP PLATE
MTD MOUNTED
MTL METAL
N NORTH
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NF NATURAL FINISH
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OFF OFFICE
OH OPPOSITE HAND, OVERHEAD
OPNG OPENING
OPP OPPOSITE
OZ OUNCE
P PAINT
PAV PAVING
PC PRECAST CONCRETE
PCT PORTLAND CEMENT TERRAZZO
PFW POLYPROPYLENE FABRIC WALLCOVERING
PL PLATE, PLASTER
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PMF PREMOLDED FILLER, PERFORATED METAL
FACING (TILE OR PANELS)
PPT PORCELAIN PAVER TILE
PR PAIR
PT POINT
PTN PARTITION
PVT PAVER TILE
QT QUARRY TILE
R RADIUS, RISER
RA RETURN AIR
RAD RADIUS
RB RESILIENT BASE, RUBBER BASE
RCP REFLECTED CEILING PLAN,
RADIANT CEILING PANEL SYSTEM
RD ROOF DRAIN
REF REFERENCE
REFR REFRIGERATOR
REQ'D REQUIRED
REV REVISION
RFI REQUEST FOR INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RL ROOF LEADER
RM ROOM
RO ROUGH OPENING
RST RESILIENT STAIR TREAD
RT RUBBER TILE FLOORING
S SOUTH
SA SUPPLY AIR
SAN SANITARY
SC SOLID CORE, HIGH GLAZED COATING,
STRUCTURAL CLAY
SCHED SCHEDULE
SCT FACING TILE
SDG SUSPENSION DECORATIVE GRIDS
SECT SECTION
SF SQUARE FEET, STONE FLOORING
SFTU GLAZED STRUCTURAL FACING TILE
SH SPRINKLER HEAD
SHT SHEET
SIM SIMILAR
SLG SPANDREL GLASS
SM SMOKE
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
SS STAINLESS STEEL
ST STAIN
STA STATION
STD STANDARD
STO STORAGE
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
SYS SYSTEM
T TREAD
T&G TONGUE AND GROOVE
TEL TELEPHONE
TEMP TEMPERED
TGC TEXTURED GYPSUM CEILING PANEL
THK THICK
TIL TECHNICAL INFORMATION LIBRARY (VA)
TMC TEXTURED METAL CEILING PANEL
TOC TOP OF CONCRETE
TOP TOP OF PAVEMENT
TOS TOP OF STEEL
TOW TOP OF WALL
TST THIN SET TERRAZZO
TT TERRAZZO TILE
TV TELEVISION
TYP TYPICAL
UNFIN UNFINISHED
UON UNLESS OTHERWISE NOTED
VB VAPOR BARRIER, VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VP VENEER PLASTER
VSF VINYL SHEET FLOORING
VTR VENT THRU ROOF
W WEST, VINYL COATED FABRIC
WALLCOVERING
W/ WITH
WB WALL BORDER
WD WOOD
WF FABRIC WALLCOVERING
W/O WITHOUT
WP WATERPROOF
WSF VINYL SHEET FLOORING (WELDED SEAMS)
WT WEIGHT
WWF WELDED WIRE FRAME
NOTES
1. ALL ABBREVIATIONS SHOWN MAY NOT BE USED ON THIS PROJECT.
2. CERTAIN COMMON ABBREVIATIONS MAY NOT BE SHOWN.
3. TEXT IN BOLD DENOTES ABBREVIATIONS FROM THE TIL.
L
& AND
@ AT
C CENTERLINE
# NUMBER, POUND
AA ANODIZED ALUMINUM, NATURAL FINISH
AAC ANODIZED ALUMINUM, COLORED
AB ANCHOR BOLT
ABA ARCHITECTURAL BARRIERS ACT
ABV ABOVE
ACT ACOUSTIC CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJUSTABLE
AF ACCESS FLOORING
AFF ABOVE FINISHED FLOOR
AFP ACCORDION FOLDING PARTITION
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF ARCHITECTS
ALT ALTERNATE
ALUM ALUMINUM
AMP ACOUSTICAL METAL PLAN CEILING
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AT ACOUSTICAL CEILING TILE
AT (SP) ACOUSTICAL CEILING, SPECIAL FACED
AUTO AUTOMATIC
AVG AVERAGE
AWF ACOUSTICAL WALLCOVERING
AWP ACOUSTICAL WALL PANEL
AWT ACOUSTICAL WALL TREATMENT
BD BOARD
BE BAKED ON ENAMEL
BEL BELOW
BF BRICK FLOORING
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BP BRICK PAVING
BR BUMPER RAIL, BRICK FACE
BRG BEARING
BRK BRICK
C, CONC CONCRETE
CAB CABINET
CAF CARPET ATHLETIC FLOORING
CB CATCH BASIN
CCT CUBICLE CURTAIN TRACK
CEM CEMENT
CG CORNER GUARD
CGFB CERAMIC GLAZED FACING BRICK
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CLOSET
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CONTRACTING OFFICER
COL COLUMN
CONF CONFERENCE
CONT CONTINUOUS
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CP CARPET
CPT CARPET MODULE TILE
CT CERAMIC TILE
CU CUBIC
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DOOR OPENING
DOZ DOZEN
DP DAMPPROOFING
DR DOOR
DS MB DIVIDER STRIPS, MARBLE
DWG DRAWING
DWGS DRAWINGS
DWR DRAWER
E EAST, EXISTING
EA EXHAUST AIR, EACH
EC EPOXY COATING
EFS EXTERIOR FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATION
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
EP ELECTRICAL PANELBOARD
EQ EQUAL
EQUIP EQUIPMENT
ERF EPOXY RESIN FLOORING
EWC ELECTRIC WATER COOLER
EWS EYE WASH STATION
EXIST EXISTING
EXP EXPANSION, EXPOSED DIVIDER STRIPS
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK
FC FLUOROCARBON
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FACE
FG FOOT GRILLE
FHC FIRE HOSE CABINET
FIN FINISH
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
CFR ENGINEERING
20251 CENTURY BLVD.
SUITE 120
GERMANTOWN, MD 20874
877-871-4229
CONSULTANT:
IMEG CORP.
101 NORTH SEVENTH STREET
SUITE 404
LOUISVILLE, KY 40202
440-262-3063
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
08-20-2024
608-23-133
AuthorChecker
3RD FLOOR LABORATORY
CONSTRUCTION
100% CD SUBMISSION
SYMBOLS, ABBREVIATIONS & NOTES
GI200
-2
-1
G I2
.p d f
Manchester VAMC 718 Smyth Road Manchester, NH 03104
SYMBOLS OF MATERIALSDRAWING SYMBOLSARCHITECTURAL ABBREVIATIONS
1. HOSPITAL STAFF SHALL ENSURE THE REMOVAL OF ANY MEDICAL WASTE, INCLUDING SHARPS CONTAINERS, FROM AREAS TO BE RENOVATED, PRIOR TO THE START OF THE PROJECT.
2. INFECTION CONTROL SHALL BE NOTIFIED BY FACILITIES MANAGEMENT STAFF IMMEDIATELY IF UNEXPECTED MEDICAL WASTE IS ENCOUNTERED.
IN STRIVING TO PROVIDE A HEALTHY AND SAFE ENVIRONMENT AT VA FACILITIES, VHA IS IMPLEMENTING A SMOKE-FREE POLICY FOR ALL VHA HEALTH CARE FACILITIES AND PROPERTY ASSIGNED TO VHA THAT IS UNDER THE CHARGE AND CONTROL OF VA. THE POLICY APPLIES TO CIGARETTES, CIGARS, PIPES OR ANY OTHER COMBUSTION OF TOBACCO, INCLUDING BUT NOT LIMITED TO ELECTRONIC OR E-CIGARETTES, VAPE PENS OR E-CIGARS.
UNDER VHA DIRECTIVE 1085, ALL VHA HEALTH CARE FACILITIES WILL BE SMOKE-FREE FOR PATIENTS, VISITORS, CONTRACTORS, VOLUNTEERS AND
VENDORS EFFECTIVE OCTOBER 1, 2019.
