This document is Addendum No. 1 for the Sheffield-Woolley Structural Repairs/Additions – REBID II project at Hinds Community College's Raymond Campus in Raymond, Mississippi, with the project bid number HCC Bid #3195. The addendum, dated April 23, 2020, modifies the original Contract Documents from March 21, 2020, and includes two primary updates: 1) Pre-bid meeting minutes from a conference held on April 21, 2020, and 2) addition of Section 14240 for Electric Hydraulic Elevator Cab and Fixtures Upgrade to the Project Manual. The pre-bid conference was held at 1:30 PM in the Physical Plant Conference Room, with the purpose of outlining the project scope and bidding requirements, and providing an opportunity for potential bidders to ask questions and visit the site.

The project specifically involves a hydraulic passenger elevator upgrade, with most existing elevator components being retained. The elevator modernization includes upgrades to cab interior finishes, hall and car station fixtures, and various technical specifications for signals, controls, and communication systems. The contract includes a one-year warranty on materials and workmanship, and requires IUEC certified mechanics with documented multi-OEM equipment training. Sealed bids were to be received by April 30th at 2:00 PM, with a total construction period of 365 calendar days and liquidated damages of $500 per calendar day. The project is specifically for one hydraulic passenger elevator with existing characteristics such as 4000 lbs capacity, 150 fpm contract speed, and serving 4 floors.

View the file

Other files

File Type Posted
3195 Drawings.pdf PDF
3195 Project Manual.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM No. 1 April 23, 2020

Sheffield-Woolley Structural Repairs/Additions – REBID II Hinds Community College

Raymond Campus Raymond, Mississippi 39154

HCC Bid #3195/Professional’s Project #018-40

This Addendum, which contains revisions/clarifications to the Work contained in the Contract Documents dated March 21, 2020 shall become a part of the Drawings and Specifications as if bound therein. Other requirements shall remain as specified. The above Contract Documents are hereby modified, corrected, and/or supplemented by this Addendum as follows:

Item #1: Pre-bid Meeting Minutes:

Here-in attached are the Pre-bid minutes and sign-in sheet held on 21 April 2020.

Item #2: Project Manual, Section 14240:

Add the here-in attached Section 14240 Electric Hydraulic Elevator Cab and Fixtures Upgrade to the Project Manual.

END OF ADDENDUM No. 1

W. Randall Ward, AIA, LEED AP - Principal / Architect BRUMFIELD WARD & Associates, Architects, PA Sheffield-Woolley Structural Repairs/Additions – REBID II

Copyright ©2018

21 April 2020

2018 Sheffield-Woolley Structural Repairs/Additions – REBID II (Raymond Campus) HINDS COMMUNITY COLLEGE (Community College Board) Raymond, Mississippi HCC Bid # 3195 / BWA #018-40

• Pre-Bid Conference Minutes •

Date: 21 April 2020

Time: 1:30 PM

Location: Physical Plant Conference Room, Physical Plant & Auxiliary Services Building 505 Eats Main Street, Raymond, MS

CONFERENCE OBJECTIVE:

The purpose of the conference was to outline the Scope of the Project and the bidding requirements. It also provided an opportunity for Potential Bidders to visit the site and pose questions or request clarifications regarding the Contract Documents.

ATTENDEES:

See attached sign-in sheet

ITEMS DISCUSSED:

I. Introductions:

Α. Team Members:

• Owner:

Hinds Community College:

Representatives: William F. Campbell, Energy Conservation & Project Architect Jesse Jones, District Director of Energy and Maintenance Jason Pope,

• Design Team:

BRUMFIELD WARD & Associates, Architects, PA:

Principal-in-Charge: W. Randy Ward, AIA, LEED AP Project Architect: E. Lantz Kuykendall, RA, NCARB, CSI, CDT Project Manager: Scott Carpenter M&E: Edmonds Engineering Structural Engineer: Barry McKinley, P.E.

Β. Conference Participants - Introductions:

II. General Comments:

A. Owner’s Opening Comments.

B. Confirm Sign-In.

C. Minutes of Conference in forthcoming Addendum.

D. General overview of Project Scope was offered.

III. Review of Bidding Requirements / Advertisement for Bids

Sealed Bids to be received until Thursday, April 30th at 2:00 P.M. by the Office of the Director of Purchasing, D.G. “Sonny” Fountain Hall, 608 Hinds Blvd., Room 208.

• Instructions to bidders (Section 00100)

- Bidder’s Checklist

• Proposal Form (Section 00300)

- Name and Company, Officer’s Signature

- Base Bid and Unit Prices Numerically Written and Described in Words; if Discrepancy, the Written Words will Govern

- Unit Prices – This was discussed as a possible modification to the bid form

- Proposed Construction Team Management Members/Subcontractors Req’d.

