320257_DWG_MECH_INSTALLATION TENT_CP-HOVEY.pdf
PDF 3 MB Posted
- Solicitation number
- W90VN824R0072
About this file
This document is a set of mechanical drawings and specifications for the installation of a Dining Facility (DFAC) Tension Fabric Structure (TFS) at Camp Hovey. The drawings detail the mechanical systems required, including HVAC equipment, kitchen equipment, plumbing, and fire protection. Key details include:
The scope of work involves relocating existing kitchen equipment from the main DFAC to the small DFAC TFS, installing new HVAC systems (30 heat pumps, 10 air curtains, 6 dehumidifiers), kitchen equipment (dishwasher, tables, etc.), fire extinguishers, and ceiling fans. The contractor shall verify existing conditions, submit shop drawings, and be responsible for any damage to existing items. The mechanical systems must be installed in compliance with applicable codes and specifications. Drawings provide layouts, equipment schedules, and general notes.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
M-1
MECHANICAL
M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S
NTS
PD
Pa
OS&Y
OXY
OD
OAIL
OA
QT
PRV
PPM
POL
POC
PLMB
PH
PG
RT
RPM
RH
RDTR
RA
R12, R22
QTY
A B B R E V I A T I O N S
SBM
SAN
SA
SCH
FLOWMETER, ORIFICEBUTTERFLY
REFRIGERANT LIQUID
CHILLED WATER SUPPLY
CHILLED WATER RETURN
AIR COOLED CONDENSING UNIT
AIR CONDITION UNIT (S)
APPARATUS DEW POINT
AIR CONDITION (-ING,-ED)
CHILLED/HOT WATER RETURN
AMERICAN WIRE GAUGE
PRESSURE, BAROMETRIC
CUBIC METER PER HOUR
CHILLED/HOT WATER SUPPLY
CAPACITYCAP
CONNECTION
CONTINUE
COMPRESSOR
CUBIC METER
CPRSR
CONN
CONT
CU M
CHILLED WATER
CAST IRON PIPE
CIRCUIT
CLASSIFICATION
COOLING LOAD
COEFFICIENT
COUNTER CLOCKWISE
CLASS
CLG LOAD
COEF
CMH
CIP
CCW
CHW
CKT
ACV ALARM CHECK VALVE
AVERAGEAVG
BOILING POINT
CENTIGRADE
BAROMETER(-TRIC)
BRAKE HORSEPOWER
BP
BHP
C
BARO PR
AWG
BARO
ALUMINUM
ALTITUDE
AMBIENT
AIR HANDLING UNIT
AMPERE(AMP, AMPS)
APPROXIMATEAPPROX
ALT
AMB
AMP
AIR COND
ADP
AL
AHU
AIR COOLED
ACCU
ACLD
ACU
CHR
C/HWR
C/HWS
CHS
RL
D DRAIN
DIAMETER, INSIDE
ISOMETRIC
IRON PIPE SIZE
JOULE
THERMAL CONDUCTIVITY
KILOGRAM
KILOGRAM PER SQ. CENTIMETER (GAUGE)
KILOGRAM PER SQ. CENTIMETER
KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)
KILOCALORIE PER HOUR
EXPANSION JOINT
EXPLOSION PROOF
FIRE HOSE CABINET
FULL LOAD AMPERES
ENTERING WATER TEMP
EVAPORAT (-E,-ING,-ED,-OR)
EXTERNAL STATIC PRESSURE
FACE AREA OR FRESH AIRFA
FHC
FHY
FLA
FIRE HYDRANT
ESP
EXPJT
EWT
EVAP
EP
EQPT
ENT
EFF
EQUIPMENT
ENTERING
EFFICIENCY
KG/SQ CM
KG/SQ CM A
KG/SQ CM G
KG
KCAL/HR
J
K
ID
ISO
IPS
NO
N.O.
NIC
NPT
MPS
NC
N/A
N.C.
