33330223RF0010026 Amendment 0002.pdf

PDF 9 MB Posted

Attached to
NMAH: Replace ACU’s for Collections Storage on 4th and 5th
Solicitation number
33330223RF0010026
Issued by

About this file

This Request for Proposal (RFP) solicits offers to replace air handling units (ACUs) serving collection storage spaces on the fourth and fifth floors of the Smithsonian Institution's National Museum of American History in Washington, DC. The scope of work includes removing existing ACUs from four mechanical equipment rooms and installing new air handling units (AHUs) to meet conservation standards for temperature and humidity control, along with providing temporary cooling systems throughout the construction period to maintain collection storage conditions. Offerors must demonstrate minimum qualifications, and technical and cost proposals will be evaluated per the criteria in the RFP. The fixed-price construction contract is estimated over $10 million, with a 570-calendar day period of performance from notice to proceed. Temporary cooling must be installed to support collection storage on the fifth floor from April 15 through October 31, 2024, utilizing rented or purchased rooftop units without freeze protection during that timeframe.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(x)

33330223RF0010026

x x

1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

OCON

Washington DC 20013-7012 PO Box 37012

MRC 1200

SMITHSONIAN INSTITUTION

2003112

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

06/05/2023

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of Contracting Officer)(Signature of person authorized to sign)

Willard B. Powell

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

Previous edition unusable

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

A. The Solicitation Number cited above, to replace ACU's for Collections Storage on 4th and

5th at the Smithsonian Institution's National Museum of American History, located in Washington, DC, is hereby amended as follows:

A.1. Attached hereto and made part of this Amendment Two are

SI Responses to RFI’s for Questions Number 1-26.

Addendum No. 1

Pre-Bid Site Walk Attendance Sheet

Continued ...

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or as heretofore changed,10A, remains unchanged and in full force and effect .

3. EFFECTIVE DATE

07/02/2023

ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

NAME OF OFFEROR OR CONTRACTOR

CONTINUATION SHEET

PAGE OF

(A) (B) (C) (D) (E) (F)

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

Sponsored by GSA

FAR (48 CFR) 53.110

REFERENCE NO. OF DOCUMENT BEING CONTINUED

33330223RF0010026/0002

A.2. Offerors shall acknowledge receipt of all amendments to this solicitation signed and dated and submit with proposal.

B. THE BID DUE DATE IS JULY 20, 2023, AT 3:00PM

EST.

Except as provided herein, all other provisions, terms and conditions of the Solicitation remain unchanged.

END OF AMENDMENT TWO

June 30, 2023 QUESTION # DATE RECEIVED REFERENCE DOCUMENT QUESTION DATE RESPONDED A/E RESPONSE RESPONSE BY

1 20-Jun-23 DRAWING ED-101

1. Question: Detail 1/ED-101 references removal notes 1, 2, 3 and 4; however, there is only one (1) Note listed at the bottom of the page. Please provide the removal notes.

26-Jun-23

Notes were accidentally cut off sheet when floor plans were combined, they will be shown on an Addend or or Conform set. Removal notes should read: i) Contractor shall trace and verify all existing-to-be removed circuits source serving the air handler units prior to any work. ii) Completely remove 120V power, Lighting serving air handling unit to be removed. iii) Completely remove existing air handling unit feeder back to paneled. iv) Remove existing fire alarm duct mounted smoke detectors and fire smoke relays (FSR) to allow for mechanical air handling unit and ductwork replacement. Safe-off fire alarm circuits at nearest J-Box for re-connection to new air handling unit. See new work electrical drawings for new duct mounted smoke detectors and FSR locations and quantities.

2 20-Jun-23 RFP

2. Question: RFP Part III – Plan of Accomplishment and Contract Time, section a.-4)-E, requires a written narrative addressing the “Procurement and installation of precast concrete panels.” There does not appear to be any work related to precast concrete panels included in the Contract Documents. Please confirm that this shall read the “Procurement and installation of mechanical equipment”.

26-Jun-23 We can confirm there is no precast concrete work required for the project.

3 20-Jun-23 RFP

3. Question: RFP Part III – Plan of Accomplishment and Contract Time, section b. - Implementation Plan requests a detailed plan that will deliver a superior quality product in the “Doors, Frames and Hardware” work. There does not appear to be any work related to doors, frames and Hardware included in the Contract Documents. Please confirm that this portion of the Implementation Plan is not applicable and should not be included.

26-Jun-23 We can confirm that no permanent changes to doors frames and hardware are described in the contract documents.

4 20-Jun-23 RFP

4. Question: RFP Part III – Plan of Accomplishment and Contract Time, section b. - Implementation Plan requests a detailed plan that will deliver a superior quality product in the “Security” work.

There does not appear to be any work related to permanent security system modifications included in the Contract Documents.

Please clarify the intent of this portion of the implementation plan.

26-Jun-23 We can confirm that no permanent changes to the security system are intended.

5 20-Jun-23 RFP

5. Question: RFP Part IV – Comparable Experience requests comparable projects “completed or in progress during the past five

(4) years.” Please clarify if comparable projects shall be from the past four or five years.

26-Jun-23 We would recommend that SI require references and qualifications for all subcontractors.

Comparable Experience requests comparable projects “completed or in progress during the past five (5) years.”

PRE-BID RFI NMAH REPLACE ACUS FOR COLLECTION STORAGE ON 4TH AND 5TH FLOORS

PROJECT NUMBER 2003112

6 20-Jun-23 RFP

6. Question: Please clarify which subcontractors shall be listed as “Key Subcontractors” and need references provided. RFP Part V section B lists “Doors, Frames and Hardware,” “Security,” and “Commissioning” as three subcontractors that should be included as Key Subcontractors. There does not appear to be any scope in the project for Doors, Frames and Hardware or Security.

Additionally, according to specification 019113, Commissioning Consultant will be procured directly by Smithsonian and would not be a Subcontractor to the Contractor. Also in Part I of the RFP, bullet point 11 indicates that Mechanical and Electrical Subcontractors are key subcontractors but they are not listed in Part V section B.

26-Jun-23 Remove the following subcontractors from Part V Section B. Doors Frames and Hardware, Security and Commissioning. Add Mechanical Systems. Commissioning consultant will be contracted by Smithsonian.

7 20-Jun-23 DRAWING A-104

7. Question: A-104 notes to replace drywall and acoustic ceilings in some areas. Please provide an RCP showing the existing ceiling types.

26-Jun-23

The ceiling system below the proposed piping crossing the corridors is 2x4’ system with standard lay in tile. Contractor to assume replacement of all tiles in the work zone indicated on A104. Contractor to remove and stockpile tile and make efforts to re use tile and grid elements. All fire alarm, lighting, sprinkler, and other ceiling mounted systems is to remain operational and in place. Contractor to replace tiles at devices that are mounted through tile. These notes can be added in an addendum or conform set for the record

8 20-Jun-23 DRAWINGS

8. Question: The mechanical drawings show different colored ductwork. Please provide a schedule showing what the colors differentiate.

26-Jun-23 The colors are for reference only, they do not indicate new versus existing scope. Different colors represent different air handling units.

9 20-Jun-23 DRAWING M-403HP

9. Question: Detail 3/M-403HP shows a “new access platform for filter” but no details are shown for the platform. Please provide a detail showing design of the platform including materials, connections to structure, dimensions, etc.

26-Jun-23

Re new access platform for filter. Detail 3/M-403 will requires a new access platform (5’x5’) constructed of heavy duty galvanized open grating. The platform shall be 10’ above the mechanical room floor. Provide ladder with welded construction for access to platform from the floor. Provide railings at all platform edges. Platform shall be located to provide service access to filter. Platform will be added to plans in an addendum or conform set for the record. GC to submit construction details to architect for approval. The details and engineering of the platform shall be provided by a qualified miscellaneous metal contractor

10 26-Jun-23 RFP

10a. Question: RFP Part I Section E notes that the Completed Statement should contain no more than 50 pages 8.5x11. Section A of the same part notes that information should be compiled into 13 tabs. In regard to these requirements, please advise the following:

a) Can audited financial statements be included as attachments that do not count toward the page limit?

Yes

11 26-Jun-23 RFP

10b. Question: RFP Part I Section E notes that the Completed Statement should contain no more than 50 pages 8.5x11. Section A of the same part notes that information should be compiled into 13 tabs. In regard to these requirements, please advise the following:

b) Can a Milestone CPM Schedule be provided under Tab 5 with the full schedule provided in 11x17 format as an attachment that does not count against the page limit?

Submission is electronic therefore the page size should be formatted as such. Yes the full schedule can be submitted as an attachment.

12 26-Jun-23 RFP

10c. Question: RFP Part I Section E notes that the Completed Statement should contain no more than 50 pages 8.5x11. Section A of the same part notes that information should be compiled into 13 tabs. In regard to these requirements, please advise the following:

c) Do tabs count as pages and if so can the requested information be included on the tabs if the information requested can be conveyed in less than one page?