1. VA DESIGN MANUAL (PG-18-0)
2. VA DESIGN, QUALITY, AND STANDARD ALERTS
3. VA DESIGN GUIDES (PG-18-12)
4. VA DESIGN AND CONSTRUCTION
PROCEDURES (PG-18-3)
5. PHYSICAL SECURITY DESIGN MANUAL FOR VA
FACILITIES
6. VA FIRE PROTECTION DESIGN MANUAL
7. VA BARRIER FREE DESIGN GUIDE (PG-18-3)
8. VA SIGNAGE DESIGN GUIDE
9. VA MASTER SPECIFICATIONS
10. VA SUSTAINABLE DESIGN MANUAL
1. A HAZARDOUS MATERISLS SURVEY WAS PERFORMED BY HGS ENGINEERING IN 2020 FOR ALL FLOORS OF BUILDING 1. THE SURVEY FOUND THAT HAZARDOUS MATERIALS (ASBESTOS-CONTAINING MATERIALS (ACM)) ARE PRESENT IN THE AREA WITHIN THIS PROJECT SCOPE.
2. REFER TO THE REPORT INCLUDED IN THE PROJECT SPECIFICATIONS (SECTION 02 82 12) FOR LOCATION, EXTENT, AND ABATEMENT/DISPOSAL REQUIREMENTS OF ACM. THE REPORT IS TITLED "UPDATE & MAINTAIN ASBESTOS INSPECTION 2020, PROJECT 608-18-104, BUILDING 1" DATED
OCTOBER 2020.
3. REFER TO SECTION 02 82 11 TRADITIONAL ASBESTOS ABATEMENT FOR ADDITIONAL REQUIREMENTS FOR ACM
4. THE GLAZING ON THE SUBWAY TILES HAS BEEN DETERMINED TO CONTAIN LEAD IN OTHER AREAS DURING PAST PROJECTS.
5. EXTERIOR WINDOWS HAVE ASBESTOS COMPONEMTS THAT MUST BE ABATED AND DISPOSED OF DURING REMOVAL.
6. FIRE RATED DOORS IDENTIFIED TO BE REMOVED UNDER THIS CONTRACT CONTAIN ASBESTOS.
7. REFER TO SPECIFICATIONS SECTION 02 83 33.13 LEAD REMOVAL AND DISPOSAL FOR ADDITIONAL REQUIREMENTS FOR LEAD REMOVAL.
1. ITEMS AND CONDITIONS NOTED, DETAILED, OR OTHERWISE IDENTIFIED ON DRAWINGS ARE APPLICABLE AND BINDING TO SIMILAR CONDITIONS ON ALL DRAWINGS.
FOR CONDITIONS NOT NOTED OR NOT DETAILED, PROVIDE MATERIALS OF EQUAL QUALITY AND PERFORMANCE TO OTHER SIMILAR CONDITIONS ON THE JOB.
2. SECTIONS SHOWN ARE INTENDED TO SHOW THE SPECIFIC CONSTRUCTION WHERE INDEXED AS WELL AS ESTABLISH THE GENERAL CONSTRUCTION DETAILS FOR SECTIONS THROUGHOUT THE PROJECT. ANY SPECIFIC QUESTIONS CONCERNING CONSTRUCTION NOT ADEQUATELY COVERED BY THE ABOVE SHALL BE DIRECTED
TO THE CONTRACTING OFFICER DURING THE BID PERIOD.
3. ALL CONSTRUCTION IS TO BE NEW AND FURNISHED AND INSTALLED BY THE CONTRACTOR, UNLESS NOTED OTHERWISE.
4. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR NOTES PERTAINING TO THEIR PARTICULAR DISCIPLINES. COORDINATE THE WORK OF ALL TRADES AND REPORT TO THE CONTRACTING OFFICER ANY PERCEIVED DISCREPANCIES. CONTRACTOR SHALL BE RESPONSIBLE FOR ESTABLISHING SEQUENCES OF CONSTRUCTION AND MEANS AND METHODS FOR HOW TO PERFORM THE WORK REQUIRED IN THE CONTRACT DOCUMENTS.
5. CONTRACTOR SHALL CAREFULLY REVIEW ALL EXISTING CONDITIONS AND DETERMINE THE MOST FEASIBLE SEQUENCE FOR PERFORMING THE NEW WORK SO AS TO
AVOID CONFLICTS IN THE FIELD.
6. ANY AREAS OR SPACES NOT CLEARLY DEFINED OR INDICATED BY NOTES SHALL BE OF SAME MATERIAL AND FINISH AS AREAS OF SIMILAR USE OR FUNCTION
ELSEWHERE IN THE BUILDING.
7. WALL AND CEILING FINISHES SHALL INCLUDE PROJECTIONS, BEAM ENCLOSURES, RECESSES, BULKHEADS, PILASTERS AND OTHER SIMILAR ITEMS.
8. ALL APPURTENANCES BUILT INTO OR THROUGH WALLS, INCLUDING DOORS, WINDOWS, DUCTS, FRAMES, LOUVERS, GRILLES, MECHANICAL WORK, ETC., SHALL FIT SNUGLY AND BE THOROUGHLY SEALED AROUND PERIMETERS. INSTALL FIRE SEALANT AROUND ALL PENETRATIONS THROUGH FLOORS, FIRE RATED WALLS AND SMOKE PARTITIONS IN ACCORDANCE WITH A UL LISTED ASSEMBLY. WORK AT EXTERIOR WALLS SHALL BE FLASHED OR OTHERWISE WATERPROOF SEALED.
9. FIELD CHECK ROUGH AND/OR FINISHED DIMENSIONS FOR ACCURATE FITTING OF CABINETS, COUNTERS, STOREFRONT, DOORS, FRAMES, FIXTURES, MILLWORK AND ALL OTHER INSTALLATIONS PRIOR TO SHOP OR FACTORY FABRICATION. PROVIDE AND INSTALL NECESSARY FILLER STRIPS, SCRIBE STRIPS, BASES, CLOSURES, FINISHES AND TRIM TO COMPLETE SUCH INSTALLATIONS. DIMENSIONS OF SUCH INSTALLATIONS SHALL BE CONSIDERED "NOMINAL". CONTRACTORS SHALL ACCOUNT FOR ALL MANUFACTURER'S REQUIRED TOLERANCES, CLEARANCES AND SHIM SPACE TO ENSURE PROPER INSTALLATION OF THE NEW WORK.
10. SEE EQUIPMENT PLANS AND FLOOR PLANS FOR CASEWORK, CABINETS, MILLWORK AND OTHER BUILT-IN ITEMS. COORDINATE WITH MEP DRAWINGS FOR SINKS, OUTLETS, AND OTHER ITEMS TO BE BUILT INTO SUCH ITEMS.
11. IF A DISCREPANCY APPEARS TO EXIST BETWEEN DRAWINGS AND/OR SPECIFICATIONS, THE MORE STRINGENT (TYPICALLY THE MORE COSTLY) REQUIREMENT SHALL APPLY. ITEMS DESCRIBED ON DRAWINGS, BUT NOT SPECIFIED, SHALL BE PROVIDED. CONTRACTOR SHALL BE RESPONSIBLE TO SUBMIT AN RFI TO SEEK
CLARIFICATION OF ANY PERCEIVED DISCREPANCY DURING BID PHASE.
12. WRITTEN INFORMATION ON DRAWINGS TAKES PRECEDENT OVER DRAWING LINES.
13. IN THE ABSENCE OF A WRITTEN DIMENSION, OR IN CASE OF DOUBT AS TO THE PROPER MEASUREMENT, CONSULT CONTRACTING OFFICER . DO NOT SCALE DRAWINGS. ASSUMPTIONS MADE, OR ACTIONS TAKEN, BASED ON SCALED DIMENSIONS SHALL BE AT THE CONTRACTOR'S RISK AND ANY RESULTING CORRECTIONS
SHALL BE PERFORMED BY CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.
14. EACH CONTRACTOR OR SUB-CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH THE WORK OF OTHER TRADES SHOWN THROUGHOUT THE COMPLETE SET OF CONTRACT DOCUMENTS. CHANGES RESULTING FROM A CONTRACTOR OR SUB-CONTRACTOR'S FAILURE TO OBTAIN AND REVIEW A COMPLETE SET OF
CONTRACT DOCUMENTS SHALL BE CORRECTED AT NO ADDITIONAL COST TO THE GOVERNMENT.
