E2.0L_ FIRST FLOOR LIGHTING PLAN Rev.0 markup.pdf

PDF 874 KB Posted

Attached to
Z1AA--347-Boise RO Facility Maintenance Services
Solicitation number
36C10D24Q0188
Issued by

About this file

This document is the First Floor Lighting Plan for the Construct National Telehealth Hub project at the Boise VA Medical Center. The plan shows the layout and configuration of lighting fixtures on the first floor, including existing lights to remain, new lights to be installed, and modifications to the lighting control system. Key details include:

The lighting system will utilize the existing lighting control panel, with a new lighting control panel added on the second floor to provide networked lighting control. Existing lighting fixtures on the interior and exterior are to remain unless noted for removal. New lighting fixtures will be integrated with the existing branch circuiting and controls. The scope includes adding an unswitched lighting circuit for exit signs, and coordinating the new lighting layout with architectural elements. The plan references additional information on the second floor lighting plan.

View the file

Other files

File Type Posted
E2.1L_ SECOND FLOOR LIGHTING PLAN Rev.0 markup.pdf PDF
36C10D24Q0188 0003.docx DOCX document
2nd floor floorplan.pdf PDF
As-builts First Floor.pdf PDF
Maintenance Milestone Schedule.docx DOCX document
36C10D24Q0188 0002.docx DOCX document
36C10D24Q0188 0001.docx DOCX document
PAST PERFORMANCE QUESTIONAIRE.docx DOCX document
36C10D24Q0188.docx DOCX document
Wage Determination.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D B

'L3B'

'L2'

'T2'

'M

SB'

'H1'

'L1'

'L3A'

'LCP'

'T3' 'T1'

'DSB-2'

M

UP

UP

N

M

L

3 5

J

7 9 11 15 17 19 21 23 25

F

E

D

C

B

A 2

G

2.5

INFILL @ (E) WINDOW

LOCATION. PATCH TO

MATCH EXISTING

ADJACENT MATERIALS,

CONSTRUCTION, AND

FIRE RATING.

PATCH TO MATCH EXISTING

ADJACENT FINISHES

AREA OF FUTURE DOOR; SEE SHEET

A-711 FOR EXACT EXTENTEXTEND FURRED COLUMN AS NEEDED TO

ACCOMODATE RELOCATED HOSE BIB. SEE

PLUMBING DRAWINGS FOR DETAILS

VESTIBULE

RVSR

COACH

OFFICE

ELECTRICAL

ROOM

VSC

COACH

VSC

COACH

TRAINING/CONFERENCE

STORAGE

CONFERENCE

SECURED

FILE

ROOM

EQUIPMENT

SHARED

PANTRY

TOILET

CLOSET

H.R.

DIRECTOR

VESTIBULE

RECEPTION/DIRECTOR

SUITE

HALL

MAIL

ROOM

VESTIBULE

REPRODUCTION/PUBLICATION

DIV.

CHIEF

SUPPORT

SERVICE

DIVISION

VSC

MANAGER

LOCKED

FILE

ROOM

OPEN

AREA

SERVICE

CENTER

OPEN

OFFICE

LOUNGE

ELECTRICAL

ROOM

MEP

SHOWER

MEN

JAN.

WOMEN

IRM

COMPUTER

ROOM

TRAINING

ROOM

INFORMATION

SECURITY

OFFICER

IDVS

DIRECTOR

IDVS

DAV

OFFICE

DAV

UNION

OFFICE

FILE

ROOM

CONFERENCE

VR&E

DIVISION

CHIEF

COUNSELOR

COUNSELOR

COUNSELOR

JOB LAB

LOAN

GUARANTY

COUNSELOR

F&FE

TOILET

TOILET

INTERVIEW

ROOM

INTERVIEW

ROOM

HALL

EQUIPMENT

VR&E

LOBBY

CORRIDOR

HALL

ELEVATOR

LOBBY

100D

ELEVATOR

MACHINE

ROOM

100A

D

D D

D

D

D

C3

C3

D

D

D D

H4-11 7 8

K

K

C

D

X5

X

5 X

W

W

W

W

12W

KEYED NOTES: #

GENERAL NOTES:

1 EXISTING LC&D LIGHTING CONTROL PANEL, EXISTING LIGHTING CONTROL

PANEL TO REMAIN, NEW LIGHTING BRANCH CIRCUIT IN ENTRY LOBBY TO

BE CIRCUITED TO EXISTING SPARE LIGHTING RELAY IN PANEL. PANEL IS

TO BE NETWORKED TO NEW LIGHTING CONTROL PANEL LOCATED ON THE

SECOND FLOOR. SEE SHEET E2.1L FOR ADDITIONAL INFORMATION.

