36A77620Q0143-218.pdf
PDF Posted
- Solicitation number
- 36A77620Q0143
About this file
This document outlines security requirements and measures for federal drug storage facilities. Rooms must have security mesh screening on windows within 40 feet of the ground or lower roof, motion intrusion detectors that emit a local 80-90 decibel alarm and can be connected to remote indicators. Exterior walls must be brick or masonry, with gypsum interior partitions. Doors must be 1.75 inch solid wood or hollow steel fitted with two locksets including a jimmy-proof rim deadbolt if not in a steel frame. Ceiling access points must be barricaded and air vents reinforced if over 100 square inches. The related federal contract opportunity is a placeholder solicitation number seeking a CBOC in New Port Richey, with no modification to the pre-solicitation notice.
36A77620Q0143 ATTACHMENT O - Warehouse Security.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36A77620Q0143-0003000.docx | DOCX document | |
| 36A77620Q0143-0002009.docx | DOCX document | |
| 36A77620Q0143-0002010.pdf | ||
| 36A77620Q0143-0002008.docx | DOCX document | |
| 36A77620Q0143-0001011.docx | DOCX document | |
| 36A77620Q0143-0001009.docx | DOCX document | |
| 36A77620Q0143-0001010.docx | DOCX document | |
| 36A77620Q0143-214.pdf | ||
| 36A77620Q0143-208.pdf | ||
| 36A77620Q0143-210.pdf | ||
| 36A77620Q0143-216.xlsx | XLSX spreadsheet | |
| 36A77620Q0143-212.pdf | ||
| 36A77620Q0143-206.pdf | ||
| 36A77620Q0143-217.pdf | ||
| 36A77620Q0143-207.pdf | ||
| 36A77620Q0143-204.pdf | ||
| 36A77620Q0143-219.pdf | ||
| 36A77620Q0143-203.docx | DOCX document | |
| 36A77620Q0143-213.pdf | ||
| 36A77620Q0143-215.pdf | ||
| 36A77620Q0143-209.pdf | ||
| 36A77620Q0143-220.xlsx | XLSX spreadsheet | |
| 36A77620Q0143-211.pdf | ||
| 36A77620Q0143-205.pdf | ||
| 36A77620Q0143-004.docx | DOCX document |
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUIREMENTS AND MEASURES DEFINED
1. WINDOWS
Windows with sills less than 40' from the ground or the roof of a lower abutment, less than 25' from windows of an adjoining building, and accessible by a building ledge leading to windows of other floor rooms require security mesh screening. Stainless steel security mesh screening shall be equivalent to woven mesh 0.028" wire diameter alloy #304 stainless steel and have a tensile strength of 800 pounds per lineal inch. Mesh shall be equivalent to 12 x 12 per inch with main and subframes of 12-gauge carbon steel with baked enamel finish and internal key locking slide bolts. Security mesh screens are to be installed on inside of windows.
2. WALLS
Exterior walls of brick and masonry construction are acceptable. Gypsum board standard construction for interior building partitions. All bulk controlled substance drug storage vault walls shall be equivalent to brick or masonry construction.
3. DOORS AND LOCKS
Solid core wood or hollow steel door construction shall be 1-3/4" thick. Dutch or half doors are unacceptable. Removable hinge pins on door exterior shall be spot welded preventing their removal. All doors must be fitted with two lock sets. If a door is not set in a steel frame, one of these locks must be a jimmy proof rim deadlock. Doors set in steel frames must be fitted with mortise lock with a deadlock pin feature. One lock (the day lock) must be automatically locking on door closure;
requiring re-entry to the room with key or lock combination and allowing egress from the room by use of an inside thumb latch. The day lock on the main door must be automatically locking, with a minimum 3/4" dead bolt and inside thumb latch. Combinations or keys to day locks will be restricted to service employees and combinations changed immediately on the termination or reassignment of an employee.
4. OTHER ROOM ACCESS MEANS
Ceiling overhead areas which enable entry into a secure room from an unsecured room must be barricaded by the installation of a suitable partition or ceiling which deters "up and over" access. Ventilation grills on doors and air circulation ducts which exceed 100 square inches in areas must be reinforced to prevent their removal from outside the room. Other possible access means such as dumbwaiter shafts, roof or wall ventilator housings, trap doors, etc., must be secured by appropriate means.
5. MOTION INTRUSION DETECTORS
a. An intrusion detection alarm system which detects entry into the room, and which broadcasts a local alarm of sufficient volume to induce an illegal entrant to abandon a burglary attempt. Intrusion detectors must have the following essential features:
(1) An internal, automatic charging DC standby power supply and a primary AC power operation.
(2) A remote, key operated activation/deactivation switch installed outside the rooms and adjacent to the room entrance door frame.
(3) An automatic reset capability following an intrusion detection.
(4) A local alarm level of 80 dB(min) to 90 dB(max) up to 100 feet from the protected room.
(5) An integral capability for the attachment of wiring for remote alarm and intrusion indicator equipment (visual or audio). See installation note subparagraph c (2) below.
(6) A low nuisance alarm susceptibility.
b. Intrusion detector equipment which operates on the principle of narrow beam interception, microwave, or photo electric eye is unacceptable.
c. Installation Notes:
(1) A locally sounding alarm should not be installed in a room which is close to an
ICU,
cardiac care, or other special treatment area where a loud alarm would have an injurious effect on patients.
(2) In addition to the locally sounding alarm, remote visuals and/or audio annunciators must be located at the telephone switchboard and/or the security operations room to assure detector monitorship during nonbusiness hours.
(3) In protected rooms of outpatient clinic not on medical center grounds, intrusion detector alarms will be remoted to a commercial security alarm monitoring firm, a local police department, or a security office charged with building security. The remoted alarms will be in addition to locally broadcast alarms in the protected areas.