This is an amendment to a solicitation for the replacement of the package air conditioning unit and associated systems at the Smithsonian Astrophysical Observatory's Submillimeter Array Facility in Mauna Kea Science Reserve, Hawaii. Key details include extending the due date for receipt of proposals to August 31, 2023 at 5:00 PM EST while maintaining all other terms. Offerors must acknowledge receipt of all amendments signed and dated. The scope of work includes replacement of control building supply and exhaust fans, electric duct heaters, air conditioning systems, installation of new fan coil units, air cooled condensing units, controls, and commissioning.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES
PO Box 37012 Washington DC 20013-7012
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) (x) 9A. AMENDMENT OF SOLICITATION NO.
33330223RF0010042
x 9B. DATED (SEE ITEM 11)
07/24/2023
10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
2. AMENDMENT/MODIFICATION NO. 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)
1883701
6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6) CODE
SMITHSONIAN INSTITUTION
MRC 1200
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended, xis not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing
Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
A. The Solicitation Number cited above, for SAO-HI (SMA): PACU Replacement at the Smithsonian Astrophysical Observatory Submillimeter Array Facility (SMA), located in Mauna Kea Science Reserve, Hawaii, is hereby amended as follows:
A.1. Attached hereto and made part of this Amendment One are the following:
Addendum No. 1
• Narrative
• Drawings
• Direct Digital Controls
• Air Conditioning and Ventilating
Continued ...
Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
Willard B. Powell
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
16C. DATE SIGNED
Previous edition unusable STANDARD FORM 30 (REV. 11/2016) Prescribed by GSA FAR (48 CFR) 53.243 x
OCON
3. EFFECTIVE DATE
07/25/2023
1 119
CONTINUATION SHEET
REFERENCE NO. OF DOCUMENT BEING CONTINUED
33330223RF0010042/0001
NAME OF OFFEROR OR CONTRACTOR
ITEM NO.
(A)
SUPPLIES/SERVICES
(B)
QUANTITY
(C)
UNIT
(D)
UNIT PRICE
(E)
AMOUNT
(F)
• Exterior Painting
COVID-19 Safety Performance and Payment Bonds Release of Claim Form
A.2. Offerors shall acknowledge receipt of all amendments to this solicitation signed and dated and submit with proposal.
B. The Due Date for Receipt of Proposals remains August 31, 2023, at 5:00 PM EST.
Except as provided herein, all other provisions, terms and conditions of the Solicitation remain unchanged.
END OF AMENDMENT ONE
NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)
Sponsored by GSA
FAR (48 CFR) 53.110
OFPAGE
2 119
ADDENDUM NO. 1
TO CONSTRUCT
PACU REPLACEMENT
SMITHSONIAN ASTROPHYSICAL OBSERVATORY CONTROL BUILDING
SF PROJECT NO: 1883701
MAUNA KEA, HILO, HAWAI‘I
FOR THE SMITHSONIAN INSTITUTION
SMITHSONIAN FACILITIES
WASHINGTON, DC 20560
ISSUED BY BOWERS + KUBOTA CONSULTING
ARCHITECT
WAIPAHU, HAWAII
JULY 14, 2023
This addendum modifies the original Solicitation Documents for the Project dated March 2023. The items in this addendum shall govern the work, taking precedence over previously issued drawings governing the items mentioned.
A. CHANGES TO DRAWINGS
1. Revised Drawings:
The following previously issued drawings dated March 2023 are revised and reissued. These revised drawings supersede the previously issued drawings.
SHEET NO. SHEET TITLE DESCRIPTION
G-002 NOTES, PROJ INFO, ABBR
TEAM & SYMBOLS
Addition of Code Analysis.
A-412 REFLECTED CEILING PLAN –
GROUND & SECOND FLOOR
Added note 4 to the Correlator Room on
Reflected Ceiling Plan – Ground.
M-001 MECHANICAL LEGEND AND
NOTES
Revised “DEMOLITION/CONSTRUCTION
PHASING NOTES”.
M-002 MECHANICAL SCHEDULES Revised mechanical schedules.
M-003 MECHANICAL SCHEDULES Added “CONDENSATE PUMP SCHEDULE”.
M-201 MECHANICAL PLAN -
BASEMENT
Added MVD-22 and supply duct mounted smoke detector.
M-202 MECHANICAL PLAN –
GROUND FLOOR
Added detail callout for Air and Dirt
Separator, and ET-1. Added notes for existing exhaust fan controls.
M-203 MECHANICAL PLAN –
SECOND FLOOR
Added volume damper on FCU-1 outside and return air duct. Added section cut line for FCU-1. Added FCU-1 supply air ductwork size and callout for duct mounted smoke detector. Added notes for existing exhaust fan controls.
M-204 MECHANICAL SECTIONS Added detail callout for Air and Dirt
Separator, and added supply duct mounted smoke detector.
SHEET NO. SHEET TITLE DESCRIPTION
M-205 MECHANICAL SECTIONS Added section views F/M205 and G/M205.
Added MVD-22 and revised notes.
M-206 AHU-1 DETAILS Revised “AHU COMPONENT LIST” No. 6.
M-207 REFRIGERANT AND
CHILLED WATER GLYCOL
DIAGRAM
Added detail callout for Air and Dirt
Separator, and ET-1. Revised condensate piping drawing note.
M-208 CONTROLS AND DETAILS Added existing exhaust fan controls to SF-
1/SF-2 sequence of operation.
M-209 CONTROL AND DETAILS Revised AHU-1 controls. Added MVD-22 and duct mounted smoke detector on
AHU-1 schematic diagram.
M-210 CONTROLS AND DETAILS Revised FCU-1 controls and schematic diagram callout. Revised 2/M210 drawing name.
M-211 CONTROLS AND DETAILS Revised FCU-2C controls. Added controls for MVD-22, drawing 4/M211.
M-212 CONTROLS AND DETAILS Revised CH-1/CH-2 sequence of operations.
M-213 MECHANICAL DETAILS Added detail 9/M213 Air and Dirt
Separator Detail and 10/M213 Expansion
Tank Detail.
F-001 FIRE PROTECTION NOTES,
SYMBOLS &
ABBREVIATIONS
Added Clean Agent Note 15.
SHEET NO. SHEET TITLE DESCRIPTION
FX-601 SEQUENCE OF OPERATION Revised notes on Sequence for reference to Combination Fire/Smoke Dampers.
E-101 ELECTRICAL PLAN –
BASEMENT FLOOR
• Added connection to DDC control panel in Basement.
E-102 ELECTRICAL PLAN –
GROUND FLOOR
• Revised circuits to DDC control panel on 1st Floor, HVAC service receptacle, and ACCU-2.
• Revised rated loads of AHU-1, EDH-1, and ACCU-1 to match Mechanical schedule.
E-103 ELECTRICAL PLAN –
SECOND FLOOR
• Revised rated load of EDH-2 to match
Mechanical schedule.
E-502 ELECTRICAL PANEL
SCHEDULES 2
• Revised panel schedules to add DDC control panel in Basement and reflect the changes in circuiting and rated loads described above.
B. CHANGES TO SPECIFICATIONS
1. Revised Sections:
The following previously issued sections dated March 2023 are revised and reissued. These revised sections supersede the previously issued sections.
SECTION
NO. SECTION TITLE DESCRIPTION
099113 EXTERIOR PAINTING Revised paragraph 3.3 E.1.a to only
“Panelboards”.
230500 AIR CONDITIONING AND
VENTILATING
• Added a new paragraph, 2.9. The rest of the products were renumbered to accommodate the new paragraph, e.g., the previous 2.9 became 2.10, the previous 2.11 became 2.12, etc.
• Revised paragraph 2.13.H and removed reference to 9-inch scale (note that previously this paragraph was 2.12.H but was renumbered due to the added paragraph, see first bullet).
230923 DIRECT DIGITAL CONTROLS • Revised AHU-1 points list.
• Added footnote for Terminal Unit points list.
• Added footnote for VAV with Reheat points list.
• Added footnote for Server Rack
Motorized Dampers points list.
• Added points list for Motorized
Damper (MVD-22).
• Renumbered points list to accommodate added points list for
Motorized Damper (MVD-22).