MAX
MIN
MPH
MM
NOT IN CONTRACT
NATIONAL TAPER PIPE (THREAD)
NUMBER
NORMALLY OPEN
MINIMUM OR MINUTE
METERS PER HOUR
METERS PER SECOND
NORMALLY CLOSED
NOISE CRITERIA
NOT APPLICABLE
MAXIMUM
MILLIMETER R
FEMALE PIPE THREAD
FUEL OIL
GALVANIZED STEEL
GAGE OR GAUGE
FIXTURE
FEED WATER PUMP
FACE VELOCITY
FLUSH VALVE
FREQUENCY
FIBERGLASS REINFORCED PLASTIC
HORIZONTAL
HOT WATER HEATER
HOT WATER
HOUR(S)
HORSEPOWER
MERCURY
HEAD
HOSE BIBB
HERTZ
GRAMS
FRPCWP CIRCULATING WATER PUMP
DIRECT EXPANSION
DRY PIPE VALVE
EQUIVALENT DIRECT RADIATION
ENTERING AIR TEMPERATURE
DOUBLE POLE DOUBLE THROW
DEWPOINT TEMPERATURE
DRY BULB TEMPERATURE
DECIBEL OR DRY BULB
DIESEL OILDO
ECON
ECC
EAT
EDR
DX
DPV
DPDT
DPT
ECONOMIZER
ECCENTRIC
o
DIFF
DIAG
DIA or
DIV
DBT
DB
DIFFERENCE
DIAGRAM
DIAMETER
DIVISION
DEGREE
HR
HORIZ
HWH
HW
HZ
HP
HG
HD
HB
GALVS
GA
GR
FXTR
FWP
FVEL
FV
CUBIC MILLIMETER
CLOCKWISE OR COLD WATER
COEFFICIENT, VALVE FLOWCv
CU MM
CW
PLUG VALVE
THREE WAY
FPT
FO
FREQ
GATE, ANGLE
GATE, GLOBE
GLOBE
GATE
CONTROL
KJ KILOJOULE
LH
LT
LWT
LPS
M
LL
LPD
LPH
LM
LAV
LAT
LBS
LG
KW
KWH
L
LATENT HEAT
LEAVING WATER TEMPERATURE
LITERS PER HOUR
LITERS PER SECOND
LAUNDRY TRAY
METERS
LIQUID LINE
LITERS PER DAY
LINEAR METER
LEAVING AIR TEMPERATURE
LAVATORY
POUNDS
LENGTH
KILOWATT
KILOWATT HOUR
LITERS
P
FLOWMETER, VENTURI
FLOW SWITCH
PRESSURE SWITCH
PRESSURE GAUGE AND COCK
PUMP (INDICATE USE)
STRAINER
STRAINER, BLOW OFF
KG/SM
KG/SM A
KG/SM G
PS
P
OFM
FS
VFM
KILOGRAM PER SQ. METER
KILOGRAM PER SQ. METER (ABSOLUTE)
KILOGRAM PER SQ. METER (GAUGE)
JACKET WATER RETURN
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
PUMPED CONDENSATE
JACKET WATER SUPPLY
VACUUM PUMP DISCHARGE
FUEL OIL TANK VENT
CONDENSATE WATER SUPPLY
CONDENSATE WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
MEDIUM TEMPERATURE HOT WATER RETURN
LOW TEMPERATURE HOT WATER SUPPLY
LOW TEMPERATURE HOT WATER RETURN
PIPE TO BE REMOVED
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
LPS
CONTROL AIR MAIN
air conditioning and refrigeration
RD
RS
(NAME)E
(NAME)
M
EXISTING PIPE
COMPRESSED AIR
VACUUM (AIR)
HWR
VAC
A
MTWS
MTWR
HWS
FOD FUEL OIL DRAIN
FOR
CS
CR
FOV
FOG
FOS FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL GAUGE
PC
VPD
MU
LPC
BBD
MAKE UP WATER
MPS
MPC
JWR
JWS
heating
PIPING
CHECK, SWINGSANITARY DRAIN
PITCH OR PIPE, UP(U), DOWN(D)
FLOOR SINK (200mm x 200mm)
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
valves : (for selective actuators)
PLAN
HOSE BIBB
AIR LINEA
BALL
ELEV.
BACKFLOW PREVENTER
PIPE SLEEVE
(NAME)
ACID
200mm x 200mm
SURFACE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
CHEMICAL SUPPLY PIPES
FUNNEL DRAIN, OPEN
FCO
FD
SCO
FLOOR OR GRADE
FLOOR OR GRADE
CONDENSATE DRAIN BELOW
CONDENSATE DRAIN ABOVE
ACID WASTE
GASG
CD
CD
AIR VENT, MANUAL
AIR VENT, AUTOMATIC
W/ MEASURING TAP
EXPANSION LOOP
EXPANSION JOINT
BALL JOINT
ANCHOR, MAIN
ANCHOR, INTERMEDIATE
ALIGNMENT GUIDE
AIR SEPARATOR
FLEXIBLE CONNECTOR
SQUARE HEAD BALANCING COCK
EJ
S
MV
AVV
CHECK, NON-SLAM
CONTROL, ELECTRIC-PNEUMATIC
CONTROL, PNEUMATIC-ELECTRIC
QUICK OPENING
PRESSURE REDUCING
NEEDLE
LOCK SHIELD
HOSE END DRAIN
SAFETY
RELIEF
SQUARE HEAD BALANCING COCK
QUICK CLOSING, FUSIBLE LINK
R
S
PE
EP
plumbing
COLD WATER
HOT WATER RETURN
HOT WATER SUPPLY
VENT
