20200803-182827-VA_Hospital_Electric_Run_Checklist.pdf

PDF 718 KB Posted

Attached to
Y1DA--Inpatient Ware Renovation 405-13-104
Solicitation number
36C24120R0142
Issued by

View the file

Other files

File Type Posted
36C24120R0142 0005.docx DOCX document
Nurse Call RFI Responses.docx DOCX document
408.08115.31.A104.pdf PDF
408.08115.31.A103.pdf PDF
S06 RFIs Responses from COR and AE.docx DOCX document
VA Hospital 7-16-2020.pdf.COPY.pdf PDF
36C24120R0142 0004.docx DOCX document
VAMC-WRJ Building 31 Drawing 31-AS-106-DA-5.pdf PDF
VAMC-WRJ Building 31 Drawing 31-AS-110-DA5-SKA-01.pdf PDF
VAMC-WRJ Building 31 Structural Drawings.pdf PDF
36C24120R0142 0003.docx DOCX document
Headwall Service Panels.pdf PDF
028211 Asbestos Abatement Rev-1.pdf PDF
IMG 6306 Above Patient Rm 192.pdf PDF
VAMC Project 405-13-109 DA-5 Drawings 04162018.pdf PDF
VAMC-WRJ Building 31 Nursing Unit 31-M-505-DA-5.pdf PDF
31-AS-105B ABATEMENT DIAGRAM LEVEL-1 Revision 1.pdf PDF
36C24120R0142 0002.docx DOCX document
Building 31 Nursing Unit Patient Lift System Turn-Key Design-Build 08192020.pdf PDF
31-AS-110-DA4.pdf PDF
P07 Wages.pdf PDF
S04 Site Vist 2.pdf PDF
36C24120R0142 0001.docx DOCX document
Inpatient Ward Renovation RFIs as of 8-25-2020.docx DOCX document
S04 Site Vist 1.pdf PDF
S02 Drawings 05012019 1.pdf PDF
S02 SPEC Vol 1 May1 2019.pdf PDF
S02 SPEC Vol 2 May1 2019.pdf PDF
36C24120R0142 Solicitation.docx DOCX document
S02 Wage Determination.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INSPECTION DETAILS

Date: 07/16/2020

Inspector Name Dan & Kevin

Location Name VA Hospital

Address 101 Veterans Drive

City White River Junction

State VT

Zip Code

Inspection Time 08:00 AM

Pump Room Locaton Basement room 15

Fire Sprinkler Contractor Unknown

GPS

Picture of Jobsite

RT Stearns

280 Heritage Ave, Unit F

Portsmouth, NH

03801

Date: 08/03/2020Electric Run Checklist

Submitted by Dan Hill at 08/03/2020 18:28 UTC Page: 1

Captured at 08/03/2020 18:28 UTC gocanvas.com

Submission ID: E93CA8B7-838F-4A5A-86F5-DA73178537B2 https://maps.google.com/?q=43.648869,-72.342850&z=14 https://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link

FIRE PUMP INFORMATION

Pump Manufacturer Aurora

Fire Pump Type Horizontal

Fire Pump Model 6-483-18B

Fire Pump Serial Number 79-65166

GPM Rating 1500

PSIG Rating 100% 100

PSIG Rating 150%

PSIG Rating 0% (Churn or Shutoff)

