1999614_SI RHC_EP2-26 IFC_Specifications Vol 2_2024-01-26.pdf
PDF 5 MB Posted
- Solicitation number
- 333302-24RF-0010021
- Issued by
-
Smithsonian Institution
About this file
This document is an early package Request for Proposals (RFP) issued by the Smithsonian Institution for the Revitalize Historic Core project. The project involves renovating the historic Smithsonian Castle building and surrounding grounds. The RFP is for Early Package 2-26 (EP 2-26), which includes early selective demolition, abatement, and new work for a partial building reopening in 2026.
The RFP provides background on the historic significance of the Smithsonian Castle and the overall project scope. It specifies the contract will be a Firm Fixed Price contract estimated to exceed $10 million. The North American Industry Classification Code (NAICS) is 236220 with a $45 million size standard. A site visit is required, and all questions must be submitted by June 6, 2024. Proposals are due by July 9, 2024. The Smithsonian Institution intends to award one contract for the work.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Early Package 2-26 (EP2-26): Early Selective Demolition & Abatement, New Work for Partial Building Reopening in 2026
Issued for Construction
Specifications - Vol 2 of 2
Smithsonian Institution Revitalize Historic Core - SIB
EYP-Loring, LLC
January 26, 2024
SF Project No. 1999614
Contract No. 33330220CF0010073
PROJECT MANUAL
For
Smithsonian Institution Revitalize Historic Core Washington, DC
EYP-Loring, LLC 1000 Potomac Street, NW, #L1 Washington, DC 20007
Consultants:
Structural Engineering Robert Silman Associates Structural Engineers DPC 1053 31st Street NW Washington, DC 20007
Landscape Architecture Rhodeside and Harwell, Inc.
500 King Street, Suite 300 Alexandria, VA 22314
Civil Engineering Sorba Engineering 22365 Broderick Drive, Suite 265 Dulles, Virginia 20166
Hazardous Materials Abatement Aerosol Monitoring & Analysis, Inc.
1331 Ashton Road P.O. Box 646 Hanover, MD 21076
Elevator Michael Blades & Associates, Ltd.
232 Laurel Lane Ponte Vedra Beach, FL 32082
Blast Engineering Applied Research Associates, Inc.
4300 San Mateo Blvd., NE Albuquerque, NM 87110
Historic Material Conservation Building Conservation Services, Inc.
242 Cherry Street Philadelphia, PA 19106
Food Service Design Culinary Design, LLC 3734 Cross Bow Court Ellicott City, MD 21042
Geotechnical Engineering Haley & Aldrich, Inc.
1497 Chain Bridge Road, Suite 304 McLean, VA 22101
Fire Protection Engineering Jensen Hughes, Inc.
3610 Commerce Drive, Suite 817 Baltimore, MD 21227
A/V – Electronic Security Phase Shift Consulting LLC 6700 Alexander Bell Dr. Suite 200 Columbia, MD 21046
Architectural Lighting Design CM Kling + Associates 1020 Cameron Street Alexandria VA 22314
Exterior Enclosure Design Simpson Gumpertz & Heger 1625 Eye Street NW, Suite 900 Washington, DC 20006
January 26, 2024 Early Package 2 Issued for Construction SF Project No. 1999614
Smithsonian Institution Seals Page Revitalize Historic Core - SIB 00 0107 - 1
DOCUMENT 000107 - SEALS PAGE
DESIGN PROFESSIONALS OF RECORD
ARCHITECT Karl W. Stumpf Page Southerland Page, Inc.
Responsible for Divisions 01-33 Sections except where indicated as prepared by other design professionals of record.
Early Package 2-26
Revitalize Historic Core - SIB 00 0107 - 2
DOCUMENT 000107 - SEALS PAGE
DESIGN PROFESSIONALS OF RECORD
CIVIL ENGINEER Matthew S. McComas, P.E.
Sorba Engineering
Responsible for the following Sections:
01 5639 Site Protection
31 1000 Site Clearing 31 2000 Earth Moving for Site Work
PE920479
DI
STR
ICT OF COLUMBIA
PROFESSIONAL ENG
IN
EE
R
M A
T
T
H
E
W
S
M
C
C
O
M
A S
C
I V
I
L
01/12/2023
Early Package 2-26
Revitalize Historic Core - SIB 00 0107 - 3
DOCUMENT 000107 - SEALS PAGE
DESIGN PROFESSIONALS OF RECORD
STRUCTURAL
ENGINEER
Kirk Mettam, P.E.
Robert Silman Associates Structural Engineers, DPC
02 0400 Shoring and Bracing 02 2900 Structural Building Monitoring 03 0130 Maintenance of Cast-in-Place Concrete
03 3000 Cast-in-Place Concrete
05 1200 Structural Steel Framing 05 3100 Steel Decking
Revitalize Historic Core - SIB 00 0107 - 4
22 0517 Sleeves and Sleeve Seals for Plumbing Piping 22 0519 Meters and Gages for Plumbing Piping 22 0523 General Duty Valves for Plumbing 22 0529 Hangers and Supports For Plumbing Piping and Equipment 22 0700 Plumbing Insulation 22 1116 Domestic Water Piping 22 1119 Domestic Water Piping Specialties
22 3300 Electric Domestic Water Heater 23 0500 General Mechanical Requirements 23 0503 Pipe and Tubes for HVAC 23 0513 Common Motor Requirements for HVAC Equipment 23 0516 Expansion Fittings and Loops for HVAC Piping 23 0517 Sleeves and Sleeve Seals for HBAC Piping 23 0523 General Duty Valves for HVAC 23 0529 Hangers and Supports for HVAC 23 0548 Noise and Vibrations Controls for HVAC
23 0553 Identification for HVAC Piping and Equipment 23 0593 Testing, Adjusting and Balancing for HVAC 23 0700 HVAC Insulation 23 0900 Instrumentation and Control for HVAC 23 2116 Hydronic Piping Specialties 23 2216 Steam and Condensate Piping Specialties 23 2223 Steam Condensate Pumps 23 2500 HVAC Water Treatment 23 3100 HVAC Ducts and Casings 23 3300 Air Duct Accessories 23 3400 HVAC Fans 23 3700 Air Outlets and Inlets 23 7300 Indoor Central-Station Air-Handling Units 23 8219 Fan Coil Units
MECHANICAL
ENGINEER
PLUMBING
J. Michael Galway, P.E.
Loring Consulting Engineers
Early Package 2-26
Revitalize Historic Core - SIB 00 0107 - 5
ELECTRICAL
Hallah Abodaff , P.E.