- Construction Period – 365 calendar days

- Liquidated Damages in the Amount of $500.00 per Calendar Day

- Out of State Contractors – Copy of Non-resident Bidder’s Current State Law

- Addenda Acknowledgement

IV. Contract /Contract Bonds (Section 00500 / 00600) Discussed

V. Insurance Requirements (Section 00900) Discussed

VI. Summary of Work (Section 01010) Discussed

VII. Allowances (Section 01020) Reviewed

VIII. Temporary Facilities (Section 01500) Reviewed

IX. Product Substitutions (Section 01630) Discussed

X. Project Scope Reviewed

XI. Site Issues / Miscellaneous:

A) Site Security Discussion

B) Material Lay-Down Areas

C) Construction Execution (should not impede ongoing activities) / Work Hours

D) Tobacco-Alcohol-Drugs / Clothing

E) Cleanliness of Site

F) Safety

XIII. Question and Answer:

1. Complete Close Out Documents will be required for each phase of the work prior to starting the next phase.

Questions to be submitted in writing, emailed to wrwarchitect@gmail.com, and copied to elkarch5@gmail.com.

XIV. Site Visit. All interested participant visited the site.

Meeting Concluded at approximately 2:00 pm

Minutes Prepared By:

BRUMFIELD WARD and Associates, Architects, PA

E. Lantz Kuykendall, RA, CDT mailto:wrwarchitect@gmail.com mailto:elkarch5@gmail.com

ELECTRIC HYDRAULIC ELEVATOR CAB AND FIXTURES UPGRADE

PART 1 - GENERAL

1.1 WORK INCLUDED

A. Passenger elevator as follows:

1. Hydraulic Passenger Elevator

B. All engineering, equipment, labor, and permits required to satisfactorily complete elevator modernization required by Contract Documents.

C. Applicable conditions of Purchasers General, Special, and Supplemental Conditions.

D. Additional equipment or finishes furnished under other sections, installed under this section:

1. Car interior finishes

2. Elevator Hall Station Fixtures

3. Elevator Car Station

E. Cartage and Hoisting: All required staging, hoisting, and movement to, on, and from the site including new equipment, reused equipment, or dismantling and removal of existing equipment.

F. Unless specifically identified as “Reuse,” “Retain,” or “Refurbish,” provide new equipment.

G. Hoistway, pit, and machine room barricades as required.

1.2 DEFINITIONS

A. Terms used are defined in the latest edition of the Safety Code for Elevators and Escalators, ASME A17.1.

B. Reference to a device or a part of the equipment applies to the number of devices or parts required to complete the installation.

C. Provisions of this specification are applicable to all elevators unless identified otherwise.

1.3 QUALITY ASSURANCE

A. Approved Contractors:

1. Hydraulic Elevators: ThyssenKrupp.

B. Approved Cab Vendors

1. Car Enclosure: thyssenKrupp.

C. Approved Components

1. Fixtures, vandal-resistant: thyssenkrupp

D. Approved Installers: OEMs must meet criteria set in Contractor Pre-qualifications.

E. Warranty:

SECTION 14240

1. Material and workmanship of installation shall comply in every respect with Contract Documents. Correct defective material or workmanship which develops within one (1) year from date of final acceptance of all work to satisfaction of Purchaser and Consultant at no additional cost, unless due to ordinary wear and tear or improper use or care by Purchaser. Perform maintenance in accordance with terms and conditions indicated in the Preventive Maintenance Agreement.

2. Defective is defined to include, but not be limited to: Operation or control system failures, car performance below required minimum, excessive wear, unusual deterioration, or aging of materials or finishes, unsafe conditions, the need for excessive maintenance, abnormal noise, or vibration, and similar unsatisfactory conditions.

3. Retained Equipment: All retained components, parts, and materials shall be cleaned, checked, modified, repaired, or replaced in strict accordance with the specification requirements defined herein. Retained equipment must be compatible for integration with new systems.

4. Make modifications, requirements, adjustments, and improvements to meet performance requirements specified herein.

1.4 DOCUMENT AND SITE VERIFICATION

A. In order to discover and resolve conflicts or lack of definition which might create problems, Contractor must review Contract Documents and site conditions for compatibility with its product prior to submittal of quotation. Review existing structural, electrical, and mechanical provisions for compatibility with Contractor’s products. Purchaser will not pay for change to structural, mechanical, electrical, or other systems required to accommodate Contractor’s equipment.