MOTOR ELECTRIC
DIAPHRAGM
valves, special duty :
SOLENOIDS
valve actuators
M
FDAD
SUCTIONQUANTITY SUCT
TONS OF REFRIGERATION
TEMPERATURE DIFFERENCE
HEAT TRANSFER COEFFICIENT
SANITARY
SUBMERSIBLE
SUPPLY AIR
SCHEDULE
RADIATOR
REFRIGERATION TON
REVOLUTIONS PER MINUTE
RELATIVE HUMIDITY
RETURN AIR
THERMAL RESISTANCE
REFRIGERANT (12, 22, ETC)
TYPICALTYP
URINAL
UNIT HEATER
UR
UH
U
THERMOSTAT
THICKNESS
THERMOMETER
TEMPERATURE
SYMBOL
TSTAT
TONS
THERM
THK
TEMP
TD
SYM
SINGLE POLE DOUBLE THROW
LPH, STANDARD CONDITIONS
LPS, STANDARD CONDITIONS
LPD, STANDARD CONDITIONS
SAYBOLT SECONDS UNIVERSAL
SAYBOLT SECONDS FUROL
SENSIBLE HEATOUTSIDE AIR INTAKE LOUVER SH
PRESSURE DROP OR DIFFERENCE
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PERCENT
PARTS PER MILLION
POINT OF CONNECTION
PLUMBING
PETROLEUM, OIL AND LUBRICANTS
QUART
OUTSIDE SCREW & YOKE
DIAMETER, OUTSIDE
PRESSURE GAGE
POLE
PASCAL
OXYGEN
SPRINKLERSPR
STEEL
STANDARD
STEAM
SQUARE
STAINLESS STEEL
STORAGESTOR
STL
STD
ST
SSU
SST
SSF
SQ
SENSIBLE LOAD
STATIC PRESSURE
SQUARE METER
SPECIFICATION
SPDT
SPEC
SM
SP
SLPH
SLPS
SLPD
SL
ALARM CHECK VALVE
SIDEWALL SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
FIRE DEPARTMENT CONNECTION
PRE-ACTION VALVE
NOT TO SCALE
OUTSIDE AIR
(2-WAY SHOWN)
DRY-PIPE VALVE
SECOND
SAFETY FACTOR
SPECIFIC GRAVITYSG
SF
SEC
VARIABLE AIR VOLUMEVAV
VENTILATION
PRESSURE, DYNAMIC(VELOCITY)
WATER-COOLED
WATER CLOSET
WATTHOUR OR WATER HEATER
WET BULB TEMPERATURE
WATERPROOF
WSHR
WCLD
WTRPRF
WH
WT
W/
WD
WC
WBT
WEIGHT
WITH
WASHER
WIDTH
VP
VOL
WB
W
VISC
VERT
VENT
VEL
VOLUME
WET BULB
WATT
VISCOSITY
VERTICAL
VELOCITY
MANUAL VOLUME DAMPER
SMOKE DAMPER (PROVIDE ACCESS DOOR)
PNEUMATIC OPERATED DAMPER
VLV
V
VAC
M
VALVE
VOLT
VACUUM
SPLITTER DAMPER
SD
AD
VD
grilles, registers and diffusers :
SG
SR
600/300
300x150
200mm NCD
FIGURE IS ON TOP
810mm x 400mm dampers
ELBOW, TURNED DOWN
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
TEE, OUTLET DOWN
TEE, SINGLE SWEEP
sprinkler
UNION, SCREWED
UNION, FLANGED
TEE, OUTLET UP
TEE
LATERAL
CONNECTION, BOTTOM
CONNECTION, TOP
ELBOW, TURNED UP
BUSHING
CAP
WELDED
FLANGED
SOLDERED
SCREWED BELL AND SPIGOT
SOLVENT CEMENT
SOUND ATTENUATOR
DETECTORS, FIRE AND/OR SMOKE
ELECTRIC MOTOR OPERATED DAMPER
FIRE DAMPER (PROVIDE ACCESS DOOR)
BACKDRAFT DAMPER
BDD
S
TRANSITION
TURNING VANES
SF
CHANGE OF ELEVATION, RISE(R), DOWN(D)
DUCT SECTION, NEGATIVE PRESS., FIRST
ACCESS DOOR, VERTICAL OR HORIZONTAL
COWL, (GOOSENECK) AND FLASHING
ACOUSTICAL LINING
FLEXIBLE DUCT
FLEXIBLE CONNECTIONFC
FIGURE IS ON TOP
R
AD
47.2
TG
94.4
UC 13mm
DG
500/300L
DUCT WORK
810mm x 400mm
810mm x 400mm
THERMOSTAT, ELECTRIC
TRAP, ELECTRIC (INDICATE TYPE)
fitting :
R
THERMOMETER
EXHAUST AIR GRILLE OR REGISTER, CEILING
DUCT SECTION, POSITIVE PRESS., FIRST
DIRECTION OF FLOW
SR
DIFFUSER, LINEAR
RETURN AIR GRILLE OR REGISTER, CEILING
CEILING DIFFUSER, SQUARE TYPE
CEILING DIFFUSER, ROUND TYPE (200mm
(600mm x 300mmH, 472 LPS)
UNDERCUT DOOR (13mm, 47.2 LPS)
DOOR GRILLE (300mmx150mmH)
NECK DIAMETER)
TRANSFER GRILLE ASSEMBLY
LOUVER, DOOR OR WALL
(500mmWx300mmH, 94.4 LPS)
RG
RR
SUPPLY AIR GRILLE OR REGISTER, SIDEWALL
EXHAUST AIR GRILLE OR REGISTER, CEILING
SUPPLY AIR GRILLE OR REGISTER, CEILING
ER
SG
EG
EXISTING WORK TO BE REMOVED.