Loring Consulting Engineers
26 0010 Supplementary Requirements for Electrical 26 0011 Facility Performance Requirements for Electrical 26 0513 Medium-Voltage Cables 26 0519 Low-Voltage Electrical Power Conductors and Cables 26 0526 Grounding and Bonding for Electrical Systems 26 0529 Hangers and Supports for Electrical Systems 26 0533.13 Conduits for Electrical Systems 26 0533.16 Boxes and Covers for Electrical Systems 26 0543 Underground Ducts and Raceways for Electrical Systems 26 0544 Sleeves and Sleeve Seals for Electrical Raceways and Cabling
26 0553 Identification for Electrical Systems 26 2416 Panelboards 26 2726 Wiring Devices 26 2813 Fuses 26 2816 Enclosed Switches
Revitalize Historic Core - SIB 00 0107 - 7
LANDSCAPE
ARCHITECT
Faye Harwell Rhodeside and Harwell, Inc.
01 5640 Temporary Tree Protection
32 1400 Unit Paving
32 9100 Planting Soil 32 9200 Lawns and Grasses
Revitalize Historic Core - SIB 00 0107 - 9
DOCUMENT 000107 - SEALS PAGE
DESIGN PROFESSIONALS OF RECORD
TELECOMMUNICATIONS
DESIGNER
Kevin L DeHaven, RCDD Phase Shift Consulting
27 0505 Selective Demolition for Communications
January 26, 2024 Early Package 2-26
Smithsonian Institution Table of Contents Revitalize Historic Core - SIB 00 0110 - 1
DOCUMENT 00 0110 - TABLE OF CONTENTS
VOLUME 1
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 0101 PROJECT TITLE PAGE
00 0107 SEALS PAGES
00 0110 TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 0000 SUPPLEMENTARY CONDITIONS FOR CONSTRUCTION (Smithsonian
Facilities spec section)
01 1000 SUMMARY
---------- AHHP CASTLE BUILT ARTIFACTS
01 3250 BUILDING INFORMATION MODELING (BIM) REQUIREMENTS - (Smithsonian
Facilities spec section)
01 3513 ARCHEOLOGICAL PROTECTION
01 3525 FIRE PREVENTION AND PROTECTION IN CONSTRUCTION, ALTERATION,
AND DEMOLITION PROJECTS
01 3591 HISTORIC TREATMENT PROCEDURES
01 4000 QUALITY REQUIREMENTS
01 5639 SITE PROTECTION (Smithsonian Facilities spec section)
01 5640 TEMPORARY TREE PROTECTION
01 6000 PRODUCT REQUIREMENTS
01 7329 CUTTING AND PATCHING
01 7419 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
---------- CONSTRUCTION AND DEMOLITION WASTE TRACKING SHEET
01 7823 OPERATION AND MAINTENANCE DATA REQUIREMENTS – (Smithsonian
Facilities spec section)
01 7900 DEMONSTRATION AND TRAINING
01 8113.14 SUSTAINABLE DESIGN REQUIREMENTS - LEED V4 BD+C
---------- LEED SCORECARD
---------- SITES SCORECARD
---------- LEED SUBMITTAL FORM
---------- SITES PRODUCT + MATERIAL FORM
---------- SITES SUBMITTAL FORM C5.6
---------- SITES SUBMITTAL FORM C5.10
01 8116 VOLATILE ORGANIC COMPOUND (VOC) CONTENT AND GENERAL
EMISSIONS RESTRICTIONS
01 8119 INDOOR AIR QUALITY MANAGEMENT
01 9113 GENERAL COMMISSIONING (provided by CxA NV5)
---------- COMMISSIONING PLAN
Revitalize Historic Core - SIB 00 0110 - 2
DIVISION 02 - EXISTING CONDITIONS
02 0400 SHORING AND BRACING
02 2900 STRUCTURAL BUILDING MONITORING
02 4200 SELECTIVE REMOVALS
02 8200 ASBESTOS ABATEMENT – (Smithsonian Facilities spec section)
02 8300 WORK ACTIVITIES IMPACTING LEAD-CONTAINING MATERIALS -
(Smithsonian Facilities spec section)
DIVISION 03 - CONCRETE
03 0130 MAINTENANCE OF CAST-IN-PLACE CONCRETE
03 3000 CAST-IN-PLACE CONCRETE
DIVISION 04 – MASONRY
04 0140.62 MASONRY REPOINTING
04 2200 CONCRETE UNIT MASONRY
DIVISION 05 - METALS
05 1200 STRUCTURAL STEEL FRAMING
05 3100 STEEL DECKING
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 4023 INTERIOR ARCHITECTURAL WOODWORK
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 8413 PENETRATION FIRESTOPPING
07 9200 JOINT SEALANTS
DIVISION 08 – OPENINGS
08 0314 TREATMENT OF HISTORIC WOOD DOORS
08 1113 HOLLOW METAL DOORS AND FRAMES
08 1416 FLUSH WOOD DOORS
08 7100 DOOR HARDWARE
DIVISION 09 – FINISHES
09 0110.15 PAINT AND COATING REMOVAL
09 0320 PLASTER
09 2116.23 GYPSUM BOARD SHAFT WALL ASSEMBLIES
09 2216 NON-STRUCTURAL METAL FRAMING
09 2900 GYPSUM BOARD
09 6813 TILE CARPETING
09 9124 INTERIOR PAINTING (MPI STANDARDS)
Revitalize Historic Core - SIB 00 0110 - 3
DIVISION 22 – PLUMBING
22 0517 SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
22 0519 METERS AND GAGES FOR PLUMBING PIPING
22 0523 GENERAL DUTY VALVES FOR PLUMBING
22 0529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
22 0700 PLUMBING INSULATION
22 0800 COMMISSIONING OF PLUMBING SYSTEMS (provided by CxA NV5)
22 1116 DOMESTIC WATER PIPING
22 1119 DOMESTIC WATER PIPING SPECIALTIES
22 3300 ELECTRIC, DOMESTIC-WATER HEATERS
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 0500 GENERAL MECHANICAL REQUIREMENTS
23 0503 PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT
23 0513 COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
23 0516 EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING
23 0517 SLEEVES AND SLEEVE SEALS FOR HVAC PIPING
23 0523 GENERAL-DUTY VALVES FOR HVAC PIPING