15. AT ALL CHANGES IN FLOOR FINISHES, PROVIDE AND INSTALL AN APPROPRIATE TRANSITION STRIP AS SHOWN ON THE DRAWINGS.
16. CONSULT HVAC AND ELECTRICAL DRAWINGS FOR LOCATIONS AND DESCRIPTIONS OF ACCESS PANELS, LOUVER OPENINGS, VENTILATORS, GRILLES, VALVE CABINETS, FIRE DAMPERS OR OTHER APPURTENANCES AFFECTING WALLS, CEILINGS OR FLOORS AND PROVIDE NECESSARY LINTELS, SUPPORT OR ANCHORING. IN
COORDINATION WITH SHOP DRAWINGS.
17. ELECTRIC SWITCHES, OUTLETS, THERMOSTATS, CONTROLS, CLOCKS, SPEAKERS, OR OTHER WALL-MOUNTED ACCESSORIES SHALL BE INSTALLED IN LOCATIONS WHICH ARE UNOBSTRUCTED BY CABINETS, COUNTERS, RACKS, MARKER AND TACKBOARDS, FIXTURES, SHELVING OR OTHER FURNISHING OR EQUIPMENT DESIGNATED FOR SPACES SHOWN ON DRAWINGS. WALL MOUNTED ITEMS ARE NOT TO BE INSTALLED ON, THROUGH, OR INTO, ANY EQUIPMENT OTHER THAN WALLS, UNLESS SPECIFICALLY NOTED OTHERWISE.
18. ELECTRICAL OUTLETS, CLOCKS, P.A. SPEAKERS, PULL STATIONS, EXIT SIGNS, OR OTHER DEVICES SHOWN DIAGRAMMATICALLY ON THE ARCHITECTURAL DRAWINGS SERVE TO ALERT CONTRACTORS OF THE PRESENCE OF SUCH DEVICES. CONSULT THE ELECTRICAL DRAWINGS FOR FURTHER INFORMATION AND ADVISE CONTRACTING OFFICER OF ANY PERCEIVED DISCREPANCY BETWEEN ARCHITECTURAL AND ELECTRICAL DRAWINGS REGARDING LOCATION OR TYPE OF DEVICES
SHOWN PRIOR TO PREPARING SUBMITTALS.
19. ELECTRIC SWITCHES, THERMOSTATS OR OTHER ELECTRONIC CONTROLS IN THE SAME VICINITY SHALL BE MOUNTED AT THE SAME HEIGHT FROM FLOOR (UNLESS
NOTED OTHERWISE) IN A UNIFORM, ORDERLY FASHION.
20. SUBMITTAL REVIEW - THE CONTRACT DOCUMENTS PROVIDE SIZES, DIMENSIONS, PRODUCT REQUIREMENTS, ETC. CONTRACTOR SHALL VERIFY THAT SUBMITTALS ARE COORDINATED WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS PRIOR TO SUBMISSION. A/E REVIEW OF SUBMITTALS IS NOT FOR THE PURPOSE OF DETERMINING THAT SIZES, DIMENSIONS, ETC MATCH WHAT HAS ALREADY BEEN PROVIDED IN THE CONTRACT DOCUMENTS. ALL DEVIATIONS FROM WHAT IS SHOWN ON THE CONTRACT DOCUMENTS SHALL BE CLOUDED ON THE SUBMITTAL OR OTHERWISE CLEARLY BROUGHT TO THE ATTENTION OF THE REVIEWER. FAILURE TO CLEARLY BRING ANY DEVIATION(S) TO THE ATTENTION OF THE REVIEWER SHALL BE UNDERSTOOD BY ALL PARTIES THAT WHAT IS SHOWN IN THE SUBMITTAL COMPLIES WITH THE CONTRACT DOCUMENTS REGARDLESS OF WHETHER OR NOT THE REVIEWER DISCOVERS THE DEVIATION. CHANGES RESULTING FROM THE CONTRACTOR'S FAILURE TO CLEARLY IDENTIFY DEVIATIONS IN SUBMITTALS SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY AND SHALL BE CORRECTED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.
21. CONTRACTORS SHALL CAREFULLY REVIEW EXISTING FIELD CONDITIONS AND COORDINATE ALL QUANTITIES, DIMENSIONS, AND TOLERANCES REQUIRED TO PERFORM THE WORK SHOWN ON THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR DETERMINING INFORMATION THAT PERTAINS SOLELY TO FABRICATION PROCESSES, INSTALLATION TECHNIQUES (MEANS AND METHODS), AND SEQUENCING OF THE WORK TO MEET THE REQUIREMENTS OF THE PROJECT SCHEDULE. EACH SUBCONTRACTOR SHALL COORDINATE WITH THE GENERAL CONTRACTOR PRIOR TO BEGINNING THEIR PORTION OF THE WORK. NO PORTION OF THE WORK SHALL
BEGIN WITHOUT APPROVED SUBMITALL FOR THAT ITEMOF WORK.
22. CONTRACTOR SHALL, AT ALL TIMES, MAINTAIN THE INTEGRITY OF EXISTING SMOKE PARTITION WALLS, SMOKE BARRIER WALLS, AND FIRE RATED WALLS TO REMAIN. SEE LIFE SAFETY DRAWINGS AND ARCHITECTURAL DRAWINGS FOR THE LOCATION OF THESE WALLS. CONSULT COR AND LOCAL VA FIRE / SAFETY PERSONNEL FOR CONFIRMATION OF THESE WALLS PRIOR TO BEGINNING DEMOLITION. DAMAGE TO ANY EXISTING-TO-REMAIN SMOKE PARTITION WALLS, SMOKE BARRIER WALLS, OR FIRE RATED WALLS, INCLUDING DAMAGE FROM REMOVAL OF INTERSECTING WALLS, SHALL BE REPAIRED AT CONTRACTOR’S EXPENSE.
23. PUBLIC EXITS SHALL REMAIN CLEAR AT ALL TIMES WHILE THE BUILDING IS OCCUPIED. NO STORAGE SHALL BE PERMITTED IN THE EXIT ACCESS. STORAGE WILL ONLY BE PERMITTED IN THE ENCLOSED CONSTRUCTION SITE, AND DESIGNATED SPACE WITH PRIOR APPROVAL OF THE VA COR.
24. PATCH ALL EXISTING AND NEW HOLES IN FLOORS, WALLS AND CEILINGS WITHIN THE PROJECT LIMITS. ENSURE THAT ALL EXISTING AND NEW PATCH WORK IS RATED TO THE LEVEL OF FLOORS, WALLS AND CEILINGS TO THE REQUIRED EXISTING CONDITION, PRIOR TO THE START OF NEW WORK.
25. UNLESS SPECIFIC DIMENSIONS ARE PROVIDED, MEP DRAWINGS ARE CONSIDERED "DIAGRAMMATIC". IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR(S) TO FIELD COORDINATE LOCATIONS, SEQUENCES, ETC FOR UNOBSTRUCTED INSTALLATION OF ITEMS THAT ARE SHOWN ON MEP DRAWINGS IN DIAGRAMMATIC FORM.
COORDINATE ABOVE-CEILING WORK OF MEP TRADES TO THAT EACH TRADE LOCATES THEIR WORK AS TIGHT TO THE STRUCTURE / DECK ABOVE AS IS FEASIBLE.
EACH SUCCESSIVE TRADE SHALL LOCATE THEIR WORK AS TIGHT TO THE TRADE BEFORE.
26. ALTHOUGH THE DRAWINGS AND SPECIFICATIONS ARE COMPLIMENTARY, SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. WHAT IS REQUIRED BY EITHER THE DRAWINGS OR SPECIFICATIONS SHALL BE INTERPRETED AS BEING REQUIRED AS PART OF THE SCOPE OF WORK FOR THIS PROJECT. ITEMS SPECIFIED, BUT NOT INDICATED ON THE DRAWINGS, SHALL BE PROVIDED. ITEMS SHOWN ON THE DRAWINGS, BUT NOT SPECIFIED, SHALL BE PROVIDED. ANY DISCREPANCIES BETWEEN THE CONTRACT DRAWINGS AND/OR SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO SEEK CLARIFICATION PRIOR TO SUBMITTING A BID AMOUNT IF THERE SHOULD APPEAR TO BE A DISCREPANCY BETWEEN DRAWINGS AND/OR THE SPECIFICATIONS. OTHERWISE, THE MOST STRINGENT (TYPICALLY THE MOST EXPENSIVE) REQUIREMENT SHALL APPLY AT THE DISCRETION OF THE COR AT NO
ADDITIONAL COST TO THE GOVERNMENT.
