PACKAGE AIR CONDITIONING UNIT (PACU) REPLACEMENT FOR SMITHSONIAN ASTROPHYSICAL OBSERVATORY, SUBMILLIMETER ARRAY BASE FACILITY (SMA) IN MAUNAKEA SCIENCE RESERVE, HAWAII
Solicitation number
33330223RF0010042
Issued by

About this file

This document package includes construction drawings and specifications for the replacement of the package air conditioning unit and associated fire alarm and fire protection systems at the Smithsonian Astrophysical Observatory's Submillimeter Array base facility in Mauna Kea Science Reserve, Hawaii. The project entails replacing the existing HVAC system and installing new fire alarm and fire suppression systems. Drawings cover demolition plans, new system layouts, schedules, details and sequences of operation. Specifications address requirements for mechanical, electrical, fire protection and alarm work. Proposed construction includes installing new chillers, air handlers, ductwork, controls and electrical components to condition the facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ChanVC Typewriter Appendix 1

NOEI

PH: (808) 536-2626 FAX: (808) 536-3926

HONOLULU, HAWAII 96813.1003 BISHOP STREET

PAUAHI TOWER, SUITE 2025

CONSULTING STRUCTURAL ENGINEERS

HONOLULU, HAWAII 96813.1003 BISHOP STREET

HONOLULU, HAWAII 96813.1003 BISHOP STREET

HONOLULU, HAWAII 96813.1003 BISHOP STREET

HONOLULU, HAWAII 96813.1003 BISHOP STREET

M

M www.coffman.com ph 808.687.8884

745 Fort Street, Suite 400 Honolulu, HI 96813

FIRE PROTECTION SYMBOLS AND ABBREVIATIONS

DESCRIPTION

SMOKE DETECTOR, PHOTOELECTRICS P

NEW

1. DESIGN AND INSTALLATION OF THE CLEAN AGENT FK-S-1-12 (NOVEC 1230) FIRE

EXTINGUISHING SYSTEM MUST BE IN ACCORDANCE WITH NFPA 2001-2018, AND

SPECIFICATION SECTION 21 22 00.

2. DEVICES AND EQUIPMENT MUST BE UL LISTED OR FM APPROVED.

3. CLEAN AGENT EXTINGUISHING SYSTEM MUST PROVIDE COVERAGE IN THE DESIGNATED

ROOMS.

4. DEVICE LOCATIONS, PIPE AND CONDUIT ROUTINGS ARE CONCEPTUAL. FINAL QUANTITY

AND LAYOUT MUST BE IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S

RECOMMENDATIONS AND EQUIPMENT LISTINGS. COORDINATE WITH MECHANICAL AND

ELECTRICAL EQUIPMENT AND RACEWAYS.

5. MINIMUM DESIGN CONCENTRATION MUST BE 4.5% AND THE MAXIMUM DESIGN

CONCENTRATION MUST BE 10%. THE DESIGN TEMPERATURE RANGE MUST BE 60 TO 90

DEGREES FAHRENHEIT. THE CONCENTRATION MUST BE MAINTAINED OVER THE

TEMPERATURE RANGE ABOVE FOR A MINIMUM OF 10 MINUTES. THE DESIGN ALTITUDE

MUST BE 13,400 FEET.

6. PIPING AND FITTINGS MUST COMPLY WITH NFPA 2001. PIPING MUST BE PROVIDED WITH

EARTHQUAKE PROTECTION. SYSTEM PIPING IN FINISHED AREAS MUST BE CONCEALED

FROM VIEW.

7. FIRE PROTECTION CONTRACTOR MUST SEAL ALL FIRE PROTECTION PENETRATIONS, SUCH

AS BUT NOT LIMITED TO, ALL PIPING, CONDUITS, JUNCTION BOXES, AND OPENINGS

REQUIRED FOR THE WORK IN ALL WALLS AND CEILINGS IN CLEAN AGENT PROTECTED

SPACES TO MAINTAIN ROOM INTEGRITY REQUIREMENTS OF NFPA 2001. WALLS INCLUDE

GYP BOARD PARTITIONS AND CONCRETE. CEILINGS AND FLOOR ARE CONCRETE.

FIRESTOP PENETRATIONS WITH SYSTEM RATED FOR ONE (1) HOUR.

8. FIRE PROTECTION CONTRACTOR MUST COORDINATE WITH THE GENERAL CONTRACTOR

TO SEAL ALL EXISTING PENETRATIONS INTO THE PROTECTED SPACE.

9. PROVIDE INSPECTION AND TESTS IN ACCORDANCE WITH NFPA 2001, CHAPTER 11 AND

ANNEX D, AND SPECIFICATION SECTION 21 20 00, INCLUDING A ROOM INTEGRITY TEST.

10. A ROOM INTEGRITY TEST MUST BE COMPLETED IN EACH ROOM FOR THE PRELIMINARY

AND FINAL ACCEPTABLE TESTING. A SECOND FINAL TEST MUST BE DONE AFTER THE

COMPLETION OF THE EXISTING SYSTEM REMOVAL. SEE SPEC SECTION 21 20 00 3.5 B.3 FOR

ADDITIONAL INFORMATION.

11. EXISTING SYSTEM MUST BE KEPT OPERATIONAL UNTIL THE NEW SYSTEMS ARE TESTED

AND ACCEPTED.

12. EXISTING CLEAN AGENT CYLINDERS AND AGENT SHALL BE RECYCLED AND CREDIT

PROVIDED BACK TO THE OWNER.

13. AIR SAMPLING PANELS FOR THE VAULT AND EQUIPMENT ROOM SHALL BE SECTOR

ADDRESSABLE (ABLE TO DISTINGUISH ALARM BY PIPE). AIR SAMPLING PANEL FOR THE

CORRELATOR ROOM SHALL BE ADDRESSABLE PER SAMPLING TUBE (ABLE TO IDENTIFY

ALARM BY SAMPLING TUBE).

14. PIPING AND NOZZLES SHOWN ARE ONLY CONCEPTUAL TO INDICATE THE ROUTING. FINAL

PIPING AND NOZZLE LAYOUT SHALL BE DONE BY THE CONTRACTOR.

ASSD AIR SAMPLING TYPE SMOKE DETECTOR, MOUNTED 5'-0" TO TOP OF PANEL

FSP CLEAN AGENT SUPPRESSION SYSTEM CONTROL PANEL, MOUNTED 5'-0" TO TOP OF PANEL

EPO EMERGENCY POWER OFF SWITCH

FACP FIRE ALARM CONTROL PANEL

CLEAN AGENT PRE-DISCHARGE AUDIO/VISUAL ALARM

P

CLEAN AGENT POST-DISCHARGE AUDIO/VISUAL ALARM

D

A

M

M/R

SV

LP

FP

CLEAN AGENT MANUAL ACTIVATION STATION

CLEAN AGENT MANUAL ABORT STATION

CLEAN AGENT STORAGE CYLINDER

LOW PRESSURE SWITCH

SOLENOID VALVE

PRESSURE SWITCH

MAIN RESERVE SWITCH

AIM

AOM

R

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

24 VOLT RELAY

ABOVE FINISHED FLOOR

TYPICAL

WEATHERPROOF

P

D

CLEAN AGENT PRE-DISCHARGE VISUAL ALARM

CLEAN AGENT POST-DISCHARGE VISUAL ALARM

CLEAN AGENT BELL

VISUAL OR AUDIO/VISUAL DEVICE AUDIO DEVICE

7' -6

6'

-8

PLAN VIEW

LP LP

TO NOZZLES 90 DEGREE ELBOW FOR

DISCHARGE HOSE

CONNECTION

CLEAN AGENT CYLINDERS MAIN

SUPPLY, NUMBER OF

CYLINDERS VARIES CYLINDER

RESERVE SUPPLY, NUMBER OF

CYLINDERS VARIES

ELEVATION VIEW

FP

SV SV

EXISTING

P

ASSD

FSP

EPO

FACP

P

D

A

M

M/R

SV

LP

FP

AIM

AOM

R

P

D

DUCT SMOKE DETECTORS P

2ND FLOOR

1ST FLOOR

BASEMENT

CLEAN AGENT

NOZZLE (TYPICAL)

CLEAN AGENT TANK

(TYPICAL)

1. INSTALL NEW FSP, ASSD, NOTIFICATION, CLEAN AGENT CYLINDERS, PIPING AND NOZZLES.

2. PERFORM PRELIMINARY TEST ON NEW SYSTEMS BEFORE CONNECTING TO SHUNT TRIPS,

DAMPERS AND AHU'S.

3. PERFORM FINAL ACCEPTANCE TESTS WITH SHUNT TRIPS, DAMPERS AND AHU'S

CONNECTED.

4. DECOMMISSION AND REMOVE EXISTING SYSTEMS AFTER NEW SYSTEMS ARE ACCEPTED.

SEE CYLINDER PHASING PLAN OR FX102.

5. PERFORM RETESTS ON CYLINDERS AND ROOM INTEGRITY TESTS.

http://www.coffman.com http://www.coffman.com http://www.coffman.com http://www.coffman.com

P

FS

P

A M

REMOVE TWO (2) EXISTING

FIKE 35 LB FM-200 CYLINDERS,

ASSOCIATED PIPING AND

NOZZLES

D

M/RSV SV

FP

REMOVE EXISTING CLEAN AGENT

VALVES AND SWITCHES (TYPICAL)

VAULT

REMOVE EXISTING FIKE

CONTROL PLAN AND ALL

EXISTING FIRE SUPPRESSION

DEVICES (TYPICAL)

FSP

FSP

M

D

A

A

M

D

A

P P

A

REMOVE TWELVE (12) EXISTING

350 CU.FT. INERGEN MAIN AND

CONNECTED RESERVE SUPPLY

CYLINDERS AND ASSOCIATED

PIPING

REMOVE TWO (2) EXISTING

FIKE 35 LB FM-200 CYLINDERS

AND ASSOCIATED PIPING

PIPE UP TO

SECOND FLOOR

M/R

SV SV

FP

M/RSV SV

FP

SV SV

FP

REMOVE EXISTING ANSUL

AUTOPULSE CONTROL PANEL

(TYPICAL)

REMOVE EXISTING INERGEN

NOZZLES AND PIPING (TYPICAL)

REMOVE EXISTING CLEAN

AGENT VALVES AND SWITCHES

(TYPICAL)

RECIEVER

LABORATORY

ELECTRONICS

LABORATORY CORRELATOR

DIGITAL

CORRELATOR

ANALOG

OFFICEVESTIBULE

STORAGE

TOILET

ECORRIDOR

REMOVE ALL EXISTING FIRE

SUPPRESSION DEVICES

CONNECTED TO ANSUL

AUTOPULSE CONTROL PANEL

(TYPICAL)

www.coffman.com ph 808.687.8884

745 Fort Street, Suite 400 Honolulu, HI 96813

NOTE: SEE FX102 FOR PHASING ON EXISTING CLEAN AGENT SUPPRESSION DEMOLITION

http://www.coffman.com http://www.coffman.com http://www.coffman.com

FSP

FA

C

P D

A

M

A P

PIPE DOWN TO

FIRST FLOOR

EXISTING FIRE ALARM

CONTROL PANEL

REMOVE EXISTING ANSUL

AUTOPULSE CONTROL PANEL

(TYPICAL)

REMOVE ALL EXISTING FIRE

SUPPRESSION DEVICES

CONNECTED TO ANSUL

AUTOPULSE CONTROL PANEL

(TYPICAL)