POINT OF CONNECTION NEW TO EXISTING
OR END OF DEMOLITION WORK
EXISTING WORK TO REMAIN.(E)
(R) REMOVE EXIST WORK
D
C
A
B
& SYMBOLS AND ABREVIATION
MECHANICAL MATERIAL INDICATIONS
CHONG, ST
INSTALLATION TENT
CAMP HOVEY
320257
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
M-2
MECHANICALMECHANICAL
MECHANICAL GENERAL NOTES
EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.
10. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE CLEARANCE, COMMENCING ANY CONSTRUCTION OR RENOVATION.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS PRIOR TO
8. ALL VALVES ON WET PIPE SYSTEM SHALL MEET NFPA 13 REQUIREMENT.
7. INSATLL SYSTEM TEST CONNECTION ON WET PIPE SYSTEM AND SHALL BE LOCATED AT THE MOST REMOTE BRANCH LINE.
6. SPRINKLERS WITH O-RINGS ARE NOT PERMITTED. PLUG TYPE TAMPER SWITCH SHALL NOT BE USED.
TO ALL RISER AND TRIM, SECTIONAL VALVES, INSPECTIORS TEST VALVES AND DRAINS.
5. PROVIDE LABEL TAG INDICATING "NORMALLY OPEN" OR "NORMALLY CLOSED" ON ALL VALVES INCLUDING AND NOT LIMITED
FLEXIBLE COUPLINGS, CLEARANCES, AND SEPARATION ASSEMBLES.
PIPING AGAINST DAMAGE WHERE SUBJECT TO EARTHQUAKES". INCLUDING, BUT NOT LIMITED TO, SWAY BRACINGS,
4. PROVIDE ALL SEISMIC PROTECTION MEASURES FOR THE FIRE PROTECTION SYSTEM IAW NFPA 13 FOR "PROTECTION OF
PIPES LESS THAN 50MM (2 INCHES) IN NOMINAL.
OF FLUID CARRIED AND DIRECTION OF FLOW. LABELS ARE NOT REQUIRED ON SPRINKLER SYSTEM BRANCH LINES AND
CONFORMING TO ASME/ANSI A13,1-1996 "SCHEME FOR IDENTIFICATION OF PIPING SYSTEMS", INDICATING THE TYPE
3. MARK ALL EXPOSED INTERIOR PIPING AT 8 METER(26 FT) INTERVALS, WITH PLASTIC WRAPAROUND TYPE PIPE LABLES
2. THE CLEARANCES AROUND PIPE PENETRATION AT FIRE RATED WALLS AND/OR FLOOR SHALL BE PROPERLY SEALED
WITH APPROVED FIRE STOPPING MATERIAL IAW SPECIFICATION 07 84 00.
11. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS CAUSED
NO ADDITIONAL COST TO THE GOVERNMENT, INCLUDING, BUT NOT NECESSARILY LIMITED TO ITEMS SUCH AS WALLS, CEILLING, ROOF, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS AS NECESSARY
TO NECESSARY TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE PROTECTION SYSTEM AT
19. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PROVIDE ACCESS DOORS
IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTOR, BACKDRAFT DAMPERS AND FOR ANY ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION 12"X12" ACCESS
PANELS FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANEL TO INSURE THAT THE EQUIPMENT
CAN BE MAINTAINED ADEQUATELY. PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH GYPBOARD OR
CONCEALED CEILINGS.
20. INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1 / 4INCH PER 1FOOT. INSULATE ALL SEWER PIPING
RECEIVING AIR CONDITIONING CONDENSATE DRAINS, OR ANY OTHER COLD LIQUID WHICH MAY CREATE
CONDENSATION, FROM SINK BODIES EXPOSED TO AIR BELOW THE FLOOR.
21. PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN 30 DEGREES OR
USE RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH TAKE-OFFS FROM THE MAIN DUCT.
PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.
22. PIPING SYSTEM SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS AND FLUSHED UNTIL
ALL WATER BEING FLUSHED IS CLEAR AS TAP WATER.
23. ALL CONDENSATE DRAINS FROM COOLING UNIT (AS NOTED ON THE DRAWINGS) SHALL BE PROVIDED WITH
SHUT-OFF VALVE WITHIN 1M OF THE UNIT.
24. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION ACTIVITIES,
1. THE EQUIPMENT SHOWN ON THE PLAN ARE SUGGESTED LOCATIONS. FINAL LAUOUT SHALL BE VERIFIED AND
IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND EQUIPMENT LISTINGS.
THE CONTRACTOR SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH, LIGHTING FIXTURES, AND HVAC DEVICES.
ALL EQUIPMENT SHALL BE UL LISTED AND/OR FM APPROVED IN ACCORDANCE WITH NFPA 13, NFPA 20 AND THE PROJECT
SPECIFICATION.
BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AT HIS OWN COST.
13. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE ANY EXISTING EQUIPMENT
DUCT WORK, PIPING ETC. DAMAGED DUE TO THE WORK PERFORMED UNDER THIS CONTRACT SHALL
BE REPAIRED OR REPLACED BY THIS CONTRACTOR AT HIS OWN COST.
14. CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY THE
CONTRACTING OFFICER.
AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.
15. FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS PROJECT.
THE DETAILS SHALL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK.
16. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH DETAILS
SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND
SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL.
17. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN STRICT
ACCORDANCE WITH APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL, O & MA STANDARD TECHNICAL
SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, ADJUSTING AND BALANCING (TAB)
REPORT SHALL BE SUBMITTED TO THE PROJECT COR FOR GOVERNMENT REVIEW AND APPROVAL.
18. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA STATIC
PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.
SCOPE OF WORK
BY A LICENSED OR CERTIFIED INSTALLER.
8. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPECIFICATION
7. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
CONDUITS AND ALL NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.
6. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD OR CONCEALED CEILINGS.
5. PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE DRAWINGS OR NOT.
UL LISTED.
DAMPER RATINGS SHALL BE COMPATIBLE WITH THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE
4. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS. FIRE
TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES. REFER
THE CONTRACTING OFFICER.
2. THE CONTRACTOR SHALL SUBMIT MECHANICAL SYSTEM INSTALLATION SHOP DRAWINGS FOR APPROVAL BY
CLEARANCE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.
1. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE
AND NOTE
GENERAL NOTES, SCOPE OF WORK
NOTE :
WORK CLASS "L" (CONSTRUCTION WORK)
CHONG, ST
INSTALLATION TENT
CAMP HOVEY
320257
IN THE SMALL DFAC AS SHOWN ON DRAWINGS.
8. INSTALL NEW CEILING FANS(4SETS) AND ALL ASSOCIATED ACCESSORIES
IN THE SMALL DFAC AS SHOWN ON DRAWINGS.
7. INSTALL NEW AIR CURTAINS(10SETS) AND ALL ASSOCIATED ACCESSORIES
IN THE SMALL DFAC AS SHOWN ON DRAWINGS.
6. INSTALL NEW FIRE EXTINGUISHER(8SETS) AND ALL ASSOCIATED ACCESSORIES
5. INSTALL NEW DEHUMIDIFIERS(6SETS) IN THE SMALL DFAC AS SHOWN ON DRAWINGS.
ALL ASSOCIATED ACCESSORIES IN THE SMALL DFAC AS SHOWN ON DRAWINGS.
4. INSTALL NEW PACKAGED HEAT PUMP UNITS(30SETS) INCLUDING PIPING, CONC. PAD AND
ALL ASSOCIATED ACCESSORIES IN THE SMALL DFAC AS SHOWN ON DRAWINGS.
3. INSTALL NEW DISHWASHER, TABLE ROLLER, PRE-WASHING TABLE AND CLEAN DISH TABLE AND
AND ALL ASSOCIATED ACCESSORIES FOR SMALL DFAC AS SHOWN ON DRAWINGS.
2. CONNECT TO KITCHEN EQUIPMENT AND UTILITY LINE(HOT, COLD(STAINLESS STELL 304) & SEWER PIPING)
1. RELOCATE EXISTING KITCHEN EQUIPMENT FROM DFAC TO SMALL DFAC AS SHOWN ON DRAWINGS.
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
THE CONTRACT DOCUMENT REQUIRMENTS.