2 NEW ENTRY AREA, SHOWN FOR REFERENCE TO EXISTING AREAS.

3 NEW STAIRWELL, SHOWN FOR REFERENCE TO EXISTING AREAS.

4 EXISTING FIRST FLOOR LIGHTING FIXTURES ON INTERIOR AND EXTERIOR

ARE TO REMAIN, UNLESS OTHERWISE NOTED ON E2.0D FOR REMOVAL.

DEVICES ARE SHOWN FOR INFORMATIONAL PURPOSES AND REFERENCE

ONLY. ALL EXISTING BRANCH CIRCUITING AND CONTROLS ARE TO BE

MAINTAINED.

5 CONNECT TO UNSWITCHED LEG OF LIGHTING CIRCUIT IN ROOM.

6 UP TO LIGHT FIXTURES IN STAIR. SEE SHEET E2.1L FOR ADDITIONAL

INFORMATION.

7 ROUTE THROUGH EXISTING SPARE RELAY IN LIGHTING CONTROL PANEL,

SEE KEYNOTE 1 ON THIS SHEET. UTILIZE EXISTING SPARE RELAY IN

EXISTING LCP FOR LIGHTING CONTROL.

8 FURNISH AND INSTALL ADDITIONAL UNSWITCHED LEG OF LIGHTING

CIRCUIT FOR CONNECTION TO EXIT SIGNS.

9 FURNISH NETWORK CONNECTION TO NEW SLAVE LIGHTING CONTROL

PANEL LOCATED IN THE SECOND FLOOR ELECTRICAL ROOM. SEE SHEET

E2.1L FOR ADDITIONAL INFORMATION.

10 REFER TO SECOND FLOOR LIGHTING PLAN E2.1L FOR LIGHTING LAYOUT,

BRANCH CIRCUITING, AND CONTROLS FOR THIS AREA.

11 EXISTING LIGHT FIXTURE TO BE RELOCATED TO THIS LOCATION. SEE

SHEET E2.0D FOR COORDINATION WITH EXISTING FIXTURE BEING

RE-LOCATED AND ASSOCIATED BRANCH CIRCUITING MODIFICATIONS.

12 COORDINATE MOUNTING OF NEW LIGHT FIXTURE WITH ARCHITECTURAL

ELEVATIONS.

13 EXTEND EXISTING BRANCH CIRCUITING TO RE-LOCATED AND NEW LIGHT

FIXTURES. SEE SHEET E2.0D FOR ADDITIONAL INFORMATION. CONTROL

NEW FIXTURES WITH EXISTING.

1 ALL EXISTING LIGHTING IS TO REMAIN AND IS SHOWN FOR REFERENCE

ONLY, UNLESS NOTED OTHERWISE.

electricalengineeringcompany engineering 4 tomorrow

800 s. industry way, suite 350 meridian, idaho 83642 phone: 208.378.4450 fax: 208.378.4451 e2co project #:

world wide web: e2co.com

18237

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

JVS JVS/JB/DTLFULLY SPRINKLERED

Revisions: Date:

Approved:

CONSTRUCTION

DOCUMENTS

1001 Connecticut Avenue NW, Suite 704 Washington, DC 20036

(855) 521-1110 Mr. Gene Klow, AIA

Concourse Federal Group

08/16/2019

Construct National Telehealth Hub, Boise VAMC

531-323

347-1

444 W Fort Street, Boise, Idaho E2.0L

FIRST FLOOR LIGHTING PLAN

SCALE: 1/8" = 1'-0"

FIRST FLOOR LIGHTING PLAN

SHEET 124 OF 145

AutoCAD SHX Text S https://us02.procore.com/562949953469612/project/drawing_areas/562949953455220/drawing_log/562949956772057 https://us02.procore.com/562949953469612/project/drawing_areas/562949953455220/drawing_log/562949956772057 https://us02.procore.com/562949953469612/project/drawing_areas/562949953455220/drawing_log/562949956772057 https://us02.procore.com/562949953469612/project/drawing_areas/562949953455220/drawing_log/562949956772057 https://us02.procore.com/562949953469612/project/drawing_areas/562949953455220/drawing_log/562949956772083 https://us02.procore.com/562949953469612/project/drawing_areas/562949953455220/drawing_log/562949956772047 https://us02.procore.com/562949953469612/project/drawing_areas/562949953455220/drawing_log/562949956772047 https://us02.procore.com/562949953469612/project/drawing_areas/562949953455220/drawing_log/562949956772047 K