23 0529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
23 0548 NOISE AND VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT
23 0553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
23 0593 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 0700 HVAC INSULATION
23 0800 COMMISSIONING OF HVAC (provided by CxA NV5)
23 0900 INSTRUMENTATION AND CONTROL FOR HVAC
23 2116 HYDRONIC PIPING SPECIALTIES
23 2216 STEAM AND CONDENSATE HEATING PIPING SPECIALTIES
23 2223 STEAM CONDENSATE PUMPS
23 2500 HVAC WATER TREATMENT
23 3100 HVAC DUCTS AND CASINGS
23 3300 AIR DUCT ACCESSORIES
23 3400 HVAC FANS
23 3700 AIR OUTLETS AND INLETS
23 7300 INDOOR CENTER-STATION AIR-HANDLING UNITS
23 8219 FAN COIL UNITS
VOLUME 2
DIVISION 26 – ELECTRICAL
26 0010 SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL
26 0011 FACILITY PERFORMANCE REQUIREMENTS FOR ELECTRICAL
26 0513 MEDIUM-VOLTAGE CABLES
26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
26 0526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 0529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
26 0533.13 CONDUITS FOR ELECTRICAL SYSTEMS
26 0533.16 BOXES AND COVERS FOR ELECTRICAL SYSTEMS
Revitalize Historic Core - SIB 00 0110 - 4
26 0543 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
26 0544 SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND
CABLING
26 0553 IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 0800 COMMISSIONING OF ELECTRICAL SYSTEMS (provided by CxA NV5)
26 2416 PANELBOARDS
26 2726 WIRING DEVICES
26 2813 FUSES
26 2816 ENCLOSED SWITCHES
26 5100 ARCHITECTURAL LIGHTING LUMINAIRES
DIVISION 27 - COMMUNICATIONS
27 0505 SELECTIVE DEMOLITION FOR COMMUNICATIONS
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
28 3111 ADDRESSABLE FIRE ALARM SYSTEM
28 3111.1 TEMPORARY FIRE ALARM SYSTEM
DIVISION 31 - EARTHWORK
31 1000 SITE CLEARNING
31 2000 EARTH MOVING FOR SITE WORK
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 1400 UNIT PAVING
32 9100 PLANTING SOIL
32 9200 LAWNS AND GRASSES
END OF TABLE OF CONTENTS
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 1
SECTION 26 0010 - SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Supplemental requirements generally applicable to the Work specified in Division 26. This Section is also referenced by related Work specified in other Divisions.
B. Related Requirements:
1. Section 260011 "Facility Performance Requirements for Electrical" for seismic-load, wind-load, acoustical, and other field conditions applicable to Work specified in this Section.
1.2 REFERENCES
A. Abbreviations and Acronyms for Electrical Terms and Units of Measure:
1. A: Ampere, unit of electrical current.
2. AC or ac: Alternating current.
3. AFCI: Arc-fault circuit interrupter.
4. AIC: Ampere interrupting capacity.
5. AL, Al, or ALUM: Aluminum.
6. ATS: Automatic transfer switch.
7. AWG: American wire gauge; see ASTM B258.
8. BIL: Basic impulse insulation level.
9. BIM: Building information modeling.
10. CAD: Computer-aided design or drafting.
11. CB: Circuit breaker.
12. CO/ALR: Copper-aluminum, revised.
13. CU or Cu: Copper.
14. CU-AL or AL-CU: Copper-aluminum.
15. DC or dc: Direct current.
16. DDC: Direct digital control (HVAC).
17. EGC: Equipment grounding conductor.
18. ELV: Extra-low voltage.
19. EMF: Electromotive force.
20. EMI: Electromagnetic interference.
21. EPM: Electrical preventive maintenance.
22. EPS: Emergency power supply.
23. EPSS: Emergency power supply system.
24. ESS: Energy storage system.
25. EV: Electric vehicle.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 2
26. FLC: Full-load current.
27. ft: Foot.
28. GEC: Grounding electrode conductor.
29. GFCI: Ground-fault circuit interrupter.
30. GFPE: Ground-fault protection of equipment.
31. GND: Ground.
32. HP or hp: Horsepower.
33. HVAC: Heating, ventilating, and air conditioning.
34. Hz: Hertz.
35. IBT: Intersystem bonding termination.
36. inch: Inch. To avoid confusion, the abbreviation "in." is not used.
37. IP: Ingress protection rating (enclosures); Internet protocol (communications).
38. IR: Infrared.
39. IT&R: Inspecting, testing, and repair.
40. ITE: Information technology equipment.
41. kAIC: Kiloampere interrupting capacity.
42. kcmil or MCM: One thousand circular mils.
43. kV: Kilovolt.
44. kVA: Kilovolt-ampere.
45. kVAr or kVAR: Kilovolt-ampere reactive.
46. kW: Kilowatt.
47. kWh: Kilowatt-hour.
48. LAN: Local area network.
49. lb: Pound (weight).
50. lbf: Pound (force).
51. LCD: Liquid-crystal display.
52. LCDI: Leakage-current detector-interrupter.
53. LED: Light-emitting diode.
54. LNG: Liquefied natural gas.
55. LRC: Locked-rotor current.
56. LV: Low voltage.
57. m: Meter.
58. MLO: Main lugs only.
59. MV: Medium voltage.
60. MVA: Megavolt-ampere.
61. mW: Milliwatt.