END OF ADDENDUM NO. 1
AutoCAD SHX Text Institution
AutoCAD SHX Text Smithsonian
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
GRAPHIC SCALE(S)
AutoCAD SHX Text
BUILDING NAME
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION 1
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SUBMISSION
AutoCAD SHX Text
REVISION 2
AutoCAD SHX Text
REVISION 3
AutoCAD SHX Text
REVISION 4
AutoCAD SHX Text
REVISION 5
AutoCAD SHX Text
REVISION 6
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SEQUENCE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
DISCIPLINE
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
WORKING STAFF
AutoCAD SHX Text
DRAWING TYPE
AutoCAD SHX Text
DRAWING TITLE
AutoCAD SHX Text
PROJECT TITLE
AutoCAD SHX Text
A/E PROJECT NUMBER
AutoCAD SHX Text
SF PROJECT NUMBER
AutoCAD SHX Text
ADDRESS
AutoCAD SHX Text
JM
AutoCAD SHX Text
JM
AutoCAD SHX Text
TTT
AutoCAD SHX Text
OF 63
AutoCAD SHX Text
FINAL
AutoCAD SHX Text
AUG 2022
AutoCAD SHX Text THIS WORK WAS PREPARED BY ME OR UNDER MY SUPERVISION AND CONSTRUCTION OF THIS PROJECT WILL BE UNDER MY OBSERVATION. ("OBSERVATION OF CONSTRUCTION" SHALL BE DEFINED IN CHAPTER 115, HAWAII ADMINISTRATIVE RULES FOR PROFESSIONAL ENGINEERS, SURVEYORS AND LANDSCAPE ARCHITECTS STATE OF HAWAII, SUBCHAPTER 1, SECTION 16-115-2 DEFINITIONS, EFFECTIVE 8/29/94.)
AutoCAD SHX Text
EXPIRATION DATE 04/30/2024
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text Y
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text S.
AutoCAD SHX Text U.
AutoCAD SHX Text A.
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text No. 10226-M
AutoCAD SHX Text
LICENSED
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text T.
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text Y
AutoCAD SHX Text A
AutoCAD SHX Text Okahara and
AutoCAD SHX Text Associates Inc.
AutoCAD SHX Text
ENGINEERS AND LANDSCAPE ARCHITECT
AutoCAD SHX Text
07/14/23 ADDENDUM NO. 1
AutoCAD SHX Text
ANTENNA MAINTENANCE BLDG
AutoCAD SHX Text
SAO SUBMILLIMETER ARRAY FACILITY
AutoCAD SHX Text
MAUNA KEA, HAWAII
AutoCAD SHX Text
REPLACEMENT
AutoCAD SHX Text
SAO SMA PACU
AutoCAD SHX Text 1883701
AutoCAD SHX Text 14A3127.05
AutoCAD SHX Text Smithsonian Facilities
AutoCAD SHX Text Washington DC 20560
AutoCAD SHX Text 600 Maryland Avenue S.W. Suite 5001
AutoCAD SHX Text A1
AutoCAD SHX Text
NEW MECHANICAL WORK
AutoCAD SHX Text (N)
AutoCAD SHX Text (E)
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
NEW
AutoCAD SHX Text
EXISTING TO BE REMOVED
AutoCAD SHX Text
%%UMECHANICAL LEGEND
AutoCAD SHX Text
%%USYMBOLS
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
%%UDESCRIPTION
AutoCAD SHX Text
%%UABBR.
AutoCAD SHX Text
POINT OF CONNECTION
AutoCAD SHX Text
POC
AutoCAD SHX Text
OR
AutoCAD SHX Text
CLEAN-OUT, WCO-WALL, FCO-FLOOR, COTG-GRADE
AutoCAD SHX Text
CO
AutoCAD SHX Text
SA OR OA
AutoCAD SHX Text
SUPPLY OR OUTSIDE AIR - DIRECTION OF FLOW
AutoCAD SHX Text
RA OR EA
AutoCAD SHX Text
RETURN OR EXHAUST AIR - DIRECTION OF FLOW
AutoCAD SHX Text 24/12
AutoCAD SHX Text
THERMOSTAT - MOUNT 48" AFF
AutoCAD SHX Text T
AutoCAD SHX Text
MANUAL VOLUME DAMPER
AutoCAD SHX Text
VD
AutoCAD SHX Text
FLEXIBLE CONNECTOR
AutoCAD SHX Text
REFRIGERANT LIQUID
AutoCAD SHX Text
REFRIGERANT SUCTION
AutoCAD SHX Text
RS
AutoCAD SHX Text
RL
AutoCAD SHX Text
RS
AutoCAD SHX Text
RL
AutoCAD SHX Text
CONDENSATE DRAIN
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text
SHUTOFF VALVE
AutoCAD SHX Text
SA
AutoCAD SHX Text
DUCT SECTION - SUPPLY AIR
AutoCAD SHX Text
RA
AutoCAD SHX Text
DUCT SECTION - RETURN AIR
AutoCAD SHX Text
TURNING VANE
AutoCAD SHX Text
FLEXIBLE DUCT
AutoCAD SHX Text
DUCT SMOKE DETECTOR
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SUPPLY AIR DIFFUSER
AutoCAD SHX Text
SAD
AutoCAD SHX Text
SAR RAR OAR EAG TAG
AutoCAD SHX Text SUPPLY AIR REGISTER RETURN AIR REGISTER OUTSIDE AIR REGISTER EXHAUST AIR GRILLE TRANSFER AIR GRILLE
AutoCAD SHX Text
AIR PURIFIER
AutoCAD SHX Text
ION
AutoCAD SHX Text DUCTWORK - 1ST FIGURE - SIDE SHOWN 1ST FIGURE - SIDE SHOWN 2ND FIGURE - SIDE NOT SHOWN
AutoCAD SHX Text
LINEAR SLOT DIFFUSER
AutoCAD SHX Text
LSD
AutoCAD SHX Text M
AutoCAD SHX Text
MOTORIZED VOLUME DAMPER
AutoCAD SHX Text
MVD
AutoCAD SHX Text
DUCTWORK WITH DUCT WRAP INSULATION
AutoCAD SHX Text
BACKDRAFT DAMPER
AutoCAD SHX Text
BD
AutoCAD SHX Text
COUNTERBALANCED BACKDRAFT DAMPER
AutoCAD SHX Text
CBBD
AutoCAD SHX Text
CW
AutoCAD SHX Text
COLD WATER
AutoCAD SHX Text
SP
AutoCAD SHX Text
SP
AutoCAD SHX Text
DUCT STATIC PRESSURE SENSOR
AutoCAD SHX Text
CHWS
AutoCAD SHX Text
CHWR
AutoCAD SHX Text
CHWS
AutoCAD SHX Text
CHWR
AutoCAD SHX Text
CHILLED WATER SUPPLY
AutoCAD SHX Text
CHILLED WATER RETURN
AutoCAD SHX Text
AFF
AutoCAD SHX Text
ABOVE FINISH FLOOR
AutoCAD SHX Text
CARBON DIOXIDE SENSOR
AutoCAD SHX Text
CO2
AutoCAD SHX Text
CO2
AutoCAD SHX Text
DUCT TEMPERATURE SENSOR - SUPPLY AIR/RETURN AIR/MIXED AIR
AutoCAD SHX Text
AI
AutoCAD SHX Text
ANALOG INPUT
AutoCAD SHX Text
BI
AutoCAD SHX Text
BINARY INPUT
AutoCAD SHX Text
AO
AutoCAD SHX Text
ANALOG OUTPUT
AutoCAD SHX Text
BO
AutoCAD SHX Text
BINARY OUTPUT
AutoCAD SHX Text
SA
AutoCAD SHX Text
RA
AutoCAD SHX Text
MA
AutoCAD SHX Text
FSD
AutoCAD SHX Text
FIRE SMOKE DAMPER
AutoCAD SHX Text
AND NOTES
AutoCAD SHX Text
MECHANICAL LEGEND
