This document is the specification for the Americlad AC-4000 Insulated Metal Infill Panel System, a one-inch five-ply insulated metal panel for use as exterior and interior cladding. The specification covers the general requirements, performance criteria, submittals, quality assurance, delivery and handling, warranty, materials, fabrication, and installation of the panel system. Key details include the aluminum sheet materials, core materials, tolerances, finishes (paint and anodized), and installation requirements such as use of setting blocks, sealants, and perimeter clearance. This specification is intended to be used as part of a larger construction project, but the specific contract opportunity details are provided separately.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMERICLAD® AC-4000
www.americlad.com
866-260-4047
Copyright 2023 Quality Metalcrafts, LLC
MANUFACTURER:
Americlad, LLC 21925 Industrial Blvd.
Rogers, MN 55374 Telephone: (866) 260-4047 Fax: (763) 255-3399 Email: info@americlad.com
SECTION 07 42 00 / 08 44 00
INSULATED METAL INFILL PANEL
(ONE INCH FIVE PLY)
PART 1 – GENERAL
1.1 RELATED DOCUMENTS
A. The drawings and provisions of the General Conditions, and the sections included under Division 1 specification sections, apply to this section
1.2 SUMMARY
A. This section includes insulated metal infill panels that are used as the exterior and interior cladding
1.3 PERFORMANCE REQUIREMENTS
A. Design panel system to accommodate tolerance of plus or minus 1/16” in overall panel thickness and plus or minus 1/8” in any direction
B. Structural Performance: provide exterior and interior wall cladding assemblies to meet effects of load and stresses from wind loads
1.4 SUBMITTALS
A. Product Data: Manufacturer’s product literature B. Manufacturer’s standard color charts C. Finish Samples: submit color samples for final approval D. Shop Drawings: submit shop drawings showing plans, sections and details
AMERICLAD
AC-4000
Panel System mailto:info@americlad.com
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications: Minimum of five years experience in manufacturing of metal wall panel products B. Installer Qualifications: Acceptable to manufacturer
1.6 DELIVERY, STORAGE AND HANDLING
A. Delivery: deliver metal panels in manufacturer’s crates packed for long haul transit
B. Storage: store materials in a dry and safe area C. Handling: handle materials to avoid any damage to materials and finishes
1.7 WARRANTY
A. The contractor must warrant the materials to be free of defects in accordance with the general conditions. Finish warranty shall be extended by paint manufacturer’s standard warranty
PART 2 – PRODUCTS
2.1 MANUFACTURER
A. Americlad, LLC 21925 Industrial Boulevard, Rogers, Minnesota 55374, Telephone: (866) 260-4047, www.americlad.com
1. AC-4000 Insulated Metal Infill Panel System (one inch five ply panel)
B. Approved equal submitted for approval 10 days prior to bid
2.2 MATERIALS
A. Aluminum Sheet: ASTM B209, Aluminum Association specification
1. 3003-H14/3105-H14/5052-H32 for painted finishes
2. 5005-H34 for anodized finish
B. Thickness: 1” (one inch) overall thickness C. Exterior Skin shall be ________________. (Specify). Color shall be
___________ (Specify) D. Stabilizer sheet under both faces shall be 1/8” thick E. Core shall be 2.5# density Expanded Polystyrene Foam or
Polyisocyanurate Foam F. Interior Skin shall be ________________(Specify). Color shall be
____________(Specify)
2.3 FABRICATION
A. Tolerances
1. Width and Length to be plus or minus 1/8”
2. Thickness to be plus or minus 1/16” http://www.americlad.com/
B. Panel surfaces shall be free from defects, scratches or marks caused during fabrication
2.4 ACCESSORIES
A. Installer shall supply all materials required for installation
2.5 FINISHES
A. Paint:
1. Coating shall be a Spray Applied Fluorocarbon Resin
Utilizing a 70% Kynar 500/Hylar 5000 resin
2. Color as selected by owner from paint manufacturer’s standard colors or Custom color as specified
3. Material to be painted in accordance with either AAMA specification 2605 or 2604 B. Anodized:
1. Class I, Clear Anodic Finish: AA-M12C22A41, mechanical finish, nonspecular as fabricated. Coating to have an anodic coating of 0.7 mil (0.018 mm) thickness
2. Class I, Color Anodic Finish: AA-M12C22A42/A44, mechanical finish, nonspecular as fabricated. Color to be determined by Owner. Coating to have an anodic coating of 0.7 mil (0.018) thickness
PART 3 – EXECUTION
3.1 PREPARATION
A. Coordinate drawings, diagrams, and instructions for installation
3.2 INSTALLATION
A. Setting blocks should be at quarter points of each panel and in a width equal or larger than the panel thickness
B. Panels to be sealed with Class A grade sealants C. Weep holes for frame assemblies to accommodate proper draining D. The entire panel perimeter should be engaged into the framing system to allow a minimum of 5/8” E. A minimum of ¼” of clearance must be maintained around the panel perimeter
3.3 CLEANING AND PROTECTION
A. Clean exposed surfaces after installation per manufacturer’s recommendation B. Touch up minor abrasions in finish with touch up paint supplied by finish applicator
END OF SECTION