Tabs do not count as pages.

13 26-Jun-23 RFP

10d. Question: RFP Part I Section E notes that the Completed Statement should contain no more than 50 pages 8.5x11. Section A of the same part notes that information should be compiled into 13 tabs. In regard to these requirements, please advise the following:

d) Per Section I of the RFP, photographs of comparable projects are desirable but not required. Please advise if photographs of comparable projects can be provided as attachments that do not count towards the page limit.

This requirement is removed.

14 26-Jun-23 RFP

11. Question: Should the Small Business Subcontracting Plan be included in the cost or technical proposal? If technical, please advise which tab and if it can be included as an attachment that does not count toward the page count.

Subcontracting Plan – This can be included in the Technical Proposal as an attachment and will not count toward the page limit. This can be placed in Tab 8. Offerors must include information requested in Part V, Section B of the RFP and FAR Clauses 52.219-S0097 and 52.219-9 Small Business Subcontracting Plan.

15 26-Jun-23 RFP

12. Question: Does the Smithsonian require that the AIA A-305 form be submitted with the Offeror's proposal for this Solicitation?

If so, please advise if it should be part of the Cost or Technical proposal. If the Technical, please confirm it can be included as an attachment that does not count against the page limit.

AIA A-305 is not required.

16 26-Jun-23 RFP

13. Question: Should Offeror's Background be submitted under Tab 1 as indicated in Part I, section A-1-A of the RFP or should it be included in Tab 2 as indicated in Part II of the RFP?

The appropriate information should be completed for both. Information requested in Tab 3 and 4 should be included in the Technical Proposal. Information requested in Section K should be included in the Cost Proposal.

RomanoJ Line

RomanoJ Typewriter Photos cannot be submitted as an attachment.

Photos are included in the page count.

17 26-Jun-23 RFP

14. Question: Information requested in Tabs 3 & 4 of the technical proposal in the RFP appears to be the same information requested to be included in the cost proposal as “Section K” Please confirm that the information should be included in both the cost and technical proposals

Please provide page numbers in the RFP where this duplication occurs.

18 26-Jun-23 DRAWING A-105

15. Question: Per Drawing A-105, staging areas for rigging AHU components to the roof is provided on the south side of the penthouse equipment yard. Please provide a drawing showing the extent of existing below grade construction on the south side of the building that is beyond the main façade.

The staging of the AHUs in on the roof of the 5th floor for the new AHUs to be installed on the Penthouse Mech Rooms. PENTHOUSE LOGISTICS PLAN drawing A-105 LP is corresponds with the 5th floor roof plan and Penthouse Mech Rooms. Attached is revised drawing A-105 LP clarifying the staging areas. The crane for rigging the AHUs is on the driveway of Constitution Avenue on the north end of the Museum.

19 26-Jun-23 DRAWING A-5

16. Question: Please advise if it is permissible to set-up a crane on the north side of the building in the horseshoe drive in order to hoist material and equipment to the roof.

Yes, set-up of the Crane is on the driveway in from to the NMAH north façade.

20 26-Jun-23 SPEC 237323

17a. Question: Section 237323, Para. 2.1.5 states, "Factory testing shall include sound and air leakage testing to the requirements specified in this Section." a) No further requirements are outlined in the section. Please confirm that factory sound and air leakage testing is not required or provide testing requirements and acceptance criteria. Note that each of the units are required to ship knocked down into individual pieces/components in order to transport them to the spaces. Factory testing of knocked down units is highly uncommon and very expensive.

30-Jun-23

Sound testing is not required. Manufacturer shall submit calculated sound levels in the eight octave bands for transmission through casing walls and sound power levels at the inlet and discharge opening.

The unit manufacturer shall provide a factory deflection test on either AHU-PW-19 or AHU-PE-

20. Casing panel deflection shall not exceed L/240 at +/- 10” w.g. ‘L’ is defined as the maximum span length and L/X is the deflection at the panel midpoint.

The unit manufacturer shall provide a factory leak test on either AHU-PW-19 or AHU-PE-20 across the cabinet exterior walls. Casing leakage shall not exceed 0.5% of the design CFM at +/- 10” w.g. Sections that will be negative pressure shall be tested under negative pressure and section that will be positive pressure shall be tested under positive pressure.

21 26-Jun-23 SPEC 237323

17b. Question: Section 237323, Para. 2.1.5 states, "Factory testing shall include sound and air leakage testing to the requirements specified in this Section." b) If factory testing of the air handling units is required, will it be witnessed by representatives of the Owner? If so, how many? Is the air handling unit manufacturer expected to include travel and expenses for the witness(es)?

30-Jun-23

Yes, factory testing of the air handling units is required and shall be witnessed by the Smithsonian representatives.

Certified factory representative shall perform the following field inspection:

- Witness and record the functional performance testing of the air handling unit at a time and date to be determined by the contractor.

- Check installed unit casing for leakage during testing.

- Check rotation and balance of fan wheel.

- Prepare a written report on findings and recommended corrective actions.

22 26-Jun-23 Spec 237323

17c. Question: Section 237323, Para. 2.1.5 states, "Factory testing shall include sound and air leakage testing to the requirements specified in this Section." c) Is the air handling unit manufacturer required to leakage test the units in the field? If so, please provide testing requirements and acceptance criteria.

30-Jun-23 Field leakage testing is not required. Where air leakage is evident during field inspection, connections shall be corrected using factory recommended methods to resolve leakage.

UP

UP

DNDN

E

F

G

H'

H

G'

I'

I

I''

J

K

J'

5 76' 9 9' 1110 11A 12 12''' 13'' 14 14A 16 18 18' 20

A-302

A-302

PENTHOUSE

PH2608

STAIR

PH2000S1

PENTHOUSE

PH2606

STAIR

PH2000S2

PENTHOUSE

PH2605

212019188 9 10 11 12' 13 14 15 16 17

D

E

F

H

J

K

L

K'

11A 14A12 13'

J'

D'

12"

E'

C'

16'15' 18'17'10"

I'

20'10'9'

G

EXISTING CHAIN LINK FENCE

CONSTITUTION AVE (NORTH)

MADISON AVE (SOUTH)

TEMPORARILY DEMOUNT FENCE

COOLING TOWER AND EMERGENCY

GENERATOR PLATFORM APPROXIMATE

EXTENTS

SMOKE EVACUATION SYSTEM APPROXIMATE EXTENTS

RIG AHU COMPONENTS TO ROOF & PROVIDE 3/4"

MARINE GRADE PLYWOOD SHEETING ON ROOF

SURFACE FOR PROTECTION OF BALLASTED

MEMBRANE ROOFING DURING RIGGING PHASE

INDICATED BY HATCHED AREAS

TEMPORARILY DEMOUNT FENCE

DOGHOUSE

DOGHOUSE

DOGHOUSE DOGHOUSE DOGHOUSE

DOGHOUSE

DOGHOUSEDOGHOUSEDOGHOUSEDOGHOUSE

DOGHOUSE

SKYLIGHT

PENTHOUSE

8000400004000

1:200

Smithsonian Facilities 600 Maryland Avenue S.W. Suite 5001

Washington, DC 20024-2520

Smithsonian Institution

KEY PLAN

GRAPHIC SCALE(S)

SHEET NO.

OF

PROJECT TITLE

A/E PROJECT NUMBER

ADDRESS

BUILDING NAME

OFEO PROJECT

NUMBER

DRAWING TITLE

WORKING STAFF

DATE SUBMISSION

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12

REVISION # DATE REVISION DESCRIPTION

TYPE

DRAWN BY

SEQUENCEDISCIPLINE

CHECKED BYDESIGNED BY

DRAWING TYPE

Annum Architects

40 Broad Street

Boston, MA 02109

617 338 3000

:2 :3

P M

REPLACE ACU’S FOR

COLLECT. STOR.ON 4TH

AND 5TH FLOORS

PENTHOUSE LOGISTICS PLAN

2003112

REPLACE ACU’S FOR COLLECT.