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text GENERAL NOTES: 1. THE ENTIRE INSTALLATION SHALL COMPLY WITH ALL APPLICABLE THE ENTIRE INSTALLATION SHALL COMPLY WITH ALL APPLICABLE REQUIREMENTS OF THE STATE OF HAWAII'S CODES, THE COUNTY OF HAWAII'S CODES, AND ALL AGENCIES HAVING JURISDICTION. 2. ALL PENETRATIONS MUST BE SEALED WITH FIRESTOPPING TO MAINTAIN ALL PENETRATIONS MUST BE SEALED WITH FIRESTOPPING TO MAINTAIN FIRE-RATING REQUIREMENTS IN ACCORDANCE WITH IBC. 3. DRAWINGS INDICATE THE GENERAL ARRANGEMENT AND SHALL BE DRAWINGS INDICATE THE GENERAL ARRANGEMENT AND SHALL BE FOLLOWED AS CLOSELY AS ACTUAL FIELD CONDITIONS PERMIT. REASONABLE MODIFICATIONS TO SUIT JOB CONDITIONS SHALL NOT CONSTITUTE A BASIS FOR ADDITIONAL COMPENSATION. 4. PROMPTLY NOTIFY AND COORDINATE WITH THE CONTRACTING OFFICER'S PROMPTLY NOTIFY AND COORDINATE WITH THE CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE (COTR) OF DISCREPANCIES OR MAJOR DEVIATIONS FROM THE PLANS DUE TO UNFORESEEN OR VARYING FIELD CONDITIONS WHICH PREVENT THE TERMS OF THE CONTRACT FROM BEING FULFILLED. COORDINATE THE WORK AMONG THE VARIOUS TRADES AS NECESSARY TO AVOID CONFLICTS AND TO ENSURE THE INSTALLATION OF WORK WITHIN THE AVAILABLE SPACE. 5. OBTAIN AND PAY FOR ALL APPLICABLE PERMITS, FEES, CERTIFICATES OBTAIN AND PAY FOR ALL APPLICABLE PERMITS, FEES, CERTIFICATES AND INSPECTIONS. 6. DIMENSIONS SHOWN ON DESIGN DRAWINGS ARE BASED ON A DIMENSIONS SHOWN ON DESIGN DRAWINGS ARE BASED ON A COMBINATION OF FIELD MEASUREMENTS AND ORIGINAL/REVISION PRINT REFERENCE DRAWINGS. FIELD VERIFY ALL CONDITIONS AND DIMENSIONS RELATING TO THE PROJECT BEFORE ORDERING MATERIALS OR COMMENCING WITH THE REQUIRED WORK. 7. FURNISH AND INSTALL ALL MATERIALS AND EQUIPMENT INCLUDING FURNISH AND INSTALL ALL MATERIALS AND EQUIPMENT INCLUDING CUTTING AND PATCHING AS REQUIRED FOR A COMPLETE AND OPERATING SYSTEM. ALL MATERIALS SHALL BE NEW, FREE FROM DEFECTS AND CONFORM TO CODE. 8. PATCH ALL SURFACES EXPOSED FROM CUTTING AND/OR REMOVAL PATCH ALL SURFACES EXPOSED FROM CUTTING AND/OR REMOVAL WORK. PATCHING SHALL MATCH THE FINISH AND QUALITY OF ADJACENT SURFACES TO THE SATISFACTION OF THE COTR AT NO ADDITIONAL COST. 9. REMOVE ANY ABANDONED EQUIPMENT, DUCTWORK, PIPING, ETC. REMOVE ANY ABANDONED EQUIPMENT, DUCTWORK, PIPING, ETC. MATERIALS IDENTIFIED DURING CONSTRUCTION. 10. THE WORD "REPLACE" MEANS REMOVE EXISTING WORK AND PROVIDE THE WORD "REPLACE" MEANS REMOVE EXISTING WORK AND PROVIDE NEW WORK AS DETAILED OR NOTED ON THE DRAWINGS. 11. ALL WORK INDICATED SHALL BE NEW WORK UNLESS OTHERWISE ALL WORK INDICATED SHALL BE NEW WORK UNLESS OTHERWISE INDICATED "EXISTING". 12. ALL ITEMS AND MATERIALS TO BE REMOVED SHALL BE DONE IN SUCH A ALL ITEMS AND MATERIALS TO BE REMOVED SHALL BE DONE IN SUCH A MANNER AS TO PREVENT DAMAGE TO ITEMS AND MATERIALS TO REMAIN. ALL SUCH DAMAGES SHALL BE REPAIRED TO THE SATISFACTION OF THE COTR AT NO ADDITIONAL COST. 13. ALL WASTE MATERIALS SHALL BE PROMPTLY REMOVED AND DISPOSED ALL WASTE MATERIALS SHALL BE PROMPTLY REMOVED AND DISPOSED OF OUTSIDE THE LIMITS OF SAO'S PROPERTY. 14. PROVIDE TEMPORARY ACCESSIBLE ROUTES AROUND CONSTRUCTION IN PROVIDE TEMPORARY ACCESSIBLE ROUTES AROUND CONSTRUCTION IN ACCORDANCE WITH ADAAG 402. 15. PAINT ALL EXPOSED MECHANICAL WORK AND SUPPORTS TO MATCH PAINT ALL EXPOSED MECHANICAL WORK AND SUPPORTS TO MATCH EXISTING. 16. RECOVER AND DISPOSE OF REFRIGERANT IN ACCORDANCE WITH SECTION RECOVER AND DISPOSE OF REFRIGERANT IN ACCORDANCE WITH SECTION 608 OF THE EPA CLEAN AIR ACT (CAA). DEMOLITION/CONSTRUCTION PHASING NOTES 1. CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION MEANS AND CONTRACTOR SHALL BE RESPONSIBLE FOR CONSTRUCTION MEANS AND METHODS IN ORDER TO COMPLETE THE PROJECT. CONTRACTOR SHALL SUBMIT DEMOLITION/CONSTRUCTION PHASING PLAN FOR APPROVAL. PHASING PLAN SHALL INCLUDE, BUT NOT LIMITED TO PLANNED UTILITY OUTAGES, DISRUPTION OF HVAC SERVICE, TEMPORARY DISRUPTION OF NORMAL OPERATIONS AND PROPOSED EQUIPMENT TRANSPORT PATHS THROUGH THE FACILITY. PHASING PLAN SHALL BE APPROVED A MINIMUM OF THIRTY (30) CALENDAR DAYS PRIOR TO COMMENCEMENT OF ON-SITE WORK. 2. THE FACILITY WILL BE OPERATIONAL AND ACCESSIBLE TO BUILDING THE FACILITY WILL BE OPERATIONAL AND ACCESSIBLE TO BUILDING USERS 7-DAYS A WEEK, MONDAY THRU SUNDAY FOR THE DURATION OF THE PROJECT. THIS CONTINUING OPERATION OF THE FACILITY MAY RESTRICT THE CONTRACTOR'S WORK. NO ADDITIONAL COMPENSATION OR TIME WILL BE MADE FOR FAILURE TO ACKNOWLEDGE AND ACCOUNT FOR THE PROJECT REQUIREMENTS IN THE BID. COORDINATE, SCHEDULE AND PERFORM WORK IN SUCH A MANNER AS TO MINIMIZE INCONVENIENCES, HAZARDS AND DISTURBANCE UPON THE FACILITY'S OCCUPANTS TO ENSURE THEIR SAFETY AND TO ACCOMMODATE THE FACILITY'S DAILY OPERATIONS AND ACTIVITIES. 3. SEE DRAWINGS AND SPECIFICATIONS FOR COMPLETE SCOPE OF WORK. SEE DRAWINGS AND SPECIFICATIONS FOR COMPLETE SCOPE OF WORK. 4. DO NOT DISRUPT NORMAL FACILITY FUNCTIONS. OBTAIN SCHEDULES DO NOT DISRUPT NORMAL FACILITY FUNCTIONS. OBTAIN SCHEDULES PRIOR TO DEVELOPING A PHASING PLAN. 5. COORDINATE SCHEDULE FOR ALL HVAC WORK (REMOVAL, INSTALLATION, COORDINATE SCHEDULE FOR ALL HVAC WORK (REMOVAL, INSTALLATION, TESTING AND BALANCING, AND COMMISSIONING) WITH THE FACILITY AND COTR. 6. VERIFY LOCATION OF EXISTING UTILITIES IN THE PROJECT AREA PRIOR VERIFY LOCATION OF EXISTING UTILITIES IN THE PROJECT AREA PRIOR TO CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OR REPLACEMENT OF ANY UTILITIES IN THE EVENT OF DAMAGES CAUSED BY HIS WORK. 7. DISRUPTIONS TO UTILITIES, EXCEPT AS PRESCRIBED HEREIN, WILL NOT DISRUPTIONS TO UTILITIES, EXCEPT AS PRESCRIBED HEREIN, WILL NOT BE ALLOWED. NO EXCEPTIONS. CONTRACTOR SHALL SCHEDULE INTERRUPTION OF UTILITY SERVICE A MINIMUM OF THIRTY (30) CALENDAR DAYS IN ADVANCE OF INTERRUPTION. 