1.5 SUBMITTALS

A. Include manufacturer’s standard submittal package, including signal fixtures and cab interiors, as applicable.

1.6 PERMIT, TEST AND INSPECTION

A. Obtain and pay for permit, license, and inspection fee necessary to complete installation.

B. Perform test required by Governing Authority in accordance with procedure described in ASME A17.2 Guide for Inspection of Elevators, Escalators, and Moving Walks in the presence of Authorized Representative. Where the Local Jurisdiction required tests to be performed after normal working hours it shall be done at no additional cost to the Purchaser.

WARRANTY

C. Mechanics must be IUEC certified mechanics and have documented formal training in multi- OEM equipment. A copy of all certifications and licenses for each mechanic shall be turned in with the bid.

D. All workmanship and products will be carry a one year warranty at no additional cost to customer

PART 2 - PRODUCTS

2.1 SUMMARY

A. One Hydraulic Passenger Elevator.

B. Unless specifically identified as “retain existing,” provide new equipment.

Existing Equipment Disposition

Number: Cars 1 Retain Existing

Capacity: 4000lbs Retain Existing

Class Loading: Passenger/Service Class A

Retain Existing

Contract Speed: 150fpm Retain Existing

Supervisory Control: Thyseenkrupp TAC 22 Retain Existing

Power Characteristics:

208 Volts, 3 Phase, 60 Hertz

Stops: Elev 1; 4 Front

Openings: Elev 1; 4 Front

Floors Served: Elev 1; 4 floors Retain Existing

Travel: Elev 1 ± 50ft

Clear Inside Car: 90 ½ in. Wide X 59in. Deep

Entrance Size: 49in Wide X 84inHigh

Entrance Type: 2SSSLH Field Verify

Door Operation: thyssenkrupp

Retain existing

2.2 HOISTWAY ENTRANCES

A. Frames: Retain existing. Provide Arabic floor designation/Braille plates, centered at 60" above finished floor, on both side jambs of all entrances. Provide plates at main egress landing with “Star” designation. Re-clad existing entrance frames with #4 Brushed Stainless Steel

B. Transom Panels: Retain existing, re-clad existing with #4 Brushed Stainless Steel

C. Door Panels: Replace existing with New #4 brushed Stainless Steel. Provide new door gibs with fire tabs at all floors. Minimum two gibs per panel, one at leading edge, and one at trailing edge of each panel. Provide code required door panel retainer mechanism on lower edge of door panel to address failure of primary lower edge door guidance.

D. Sight Guards: 14 gauge, same material and finish as hoistway entrance door panels.

Construct without sharp edges.

E. Sills: Retain existing. Clean. Check and tighten all fastenings.

F. Sill Supports: Retain existing. Check and tighten all fastenings.

G. Fascia, Toe Guards, and Hanger Covers: Retain existing. Provide as required where damaged or missing. Check and tighten all fastenings. Paint/Stencil floor number on fascia or hoistway wall all floors visible where car doors are initially opened.

H. Struts and Headers: Retain existing. Check and tighten all fastenings.

2.3 CAR EQUIPMENT

A. Frame: Retain Existing. Check and tighten all fastenings.

B. Platform: Retain existing. Reinforce if required. Check and tighten all fastenings.

C. Finish Floor Covering:

1. Cars 1: Owner selection. Owners responsibility.

D. Sills: Retain existing. Clean full width. Check and tighten all fastenings.

E. Doors: Fully enclosed 16 gauge steel, sandwich construction without binder angles. Provide leading edges of center-opening doors with rubber astragals. Provide a minimum of two (2) gibs per panel, one at leading and one at trailing edge with gibs in the sill groove entire length of door travel. Construct door panels with interlocking, stiffening ribs. New doors to be brushed stainless steel finish.

F. Door Hangers: Two-point hanger roller with neoprene roller surface and suspension with eccentric upthrust roller adjustment.

G. Door Track: Bar or formed, cold-drawn removable steel track with smooth roller contact surface.

H. Door Header: reuse existing

I. Car Gate Switch: reuse existing

J. Door Clutch: reuse existing

K. Restricted Opening Device: Restrict opening of car doors outside unlocking zone. Plunger type restrictors not acceptable.

L. Door Operator: reuse existing

M. Door Control Device: reuse exisitng

N. Car Operating Panel:

Car operating panels without faceplates, consisting of a metal box containing vandal resistant operating fixtures, mounted behind the car front return panels.

1. Suitably identify floor buttons, alarm button, door open button, door close button and emergency push-to-call button with stainless tactile symbols. Configure plates per local building code accessibility standards including Braille. Locate operating controls no higher than 48" above the car floor; no lower than 35" for emergency push-to-call button and alarm button.