27. ABOVE-CEILING COORDINATION – PRIOR TO PERFORMING ANY ABOVE-CEILING WORK, THE CONTRACTOR, WORKING WITH ALL SUB-CONTRACTORS, SHALL CREATE DRAWINGS THAT SHOW COORDINATION OF ALL ABOVE-CEILING WORK ITEMS WITH EXISTING CONDITIONS AND PROPOSED CEILINGS. DRAWINGS SHALL INCLUDE CRITICAL CROSS-SECTIONS SHOWING BOTTOM OF EXISTING STRUCTURE, ALL NEW ABOVE-CEILING UTILIES (DUCTS, PIPES,, EQUIPMENT, POWER, DATA, ETC.) NEW SUPPORTS, AND DESIGNEDCEILING HEIGHTS. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE SEQUENCES OF INSTALLATION TO ENSURE THAT ABOVE-CEILING ITEMS CAN FIT ABOVE THE CEILING HEIGHTS INDICATED ON THE REFLECTED CEILING PLAN(S). CONTRACTOR SHALL BRING ALL PERCEIVED CONFLICTS TO THE ATTENTION OF THE ARCHITECT / ENGINEER FOR RESOLUTION PRIOR TO THE START OF THE WORK. CONFLICTS RESULTING FROM INACCURATE COORDINATION DRAWINGS AND / OR FAILURE TO IDENTIFY CONFLICTS PRIOR TO INSTALLATION OF THE WORK SHALL BE CORRECTED / ADJUSTED AT THE CONTRACTOR’S EXPENSE AND SHALL RESULT IN NO ADDITIONAL COST TO THE GOVERNMENT.
28 PRIOR TO BEGINNING PRODUCT-RELATED SUBMITTALS, THE CONTRACTOR SHALL PROVIDE A SUBMITTAL SCHEDULE THAT LISTS ALL PRODUCT-RELATED SUBMITTALS ANTICIPATED FOR THIS PROJECT. THE SUBMITTAL SCHEDULE SHALL INCLUDE SPECIFICATION SECTION, SUBMITTAL NAME, ANTICIPATED DATE TO BE
ISSUED, AND ANTICIPATED DUE DATE. PRIORITIZE SUBMITTALS SO THAT CRITICAL PATH SUBMITTALS ARE SUBMITTED FIRST. SCHEDULE SUBMITTALS TO AVOID MORE THAN FIVE (5) SUBMITTALS BEING DUE IN THE SAME FIVE (5) BUSINESS DAY TIME-PERIOD. FAILURE TO SUBMIT REQUIRED SUBMITTAL SCHEDULE WILL RESULT IN EXCESSIVE SUBMITTALS BEING REJECTED WITHOUT REVIEW OR WILL RELIEVE THE GOVERNMENT OF LIABILITY FOR DELAYED SUBMITTAL
REVIEWS. REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR SUBMITTALS AND CONSTRUCTION SCHEDULE.
DEDUCT ALTERNATE #1: EXTERIOR WINDOWS
BASE BID: REMOVE AND REPLACE EXTERIOR WINDOWS AS SHOWN ON THE CONSTRUCTION DOCUMENTS.
DEDUCT ALTERNATE: DO NOT REMOVE AND REPLACE EXTERIOR WINDOWS. LEAVE EXISTING EXTERIOR WINDOWS IN PLACE
DEDUCT ALTERNATE #2: INSTALL PNEUMATIC TUBE SYSTEM
BASE BID: FURNISH AND INSTALL PNEUMATIC TUBE SYSTEM AS SHOWN ON THE CONSTRUCTION DOCUMENTS.
DEDUCT ALTERNATE: DO NOT FURNISH AND INSTALL PNEUMATIC TUBE SYSTEM (INCLUDING STATIONS, BLOWER, TUBES, CLOSURES AT STATIONS, ETC.) PROVIDE GYPSUM BOARD ENCLOSURE AT CHASE WHERE STATIONS ARE TO BE LOCATED.
DEDUCT ALTERNATE #3: DUMBWAITER
BASE BID: FURNISH AND INSTALL DUMBWAITER AND ALL ASSOCIATED DEMOLITION, SHAFT, STRUCTURAL SUPPORTS, ETC. AS SHOWN ON
THE CONSTRUCTION DOCUMENTS.
DEDUCT ALTERNATE: DO NOT FURNISH AND INSTALL DUMBWAITER AND ALL ASSOCIATED DEMOLITION, SHAFT, STRUCTURAL SUPPORTS, ETC. AS SHOWN ON THE CONSTRUCTION DOCUMENTS.
1. THE WORK OF THIS CONTRACT MAY REQUIRE PARTIAL REMOVAL OR DISASSEMBLY OF EXISTING CEILINGS AND/OR WALLS FOR ACCESS TO SPACES WHERE NEW ITEMS ARE REQUIRED TO BE INSTALLED OR EXISTING ITEMS ARE REQUIRED TO BE DEMOLISHED. EXAMPLES OF ITEMS INCLUDE TELECOMMUNICATIONS, PLUMBING, ELECTRICAL, MECHANICAL, FIRE PROTECTION, STRUCTURAL, ETC. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THOROUGHLY REVIEWING THE CONSTRUCTION DOCUMENTS AND FOR DETERMINING THE EXTENT OF REMOVAL OR DISASSEMBLY WORK NECESSARY TO PERFORM THE WORK OF THIS PROJECT IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS
2. THE CONTRACTOR SHALL FIELD-VERIFY AND DOCUMENT THE EXISTING CONDITIONS OF CEILING OR WALL SURFACES TO BE REMOVED OR
DISASSEMBLED PRIOR TO BEGINNING THE WORK.
3. THE CONTRACTOR SHALL CAREFULLY REMOVE, OR DISASSEMBLE, EACH EXISTING CEILING OR WALL SURFACE IN A MANNER THAT PREVENTS DAMAGE TO ADJACENT EXISTING SURFACES. DAMAGE TO EXISTING SURFACES SHALL BE REPAIRED BY THE CONTRACTOR.
4. AFTER THE WORK HAS BEEN COMPLETED, THE CONTRACTOR SHALL REPLACE, PATCH, AND FINISH THE EXISTING SURFACE TO THE CONDITION
IT WAS IN PRIOR TO REMOVAL.
5. REFER TO PLUMBING DRAWINGS FOR LOCATIONS OF 3RD FLOOR DRAINS THAT REQUIRE WORK IN 2ND FLOOR CEILINGS. THESE NOTES SHALL
APPLY TO THE 2ND FLOOR WORK TO INSTALL ABOVE-CEILING WORK.
6. REFER TO STRUCTURAL DRAWINGS FOR STEEL SUPPORT ITEMS TO BE INSTALLED ABOVE 2ND FLOOR CEILINGS. THESE NOTES SHALL APPLY
TO THE 2ND FLOOR WORK TO INSTALL ABOVE-CEILING STEEL SUPPORT ITEMS.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
CFR ENGINEERING
20251 CENTURY BLVD.
SUITE 120
GERMANTOWN, MD 20874
877-871-4229
CONSULTANT:
IMEG CORP.