62. MW: Megawatt.
63. MWh: Megawatt-hour.
64. NC: Normally closed.
65. NO: Normally open.
66. NPT: National (American) standard pipe taper.
67. OCPD: Overcurrent protective device.
68. PCU: Power-conditioning unit.
69. PF or pf: Power factor.
70. PLC: Programmable logic controller.
71. PoE: Power over Ethernet.
72. PVC: Polyvinyl chloride.
73. RMS or rms: Root-mean-square.
74. RPM or rpm: Revolutions per minute.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 3
75. SPD: Surge protective device.
76. SWD: Switching duty.
77. TCP/IP: Transmission control protocol/Internet protocol.
78. UL: (standards) Underwriters Laboratories, Inc.; (product categories) UL, LLC.
79. UL CCN: UL Category Control Number.
80. UPS: Uninterruptible power supply.
81. USB: Universal serial bus.
82. UV: Ultraviolet.
83. V: Volt, unit of electromotive force.
84. V(ac): Volt, alternating current.
85. V(dc): Volt, direct current.
86. VA: Volt-ampere, unit of complex electrical power.
87. VAR: Volt-ampere reactive, unit of reactive electrical power.
88. VFC: Variable-frequency controller.
89. W: Watt, unit of real electrical power.
90. Wh: Watt-hour, unit of electrical energy usage.
91. WR: Weather resistant.
B. Abbreviations and Acronyms for Electrical Raceway Types:
1. EMT: Electrical metallic tubing.
2. ENT: Electrical nonmetallic tubing.
3. ERMC: Electrical rigid metal conduit.
4. ERMC-S: Steel electrical rigid metal conduit.
5. ERMC-S-G: Galvanized-steel electrical rigid metal conduit.
6. ERMC-S-PVC: PVC-coated-steel electrical rigid metal conduit.
7. ERMC-SS: Stainless steel electrical rigid metal conduit.
8. FMC: Flexible metal conduit.
9. IMC: Steel electrical intermediate metal conduit.
10. LFMC: Liquidtight flexible metal conduit.
11. LFMC-A: Aluminum liquidtight flexible metal conduit.
12. LFMC-S: Steel liquidtight flexible metal conduit.
13. LFMC-SS: Stainless steel liquidtight flexible metal conduit.
14. LFNC: Liquidtight flexible nonmetallic conduit.
15. LFNC-A: Layered (Type A) liquidtight flexible nonmetallic conduit.
16. LFNC-B: Integral (Type B) liquidtight flexible nonmetallic conduit.
17. LFNC-C: Corrugated (Type C) liquidtight flexible nonmetallic conduit.
18. PVC: Rigid PVC conduit.
19. PVC-40: Schedule 40 rigid PVC conduit.
20. PVC-80: Schedule 80 rigid PVC Conduit.
21. RGS: See ERMC-S-G.
22. RMC: See ERMC.
C. Abbreviations and Acronyms for Electrical Single-Conductor and Multiple-Conductor Cable Types:
1. AC: Armored cable.
2. MC: Metal-clad cable.
3. MI: Mineral-insulated, metal-sheathed cable.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 4
4. MV: Medium-voltage cable.
5. NM: Nonmetallic sheathed cable.
6. NMC: Nonmetallic sheathed cable with corrosion-resistant nonmetallic jacket.
7. NMS: Nonmetallic sheathed cable with signaling, data, and communications conductors, plus power or control conductors.
8. NPLF: Non-power-limited fire-alarm circuit cable.
9. NPLFP: Non-power-limited fire-alarm circuit cable for environmental air spaces.
10. NPLFR: Non-power-limited fire-alarm circuit riser cable.
11. THW: Thermoplastic, heat- and moisture-resistant cable.
12. THHN: Thermoplastic, heat-resistant cable with nylon jacket outer sheath.
13. THHW: Thermoplastic, heat- and moisture-resistant cable.
14. THWN: Thermoplastic, moisture- and heat-resistant cable with nylon jacket outer sheath.
15. TW: Thermoplastic, moisture-resistant cable.
D. Definitions:
1. Basic Impulse Insulation Level (BIL): Reference insulation level expressed in impulse crest voltage with a standard wave not longer than 1.5 times 50 microseconds and 1.5 times 40 microseconds.
2. Cable: In accordance with NIST NBS Circular 37 and IEEE standards, in the United States for the purpose of interstate commerce, the definition of "cable" is
(1) a conductor with insulation, or a stranded conductor with or without insulation (single-conductor cable); or (2) a combination of conductors insulated from one another (multiple-conductor cable).
3. Communications Jack: A fixed connecting device designed for insertion of a communications cable plug.
4. Conductor: In accordance with NIST NBS Circular 37 and IEEE standards, in the United States for the purpose of interstate commerce, the definition of "conductor" is (1) a wire or combination of wires not insulated from one another, suitable for carrying an electric current; (2) (National Electrical Safety Code) a material, usually in the form of wire, cable, or bar, suitable for carrying an electric current;
or (3) (general) a substance or body that allows a current of electricity to pass continuously along it.
5. Designated Seismic System: A system component that requires design in accordance with Ch. 13 of ASCE/SEI 7 and for which the Component Importance Factor is greater than 1.0.
6. Direct Buried: Installed underground without encasement in concrete or other protective material.
7. Enclosure: The case or housing of an apparatus, or the fence or wall(s) surrounding an installation, to prevent personnel from accidentally contacting energized parts or to protect the equipment from physical damage. Types of enclosures and enclosure covers include the following:
a. Cabinet: An enclosure that is designed for either surface mounting or flush mounting and is provided with a frame, mat, or trim in which a swinging door or doors are or can be hung.
b. Concrete Box: A box intended for use in poured concrete.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 5
c. Conduit Body: A means for providing access to the interior of a conduit or tubing system through one or more removable covers at a junction or terminal point. In the United States, conduit bodies are listed in accordance with outlet box requirements.
d. Cutout Box: An enclosure designed for surface mounting that has swinging doors or covers secured directly to and telescoping with the walls of the enclosure.
e. Floor Box: A box mounted in the floor intended for use with a floor box cover and other components to complete the floor box enclosure.
f. Junction Box: A box with a blank cover that joins different runs of raceway or cable and provides space for connection and branching of the enclosed conductors.
g. Outlet Box: A box that provides access to a wiring system having pryout openings, knockouts, threaded entries, or hubs in either the sides or the back, or both, for the entrance of conduit, conduit or cable fittings, or cables, with provisions for mounting an outlet box cover, but without provisions for mounting a wiring device directly to the box.
h. Pull Box: A box with a blank cover that joins different runs of raceway and provides access for pulling or replacing the enclosed cables or conductors.
i. Recessed Access Floor Box: A floor box with provisions for mounting wiring devices below the floor surface.
j. Recessed Access Floor Box Cover: A floor box cover with provisions for passage of cords to recessed wiring devices mounted within a recessed floor box.
k. Termination Box: An enclosure designed for installation of termination base assemblies consisting of bus bars, terminal strips, or terminal blocks with provision for wire connectors to accommodate incoming or outgoing conductors, or both.
