ACM Inspection Report 2020-10 Building 1.pdf

PDF 22 MB Posted

Attached to
Z1DA--608-23-133, Third Floor Lab Construction Federal contract opportunity
Solicitation number
36C24124B0052
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This document is an ACM Inspection Report for Building 1 dated October 2020. The related federal contract opportunity is Solicitation Number 36C24124B0052 for Z1DA--608-23-133, Third Floor Lab Construction at the Manchester, VAMC. This is an invitation for bid issued by the Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 1. The solicitation is for the construction of a third-floor laboratory. Relevant details and requirements are provided in the attached solicitation documents. No further information is included in this specific file.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--608-23-133, Third Floor Lab Construction, newest first.
File Type Posted
603-23-133 Third Floor Lab Construction RFIs and Answers 9-20-2024.pdf PDF
Revised SOW - 608-23-133 Third Floor Lab Construction 8-7-2024.pdf PDF
VA.MHT Lab Reno -AD102 - BID RFI 133.pdf PDF
36C24124B0052 0004.pdf PDF
AC-4000_ALUMINUM-INSULATED-1-INCH-INFILL-PANEL-SYSTEM-SPECIFICATIONS.pdf PDF
07 81 00 Applied Fireproofing -Bid RFI 83.pdf PDF
VA MHT Lab Reno - Addendum 1 MEP Sheets.pdf PDF
Warranty_Roofs_23_19_15_14.pdf PDF
01 45 29 Testing Laboratory Services - Bid RFI 81.pdf PDF
608-23-133 Lab project existing conditions photos.pdf PDF
36C24124B0052 0003.pdf PDF
Attachment 1 Site Visit Sign-In Lab Project.pdf PDF
VA.MHT Lab Reno -100% Bid Set at full size.pdf PDF
Attachment 2 Manchester Lab Specs Vol. 2.pdf PDF
36C24124B0052 0002.pdf PDF
Attachment 3 of 5 VA MHT 100 Percent Design.pdf PDF
36C24124B0052 0001.pdf PDF
Attachment 2 of 5 VA MHT 100 Percent Design.pdf PDF
Attachment 6 Manchester Lab 100 Percent Bid Set Specs.pdf PDF
Attachment 5 of 5 VA MHT 100 Percent Design 02.pdf PDF
Attachment 1 of 5 VA MHT 100 Percent Design.pdf PDF
Attachment 4 of 5 VA MHT 100 Percent Design.pdf PDF
Davis-Bacon Act WD NH20240021.docx DOCX document
S02 PRE-AWARD CONTRACTOR EVALUATION FORM.docx DOCX document
608-23-133 3rd Floor Lab JandA Brand Name Products v1.pdf PDF
Instructions to Bidders.docx DOCX document
23031.00 VA.MHT Lab Reno 95 CD VA Submission compressed.pdf PDF
36C24124B0052_1.docx DOCX document
SOW - 608-23-133 Third Floor Lab Construction 8-7-2024.pdf PDF
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Update & Maintain Asbestos Inspection 2020

Project 608-18-104

Building 1

Prepared for:

Veterans Affairs Medical Center (VAMC)

Manchester (MAN) 718 Smyth Road

Manchester, NH 03104

Prepared by:

HGS Engineering, Inc.

1121 Noble Street Anniston, Alabama 36201

October 2020

Manchester VA Medical Center—October 2020

Table of Contents

Executive Summary

Methodology

Appendix A Summary of Asbestos Containing Materials

Appendix B Analytical Report

Appendix C Picture Log

Appendix D Drawings

Appendix E Certifications

Executive Summary

HGS Engineering (HGS) conducted an asbestos inspection of Building 1 at the Veterans Affairs Medical Center Manchester (VAMC MAN) in February and March 2020. The HGS Engineering, Inc. onsite Project/Safety Manager was Whitt Wilkins. Main inspection efforts were performed by Tim Thompson, a licensed New Hampshire asbestos inspector with supplemental inspections being conducted by Whitt Wilkins.

Building 1 has nine floors, which consists of approximately 189,400 square feet of space.

This building functions as the main hospital. The building contains a full basement, with supplemental tunnels used for steam piping running throughout the building. In discussion with VAMC MAN personnel, several changes were noted as having occurred to the building since the previous report, with renovations to flooring and pipe insulation occurring on several floors due to water leaks and other activities.