101 NORTH SEVENTH STREET
SUITE 404
LOUISVILLE, KY 40202
440-262-3063
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
08-20-2024
608-23-133
AuthorChecker
3RD FLOOR LABORATORY
CONSTRUCTION
100% CD SUBMISSION
GENERAL NOTES
GI300
-2
-1
G I3
.p d f
Manchester VAMC 718 Smyth Road Manchester, NH 03104
REFERENCES
SMOKING POLICY
MEDICAL WASTE NOTES
NOTE: SEE LIFE SAFETY DRAWINGS FOR SPECIFIC EDITIONS OF APPLICABLE CODES
GENERAL NOTES
HAZARDOUS MATERIALS NOTES
DEDUCT ALTERNATES
ACCESS TO EXISTING CONCEALED AREA NOTES:
CLOCK OR
CLOCK
OUTLET
MANUAL FIRE
ALARM PULL
STATION
LIGHT
SWITCH &
DIMMER
DUPLEX
OUTLET
(LOW)
DUPLEX
OUTLET
(HIGH)
DESK
INTERCOM
OUTLET
INTERCOM
STATION
PHONE/DATA
OUTLET
THERMOSTAT SPECIAL
PURPOSE
OUTLETS
OR
JUNCTION
BOX
SPECIAL
PURPOSE
OUTLETS
DARK ROOM
STATUS LIGHT
SWITCH AT
DOOR OR
CASED OPENING
AUDIBLE
AND/OR VISUAL
FIRE ALARM
SECURITY
STROBE LIGHT
(BLUE LIGHT)
FIREMAN'S
TELEPHONE
JACK
EMERGENCY
STROBE OR
LIGHT
RACEWAY
7'
T O
C O
N T
R O
LS
4'
-0
M A
X H
IG
H
R E
A C
H
3' -0
M
IN
T
O C
O N
T R
O
LS
1' -3
M
IN
L
O W
R E
A C
H
1'
A
LI
G N
W
IT
H T
O P
O F
A D
JA
C
E N
T F
R A
M
E 8" TYP 8" TYP
T O
P O
F B
O X
4'
7'
7'
7'
NURSE CALL
STATION
WITH
CONTROLS
NURSE CALL
STATION
WITHOUT
CONTROLS
5'
NURSE CALL
CORRIDOR
LIGHT (DOME
LIGHT)
7'
DUPLEX OUTLET
ABOVE
COUNTER /
BACKSPLASH
3"
WALL-MTD
TELEPHONE
OUTLET
CARD READER,
LOCAL ALARM,
OR ARMING
STATION
3'
COUNTER
TOP / TOP OF
BACKSPLASH
COAT
HOOKS
(WALL-MTD)
COAT HOOK
(DOOR-MTD)
6"
5'
EQ EQ
6'
T O
C O
N T
R O
LS
4'
-0
M A
X H
IG
H
R E
A C
H
3' -0
M
IN
T
O C
O N
T R
O
LS
1' -3
M
IN
L
O W
R E
A C
H
MEDICAL
GAS ALARM
PANEL
FEC OR
FHV CABINET
1' - 0"
5'
4'
"12" 42"
40"
P L U
M B
IN
G
W A
L L
6" 42"
T O
IL
E
T S
ID
E
W A
L L
6" 36"
S
ID
E W
A L L
12"36"
C O
N T
R O
L W
A L L
T O
IL
E
T S
ID
E
W A
L L
7"
IF A DOUBLE ROLL
DISPENSER IS PROVIDED,
DIMENSION IS TO ROLL
CLOSEST TO TOILET
TOILET PAPER
DISPENSER
S
ID
E W
A L L
15"
COUNTER
MOUNTED
LAVATORY
S
ID
E W
A L L
15"
WALL
MOUNTED
LAVATORY
C O
U N
T E
R H
E
IG
H T
WALL MOUNTED
POSTURE MIRROR
WALL MOUNTED
MIRROR
T O
R
E F
L E
C T
IN
G
S U
R F
A C
E
18"
MIRROR TO
BE 18" X 36" U.N.O
T O
O P
E R
T A
T
IO
N
CENTER
MIRROR
OVER SINK
U.N.O
S H
O W
E R
W A
L L
WALL MOUNTED
SHOWER SEAT
T O
WALL MOUNTED
SOAP DISPENSER
T O
O P
E R
A T
IO
N
S H
O W
E R
W A
L L
T O
IL
E
T C
.L
18"
SWING UP
GRAB BAR
T O
O P
E R
T A
T
IO
N
T O
T O
P
FIRE
EXTINGUISHER IN
FULLY RECESSED CABINET
WALL MOUNTED
MOP HOLDER
T O
F R
O N
T T
P
D G
E O
F D
E C
K
L
IP
W H
N
L
W E
R E
D
WALL MOUNTED
HORIZONTAL
DIAPER CHANGING
STATION
WALL MOUNTED
GRAB BAR
(TOILET SIDE)
WALL MOUNTED
GRAB BAR
(TOILET REAR)
WALL MOUNTED
SHOWER
GRAB BARS
WALL MOUNTED PAPER
TOWEL DISPENSER
(WITH OR WITHOUT
INTEGRAL
TRASH RECEPTICLE)
OR TO TOP OF
RIM, WHICHEVER
IS GREATER.
SWING UP
GRAB BAR
EQUIPMENT, PANEL BOARD,
CABINET, OR SIMILAR FEATURE
CRASH RAIL (ALL TYPES), UON
TYPE NO 1 (SHOWN),
TYPE NO 2, OR TYPE
NO 4 CORNER OR
EDGE GUARD
WHERE BUMPER/CRASH
RAILS TERMINATE OR DO
NOT TURN CORNER
BUMPER RAIL
(ALL TYPES),
UON
DOOR FRAME OR
CASED OPENING
FRAME
OUTLET OR SIMILAR
OUTLET OR
SIMILAR WHEN
ADJ TO FRAME
WHERE
BUMPER/CRASH
RAILS TURN
CORNER
CORNER OR
EDGE GUARD
CORNER OR EDGE
GUARD
COMBINATION
HANDRAIL/CRASH
RAIL (ALL TYPES),
UON
WHERE
TERMINATES
WHERE
COMBINATION
HANDRAIL /
CRASH RAIL
TURNS CORNER
DOOR FRAME OR
CASED
OPENING FRAME
CORNER OR EDGE
GUARD
RECESSED CORNER OR EDGE
GUARD EXTENDING FROM
FLOOR TO CEILING OR
HEADER, TYPICAL UNLESS
OTHERWISE NOTED
EQUIPMENT,
PANEL BOARD,
CABINET, OR
SIMILAR FEATURE
2'
0"
U O
N
1'
U O
N
4'
T Y
P E
2" TYP 2" TYP 2" TYP
4" TYP 4" TYP
2" TYP
T O
P O
F R
A
IL
2'
0"
2" TYP 2" TYP 2" TYP
7'
T
Y P
E N
O S
A
N D
2" TYP 2" TYP 2" TYP
T O
P O
F R
A
IL
2'
0"7'
T Y
P E
N O
S
A N
D
2" TYP
8" 4" TYP
8"
1'
2"
WP-01 WP-01
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
CFR ENGINEERING
20251 CENTURY BLVD.
SUITE 120
GERMANTOWN, MD 20874
877-871-4229
CONSULTANT:
IMEG CORP.
101 NORTH SEVENTH STREET
SUITE 404
LOUISVILLE, KY 40202
440-262-3063
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
08-20-2024
608-23-133
AuthorChecker
3RD FLOOR LABORATORY
CONSTRUCTION
100% CD SUBMISSION
TYPICAL MOUNTING HEIGHTS
GI301
-2
-1
G I3
/2
/2
.p d f
Manchester VAMC 718 Smyth Road Manchester, NH 03104
GENERAL MOUNTING HEIGHT NOTESTYPICAL MOUNTING HEIGHTS AND CLEARANCES
CORNER GUARD / BUMPER RAIL / CRASH RAIL / CORRIDOR HANDRAIL TYPICAL MOUNTING HEIGHTS AND CONFIGURATION DIAGRAMS
A. IT IS THE INTENT OF THE DESIGN THAT ALL ITEMS SHOWN MOUNTED AT TYPICAL HEIGHTS
BE ACCESSIBLE TO PERSONS WITH DISABILITIES.
B. THE PURPOSE OF THIS SHEET IS TO ILLUSTRATE TYPICAL MOUNTING HEIGHTS AND - WHERE
APPLICABLE - TYPICAL MINIMUM OR MAXIMUM CLEARANCES AND/OR TYPICAL MOUNTING
CONFIGURATIONS FOR A VARIETY OF ITEMS. CAUTION: THIS SHEET MAY ILLUSTRATE ITEMS
OR CONFIGURATIONS WHICH DO NOT OCCUR AS PART OF THE WORK OF THIS PROJECT.
REFER TO THE PLANS, ELEVATIONS, SECTIONS, DETAILS, AND SCHEDULES TO DETERMINE
WHICH ITEMS AND CONFIGURATIONS APPLY TO THE WORK OF THIS PROJECT.