8. Emergency Systems: Those systems legally required and classed as emergency by municipal, state, federal, or other codes, or by any governmental agency having jurisdiction that are designed to ensure continuity of lighting, electrical power, or both, to designated areas and equipment in the event of failure of the normal supply for safety to human life.
9. Fault Limited: Providing or being served by a source of electrical power that is limited to not more than 100 W when tested in accordance with UL 62368-1.
a. The term "fault limited" is intended to encompass most Class 1, 2, and 3 power-limited sources complying with Article 725 of NFPA 70; Class ES1 and ES2 electrical energy sources that are Class PS1 electrical power sources (e.g., USB); and Class ES3 electrical energy sources that are Class PS1 and PS2 electrical power sources (e.g., PoE). See UL 62368-1 for discussion of classes of electrical energy sources and classes of electrical power sources.
10. Jacket: A continuous nonmetallic outer covering for conductors or cables.
11. Plenum: A compartment or chamber to which one or more air ducts are connected and that forms part of the air distribution system.
12. Sheath: A continuous metallic covering for conductors or cables.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 6
13. UL Category Control Number (CCN): An alphabetic or alphanumeric code used to identify product categories covered by UL's Listing, Classification, and Recognition Services.
14. Voltage Class: For specified circuits and equipment, voltage classes are defined as follows:
a. Control Voltage: Having electromotive force between any two conductors, or between a single conductor and ground, that is supplied from a battery or other Class 2 or Class 3 power-limited source.
b. Line Voltage: (1) (controls) Designed to operate using the supplied low-voltage power without transformation. (2) (transmission lines, transformers, SPDs) The line-to-line voltage of the supplying power system.
c. Extra-Low Voltage (ELV): Not having electromotive force between any two conductors, or between a single conductor and ground, exceeding 30 V(ac rms), 42 V(ac peak), or 60 V(dc).
d. Low Voltage (LV): Having electromotive force between any two conductors, or between a single conductor and ground, that is rated above 30 V but not exceeding 1000 V.
e. Medium Voltage (MV): Having electromotive force between any two conductors, or between a single conductor and ground, that is rated about 1 kV but not exceeding 69 kV.
15. Wire: In accordance with NIST NBS Circular 37 and IEEE standards, in the United States for the purpose of interstate commerce, the definition of "wire" is a slender rod or filament of drawn metal. A group of small wires used as a single wire is properly called a "stranded wire." A wire or stranded wire covered with insulation is properly called an "insulated wire" or a "single-conductor cable." Nevertheless, when the context indicates that the wire is insulated, the term "wire" will be understood to include the insulation.
1.3 COORDINATION
A. Interruption of Existing Electrical Service: Do not interrupt electrical service to facilities occupied by Owner or others unless permitted under the following conditions:
1. Notify no fewer than seven days in advance of proposed interruption of electrical service.
2. Do not proceed with interruption of electrical service without SI’s written permission.
3. Coordinate interruption with systems impacted by outage including, but not limited to, the following:
a. Exercising generators.
b. Emergency lighting.
c. Elevators.
d. Fire-alarm systems.
B. Arrange to provide temporary electrical service or power in accordance with requirements specified in Division 01.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 7
1.4 SEQUENCING
A. Conduct and submit results of power system studies before submitting Product Data and Shop Drawings for electrical equipment.
1.5 ACTION SUBMITTALS
A. Coordination Drawings for Structural Supports: Show coordination of structural supports for equipment and devices, including restraints and bracing for control of seismic and wind loads, with other systems, equipment, and structural supports in the vicinity.
B. Coordination Drawings for Conduit Routing: Conduit routing plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of items involved:
1. Structural members in paths of conduit groups with common supports.
2. HVAC and plumbing items and architectural features in paths of conduit groups with common supports.
3. control devices, and other equipment.
C. Coordination Drawings for Duct Banks:
1. Show duct profiles and coordination with other utilities and underground structures.
2. Include plans and sections, drawn to scale, and show bends and locations of expansion fittings.
1.6 INFORMATIONAL SUBMITTALS
A. Delegated Design Drawings for Structural Masonry Wall Penetrations: Where indicated on Drawings, provide reflected ceiling plan(s), supplemented by elevations, sections, and other details, drawn to scale, signed and sealed by a qualified structural professional engineer, on which the following items are shown and coordinated with each other, using input from installers of the items involved:
1. Location and dimensions of structural members supporting wall.
2. Location and dimensions of columns near penetrations.
3. Location and dimension of headers and lintels.
4. Doors and windows near penetrations.
5. Location and dimensions of penetrating cuts.
6. Sprinkler piping and sleeves.
7. Plumbing piping and sleeves.
8. Ductwork and sleeves.
9. Conduit and sleeves.
10. Firestopping assemblies for rated penetrations.
11. Structural supports for piping, ductwork, and conduit on both sides of wall.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 8
B. Welding certificates.
C. Qualification Statements:
1. For structural professional engineer.
2. For electrical professional engineer.
3. For medium-voltage and low-voltage electrical testing agency and on-site electrical testing supervisor.
4. For power-limited electrical testing agency and on-site power-limited testing supervisor.
D. Operation and Maintenance Data:
1. Provide emergency operation, normal operation, and preventive maintenance manuals for each system, equipment, and device listed below:
2. Include the following information:
a. Manufacturer's operating specifications.
b. Schedule of maintenance material items recommended to be stored at
Project site.
c. Detailed instructions covering operation under both normal and abnormal conditions.
d. Time-current curves for overcurrent protective devices and manufacturer's written instructions for testing and adjusting their settings.
e. List of load-current and overload-relay heaters with related motor nameplate data.
1.7 QUALIFICATIONS
A. Electrical Professional Engineer: Professional engineer possessing an active PE license with electrical engineering specialty in Washington DC, with expertise in electrical engineering, including electrical power system modeling and analysis of electrical safety in accordance with NFPA 70E.
B. Welder: Installer possessing active qualifications specified in Section 010000 with training and certification in accordance with AWS D1.1/D1.1M
C. ERMC-S-PVC Installers: Installer possessing active qualifications specified in Section 010000 and able to present unexpired certified Installer credentials issued by ERMC-S-PVC manufacturer prior to starting installation.
D. Medium-Voltage Cable Installer: Entity possessing active qualifications specified in Section 010000 with training and manufacturer certification to install, splice, and terminate medium-voltage cable in accordance with NEC.