STOR.ON 4TH AND 5TH FLOORS

12/21/22 CONSTRUCTION DOCUMENTS

A L P

B Y

A p p ro v e r E n te r Is s u e

D a te

C O N S T R U C T

IO

N

D O C U M E N T S

NMAH

600 MARYLAND AVE SW,

WASHINGTON, DC 20002

NMAH

2003112

A-105LP

JM ERER/MF

SCALE =1 : 200A-105LP

1 PENTHOUSE OVERALL LOGISTICS PLAN

NO ELEVATOR

ACCESS THIS FLOOR

NO ELEVATOR

ACCESS THIS FLOOR

WORKZONE

PH2603

WORKZONE

PH2602

AHU-4CW-19

AHU-4CW-20

4 3 2

LOCATION OF TEMPORARY

AHU

LOCATION OF TEMPORARY

AHU

PATH FROM STAGING AREA TO PENTHOUSE

RFI 15 SKETCH 4TH AND 5TH FLOOR STORAGE HVAC ANNUM ARCHITECTS

2023/06/29 Page 1 of 1 lsmith Image lsmith Text Box

5 - ARIAL PHOTO

lsmith Rectangle lsmith Rectangle lsmith Callout

STAGING AREA

lsmith Callout

STAGING AREA

20-June-23

RFP

1. Question: Page 4 of the RFP, part A.1.A shows the Offeror’s Background as part of Tab no. 1. Page 7 shows this as Tab no. 2.

Page 7 should show Tab 1.

2. Question: Please confirm which tab should include Part II section J (List of Officers, Partners, and/or Owners).

Submit under Tab 1.

3. Question: Is there a worksheet for Tab 3- Suspension or Debarment, or is it Section K under Part II- Offeror’s Background (which states “Submit under Tab 4”)?

There is no worksheet. If the response is YES to section K, the details would be submitted under TAB 3. If the response is no, there will be no submission for TAB 3.

4. Question: Please confirm that Safety/EMR is Part V or VI, not IV.

Safety/EMR should be part V.

Smithsonian Facilities 600 Maryland Avenue S.W. Suite 5001

Washington, DC 20024-2520

Smithsonian Institution

GRAPHIC SCALE(S)

SHEET NO.

OF

PROJECT TITLE

A/E PROJECT NUMBER

ADDRESS

BUILDING NAME

OFEO PROJECT

NUMBER

DRAWING TITLE

WORKING STAFF

DATE SUBMISSION

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12

REVISION # DATE REVISION DESCRIPTION

TYPE

DRAWN BY

SEQUENCEDISCIPLINE

CHECKED BYDESIGNED BY

DRAWING TYPE

Annum Architects 40 Broad Street Boston, MA 02109 617 338 3000

Altieri Sebor Wieber, LLC 31 Knight Street Norwalk, CT 06851 203 866 5538 171 Milk Street 3rd floor Boston, MA 02109 617 468 1000

: 5 :0 P M

REPLACE ACU’S FOR

COLLECT. STOR.ON 4TH

AND 5TH FLOORS

PANEL SCHEDULES

2003112

REPLACE ACU’S FOR COLLECT.

STOR.ON 4TH AND 5TH FLOORS

12/21/22 CONSTRUCTION DOCUMENTS

E D G

B Y A p p ro ve r E n te r Is su e D a te

C O N S

TR

U C

TI

O N

D O C U M E N

TS

NMAH

600 MARYLAND AVE SW,

WASHINGTON, DC 20002

NMAH

2003112

E-604DG

Author CheckerDesignerEX. 4D1EX. 4C1

EX. PHB1EX. PHBEX. PHA1

EX. 4DEX. 4CEX. 4BB

Notes:

TOTAL CURRENT: 394 A

TOTAL LOAD: 327.63 kVA

12 TEMP. ERC-4-5-3 3 400 A 225 A 173 A 144.00 PROVIDE NEW CIRCUIT...

11 TEMP. ERC-4-5-2 3 400 A 225 A 173 A 144.00 PROVIDE NEW CIRCUIT...

10 TEMPORARY UNIT 3 30 A 20 A 6 A 4.80 USE SPARE CIRCUIT BREAKER.

9 TEMPORARY ELECTRIC... 3 100 A 50 A 36 A 30.00 USE SPARE CIRCUIT BREAKER.

8 AHU-PE-20 3 30 A 15 A 6 A 4.83 USE SPARE CIRCUIT BREAKER.

7 SPARE 3 -- 20 A -- 0.00

6 PANEL EX. PHB VIA XFMR PHB 3 -- 20 A -- 0.00

5 SPARE 3 -- 20 A -- 0.00

4 RF-R4 3 -- 20 A -- 0.00

3 SPARE 3 -- 20 A -- 0.00

2 AC-4 3 -- 20 A -- 0.00

1 EX. MCC PHB 3 -- 100 A -- 0.00

CKT LOAD NAME # OF

POLES

FRAME

SIZE

TRIP

RATING

CURRENT

(AMPERE)

LOAD

(kVA) REMARKS

No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS

OPTIONS:

MAIN: 400

MOUNTING: WIRE: BUS: 400

SUPPLY FROM: PHASE: 3 MAIN TYPE: MCB

LOCATION: VOLTS: 480Y/277V A.I.C. RATING: 22,000

DISTRIBUTION PANEL: EX. PHB1

1. USE SPARE CIRCUIT BREAKER FOR NEW CIRCUITS.

NOTES:

Total Connected Current (Amps): 47 A Total Connected Load (kVA): 39.01 kVA

Total VA 13 13 13

41 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 42

39 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 40

37 SPACE -- -- -- 0.00 0.00 -- -- -- SPACE 38

35 SPACE -- -- -- 0.00 0.00 36

33 SPACE -- -- -- 0.00 0.00 34

31 SPACE -- -- -- 0.00 0.00

3 50 EF-9

VFD EF-9

29 SPACE -- -- -- 0.00 0.00 30

27 SPACE -- -- -- 0.00 0.00 28

25 SPACE -- -- -- 0.00 0.00

3 30 Air Compressor

23 10.00 0.00 24

21 10.00 0.00 22

TEMPORARY

ELECTRIC HUMIDIFIER 4#6+1#10G-1"C 50 3

10.00 0.00

3 25 SPARE

17 0.00 1.60 18

15 0.00 1.60 16

AC-1 100 3

0.00 1.60

3 20 4#12+G-3/4"C TEMPORARY UNIT

11 0.00 1.40 12

9 0.00 1.40 10

Panel PHA (via XFMR PHA) 50 3

0.00 1.40

3 15 4#12+G-3/4"C AHU-PW-19

5 0.00 0.00 6

3 0.00 0.00 4

RF-R-1 50 3

0.00 0.00

3 20 MCC PHA

CK

T LOAD DESCRIPTION WIRE SIZE

(AWG) TRIP P A B C P TRIP WIRE SIZE

(AWG) LOAD DESCRIPTION CK

T

No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS SINGLE SECTION

OPTIONS: MAIN:

MOUNTING: WIRES: BUS:

SUPPLY FROM: PHASE: 3 MAIN TYPE: MLO

LOCATION: VOLTS: 480Y/277V A.I.C. RATING: 22,000

PANELBOARD: EX. PHA1

1. PROVIDE NEW CIRCUIT BREAKER. MATCH CIRCUIT BREAKER TYPE WITH EXISTING.

Notes:

TOTAL CURRENT: 203 A

TOTAL LOAD: 168.72 kVA

24 TEMP. ERC-4-2-1 3 400 A 250 A 194 A 161.00 PROVIDE NEW CIRCUIT...

23 TEMP BLOWER 3 100 A 15 A 5 A 3.82 SEE NOTE 1

22 EF-4-W 3 -- 15 A -- 0.00

21 F2P-5 3 -- 30 A -- 0.00 20 F2P-6 3 -- 30 A -- 0.00

19 PNL EX. 4A VIA XF 3 -- 70 A -- 0.00

18 ACU-6 CKT 2 3 -- 80 A -- 0.00

17 RF5 3 -- 80 A -- 0.00

16 ACU-6 CKT 1 3 -- 150 A -- 0.00

15 RF6S 3 -- 150 A -- 0.00

14 AHU-4W-12 3 100 A 15 A 5 A 3.90 USE SPARE CIRCUIT BREAKER.

13 PRE HEAT ACU5 3 -- 15 A -- 0.00

12 PNL EX. 4A VIA XF 3 -- 70 A -- 0.00

11 ACU6-1 3 -- 80 A -- 0.00

10 RF-5 3 -- 80 A -- 0.00

9 ACU6-A 3 -- 150 A -- 0.00

8 EXISTING RF6S 3 -- 150 A -- 0.00

7 ACU-6 PREHEAT 3 -- 150 A -- 0.00

6 ACU-5 PREHEAT 3 -- 150 A -- 0.00

5 AC-5 CKT 2 3 -- 150 A -- 0.00

4 AC-5 CKT 1 3 -- 150 A -- 0.00

3 METER 3 -- 15 A -- 0.00

2 EF-2 3 -- 15 A -- 0.00

1 EX AHU-2 3 -- 15 A -- 0.00

CKT LOAD NAME # OF

POLES

FRAME

SIZE

TRIP

RATING

CURRENT

(AMPERE)

LOAD

(kVA) REMARKS

No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS

OPTIONS:

MAIN: 800A

MOUNTING: WIRE: BUS: 800A

SUPPLY FROM: PHASE: 3 MAIN TYPE: MLO

LOCATION: VOLTS: 480Y/277V A.I.C. RATING: 22,000

DISTRIBUTION PANEL: DP-W4-M

1. USE SPARE CIRCUIT BREAKER FOR NEW CIRCUITS.

NOTES:

Total Connected Current (Amps): 2 A Total Connected Load (kVA): 0.72 kVA

Total VA 0 1 0

41 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 42

39 EX. LOAD 20 1 0.00 0.72 1 20 2#12-G-3/4" C. 120V CKT MECH... 40

37 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 38

35 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 36

33 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 34

31 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 32

29 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 30

27 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 28

25 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 26

23 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 24

21 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 22

19 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 20

17 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 18

15 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 16

13 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 14

11 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 12

9 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 10

7 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 8

5 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 6

3 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 4

1 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 2

CK

T LOAD DESCRIPTION WIRE SIZE

(AWG) TRIP P PHASE A

(kVA)

PHASE B

(kVA)

PHASE C

(kVA) P TRIP WIRE SIZE

(AWG) LOAD DESCRIPTION CK

T

No No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS SINGLE SECTION

OPTIONS: MAIN:

MOUNTING: SURFACE WIRES: 4 BUS:

SUPPLY FROM: PHASE: 3 MAIN TYPE:

LOCATION: VOLTS: 120/208 Wye A.I.C. RATING: 65,000

PANELBOARD: 4A

EX. PHA

EX. 4A

NOTES:

Total Connected Current (Amps): 5 A

Total Connected Load (kVA): 1.96 kVA

Total VA 2 0 0 41 EX. LOAD 20 1 0.00 0.00 1 20 Spare 42

39 EX. LOAD 20 1 0.00 0.00 1 20 Spare 40

37 EX. LOAD 20 1 0.00 0.00 1 20 Spare 38

35 EX. LOAD 20 1 0.00 0.00 1 20 Spare 36

33 EX. LOAD 20 1 0.00 0.00 1 20 Spare 34

31 EX. LOAD 20 1 0.00 0.00 1 20 Spare 32

29 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 30

27 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 28

25 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 26

23 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 24

21 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 22

19 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 20

17 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 18

15 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 16

13 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 14

11 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 12

9 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 10

7 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 8

5 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 6

3 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 4

1 P-1, P-2 2#12+G-3/4"C 20 1 1.06 0.90 1 20 2#12+G-3/4"C 120V TO MECH EQUIP 2

CK

T LOAD DESCRIPTION WIRE SIZE

(AWG) TRIP P PHASE A

(kVA)

PHASE B

(kVA)

PHASE C

(kVA) P TRIP WIRE SIZE

(AWG) LOAD DESCRIPTION CK

T

No No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS SINGLE SECTION

OPTIONS: MAIN:

MOUNTING: SURFACE WIRES: 4 BUS:

SUPPLY FROM: PHASE: 3 MAIN TYPE:

LOCATION: VOLTS: 208Y/120V A.I.C. RATING: 65,000

PANELBOARD: EX. 4BB

EXISTING TO REMAIN

1. USE SPARE CIRCUIT BREAKER FOR NEW CIRCUITS.

NOTES:

Total Connected Current (Amps): 18 A Total Connected Load (kVA): 6.57 kVA

Total VA 0 4 3 41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 EX. RECP 4502 20 1 0.00 2.75 18

15 EX. RECP 4503 20 1 0.00 2.75

2 35 3#10+G-3/4"C P-3, P-4

13 EX. RECP 4506 20 1 0.00 0.00 1 20 Spare 14

11 EX. WATER SOFTNER 20 1 0.00 0.00 1 20 LTG RM 4506, 4503 12

9 120V TO MECH EQUIP 2#12+G-3/4"C 20 1 1.08 0.00 1 20 LTG RM 4502 10

7 EX. CONTROL PW 20 1 0.00 0.00 1 20 Spare 8

5 EX. CONTROL PW 20 1 0.00 0.00 1 20 EX. WATER HEATER 6

3 EX. PENTHOUSE LTG 20 1 0.00 0.00 1 20 EX. PENTHOUSE LTG 4

1 EX. PENTHOUSE LTG 20 1 0.00 0.00 1 20 EX. PENTHOUSE LTG 2

CK

T LOAD DESCRIPTION WIRE SIZE

(AWG) TRIP P PHASE A

(kVA)

PHASE B

(kVA)

PHASE C

(kVA) P TRIP WIRE SIZE

(AWG) LOAD DESCRIPTION CK

T

No No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS SINGLE SECTION

OPTIONS: MAIN: 100

MOUNTING: SURFACE WIRES: 4 BUS:

SUPPLY FROM: PHASE: 3 MAIN TYPE:

LOCATION: VOLTS: 208Y/120V A.I.C. RATING: 65,000

PANELBOARD: EX. 4C

EXISTING TO REMAIN

1. PROVIDE NEW CIRCUIT BREAKER FOR NEW CIRCUITS. MATCH BREAKER TYPE WITH EXISTING.

NOTES:

Total Connected Current (Amps): 1 A Total Connected Load (VA): 0.36 kVA

Total VA 0 0 0 41 Space -- -- -- 0.00 0.00 -- -- -- Space 42

39 Space -- -- -- 0.00 0.00 -- -- -- Space 40

37 Space -- -- -- 0.00 0.00 -- -- -- Space 38

35 Space -- -- -- 0.00 0.00 -- -- -- Space 36

33 Space -- -- -- 0.00 0.00 -- -- -- Space 34

31 Space -- -- -- 0.00 0.00 -- -- -- Space 32

29 0.00 0.00 30

FCUs 2#2+G-3/4" C. 20 2

0.00 0.00 2 20 2#2+G-3/4" C. FCUs

25 DED. RECP 4027 20 1 0.00 0.36 1 20 2#12+G-3/4"C 120V TO MECH EQUIP 26

23 DED. RECP 4027 20 1 0.00 0.00 24

21 RECP RM 4611 20 1 0.00 0.00 22

19 MECH RM RECP 20 1 0.00 0.00

3 40 220V CORD. WEST WALL

17 RECP RM 4611 20 1 0.00 0.00 1 20 LTG RM 4606 18

15 LTG RM 4611 20 1 0.00 0.00 1 20 RECP RM 4606 16

13 CONTROL CKT 20 1 0.00 0.00 1 20 RECP RM 4606 14

11 MECH RM RECP 20 1 0.00 0.00 1 20 LTG RM 4602 12

9 MECH RM RECP 20 1 0.00 0.00 1 20 RECP RM 4602 10

7 MECH RM LTG 20 1 0.00 0.00 1 20 LTG RM 4604 8

5 Space -- -- -- 0.00 0.00 6

3 Space -- -- -- 0.00 0.00 4

1 Space -- -- -- 0.00 0.00

3 100 MAIN

CK

T LOAD DESCRIPTION WIRE SIZE

(AWG) TRIP P A B C P TRIP WIRE SIZE

(AWG) LOAD DESCRIPTION CK

T

No No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS SINGLE SECTION

OPTIONS: MAIN:

MOUNTING: SURFACE WIRES: 4 BUS:

SUPPLY FROM: PHASE: 3 MAIN TYPE:

LOCATION: VOLTS: 120/208 Wye A.I.C. RATING: 65,000

PANELBOARD: EX. 4D

EXISTING TO REMAINEXISTING TO REMAIN

NOTES:

Total Connected Current (Amps): 2 A

Total Connected Load (kVA): 0.72 kVA

Total VA 0 0 0

29 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 30

27 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 28

25 CT CNTRL 4A, 4B 20 1 0.00 0.00 1 20 CT WATER MAKEUP 26

23 CT CNTRL 3A, 3B 20 1 0.00 0.00 1 20 SIEMENS CNTRL PNL 24

21 CT CNTRL 1A, 1B, 1C 20 1 0.00 0.00 1 20 CT CNTRL 2A, 2B, 2C 22

19 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 20

17 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 18

15 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 16

13 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 14

11 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 12

9 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 10

7 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 8

5 TEMP. 120V TO MECH 2#12+G-3/4"C 20 1 0.36 0.00 1 20 EX. LOAD 6

3 120V TO MECH EQUIP 2#12+G-3/4"C 20 1 0.36 0.00 1 20 EX. LOAD 4

1 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 2

CK

T LOAD DESCRIPTION WIRE SIZE

(AWG) TRIP P PHASE A

(kVA)

PHASE B

(kVA)

PHASE C

(kVA) P TRIP WIRE SIZE

(AWG) LOAD DESCRIPTION CK

T

No No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS SINGLE SECTION

OPTIONS: MAIN:

MOUNTING: SURFACE WIRES: 4 BUS:

SUPPLY FROM: PHASE: 3 MAIN TYPE:

LOCATION: VOLTS: 120/208 Wye A.I.C. RATING: 65,000

PANELBOARD: EX. PHA

1. USE SPARE CIRCUIT BREAKER FOR NEW CIRCUITS.

NOTES:

Total Connected Current (Amps): 2 A Total Connected Load (kVA): 0.72 kVA

Total VA 0 0 1

41 EX. LOAD 20 1 0.00 0.72 1 20 2#12+G-3/4"C 120V TO MECH EQUIP 42

39 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 40

37 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 38

35 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 36

33 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 34

31 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 32

29 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 30

27 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 28

25 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 26

23 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 24

21 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 22

19 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 20

17 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 18

15 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 16

13 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 14

11 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 12

9 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 10

7 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 8

5 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 6

3 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 4

1 EX. LOAD 20 1 0.00 0.00 1 20 EX. LOAD 2

CK

T LOAD DESCRIPTION WIRE SIZE

(AWG) TRIP P PHASE A

(kVA)

PHASE B

(kVA)

PHASE C

(kVA) P TRIP WIRE SIZE

(AWG) LOAD DESCRIPTION CK

T

No No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS SINGLE SECTION

OPTIONS: MAIN:

MOUNTING: SURFACE WIRES: 4 BUS:

SUPPLY FROM: PHASE: 3 MAIN TYPE:

LOCATION: VOLTS: 120/208 Wye A.I.C. RATING: 65,000

PANELBOARD: EX. PHB

EXISTING TO REMAIN EXISTING TO REMAINEXISTING TO REMAIN EXISTING TO REMAIN

EX. 4B1EX. DP-W4-M

Notes:

TOTAL CURRENT: 161 A

TOTAL LOAD: 134.25 kVA

16 TEMP. ERC-4-7-5 3 100 A 40 A 25 A 21.00 PROVIDE NEW CIRCUIT...

15 TEMP. ERC-4-7-4 3 100 A 40 A 25 A 21.00 PROVIDE NEW CIRCUIT...

14 TEMP. ERC-4-7-3 3 100 A 40 A 25 A 21.00 PROVIDE NEW CIRCUIT...

13 TEMP. ERC-4-7-6 3 100 A 40 A 25 A 21.00 PROVIDE NEW CIRCUIT...

12 TEMP. ERC-4-7-10 3 100 A 45 A 31 A 26.00 PROVIDE NEW CIRCUIT...

11 TEMP. ERC-4-7-9 3 100 A 40 A 25 A 21.00 PROVIDE NEW CIRCUIT...

10 R-13 3 -- 30 A -- 0.00

9 EX. 4D VIA XFMR 4D 3 -- 60 A -- 0.00

8 Spare 3 -- 50 A -- 0.00

7 ACC-1 3 -- 20 A -- 0.00

6 Spare 3 -- 50 A -- 0.00

5 AC-12 3 -- 100 A -- 0.00

4 AHU-4E-17 3 15 A 15 A 4 A 3.25 USE SPARE CIRCUIT BREAKER.

3 AC-13 3 -- 100 A -- 0.00

2 EX. MCC-4D 3 400 A 100 A 0 A 0.00

1 RF R-12 3 -- 50 A -- 0.00

CKT LOAD NAME # OF

POLES

FRAME

SIZE

TRIP

RATING

CURRENT

(AMPERE)

LOAD

(kVA) REMARKS

No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS

OPTIONS:

MAIN: 400

MOUNTING: WIRE: BUS: 400

SUPPLY FROM: PHASE: 3 MAIN TYPE: MLO

LOCATION: VOLTS: 480Y/277V A.I.C. RATING: 22,000

DISTRIBUTION PANEL: EX. 4D1

Notes:

TOTAL CURRENT: 206 A

TOTAL LOAD: 170.96 kVA

16 TEMP. ERC-4-5-1 3 400 A 225 A 173 A 144.00 PROVIDE NEW CIRCUIT...

15 TEMP BLOWER COIL UNITS 3 400 A 15 A 9 A 7.65 USE SPARE CIRCUIT BREAKER.

14 TEMP BLOWER COIL UNITS 3 400 A 20 A 14 A 11.47 PROVIDE NEW CIRCUIT...

13 SPACE -- -- -- -- 0.00 --

12 SPARE 1 -- 20 A -- 0.00

11 SPACE -- -- -- -- 0.00 --

10 SPARE 3 -- 50 A -- 0.00

9 SPACE -- -- -- -- 0.00 --

8 SPARE 3 -- 50 A -- 0.00

7 REHEAT PNL 5TH FLR RM 5117 3 -- 100 A -- 0.00

6 AHU-4CE-16 3 100 A 15 A 4 A 3.18 PROVIDE NEW CIRCUIT...

5 RF AC-10 3 -- 50 A -- 0.00

4 AHU-4CE-15 3 100 A 15 A 6 A 4.66 PROVIDE NEW CIRCUIT...

3 RF AC-11 3 -- 50 A -- 0.00

2 MCC 4C 3 -- 100 A -- 0.00

1 PANEL EX. 4C VIA XFMR 4C 3 100 A 60 A 0 A 0.00

CKT LOAD NAME # OF

POLES

FRAME

SIZE

TRIP

RATING

CURRENT

(AMPERE)

LOAD

(kVA) REMARKS

No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS

OPTIONS:

MAIN: 400

MOUNTING: WIRE: BUS: 400

SUPPLY FROM: PHASE: 3 MAIN TYPE: MCA

LOCATION: VOLTS: 480Y/277V A.I.C. RATING: 35,000

DISTRIBUTION PANEL: EX. 4C1

Notes:

TOTAL CURRENT: 366 A

TOTAL LOAD: 304.64 kVA

12 TEMP. ERC-4-4-1 3 400 A 200 A 143 A 119.00 PROVIDE NEW CIRCUIT...

11 TEMP BLOWER COIL UNITS 3 100 A 15 A 9 A 7.65 PROVIDE NEW CIRCUIT...

10 TEMP BLOWER COIL UNITS 3 100 A 15 A 9 A 7.65 PROVIDE NEW CIRCUIT...

9 AHU-4CW-14 3 100 A 15 A 2 A 1.89 USE SPARE CIRCUIT BREAKER.

8 AHU-4CW-13 3 100 A 25 A 9 A 7.46 USE SPARE CIRCUIT BREAKER.

7 EX. PUMP 1 AND PUMP2 3 -- 0 A -- 0.00

6 EX. RF R-7 3 -- 0 A -- 0.00

5 EX. RF AC-8 3 -- 0 A -- 0.00

4 TEMP. ERC-4-4-2 3 400 A 250 A 194 A 161.00 PROVIDE NEW CIRCUIT...

3 EX. 4B VIA XF 3 -- 70 A -- 0.00

2 EX. MCC-4-B 3 -- 100 A -- 0.00

1 EX. LOAD 3 -- 0 A -- 0.00

CKT LOAD NAME # OF

POLES

FRAME

SIZE

TRIP

RATING

CURRENT

(AMPERE)

LOAD

(kVA) REMARKS

No No No No

FEED THRU LUGS 600-KCM LUGS FLUSH MOUNT ISOLATED GROUND BUS

OPTIONS:

MAIN: 400A

MOUNTING: WIRE: BUS: 400A

SUPPLY FROM: PHASE: 3 MAIN TYPE: MLO

LOCATION: VOLTS: 480Y/277V A.I.C. RATING: 22,000

DISTRIBUTION PANEL: EX. 4B1

EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN EXISTING TO REMAIN

1 6/20/23 Addendum 1

ChanVC Highlight

SQUARE ELBOW

DOUBLE

THICKNESS

VANES

BRANCH DUCT

SUPPLY TAP

X

X

12" MAX

AIRFLOW

12" MAX

X

AIRFLOW

BRANCH DUCT

RETURN TAP

AIRFLOW

R

R=W

W

SUPPLY SPLITRADIUS ELBOWCOIL OR REGISTER

R

R=W

W

WAIRFLOW

DUCT TAP TO

REHEAT COIL

OR REGISTER

VOLUME EXTRACTOR

WITH MANUAL

ADJUSTING LEVER

20DEG MAX

TRANSITION

12 X 8*

* DIMENSIONS DENOTE

CLEAR INSIDE DIMENSIONS

ACOUSTICAL

LINED DUCT

DUCT CONSTRUCTION DETAILS

NOTE: SPECIFICATIONS EXCEED

SMACNA STANDARDS IN

SOME INSTANCES.

SMACNA SHALL BE

CONSIDERED THE MINIMUM

STANDARD UNLESS

OTHERWISE NOTED

M-500DTM-500DT N.T.S.

X

DUCT SUPPORT DETAIL

2" MINIMUM

SHEET METAL SCREWS

6" O.C. MIN. OF TWO

BOLT & WASHER

BENT STRAP

EXPANSION

SHIELD

3/8" ROD ONLY

18 ga X 1" GALV.