C. THE MOUNTING HEIGHTS, CLEARANCES, AND CONFIGURATIONS SHOWN ON THIS SHEET ARE
TYPICAL AND SHALL APPLY TO ALL INSTANCES OF THE ITEM (OR GROUP OF ITEMS) SHOWN
UNLESS SPECIFICALLY NOTED OR DIMENSIONED OTHERWISE.
D. SPECIAL OR NON-TYPICAL MOUNTING HEIGHTS OCCUR ONLY WHERE INDICATED BY
ANNOTATED SYMBOLS; BY KEY NOTES; BY NOTES ON PLANS, ELEVATIONS, OR DETAILS; OR
BY UNIQUE DIMENSIONS ON ELEVATIONS OR DETAILS.
E. MOUNTING CONFIGURATION DIAGRAMS ARE ELEVATIONS WHICH ILLUSTRATE TYPICAL
RULES GOVERNING THE RELATIONSHIPS BETWEEN, AND PLACEMENT OF, ITEMS WHICH
OCCUR IN GROUPS OF RELATED ITEMS OR IN CLOSE PROXIMITY TO OTHER PARTS OF THE
WORK (SUCH AS SWITCHES AND DOOR FRAMES). UNLESS OTHER MOUNTING
CONFIGURATIONS ARE SPECIFICALLY NOTED, DIMENSIONED, OR ELEVATED, THE TYPICAL
RELATIONSHIPS, ARRANGEMENTS, AND THE TYPICAL CONFIGURATION DIAGRAMS APPLY
THROUGHOUT THE WORK OF THIS PROJECT.
382 SF
CALL CENTER
W347 303 SF
OFFICE
W348
185 SF
STAIR NO.3
W349
CH
AS
E
31 SF
UTILITY RM
W352
182 SF
MALE TLT
W353
152 SF
STORAGE
W354
159 SF
EXAM ROOM
W355
83 SF
LACTATION RM
W357
61 SF
BIOHAZARD
W356 22 SF
ELEC.
W357A
FIRE CL
382 SF
BIOMED
W346
297 SF
OFFICE
W345
146 SF
OFFICE
W341
289 SF
OFFICE
W342
286 SF
OFFICE
W343
283 SF
STORAGE
W344
34 SF
TOILET
W340
384 SF
OFFICE
W339
LC
CORRIDOR
CORRIDOR
AREA NOT IN SCOPE
A B C D F
H I K LJ
NOT IN SCOPE
NOT IN SCOPE
285 SF
EXAM ROOM
N363
269 SF
EXAM ROOM
N362
142 SF
EXAM
W366
38 SF
BATH
N386A
31 SF
TLT
N387A28 SF
STOR.
N386B
103 SF
FEMALE
W370
11 SF
TEL CL
N359A
125 SF
SPD STOR
N359
151 SF
STORAGE
N358
ELEVATOR NO.1
ELEVATOR NO.2
SERVICE
ELEVATOR NO.3
46 SF
DUMBWAITER
CLOSET
N361
53 SF
TOILET
N360
G
E
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
CFR ENGINEERING
20251 CENTURY BLVD.
SUITE 120
GERMANTOWN, MD 20874
877-871-4229
CONSULTANT:
IMEG CORP.
101 NORTH SEVENTH STREET
SUITE 404
LOUISVILLE, KY 40202
440-262-3063
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
08-20-2024
608-23-133
AuthorChecker
3RD FLOOR LABORATORY
CONSTRUCTION
100% CD SUBMISSION
EXISTING CONDITIONS PLAN
GC200
-2
-1
G C
/2
/2
.p d f
Manchester VAMC 718 Smyth Road Manchester, NH 03104
1/8" = 1'-0"A15
EXISTING CONDITIONS PLAN - 3RD FLOOR
NFPA 101 LIFE SAFETY CODE 2021 MANCHESTER NEW HAMPSHIRE
RENOVATE LAB
TOTAL PROJECT AREA 7,800 SF
OCCUPANCY COUNT BUSINESS USE:
7,800 SF / 150 SF PER
BUSINESS USE CONDENSED:
7,800 SF / 50 SF PER
OCCUPANT = 52 OCCUPANTS
EGRESS CAPACITY PROVIDED EXIT DOOR: 48" DOOR 48/.2 = 240
OCCUPANTS MAX.
TOTAL EGRESS CAPACITY 240 OCCUPANTS
CORRIDOR MINIMUM 72" ALLOWED BY VA STANDARDS
94" EXISTING EXIT CORRIDORS
CHAPTER 39 – EXISTING BUSINESS OCCUPANCY
39.2 MEANS OF EGRESS REQUIREMENTS
39.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH CHAPTER 7 AND THIS
CHAPTER.
7.1.10 MEANS OF EGRESS RELIABILITY
7.1.10.1 MEANS OF EGRESS SHALL BE CONTINUOUSLY MAINTAINED FREE OF ALL
OBSTRUCTIONS OR IMPEDIMENTS TO FULL INSTANT USE IN THE CASE OF FIRE OR
OTHER EMERGENCY.
39.5.2 HEATING, VENTILATING, AND AIR-CONDITIONING. HEATING, VENTILATING, AND AIR-
CONDITIONING EQUIPMENT SHALL COMPLY WITH THE PROVISIONS OF SECTION 9.2.
9.2.1 AIR CONDITIONING, HEATING, VENTILATION DUCTWORK, AND RELATED EQUIPMENT. AIR
CONDITIONING, HEATING, VENTILATION DUCTWORK, AND RELATED EQUIPMENT SHALL BE IN
ACCORDANCE WITH NFPA 90A.
39.2.2.2. DOORS
39.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE PERMITTED
39.2.3 CAPACITY OF MEANS OF EGRESS.
39.2.3.1 THE CAPACITY OF MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH SECTION
7.3
7.3 / TABLE 7.3.3.1 THE CAPACITY OF MEANS OF EGRESS PROVIDING TRAVEL BY MEANS
OF STAIRS SHALL BE 0.3 IN. PER PERSON, AND THE CAPACITY OF MEANS OF EGRESS
PROVIDING HORIZONTAL TRAVEL (WITHOUT STAIRS) BY MEANS SUCH AS DOORS,
RAMPS, OR HORIZONTAL EXITS SHALL BE 0.2 IN. PER PERSON.
39.2.3.2 THE CLEAR WIDTH OF ANY CORRIDOR OR PASSAGEWAY SERVING AN
OCCUPANT LOAD OF 50 OR MORE SHALL BE NOT LESS THAN 44 IN.
39.2.4 NUMBER OF MEANS OF EGRESS
39.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE FOLLOWING, EXCEPT AS
OTHERWISE PERMITED
(2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED ON EVERY STORY.
39.2.5 ARRANGEMENT OF MEANS OF EGRESS
39.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN ACCORDANCE WITH SECTION 7.5.
7.5.1.3.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE IWHT SECTION 9.7, THE MINIMUM
SPEARATION DISATNACE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT DISCHARGES,
MEASURED IN ACCORDANCE WITH 7.5.1.3.2, SHALL BE NOT LESS THAN ONE-THIRD THE
LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR AREA
TO BE SERVED.
39.2.5.2.1 IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED
AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1), DEAD-END
CORRIDORS SHALL NOT EXCEED 50 FT.
39.2.5.3.1 COMMON PATH OF TRAVEL SHALL NOT EXCEED 100 FT IN A BUILDING
PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER
SYSTEM IN ACCORDANCE WITH 9.7.1.1(1).
39.2.6 TRAVEL DISTANCE TO EXITS
39.2.6.3 TRAVEL DISTANCE SHALL NOT EXCEED 300 FT IN BUSINESS OCCUPANCIES
THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
ACCORDANCE WITH 9.7.
39.2.7 DISCHARGE FROM EXITS. EXITS SHALL COMPLY WITH SECTION 7.7.
7.7.1 EXIT TERMINATION. EXITS SHALL TERMINATE DIRECTLY, AT A PUBLIC WAY OR AT
AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH
7.7.1.4
7.7.1.2 THE REQUIREMENT OF 7.7.1 SHALL NOT APPLY TO INTERIOR EXIT DISCHARGE AS
OTHERWISE PROVIDED IN 7.7.2.