E. Medium-Voltage Duct Installer: Entity possessing active qualifications specified in Section 010000 with documented training and experience with installation of medium-voltage duct banks in accordance with NEC.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 9
F. Medium-Voltage Equipment Installer: Entity possessing active qualifications specified in Section 010000 with documented training and experience with hazards and safety requirements associated with installation and operation of medium-voltage equipment
G. Low-Voltage Electrical Testing and Inspecting Agency: Entities possessing active credentials from a qualified electrical testing laboratory recognized by authorities having jurisdiction.
1. On-site electrical testing supervisors must have documented certification and experience with testing electrical equipment in accordance with NETA 2021 testing standards.
H. Medium-Voltage Electrical Testing and Inspecting Agency: Entities possessing active credentials from a qualified electrical testing laboratory recognized by authorities having jurisdiction.
1. On-site electrical testing supervisors must have documented certification and experience with testing electrical equipment in accordance with NETA 2021 testing standards.
1.8 FIELD CONDITIONS
A. Modeling, analysis, product selection, installation, and quality control for Work specified in Division 26 must comply with requirements specified in Section 260011 "Facility Performance Requirements for Electrical."
B. Service Conditions for Electrical Power Equipment: Besides conditions specified in Section 260011 "Facility Performance Requirements for Electrical," specified electrical power equipment must be suitable for operation under service conditions specified as usual service conditions in applicable NEMA PB series, IEEE C37 series, and IEEE C57 series standards, except for the following:
PART 2 - PRODUCTS
PART 3 - EXECUTION
3.1 FIELD QUALITY CONTROL
A. Administrant for Medium-Voltage Electrical Tests and Inspections:
1. Engage qualified medium-voltage electrical testing and inspecting agency to administer and perform tests and inspections.
B. Administrant for Low-Voltage Electrical Tests and Inspections:
1. Engage qualified low-voltage electrical testing and inspecting agency to administer and perform tests and inspections.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Supplemental Requirements for Electrical 26 0010 - 10
END OF SECTION 260010
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Facility Performance Requirements for Electrical 26 0011 - 1
SECTION 26 0011 - FACILITY PERFORMANCE REQUIREMENTS FOR ELECTRICAL
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Field conditions and other facility performance requirements applicable to Work specified in Division 26.
1.2 FIELD CONDITIONS
A. Seismic Hazard Design Loads:
1. Unless otherwise indicated on Contract Documents, specified Work must withstand seismic hazard design loads determined in accordance with requirements specified in this Section, adjusted for installed elevation above or below grade.
a. The term "withstand" means "unit must remain in place without separation of parts from unit when subjected to specified seismic hazard design loads."
2. Perform calculations to obtain force information necessary to properly select seismic-restraint devices, fasteners, and anchorage. Perform calculations using methods acceptable to applicable code authorities and as presented in ASCE/SEI 7-10 including supplement No. 1. Where "ASCE/SEI 7" is used throughout this Section, it must be understood that the edition referred to in this subparagraph is the edition intended as reference throughout the Section Text.
a. Data indicated below to be determined by Delegated Design Contractor must be obtained by Contractor and must be included in individual component submittal packages.
b. Coordinate seismic design calculations with wind-load calculations for equipment mounted outdoors.
c. Building Occupancy Category: II.
d. Building Risk Category: II.
e. Building Site Classification: A.
3. Calculation Factors, ASCE/SEI 7-10, Ch. 13 - Seismic Design Requirements for Nonstructural Components: All section, paragraph, equation, and table numbers refer to ASCE/SEI 7-10 unless otherwise indicated.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Facility Performance Requirements for Electrical 26 0011 - 2
a. Horizontal Seismic Design Force (Fp): Calculated by Delegated Design Contractor by ASCE/SEI 7-10, Equation 13.3-1. Factors below must be obtained for this calculation:
1) Component Amplification Factor (ap): See Drawing Schedule for each component.
2) Component Importance Factor (Ip): See Drawing Schedule for each component.
3) Component Operating Weight (Wp): For each component. Obtain by
Delegated Design Contractor from equipment submittal.
4) Component Response Modification Factor (Rp): See Drawing Schedule for each component.
5) Height in Structure of Point of Attachment of Component for Base (z):
Determined from Project Drawings for each component by Contractor. For items at or below the base, "z" must be taken as zero.
6) Average Roof Height of Structure for Base (h): Determine from Project Drawings by Delegated Design Contractor.
b. Vertical Seismic Design Force: Calculate by Delegated Design Contractor using method explained in ASCE/SEI 7-10, Paragraph 13.3.1.
c. Seismic Relative Displacement (Dpl): Calculate by Delegated Design Contractor using methods explained in ASCE/SEI 7-10, Paragraph 13.3.2. Factors below must be obtained for this calculation:
1) Relative Seismic Displacement that Each Component Must Be Designed to Accommodate (Dp): Calculate by Delegated Design Contractor in accordance with ASCE/SEI 7-10, Paragraph 13.3.2.
2) Deflection at Building Level x of Structure A (δxA): See Drawing Schedule for each component.
3) Deflection at Building Level y of Structure A (δyA): See Drawing Schedule for each component.
4) Deflection at Building Level y of Structure B (δyB): See Drawing Schedule for each component.
5) Height of Level x to Which Upper Connection Point Is Attached (hx):
Determine for each component by Delegated Design Contractor from Project Drawings and manufacturer's data.
6) Height of Level y to Which Upper Connection Point Is Attached (hy):
Determine for each component by Delegated Design Contractor from Project Drawings and manufacturer's data.
7) Allowable Story Drift for Structure A (ΔaA): See Drawing Schedule for each component.
8) Allowable Story Drift for Structure B (ΔaB): See Drawing Schedule for each component.
9) Story Height Used in the Definition of the Allowable Drift Δa (hsx): See Drawing Schedule for each component.
B. Wind Hazard Design Loads:
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Facility Performance Requirements for Electrical 26 0011 - 3
1. Perform calculations to obtain force information necessary to properly select wind-load restraint devices, fasteners, and anchorage. Perform calculations using methods acceptable to applicable code authorities and as presented in ASCE/SEI 7-10. Where "ASCE/SEI 7" is used throughout this Section, it must be understood that the edition referred to in this subparagraph is intended as referenced throughout the Section Text unless otherwise indicated.
a. Data indicated below that are specific to individual pieces of equipment must be obtained by Contractor and must be included in individual component submittal packages.
b. Coordinate design wind-load calculations with seismic-load calculations for equipment requiring both seismic- and wind-load reinforcement. Comply with requirements in other Sections in addition to those in this Section.