On February 10, 2020, Tim Thompson performed an asbestos re-assessment of Building 1 using the previously provided report completed in 2009 by ATC Associates. This report was used by HGS to update the presence of the asbestos-containing materials (ACM) found. This report identifies 105 homogenous materials throughout Building 1; HGS walked and visually inspected all areas and took eighteen bulk samples for laboratory analysis. Laboratory Resources and Solutions (LRS) in Ashville, Alabama, analyzed all eighteen samples. Three samples tested positive for asbestos in room N71 in the basement. These samples were added and highlighted in blue to Appendix A. Sample locations and results were also added to the AutoCAD drawings.

On March 17, 2020, Whitt Wilkins conducted inspections inside the steam tunnels in Building 1 using approved permit-required confined space entry procedures. Most materials (consisting of thermal system insulation, (TSI)) were found to be non-ACM, abated since the 2009 report. However, five samples of suspected ACM were collected and sent to be analyzed by LRS. Four samples tested positive for asbestos in room N86.

These samples were added and highlighted in blue to Appendix A. Sample locations and results were also added to the AutoCAD drawings.

HGS also reviewed previous abatement reports provided by the contracting officer’s representative (COR). All materials found to be abated after the 2009 inspection were removed from Appendix A and were highlighted in yellow. HGS also reviewed additional inspections and any additional samples taken after the 2009 inspection but before the 2020 inspection were highlighted in green and added to Appendix A.

HGS did not take any exterior samples, remove any floor tiles, or create holes in any drywall. This building shows no asbestos issues requiring immediate attention. The floor tiles are in good condition, and routine maintenance should last for an extended amount of time. The information presented in this report should be used as a base for future renovations, abatements, and other work.

Methodology

HGS Engineering performed an asbestos re-assessment survey that assessed all locations identified in two previous reports. The survey required HGS to locate and then identify all previously identified ACM. The survey also re-assessed the condition of any remaining ACM. If the ACM could not be accessed due to renovation, this was noted in the report. If the ACM had been removed, this was also pointed out in the report. The report includes recommendations for any remaining ACM to include being included in the facility Asbestos Operations and Maintenance (O&M) Report.

HGS Engineering started this process with an extensive walkthrough of the facility to attempt to locate the building material, and homogenous areas identified in previous reports and make notes of current building materials that may not have been tested in previous surveys. HGS received excellent information from personnel that had been at this site for many years about when areas were remodeled or replaced.

HGS selected sampling locations by identifying materials suspected to contain greater than 1 percent asbestos based on observable differences, group the material building-wide, and collect samples using a building-wide random sampling plan. When and if additional samples needed to be taken, HGS used non-destructive processes. All sampling was performed in an unobtrusive area if at all possible.

HGS Engineering collected all samples of suspected ACM per the Environmental Protection Agency (EPA) and the Occupational Safety and Health Administration (OSHA) regulations preventing airborne fiber exposure to the surveyor and facility personnel. Samples collected in occupied office spaces were taken in locations that minimize the risk of potential occupants' potential exposure and the visual impact of the resulting sample location. HGS restored any visible sample locations to a condition as close to the original as possible. HGS encapsulated all locations to prevent any subsequent release of asbestos fibers after sample collection. HGS marked sample locations, except for conspicuous sample locations within occupied areas. HGS photographed sample locations at the time of sample collection to aid in future identification of sampling location.

HGS utilized inconspicuous sample locations and employed methods that were least disruptive to finished surfaces where sampling was required of accessible suspect materials. HGS used non-destructive means for collecting samples. HGS repaired areas disturbed by sampling. For example, a hole utilized for sampling insulation was covered via tape if possible.

The procedure used for sampling was:

1. Place a plastic drop cloth under all friable material (as applicable) before taking the sample.

2. Put on appropriate personal protective equipment when necessary.

3. Thoroughly sprayed water on friable materials (as applicable) before removing a sample.

4. Penetrate all layers of material being sampled.

5. Place the sample in the numbered sample container, seal the container, and wipe the container with a wet wipe.

6. Clean the sampling tool and wet wipe or high efficiency particulate air filter

(HEPA) vacuum the plastic drop cloth.

7. Clean and “restore” the area.

8. Discard any potentially asbestos-contaminated waste which has been generated, as well as any other materials that may have become contaminated in a labeled asbestos waste bag.

Each location from which a sample was taken, and any area in which asbestos or suspect asbestos debris may have fallen, was cleaned using appropriate methods (e.g., wet wiping, HEPA vacuuming) following the collection of the sample. The site from which a bulk sample of thermal system insulation was taken was sprayed with a commercial sealant, caulked, and taped. No attempt was made to restore the surface to its original condition.