METAL STRAP

INSERT & SPRING

LOADED NUT

C-CLAMP WITH

RETAINING CLIP SIDE

BEAM CLAMP

LOCKNUT

(TYPICAL)

3/8" ROD ONLY

BEAM CLAMP

GALVANIZED

THREADED ROD

GALVANIZED

SUPPORT

ANGLE

25" OR WIDEROPTIONAL FOR 30"

OR SMALLER

DUCT WIDTH ROD DIA. SUPPORT ANGLE OR

EQUIVALENT CHANNEL

MAXIMUM

SPACING

MAXIMUM

AREA*

8'-0" O.C.

6'-0" O.C.

6'-0" O.C.

4'-0" O.C.

4'-0" O.C.

4 SQ. FT.

10 SQ. FT.

10 SQ. FT.

3/8"

3/8"

1/2"

1/2"

1/2"

25" TO 30"

31" TO 42"

43" TO 60"

61" TO 84"

85" AND UP

* REDUCE SPACING TO NEXT SMALLER INTERVAL IF DUCT AREA EXCEEDS MAXIMUM

1 1/2" X 1 1/2" X 1/8"

1 1/2" X 1 1/2" X 1/8"

1 1/2" X 1 1/2" X 1/8"

2" X 2" X 1/4"

2" X 2" X 1/4"

M-500DTM-500DT N.T.S.

EXPANSION TANK DETAIL

* SECOND VALUE IS

ACCEPTANCE VOLUME

A B C

SIZE*

QUAN.

BACKFLOW PREVENTER

BY OTHER DIVISION

ISOLATION VALVE (TYP.)

GLOBE VALVE FOR

QUICK FILL

PRESSURE REDUCING

VALVE SET AT B PSI

TERMINATE ABOVE

FUNNEL DRAIN

DIAPHRAGM

TYPE EXPANSION

TANK

AIR ELIMINATORTERMINATE ABOVE

FUNNEL DRAIN

LINE SIZE

AIR SEPARATOR

TO PUMP

SUCTION

TERMINATE ABOVE

FUNNEL DRAIN

RELIEF VALVE SET

AT C PSI

A

M-500DTM-500DT N.T.S.

A

HWR

HWS

A

STRAINER

COMBINATION

BALANCE & FLOW VALVE

AIR VENT

TYPICAL

PRESSURE & TEMPERATURE

PORT (TYPICAL)

ISOLATION VALVE

BLOWDOWN VALVE

CONTROL VALVE

REDUCER

GPM A

HOSE END

BALL VALVE

UNION

(TYPICAL)

HOT WATER REHEAT COIL4

M-500DTM-500DT N.T.S.

2" and Smaller 2 1/2" and Larger

Fluids 150°F -250°F (15psi Steam) - 50' from Anchor Fluids greater than 250°F - 30' from Anchor

Fluids greater than 100°F 2" and Smaller 2 1/2" and Larger

Fluids less than 100°F 2" and Smaller 2 1/2" and Larger

12" RIGID

INSULATION

12" SHIELD

HANGER

PIPE

INSULATION

18" RIGID INSULATION

18" SHIELD

ROD

DOUBLE NUTS

AND WASHERS

12" RIGID

INSULATION

12" SHIELD

INSULATION INSERT

SADDLE

HANGER SCHEDULE

PIPE SIZE ROD SIZE MAX. SPACING

up to 1 1/4" up to 1 1/2" 1 1/2" & 2" 2 1/2" & 3"

4" & 5" 6"

8", 10", 12" 14" & 16"

18"

3/8" DIA.

3/8" DIA.

3/8" DIA.

1/2" DIA.

5/8" DIA.

3/4" DIA.

7/8" DIA.

1" DIA.

1 1/8" DIA.

8' Steel 6' Copper & Steel

10' 10' 10' 10' 10' 10' 10'

PIPE HANGER DETAIL7

M-500DTM-500DT N.T.S.

METAL DECK HANGER BOLTS CONCRETE DECK INSERTS

BEAM CLAMPS

SUPPLEMENTAL STEEL

WELDING PROCEDURE TO

BE SUBMITTED FOR REVIEW

INTERMEDIATE ATTACHMENT

ONE SIZE LARGER THAN

LARGEST HANGER ROD

END ATTACHMENT

TO BE SAME AS

LARGEST HANGER ROD

SQUARE STEEL WASHER TYP

BACK TO BACK STRUCTURAL SHAPES

WITH SPACERS WELDED AT 24" INTERVALS

TWO HANGER RODS MAXIMUM

BETWEEN STRUCTURE ATTACHMENTS

PIPE HANGER ATTACHMENT DETAIL6

M-500DTM-500DT N.T.S.

MANUAL & AUTOMATIC AIR VENTS8

M-500DTM-500DT N.T.S.

4 x PIPE

DIAMETER

10" MAX.

4 x PIPE

DIAMETER

10" MAX.

1/2" ISOLATION VALVE

REDUCER

INSULATION

MANUAL

HIGH POINT

IN SYSTEM

AUTOMATIC

AUTOMATIC AIR VENT

1/4" TYPE "L" COPPER TUBE

TO NEAREST SUITABLE DRAIN

CONVERTOR CONNECTIONS

HOT WATER

CONVERTOR

FULL SIZE OF

OUTLET

F&T TRAP

CONDENSATE RETURN

MAIN

FULL SIZE OF

INLET

HOT WATER SUPPLY

HOT WATER RETURN

THERMOMETER (TYP.)

TO DRAIN

RELIEF VALVE

12" MIN.

6" MIN.

DIRT POCKET WITH

CAP OR FLANGE

UNION (TYP.)

GLOBE OR PLUG VALVE

SAME SIZE

AS LARGER

CONTROL VALVE

STEAM

MAIN

STRAINER

CONTROL VALVE

ECCENTRIC REDUCER

ISOLATION VALVE

TYPICAL

A B

B

C A

M-500DTM-500DT N.T.S.

VACUUM BREAKER

BLOWDOWN

VALVE

END OF MAIN DRIP

PITCH DOWN

12" MIN.

6" MIN

UNION (TYP.)

DIRT POCKET WITH

CAP OR FLANGE

1/2" GLOBE VALVE

3/4" MINIMUM

GATE VALE (TYP.)

CONDENSATE RETURN MAIN

FOUR ELBOW

SWING JOINT

F&T TRAP

STRAINER WITH

BLOW DOWN VALVE

PITCH DOWN

STEAM MAIN

FULL SIZE

OF MAIN

M-500DTM-500DT N.T.S.

STEAM HUMIDIFIER DETAIL

FROM HUMIDIFIER

CONTROL VALVE

A

DISTRIBUTION MANIFOLDS A B

6" MIN.

10" MIN.

B

PROVIDE STAINLESS STEEL

BLANK OFF AROUND HUMIDIFIER

CONDENSATE TO COOLER

TEMPERATURE ACTUATED

VALVE

COLD WATER FROM

BACKFLOW PREVENTER

TEMPERATURE SENSOR

TEMPERED WATER

TO FLOOR DRAIN

VACUUM BREAKER

CONDENSATE COOLER

M-500DTM-500DT N.T.S.

UNFIRED STEAM GENERATOR16

M-500DTM-500DT N.T.S.

PP

P

P

LEVEL CONTROLLER

LOW PRESSURE

HUMIDIFICATION

STEAM (LPHS)

COLD WATER

PRIMARY STEAM

(H/MPS)

CONDENSATE RETURN

(H/MPR)

VENT TO ROOF

NOTES:

1. PIPING TO THE UPPER HEATER HEAD SHOULD BE PROVIDED WITH UNIONS OR FLANGES WHICH ARE LOCATED

BEYOND THE OUTSIDE DIAMETER OF THE HEAD TO PERMIT REMOVAL OF THE HEAD AND SHELL.

2. THE CONTROL VALVE SHOULD BE LOCATED 6" TO 12" ABOVE THE LOWER HEAD FLANGE. THE PIPING BETWEEN

THE VALVE AND HEATER CONNECTION SHOULD BE AS SHORT AS POSSIBLE.

3. REDUCERS, ON THE WATER INLET SIDE SHOULD BE LOCATED ADJACENT TO THE HEATER EXPANSION FITTINGS, ON THE WATER INLET SIDE, SHOULD BE LOCATED AS FAR AS POSSSIBLE FROM THE HEATER.