REMOVE EXISTING FM-200 NOZZLES

AND PIPING

OFFICE

CORRIDOR

BREAK ROOM

EQUIP ROOM

CORRIDOR

CONTROL ROOMSTORAGE

STORAGETOILET

www.coffman.com ph 808.687.8884

745 Fort Street, Suite 400 Honolulu, HI 96813 http://www.coffman.com http://www.coffman.com http://www.coffman.com

PROTECT THIS SPACE

WITH NOVEC 1230 SYSTEM

VAULT

P

D A M

D

ASSD

PROVIDE AIR

ASPIRATING SMOKE

DETECTION FOR

PROTECTED SPACE

R

DAMPER

CLEAN AGENT

PIPING UP

THRU FLOOR

S

PROTECT THIS SPACE

WITH NOVEC 1230 SYSTEM

RECIEVER

LABORATORY

ELECTRONICS

LABORATORY CORRELATOR

DIGITAL

CORRELATOR

ANALOG

OFFICE

VESTIBULE

STORAGETOILET

ECORRIDOR

P

D

A

M

P

D

A

M

D

FS

P

AS

SD

PROVIDE ADDRESSABLE

SAMPLING POINTS TYPE

OF DETECTION

SEE FX102 FOR ENLARGED

VIEW OF SUPPRESSION

SYSTEM AND INSTALLATION

PHASING

R

AHU-1

R

DAMPER

R

PANEL LP6

SHUNT TRIP

FA

C

P

PROVIDE NOVEC 1230

NOZZLE INSIDE DUCTWORK

PROVIDE A SAMPLING

PORT AT EACH RACK

(TYPICAL)

R

SHUNT TRIP

R

SHUNT TRIP

R

SHUNT TRIP

PROVIDE A SAMPLING

PORT AT CEILING

(TYPICAL OF 4)

CLEAN AGENT

PIPING ABOVE

CEILING

NOVEC 1230 NOZZLE

(TYPICAL)

CLEAN AGENT

PIPING DN

THRU FLOORCLEAN AGENT

PIPING UP

THRU FLOOR

R

PANEL DP

SHUNT TRIP

R

PANEL LP2

SHUNT TRIP

PANEL VAULT

www.coffman.com ph 808.687.8884

745 Fort Street, Suite 400 Honolulu, HI 96813 http://www.coffman.com http://www.coffman.com http://www.coffman.com

PROTECT THIS SPACE

WITH NOVEC 1230 SYSTEM

OFFICE

CORRIDOR

BREAK ROOM

EQUIP ROOM

CORRIDOR

CONTROL ROOM

STORAGE

STORAGETOILET

P

D

D

A M

AS

SD

PROVIDE AIR

ASPIRATING SMOKE

DETECTION FOR

PROTECTED SPACE

R

DAMPER

R

FCU-1

CLEAN AGENT

PIPING ABOVE

CEILING

NOVEC 1230 NOZZLE

CLEAN AGENT

PIPING DN

THRU FLOOR

R

DAMPER

R

DAMPER

R

DAMPER

S

SV LP FP

SV LP FP

SV LP FP

SV LP FP

SV LP FP

SV LP FP

SV

LP

MR

SV

LP

MR

SV

LP

MR

SV

LP

FP

SV

LP

FP

SV

LP

FP

SV

LP

MR

SV

LP

SV

LP

CORRELATOR VAULT

2ND FLOOR

EQUIPMENT

MR

MR

www.coffman.com ph 808.687.8884

745 Fort Street, Suite 400 Honolulu, HI 96813

TEMPORARILY INSTALL MAIN SUPPLY FOR EACH

ROOM

DEMOLISH EXISTING TANKS AND

INSTALL RESERVE SUPPLY IN

FINAL LOCATION AFTER

SYSTEMS ARE ACCEPTED

RELOCATE MAIN SUPPLY FROM

TEMPORARY LOCATION TO FINAL

LOCATION

REPIPE TO CORRELATOR

REPIPE TO 2ND FLOOR EQUIPMENT

ROOM

http://www.coffman.com http://www.coffman.com http://www.coffman.com

FSP

TVSS

PD

D D

VAULT EXTERIOR

A M

AOM

RASSD

AIM AIM AIM

PD

D D

CORRELATOR

ANALOG

EXTERIOR

A M

ELECTRONIC

LABORATORY

AIM A M

CORRELATOR

DIGITAL

CRAWL

SPACE

AOM

R

AOM

R

ASSD

AIM AIM AIM

PD

D D

CONTROL

ROOM

A M

STORAGE

ROOM

AIMAOM

R

EQUIP

ROOM

AOM

R

ASSD

AIM AIM AIMAIM

AOM

SV

AIM

LP

AIM

FP

ELECTRONIC LABORATORY

AOM

SV

AIM

LP

AOM

MR

AOM

SV

AIM

LP

AIM

FP

AOM

SV

AIM

LP

AOM

MR

AOM

SV

AIM

LP

AIM

FP

AOM

SV

AIM

LP

AOM

MR

VAULTCORRELATOREQUIP

ROOM

PD

D

AOM

R

AOM

R

AOMAOMAOMAOMAOMAOMAOMAOM

AIM

AIMAOM

R

AOM

R

FACP

AOM

R

AOM

R

AOM

R

AOM

R

AOM

R

S

S

AOM

www.coffman.com ph 808.687.8884

745 Fort Street, Suite 400 Honolulu, HI 96813

IN

TERRUPT TIM

E D

ELA

Y SEQUENCE AT FSP

OPERATION OF MAIN-TO-RESERVE TRANSFER SWITCH ON CLEAN AGENT SYSTEM

ACTIVATION OF LOW PRESSURE SWITCH ON CLEAN AGENT SYSTEM

OPEN CONDITION OF CLEAN AGENT SYSTEM RELEASING SOLENOID VALVE

ACTIVATION OF PRESSURE ALARM SWITCH ON CLEAN AGENT SYSTEM

COMPLETION OF CLEAN AGENT SYSTEM 30 SECOND TIME DELAY SEQUENCE

ACTIVATION OF CLEAN AGENT SYSTEM ABORT STATION DURING TIME DELAY SEQUENCE

ACTIVATION OF CLEAN AGENT SYSTEM MANUAL ACTUATION STATION

SYSTEM INPUT

FSP R

ELE

ASES C

LE

AN AGENT SYSTEM

ACTIVATE POST-D

ISCHARGE AUDIO

/VISUAL A

LA

RMS

X

X

X

X X

X

X

ANNUNCIATE SUPERVISORY ZONE AT FSP, S

END SIG

NAL T

O BUILD

IN

G FACP

ANNUNCIATE TROUBLE

ZONE AT FSP, S

END SIG

NAL T

O BUILD

IN

G FACP

FSP TO ACTIVATE PRE-D

ISCHARGE AUDIO

/VISUAL A

LA

RMS

SYSTEM OUTPUT

FSP TO IN

ITIATE 30

SECOND TIM

E D

ELA

Y SEQUENCE

SEQUENCE OF OPERATION

A

B

C

D

E

F

G

H

I

J

1 2 3 4 5 6 7 8 9 10 11 1312

TROUBLE CONDITION ON CLEAN AGENT SUPPRESSION SYSTEM CIRCUITS X

A

B

C

D

E

F

G

H

I

J

FSP TO STOP PRE-D

ISCHARGE AUDIO

/VISUAL A

LA

RMS AND

X

ACTIVATION OF SERVICE DISCONNECT SWITCH X

OVERRID

E R

ELE

ASE O

F C

LE

AN AGENT SYSTEM

X

FSP SHUT D

OWN ASSOCIATED AIR

H

ANDLIN

G U

NITS AFTER 10

SECOND D

ISCHARGE +

FSP TO ACTIVATE POST-D

ISCHARGE AUDIO

/VISUAL A

LA

RMS

XX

X

FSP TO C

LO

SE M

OTORIZED FIR

E/SMOKE D

AMPER AFTER A 10

SECOND D

ELA

Y

X

X

K K

X X * AIR SAMPLING SYSTEM SET POINTS SHALL BE AS FOLLOWS:

LOW LEVEL (MAXIMUM SENSITIVITY): 0.2%

OBSCURATION/FOOT

BASED ON AMBIENT

CONDITIONS OF THE SPACE

MEDIUM LEVEL (MINIMUM SENSITIVITY): 0.5%

FIRE 1 OBSCURATION/FOOT

HIGH LEVEL (SMOKE DETECTOR EQUIVALENT): 2.0%

FIRE 2 OBSCURATION/FOOT

NOTE:

AMBIENT CONDITIONS MUST BE DETERMINED IN ORDER TO

PROPERLY SELECT THE MAXIMUM SENSITIVITY SET POINT. THE

INSTALLED SYSTEM SHALL RUN FOR A MINIMUM OF ONE WEEK

TO CALIBRATE THE AMBIENT CONDITIONS, AND THE ALARM SET

POINTS SHALL BE SET ACCORDINGLY AS INDICATED ABOVE

** SYSTEM OUTPUT FUNCTION LIMITED TO THE SPACE

ASSOCIATED WITH THE SYSTEM INPUT DEVICE ACTIVATED

+ FOR EQUIPMENT ROOM SYSTEM: FCU-1 SHUTS DOWN IMMEDIATELY.

VERY EARLY WARNING SMOKE DETECTION SYSTEM ALARM ON FIRE 1

VERY EARLY WARNING SMOKE DETECTION SYSTEM SUPERVISORY

VERY EARLY WARNING SMOKE DETECTION SYSTEM TROUBLE

L LX

X

SHUNT TRIP U

PS/POWER TO R

OOM

VERY EARLY WARNING SMOKE DETECTION SYSTEM ALARM ON TWO PIPES AT FIRE 2 LEVELS

M

X X X

X

X

14 15

M

ANNUNCIATE ALA

RM AT FSP - S

END SMOKE D

ETECTIO

N ALA

RM TO

BUILD

IN

G FACP (E

ACH SYSTEM)

ANNUNCIATE ALA

RM AT FSP - S

END C

LE

AN AGENT R

ELE

ASE TO

BUILD

IN

G FACP (E

ACH SYSTEM)

NOTES:

1. CLEAN AGENT SEQUENCE IS TYPICAL FOR EACH SYSTEM. VAULT, CORRELATOR, AND EQUIPMENT ROOM SHALL FUNCTION AS SEPARATE SYSTEMS.

2. CORRELATOR SYSTEM SHALL DISCHARGE INTO THE ROOM AND RETURN DUCT. AHU SHALL OPERATE DURING THE DISCHARGE TO DISTRIBUTE CLEAN

AGENT INTO THE RACKS. AT THE END OF THE DISCHARGE AHU SHALL SHUT OFF AND DAMPERS SHALL CLOSE.