8. CONTACT THE COTR AND THE FACILITY IMMEDIATELY SHOULD AN CONTACT THE COTR AND THE FACILITY IMMEDIATELY SHOULD AN UNPLANNED UTILITY OUTAGE OCCURS. 9. NOT ALL EXISTING UTILITIES INCLUDING PLUMBING, FIRE ALARM WIRING, NOT ALL EXISTING UTILITIES INCLUDING PLUMBING, FIRE ALARM WIRING, CONTROL WIRING, ELECTRICAL CONDUITS, CABLES, ETC. IN CEILING ARE SHOWN. PROTECT EXISTING UTILITIES IN PLACE. RELOCATE OR INSTALL NEW HANGERS IF NECESSARY. 10. MAKE ARRANGEMENTS WITH THE COTR TO TEST THE FACILITY'S ENTIRE MAKE ARRANGEMENTS WITH THE COTR TO TEST THE FACILITY'S ENTIRE FIRE ALARM SYSTEM LOCATED WITHIN THE PROJECT LIMITS PRIOR TO CONSTRUCTION. TEST(S) SHALL BE SCHEDULED TO AVOID DISRUPTION OF NORMAL OPERATIONS. NOTIFY THE COTR OF ANY FAILURES. CONTRACTOR SHALL PAY FOR ALL COSTS ASSOCIATED WITH THE TESTS. COST SHALL BE CONSIDERED INCIDENTAL AND INCLUDED IN THE BASE BID. 11. TAKE PRECAUTION(S) TO AVOID NUISANCE FIRE ALARMS. ALL COSTS TAKE PRECAUTION(S) TO AVOID NUISANCE FIRE ALARMS. ALL COSTS ASSOCIATED WITH FALSE FIRE ALARMS DUE TO CONSTRUCTION SHALL BE BORNE BY THE CONTRACTOR. 12. DURING NORMAL OPERATIONS, AHU-1 SHALL BE EQUIPPED WITH MERV DURING NORMAL OPERATIONS, AHU-1 SHALL BE EQUIPPED WITH MERV 8 PRE-FILTER AND MERV 14 FINAL FILTER. 13. AHU-1 SELECTION SHALL BE ABLE TO PERFORM WITH THE CONDITIONS AHU-1 SELECTION SHALL BE ABLE TO PERFORM WITH THE CONDITIONS LISTED BELOW. AHU-1 TAB AND COMMISSIONING SHALL BE CONDUCTED FOR THE CONDITIONS LISTED BELOW: A. CONDITION NO. 1: MERV 8 PRE-FILTER WITH MERV 14 FINAL CONDITION NO. 1: MERV 8 PRE-FILTER WITH MERV 14 FINAL FILTER B. CONDITION NO. 2: MERV 8 PRE-FILTER WITH MERV 16 FINAL CONDITION NO. 2: MERV 8 PRE-FILTER WITH MERV 16 FINAL FILTER MECHANICAL: : 1. REPLACEMENT OF CONTROL BUILDING SUPPLY FANS, EXHAUST FANS, REPLACEMENT OF CONTROL BUILDING SUPPLY FANS, EXHAUST FANS, ELECTRIC DUCT HEATERS AND AC SYSTEMS. A. REMOVE EXISTING FIRST FLOOR SUPPLY FANS, ELECTRIC DUCT REMOVE EXISTING FIRST FLOOR SUPPLY FANS, ELECTRIC DUCT HEATERS, EXHAUST FANS, DUCTWORK, ABANDONED STEAM PIPING, THERMOSTATS, AND HUMIDISTATS. B. INSTALL NEW SUPPLY FANS, ELECTRIC DUCT HEATERS, INSTALL NEW SUPPLY FANS, ELECTRIC DUCT HEATERS, DUCTWORK AND THERMOSTATS. C. REMOVE EXISTING SECOND FLOOR SUPPLY FANS, ELECTRIC REMOVE EXISTING SECOND FLOOR SUPPLY FANS, ELECTRIC DUCT HEATERS, EXHAUST FANS, DUCTWORK, ABANDONED STEAM PIPING THERMOSTATS AND HUMIDISTATS. D. INSTALL NEW SUPPLY FANS, ELECTRIC DUCT HEATERS, INSTALL NEW SUPPLY FANS, ELECTRIC DUCT HEATERS, DUCTWORK, AND THERMOSTATS. E. INSTALL NEW FCU-1, DUCTWORK, REFRIGERANT PIPING, INSTALL NEW FCU-1, DUCTWORK, REFRIGERANT PIPING, DAMPERS, CONTROLS AND APPURTENANCES. F. INSTALL NEW ACCU-1. TEMPORARILY LOCATE OUTSIDE OF THE INSTALL NEW ACCU-1. TEMPORARILY LOCATE OUTSIDE OF THE EXISTING ACCU ENCLOSURE. CONNECT REFRIGERANT PIPING AND CONTROLS. EXISTING ACCU'S PROVIDING SERVICE TO THE 2ND FLOOR SERVER ROOM AND CONTROL ROOM SHALL REMAIN IN PLACE AND OPERATIONAL UNTIL THE SUCCESSFUL STARTUP OPERATIONS OF THE NEW FCU-1 AND ACCU-1. OPERATE NEW SYSTEM IN FULL COOLING MODE TROUBLE FREE FOR 30 DAYS PRIOR TO REMOVING EXISTING UNITS FROM SERVICE. G. REMOVE EXISTING FCU'S, ACCU'S REFRIGERANT PIPING, AND REMOVE EXISTING FCU'S, ACCU'S REFRIGERANT PIPING, AND CONTROLS THAT ARE PROVIDING SERVICE TO THE 2ND FLOOR SERVER ROOM. H. RELOCATE ACCU-1 TO ENCLOSURE. PRIOR TO RELOCATING, RELOCATE ACCU-1 TO ENCLOSURE. PRIOR TO RELOCATING, STARTUP AND OPERATE THE FCU-1 IN ECONOMIZER MODE. I. INSTALL NEW ACCU-2, FCU-2A, FCU-2B, AND FCU-2C INSTALL NEW ACCU-2, FCU-2A, FCU-2B, AND FCU-2C PROVIDING SERVICE TO THE 2ND FLOOR SERVER ROOM AND CONTROL ROOM. INSTALL REFRIGERANT PIPING, CONDENSATE PIPING, AND CONTROLS. STARTUP SYSTEM AND OPERATE TROUBLE FREE FOR 30 DAYS. 2. REPLACEMENT OF THE EXISTING PACU WITH NEW CHILLERS AND AHU'S. REPLACEMENT OF THE EXISTING PACU WITH NEW CHILLERS AND AHU'S. A. PRETAB EXISTING PACU AND AIRFLOW TO EACH SERVER RACK. PRETAB EXISTING PACU AND AIRFLOW TO EACH SERVER RACK. SUBMIT REPORT FOR REVIEW. B. DISCONNECT EXISTING PACU FROM THE DUCTWORK AND DISCONNECT EXISTING PACU FROM THE DUCTWORK AND CONTROLS. ONCE DISCONNECTED, THE CONTRACTOR WILL HAVE A MAXIMUM OF FOUR CALENDAR WEEKS TO RELOCATE, RECONNECT, AND STARTUP AIR CONDITIONING SERVICE TO THE CORRELATOR ROOM. C. WHILE THE PACU IS DISCONNECTED: WHILE THE PACU IS DISCONNECTED: I. REMOVE THE EXISTING MOTORIZED DAMPERS, SWITCHES, REMOVE THE EXISTING MOTORIZED DAMPERS, SWITCHES, AND MANUAL VOLUME DAMPERS AT EACH SERVER RACK INLET RISER. II. INSTALL NEW TERMINAL UNITS AND MOTORIZED DAMPERS AS INSTALL NEW TERMINAL UNITS AND MOTORIZED DAMPERS AS INDICATED ON DRAWINGS. III. INSTALL NEW AIR AND TEMPERATURE SENSOR INSTALL NEW AIR AND TEMPERATURE SENSOR I. RELOCATE PACU FROM THE EXISTING PAD TO ALLOW FOR RELOCATE PACU FROM THE EXISTING PAD TO ALLOW FOR CONSTRUCTION OF THE NEW AIR HANDLING UNIT AND CHILLERS. INSTALL ON SOLID LEVEL SURFACE. J. INSTALL TEMPORARY CONNECTIONS FROM THE PACU TO THE INSTALL TEMPORARY CONNECTIONS FROM THE PACU TO THE SUPPLY AND RETURN AIR DUCTWORK. RECONNECT