SHALL BE RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR
NOTE :
MECHANICAL
M-3
CHONG, ST
REPAIR DFAC. BLDG. S-4158
CAMP HOVEY
305504
AND NOTE
MECHANICAL EQUIPMENT SCHEDULE-1
1 131DISHWASHER / ELEC. TYPE 208 3 5-1/4 49.55 2"3/4"
REMARKS
1 TABLE ROLLER
1 PRE-WASHING TABLE
1 CLEAN DISH TABLE
QTY.ITEM NO SERVICE T Y P E
COOLING CAP
(W)
REMARKSREFRIGERANT
TYPE
VOLT/PH/HZ
POWER INPUT
(W)
CAPACITY SHALL BE BASED ON 35DEG C 31 2
ALL HEAT PUMP UNIT REFRIGERANT PIPING SHALL BE INSTALLED PERMANUFACTURER RECOMMENDATIONS.WIRELESS REMOTE CONTROLLER.NOTES :
MOP
(A)
31 2 4
HP
SMALL DFAC30
PACKAGED SPLIT HEAT PUMP TYPE
FLOOR MOUNTED
14,500 3,830 220/1/60 R-410A30A16,300
HEATING CAP
(W)
5 3 YEARS WARRANTY.
(4.1TON) (4.2TON)
QTY.ITEM NO SERVICE T Y P E DESCRIPTION
FE
8 KITCHEN AREA
1 CAPACITY(KG) : 6
2 OPERATING TEMPERATURE : +5 C TO + 55 C
3 WORKING PRESSURE AT 27 C : 15bar
MAX. SERVICE PRESSURE : 1.9Mpa
TEST PRESSURE : 35bar
6 AVERAGE DISCHARGE TIME(S) : 75
REMARKST Y P ESERVICEITEM NO QTY
VOLT/PH/Hz
CAPACITY
DEHUMIDIFIER
(CMM)
FAN CAP.
15.5220 / 1 / 60DIINING ROOMS 280 LITER/DAY
AUTO DRAIN TYPE WITH PUMP
FLOOR MOUNTED,
NOWOOEL CO. LTD. MODEL NO.:NED-285P OR APPROVED EQUAL.
POWER
2,180W/HR
ELECTRICAL
DHU
Q'TY
ITEM NO DESCRIPTION
REMARKS
HP
FAN MOTOR
ITEM NO SERVICE T Y P EQTY
VOLT/ PH/ HZ
208 / 1 / 60
CEILING FAN(LOCAL PRODUCT)
AIR CURTAIN(LOCAL PRODUCT)
PACKAGED HEAT PUMP UNIT(LOCAL PRODUCT)
DEHUMIDIFIER(LOCAL PRODUCT)
DINING AREA
REMARKS
DW
DW
1A
DW
1B
DW
1C
AC
CF
LG ELECTRINICES MODEL "NO. RPUW052S2S OR APPROVED EQUAL.
1/ 2CEILING HUNG
CONTROL:ON-OFF, DIRECTION(CW OR CCW) &
SPEED BY WIRELESS CONTROLLER(LCD TOUCH)
BLADE
DIA.:3M,
5 AIRFOIL TYPE
SN INNOVATION CO., LTD, MODEL : LCF300/AIR360
OR APPROVED EQUAL.
POWER : 485W, 208V, 1PH, 60HZ.
WIND SPEED : 17m/s
M E C H A N I C A L E Q U I P M E N T S C H E D U L E - 1
(K CLASS)
KITCHEN FIRE EXTINGUISHER
FIRE EXTINGUISHER FOR KITCHEN AREA
RACK COVEYOR TYPE 2-TNAK
MFR. "SOMATKOREA" MODEL : SJM-R2E OR APPROVED EQUAL.
SIZE: 2500 * 750 * 850
MFR. "SOMATKOREA" OR APPROVED EQUAL.
SIZE: 1500 * 750 * 850
MFR. "SOMATKOREA" OR APPROVED EQUAL.
SIZE: 2000 * 750 * 850
MFR. "SOMATKOREA" OR APPROVED EQUAL.
DISHWASHER(LOCAL PRODUCT)
SYMBOL QTY DESCRIPTION
VOLTS PH
POWER
AMPS HP KW
CORD/
PLUG
DIR
CONN
WATER
CW HW
WASTE
DIR IND
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-4
CHONG, ST
INSTALLATION TENT
CAMP HOVEY
320257
SCALE : 1 / 100
KITCHEN AREA FOOD SERVING AREA
DINING AREA (300 SEATS)
AREA
ENTRANCE
EXIT AREA
DISH WASHING AREA
(TYP OF 30)
NEW CONC.PAD
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
CASHIER COUNTER QUEUING AREA
HP
NOTE :
2. SUBMIT SHOP DRAWINGS HEAT PUMP SYSTEM.
HEAT PUMP SYSTEM IN THE SMALL DFAC FOR APPROVAL BY COR.