X

X

TRANSFER D

ISCHARGE C

IR

CUIT FROM M

AIN

TO R

ESERVE AT FSP

(R

ESERVE TO M

AIN

IN

R

ESERVE POSITIO

N)

X

DUCT SMOKE DETECTORN NX

FSP SHUT D

OWN ASSOCIATED AIR

H

ANDLIN

G U

NIT

X

X

CLE

AN AGENT SYSTEM ACTIVATIO

N SIG

NAL T

O D

DC

X

X

X http://www.coffman.com http://www.coffman.com http://www.coffman.com

ELECTRICAL LEGEND

DUPLEX RECEPTACLE, +18" UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE, GFCI TYPE, +18" UNLESS OTHERWISE NOTED

DUPLEX RECEPTACLE, GFCI TYPE, WITH WEATHERPROOF COVER +18" UNLESS

OTHERWISE NOTED

SPECIAL PURPOSE OUTLET, NEMA TYPE AS NOTED

DESCRIPTION

TELECOM CABINET, SIZE AS NOTED

EQUIPMENT CONNECTION

CEILING MOUNTED JUNCTION BOX, 4-11/16" SQUARE

WALL MOUNTED JUNCTION BOX, 4-11/16" SQUARE

JUNCTION BOX, SIZE AS NOTED

PANELBOARD

DISCONNECT SWITCH, SIZE AND RATING AS NOTED

COMBINATION DISCONNECT SWITCH/MOTOR STARTER. FURNISHED BY

MECHANICAL, INSTALL BY ELECTRICAL CONTRACTOR

RACEWAY AND CONDUCTORS BELOW FLOOR OR GRADE

RACEWAY AND CONDUCTORS CONCEALED ABOVE GRADE

CONDUIT STUB OUT

PANEL AND CIRCUIT DESIGNATION (PANEL '2PL', CIRCUIT '1' INDICATED)

FIRE ALARM MANUAL PULL STATION, +48"

VISIBLE NOTIFICATION APPLIANCE, WALL MOUNTED +80" TO BOTTOM OF LENS

COMBINATION AUDIBLE (HORN)/VISIBLE NOTIFICATION APPLIANCE, WALL MOUNTED

+80" TO BOTTOM OF LENS

SMOKE DETECTOR, ADDRESSABLE, PHOTOELECTRIC

HEAT DETECTOR, FIXED TEMPERATURE

FIRE ALARM CONTROL PANEL, +72" TO TOP OF CABINET

SHEET NOTE, SEE SAME SHEET

FLEX CONNECTION

SINGLE RECEPTACLE, +18" UNLESS OTHERWISE NOTED

WALL MOUNTED SPECIAL PURPOSE OUTLET, NEMA TYPE AS NOTED

EXISTING

TO

REMAIN

TOGGLE SWITCH SINGLE POLE, +48" MAX TO TOP OF DEVICE UNLESS OTHERWISE

NOTED

TELEDATA OUTLET PROVISION, +18" UNLESS OTHERWISE NOTED

WP

E

J

J

J

F P

P

P

FACP

REVISION DELTA

WALL MOUNTED SMOKE DETECTOR, 4"-12" DOWN FROM CEILING TO THE TOP OF THE

DETECTOR

COMBINATION AUDIBLE(HORN)/VISIBLE NOTIFICATION APPLIANCE, CEILING MOUNTED

VISIBLE NOTIFICATION APPLIANCE, CEILING MOUNTED

ABBREVIATIONS

AC ALTERNATING CURRENT

ACCU AIR-COOLED CONDENSING UNIT

AF AMPERES, FRAME

AHU AIR HANDLING UNIT

ASSD AIR SAMPLING TYPE SMOKE DETECTOR

AT AMPERES, TRIP

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAGE

BS BELL ALARM SWITCH

CH CHILLER

CHAN CHANNEL

COTR CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE

DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER

DC DIRECT CURRENT

DIST PNL DISTRIBUTION PANEL

DS DISCONNECT SWITCH

(E)/EXST EXISTING

ECB ENCLOSED CIRCUIT BREAKER

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EMT ELECTRICAL METALLIC TUBING

EOL END OF LINE RESISTOR

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FCU FAN-COIL UNIT

FP FIRE PROTECTION

F/SD FIRE/SMOKE DAMPER

FSP FIRE SUPPRESSION PANEL

GFI GROUND FAULT INTERRUPTING

GND GROUND

HELCO HAWAII ELECTRIC & LIGHT COMPANY

JB JUNCTION BOX

MCC MOTOR CONTROL CENTER

NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

PACU PACKAGED AIR CONDITIONING UNIT

PD PROTECTIVE DEVICE

PNL PANEL

SAO SMITHSONIAN ASTROPHYSICAL OBSERVATORY

SF SUPPLY FAN

ST SHUNT TRIP

SYS SYSTEM

TELECOM TELECOMMUNICATIONS

TU TERMINAL UNIT

TYP TYPICAL

UFC UNIFORM FIRE CODE

UL UNDERWRITER'S LABORATORIES, INC.

VAV VARIABLE AIR VOLUME

VESDA VERY EARLY SMOKE DETECTION APPARATUS

RACEWAY AND CONDUCTORS EXPOSED ABOVE GRADE

ELECTRICAL ONE-LINE DIAGRAM LEGEND

DESCRIPTION

EXISTING

TO

REMAIN

POWER TRANSFORMER, SIZE AND RATINGS AS INDICATED. DELTA AND WYE-TYPE

CONNECTIONS SHOWN.

M

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

METER

GROUND

CIRCUIT BREAKER

DISCONNECT SWITCH

FUSE

G GENERATOR, SIZE AND RATINGS AS INDICATED

SPECIAL PURPOSE OUTLET

PLUG-IN LINE OR PULL-APART LOAD OR CONTROL TERMINAL

MOTOR, NUMBER INDICATES HORSEPOWER1

MCB

MCP

SELECTOR SWITCH

H - HAND

O - OFF

A - AUTO

COMBINATION MOLDED CASE CIRCUIT BREAKER AND MAGNETIC MOTOR CONTACTOR,

RATING AS INDICATED

COMBINATION MOTOR CIRCUIT PROTECTOR AND MAGNETIC MOTOR STARTER,

RATING AS INDICATED

3P 3A

3P 20A

NEW

2PL-1

WP

E

J

J

J

F P

P

P

FACP

NEW

M

G

MCB

MCP3P

3A

3P 20A

EXISTING

TO BE

DEMOLISHED

WP

E

J

J

J

F P

P

P

FACP

M

G

MCB

MCP3P

3A

3P 20A

EXISTING

TO BE

DEMOLISHED

X

X X

POTENTIAL TRANSFORMERX X

ELECTRICAL NOTES

PROJECT DESCRIPTION:

THE INTENT OF THIS PROJECT IS TO REPLACE THE HEATING, VENTILATION, AND AIR CONDITIONING (HVAC) SYSTEM, AND THE FIRE ALARM AND FIRE PROTECTION SYSTEMS AT THE SMITHSONIAN SUMMIT FACILITY AT MAUNA KEA, HI. THE ELECTRICAL SCOPE OF WORK IS TO PROVIDE POWER TO NEW MECHANICAL EQUIPMENT, FIRE ALARM, AND FIRE SUPPRESSION EQUIPMENT. THE EXISTING FIRE ALARM SYSTEM SHALL BE EXISTING TO REMAIN AND SHALL NOT BE DEMOLISHED UNTIL THE NEW FIRE ALARM SYSTEM IS

INSTALLED AND FULLY OPERATIONAL.

GENERAL NOTES:

A. REFER TO COMPLETE CONTRACT DOCUMENTS FOR OTHER DETAILS AND REQUIREMENTS.

B. CONFORM TO THE BUILDING, FIRE, AND ELECTRICAL CODES OF THE COUNTY OF HAWAII, LAWS AND REGULATIONS OF THE

COUNTY OF HAWAII AND STATE OF HAWAII.

C. OBTAIN AND PAY FOR REQUIRED LICENSES, FEES, AND OTHER CHARGES. DELIVER CERTIFICATES OF COMPLETION AND

INSPECTION TO THE COTR. SUBCONTRACTORS SHALL BE LICENSED FOR THE WORK THEY PERFORM.

D. PROVIDE 4 COPIES OF DATA ON LUMINAIRES, ELECTRICAL EQUIPMENT, AND WIRING DEVICES THAT HAVE BEEN CHECKED BY

THE CONTRACTOR FOR COTR'S REVIEW AND APPROVAL. ALLOW TEN WORKING DAYS FOR REVIEW PROCESS. (IF SUBSTITUTE PRODUCTS ARE PROPOSED FOR USE, THE BIDDER SHALL, PRIOR TO BID OPENING, SUBMIT 4 COPIES OF SHOP DRAWINGS OR CATALOG CUTS FOR APPROVAL. SUBSTITUTIONS AFTER RECEIPT OF APPROVED SUBMITTALS SHALL NOT BE PERMITTED

UNLESS APPROVED IN WRITING BY THE COTR.)

E. FIRE ALARM, TELECOMMUNICATIONS, CABLE TELEVISION, AND FURNITURE SYSTEMS SHOP DRAWINGS (OBTAIN DRAWINGS

FROM COTR CONTRACTED VENDORS) ARE A PART OF THE CONTRACT DOCUMENTS.

F. MAINTAIN A SET OF CONTRACT DRAWINGS AT THE JOB SITE MARKING THEM TO SHOW VARIATIONS BETWEEN CONSTRUCTION ACTUALLY PROVIDED AND THAT INDICATED ON CONTRACT DOCUMENTS. PRIOR TO FINAL INSPECTION, TRANSFER THESE DATA

AND SUBMIT 1 SET OF CLEAN RECORD DRAWINGS TO THE COTR.

G. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY AND HAVE NOT BEEN VERIFIED BY THE ENGINEER OR HIS REPRESENTATIVE. VISIT THE JOB SITE AND BECOME AWARE OF EXISTING CONDITIONS. CONTRACTOR SHALL DETERMINE THE EXACT CONDITION OF EXISTING WIRING BEFORE COMMENCING WORK, AND SHALL BE RESPONSIBLE FOR ANY DAMAGE

CAUSED BY THE CONTRACTOR'S FAILURE TO LOCATE AND PRESERVE CONDITIONS.

H. THE ELECTRICAL INSTALLATION SHALL BE GUARANTEED FOR ONE YEAR AFTER ACCEPTANCE BY SAO. WHEN NOTIFIED BY SAO OF FAILURE OF ANY PART OF THE INSTALLATION DURING THE GUARANTEE PERIOD, THE CONTRACTOR SHALL REPAIR OR

REPLACE THE DEFECTIVE PART AT HIS OWN EXPENSE TO THE SATISFACTION OF SAO.

I. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION.

J. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR SAFETY ON THE JOBSITE.

K. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT FOR TEMPORARY CONSTRUCTION POWER AS REQUIRED.

L. DRAWINGS ARE OF SMALL SCALE AND ARE SCHEMATIC. LOCATIONS OF EQUIPMENT AND SYSTEM ELEMENTS ARE

APPROXIMATE. RELOCATE ANY DEVICE WITHIN 10 FEET PRIOR TO INSTALLATION, WITHOUT ADDITIONAL COST, AT THE

DIRECTION OF THE COTR.

M. CONSULT THE ARCHITECTURAL, MECHANICAL, AND FIRE PROTECTION DRAWINGS FOR DETAILS NOT SHOWN ON THE ELECTRICAL AND FIRE ALARM DRAWINGS. ANY CONFLICTS IN LOCATING EQUIPMENT SHALL BE BROUGHT TO THE COTR'S ATTENTION FOR RESOLUTION. IF DIRECTED BY THE COTR, THE CONTRACTOR SHALL MAKE REASONABLE MODIFICATION TO THE LAYOUT OF EQUIPMENT TO PREVENT CONFLICT WITH OTHER TRADES OR FOR THE PROPER EXECUTION OF THE WORK AT

NO EXTRA COST.

N. INSTALLATION AND WORKMANSHIP:

1. INSTALLATION SHALL CONFORM TO SEISMIC DESIGN REQUIREMENTS OF CHAPTER 16 OF THE 2021 INTERNATIONAL

BUILDING CODE. PROVIDE SEISMIC BRACING FOR WALL MOUNTED ENCLOSURES, LUMINAIRES, AND OTHER ELECTRICAL

EQUIPMENT.