Sample locations in mechanical rooms, utility rooms, etc., were labeled with the sample number and date.

All precautions were taken to prevent the exposure of VAMC MAN personnel, visitors, and other occupants of the building. Any hazardous wastes generated during the inspection were dealt with appropriately according to all relevant federal, state, and local laws, statutes, regulations, and standards.

HGS used a chain of custody records that conform to established EPA and U.S.

Department of Transportation procedures and be kept for all samples taken and submitted for each building by the Lead Inspector.

HGS's inspection team photographed representative sample sites of each material sampled to document the material's appearance and the general condition. Photographs were made of notable exceptions of the general condition of the material. Photos were labeled to avoid any confusion.

APPENDIX A

SUMMARY OF ASBESTOS CONTAINING MATERIALS

Appendix A Summary of Asbestos Containing Materials

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response Assessment

Under Basement -

ACM

Pipe Insulation4 1-37 NA Fair 7/5

Rooms E07, E20, E30, N86, W46, W53, W63

ACM identified in 2009 report & since removed Added from additional inspections done prior to 2020 report All samples taken in 2020

Condition

CRAWL SPACE/TUNNEL

Location(s) Material HA Estimated Quantity

The rooms identified to the left with tunnel access are discussed in subsequent sections of the report, with the language "Under" preceding each room number in the Location column. The access point in N100 was not entered to the significant amount of flowing & standing water in tunnel.

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-1

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response Assessment

Black Waterproofing Mastic Along Exterior Wall

1-11 450 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

HALocation(s) Material

Room E02A - Non-ACM

Condition

BASEMENT

Room E01 -

ACM

Room E02A -

ACM

Estimated Quantity

Room E01 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-2

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response Assessment

HALocation(s) Material Condition

Estimated Quantity

Black Waterproofing Mastic Along Exterior Wall

1-11 250 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

Room E02C -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA

Room E02C - Non-ACM

Room E03 - Non-ACM

Room E02B -

ACM

Room E03 -

ACM

Room E02B - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-3

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response Assessment

HALocation(s) Material ConditionEstimated Quantity

Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room E04 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Pipe Insulation – Enclosed in Ceiling Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Green Pebble Style Terrazzo Floor

1-50 NA NA NA

Room E06 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Tan Pebble Style Terrazzo 1-45 NA NA NA

Room E07 -

ACM

Room E06 - Non-ACM

Room E07 - Non-ACM

Room E05 -

ACM

Room E04 - Non-ACM

Room E05 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-4

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response Assessment

HALocation(s) Material ConditionEstimated Quantity

Under Room E07- Non ACM

TSI- Yellow fiber 1-72-1 NA NA NA

Room E08 Will be inspected during next visit

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Gray Duct Sealant 1-15 NA NA NA Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room E09 -

ACM

Room E09A -

ACM

Room E09 - Non-ACM

Room E09A - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-5

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Gray Duct Sealant 1-15 NA NA NA

Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

Room E10 Will be inspected during next visit

Room E11 Will be inspected during next visit

Room E12 Will be inspected during next visit

Room E13 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room E14 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room E15 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Blue Pebble Style Sheet Flooring 1-18 NA NA NA

Yellow Mastic Associated with Blue Pebble Style Sheet Flooring

1-19 NA NA NA

2' x 2' Ceiling Tile 1-10 NA NA NA

Room E15 - Non-ACM

Room E13 - Non-ACM

Room E14 -

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-6

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Black Waterproofing Mastic Along Exterior Wall

1-11 150 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Blue Pebble Style Sheet Flooring 1-18 NA NA NA

Yellow Mastic Associated with Blue Pebble Style Sheet Flooring

1-19 NA NA NA

2' x 2' Ceiling Tile 1-10 NA NA NA Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room E18 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Tan Pebble Style Sheet Flooring 1-51 NA NA NA

Room E16 - Non-ACM

Room E18 - Non-ACM

Room E17 - Non-ACM

Room E17 -

ACM

Room E16 -

ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-7

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Yellow/Black Mastic Associated with Tan Pebble Style Sheet Flooring

1-52 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room E19 - Assumed – Pipe Insulation –

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA HVAC Duct Flange Sealant 1-74 NA NA NA

Room E20 Non ACM

TSI- Yellow fiber 1-72-1 NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 75 sq ft Good 7/5