2. Design wind pressure "p" for external sidewall-mounted equipment must be calculated by Delegated Design Contractor using methods in ASCE/SEI 7-16, Ch. 30. Perform calculations according to one of the following, as appropriate:
a. PART 1: Low-Rise Buildings.
b. PART 2: Low-Rise Buildings (Simplified).
c. PART 3: Buildings with "h" less than 18.3 m (60 ft.).
d. PART 4: Buildings with "h" greater than 18.3 m (60 ft.) and less than 48.8 m
(160 ft.).
e. PART 5: Open Buildings.
3. Design wind pressure "p" for rooftop equipment must be calculated by Delegated Design Contractor using methods in ASCE/SEI 7-16, Ch. 30, PART 6: Building Appurtenances and Rooftop Structures and Equipment.
4. Design wind pressure "p" for external sidewall-mounted equipment must be calculated by Delegated Design Contractor using methods in ASCE/SEI 7-10, Ch. 30. Perform calculations according to one of the following, as appropriate:
a. PART 1: Low-Rise Buildings.
b. PART 2: Low-Rise Buildings (Simplified).
c. PART 3: Buildings with "h" greater than 18.3 m (60 ft.).
d. PART 4: Buildings with "h" less than 48.8 m (160 ft.).
e. PART 5: Open Buildings.
5. Design wind pressure "p" for rooftop equipment must be calculated by Delegated Design Contractor using methods in ASCE/SEI 7-10, Ch. 30, PART 6: Building Appurtenances and Rooftop Structures and Equipment.
a. Risk Category: II.
C. Altitude:
1. Sea level to 300 m (1000 ft.).
D. Temperature Variation: Allow for thermal movements from the following differential temperatures:
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Facility Performance Requirements for Electrical 26 0011 - 4
1. Ambient Temperature Differential: 67 deg C (120 deg F).
2. Material Surface Temperature Differential: 100 deg C (180 deg F).
E. Ground Water:
1. Assume ground-water level is 900 mm (36 inch) below ground surface unless a higher water table is indicated on Drawings.
PART 2 - PRODUCTS (Not Used)
PART 3 - EXECUTION (Not Used)
END OF SECTION 260011
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Medium-Voltage Cables 26 0513 - 1
SECTION 26 0513 - MEDIUM-VOLTAGE CABLES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Cables.
2. Connectors.
3. Solid terminations.
4. Separable insulated connectors.
5. Splice kits.
6. Medium-voltage tapes.
7. Arc-proofing materials.
8. Fault indicators.
B. Related Requirements:
1. Section 260010 "Supplemental Requirements for Electrical" for additional abbreviations, definitions, submittals, qualifications, testing agencies, and other Project requirements applicable to Work specified in this Section.
2. Section 260011 "Facility Performance Requirements for Electrical" for seismic-load, wind-load, acoustical, and other field conditions applicable to Work specified in this Section.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of cable. Include splices and terminations for cables and cable accessories.
1.3 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Indicate location of each cable, splice, and termination.
B. Material Certificates: For each type of cable and accessory.
C. Design Data: Cable pulling calculations, including conduit size and fill percentage, pulling tensions, cable sidewall pressure, jam probability, voltage drop, and ground wire sizing for each cable.
D. Source quality-control reports.
E. Field quality-control reports.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Medium-Voltage Cables 26 0513 - 2
PART 2 - PRODUCTS
2.1 SYSTEM DESCRIPTION
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. Comply with IEEE C2 and NFPA 70.
C. Source Limitations: Obtain cables and accessories from single source from single manufacturer.
2.2 CABLES
A. Cable Type: Type MV 105.
B. Conductor Insulation: Ethylene-propylene rubber.
1. Voltage Rating: 15 kV.
2. Insulation Thickness: 133 percent insulation level.
C. Conductor: Copper.
D. Comply with UL 1072, AEIC CS8, ICEA S-93-639/NEMA WC 74 and ICEA S-97-682..
E. Conductor Stranding: Compact round, concentric lay, Class B.
F. Shielding: Copper tape, helically applied over semiconducting insulation shield.
G. Shielding and Jacket: Corrugated copper drain wires embedded in extruded, chlorinated, polyethylene jacket.
H. Cable Jacket: Chlorosulfonated polyethylene.
2.3 CONNECTORS
A. Comply with ANSI C119.4 for connectors between aluminum conductors or for connections between aluminum to copper conductors.
B. Copper-Conductor Connectors: Copper barrel crimped connectors.
2.4 SOLID TERMINATIONS
A. Multiconductor Cable Sheath Seals: Type recommended by seal manufacturer for type of cable and installation conditions, including orientation.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Medium-Voltage Cables 26 0513 - 3
1. Cold-shrink sheath seal kit with preformed sleeve openings sized for cable and insulated conductors.
B. Shielded-Cable Terminations: Comply with the following classes of IEEE 48. Insulation class shall be equivalent to that of cable. Include shield ground strap for shielded cable terminations.
1. Class 3 Terminations: Kit with stress cone and compression-type connector.
2.5 SEPARABLE INSULATED CONNECTORS
A. Description: Modular system, complying with IEEE 386, with disconnecting, single-pole, cable terminators and with matching, stationary, plug-in, dead-front terminals designed for cable voltage and for sealing against moisture.
B. Terminations at Distribution Points: Modular type, consisting of terminators installed on cables and modular, dead-front, terminal junctions for interconnecting cables.
C. Load-Break Cable Terminators: Elbow-type units with 200 A load make/break and continuous-current rating; coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test point on terminator body that is capacitance coupled.
D. Dead-Break Cable Terminators: Elbow-type unit with 600 A continuous-current rating;
designed for de-energized disconnecting and connecting; coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test point on terminator body that is capacitance coupled.
E. Dead-Front Terminal Junctions: Modular bracket-mounted groups of dead-front stationary terminals that mate and match with above cable terminators. Two-, three-, or four-terminal units as indicated, with fully rated, insulated, watertight conductor connection between terminals and complete with grounding lug, manufacturer's standard accessory stands, stainless steel mounting brackets, and attaching hardware.