2. COORDINATE OUTAGES ON ELECTRICAL SYSTEM IN WRITING WITH THE COTR 14 DAYS BEFORE DESIRED OUTAGE DATE.

OUTAGES SHALL BE KEPT TO A MINIMUM IN DURATION AND QUANTITY. OUTAGES WILL BE GRANTED AT THE SOLE

CONVENIENCE OF BUILDING MANAGEMENT.

3. WORK SHALL BE NEATLY EXECUTED, WORKMANLIKE IN APPEARANCE, SYMMETRICAL, PLUMB, UNIFORM, PROPERLY

ALIGNED AND SECURED IN PLACE.

4. LAY OUT WORK IN ADVANCE. EXERCISE CARE WHERE CUTTING, CHANNELING, CHASING OR DRILLING FLOORS, WALLS, PARTITIONS, CEILINGS, OR OTHER SURFACES. FLOOR PENETRATIONS SHALL BE ACCOMPLISHED BY A LICENSED CORING CONTRACTOR. CONCRETE FLOOR SLABS SHALL BE X-RAYED BEFORE ANY CORING. REPAIR DAMAGE TO BUILDINGS, PIPING, AND EQUIPMENT USING SKILLED CRAFTSMEN OF TRADES INVOLVED. CUTTING, REPAIRS AND REFINISHING SHALL

BE SUBJECT TO THE APPROVAL OF THE COTR.

5. FASTEN TO CONCRETE WITH EXPANSION BOLTS OR CONCRETE INSERTS; TO WOOD WITH WOOD SCREWS; AND TO LIGHT

STEEL CONSTRUCTION WITH SHEET METAL SCREWS.

6. VERIFY LOCATIONS OF FLOOR PENETRATIONS, IF ANY REQUIRED, AND OUTLET LOCATIONS IN RELATION TO STRUCTURAL AND OTHER ELEMENTS. NOTIFY THE COTR IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING WITH ANY WORK.

7. REPAIR, PATCH, AND PAINT EXISTING CEILINGS AND WALLS AFFECTED BY ELECTRICAL WORK NOT COVERED BY GENERAL

CONTRACTOR.

E. WIRING METHOD:

1. USE ELECTRICAL METALLIC TUBING IN CONCEALED LOCATIONS AND SURFACE METAL RACEWAY IN EXPOSED LOCATIONS

AS INSTRUCTED BY THE COTR. INSTALL RACEWAY PARALLEL WITH OR AT RIGHT ANGLES TO CEILINGS, WALLS, AND

STRUCTURAL MEMBERS.

2. PROVIDE FLEXIBLE CONNECTION FOR EQUIPMENT SUBJECT TO VIBRATION AND LUMINAIRES MOUNTED ON ACCESSIBLE

CEILING PANELS OR GRID.

3. FIRE ALARM WIRING WILL BE IN CONDUIT SYSTEM. JUNCTION BOXES SHALL BE SPRAYED RED AND LABELED “FIRE ALARM”.

4. CONDUCTORS FOR 20 AMPERE BRANCH CIRCUITS OF 120 VOLTS MORE THAN 100 FEET LONG FROM PANEL TO CENTER OF

LOAD SHALL NOT BE SMALLER THAN NO. 10.

5. MULTI-WIRE BRANCH CIRCUITS: COMBINE UP TO THREE (3) 20A, 1 POLE BRANCH CIRCUITS IN A SINGLE CONDUIT HOMERUN.

SHARED NEUTRALS ARE NOT ALLOWED.

6. TELEPHONE AND DATA RACEWAY INSTALLATION SHALL BE IN ACCORDANCE WITH EIA/TIA 569.

7. BONDING. ALL METAL COMPONENTS SHALL BE BONDED TO PROVIDE A CONTINUOUS CONDUCTING PATH BACK TO THE

SERVICE GROUND OR DERIVED SYSTEM GROUND.

8. A GREEN EQUIPMENT GROUND CONDUCTOR, SIZED PER NEC TABLE 250-122, SHALL BE RUN WITH THE CONDUCTORS FOR

EACH FEEDER AND BRANCH CIRCUIT. CONDUIT ALONE AS EQUIPMENT GROUND CONDUCTOR IS NOT ACCEPTABLE.

9. PROVIDE AND INSTALL ALL JUNCTION BOXES AND PULL BOXES REQUIRED FOR INSTALLATION OF ELECTRICAL DEVICES AND

EQUIPMENT, WHETHER OR NOT SPECIFICALLY INDICATED ON THE PLANS. SIZING OF BOXES SHALL BE PER NEC.

10. LABEL ALL JUNCTION BOXES AND PULL BOXES INDICATION PANEL NAME AND CIRCUIT NUMBERS OF ALL BRANCH CIRCUIT

CONDUCTORS CONTAINED WITHIN THE BOX. INSTALL PULLSTRING (PLASTIC HAVING MINIMUM 200 POUND TENSILE

STRENGTH) IN EMPTY CONDUITS IN WHICH WIRE IS TO BE INSTALLED BY OTHERS.

F. PAINT ALL NEW CONDUITS, JUNCTION BOXES, AND PULL BOXES TO MATCH ADJACENT SURFACES.

G. SEAL OPENINGS AROUND NEW ELECTRICAL PENETRATIONS THROUGH FIRE RESISTANCE-RATED WALLS, PARTITIONS, FLOORS, OR CEILINGS TO MAINTAIN FIRE RESISTIVE INTEGRITY. WHERE AN EXISTING PENETRATION IS USED, SEAL PENETRATION

AFTER WORK IS COMPLETED.

H. COORDINATE ELECTRICAL WORK WITH OTHER TRADES AND WITH COTR.

I. FASTEN NAMEPLATES TO THE DEVICE WITH A MINIMUM OF TWO SHEETMETAL SCREWS OR TWO RIVETS.

J. PERFORM AN OPERATIONAL TEST AFTER COMPLETING THE INSTALLATION TO ASSURE PROPER OPERATION OF ITEMS OF THE

WORK.

K. CLEAN UP DEBRIS AT END OF EACH DAYS WORK. REMOVE MARKINGS FROM ELECTRICAL EQUIPMENT AND DEVICES.

DUCT SMOKE DETECTOR, ADDRESSABLE, PHOTOELECTRIC

FIRE SMOKE DAMPERF/SD F/SD F/SD

FSP FIRE SUPPRESSION PANEL, FURNISHED BY OTHERS, ELECTRICAL CONNECTION

BY ELECTRICAL CONTRACTOR

FSP FSP

CONDUIT RISER UP/DOWN/ / /

END OF LINE RESISTOREOLEOLEOL

FLOW SWITCH, INSTALLED BY SPRINKLER CONTRACTOR, FIRE ALARM CONNECTION

BY ELECTRICAL CONTRACTOR

TAMPER SWITCH, INSTALLED BY SPRINKLER CONTRACTOR, FIRE ALARM

CONNECTION BY ELECTRICAL CONTRACTOR

FS

TS

FS

TS

FS

TS

FIRE ALARM REMOTE ANNUNCIATOR, +72" TO TOP OF ENCLOSUREFAA FAA FAA

WALL MOUNTED AIR SAMPLING TYPE SMOKE DETECTOR

A A A

RELOCATED(R)

CIRCUIT RATING (EXAMPLE: 3 POLES, 20 AMP INDICATED)3P20A

QUAD RECEPTACLE, GFCI TYPE, WITH WEATHERPROOF COVER +18" UNLESS

OTHERWISE NOTED

WPWP WP

CIRCUIT AND SWITCH ID DESIGNATION, (CIRCUIT '1', SWITCH ID 'a' INDICATED)1a

2 x 4 FLUORESCENT LUMINAIRE

2 x 4 FLUORESCENT LUMINAIRE WITH EMERGENCY BATTERY PACK

2 x 2 FLUORESCENT LUMINAIRE

2 x 2 FLUORESCENT LUMINAIRE WITH EMERGENCY BATTERY PACK

TRACK LIGHTING

ELECTRICAL LEGEND AND NOTES

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829 honolulu@wsp.com

PROPOSED SEQUENCE OF WORK

TO MINIMIZE THE DURATION OF OUTAGES TO THE FACILITY, REFER TO THE FOLLOWING PROPOSED SEQUENCE OF WORK.

COORDINATE SEQUENCE AND ALL OUTAGES WITH OTHER DISCIPLINES AND COTR. SUBMIT ALTERNATIVE PROPOSED SEQUENCES

OF WORK TO COTR FOR APPROVAL PRIOR TO COMMENCING WORK.

ELECTRICAL:

1. REPLACEMENT OF CONTROL BUILDING SUPPLY FANS, EXHAUST FANS, ELECTRIC DUCT HEATERS, AND AIR CONDITIONING

SYSTEMS.

A. INSTALL FEEDER FROM DISTRIBUTION PANEL DP TO NEW PANEL LPM LOCATION, TERMINATE WIRING IN CEILING.

B. WHEN MECHANICAL CONTRACTOR IS READY TO DEMOLISH EXISTING MECHANICAL EQUIPMENT ON MOTOR CONTROL

CENTER MCC-CB (SUPPLY FANS, EXHAUST FANS, ELECTRIC DUCT HEATERS), DEMOLISH EXISTING MCC-CB AND

CONNECTIONS TO CORRESPONDING EXISTING LOADS.

C. WHILE MECHANICAL CONTRACTOR IS INSTALLING NEW SUPPLY FANS, EXHAUST FANS, AND ELECTRIC DUCT HEATERS, INSTALL NEW PANEL LPM. EXTEND FEEDER FROM CEILING TO CONNECT TO NEW PANEL LPM.

D. INSTALL BRANCH CIRCUIT CONNECTIONS TO INITIAL MECHANICAL EQUIPMENT SERVING SERVER EQUIPMENT ROOM (FCU-1

AND ACCU-1) FROM CIRCUITS INDICATED ON PLAN.

E. WHEN MECHANICAL CONTRACTOR IS READY TO DEMOLISH EXISTING ACCU'S AND FCU'S, DEMOLISH EXISTING ELECTRICAL

CONNECTIONS TO ACCU'S AND FCU'S.

F. INSTALL CONNECTIONS FROM CIRCUITS INDICATED ON PLAN TO REMAINING NEW AIR CONDITIONING EQUIPMENT (ACCU-2, REMAINING FAN COIL UNITS, SUPPLY FANS, EXHAUST FANS, AND ELECTRIC DUCT HEATERS).

2. REPLACEMENT OF PACU WITH NEW CHILLERS AND AHU'S

A. EXISTING PACU WILL BE REMOVED AND RELOCATED TO PROVIDE TEMPORARY AIR CONDITIONING. WHEN MECHANICAL

CONTRACTOR IS READY TO REMOVE PACU, DE-ENERGIZE FEEDER FROM MAIN SWITCHBOARD TO PACU AND DISCONNECT

WIRING FROM EXISTING DISCONNECT SWITCH MOUNTED ON PACU.

B. PER MECHANICAL SEQUENCE OF WORK, THE CONTRACTOR WILL HAVE A MAXIMUM OF FOUR CALENDAR WEEKS TO RELOCATE, RECONNECT, AND STARTUP PACU FOR TEMPORARY OPERATION. DURING THOSE FOUR CALENDAR WEEKS:

1) INTERCEPT EXISTING FEEDER TO EXISTING PULLBOX AT PACU WITH NEW PULLBOX. REMOVE EXISTING PULLBOX AT

PACU AND CORRESPONDING FEEDER WIRING BETWEEN NEW AND EXISTING PULLBOXES.