EXISTING CONTROLS. K. STARTUP PACU AND BALANCE TO MATCH PRETAB AIRFLOWS. STARTUP PACU AND BALANCE TO MATCH PRETAB AIRFLOWS. L. INSTALLNEW AHU, CHILLERS/PUMP, STORAGE TANK, PIPING INSTALLNEW AHU, CHILLERS/PUMP, STORAGE TANK, PIPING APPURTENANCES, AND CONTROLS. M. INSTALL NEW TEMPERATURE SENSORS, HUMIDITY SENSORS, INSTALL NEW TEMPERATURE SENSORS, HUMIDITY SENSORS, SMOKE DETECTORS, AND CONTROLS. N. PRESSURE TEST NEW CHILLED WATER PIPING. PRESSURE TEST NEW CHILLED WATER PIPING. O. STARTUP CHILLER AND PUMPS. STARTUP CHILLER AND PUMPS. P. DISCONNECT EXISTING PACU FROM DUCTWORK AND CONTROLS. DISCONNECT EXISTING PACU FROM DUCTWORK AND CONTROLS. ONCE DISCONNECTED CONTRACTOR WILL HAVE TWO CALENDAR WEEKS TO CONNECT NEW AHU AND STARTUP AIR CONDITIONING SERVICE TO THE CORRELATOR ROOM. Q. WHILE THE UNIT IS DISCONNECTED AND THE CORRELATOR WHILE THE UNIT IS DISCONNECTED AND THE CORRELATOR ROOM IS SHUT DOWN: I. PERFORM DUCT LEAKAGE TESTING AND REPAIR AND/OR PERFORM DUCT LEAKAGE TESTING AND REPAIR AND/OR RESEAL ANY LEAKING JOINTS. II. TEST TERMINAL UNIT AND AHU CONTROLS. TEST TERMINAL UNIT AND AHU CONTROLS. III. REMOVE SWITCHES AT DISCHARGE OF SERVER RACKS REMOVE SWITCHES AT DISCHARGE OF SERVER RACKS AND PATCH DUCTS. PATCH DUCTS. IV. REPLACE DUCT INSULATION WITH NEW. REPLACE DUCT INSULATION WITH NEW. M. CONNECT AHU TO SUPPLY AND RETURN DUCTS. CONNECT AHU TO SUPPLY AND RETURN DUCTS. N. STARTUP AHU. OPERATE TROUBLE FREE FOR 30 DAYS PRIOR STARTUP AHU. OPERATE TROUBLE FREE FOR 30 DAYS PRIOR TO REMOVING PACU. O. REMOVE PACU. REMOVE PACU. AIR CONDITIONING AND VENTILATION NOTES 1. FURNISH AND INSTALL ALL EQUIPMENT, ACCESSORIES, CONNECTIONS, FURNISH AND INSTALL ALL EQUIPMENT, ACCESSORIES, CONNECTIONS, MATERIALS AND INCIDENTAL ITEMS NECESSARY TO FULLY COMPLETE THE INSTALLATION OF THE AIR CONDITIONING SYSTEMS SHOWN ON THESE DRAWINGS. 2. SIZE AND INSTALL ALL REFRIGERANT PIPING AND ACCESSORIES PER SIZE AND INSTALL ALL REFRIGERANT PIPING AND ACCESSORIES PER MANUFACTURER'S RECOMMENDATIONS. 3. BALANCE ALL AIRFLOW RATES SHOWN. BALANCE ALL AIRFLOW RATES SHOWN. 4. SUBMIT AS-BUILT DRAWINGS TO THE COTR PRIOR TO PROJECT SUBMIT AS-BUILT DRAWINGS TO THE COTR PRIOR TO PROJECT CLOSEOUT.
AutoCAD SHX Text A1
AutoCAD SHX Text A1
A1
AutoCAD SHX Text Smithsonian
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
GRAPHIC SCALE(S)
AutoCAD SHX Text
BUILDING NAME
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION 1
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SUBMISSION
AutoCAD SHX Text
REVISION 2
AutoCAD SHX Text
REVISION 3
AutoCAD SHX Text
REVISION 4
AutoCAD SHX Text
REVISION 5
AutoCAD SHX Text
REVISION 6
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SEQUENCE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
DISCIPLINE
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
WORKING STAFF
AutoCAD SHX Text
DRAWING TYPE
AutoCAD SHX Text
DRAWING TITLE
AutoCAD SHX Text
PROJECT TITLE
AutoCAD SHX Text
A/E PROJECT NUMBER
AutoCAD SHX Text
SF PROJECT NUMBER
AutoCAD SHX Text
ADDRESS
AutoCAD SHX Text
JM
AutoCAD SHX Text
JM
AutoCAD SHX Text
TTT
AutoCAD SHX Text
OF 63
AutoCAD SHX Text
FINAL
AutoCAD SHX Text
AUG 2022
AutoCAD SHX Text THIS WORK WAS PREPARED BY ME OR UNDER MY SUPERVISION AND CONSTRUCTION OF THIS PROJECT WILL BE UNDER MY OBSERVATION. ("OBSERVATION OF CONSTRUCTION" SHALL BE DEFINED IN CHAPTER 115, HAWAII ADMINISTRATIVE RULES FOR PROFESSIONAL ENGINEERS, SURVEYORS AND LANDSCAPE ARCHITECTS STATE OF HAWAII, SUBCHAPTER 1, SECTION 16-115-2 DEFINITIONS, EFFECTIVE 8/29/94.)
AutoCAD SHX Text
EXPIRATION DATE 04/30/2024
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text Y
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text S.
AutoCAD SHX Text U.
AutoCAD SHX Text A.
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text No. 10226-M
AutoCAD SHX Text
LICENSED
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text T.
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text Y
AutoCAD SHX Text A
AutoCAD SHX Text Okahara and
AutoCAD SHX Text Associates Inc.
AutoCAD SHX Text
ENGINEERS AND LANDSCAPE ARCHITECT
AutoCAD SHX Text
07/14/23 ADDENDUM NO. 1
AutoCAD SHX Text
ANTENNA MAINTENANCE BLDG
AutoCAD SHX Text
SAO SUBMILLIMETER ARRAY FACILITY
AutoCAD SHX Text
MAUNA KEA, HAWAII
AutoCAD SHX Text
REPLACEMENT
AutoCAD SHX Text
SAO SMA PACU
AutoCAD SHX Text 1883701
AutoCAD SHX Text 14A3127.05
AutoCAD SHX Text Smithsonian Facilities
AutoCAD SHX Text Washington DC 20560
AutoCAD SHX Text 600 Maryland Avenue S.W. Suite 5001
AutoCAD SHX Text A1
AutoCAD SHX Text
SENSIBLE
AutoCAD SHX Text
TOTAL COOLING CAP. (BTUH)
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
WB
AutoCAD SHX Text
DB
AutoCAD SHX Text
ENT. AIR (%%DF)
AutoCAD SHX Text 11,600
AutoCAD SHX Text 261,00
AutoCAD SHX Text 71.6
AutoCAD SHX Text 43.04
AutoCAD SHX Text
SERVER RM C206
AutoCAD SHX Text
FLOOR MOUNTED VERTICAL UNIT
AutoCAD SHX Text
FCU
AutoCAD SHX Text
AutoCAD SHX Text
OPER. WEIGHT (LBS)
AutoCAD SHX Text
WALL MOUNT
AutoCAD SHX Text
FCU
AutoCAD SHX Text 2A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 11.13
AutoCAD SHX Text 0-2,985
AutoCAD SHX Text 29,000
AutoCAD SHX Text 208/230
AutoCAD SHX Text 2,985
AutoCAD SHX Text 67.3
AutoCAD SHX Text 43.5
AutoCAD SHX Text
AutoCAD SHX Text 1.15
AutoCAD SHX Text
AutoCAD SHX Text DESIGN BASED ON CARRIER 42DVA30. FURNISH WITH VOLTAGE PHASE PROTECTION AND DISCONNECT SWITCH.