7.7.2 EXIT DISCHARGE THROUGH INTERIOR BUILDING AREAS. EXITS SHALL BE PERMITTED TO
DISCHARGE THROUGH INTERIOR BUILDING AREAS, PROVIDE THAT ALL OF THE FOLLOWING
ARE MET:
(1) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER OF EXIT STAIRS SERVING
NORMALL OCCUPIED AREAS OF EACH FLOOR, AND NOT MORE THAN 50 PERCENT OF THE
EXIT STAIR CAPACITY REQUIRED FOR NORMALLY OCCUPIED AREAS OF EACH FLOOR,
SHALL DISCHARGE THROUGH AREAS ON ANY LEVEL OF DISCHARGE, EXCEPT AS
OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
(A)ONE HUNDRED PERCENT OF THE EXITS SHALL BE PERMITTED TO DISCHARGE
THROUGH AREAS ON ANY LEVEL OF DISCHARGE IN DETENTION AND CORRECTIONAL
OCCUPANCIES AS OTHERWISE PROVIDED IN CHAPTERS 22 AND 23.
(B) IN EXISTING BUILDINGS, THE 50 PERCENT LIMIT ON EGRESS CAPACITY SHALL NOT
APPLY IF THE 50 PERCENT LIMIT ON THE REQUIRED NUMBER OF EXITS IS MET.
(2) EACH LEVEL OF DISCHARGE SHALL DISCHARGE DIRECTLY OUTSIDE AT THE FINISHED
GROUND LEVEL OR DISCHARGE DIRECTLY OUTSIDE AND PROVIDE ACCESS TO THE
FINISHED GROUND LEVEL BY OUTSIDE STAIRS OR OUTSIDE RAMPS.
(3) THE INTERIOR EXIT DISCHARGE SHALL LEAD TO A FREE AND UNOBSTRUCTED WAY
TO THE EXTERIOR OF THE BUILDING, AND SUCH WAY SHALL BE READILY APPARENT OR
SHALL BE IDENTIFIABLE BY EXIT SIGNAGE FROM THE POINT OF DISCHARGE FROM THE
EXIT.
(4) THE INTERIOR EXIT DISCHARGE SHALL BE PROTECTED BY ONE OF THE FOLLOWING
METHODS:
(A) THE LEVEL OF DISCHARGE SHALL BE PROTECTED THROUGHOUT BY AN APPROVED
AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7, OR THE PORTION
OF THE LEVEL OF DISCHARGE USED FOR INTERIOR EXIT DISCHARGE SHALL BE
PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
SECTION 9.7 AND SHALL BE SEPARATED FROM THE NONSPRINKLERED PORTION OF THE
FLOOR BY FIRE BARRIERS WITH A FIRE RESISTANCE RATING MEETING THE
REQUIREMENTS FO RTHE ENCLOSURE OF EXITS.
(5) THE ENTIRE AREA ON THE LEVEL OF DISCHARGE SHALL BE SEPARATED FROM AREAS
BELOW BY CONSTRUCTION HAVING A FIRE RESISTANCE RATING NOT LESS THAN THAT
REQUIRED FOR THE EXIT ENCLOSURE, UNLESS OTHERWISE PERMITED IN 7.7.2(6).
(6) LEVELS BELOW THE LEVEL OF DISCHARGE IN AN ATRIUM SHALL BE PERMITTED TO
BE OPEN TO THE LEVEL OF DISCHARGE WHERE SUCH LEVEL OF DISCHARGE IS
PROTECTED IN ACCORDANCE WITH 8.6.7.
BULK SUPPLY
W307
HAZ STOR
W306
MECHANICAL
ROOM
W309
STAIR
NO.3
SUPERVISOR
OFFICE
N319
SUPERVISOR
OFFICE
N318
CHIEF
PATHOLOGIST
N316
URIANALYSIS
W310
BLOOD BANK
W311
MANAGER
OFFICE
N317
HISTOLOGY
W305
MICROBIOLOGY
W304
CHEMISTRY,
HEMATOLOGY,
COAG., GLYCOS.
W303
SEND OUT AREA
W302
INTAKE/PROC
W301
HAC
W308
CORRIDOR
W312
MECHANICAL
ROOM
N312
HOOD-
HOOD-
FU
ME
HO
OD
NOT IN SCOPE
NOT IN SCOPE
CORRIDOR
N320
FEC
PATH TO EXIT 83'-9"
REQUIRED TRAVEL DISTANCE:
UNDER 100'-0"
FEC
CONFERENCE
ROOM
W300A
BREAK ROOM
W300
HATCHED AREA DENOTES 2HR FLOOR INFILL
FOR EXISTING LINEN CHUTE
TELECOM ROOM
W300B
GROUP OFFICE
N315
WOMEN TOILET
N314
MEN TOILET
N313
WAITING ROOM
N321PATH TO EXIT 25'-3"
DEAD END CORRIDOR DISTANCE:
UNDER 50'-0"
CODE ANALYSIS LEGEND
1 HOUR FIRE BARRIER PER NFPA 101 8.6 /
19.3.2.1.2. OPENINGS FIRE RATED FOR 45
MINUTES UNLESS SHAFT, EXIT ENCLOSURE, OR
EXIT PASSAGEWAY WALLS WHICH REQUIRE 1
HOUR RATED OPENINGS.
2 HOUR FIRE BARRIER PER NFPA 101 8.2.
OPENINGS FIRE RATED FOR 90 MINUTES.
EGRESS PATH WITH NAME, SEGMENT LENGTH,
AND DIRECTION INDICATEDPATH A
OPENING RATING IN MINUTES
OPENING RATING IN MINUTES
FEC FIRE EXTINGUISHER CABINET
EXIT SIGN
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revision s:
Dat e: CONSULTANTS:
/8
'-0
4 '
8 '
6 '
/4
'-0
/8
'-0
/2
'-0
/4
'-0
'-0
-1 /2
'-0
'-0
CONSULTANT:
COMPANY NAME
COMPANY
ADDRESS
COMPANY
ADDRESS
XXX-XXX-XXXX
CONSULTANT:
COMPANY NAME
COMPANY ADDRESS
COMPANY ADDRESS
XXX-XXX-XXXX
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA
22314 703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
2 '
2 '
08/20/2024
608-23-133
AuthorChecker
3RD FLOOR LABORATORY
CONSTRUCTION
100% CD SUBMISSION
LIFE SAFETY ANALYSIS AND 3RD
LEVEL PLAN
LS100
8-
-1
. L
S1
. 1 1/
/2
3.
pd f
Manchester VAMC 718 Smyth Road Manchester, NH 03104
1/8" = 1'-0"1 3RD LEVEL LIFE SAFETY FLOOR PLAN
1. REMOVE WALL(S) INCLUDING FINISHES, DOORS, WINDOWS, FRAMES AND ALL OTHER
RELATED ITEMS. REMOVE WALLS FROM EXISTING SLAB TO STRUCTURE ABOVE.
2. REMOVE ALL ROOM FINISHES. REMOVE FLOOR FINISHES DOWN TO SLAB (INCLUDES
FLOORING, BASE, ALL ADHESIVES, GROUT, ETC). PREPARE EXISTING SLAB TO RECEIVE
NEW FLOORING.
3. REMOVE PERIMETER WALL GYPSUM BOARD DOWN TO EXISTING EXTERIOR WALL
STRUCTURE.
4. REMOVE DOOR(S) AND FRAME(S). (TO INCLUDE STOPS, HOLD OPENS, ANCHORS AND
THRESHOLDS WHERE THEY OCCUR)
5. REMOVE SINK AND ASSOCIATED ACCESSORIES.
6. REMOVE CASEWORK / MILLWORK AND ALL ANCHORS, BLOCKING, ETC.
7. CAREFULLY REMOVE EXISTING EXTERIOR WINDOW AND SILL, INCLUDING FRAME, CLIPS,
BLOCKING, ETC.
8. REMOVE CERAMIC TILE AND BASE.
9. REMOVE ALL CEILINGS AND BULKHEADS INCLUDING ALL ANCHORS, HANGERS, LIGHTING
DEVICES, ETC.
10. REMOVE DISPLAY / DIRECTORY CASE - SALVAGE TO OWNER.
11. REMOVE ALL PLUMBING FIXTURES & ACCESSORIES (GRAB BARS, WALL-MOUNTED
DISPENSERS, ETC). SEE M.E.P. DWGS. FOR FIXTURE & PIPING DEMOLITION.