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF
HP
HP
DRAIN
DHU
DRAIN
DHU
DRAIN
DHU
DRAIN
DHU
DRAIN
DHU
DRAIN
DHU
AC
AIR CURTAIN(TYP OF 10)
AC
AC
AC
AC
AC
AC
AC
AC
AC
DEHUMIDIFIER(TYP OF 6)
HEAT PUMP(TYP OF 30)
GROUND NEW HVAC PLAN -1
HP
GROUND NEW HVAC PLAN-1
AND NOTE
M4
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-5
CHONG, ST
INSTALLATION TENT
CAMP HOVEY
320257
SCALE : 1 / 100
KITCHEN AREA FOOD SERVING AREA
QUEUING AREA
DINING AREA (300 SEATS)
AREA
ENTRANCE
EXIT AREA
DISH WASHING AREA
CASHIER COUNTER
FEC
FE
CF
CF
CF
CF
CEILING FAN(TYP OF 4)
(GFGI)
KITCHEN HOOD
(GFGI)(TYP)
KITCHEN HOOD
(GFGI)(TYP)
KITCHEN HOOD
(GFGI)(TYP)
KITCHEN HOOD
(GFGI)(TYP)
DISHWASHER HOOD
GROUND NEW HVAC PLAN -2
(TYP)
KITCHEN HOOD(GFGI)
EXHAUST FAN FOR
(TYP)
KITCHEN HOOD(GFGI)
EXHAUST FAN FOR
NOTE :
REPLACED BY THIS CONTRACTOR AT HIS OWN COST.
THE WORK PERFORMED UNDER. THIS CONTRACT SHALL BE REPAIRED OR
DAMAGE ANY EXISTING KITCHEN EQUIPMENT, PIPING ETC. DAMAGED DUE TO
3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT
EXISTING KITCHEN EQUIPMENTS.
DIMENSIONS AND PIPING SIZE PRIOR TO REMOVING AND REINSTALLING
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CONDITION,
KITCHEN EQUIPMENTS IN TENT FOR APPROVAL BY THE DFEC USER.
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF
(TYP)
KITCHEN HOOD(GFGI)
EXHAUST FAN FOR
FIRE EXTINGUISHER(TYP OF 8)
LEGEND:
GFGI GOVERNMENT FURNISHED AND GOVERNMENT INSTALLED
GROUND NEW HVAC PLAN-2,
LEGEND AND NOTE
M5
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-6
20 15
1 SINK HEATER
POWER SOAK UNIT
PRE-RINSE
FAUCET
NO QTY DESCRIPTION
EQUIPMENT
3/4"
3/4"
1/2"
3/4"
1/2"
PLUMBING
WATER
CW HW
WASTE
DIR IND
1"2 HOT SERVING TABLE
GRIDDLE 1
ICE MACHINE 1/2" 3/4"1
TWO DECK CONVECTION OVEN2
TWIN 6 GALLON STEAM KETTLE 1/2" 1/2" 1-1/2"1
3"2 DOOR ROLL-THRU REFRIGERATOR2
WORKTABLE3
40 GALLON BRAISING PAN
TRAY SLIDELOT
6 REFRIGERATED COLD PAN 3/4"
2 SNEEZEGUARD WITH LIGHTS
3 HEATED WELLS
1 DISPLAY REFRIGERATOR 3/4"
4 COFFEE BUNN
2 BREAD CASE
1 RICE COOKER
1 MILK DISPENSER
1 MICROWAVE
1 CONVEYOR TOASTER
BEVERAGE/CONDIMENT COUNTER2
2"
WARMER
3/4"
1/2" 3/4"
1/2"
1 RANGE FLATTOP
GENERAL REMARKS
EXISTING EQUIPMENT TO BE REUSEDCLASS E
LEASED EQUIPMENT
INSTALLED FROM CONSTRUCTION FUNDS
CONTRACTOR FURNISHED, CONTRACTOR
CLASS L
LEGEND:
CLASS A
SCALE : 1 / 100
CLASS
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
REPLACED BY THIS CONTRACTOR AT HIS OWN COST.
THE WORK PERFORMED UNDER. THIS CONTRACT SHALL BE REPAIRED OR
DAMAGE ANY EXISTING KITCHEN EQUIPMENT, PIPING ETC. DAMAGED DUE TO
3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT
EXISTING KITCHEN EQUIPMENTS.
DIMENSIONS AND PIPING SIZE PRIOR TO REMOVING AND REINSTALLING
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CONDITION,
KITCHEN EQUIPMENTS IN TENT FOR APPROVAL BY THE DFEC USER.