AutoCAD SHX Text 29,000
AutoCAD SHX Text 261,00
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 0.60
AutoCAD SHX Text
AutoCAD SHX Text 18,000
AutoCAD SHX Text 208/230
AutoCAD SHX Text
AutoCAD SHX Text 67.3
AutoCAD SHX Text 43.5
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text DESIGN BASED ON TOSHIBA CARRIER MMK-AP0247HPUL. FURNISH WITH VOLTAGE PROTECTION AND DISCONNECT SWITCH.
AutoCAD SHX Text 18,000
AutoCAD SHX Text
%%UAIR COOLED CONDENSING UNIT SCHEDULE
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
FCU SERVED
AutoCAD SHX Text
AMBIENT TEMP (°F)
AutoCAD SHX Text
VOLTAGE
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
MCA
AutoCAD SHX Text
MOCP
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text SOUND RATING (dBA) A
AutoCAD SHX Text
OPER. WEIGHT (LBS)
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
HZ
AutoCAD SHX Text
COOLING CAPACITY (BTUH)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 208/230
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ACCU
AutoCAD SHX Text
AutoCAD SHX Text DESIGN BASED ON TOSHIBA CARRIER MCY-MAP0607HS. FURNISH WITH VOLTAGE PROTECTION AND DISCONNECT SWITCH.
AutoCAD SHX Text 36,000
AutoCAD SHX Text 36.3
AutoCAD SHX Text
AutoCAD SHX Text
FCU-1
AutoCAD SHX Text
SEER
AutoCAD SHX Text 17.6
AutoCAD SHX Text
AutoCAD SHX Text
FCU
AutoCAD SHX Text 2B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 208/230
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ACCU
AutoCAD SHX Text
AutoCAD SHX Text DESIGN BASED ON TOSHIBA CARRIER MCY-MAP0607HS. FURNISH WITH VOLTAGE PROTECTION AND DISCONNECT SWITCH.
AutoCAD SHX Text 60,000
AutoCAD SHX Text 36.3
AutoCAD SHX Text
AutoCAD SHX Text
FCU-2A, FCU-2B AND FCU-2C
AutoCAD SHX Text 20.5
AutoCAD SHX Text
AutoCAD SHX Text 8.9
AutoCAD SHX Text
AutoCAD SHX Text 13,500
AutoCAD SHX Text 13,500
AutoCAD SHX Text
WALL MOUNT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 0.60
AutoCAD SHX Text
AutoCAD SHX Text 18,000
AutoCAD SHX Text 208/230
AutoCAD SHX Text
AutoCAD SHX Text 67.3
AutoCAD SHX Text 43.5
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text DESIGN BASED ON TOSHIBA CARRIER MMK-AP0247HPUL. FURNISH WITH VOLTAGE PROTECTION AND DISCONNECT SWITCH.
AutoCAD SHX Text 18,000
AutoCAD SHX Text
AutoCAD SHX Text 13,500
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
%%UAIR COOLED WATER-GLYCOL CHILLER SCHEDULE
AutoCAD SHX Text
PACKAGED AIR COOLED SCROLL
AutoCAD SHX Text
AutoCAD SHX Text
CH
AutoCAD SHX Text
AutoCAD SHX Text
ENT (°F)
AutoCAD SHX Text
GPM
AutoCAD SHX Text
AutoCAD SHX Text
COOLER
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
MIN. COOLING CAPACITY (TONS)
AutoCAD SHX Text
MIN. STEP CAPACITY (%)
AutoCAD SHX Text
PD (FT)
AutoCAD SHX Text
AMBIENT TEMP (°F)
AutoCAD SHX Text
EER A(W/O PUMP)
AutoCAD SHX Text 12.04
AutoCAD SHX Text
AutoCAD SHX Text 22.4
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
MCA
AutoCAD SHX Text
VOLTAGE
AutoCAD SHX Text
HZ
AutoCAD SHX Text
MOCP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 61.5
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REFRIGERANT
AutoCAD SHX Text 410A
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
1. DESIGN BASED ON CARRIER MODEL 30RAP025. DESIGN BASED ON CARRIER MODEL 30RAP025. 2. FURNISH WITH PUMP PACKAGE INCLUDING DUAL PUMPS. FURNISH WITH PUMP PACKAGE INCLUDING DUAL PUMPS. 3. FURNISH WITH 119 GALLONS CHILLED WATER-GLYCOL FURNISH WITH 119 GALLONS CHILLED WATER-GLYCOL STORAGE TANK. 4. FURNISH WITH CONTROL TRANSFORMER, MOTOR STARTER, FURNISH WITH CONTROL TRANSFORMER, MOTOR STARTER, DISCONNECT SWITCH, AND VOLTAGE PHASE PROTECTION. 5. FURNISH WITH DIGITAL COMPRESSOR AND VARIABLE SPEED FURNISH WITH DIGITAL COMPRESSOR AND VARIABLE SPEED CONDENSER FANS. 6. SEE NOISE SCHEDULE FOR SOUND RATINGS.SEE NOISE SCHEDULE FOR SOUND RATINGS.
AutoCAD SHX Text
MECHANICAL SCHEDULES
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATION (FT)
AutoCAD SHX Text 13,500
AutoCAD SHX Text
ELEVATION (FT)
AutoCAD SHX Text 13,500
AutoCAD SHX Text 13,500
AutoCAD SHX Text
CH
AutoCAD SHX Text
AutoCAD SHX Text
IPLV A
AutoCAD SHX Text 14.93
AutoCAD SHX Text
PUMP DATA
AutoCAD SHX Text
GPM
AutoCAD SHX Text
KW
AutoCAD SHX Text
HEAD (FT)
AutoCAD SHX Text
HP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1.925
AutoCAD SHX Text
AutoCAD SHX Text
LOCAITON
AutoCAD SHX Text
MECHANICAL ENCLOSURE
AutoCAD SHX Text
MECHANICAL ENCLOSURE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
COMPRESSOR
AutoCAD SHX Text
ROTARY
AutoCAD SHX Text
ROTARY
AutoCAD SHX Text
QTY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REFRIGERANT
AutoCAD SHX Text 410A
AutoCAD SHX Text 410A
AutoCAD SHX Text
FAN
AutoCAD SHX Text
CONDENSER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FOULING FACTOR (HR-SQFT-°F)/BTU
AutoCAD SHX Text 0.000100
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COIL
AutoCAD SHX Text
ROWS
AutoCAD SHX Text
FACE VEL. (FPM)
AutoCAD SHX Text 43.3
AutoCAD SHX Text
FACE AREA (SQFT)
AutoCAD SHX Text
AutoCAD SHX Text
FINS PER IN.
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
UNIT TYPE
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
MCA
AutoCAD SHX Text
SENSIBLE
AutoCAD SHX Text
TOTAL COOLING CAPACITY (BTUH)
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
WB
AutoCAD SHX Text
DB
AutoCAD SHX Text
ENTERING AIR (%%DF)
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
%%UFAN COIL UNIT SCHEDULE (1 TO 1 DX AND VRF)
AutoCAD SHX Text
AREA SERVED
AutoCAD SHX Text
VOLTAGE
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
OUTSIDE
AutoCAD SHX Text
HZ
AutoCAD SHX Text SOUND RATING (dBA)
AutoCAD SHX Text
OPER. WEIGHT (LBS)
AutoCAD SHX Text
EXTERNAL STATIC (IN W.G.)