2) TAP EXISTING FEEDER WIRING AT NEW PULLBOX AND INSTALL NEW FEEDER CONDUIT AND WIRING FROM NEW

PULLBOX TO TEMPORARY PACU LOCATION.

3) INSTALL PANEL DM. TAP EXISTING FEEDER SERVING PACU AT NEW PULLBOX TO FEED PANEL DM. MAINTAIN PANEL DM

MAIN BREAKER IN THE 'OFF' POSITION. ALL BRANCH CIRCUIT BREAKERS SHALL BE MAINTAINED IN THE 'OFF' POSITION

AND DE-ENERGIZED UNTIL BRANCH CIRCUIT LOADS ARE READY TO BE ENERGIZED.

4) AFTER PACU HAS BEEN RELOCATED, CONNECT NEW FEEDER TO EXISTING DISCONNECT SWITCH MOUNTED ON PACU.

5) WHEN PACU IS READY FOR TEMPORARY OPERATION, RE-ENERGIZE FEEDER FROM MAIN SWITCHBOARD TO PACU.

C. WHILE PANEL DM IS STILL DE-ENERGIZED (MAIN BREAKER IS STILL 'OFF'), INSTALL BRANCH CIRCUIT CONNECTIONS TO NEW

MECHANICAL EQUIPMENT (AHU AND CHILLERS).

D. AFTER NEW MECHANICAL EQUIPMENT ARE INSTALLED AND READY FOR OPERATION, FIRST DE-ENERGIZE PACU, THEN SWITCH PANEL DM MAIN BREAKER AND CORRESPONDING BRANCH CIRCUIT BREAKERS TO THE 'ON' POSITION TO

ENERGIZE NEW MECHANICAL EQUIPMENT.

E. WHEN MECHANICAL CONTRACTOR IS READY TO REMOVE PACU, REMOVE TEMPORARY FEEDER CONDUIT AND WIRING SERVING PACU (FROM NEW PULLBOX TO PACU). MAINTAIN EXISTING FEEDER FROM MAIN SWITCHBOARD TO SERVE PANEL

DM.

FIRE ALARM:

1. INSTALL NEW FACP, ANNUNCIATOR PANEL, INITIATING AND NOTIFICATION APPLIANCES, AND FSP RELAY MODULES.

2. INSTALL NEW TELEPHONE AND DATA LINES TO CONNECT FIRE ALARM SYSTEM TO EXISTING TELEPHONE AND COMPUTER

SYSTEM, AND PROGRAM NEW FIRE ALARM SYSTEM FOR REMOTE MONITORING.

3. PRIOR TO DISCONNECTING EXISTING FIRE ALARM SYSTEM FROM SHUNT TRIP BREAKERS AND EXISTING ANTENNA VESDA

SYSTEM, PERFORM INITIAL TESTS AND INSPECTIONS OF NEW FIRE ALARM SYSTEM PER SPECIFICATIONS.

4. AFTER NEW FIRE ALARM SYSTEM HAS BEEN TESTED AND APPROVED AND IS OPERATIONAL, CONNECT NEW FIRE ALARM

SYSTEM TO EXISTING SHUNT TRIP BREAKERS AND EXISTING ANTENNA VESDA SYSTEM.

5. PERFORM FINAL TESTS AND INSPECTIONS OF NEW FIRE ALARM SYSTEM PER SPECIFICATIONS.

6. AFTER NEW FIRE ALARM SYSTEM HAS PASSED FINAL TESTS AND INSPECTIONS, COMPLETELY REMOVE EXISTING FIRE ALARM

SYSTEM INCLUDING, BUT NOT LIMITED TO, ALL PANELS, DEVICES, CONDUIT AND WIRING.

ELECTRICAL SEQUENCE OF WORK

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829

F G H IE

0.5

1.3

2.3

3.8

4.7

4.8

EEEE

EEEE

EEEE

(E)TO CIRCUIT

ON PANEL LP2

E

E

(E)VAV-2

(E)VAV-1

(E)MOTORIZED

DAMPER, TYP

EEEE

E E E E E

NORTH

ELECTRICAL DEMO PLAN - BASEMENT

FLOOR

0 2' 4' 8'

GRAPHIC SCALE

1/4" = 1'-0"

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829 honolulu@wsp.com

1/4" = 1'-0"

ELECTRICAL DEMO PLAN - BASEMENT FLOOR1

GENERAL NOTES:

A. COORDINATE ALL OUTAGES WITH COTR PRIOR TO COMMENCING WORK. SEE

PROPOSED SEQUENCE OF WORK ON SHEET E002 AND COORDINATE SEQUENCE

WITH OTHER DISCIPLINES AND WITH COTR.

SHEET NOTES:

VERIFY EXISTING CIRCUIT FEEDING EQUIPMENT. MAINTAIN EXISTING ELECTRICAL

CONNECTION, CONDUIT, AND WIRING.

MOTORIZED DAMPERS AND CORRESPONDING WIRING TO BE REMOVED BY OTHERS.

COORDINATE WITH MECHANICAL CONTRACTOR.

EXISTING VAV TO REMAIN. WIRING TO BE REMOVED BY OTHERS, COORDINATE WITH

MECHANICAL CONTRACTOR.

(E)MAIN

SWITCHBOARD

MSB WITH ATS

E E

E

E

E

E E E

TO DISTRIBUTION

SWITCHBOARD DSB

(E)PACU

(E)RAD-7

LP2-17,19

MCC-CB,

UNIT 1C

MCC-CB,

UNIT 1E

(E)SUPPLY

FAN SF-1

(E)ELECTRIC DUCT

HEATER EDH-1

MCC-CB,

UNIT 1B

(E)EXHAUST

FAN EF-1

(E)2"C, 4#3/0, 1#4 GND

(E)DISTRIBUTION

SWITCHBOARD

DSB

(E)ACCU 1

(E)PANEL FP

(E)PANEL LP1

LP6-32,34,36

LP5-25,27

(E)MOTOR CONTROL

CENTER MCC-CB

(E)PANEL LP2

JJ

(E)DIST PNL DP

LP1-1 LP1-1

LP1-1LP1-1

LP1-5

LP1-5

LP1-5

LP2-3 LP2-3

LP2-1LP2-1

LP2-3LP2-3

LP2-3 LP2-3

(E)PANEL D1

(E)PANEL LP

(E)PANEL "LP7"

(E)3/4"C, 2#12 FOR

SHUNT TRIP TO

EXSITING FACP

E E

E

E

(E)RAD-1

LP1-9,11

(E)RAD-4

LP2-5,7

(E)RAD-5

LP2-9,11

(E)RAD-6

(DISCONNECTED)

TYP

TYP

TYP

TYP

TYP

TYP

0 2' 4' 8'

GRAPHIC SCALE

1/4" = 1'-0"

NORTH

ELECTRICAL DEMO PLAN - GROUND FLOOR

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829 honolulu@wsp.com

GENERAL NOTES:

A. COORDINATE ALL OUTAGES WITH COTR PRIOR TO COMMENCING WORK. SEE PROPOSED SEQUENCE OF WORK ON SHEET E002 AND

COORDINATE SEQUENCE WITH OTHER DISCIPLINES AND WITH COTR.

SHEET NOTES:

VERIFY EXISTING CIRCUIT FEEDING EQUIPMENT. DEMOLISH EXISTING ELECTRICAL CONNECTION, CONDUIT, AND WIRING.

DEMOLISH EXISTING ELECTRICAL CONNECTION, MECHANICAL EQUIPMENT TO BE REMOVED AND STORED FOR RELOCATION BY OTHERS.

DEMOLISH EXISTING MCC-CB, MAINTAIN EXISTING FEEDER FROM DSB AND MAINTAIN EXISTING FEEDER TO ROLL-UP DOOR.

REMOVE EXISTING SHUNT TRIP WIRING, ABANDON EXISTING CONDUIT.

REMOVE AND STORE EXISTING LIGHT FIXTURES TO ACCOMMODATE DEMOLITION OF CEILING AND MECHANICAL WORK. MAINTAIN

EXISTING WIRING FOR RECONNECTION OF LIGHT FIXTURES IN NEW WORK.

DISCONNECT ELECTRICAL CONNECTION TO RADIANT HEATER TO ACCOMMODATE DEMOLITION OF CEILING AND MECHANICAL WORK.

MAINTAIN EXISTING WIRING FOR RECONNECTION OF RADIANT HEATER IN NEW WORK. RADIANT HEATER TO BE REMOVED BY OTHERS, COORDINATE WITH MECHANICAL CONTRACTOR.

CUT EXISTING FEEDER CONDUIT AND WIRING TO PACU, TO BE INTERCEPTED BY NEW PULLBOX.

1/4" = 1'-0"

ELECTRICAL DEMO PLAN - GROUND FLOOR1

(E)PANEL LP5

E

(E)PANEL LP6

(E)PANEL LP4

E

E

E

E

E

E

E

LP5-21

MCC-CB,

UNIT 2B

MCC-CB,

UNIT 2D

MCC-CB,

UNIT 2A

(E)SUPPLY

FAN SF-2

(E)ELECTRIC DUCT

HEATER EDH-2

(E)SUPPLY

FAN SF-3

(E)EXHAUST

FAN EF-2

(E)FCU

(E)FCU

(E)FCU

(E)FCU

LP6-17,19

LP6-13,15

LP5-26,28

E

(E)ROLL-UP DOOR

MCC-CB,

UNIT 2G

LP4-1 LP4-1

LP4-7

LP5-1 LP5-1 LP6-1 LP6-1

LP6-1LP6-1LP5-1

LP5-3

LP4-9

LP5-5

LP4-3

LP5-5 LP5-5LP5-5

2 2

E E E

EE

(E)RAD-15

LP4-20,22

5 (E)RAD-8

LP5-7,9

5 (E)RAD-9

LP6-5,7

(E)RAD-11

LP6-9,11

(E)RAD-10

LP5-11,13

TYP

TYP

TYP

TYP

TYP

0 2' 4' 8'

GRAPHIC SCALE

1/4" = 1'-0"

NORTH

ELECTRICAL DEMO PLAN - SECOND FLOOR

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829 honolulu@wsp.com

GENERAL NOTES:

A. COORDINATE ALL OUTAGES WITH COTR PRIOR TO COMMENCING WORK. SEE PROPOSED SEQUENCE OF WORK ON SHEET E002 AND

COORDINATE SEQUENCE WITH OTHER DISCIPLINES AND WITH COTR.

SHEET NOTES:

VERIFY EXISTING CIRCUIT FEEDING EQUIPMENT. DEMOLISH EXISTING ELECTRICAL CONNECTION, CONDUIT, AND WIRING.

VERIFY EXISTING CIRCUIT FEEDING TRACK LIGHT FIXTURES. REMOVE EXISTING FIXTURE AND CORRESPONDING CONDUIT AND WIRING.

MAINTAIN EXISTING ROLL-UP DOOR CONNECTION, DISCONNECT, AND MOTOR CONTROLLER. MAINTAIN EXISTING FEEDER FROM

MCC-CB.

REMOVE AND STORE EXISTING LIGHT FIXTURES TO ACCOMMODATE DEMOLITION OF CEILING AND MECHANICAL WORK. MAINTAIN

EXISTING WIRING FOR RECONNECTION OF LIGHT FIXTURES IN NEW WORK.