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF
PLAN-1 AND FOOD SERVICE EQUIPMENT
FOOD SERVICE EQUIPMENT & UTILITY SCHEDULE -1
CHONG, ST
INSTALLATION TENT
CAMP HOVEY
320257
DISH WASHING AREA
EXIT AREA
OPENING
RETURN TABLE
AREA
ENTRANCE
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
KITCHEN AREA FOOD SERVING AREA
QUEUING AREA
DINING AREA (300 SEATS)
AREA
ENTRANCE
DISH WASHING AREA
CASHIER COUNTER
FEC
SMALL DFAC KITCHEN EQUIPMENT PLAN - 1
NOTE-1 :
NOTE-2 :
1 E27 REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)REACH-IN FREEZER
1 E28 REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
1 E29 REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
1 E30 REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
SORTING SHELF
SOILED DISHTABLE W/SCRAP TROUGH 1/2"
FOOD WASTE TROUGH COLLECTOR SYSTEM
2"
SMALL DFEC TENT KITCHEN EQUIPMENT
& UTILITY SCHEDULE-1. LEGEND & NOTE-1&2
M6
STAINLESS STELL 304.
3. THE COLD & HOT WATER PIPES SHALL BE CONSTRUCTED FROM
2. SUBMIT SHOP DRAWINGS HOT, COLD AND SEWER PIPING.
HOT, COLD AND SEWER PIPING IN THE SMALL DFAC FOR APPROVAL BY COR.
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF
2 E31 REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
E32 REMOVED & REINSTALL EXISTING EQUIPMENT(FROM DFAC TO TENT)
SILVER SOAK SINK
LOT DISH DOLLY
1-1/2"
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
M-7
SCALE : 1 / 100
KITCHEN AREA
FULL PARTITION
LOW PARTITION
(H: 800)
FULL PARTITION
SCALE : 1 / 50
M71-
DISH WASING AREA PARTIAL PLAN
EXISTING EQUIPMENT TO BE REUSEDCLASS E
LEASED EQUIPMENT
INSTALLED FROM CONSTRUCTION FUNDS
CONTRACTOR FURNISHED, CONTRACTOR
CLASS L
LEGEND:
CLASS A
NOTE :
REPLACED BY THIS CONTRACTOR AT HIS OWN COST.
THE WORK PERFORMED UNDER. THIS CONTRACT SHALL BE REPAIRED OR
DAMAGE ANY EXISTING KITCHEN EQUIPMENT, PIPING ETC. DAMAGED DUE TO
3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT
EXISTING KITCHEN EQUIPMENTS.
DIMENSIONS AND PIPING SIZE PRIOR TO REMOVING AND REINSTALLING
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CONDITION,
KITCHEN EQUIPMENTS IN TENT FOR APPROVAL BY THE DFAC USER.
1. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF
DISH WASHING AREA
DISH WASHING AREA
EXIT AREA
OPENING
RETURN TABLE
AREA
ENTRANCE
DINING AREA (300 SEATS)
QUEUING AREACASHIER COUNTER
FOOD SERVING AREA
HIGH PARTITION
(H: 2,000)
LOW PARTITION
(H: 800)
DISHWASHER
PLAN-2 AND FOOD SERVICE EQUIPMENT
FOOD SERVICE EQUIPMENT & UTILITY SCHEDULE -2
CHONG, ST
INSTALLATION TENT
CAMP HOVEY
320257
1C
DW
DW
1A
DW
1B
DW
SMALL DFAC KITCHEN EQUIPMENT PLAN - 2
SMALL DFEC TENT KITCHEN EQUIPMENT
& UTILITY SCHEDULE-2, DISHWASHING AREA
PARTIAL PLAN, LEGEND & NOTE
M7
M7
NO QTY DESCRIPTION
EQUIPMENT
KWVOLTS PH AMPS
POWER
HP
ELECTRICAL
PLUG
CORD/
CONN
DIR
PLUMBING
WATER
CW HW
WASTE
DIR IND
208 3 2"
GENERAL REMARKS CLASS
49.55 3/4"
PRE-WASHING TABLE
CLEAN DISH TABLE
TABLE ROLLER SIZE: 2500 * 750 * 850
SIZE: 2000 * 750 * 850
SIZE: 1500 * 750 * 850
RACK COVEYOR TYPE 2-TNAK A
A
A
A
DISHWASHER / ELEC. TYPE1
DW
1A
DW
1B
DW
1C
DW
| MECH_DWG_320257_INSTALLATION TENT, CP HOVEY(FINAL)-M1 |
| MECH_DWG_320257_INSTALLATION TENT, CP HOVEY(FINAL)-M2 |
| MECH_DWG_320257_INSTALLATION TENT, CP HOVEY(FINAL)-M3 |
| MECH_DWG_320257_INSTALLATION TENT, CP HOVEY(FINAL)-M4 |
| MECH_DWG_320257_INSTALLATION TENT, CP HOVEY(FINAL)-M5 |
| MECH_DWG_320257_INSTALLATION TENT, CP HOVEY(FINAL)-M6 |
| MECH_DWG_320257_INSTALLATION TENT, CP HOVEY(FINAL)-M7 |
File details come from the government source that posted it. Updated .