AutoCAD SHX Text
MOCP
AutoCAD SHX Text
FLA
AutoCAD SHX Text
ELEVATION (FT)
AutoCAD SHX Text
ACTUAL AIRFLOW (ACFM)
AutoCAD SHX Text
CHILLED WATER
AutoCAD SHX Text
ENT (%%DF)
AutoCAD SHX Text
PD (FT. WG)
AutoCAD SHX Text
(GPM)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 15.8
AutoCAD SHX Text
COOLING MEDIUM (WATER-GLYCOL %)
AutoCAD SHX Text
60% WATER / 40% GLYCOL
AutoCAD SHX Text AEFFICIENCIES ARE CERTIFIED IN ACCORDANCE WITH THE AHRI AIR-COOLED WATER-CHILLING PACKAGES CERTIFICATION PROGRAM, WHICH IS BASED ON AHRI STANDARD 550/590.
AutoCAD SHX Text
LVG (°F)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
STORAGE C201
AutoCAD SHX Text
UNIT LOCATION
AutoCAD SHX Text
EQUIPMENT ROOM C206
AutoCAD SHX Text
EQUIPMENT ROOM C206
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
%%UAIR HANDLING UNIT SCHEDULE CONT.
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
LVG (%%DF)
AutoCAD SHX Text
AutoCAD SHX Text 0.0
AutoCAD SHX Text
FOULING FACTOR (HR-SQFT-°F)/BTU
AutoCAD SHX Text 45 A
AutoCAD SHX Text 45 A
AutoCAD SHX Text ASOUND POWER LEVELS MEASURED 3 FT. BELOW UNIT AND 3FT. IN FRONT OF UNIT. BEXTERNAL STATIC INCLUDES FILTER (MID LIFE CONDITION).
AutoCAD SHX Text
TOTAL STATIC (IN W.G.)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 0.75
AutoCAD SHX Text ATOTAL STATIC AND VFD FREQUENCY INCLUDES PRE-FILTER (MERV 8 INITIAL RESISTANCE) AND FINAL FILTER (MERV 14 INITIAL RESISTANCE). BTOTAL STATIC AND VFD FREQUENCY INCLUDES PRE-FILTER (MERV 8 FINAL RESISTANCE) AND FINAL FILTER (MERV 14 FINAL RESISTANCE). CTOTAL STATIC AND VFD FREQUENCY INCLUDES PRE-FILTER (MERV 8 INITIAL RESISTANCE) AND FINAL FILTER (MERV 16 INITIAL RESISTANCE). DTOTAL STATIC AND VFD FREQUENCY INCLUDES PRE-FILTER (MERV 8 FINAL RESISTANCE) AND FINAL FILTER (MERV 16 FINAL RESISTANCE). EEXTERNAL STATIC DOES NOT INCLUDE PRE-FILTER AND FINAL FILTER.
AutoCAD SHX Text
SERVER RM C206
AutoCAD SHX Text
SERVER RM C206
AutoCAD SHX Text
1. SUPPLY FANS SHALL BE QTY. 4, GREENHECK MODEL 16-APH. EACH SUPPLY FAN SHALL BE FURNISHED WITH ABB VFDS. SUPPLY FANS SHALL BE QTY. 4, GREENHECK MODEL 16-APH. EACH SUPPLY FAN SHALL BE FURNISHED WITH ABB VFDS. 2. RETURN FANS SHALL BE QTY. 2, GREENHECK MODEL 18-APH. EACH RETURN FANS SHALL BE FURNISHED WITH ABB VFDS. RETURN FANS SHALL BE QTY. 2, GREENHECK MODEL 18-APH. EACH RETURN FANS SHALL BE FURNISHED WITH ABB VFDS. 3. FURNISH MISTOP SNOSTOP PANELS ON THE OUTSIDE AIR INTAKE HOOD. MISTOP SNOSTOP PANEL WIRING SHALL BE INTERNAL FURNISH MISTOP SNOSTOP PANELS ON THE OUTSIDE AIR INTAKE HOOD. MISTOP SNOSTOP PANEL WIRING SHALL BE INTERNAL TO THE UNIT. PROVIDE NECESSARY DISCONNECTS FOR MISTOP SNOSTOP PANEL MAINTENANCE. 4. FURNISH WITH VOLTAGE PHASE PROTECTION. FURNISH WITH VOLTAGE PHASE PROTECTION. 5. SEE NOISE SCHEDULE FOR SOUND RATINGS.SEE NOISE SCHEDULE FOR SOUND RATINGS.
AutoCAD SHX Text
UNIT TYPE
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
%%UAIR HANDLING UNIT SCHEDULE
AutoCAD SHX Text
AREA SERVED
AutoCAD SHX Text
CORRELATOR C107
AutoCAD SHX Text 0-18,500
AutoCAD SHX Text 18,500
AutoCAD SHX Text
CUSTOM
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
OUTSIDE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ELEVATION (FT)
AutoCAD SHX Text 13,500
AutoCAD SHX Text
ACTUAL AIRFLOW (ACFM)
AutoCAD SHX Text
UNIT LOCATION
AutoCAD SHX Text
EXTERIOR, ON PAD
AutoCAD SHX Text
SUPPLY FAN (QTY. 4 FANS)
AutoCAD SHX Text
TOTAL STATIC (IN W.G.)
AutoCAD SHX Text 3,705
AutoCAD SHX Text
RPM
AutoCAD SHX Text
VFD FREQUENCY (HZ)
AutoCAD SHX Text
RETURN FAN (QTY. 2 FANS)
AutoCAD SHX Text
TOTAL STATIC (IN W.G.)
AutoCAD SHX Text
RPM
AutoCAD SHX Text
VFD FREQUENCY (HZ)
AutoCAD SHX Text 3,511
AutoCAD SHX Text
AutoCAD SHX Text
5.19 /6.35 A/6.35 B
AutoCAD SHX Text
5.41 /6.35 C/6.35 D
AutoCAD SHX Text
3.88 E
AutoCAD SHX Text 61 /64 A/64 B
AutoCAD SHX Text 62 /64 C/64 D
AutoCAD SHX Text 4.63
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
MCA
AutoCAD SHX Text
VOLTAGE
AutoCAD SHX Text
HZ
AutoCAD SHX Text
MOCP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CONTROL RM C205
AutoCAD SHX Text
CASSETTE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 3,000
AutoCAD SHX Text 208/230
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 3,000
AutoCAD SHX Text 70.2
AutoCAD SHX Text 42.0
AutoCAD SHX Text
AutoCAD SHX Text 0.79
AutoCAD SHX Text
AutoCAD SHX Text DESIGN BASED ON TOSHIBA CARRIER MMU-AP0074HPUL. FURNISH WITH VOLTAGE PROTECTION AND DISCONNECT SWITCH.
AutoCAD SHX Text 13,500
AutoCAD SHX Text
FCU
AutoCAD SHX Text 2C
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
UNIT TYPE
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
MCA
AutoCAD SHX Text
SENSIBLE
AutoCAD SHX Text
TOTAL COOLING CAPACITY (BTUH)
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
WB
AutoCAD SHX Text
DB
AutoCAD SHX Text
COOLING ENTERING AIR (%%DF)
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
%%UFAN COIL UNIT SCHEDULE (VRF)
AutoCAD SHX Text
AREA SERVED
AutoCAD SHX Text
VOLTAGE
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
OUTSIDE
AutoCAD SHX Text
HZ
AutoCAD SHX Text SOUND RATING (dBA)
AutoCAD SHX Text
OPER. WEIGHT (LBS)
AutoCAD SHX Text
MOCP
AutoCAD SHX Text
ELEVATION (FT)
AutoCAD SHX Text
ACTUAL AIRFLOW (ACFM)
AutoCAD SHX Text
UNIT LOCATION
AutoCAD SHX Text
CONTROL ROOM C205
AutoCAD SHX Text 25 A
AutoCAD SHX Text
ASOUND POWER LEVELS MEASURED 5 FT. BELOW UNIT.