12. REMOVE BATHROOM STALLS & TOILET PARTITIONS.
13. REMOVE ALL UNIT HEATERS, RADIATORS, PIPING, CONCRETE BASE, ETC. REFER TO MEP
DRAWINGS.
14. SALVAGE AND RELOCATE ACCESS CONTROL PANELS.
15. CAREFULLY SAWCUT AND REMOVE EXISTING FLOOR SLAB AND STRUCTURE TO CREATE
OPENING FOR NEW DUMBWAITER. REFER TO DUMBWAITER DETAILS AND
STRUCTURAL.
DEMOLITION KEY NOTES #
CALL CENTER
W347
OFFICE
W348
STAIR NO.3
W349
CH
AS
E
UTILITY RM
W352
MALE TLT
W353
STORAGE
W354
EXAM ROOM
W355
LACTATION RM
W356
BIOHAZARD
W357
ELEC.
W357A
FIRE CL
BIOMED
W346
OFFICE
W345
OFFICE
W341
OFFICE
W342
OFFICE
W343
STORAGE
W344
TOILET
W340 OFFICE
W339
LC
CORRIDOR
1 11
11 1
11 11 1
1 1
1 111
11111
2 3 2 3 2 3 2 3 2 3
2 3
2 3
2 3 2 3 2 3 2 3 2 3
2 3
44 4 4
5 5
7 7
7 7 7 7 7 7 7 7 7 7
7 7 7 7 7
8 8
8 8
8 8
9 9 9 9
2 9
13 13 13 13 13 13 13 13 13
13 13 13 13 13 13 13 13 13 13
13 13 13
A B C D F
H I K L
J
J
4 4
4 4
A3
A3
A3
3 3
5 5
13 13
2 2
2 2 2
2'
1/
4"
4 1
1 1111
4 4
2'
1/
2"
A4
AD101
G
E
AE908
A17
7 7 7
TYP.
CAUTION: OPENING IN FLOOR
FOR MECHANICAL SHAFT
2'
1 1 1 1
1 1
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
CONSULTANT:
CFR ENGINEERING
20251 CENTURY BLVD.
SUITE 120
GERMANTOWN, MD 20874
877-871-4229
CONSULTANT:
IMEG CORP.
101 NORTH SEVENTH STREET
SUITE 404
LOUISVILLE, KY 40202
440-262-3063
ARCHITECT:
CB DESIGN GROUP
421 KING ST.
SUITE 301
ALEXANDRIA, VA 22314
703-772-4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
J
K
12345678910111213141516
08-20-2024
608-23-133
AuthorChecker
3RD FLOOR LABORATORY
CONSTRUCTION
100% CD SUBMISSION
DEMOLITION PLAN
AD100
-2
-1
A D
.p d f
Manchester VAMC 718 Smyth Road Manchester, NH 03104
W347 - CALL CENTER W348 - OFFICE W352 - UTILITY RM W353 - MALE TLT W354 - "STORAGE" W355 - EXAM ROOM W357 - BIOHAZARD
W339 - OFFICEW340 - TOILETW341 - OFFICEW342 - OFFICEW343 - OFFICEW343 - CORRIDOR W344 - STORAGEW346 - BIOMED
GENERAL DEMOLITION NOTES
D1 CONCRETE SLABS TO REMAIN SHALL BE PATCHED, SCRAPED, LEVELED, AND CLEANED TO
PROVIDE SURFACE SUITABLE FOR NEW FINISHES. CONTRACTOR IS RESPONSIBLE FOR
PROVIDING ALL CONCRETE SLAB DEMOLITION AND REPLACEMENT NECESSARY TO INSTALL
NEW WORK.
D2 PARTITIONS SHOWN TO BE REMOVED SHALL BE CONFIRMED BY THE CONTRACTOR AS TO
TYPE OF PARTITION AND EXACT LOCATION. COMPLETELY REMOVE PARTITIONS FROM FLOOR
TO STRUCTURE, INCLUDING ALL FASTENERS, GROUTS, SEALANTS, ETC, UNLESS NOTED
OTHERWISE. MASONRY PARTITIONS WHICH EXTEND THROUGH THE SLAB SHALL BE REMOVED
TO 8" BELOW FINISH FLOOR. FILL SLAB OPENING WITH CONCRETE FILL TO RECEIVE FLOOR
FINISH. WHERE WALLS SCHEDULED TO BE REMOVED SIT ON SLABS, GRIND SLAB TO RECEIVE
FLOOR FINISH. REMOVAL OF WALLS / PARTITIONS SHALL INCLUDE ALL ITEMS MOUNTED ON
AND IN THE WALL / PARTITION.
D3 REMOVE, PATCH, AND REPAIR PORTIONS OF WALL PARTITIONS WHICH CONFLICT WITH NEW
WORK TO BE INSTALLED, EVEN IF NOT SPECIFICALLY NOTED TO BE DEMOLISHED ON PLANS.
D4 WALLS TO BE REMOVED FROM INTERSECTING MASONRY WALLS SHALL INCLUDE TOOTHED-IN
REPLACEMENT OF DAMAGED MASONRY ON WALL TO REMAIN AND REMOVAL OF TIES
PROJECTING FROM WALLS.
D5 ALL EXISTING STRUCTURE SHALL REMAIN, UNLESS NOTED OTHERWISE.
D6 COORDINATE DEMOLITION OF ALL STRUCTURAL ITEMS (COLUMNS, BEAMS, SLABS, ETC) WITH
STRUCTURAL DRAWINGS. EXTENT OF DEMOLITION AREA SHALL BE IN ACCORDANCE WITH
STRUCTURAL REQUIREMENTS AND COORDINATED WITH ALL NEW WORK.
D7 TEMPORARILY SUPPORT ALL BEAMS, LINTELS, PORTIONS OF WALLS, ETC, TO BE DISTURBED
BY DEMOLITION WORK UNTIL THEY ARE RE-SUPPORTED BY NEW WORK.
D8 CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF EXISTING
BUILDING ELEMENTS TO REMAIN THROUGHOUT THE SEQUENCE OF WORK. ANY DAMAGE TO
EXISTING BUILDING CONDITIONS SHOWN TO REMAIN SHALL BE RESTORED TO NEW WORK
CONDITION AT NO ADDITIONAL COST TO THE OWNER.
D9 WINDOWS SCHEDULED FOR REMOVAL SHALL BE REMOVED COMPLETELY. FASTENERS MAY
BE CUT FLUSH WITH HEAD, JAMBS, AND SILLS IF THE NEW WINDOW UNIT WILL CONCEAL
FASTENER. PROTECT EXISTING SILLS SCHEDULED TO REMAIN. ALL EXISTING WINDOW
OPENINGS MUST BE FIELD MEASURED.
D10 WHERE FINISHES ARE INDICATED TO BE REMOVED, REMOVAL SHALL INCLUDE ANY GROUT,
ADHESIVES, FASTENERS, AND ALL OTHER ITEMS USED TO ATTACH THE FINISHES TO THE
SURFACES THEY COVER.
D11 WHERE CEILINGS ARE TO BE REMOVED, REMOVE ALL CEILING SYSTEMS COMPLETELY,
INCLUDING GRID, TRIM, HANGERS, CLIPS, ETC. DOUBLE CEILINGS ARE NOT PERMITTED
WHERE NEW CEILINGS ARE SPECIFIED. REMOVE ALL ORIGINAL CONCEALED CEILINGS WHERE
ENCOUNTERED. WHERE HARD CEILINGS ARE TO BE REMOVED, REMOVE ENTIRE CEILING
INCLUDING FRAMING AND SUPPORTS.
D12 ALL EXISTING SURFACES TO REMAIN SHALL BE PROTECTED, PATCHED/REPAIRED/REPLACED
IF DAMAGED, AND CLEANED PRIOR TO APPLICATION OF FINISHES.
D13 CONTRACTOR TO PROTECT ALL EQUIPMENT AND OTHER EXISTING ELEMENTS IN SCOPE OF
NEW WORK AND DEMOLITION AREA.
D14 REMOVE ALL WINDOW TREATMENTS IN AREAS OF RENOVATION AND DEMOLITION UNLESS
NOTED OTHERWISE.
D15 REFER TO,…