VA Hospital 7-16-2020.pdf.COPY.pdf
PDF 126 KB Posted
- Attached to
- Y1DA--Inpatient Ware Renovation 405-13-104
- Solicitation number
- 36C24120R0142
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Client: VA Hospital Location: White River Juction VT Date: 16-Jul-20 Tested by: Dan & Kevin
Pump Identification: Aurora Mod: 6-483B Ser# 79-65166 Rated GPM 1500 Rated PSIG: 96 Rated PSIG @ 0% : 112 Suction Pipe: 6 3 Rated GPM @ 2250 PSIG @ 150% : 72 Rated Pump RPM: 1770 Discharge Pipe: 6 3
* * * Distance from the pumping water level to the center of the discharge gauge in FEET - Vertical Turbine Pumps 0.00 Feet
Rated Pump RPM
As Tested Pump
RPM
Test Discharge Pressure
Test Suction
Pressure (+ or -)
Test Net Head
(PSIG)
Nozzle Diameters Nozzle "K" Test Nozzle
Pitot Pressure
Calculated Test Flow
(GPM)
ACTUAL
FLOW
(GPM)
(rpm corrected)
ACTUAL
NET HEAD
(PSIG)
(rpm corrected)
Actual % of Rated Flow
1770 1797 190 74.00 116.00 1.750 0.97 0 0 0 113 0 "A-B" Leg Amperage Voltage "B-C" Leg Amperage Voltage "A-C" Leg Amperage Voltage
Average 0.00 0.00
1770 1790 175 68.00 107.00 1.750 0.97 32 501 496 105 "A-B" Leg Amperage Voltage 1.750 0.97 32 501 496 "B-C" Leg Amperage Voltage 1.750 0.97 32 501 496 "A-C" Leg Amperage Voltage 1.750 0.97 0 0 0
Average 0.00 0.00 1.750 0.97 0 0
1.750 0.97 0 0
1.750 0.97 0 0
TOTAL 1504 1487 105 99.13%
1770 1787 144 60.00 84.00 1.750 0.97 40 560 555 82 "A-B" Leg Amperage Voltage 1.750 0.97 40 560 555 "B-C" Leg Amperage Voltage 1.750 0.97 41 567 562 "A-C" Leg Amperage Voltage 1.750 0.97 41 567 562
Average 0.00 0.00 1.750 0.97 0 0
1.750 0.97 0 0
1.750 0.97 0 0
TOTAL 2256 2234 82 148.95%
RATED 0 112
1500 96 2250 72
ACTUAL 0 113
1487 105 2234 82
#REF! #REF!
#REF! #REF!
Suction Gauge:
Discharge Gauge:
280 Heritage Ave. Unit F Portsmouth, NH 03801
Pump Performance Test Report Phone: (603) 319-4171 Fax: (603) 319-4173
0 500 1000 1500 2000 2500
PUMP PERFORMANCE CURVES (Actual Test is RPM Corrected)
MANUFACTURER'S TEST CURVE
ACTUAL TEST PERFORMANCE CURVE
RPM Corrected
File details come from the government source that posted it. Updated .