DISCONNECT ELECTRICAL CONNECTION TO RADIANT HEATER TO ACCOMMODATE DEMOLITION OF CEILING AND MECHANICAL WORK.

MAINTAIN EXISTING WIRING FOR RECONNECTION OF RADIANT HEATER IN NEW WORK. RADIANT HEATER TO BE REMOVED BY OTHERS, COORDINATE WITH MECHANICAL CONTRACTOR.

1/4" = 1'-0"

ELECTRICAL DEMO PLAN - SECOND FLOOR1

1.3

2.3

3.8

4.7

4.8

EEEE

EEEE

EEEE

TU-4TU-3TU-2TU-1

TU-8TU-7TU-6TU-5

TU-12TU-11TU-10TU-9

E

E

(E)VAV-2

(E)VAV-1

(E)TO CIRCUIT

ON PANEL LP2

J

12"X12"X4"D JB,

VAV & TU 24V

POWER SUPPLY

E E E E

E E E E E

MOTORIZED

DAMPER, TYP

NORTH

ELECTRICAL PLAN - BASEMENT FLOOR

0 2' 4' 8'

GRAPHIC SCALE

1/4" = 1'-0"

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829 honolulu@wsp.com

GENERAL NOTES:

A. COORDINATE ALL OUTAGES WITH COTR PRIOR TO COMMENCING WORK. SEE

PROPOSED SEQUENCE OF WORK ON SHEET E002 AND COORDINATE SEQUENCE

WITH OTHER DISCIPLINES AND WITH COTR.

SHEET NOTES:

INTERCEPT EXISTING WIRING WITH NEW PULLBOX. PROVIDE POWER SUPPLY

COMPATIBLE WITH NEW TU'S AND VAV'S. SEE MANUFACTURER INSTALLATION

INSTRUCTIONS AND CONSULT WITH MANUFACTURER FOR COMPATIBLE POWER

SUPPLIES. SIZE JB AS APPROPRIATE TO ACCOMMODATE POWER SUPPLY.

CONNECT NEW CONDUIT AND WIRING TO EXISTING VAV.

1/4" = 1'-0"

ELECTRICAL PLAN - BASEMENT FLOOR1

(E)MAIN

SWITCHBOARD

MSB WITH ATS

(E)PANEL LP2E

E

E

(E)PANEL FP

E

AHU-1

480V, 3PH, 71MCA

3P100A DS, NEMA 4X

RAD-7

LP2-17,19

SF-1

120V, 1PH, 3/4HP

1P20A DS, NEMA 1

(E)DISTRIBUTION

SWITCHBOARD

DSB

ACCU-2

208V, 1PH, 36.3MCA

2P60A DS, NEMA 4X

E E

CH-2

480V, 3PH, 61.5MCA

3P100A DS, NEMA 4X

CH-1

480V, 3PH, 61.5MCA

3P100A DS, NEMA 4X

LPM-6,8

E

ACCU-1

208V, 1PH, 30MCA

2P60A DS, NEMA 4X

LPM-5,7

E

EDH-1

120V, 1PH, 3.75KW

1P60A DS, NEMA 1

LPM-1,3

PANEL DM

(R)

DM-7,9,11

DM-2,4,6

DM-1,3,5

LPM-2,10,12

TO DISTRIBUTION

SWITCHBOARD DSB

J

WP

PANEL LPM

(E)DIST PNL DP

TO DIST

PNL DP

LP1-1 LP1-1

LP1-1LP1-1

LP1-5

LP1-5

LP1-5

LP2-3 LP2-3

LP2-1LP2-1

LP2-3LP2-3

LP2-3 LP2-3

ECB-RU 5

(E)2"C, 4#3/0, 1#4 GND

(E)PANEL D1

(E)PANEL LP

(E)PANEL "LP7"

(E)PANEL LP1

E E

E

E

(E)RAD-1

LP1-9,11

(E)RAD-4

LP2-5,7

(E)RAD-5

LP2-9,11

(E)RAD-6

(DISCONNECTED)

TYP

TYP

TYP

TYP

TYP

WP

LPM-2

J 7

LPM-4

J

PARTICULATE

MONITOR, PM-1

J

E

DDC CONTROL

PANEL

HEAT TRACE

0 2' 4' 8'

GRAPHIC SCALE

1/4" = 1'-0"

NORTH

ELECTRICAL PLAN - GROUND FLOOR

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829 honolulu@wsp.com

GENERAL NOTES:

A. COORDINATE ALL OUTAGES WITH COTR PRIOR TO COMMENCING WORK. SEE PROPOSED SEQUENCE OF WORK ON SHEET E002 AND

COORDINATE SEQUENCE WITH OTHER DISCIPLINES AND WITH COTR.

SHEET NOTES:

INSTALL PANEL DM, CONNECT TO EXISTING FEEDER TO PACU VIA NEARBY PULLBOX. PANEL DM SHALL REMAIN DE-ENERGIZED UNTIL

EXISTING PACU IS DISCONNECTED AND DEMOLISHED.

CONNECT TO FACTORY-MOUNTED DISCONNECT SWITCH, PROVIDED BY OTHERS. CONFIRM LOCATION OF DISCONNECT SWITCH PRIOR

TO ROUGH-IN.

CONFIRM WITH AHU MANUFACTURER IF ACCEPTABLE TO MOUNT SERVICE RECEPTACLE TO SURFACE OF EQUIPMENT. OTHERWISE, INSTALL UNISTRUT FRAME TO MOUNT SERVICE RECEPTACLE.

INSTALL FEEDER TO NEW PANEL LPM PRIOR TO DEMOLITION OF MCC-CB AND TERMINATE IN CEILING. INSTALL PANEL LPM AND EXTEND

FEEDER DOWN TO PANEL.

1/4" = 1'-0"

ELECTRICAL PLAN - GROUND FLOOR1

EXTEND EXISTING FEEDER REMAINING FROM DEMOLITION TO NEW ENCLOSED CIRCUIT BREAKER ECB-RU, CONDUIT AND WIRING SIZE TO MATCH EXISTING. CONNECT ECB-RU TO EXISTING FEEDER TO ROLL-UP DOOR. SEE SHEET E103 FOR CONTINUATION.

AFTER COMPLETION OF MECHANICAL WORK AND DURING REINSTALLATION OF CEILING, REINSTALL EXISTING LIGHT FIXTURES AND RECONNECT RADIANT HEATERS REMAINING FROM DEMOLITION. RECONNECT TO EXISTING WIRING REMAINING FROM DEMOLITION.

INSTALL JUNCTION BOX CONCEALED IN CEILING FOR CONNECTION TO HEAT TRACE CONDUCTORS. INSTALL CONNECTION TO HEAT

TRACE PER MANUFACTURER INSTRUCTIONS.

PROVIDE POWER SUPPLY COMPATIBLE WITH PARTICULATE MONITOR. SEE MANUFACTURER INSTALLATION INSTRUCTIONS AND CONSULT WITH MANUFACTURER FOR COMPATIBLE POWER SUPPLIES. SIZE JB AS APPROPRIATE TO ACCOMMODATE POWER SUPPLY.

INTERCEPT EXISTING PACU FEEDER CONDUIT AND WIRING REMAINING FROM DEMOLITION WITH NEW 24"X24"X12" PULLBOX.

(E)PANEL LP6

(E)PANEL LP4

E

E

FCU-2C

208V, 1PH, 0.79MCA

2P30A DS, NEMA 1

FCU-2A

208V, 1PH, 0.60MCA

2P30A DS, NEMA 1

E

FCU-1

208V, 3PH, 3HP

3P30A DS, NEMA 1

ESF-2

120V, 1PH, 3/4HP

1P20A DS, NEMA 1

E

LP5-19,21

EDH-2

120V, 1PH, 3.75KW

1P60A DS, NEMA 1

LP6-31,33,35

E

LP4-13DDC CONTROL

PANEL

E

LP6-17,19

FCU-2B

208V, 1PH, 0.60MCA

2P30A DS, NEMA 1

E

TO ECB-RU

(E)ROLL-UP DOOR

LP4-1 LP4-1

LP4-7

LP5-1 LP5-1 LP6-1 LP6-1

LP6-1LP6-1LP5-1

LP4-9

LP5-5

LP4-3

LP5-5 LP5-5LP5-5

LP5-3

(E)PANEL LP5

E E E

EE

(E)RAD-15

LP4-20,22

3 (E)RAD-8

LP5-7,9

3 (E)RAD-9

LP6-5,7

(E)RAD-11

LP6-9,11

(E)RAD-10

LP5-11,13

TYP

TYP

TYP

TYP

TYP

J

LP6-15

J

LP6-13

E

LP5-25,27

HEAT TRACE

HEAT TRACE

0 2' 4' 8'

GRAPHIC SCALE

1/4" = 1'-0"

NORTH

ELECTRICAL PLAN - SECOND FLOOR

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829 honolulu@wsp.com

GENERAL NOTES:

A. COORDINATE ALL OUTAGES WITH COTR PRIOR TO COMMENCING WORK. SEE PROPOSED SEQUENCE OF WORK ON SHEET E002 AND

COORDINATE SEQUENCE WITH OTHER DISCIPLINES AND WITH COTR.

SHEET NOTES:

AFTER COMPLETION OF MECHANICAL WORK AND DURING REINSTALLATION OF CEILING, REINSTALL EXISTING LIGHT FIXTURES REMAINING FROM DEMOLITION. RECONNECT TO EXISTING WIRING REMAINING FROM DEMOLITION.

EXISTING FEEDER FROM NEW ECB-RU, SEE SHEET E102 FOR CONTINUATION.

AFTER COMPLETION OF MECHANICAL WORK AND DURING REINSTALLATION OF CEILING, REINSTALL RADIANT HEATERS REMAINING

FROM DEMOLITION. RECONNECT TO EXISTING WIRING REMAINING FROM DEMOLITION.

INSTALL JUNCTION BOX CONCEALED IN CEILING FOR CONNECTION TO HEAT TRACE CONDUCTORS. INSTALL CONNECTION TO HEAT

TRACE PER MANUFACTURER INSTRUCTIONS.