1. Protective Cap: Insulating, electrostatic-shielding, water-sealing cap with drain wire.
2. Portable Feed-Through Accessory: Two-terminal, dead-front junction arranged for removable mounting on accessory stand of stationary terminal junction.
3. Grounding Kit: Jumpered elbows, portable feed-through accessory units, protective caps, test rods suitable for concurrently grounding three phases of feeders, and carrying case.
4. Standoff Insulator: Portable, single dead-front terminal for removable mounting on accessory stand of stationary terminal junction. Insulators suitable for fully insulated isolation of energized cable-elbow terminator.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Medium-Voltage Cables 26 0513 - 4
F. Test-Point Fault Indicators: Applicable current-trip ratings and arranged for installation in test points of load-break separable connectors, and complete with self-resetting indicators capable of being installed with shotgun hot stick and tested with test tool.
G. Tool Set: Shotgun hot stick with energized terminal indicator, fault-indicator test tool, and carrying case.
2.6 SPLICE KITS
A. Description: For connecting medium voltage cables; type as recommended by cable or splicing kit manufacturer for the application.
B. Standard: Comply with IEEE 404.
C. Splicing Products: As recommended, in writing, by splicing kit manufacturer for specific sizes, materials, ratings, and configurations of cable conductors. Include all components required for complete splice, with detailed instructions.
1. Combination tape and cold-shrink-rubber sleeve kit with rejacketing by cast-epoxy-resin encasement or other waterproof, abrasion-resistant material.
2. Premolded, cold-shrink-rubber, in-line splicing kit.
3. Premolded, EPDM splicing body kit with cable joint sealed by interference fit of mating parts and cable.
2.7 MEDIUM-VOLTAGE TAPES
A. Description: Electrical grade, insulating tape rated for medium voltage application.
B. Ethylene/propylene rubber-based, 0.76 mm (30 mill) splicing tape, rated for 130 deg C operation. Minimum 20 mm (3/4 inch) wide.
C. Silicone rubber-based, 0.30 mm (12 mil) self-fusing tape, rated for 130 deg C operation.
Minimum 38 mm (1-1/2 inch) wide.
D. Insulating-putty, 3.175 mm (125 mil) elastic filler tape. Minimum 38 mm (1-1/2 inch) wide.
2.8 ARC-PROOFING MATERIALS
A. Description: Fire retardant, providing arc flash protection.
B. Tape for First Course on Metal Objects: 250 micrometer (10 mil) thick, corrosion-protective, moisture-resistant, PVC pipe-wrapping tape.
C. Arc-Proofing Tape: Fireproof tape, flexible, conformable, intumescent to 8 mm (0.3 inch) thick, and compatible with cable jacket.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Medium-Voltage Cables 26 0513 - 5
D. Glass-Cloth Tape: Pressure-sensitive adhesive type, 25 mm (1 inch) wide.
2.9 SOURCE QUALITY CONTROL
A. Test and inspect cables according to ICEA S-97-682 before shipping.
B. Test strand-filled cables for water-penetration resistance according to ICEA T-31-610, using a test pressure of 35 kPa (5 psig).
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install cables according to IEEE 576.
B. Proof conduits prior to conductor installation by passing a wire brush mandrel and then a rubber duct swab through the conduit. Separate the wire brush and the rubber swab by 1200 to 1800 mm (48 to 72 inch) on the pull rope.
1. Wire Brush Mandrel: Consists of a length of brush approximately the size of the conduit inner diameter with stiff steel bristles and an eye on each end for attaching the pull ropes. If an obstruction is felt, pull the brush back and forth repeatedly to break up the obstruction.
2. Rubber Duct Swab: Consists of a series of rubber discs approximately the size of the conduit inner diameter on a length of steel cable with an eye on each end for attaching the pull ropes. Pull the rubber duct swab through the duct to extract loose debris from the duct.
C. Pull Conductors: Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
1. Where necessary, use manufacturer-approved pulling compound or lubricant that does not deteriorate conductor or insulation.
2. Use pulling means, including fish tape, cable, rope, and basket-weave cable grips, that do not damage cables and raceways. Do not use rope hitches for pulling attachment to cable.
3. Use pull-in guides, cable feeders, and draw-in protectors as required to protect cables during installation.
4. Do not pull cables with ends unsealed. Seal cable ends with rubber tape.
D. Install exposed cables parallel and perpendicular to surfaces of exposed structural members and follow surface contours where possible.
E. Support cables according to Section 260529 "Hangers and Supports for Electrical Systems."
F. Install "buried-cable" warning tape 305 mm (12 inch) above cables.
Early Package 2-26
Smithsonian Institution Revitalize Historic Core – SIB
Medium-Voltage Cables 26 0513 - 6
G. In manholes, handholes, pull boxes, junction boxes, and cable vaults, train cables around walls by the longest route from entry to exit; support cables at intervals adequate to prevent sag.
H. Install sufficient cable length to remove cable ends under pulling grips. Remove length of conductor damaged during pulling.
I. Install cable splices at pull points and elsewhere as indicated; use standard kits. Use dead-front separable watertight connectors in manholes and other locations subject to water infiltration.
J. Install terminations at ends of conductors, and seal multiconductor cable ends with standard kits.
K. Install separable insulated-connector components as follows:
1. Protective Cap: At each terminal junction, with one on each terminal to which no feeder is indicated to be connected.
2. Portable Feed-Through Accessory: At each terminal junction, with one on each terminal.
3. Standoff Insulator: At each terminal junction, with one on each terminal.
L. Arc Proofing: Unless otherwise indicated, arc proof medium-voltage cable at locations not protected by conduit, cable tray, direct burial, or termination materials. In addition to arc-proofing tape manufacturer's written instructions, apply arc proofing as follows:
1. Clean cable sheath.
2. Wrap metallic cable components with 250 micrometer (10 mil) pipe-wrapping tape.
3. Smooth surface contours with electrical insulation putty.
4. Apply arc-proofing tape in one half-lapped layer with coated side toward cable.
5. Band arc-proofing tape with two layers of 25 mm (1 inch) wide half-lapped, adhesive, glass-cloth tape at each end of the arc-proof tape.
M. Seal around cables passing through fire-rated elements according to Section 07 8413 “Penetration Firestopping”
N. Install fault indicators on each phase where indicated.
O. Ground shields of shielded cable at terminations, splices, and…
This is the start of the file's text. The full file is on GovTribe.