Pump RPM

Fire Pump Nameplate

RT Stearns

280 Heritage Ave, Unit F

Portsmouth, NH

03801

Date: 08/03/2020Electric Run Checklist

Submitted by Dan Hill at 08/03/2020 18:28 UTC Page: 2

Captured at 08/03/2020 18:28 UTC gocanvas.com

Submission ID: E93CA8B7-838F-4A5A-86F5-DA73178537B2

FIRE PUMPÊCONTROLLER INFORMATION

Fire Pump Controller Manufacturer SYLVANIA

Fire Pump Controller Model A10-308483

Fire Pump Controller Serial Number 297550-1-1

Fire Pump Controller Method of Start Primary Resist

Transfer switch? NO

Fire Pump Controller Voltage Rating 208/3/60

Fire Pump Controller Nameplate

RT Stearns

280 Heritage Ave, Unit F

Portsmouth, NH

03801

Date: 08/03/2020Electric Run Checklist

Submitted by Dan Hill at 08/03/2020 18:28 UTC Page: 3

Captured at 08/03/2020 18:28 UTC gocanvas.com

Submission ID: E93CA8B7-838F-4A5A-86F5-DA73178537B2

JOCKEY PUMP CONTROLLER INFORMATION

Jockey Pump Controller Manufacturer GE

Jockey Pump Controller Serial Number 335F1604S

Jockey Pump Controller Voltage Rating 460/3/60

Jockey Pump Controller Model 55-526374

Jockey Pump Controller Nameplate

RT Stearns

280 Heritage Ave, Unit F

Portsmouth, NH

03801

Date: 08/03/2020Electric Run Checklist

Submitted by Dan Hill at 08/03/2020 18:28 UTC Page: 4

Captured at 08/03/2020 18:28 UTC gocanvas.com

Submission ID: E93CA8B7-838F-4A5A-86F5-DA73178537B2

JOCKEY PUMP INFORMATION

Jockey Pump Manufacturer BURNS PUMPS

Jockey Pump Serial Number 179744

Jockey Pump Model Number 310CS5M

Jockey Pump Horsepower 1.0

Jockey Pump Nameplate

RT Stearns

280 Heritage Ave, Unit F

Portsmouth, NH

03801

Date: 08/03/2020Electric Run Checklist

Submitted by Dan Hill at 08/03/2020 18:28 UTC Page: 5

Captured at 08/03/2020 18:28 UTC gocanvas.com

Submission ID: E93CA8B7-838F-4A5A-86F5-DA73178537B2

FIRE PUMP MOTOR INFORMATION

Fire Pump Motor Manufacturer US Motors

Fire Pump Motor Model Number

Fire Pump Motor Serial Number

Fire Pump Motor Horsepower 200

Fire Pump Motor Service Factor 1.15

Fire Pump Motor Locked Rotor Code B

Fire Pump Design Letter G

Fire Pump Motor FLA 228

Fire Pump Motor Voltage 460/3/60

Fire Pump Motor RPM 1770

Fire Pump Motor Nameplate

RT Stearns

280 Heritage Ave, Unit F

Portsmouth, NH

03801

Date: 08/03/2020Electric Run Checklist

Submitted by Dan Hill at 08/03/2020 18:28 UTC Page: 6

Captured at 08/03/2020 18:28 UTC gocanvas.com

Submission ID: E93CA8B7-838F-4A5A-86F5-DA73178537B2

CHECKLIST ITEMS

Heat in pump room is 40*F or higher? YES

Controller pilot light (power on) is illuminated? BULB IS NOT WORKING

All alarm pilot lights off? N/A

Transfer switch normal power light is illuminated (if applicable)?

N/A

Phase-reversal alarm is not illuminated? ( If applicable ) N/A

Isolating lever for standby power is closed? ( If applicable )

NOT APPLICABLE

Pump suction, discharge and bypass valves are open? YES

All piping free of leaks? YES

Verified fire pump packing drip rate? ( Recommend 1 drip per second )

YES

Packing drain cups free of stoppage? YES

Suction pressure normal? YES

Discharge pressure normal? YES

Is test header control valve in the closed position? YES

Suction reservoir is full? ( If applicable ) NOT APPLICABLE

Power to jockey pump is provided? YES

Inspect and test circuit breakers? YES

Check operation of all applicable alarms associated with the fire pump ( not sprinkler system )

N/A

Are all normal operational lights illuminated on tank status panel? ( if applicable )

NOT APPLICABLE

Checked tank status panel floats for proper operation? ( if applicable and accessible )

NOT APPLICABLE

CLOSE OUT INFORMATION AND SIGNATURE

Fire Pump Cut In Pressure 130

Fire Pump Cut Out Pressure* 135

* Fire pump cut out value is the pressure at which the pressure switch is reset and does not represent an automatic stop pressure setting. The fire pump is a manual stop only, unless otherwise stated in this checklist.

Jockey Pump Cut In Pressure 160

Jockey Pump Cut Out Pressure 170

Fire Pump Left In Service YES

Alarms Operational at Time of Departure YES

This Report Reviewed and Witnessed by:

RT Stearns

280 Heritage Ave, Unit F

Portsmouth, NH

03801

Date: 08/03/2020Electric Run Checklist

Submitted by Dan Hill at 08/03/2020 18:28 UTC Page: 7

Captured at 08/03/2020 18:28 UTC gocanvas.com

Submission ID: E93CA8B7-838F-4A5A-86F5-DA73178537B2

Job Notes:

This is an annual Pump test only.

1. Power to the jockey pump controller is fed from the fire pump controller, NFPA does not allow that practice .

2. The jockey pump suction piping is in the wrong location, it should be on the city side of the fire pump control valve.

3. Jockey pump and fire pump sensing lines are shared, NFPA would have the separated and in different locations.

4. The recommended location for the test header is between the fire pump discharge check valve and the discharge control valve.

Please note that the fire pump test report data information is taken from the actual test data. We are unsure of the actual factory data for this fire pump due to the fact that the impeller was trimmed to achieve a different churn pressure. The only supplied data that we were given was the 1500 gpm at

100 psi rating and that was on a piece of paper affixed to the pump.

RT Stearns

280 Heritage Ave, Unit F

Portsmouth, NH

03801

Date: 08/03/2020Electric Run Checklist

Submitted by Dan Hill at 08/03/2020 18:28 UTC Page: 8

Captured at 08/03/2020 18:28 UTC gocanvas.com

Submission ID: E93CA8B7-838F-4A5A-86F5-DA73178537B2