1/4" = 1'-0"

ELECTRICAL PLAN - SECOND FLOOR1

DISTRIBUTION SWITCHBOARD - DSB

480V, 3PH, 3W, 60HZ, 1200A MAIN, GND BUS, 65KA SC BRACING

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21, 22 23 24

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P110AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

250AF

GFI

3P30AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P150AT

250AF

GFI

3P250A

NON-GFI

3P110AT

250AF

GFI

3P110AT

250AF

GFI

3P50A

NON-GFI

3P80AT

150AF

NON-GFI

C2

/K

3 [ 3#

6 W /G

ND

C2

/K

2 [ 3#

6 W /G

ND

C2

/K

1 [ 3#

6 W /G

ND

C2

/K

5 [ 3#

6 W /G

ND

CT

C2

/K

8 [ 3#

2 W /G

ND

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

EH

H1

C2

/K

4 [ 3#

6 W /G

ND

C2

/K

8 [ 3#

6 W /G

ND

C2

/K

7 [ 3#

6 W /G

ND

IF

A

FE

ED

ER

KV

A

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

3# 6 &

1# 8 G

ND

C2

/K

1 [ 3#

0 K

CM

IL

W /G

ND

K2

[3 #3

/0 W

/G

ND

1-

3/C #6

1#

8 G

ND

C2

/K

6 [ 3#

6 W /G

ND

1- 3/C

#6

1# 8 G

ND

C2

/K

4 [ 3#

0K

CM

IL

W /G

ND

3P60A

K2

[3 #4

/0 W

/G

ND

3# 6 &

1# 8 G

ND C2

/K

9 [ 3#

3/0 W

/G

ND

K2

[3

#6 W

/G

ND

EHH11

3# 6 &

1# 8 G

ND

3P60A

PA

D

9 &

RE

CE

PT

AC

LE

S

3# 6 &

1# 8 G

ND

PA

D

RE

CE

PT

AC

LE

C2

/K

3 [ 3#

2 W /G

ND

3P60A 3P60A

3# 6 &

1# 8 G

ND

3/C #6

1#

8 G

ND

3# 6 &

1# 8 G

NDC2

/K

6 [ 3#

0 K

CM

IL

W /G

ND

C2

/K

9 [ 3#

0K

CM

IL

W /G

ND

C2

/K

1 [ 3#

0K

CM

IL

W /G

ND

K2

[3 #4

/0 W

/G

ND

K2

[3 #3

/0 W

/G

ND

3P60A

K2

[3 #1

/0 W

/G

ND

PA

D

RE

CE

PT

AC

LE

S

PA

D

RE

CE

PT

AC

LE

S

PA

D

RE

CE

PT

AC

LE

S

3# 6 &

1# 8 G

ND

3# 6 &

1# 8 G

ND

C2

/K

3 [ 3#

6 W /G

ND

C2

/K

[3#

3/0 W

/G

ND

K2

[3

#1 /0

W /G

ND

3/# 6 &

1# 8 G

ND

3P60A

PA

D

RE

CE

PT

AC

LE

S

3# 6 &

1# 8 G

ND

3P500A

2 1/2(64)C, 3#250

KCMIL & 1#2 GND

TR1

150KVA

480V- 208Y/120V

2 SETS - 3"(76)C,

4#350 KCMIL,

2#2 GND

2"(51)C, 4#3/0, 1#4 GND

MC

C-

CB

SE

E

SH

T

ED

NEW GEN JB

IN-LINE SPLICE

CONTROL

PNL

100%

3P1600AF

1200AT

EMERGENCY GENERATOR

800KW, 1000KVA, 0.8PF,

480/277V,3PH, 3W, 1800 RPM

GFI PROTECTION: INTEGRAL WITHIN GENERATOR

DERATING FACTORS:

ALTITUDE: 70.0% x 800KW = 561KW, 701KVA FUEL: 93.7% x 561KW = 518KW, 648KVA

2"(51)C, 3#4/0 &

1#2 GND

1 1/4"(32)C, 3#2 &

1#6 GND

3/4"(19)C, 2#12

TO FACP

3/4"(19)C, 3#12

& 1#12 GND

MILLING MACHINE

4 KVA,3PH,480V

1#8 GND, BOND TO

BLDG. STRUCTURE

PANEL D1

2 SETS - 3-600 KCMIL

HELCO 12.47KV

UG DISTRIBUTION

PRIMARY WIRING

BY HELCO IN 2-5"(127)C

HELCO TRANSFORMER

750KVA (660KVA AT ALTITUDE)

12.47KV-480Y/277V, 5.75%Z

3-4"(102)C, SERVICE ENTRANCE

CONDUCTORS BY HELCO

PT'S

CT'S

HELCO

KWH METER

GFI 100%

RATED

3P1000A

3P1200A

ATS

3P175AT

GFI

3P125AT

GFI

3P250AT

ST/GFI

MAIN SWITCHBOARD MSB

SECTION 3, DISTRIBUTION

PACU

BRIDGE CRANE

TROLLEY DUCT

SLEEVES

1"(25)C, CONTROLS

4"(102)C, POWER

4"(102)C WITH ATS/GENERATOR CONTROL WIRES

3 SETS - 4"(102)C,

3-750 KCMIL & 1#3/0 GND

GENERATOR ROOM PIT

3 SETS -

4"(102)C, 3-750 KCMIL

& 1#3/0 GND

480Y/277V, 3PH, 4W

, 60HZ, 1200A

PF

B

PA

D

RE

CE

PT

AC

LE

TR3

30KVA

480V-208Y/120V

52C, 4#2, 1#6 GND

3P500A

3P100A 3P150A 3P200A 3P50A 3P125A

3/4"(19)C, 2#12

2P40A

DISTRIBUTION PANELBOARD (PANEL DP)

208Y/120V, 3PH, 4W, 600A MAINS, EQPT GND BUS, ISOLATED GROUND, 42KA SC BRACING

3/4"C, 3#6, 1#8 GND

PANEL FP

120/208V, 1 PH, 3W, 100A, GND BUS

1P20A 1P20A 1P20A 1P20A

FACP AT

MODULE 5

1 1 /4"

(3 2)

C, 4#

2, 2#

8 G

ND

1 1 /2"

(3 8)

C, 4#

1, 2#

8 G

ND

F 4P200A

3" (7

6) C, 4#

0 K

CM

IL,

2#

2 G

ND

1" (2

5) C, 4# 6, 2# 8 G

ND

1 1 /2"

(3 8)

C, 4#

1, 2#

8 G

ND

250A

NA

ST

J

PANEL LP1

AT MODULE 1

PANEL LP2

AT MODULE 2

PANEL LP3B

AT MODULE 3

PANEL LP3A

AT MODULE 3

PANEL LP4

AT MODULE 4

PANEL LP5

AT MODULE 5

PANEL LP6

AT MODULE 6

FA CONTROL

PANEL

TO INERT GAS

FIRE PROTECTION

PANELS 1 & 2

3/4"(19)C, 4#12

3P60A

TR2

75KVA

480V- 208Y/120V

2"(52)C, 4#3/0, 1#6 GND

3P175A

PA

NE

L L P

1"(25)C, 3#4, 1#8 GND

52C, 3#6, 1#8 GND

3/4"(19)C, 2#12 & 1#12 GND

INERT GAS

FP SYSTEM

PANEL FSP-1

3P125A

PA

NE

L

GE

N

3P60A PA

NE

L

LP

52C, 4#6, 1#8 GND

3P800AT

non-GFI

3 SETS -

5"(127)C, 3-750 KCMIL

& 1#2/0 GND

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

S

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

S

TO GENERATOR

ANNUNCIATOR

3P200A

3" (7

6) C, 4#

0 K

CM

IL,

2#

2 G

ND

52C, 3#6, 1#8 GND

2 SETS - 3"(76)C,

4#350 KCMIL,

2#2 GND

GENERAL NOTES:

A. COORDINATE ALL OUTAGES WITH COTR PRIOR TO COMMENCING WORK.

SEE PROPOSED SEQUENCE OF WORK ON SHEET E002 AND

COORDINATE SEQUENCE WITH OTHER DISCIPLINES AND WITH COTR.

B. UNIT MEASUREMENTS IN PARENTHESES ARE IN MILLIMETERS.

SHEET NOTES:

DISCONNECT EXISTING ELECTRICAL CONNECTION TO PACU IN

COORDINATION WITH WHEN MECHANICAL CONTRACTOR IS READY TO

REMOVE AND RELOCATE PACU.

DEMOLISH EXISTING ELECTRICAL POWER CONNECTION TO FIRE

SUPPRESSION PANEL. FIRE SUPPRESSION PANEL TO BE DEMOLISHED

BY OTHERS. SEE FIRE PROTECTION DRAWINGS FOR DETAILS AND

COORDINATE WITH FIRE PROTECTION CONTRACTOR.

REMOVE EXISTING SHUNT TRIP WIRING, ABANDON EXISTING CONDUIT.

DEMOLISH EXISTING CONNECTION TO MCC-CB, STUB EXISTING

CONDUIT AND MAINTAIN EXISTING WIRING.

PARTIALLY DEMOLISH EXISTING FEEDER TO PACU AND

CORRESPONDING PULLBOX, STUB EXISTING CONDUIT AND CUT

EXISTING WIRING.

PANEL V

AT VAULT

3P90A

ST

INERT GAS

FP SYSTEM

PANEL FSP-2

INERT GAS

FP SYSTEM

PANEL FSP-3

1P20A

VAULT FIKE

RELEASING

PANEL FSP-4

2 2 2 2

MAIN SWITCHBOARD

MSB SECTION 1, METER

UNINTERRUPTIBLE POWER SUPPLY

(INSTALLED UNDER SEPARATE PROJECT)

750KVA, 480/277V, 3PH, 3W, 65KAIC

DERATING FACTORS:

ALTITUDE: 84.0% x 750KVA = 630KVA

UPS

3 SETS - 4"(102)C,

3-500 KCMIL & 1#3/0 GND

G M ROTARY ENERGY

STORAGE SYSTEM

SYNCHRONOUS

MOTOR-GENERATOR

3 SETS - 4"(102)C,

3-500 KCMIL & 1#3/0 GND

MAIN SWITCHBOARD

MSB SECTION 2, ATS

3P1000A

3P1000A

MAINTENANCE BYPASS

(INSTALLED UNDER

SEPARATE PROJECT)

480/277V, 3PH, 3W, 1200A, 65KAIC

N.O.

N.C.

3P1000A

N.C.

24"X24"X12"D

PULLBOX

3"(78)C, 3-350KCM,

1#4 GND

M 3

2"(51)C, 4#3/0, 1#4 GND

NOT TO SCALE

ELECTRICAL SINGLE-LINE DIAGRAM - MAIN DEMO1

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829 honolulu@wsp.com

ELECTRICAL SINGLE-LINE

DIAGRAM - MAIN DEMO

3P150A

ST

BS

TO DISTRIBUTION

SWITCHBOARD,

SEE SHEET ED401

2"(51)C, 4#3/0, 1#4 GND

TO FA CONTROL PANEL

3/4"(19)C, 2#19

1A

1B 1C 1D 1E 1F 2A 2B 2C 2D 2E 2F 2G 2H 3A 3B 3C 3D 3E 3F

3P15A3P15A3P15A3P25A

3/4 "C

, 3 #1

1#

G

ND

3/4 "C

, 3 #1

1#

G

ND

J J

16KW 6KW

MCP MCP

3P7A

T 3P7A

T

3/4"C, 4#14

A/C-1

DDC

CONTROL

PANEL

SP

AC

E

SP

AC

E

SP

AC

E

SP

AC

E

J J

3P30A 3P30A

3/4 "C

, 3 #1

1#

G

ND

3/4 "C

, 3 #1

1#

G

ND

3/4 "C

, 3 #1

1#

G

ND

3P30A

SF

-4

SF

-3

SP

AC

E

RO

LL

-U P

DO

OR

3P30A3P30A3P30A3P30A

MCB

C

MCB

CH

O A

3P25A T

3P20A T

3P3A T

3P7A

T MCP MCP

3P70A

MCB

C

3P25A

TMCB

C

3P20A T

3P3A

T MCP

3P3A

T MCP

3/4 "C

, 3 #1

1#

G

ND

3/4 "C

, 3 #1

1#

G

ND

3/4 "C

, 3 #1

1#

G

ND

3/4 "C

, 3 #1

1#

G

ND

2 1

16KW11.4KW

ED

H-

ED

H-

ED

H-

HU

-2

EF

-3

SF

-2

SP

AC

E

ED

H-

HU

-1

SF

-1

EF

-1

3P30A3P30A3P30A3P30A

2 1

11.4KW

3/4 "C

, 3 #1

1#

G

ND

3/4 "C

, 3 #1

1#

G

ND

3/4 "C

, 3 #1

1#

G

ND

3/4 "C

, 3 #1

1#

G

ND

16KW

CONTROL

BUILDING

HVAC SYSTEM

MASTER

TIME

CLOCK

CABINET

1"C, 16#14

3/4 "C

2#

3/4 "C

2#

3/4 "C

2#

3/4 "C

2#

MCC-CB

480V, 3PH, 3W, 60HZ, 600A MAINS. GND BUS, 22KA SC BRACING

GENERAL NOTES:

A. COORDINATE ALL OUTAGES WITH COTR PRIOR TO COMMENCING WORK.

SEE PROPOSED SEQUENCE OF WORK ON SHEET E002 AND

COORDINATE SEQUENCE WITH OTHER DISCIPLINES AND WITH COTR.