4. CONDENSATE RETURN PIPING SHOULD BE ARRANGED TO PERMIT THE CONDENSATE TO DRAIN FREELY.

5. DRAIN VALVE SHOULD BE PIPED DIRECTLY TO A FLOOR DRAIN. RELIEF VALVE SHOULD BE PIPED UP TO ROOF.

6. COLD WATER SUPPLY PRESSURE MUST BE GREATER THAN SECONDARY STEAM PRESSURE.

7. REFER TO PLANS FOR PIPE SIZES.

8. REFER TO PLANS FOR VENTING AND RELIEF PIPING DETAILS.

CHECK VALVE

STEAM TRAP

STRAINER W/

BLOWDOWN VALVE

ISOLATION VALVE

PRESSURE GAUGE

VACUUM BREAKER

CONTROL VALVE

DRAIN VALVE

RELIEF VALVE

UNION

DRAW THRU CONFIGURATION

1. H=UNIT STATIC PRESSURE IN INCHES

OF WATER PLUS 1 INCH.

2. L= 1/2 OF H.

BLOW THRU CONFIGURATION

1. H=1 INCH.

2. L=TOTAL STATIC PRESSURE IN INCHES

OF WATER PLUS 1 INCH.

DRAIN PAN

H (REFER TO NOTE 1)

L (REFER TO NOTE 2)

REFER TO NOTE 4

CONDENSATE DRAIN SHALL BE

A MINIMUM OF THE NIPPLE

SIZE ON THE DRAIN PAN

CLEAN OUT PLUG

PITCH DOWN

TOWARD DRAIN

CLEAN OUT PLUG

NOTES:

1. REFER TO PLANS AND SCHEDULES TO DETERMINE UNIT'S CONFIGURATION.

2. REFER TO SCHEDULES FOR UNIT'S TOTAL STATIC PRESSURE.

3. MANUALLY PRIME TRAPS PRIOR TO START-UP OF UNIT.

4. UNITS ABOVE CEILING: DRAIN PIPING SHALL BE INSULATED AND PIPED TO THE NEAREST

DRAIN (UNLESS OTHERWISE NOTED) WITH AN AIR GAP OF 2X THE CONDENSATE DRAIN SIZE.

UNITS ON ROOF: DRAIN PIPING SHALL BE HEAT TRACED, INSULATED AND PIPED TO ROOF

DRAIN, SPLASH BLOCK (BY THIS DIVISION) OR LOCATED INSIDE THE BUILDING.

UNITS INSIDE THE BUILDING: DRAIN SHALL BE PIPED TO THE NEAREST FLOOR DRAIN

(UNLESS OTHERWISE NOTED) WITH AN AIR GAP OF 2X THE CONDENSATE DRAIN SIZE.

COOLING COIL DRAIN TRAP DETAIL1

M-500DTM-500DT N.T.S.

F&T TRAP

0.0-4.0 3/4"

4.0-8.0 1"

8.0-16.0 1-1/4"

H-4W-12 1" 3/4"

H-4CW-13 1" 3/4"

H-4CW-14 1" 3/4"

H-4CE-15 1-1/4" 1"

H-4CE-16 1" 3/4"

H-4E-17 1" 3/4"

H-PW-19 1-1/4" 1"

UNIT NO.

H-PE-20 1-1/4" 1"

DIRT POCKET WITH

CAP OR FLANGE

12" MIN.

6" MIN

HOSE END

BALL VALVE

MANUAL BYPASS

TO EXISTING

HUMIDIFICATION

STEAM SYSTEM

2.0/1.0

ET-1 ET-2

2.0/1.0

1" 1" 30 30 75 75

TO BLOWDOWN SEPARATOR

CONDENSATE OUTLET

TO EXISTING LPR

1"=1"

1" 2"

1/8"=1' -0"

4' 8' 16'

1"=100' -0"

100' 200'

1/16"=1' -0"

8' 16' 32'

1"=50' -0"

50' 100'

Smithsonian Facilities 600 Maryland Avenue S.W. Suite 5001

Washington, DC 20024-2520

Smithsonian Institution

KEY PLAN

GRAPHIC SCALE(S)

SHEET NO.

OF

PROJECT TITLE

A/E PROJECT NUMBER

ADDRESS

BUILDING NAME

OFEO PROJECT

NUMBER

DRAWING TITLE

WORKING STAFF

DATE SUBMISSION

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12

REVISION # DATE REVISION DESCRIPTION

TYPE

DRAWN BY

SEQUENCEDISCIPLINE

CHECKED BYDESIGNED BY

DRAWING TYPE

Annum Architects 40 Broad Street Boston, MA 02109 617 338 3000

Altieri Sebor Wieber, LLC 31 Knight Street Norwalk, CT 06851 203 866 5538 171 Milk Street 3rd floor Boston, MA 02109 617 468 1000

: 3 :4 P M

REPLACE ACU’S FOR

COLLECT. STOR.ON 4TH

AND 5TH FLOORS

MECHANICAL DETAILS

2003112

REPLACE ACU’S FOR COLLECT.

STOR.ON 4TH AND 5TH FLOORS

12/21/22 CONSTRUCTION DOCUMENTS

M D T B Y A p p ro ve r E n te r Is su e D a te

C O N S

TR

U C

TI

O N

D O C U M E N

TS

NMAH

600 MARYLAND AVE SW,

WASHINGTON, DC 20002

NMAH

2003112

M-500DT

HY MFHY

PIPING ROOF PENETRATION12

M-500DTM-500DT N.T.S.

NOTES:

1. INSIDE CLEAR DIMENSIONS OF THE CURB SHALL BE:

-WIDTH: EQUAL TO THE O.D. OF THE LARGEST PIPE, INCLUDING INSULATION, PLUS 4" OF CLEARANCE.

MINIMUM WIDTH IS 12".

-LENGTH: EQUAL TO THE OVERALL WIDTH OF THE PIPING RACK AND INSULATION PLUS 4" OF CLEARANCE.

2. PROVIDE A MIN OF 2" CLEARANCE BETWEEN PIPE PENETRATIONS IN THE INSULATED METAL PANEL.

3. ROOF OPENINGS SHALL BE 4" SMALLER THAN THE INSIDE CURB DIMENSIONS IN BOTH DIRECTIONS. REFER TO

STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION REGARDING ROOF OPENING FRAMING.

4. EXTERIOR PIPE INSULATION AND JACKET SHALL EXTEND INTO THE PIPING ENCLOSURE. SEAL THE BUTT JOINT BETWEEN INTERIOR AND EXTERIOR INSULATION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

ADD INSULATION AT CAP

20 GAUGE ALUMINUM

WEATHERPROOF CAP/COUNTER

FLASHING SECURED TO CURB

ROOF MEMBRANE

ROOF INSULATION

ROOF. REFER TO

ARCHITECTURAL DWGS.

FOR ROOF DETAILS.

REFER TO NOTE #3.

PIPING THROUGH SIDE

OF CURB. SEAL WATERTIGHT.

INSULATED ALUMINUM ROOF CURB

TO MATCH ROOF INSULATION

R-VALUE WITH CANT STRIPS.

2" INSULATED METAL PANEL.

DRILLED FOR OPENINGS.

REFER TO NOTE#2.

PIPING AND

INSULATION.

WIDTH

REFER TO NOTE #1

WIDTH

REFER TO

NOTE #1

LENGTH

REFER TO NOTE #1

REFER TO NOTE #2

CURB

REFER TO NOTE #4

1/2"

PRESSURE

GAUGE

UNION

TYPICAL

HOSE END

GATE VALVE

TYPICAL

THERMOMETER

TYPICAL

AIR VENT

TYPICAL

CHILLED WATER COOLING COIL

CHS

CHR

ISOLATION

VALVE

TYPICAL

BLOWDOWN

VALVE

STRAINER

CONTROL VALVE

ECCENTRIC REDUCEER

UNION (TYPICAL)

COMBINATION BALANCE

& FLOW VALVE

A

UNIT NO.

CONN

A

M-500DTM-500DT N.T.S.

STACKED CHILLED WATER COOLING COIL

A B

UNIT NO.

CONNECTIONS

M-500DTM-500DT N.T.S.

BLOWDOWN SEPARATOR

4" VENT TO ROOF

1/2" STRAINER

TEMPERATURE REGULATOR VALVE

1"

BLOWDOWN

SEPARATOR

COLD WATER INLET

3 LEGS TYP.

BIMETAL

THERMOMETER

TEMPERATURE

SENSING

BULB

SLAB

PLUG VALVE

COLD WATER

SUPPLY LINE

1/2"

3"

FROM UNFIRED

STEAM GENERATOR

M-500DT M-500DT

3" DRAIN TO EXISTING

BLOWDOWN RECEPTOR

AHU-4CW-13 2-1/2"

AHU-4W-12 2"1"

AHU-4CW-14 1"3/4"

AHU-4CE-15 2"1"

AHU-4CE-16 1-1/2"1"

AHU-4E-17 2-1/2"1"

AHU-PW-19 2-1/2"2"

AHU-PE-20 2"2"

A B

UNIT NO.

CONNECTIONS

C-1 4" 3"

4" 3"C-2

C

2"

2"

1 6/20/23 Addendum #1

BALL VA.