Assumed – Pipe Insulation –

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

2' x 4' Ceiling Tile 1-41 NA NA NA HVAC Duct Flange Sealant 1-74 NA NA NA 12” x 12” Multi-Color Floor Tile in pattern and Associated Mastic

1-35, 1-36 730 sq ft Good 7/5

Black Waterproofing Mastic Along Exterior Wall

1-11 20 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA

Room E21 -

Room E19 - Non-ACM

Room E21 -

ACM

Room E22 -

ACM

Room E22 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-8

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA Pink Spray-on Fireproofing Insulations

1-34 NA NA NA

12” x 12” Multi-Color Floor Tile in pattern and Associated Mastic

1-35, 1-36 20 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA Pink Spray-on Fireproofing Insulations

1-34 NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 200 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room E25 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room E23 -

ACM

Room E24 -

ACM

Room E22A - Non-ACM

Room E22A -

ACM

Room E23 - Non-ACM

Room E24 - Non-ACM

Room E25 -

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-9

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Black Waterproofing Mastic Along Exterior Wall

1-11 120 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room E27 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA

Room E28 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 2 Radiator Enclosures

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA

Room E29 -

ACM

Room E29 -

Room E26 - Non-ACM

Room E26 -

ACM

Room E28 - Non-ACM

Room E27 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-10

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 200 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 2 Radiator Enclosures

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Under Room E30- Non ACM

TSI- Yellow fiber 1-72-1 NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 50 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA

Room E30 - Non-ACM

Room E30A - Non-ACM

Room E30 -

ACM

Room E30A -

ACM

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-11

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Gray Duct Sealant 1-15 NA NA NA Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

Room E32 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Blue Pebble Style Sheet Flooring 1-18 NA NA NA

Room E31 - Non-ACM

Room E32 -

Room E31 -

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-12

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Yellow Mastic Associated with Blue Pebble Style Sheet Flooring

1-19 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 400 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 2 Radiator Enclosures

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Blue Pebble Style Sheet Flooring 1-18 NA NA NA

Yellow Mastic Associated with Blue Pebble Style Sheet Flooring

1-19 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

Room E34 Will be inspected during next visit

Room E35 Will be inspected during next visit

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA

Room E33 -

ACM

Room E36 -

ACM

Room E36 -

Room E33 -

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-13

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Gray Duct Sealant 1-15 NA NA NA Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

2' x 2' Ceiling Tile 1-10 NA NA NA Pink Spray-on Fireproofing Insulations

1-34 NA NA NA

9” x 9” Tan Floor Tile 1-72 400 sq ft Fair 7/5 Black Waterproofing Mastic Along Exterior Wall

1-11 200 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Computer Floor Stanchon Mastic 1-71 NA NA NA

Black Mastic Associated with 9” x 9” Tan Floor Tile

1-73 NA NA NA

Room E37 -

ACM

Room E38 -

Room E38 -

Room E37 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-14

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Red Firestop Sealant 1-40 NA NA NA Pink Spray-on Fireproofing Insulations

1-34 NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Room E38A - Non-ACM

Red Firestop Sealant 1-40 NA NA NA

12” x 12” Multi-Color Floor Tile in pattern and Associated Mastic

1-35, 1-36 730 sq ft Good 7/5

Black Insulating Pipe Wrap 1-05 350 ln ft Fair 5/5 Black Waterproofing Mastic Along Exterior Wall

1-11 20 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA Pink Spray-on Fireproofing Insulations

1-34 NA NA NA

Room E39A -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Tan Pebble Style Sheet Flooring 1-51 NA NA NA

Yellow/Black Mastic Associated with Tan Pebble Style Sheet Flooring

1-52 NA NA NA

Covebase Mastic 1-14 NA NA NA

Black Waterproofing Mastic

1-11 100 sq ft Good 7/5Room E39B -

Room E39 -

Room E39A - Non-ACM

Room E38A -

ACM

Room E39 -

ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-15

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Pipe Insulation – Enclosed in Ceiling Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Tan Pebble Style Sheet Flooring 1-51 NA NA NA

Yellow/Black Mastic Associated with Tan Pebble Style Sheet Flooring

1-52 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Gray Duct Sealant 1-15 NA NA NA

Side Black Waterproofing 070610-91348-B01A NA NA NA E39B/East

Side Non-ACM

Black Waterproofing 070610-91348-B01B NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 150 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Pipe Insulation – Enclosed in Ceiling Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Tan Pebble Style Sheet Flooring 1-51 NA NA NA