B. UNIT MEASUREMENTS IN PARENTHESES ARE IN MILLIMETERS.

SHEET NOTES:

MAINTAIN EXISTING CONDUIT AND WIRING TO ROLL-UP DOOR.

3P30A 3P30A

H O A

H O A

H O A

H O A

H O A

H O A

H O A

H O A

H O A

NOT TO SCALE

ELECTRICAL SINGLE-LINE DIAGRAM - MCC-CB DEMO1

Smithsonian Facilities

Washington DC 20560 600 Maryland Avenue S.W. Suite 5001

Institution Smithsonian

WSP USA Buildings Inc.

1001 Bishop Street Suite 2400 Honolulu Hawaii 96813 USA

Telephone 808 536 1737 Facsimile 808 537 5829 honolulu@wsp.com

DIAGRAM - MCC-CB DEMO

DISTRIBUTION SWITCHBOARD - DSB

480V, 3PH, 3W, 60HZ, 1200A MAIN, GND BUS, 65KA SC BRACING

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P110AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

250AF

GFI

3P30AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P60AT

150AF

GFI

3P150AT

250AF

GFI

3P110AT

250AF

GFI

3P110AT

250AF

GFI

C2

/K

3 [ 3#

6 W /G

ND

C2

/K

2 [ 3#

6 W /G

ND

C2

/K

1 [ 3#

6 W /G

ND

C2

/K

5 [ 3#

6 W /G

ND

CT

C2

/K

8 [ 3#

2 W /G

ND

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

EH

H1

C2

/K

4 [ 3#

6 W /G

ND

C2

/K

8 [ 3#

6 W /G

ND

C2

/K

7 [ 3#

6 W /G

ND

IF

A

FE

ED

ER

KV

A

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

3# 6 &

1# 8 G

ND

C2

/K

1 [ 3#

0 K

CM

IL

W /G

ND

K2

[3 #3

/0 W

/G

ND

1-

3/C #6

1#

8 G

ND

C2

/K

6 [ 3#

6 W /G

ND

1- 3/C

#6

1# 8 G

ND

C2

/K

4 [ 3#

0K

CM

IL

W /G

ND

3P60A

K2

[3 #4

/0 W

/G

ND

3# 6 &

1# 8 G

ND C2

/K

9 [ 3#

3/0 W

/G

ND

K2

[3

#6 W

/G

ND

EHH11

3# 6 &

1# 8 G

ND

3P60A

PA

D

9 &

RE

CE

PT

AC

LE

S

3# 6 &

1# 8 G

ND

PA

D

RE

CE

PT

AC

LE

C2

/K

3 [ 3#

2 W /G

ND

3P60A 3P60A

3# 6 &

1# 8 G

ND

3/C #6

1#

8 G

ND

3# 6 &

1# 8 G

NDC2

/K

6 [ 3#

0 K

CM

IL

W /G

ND

C2

/K

9 [ 3#

0K

CM

IL

W /G

ND

C2

/K

1 [ 3#

0K

CM

IL

W /G

ND

K2

[3 #4

/0 W

/G

ND

K2

[3 #3

/0 W

/G

ND

3P60A

K2

[3 #1

/0 W

/G

ND

PA

D

RE

CE

PT

AC

LE

S

PA

D

RE

CE

PT

AC

LE

S

PA

D

RE

CE

PT

AC

LE

S

3# 6 &

1# 8 G

ND

3# 6 &

1# 8 G

ND

C2

/K

3 [ 3#

6 W /G

ND

C2

/K

[3#

3/0 W

/G

ND

K2

[3

#1 /0

W /G

ND

3/# 6 &

1# 8 G

ND

3P60A

PA

D

RE

CE

PT

AC

LE

S

3# 6 &

1# 8 G

ND

NEW GEN JB

IN-LINE SPLICE

CONTROL

PNL

100%

3P1600AF

1200AT

EMERGENCY GENERATOR

800KW, 1000KVA, 0.8PF,

480/277V,3PH, 3W, 1800 RPM

GFI PROTECTION: INTEGRAL WITHIN GENERATOR

DERATING FACTORS:

ALTITUDE: 70.0% x 800KW = 561KW, 701KVA FUEL: 93.7% x 561KW = 518KW, 648KVA

2"(51)C, 3#4/0 &

1#2 GND

1 1/4"(32)C, 3#2 &

1#6 GND

3/4"(19)C, 3#12

& 1#12 GND

MILLING MACHINE

4 KVA,3PH,480V

1#8 GND, BOND TO

BLDG. STRUCTURE

PANEL D1

2 SETS - 3-600 KCMIL

HELCO 12.47KV

UG DISTRIBUTION

PRIMARY WIRING

BY HELCO IN 2-5"(127)C

HELCO TRANSFORMER

750KVA (660KVA AT ALTITUDE)

12.47KV-480Y/277V, 5.75%Z

3-4"(102)C, SERVICE ENTRANCE

CONDUCTORS BY HELCO

MAIN SWITCHBOARD

MSB SECTION 1, METER

PT'S

CT'S

HELCO

KWH METER

GFI 100%

RATED

3P1000A

3P1200A

ATS

3P175AT

GFI

3P125AT

GFI

MAIN SWITCHBOARD MSB

SECTION 3, DISTRIBUTION

BRIDGE CRANE

TROLLEY DUCT

SLEEVES

1"(25)C, CONTROLS

4"(102)C, POWER

4"(102)C WITH ATS/GENERATOR CONTROL WIRES

3 SETS - 4"(102)C,

3-750 KCMIL & 1#3/0 GND

GENERATOR ROOM PIT

3 SETS -

4"(102)C, 3-750 KCMIL

& 1#3/0 GND

480Y/277V, 3PH, 4W

, 60HZ, 1200A

PA

D

RE

CE

PT

AC

LE

3P500A

3P100A 3P150A 3P200A 3P50A 3P125A

DISTRIBUTION PANELBOARD (PANEL DP)

208Y/120V, 3PH, 4W, 600A MAINS, EQPT GND BUS, ISOLATED GROUND, 42KA SC BRACING

3/4"C, 3#6, 1#8 GND

1 1 /4"

(3 2)

C, 4#

2, 2#

8 G

ND

3" (7

6) C, 4#

0 K

CM

IL,

2#

2 G

ND

1" (2

5) C, 4# 6, 2# 8 G

ND

1 1 /2"

(3 8)

C, 4#

1, 2#

8 G

ND

PANEL LP1

AT MODULE 1

PANEL LP3B

AT MODULE 3

PANEL LP3A PANEL LP4

AT MODULE 4

PANEL LP5

AT MODULE 5

PANEL LP6

AT MODULE 6

TO INERT GAS FIRE

PROTECTION PANEL

FSP-0 (BY OTHERS)

3P800AT

non-GFI

3 SETS -

5"(127)C, 3-750 KCMIL

& 1#2/0 GND

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

S

PA

D

RE

CE

PT

AC

LE

PA

D

RE

CE

PT

AC

LE

S

TO GENERATOR

ANNUNCIATOR

3P200A

3" (7

6) C, 4#

0 K

CM

IL,

2#

2 G

ND

20 21, 22 23 24

3P250A

NON-GFI

3P50A

NON-GFI

3P80AT

150AF

NON-GFI

3P500A

2 1/2(64)C, 3#250

KCMIL & 1#2 GND

TR1

150KVA

480V- 208Y/120V

2 SETS - 3"(76)C,

4#350 KCMIL,

2#2 GND

TR3

30KVA

480V-208Y/120V

52C, 4#2, 1#6 GND

3P60A

TR2

75KVA

480V- 208Y/120V

2"(52)C, 4#3/0, 1#6 GND

3P175A

PA

NE

L L P

1"(25)C, 3#4, 1#8 GND

52C, 3#6, 1#8 GND

3P125A

PA

NE

L

GE

N

3P60A PA

NE

L

LP

52C, 4#6, 1#8 GND

52C, 3#6, 1#8 GND

2 SETS - 3"(76)C,

4#350 KCMIL,

2#2 GND

3P250AT

ST/GFI

PANEL LP2

AT MODULE 2

PANEL V

AT VAULT

3P90A

ST

PANEL LP3C

3P100A

PANEL LPM

AT MODULE 2

1 1 /4"

(3 2)

C, 4#

2, 2#

8 G

ND

UNINTERRUPTIBLE POWER SUPPLY

(INSTALLED UNDER SEPARATE PROJECT)

750KVA, 480/277V, 3PH, 3W, 65KAIC

DERATING FACTORS:

ALTITUDE: 84.0% x 750KVA = 630KVA

UPS

3 SETS - 4"(102)C,

3-500 KCMIL & 1#3/0 GND

G M ROTARY ENERGY

STORAGE SYSTEM

SYNCHRONOUS

MOTOR-GENERATOR

3 SETS - 4"(102)C,

3-500 KCMIL & 1#3/0 GND

3P1000A

3P1000A

MAINTENANCE BYPASS

(INSTALLED UNDER

SEPARATE PROJECT)

480/277V, 3PH, 3W, 1200A, 65KAIC

N.O.

N.C.

3P1000A

N.C.

MAIN SWITCHBOARD

MSB SECTION 2, ATS

PANEL DM

24"X24"X12"D

PULLBOX

3(78)C, 3-350KCM,

1#4 GND

GENERAL NOTES:

A. COORDINATE ALL OUTAGES WITH COTR PRIOR TO COMMENCING WORK.

SEE PROPOSED SEQUENCE OF WORK ON SHEET E002 AND

COORDINATE SEQUENCE WITH OTHER DISCIPLINES AND WITH COTR.

B. UNIT MEASUREMENTS IN PARENTHESES ARE IN MILLIMETERS.

SHEET NOTES:

SHUNT TRIP BREAKER. WIRING CONNECTION TO SHUNT TRIP RELAY

AND FIRE SUPPRESSION PANEL BY OTHERS. SEE FIRE PROTECTION

DRAWINGS FOR MORE INFORMATION.

INTERCEPT EXISTING CONDUIT STUB REMAINING FROM DEMOLITION

WITH JUNCTION BOX AS REQUIRED, EXTEND CONDUIT AND WIRING TO

NEW ECB-RU.

INTERCEPT EXISTING CONDUIT STUB REMAINING FROM DEMOLITION

WITH PULLBOX. TAP WIRING IN NEW PULLBOX FOR PANEL DM AND

TEMPORARY PACU CONNECTION.

2P40A

PANEL FP

120/208V, 1 PH, 3W, 100A, GND BUS

1P20A 1P20A 1P20A 1P20A

3/4"(19)C, 2#12 & 1#12 GND

FACP AT

MODULE 2

INERT GAS

FP SYSTEM

PANEL FSP-0

FIRE ALARM

ANNUNCIATOR

PANEL

POWER

SUPPLY TO

ASSD, F/SD

3P200A

ST

1 1

TO INERT GAS FIRE

This is the start of the file's text. The full file is on GovTribe.