AutoCAD SHX Text
TOTAL HEATING CAPACITY (BTUH)
AutoCAD SHX Text
HEATING ENT/LVG AIR (%%DF)
AutoCAD SHX Text 3,800
AutoCAD SHX Text 3,800
AutoCAD SHX Text 63.5
AutoCAD SHX Text 83.2
AutoCAD SHX Text
SENSIBLE
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
DB
AutoCAD SHX Text
DB
AutoCAD SHX Text
%%UHEAT TRACE
AutoCAD SHX Text
AHU-1, FCU-1, FCU-2A, FCU-2B, AND FCU-2C
AutoCAD SHX Text 150 A185 B
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
UNIT SERVED
AutoCAD SHX Text
MAX CONTINUOUS EXPOSURE TEMP (°F)
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text DESIGN IS BASED ON THERMON MODEL FLX. PROVIDE 30 mA GROUND FAULT PROTECTION.
AutoCAD SHX Text
HEAT TRACE
AutoCAD SHX Text
APOWER ON. BPOWER OFF.
AutoCAD SHX Text 0.38
AutoCAD SHX Text
MINIMUM BEND RADIUS (IN.)
AutoCAD SHX Text 5°F
AutoCAD SHX Text -76°F
AutoCAD SHX Text 1.25
AutoCAD SHX Text
EXTERNAL STATIC (IN. W.G.)
AutoCAD SHX Text 7.5
AutoCAD SHX Text
HP MIN. (PER FAN)
AutoCAD SHX Text
AutoCAD SHX Text
HP MIN. (PER FAN)
AutoCAD SHX Text A1
AutoCAD SHX Text A1
AutoCAD SHX Text
AutoCAD SHX Text
FINS PER IN. (MAX)
AutoCAD SHX Text Smithsonian
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
GRAPHIC SCALE(S)
AutoCAD SHX Text
BUILDING NAME
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REVISION 1
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SUBMISSION
AutoCAD SHX Text
REVISION 2
AutoCAD SHX Text
REVISION 3
AutoCAD SHX Text
REVISION 4
AutoCAD SHX Text
REVISION 5
AutoCAD SHX Text
REVISION 6
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SEQUENCE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
DISCIPLINE
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
WORKING STAFF
AutoCAD SHX Text
DRAWING TYPE
AutoCAD SHX Text
DRAWING TITLE
AutoCAD SHX Text
PROJECT TITLE
AutoCAD SHX Text
A/E PROJECT NUMBER
AutoCAD SHX Text
SF PROJECT NUMBER
AutoCAD SHX Text
ADDRESS
AutoCAD SHX Text
JM
AutoCAD SHX Text
JM
AutoCAD SHX Text
TTT
AutoCAD SHX Text
OF 63
AutoCAD SHX Text
FINAL
AutoCAD SHX Text
AUG 2022
AutoCAD SHX Text THIS WORK WAS PREPARED BY ME OR UNDER MY SUPERVISION AND CONSTRUCTION OF THIS PROJECT WILL BE UNDER MY OBSERVATION. ("OBSERVATION OF CONSTRUCTION" SHALL BE DEFINED IN CHAPTER 115, HAWAII ADMINISTRATIVE RULES FOR PROFESSIONAL ENGINEERS, SURVEYORS AND LANDSCAPE ARCHITECTS STATE OF HAWAII, SUBCHAPTER 1, SECTION 16-115-2 DEFINITIONS, EFFECTIVE 8/29/94.)
AutoCAD SHX Text
EXPIRATION DATE 04/30/2024
AutoCAD SHX Text H
AutoCAD SHX Text S
AutoCAD SHX Text Y
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text I
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text S.
AutoCAD SHX Text U.
AutoCAD SHX Text A.
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text
PROFESSIONAL
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text No. 10226-M
AutoCAD SHX Text
LICENSED
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text T.
AutoCAD SHX Text T
AutoCAD SHX Text O
AutoCAD SHX Text Y
AutoCAD SHX Text A
AutoCAD SHX Text Okahara and
AutoCAD SHX Text Associates Inc.
AutoCAD SHX Text
ENGINEERS AND LANDSCAPE ARCHITECT
AutoCAD SHX Text
07/14/23 ADDENDUM NO. 1
AutoCAD SHX Text
ANTENNA MAINTENANCE BLDG
AutoCAD SHX Text
SAO SUBMILLIMETER ARRAY FACILITY
AutoCAD SHX Text
MAUNA KEA, HAWAII
AutoCAD SHX Text
REPLACEMENT
AutoCAD SHX Text
SAO SMA PACU
AutoCAD SHX Text 1883701
AutoCAD SHX Text 14A3127.05
AutoCAD SHX Text Smithsonian Facilities
AutoCAD SHX Text Washington DC 20560
AutoCAD SHX Text 600 Maryland Avenue S.W. Suite 5001
AutoCAD SHX Text A1
AutoCAD SHX Text
MECHANICAL SCHEDULES
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%U(E) VAV BOX, (N) MVD, AND (N) TERMINAL UNIT SCHEDULE
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
AutoCAD SHX Text 18"X12"
AutoCAD SHX Text
CORRELATOR C107
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text
SUPPLY AIR FROM AHU
AutoCAD SHX Text
ELEC. CONTROL VOLTAGE (V)
AutoCAD SHX Text
MIN. INLET STATIC PRESS. (IN W.G.)
AutoCAD SHX Text
OUTLET SIZE
AutoCAD SHX Text
INLET SIZE (" )
AutoCAD SHX Text
MINIMUM AIR (ACFM)
AutoCAD SHX Text
DESIGN AIR (ACFM)
AutoCAD SHX Text
AREA SERVED
AutoCAD SHX Text 24"X21"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text DESIGN BASED ON TITUS MODEL DQCV SLIP-IN RETROFIT TERMINAL UNIT. PROVIDE 120V/1 WITH24V STEP-DOWN TRANSFORMER AND DISCONNECT
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text 1,430
AutoCAD SHX Text 18"X12"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 24"X21"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text 18"X12"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 24"X21"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text 18"X12"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 24"X21"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text 18"X10"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 24"X21"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text 18"X10"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 24"X21"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text 18"X10"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 24"X21"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text 18"X10"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 24"X21"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text 18"X10"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 24"X21"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text 14"X8"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 20"X16"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AutoCAD SHX Text 14"X8"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 20"X16"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text 14"X8"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 20"X16"
AutoCAD SHX Text
TU
AutoCAD SHX Text
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text W
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
%%U(E) CONVECTION HEATER SCHEDULE
AutoCAD SHX Text
UNIT SERVED
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text L
AutoCAD SHX Text
SIZE
AutoCAD SHX Text H
AutoCAD SHX Text
LABORATORY C105
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 7"
AutoCAD SHX Text
DESIGN BASED ON QMARK MODEL CDF SERIES.
AutoCAD SHX Text
ELEVATION (FT)
AutoCAD SHX Text 13,500
AutoCAD SHX Text
VOLTS
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
HZ
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
KW
AutoCAD SHX Text
AutoCAD SHX Text
OPER. WEIGHT (LBS)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 12"X10"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 12"X10"
AutoCAD SHX Text
PROVIDE 120V/1 WITH 24V STEP-DOWNTRANSFORMER AND DISCONNECT
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AutoCAD SHX Text
VAV-1
AutoCAD SHX Text
AutoCAD SHX Text 12"X10"
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text 12"X10"
AutoCAD SHX Text
PROVIDE 120V/1 WITH 24V STEP-DOWNTRANSFORMER AND DISCONNECT
AutoCAD SHX Text
AHU-1
AutoCAD SHX Text
AutoCAD SHX Text
VAV-2
AutoCAD SHX Text
(E) RAD-1
AutoCAD SHX Text
TOILET C103
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-2
AutoCAD SHX Text
STORAGE C104
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-3
AutoCAD SHX Text
LABORATORY C105
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-4
AutoCAD SHX Text
LABORATORY C105
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-5
AutoCAD SHX Text
LABORATORY C105
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-6
AutoCAD SHX Text
OFFICE C106
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-7
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-8
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-9
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-10
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(E) RAD-11
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 24"
AutoCAD SHX Text
RECESSED
AutoCAD SHX Text 24"
AutoCAD SHX Text 13,500
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OPEN AREA C209
AutoCAD SHX Text
(E) RAD-15
AutoCAD SHX Text
STORAGE C204
AutoCAD SHX Text
(E) RAD-16
AutoCAD SHX Text
TOILET C203
AutoCAD SHX Text
(E) RAD-17