Yellow/Black Mastic Associated with Tan Pebble Style Sheet Flooring

1-52 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Gray Duct Sealant 1-15 NA NA NA Black foam pipe insulation 070810-91348-B01B NA NA NA

Room E39B -

Room E39C -

ACM

Room E39C - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-16

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Pipe Insulation – Enclosed in Ceiling Chase

NA NA NA 7/5

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Tan Pebble Style Sheet Flooring 1-51 NA NA NA

Yellow/Black Mastic Associated with Tan Pebble Style Sheet Flooring

1-52 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Gray Duct Sealant 1-15 NA NA NA

E39E (corridor) Non-ACM

Black foam pipe insulation 070810-91348-B01A NA NA NA

12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 365 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Ceiling Chase

NA NA NA 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Red Firestop Sealant 1-40 NA NA NA Pink Spray-on Fireproofing Insulations

1-34 NA NA NA

12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 165 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA

Room E39D -

ACM

Room N66 -

ACM

Room N67 -

ACM

Room E39D - Non-ACM

Room N66 - Non-ACM

Room N67 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-17

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA 12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 150 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA

Room N68 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Red Firestop Sealant 1-40 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 900 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Red Firestop Sealant 1-40 NA NA NA

Room N70 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Red Firestop Sealant 1-40 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 400 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 4 Radiator Enclosures

NA NA NA 7/5

Room N67A -

ACM

Room N69 - Non-ACM

Room N70 - Non-ACM

Room N68 -

Room N67A -

Room N69 -

ACM

Room N71 -

ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-18

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Gray Duct Sealant 1-15 NA NA NA Interior Window Frame Caulk 1 -

4 Windows

1-31 NA NA NA

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Gray Duct Sealant 1-15 NA NA NA Red Firestop Sealant 1-40 NA NA NA

Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 150 sq ft Good 7/5

TSI- white wrap/mastic 1-72-3 1-72-4 1-72-9

20 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Transite – 1 Radiator Enclosure

NA NA NA 7/5

Interior Window Frame Caulk 1 -

1 Window 1-31 NA NA NARoom N72 -

Non-ACM

Room N71A -

ACM

Room N72 -

ACM

Room N71 - Non-ACM

Room N71A - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-19

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

TSI- Yellow fiber 1-72-1 1-72-2 1-72-5 1-72-6 1-72-7 1-72-8 1-72-10 1-72-11 1-72-12 1-72-13

NA NA NA

Room N73 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA 12" x 12" White with Tan Fleck Floor Tile

1-56 NA NA NA

Black Mastic Associated with 12" x 12" White with Tan Fleck Floor Tile

1-57 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA Red Firestop Sealant 1-40 NA NA NA Interior Window Frame Caulk 1 -

1 Window

1-31 NA NA NA

Room N74 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 200 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA

Room N75 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA

Room N74 - Non-ACM

Room N74A - Non-ACM

Room N74A -

Room N73 -

Room N75 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-20

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Ceramic Tile Grout 1-90 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room N76 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room N76A -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 300 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Ceramic Tile Grout 1-90 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Red Duct Sealant 1-42 NA NA NA Pipe Hanger Insulation 1-03 NA NA NA

Room N77 -

ACM

Room N78 -

ACM

Room N76A - Non-ACM

Room N78 - Non-ACM

Room N76 -

Room N77 -

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-21

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Room N81 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Green Pebble Style Terrazzo Floor

1-50 NA NA NA

Room N82 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Tan Pebble Style Terrazzo 1-45 NA NA NA

Room N83 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 1,100 sq ft Good 7/5

Black Waterproofing Mastic Along Exterior Wall

1-11 175 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA

Base Coat Plaster 1-27 NA NA NA Ceramic Tile Grout 1-90 NA NA NA Covebase Mastic 1-14 NA NA NA Red Firestop Sealant 1-40 NA NA NA 12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 220sq ft Good 7/5

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 185 sq ft Good 7/5

Room N85 - Non-ACM

Room N81 - Non-ACM

Room N82 - Non-ACM

Room N85 -

ACM

Room N86 -

ACM

Room N84 -

ACM

Room N84 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-22

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Red Firestop Sealant 1-40 NA NA NA

Under Room N86-

ACM

TSI- Aircell, gray,black, and off white wrap

1-86-1 1-86-2 1-86-3 1-86-4

10 sq ft Good 7/5

Under Room N86- Non ACM

TSI- Aircell, gray,black, and off white wrap

1-86-5 NA NA NA

12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 300 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Multi-Color Fleck Floor Tile