UNION (TYP.)

CONTROL VALVE

SUPPLY AND ON EACH

PROVIDE ON COMMON

THERMOMETER TYPICAL

ECCENTRIC REDUCER

BRANCH RETURN

PRESSURE

BALL VALVE TYPICAL

HOSE END WITH

UNION

GAUGE

BALL

VA.

1/2"

VALVE (TYPICAL)

AUTOMATIC BALANCING

AIR VENT

BUTTERFLY OR

BALL VA. (TYPICAL)

HOSE END BALL VA

CHS

CHR

STRAINER

AIR VENT

TYPICAL

CONTROL VALVE

A

A

B

HOT WATER CONVERTOR

UNIT

NO LOCATION

SYSTEM

SERVED PSI LBS/HR TRAP CAP

SHELL SIDE

EWT LWT GPM FOULING PD

TUBE SIDE

MAKE/MODEL REMARKS

PUMPS

REMARKSMAKE/MODELTYPE

ELECTRICAL

RPMPHVOLTSHPBHP

MAX

FT

HEAD

TEMP

MAX

GPMFLUIDSERVED

SYSTEM

LOCATIONNO

UNIT

P-2 REHEAT COILSMECH RM 4000M2

P-1 WATERMECH RM 4000M2

P-3

HOT WATER COILS

UNIT NO LOCATION SERVES

CAP

MBH CFM EAT LAT VEL PD

AIR DATA

EWT LWT GPM PD

WATER DATA

SIZE ROW/FIN MAKE/MODEL REMARKS

HWC-4-2-1

HWC-4-4-1

HWC-4-4-2

MECH RM 4000M1 64 50 75 720 0.23 IN 130 110 6.36 7.06 FT 26x18 2 TRANE DTTB2340RM 4001FB

FPI

ROWS

PD

AIR

FPM

VELWATER DATA

GPMLWTEWT

AIR DATA

LATEATSMBH

TMBH

CURRENT CHILLED WATER COIL

UNIT NO LOCATION SERVES

MAX

CURRENT OA CFM

WHEEL

TYPE

FAN

TYPE

FAN

RPM

MAX

BHP W VOLTS PH RPM

ELECTRICAL

SUPPLY FAN SECTION

REMARKSMAKE/MODEL

AIR HANDLING UNIT SCHEDULE

CURRENT

AHU-4CE-15

AHU-4CE-16

22004TH FLOOR WEST 220MECH RM 4000M1 3 -2367 -AHU-4W-12 N/A 460 500

MAX13.8374.3 DB

62.5 WB

49.5 DB

49.0 WB -

AHU-4CW-13

INGENIA43.0 54.9PLENUM

FAN ARRAY

UNFIRED STEAM GENERATOR

UNIT

NO LOCATION

SYSTEM

SERVED PSI LBS/HR

STEAM INPUT STEAM OUTPUT

MAKE/MODEL REMARKSPSI LBS/HR

C-2 HW REHEAT COILS

C-1 HW REHEAT COILSMECH RM 4000M2

P-4

AHU-PE-20

AHU-4CW-14

AHU-4E-17

AHU-PW-19

MECH RM 4000M3

MECH RM 4000M3

MECH RM 4000M3

REHEAT COILS

REHEAT COILS

REHEAT COILS

5700 3 -4037 17.09 7457 (2)CDQ 460 619.1 (T)

295.0 (S) DESICCANT WHEEL

4000 3 -3332 - 460 25.15 -43.0 54.9

6900 3 -3071 - 460 43.37 -43.0 55.0

4500 3 -3980 - 460 28.28169.7 (T)

122.1 (S) 43.0 55.0

2700 3 -3272 - 460 16.9743.0 55.0

14,900 3 -2947 - 460 93.6543.0 54.9

12,000 3 -3112 - 460 75.4343.0 55.1

MECH RM 4000M2

MECH RM 4000M3

MECH RM 4000M3

MECH RM 4000M4

MECH RM PH2603

MECH RM PH2602

MECH RM 4000M2

USG-2 STEAMMECH RM 4000M3

USG-1 MECH RM 4000M2 STEAM 31445 25015 CEMLINE V45USG1018 -

37745 30015 -

360 0.05 IN 2.04 3.47 FT 33x9740RM 4000M7, 4107A, 4406, 4110

689 0.21 IN 6.09 6.54 FT 26x182240RM 4107

833 0.31 IN 8.49 4.56 FT 30x183125

675 0.23 IN 5.02 7.91 FT 32x121800

698 0.22 IN 6.01 5.68 FT 38x122210

592 0.22 IN 1.16 0.46 FT 10x9370

624 0.24 IN 1.20 0.49 FT 10x9390

588 0.20 IN 0.79 0.64 FT 10x6245

MECH RM 4000M2

MECH RM 4000M2

MECH RM 4000M3

MECH RM 4000M3

MECH RM 4000M3

MECH RM 4000M4

MECH RM 4000M4

MECH RM 4000M4

HWC-4-5-1

HWC-4-5-2

HWC-4-5-3

HWC-4-7-3

HWC-4-7-4

HWC-4-7-5

816 0.20 IN 0.96 0.54 FT 10x6340MECH RM 4000M4

MECH RM 4000M4

MECH RM 4000M4

HWC-4-7-6

HWC-4-7-9

HWC-4-7-10

CEMLINE V45USG1018

50 75 130 110

75 130 110

75 130 110

75 130 110

75 130 110

75 130 110

75 130 110

75 130 110

75 130 110

75 130 110

75 130 110

MODEL

VSR200

AIR SEPARATOR

ITEM MANUFACTURER

SPIROTHERM 6.3"

DIAMETER

GPM

19"

HEIGHT

SIZE

REMARKS

AS-1

VSR200SPIROTHERM 6.3"19" -AS-2

SERVICE

EXPANSION TANK SCHEDULE

ITEM MODEL LOCATION

DIA.

VOLUME

ACCEPT.

HOT WATER

TYPE

INITIAL

PRESS.

FILL

SIZE

HEIGHT

REMARKSMAKE

BELL & GOSSETTET-1 DIAPHRAGMHFT-15 1.0 8"

(GAL.)

HOT WATERBELL & GOSSETTET-2 DIAPHRAGMHFT-15 1.0 8"12-5/8"

MECH RM 4000M2

MECH RM 4000M3

12 PSI

12 PSI

NOTES:

MANUFACTURERITEM MODEL

SIZE (INCHES)ENT AIR

STEAM HUMIDIFIER SCHEDULE

CFMLOCATION

DB°F DB°F%RH

LVG AIR

%RH PSIG

STEAM

WIDTH HEIGHT

LBS\HR

MAX.

ABSORB.

DISTANCE

1. PROVIDE DRAIN COOLER FOR EACH HUMIDIFIER.

2. REFER TO FLOW DIAGRAMS FOR QUANTITY.

DRI-STEEM ULTRA-SORB LV 7400 65 54 70 50 15 MATCH UNIT MATCH UNIT 27.64H-4W-12

H-4CW-13

H-4CW-14

H-4CE-15

H-4CE-16

DRI-STEEM ULTRA-SORB LV

DRI-STEEM ULTRA-SORB LV

DRI-STEEM ULTRA-SORB LV

DRI-STEEM ULTRA-SORB LV

MATCH UNIT MATCH UNIT

MATCH UNIT MATCH UNIT

MATCH UNIT MATCH UNIT

MATCH UNIT MATCH UNIT

6"

3. DISPERSION TUBES SHALL BE INSULATED TYPE.

H-4E-17 DRI-STEEM MATCH DUCT MATCH DUCT6500ULTRA-SORB LV

TSP ESP

6.5"

8.13"

5.5"

6.5"

6.0"

6.5"

6.5"

6.5"

3.0"

3.0"

2.5"

3.0"

3.0"

3.0"

3.5"

3.5"

N/A

N/A

N/A

N/A

N/A

N/A

NOTES: 1. PROVIDE CONDENSATE BLOWDOWN COOLER FOR EACH UNFIRED STEAM GENERATOR

H-PW-19 DRI-STEEM ULTRA-SORB LV MATCH UNIT MATCH UNIT15500

H-PE-20 DRI-STEEM MATCH DUCT MATCH DUCT17500ULTRA-SORB LV

AHU-4W-12

AHU-4CW-13

AHU-4CW-14

AHU-4CE-15

AHU-4CE-16

AHU-4E-17

AHU-PW-19

AHU-PE-20

6"

6"

6"

6"

6"

6"

6"

60 43

64 55

64 55

64 55

64 55

64 55

64 55

TRANE CDQ

INGENIA

INGENIA

INGENIA

INGENIA

INGENIA

INGENIA

PLENUM

FAN ARRAY

PLENUM

FAN ARRAY

PLENUM

FAN…