1-16 NA NA NA

Black Mastic Associated with 12" x 12" White with Multi-Color Fleck Floor Tile

1-17 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Red Firestop Sealant 1-40 NA NA NA 12” x 12” Multicolor in Pattern Floor Tile and Associated Mastic

1-35, 1-36 320 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA

Room N87 -

ACM

Room N88 -

ACM

Room N87 -

Room N86 -

Room N88 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-23

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA 12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 1,100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

2' x 2' Ceiling Tile 1-10 NA NA NA Room N91 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Red Firestop Sealant 1-40 NA NA NA

Room N92 -

ACM

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Room N89 -

ACM

Room N90 -

ACM

Room N90 - Non-ACM

Room N89 - Non-ACM

Room N91 -

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-24

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" Light Blue Floor Tile with Dark Blue Fleck

1-21 NA NA NA

Black Mastic Associated with 12" x 12" Light Blue Floor Tile with Dark Blue Fleck

1-22 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 150 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 125 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA Black Waterproofing Mastic Along Exterior Wall

39824 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Room N93 - Non-ACM

Room N93A - Non-ACM

Room N92 - Non-ACM

Room N93 -

ACM

Room N93A -

ACM

Room N94 -

ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-25

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA 12" x 12" White with Gray Fleck Floor Tile

1-69 NA NA NA

Black Mastic Associated with 12" x 12" White with Gray Fleck Floor Tile

1-70 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 150 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Ceramic Tile Grout 1-90 NA NA NA 12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 130 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA Pink Spray-on Fireproofing Insulations

1-34 NA NA NA

Red Firestop Sealant 1-40 NA NA NA 12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 20 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room N96 -

ACM

Room N95 - Non-ACM

Room N96 - Non-ACM

Room N94A - Non-ACM

Room N94 - Non-ACM

Room N94A -

ACM

Room N95 -

ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-26

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Pink Spray-on Fireproofing Insulations

1-34 NA NA NA

Red Firestop Sealant 1-40 NA NA NA 9” x 9” Gray/ Black Floor Tile 1-75 20 sq ft Fair 7/5 Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Pipe Insulation – Enclosed in Ceiling Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Black Mastic Associated with 9” x 9” Gray/ Black Floor Tile

1-76 NA NA NA

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Pipe Insulation – Enclosed in Ceiling Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Green Pebble Style Terrazzo Floor

1-50 NA NA NA

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Assumed – Pipe Insulation – Enclosed in Ceiling Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Red Firestop Sealant 1-40 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 150 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Yellow Carpet Mastic 1-23 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA

Room NW1 -

Room N99 -

Room N97 -

ACM

Room N98 -

ACM

Room N99 -

ACM

Room NW1 - Non-ACM

Room N97 - Non-ACM

Room N98 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-27

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Pink Spray-on Fireproofing Insulations

1-34 NA NA NA

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Woodgrain Pattern Sheet Flooring

1-12 NA NA NA

Yellow/Black Mastic Associated with Woodgrain Pattern Sheet Flooring

1-13 NA NA NA

Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 200 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Yellow Carpet Mastic 1-23 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA Black Waterproofing Mastic Along Exterior Wall

1-11 200 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA Yellow Carpet Mastic 1-23 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 2' Ceiling Tile 1-10 NA NA NA 12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 380 sq ft Good 7/5

Black Waterproofing Mastic Along Exterior Wall

1-11 350 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall Chase

NA NA NA 7/5

Room NW5 -

Room NW2 -

Room NW3 -

ACM

Room NW4 -

ACM

Room NW2 - Non-ACM

Room NW3 - Non-ACM

Room NW4 - Non-ACM

Notes:

Please refer to the report for information regarding the scope of work and limitations of this inspection to include details of ACM removal actions as well as crawl space information. A-28

VA Medical Center Manchester Building #1

AHERA

Hazard

/Response

Skim Coat Plaster 1-26 NA NA NA Base Coat Plaster 1-27 NA NA NA

Sheetrock 1-01 NA NA NA Joint Compound 1-02 NA NA NA Yellow Carpet Mastic 1-23 NA NA NA Covebase Mastic 1-14 NA NA NA 2' x 4' Ceiling Tile 1-41 NA NA NA 12” x 12” Tan Mottled Floor Tile and Associated Mastic

1-105, 1-106 125 sq ft Good 7/5

Black Waterproofing Mastic Along Exterior Wall

1-11 100 sq ft Good 7/5

Assumed – Pipe Insulation – Enclosed in Wall…