2. Provide minimum 3/4" diameter raised or flush floor pushbuttons which illuminate to indicate call registration.

3. Provide alarm button to ring bell located on car. Illuminate button when actuated.

4. Provide keyed stop switch at bottom of car operating panel in locked car service compartment.

5. Provide “door open” button to stop and reopen doors or hold doors in open position.

6. Provide “door close” button to activate door close cycle. Cycle shall not begin until normal door dwell time for a car or hall call has expired, except firefighters’ operation.

7. Provide firefighters’ Phase II key switch with engraved instructions filled red. Include light jewel, buzzer, and call cancel button.

8. Install firefighters’ telephone jack.

9. Provide lockable service compartment with recessed flush door. Door material and finish shall match car return panel or car operating panel faceplate. Inside surface of door shall contain an integral flush window for displaying the elevator operating permit.

10. Include the following controls in lockable service cabinet with function and operating positions identified by permanent signage or engraved legend:

a. Inspection switch.

b. Light switch.

c. Three-position exhaust blower switch.

d. Independent service switch.

e. Constant pressure test button for battery pack emergency lighting.

f. 120-volt, AC, GFCI protected electrical convenience outlet.

g. Stop key switch.

11. Provide black paint filled (except as noted), engraved, or approved etched signage as follows with approved size and font:

a. Phase II firefighters’ operating instructions on main operating panel above corresponding keyswitch filled red.

b. Car number on main car operating panel.

c. “No Smoking” on main car operating panel.

d. Car capacity in pounds on main car operating panel service compartment door.

O. Communication System:

1. “Push to Call,” two-way communication instrument in car with automatic dialing, tracking, and recall features with shielded wiring to car controller in machine room. Provide dialer with automatic rollover capability with minimum two numbers.

a. “Push to Call” button or adjacent light jewel shall illuminate and flash when call is acknowledged. Button shall match car operating panel pushbutton design.

Provide uppercase “PUSH TO CALL” “HELP ON THE WAY” engraved signage adjacent to button to indicate when call is placed and when call is received.

Coordinate signage with communications provider.

b. Provide “Push to Call” button tactile symbol, engraved signage, and Braille adjacent to button mounted integral with car front return panel.

2. Firefighters’ telephone jack in car and firefighters’ panel, with four shielded wires to machine room junction box. Jack bezel shall match adjacent controls.

2.4 CAR ENCLOSURE

A. Car Enclosure Passenger Elevator, Cars 1: Retain existing car shell. Overall car weight to be verified and documented, prior to removal of any equipment from the existing car frame or car enclosure. Check and tighten all fastenings. Provide new interior finishes as specified and/or detailed on architectural drawings. Modify shell for application of new signal and pushbutton fixtures. New cab weight including all new finishes to be verified following completion of modernization. Post modernization weight not to exceed code allowable limits. Provide the following features:

1. Shell: Retain.

2. Canopy: Retain.

3. Cab Fronts; Return Panels, Columns and Transoms: Applied Panel Car Operating

Stations, Main and Auxiliary. All finish stainless steel fronts to match.

4. Car Door Panels: Reinforced minimum16 gauge stainless steel satin finish.

5. Base: Stainless steel with concealed ventilation cutouts.

6. Interior Wall Finish: Removable panels, faced and edged, with color core plastic laminate. Color and finish as selected by owner.

7. Ventilation: Two-speed OE mounted to car canopy on isolated rubber grommets.

Exhaust blower shall meet requirements of Item 2.03, H. Ventilation shall shut off after adjustable period (60 – 180 seconds) of no elevator demand.

8. Lighting: Provide LED fixtures with wiring and hookup. Coordinate with emergency lighting requirements. Lighting shall shut off after adjustable period (60 – 180 seconds) of no elevator demand. Provide emergency lighting integral with portion of normal car lighting system.

9. Suspended Ceiling: Stainless steel finish containing 6- 9 LED fixtures.

10. Handrails: Minimum 1-1/4" diameter stainless steel tubular grab bar across rear and side walls.

11. Pads and Buttons or Hooks, Cars 1: Three-piece removable pads. Two pads covering side walls and adjacent front returns and one covering rear wall. Provide cutouts to access main car operating panel.

2.5 HALL CONTROL STATIONS

A. Elevators 1, Pushbuttons: Provide 1 risers with flush mounted faceplates. Include vandal proof pushbuttons for each direction of travel which illuminate to indicate call registration. Provide LED illumination. Include approved engraved message and pictorial representation prohibiting use of elevator during fire or other emergency situation as part of faceplate. Pushbutton design shall match car operating panel pushbuttons. Provide vandal resistant pushbutton and light assemblies. Provide enlarged faceplate to cover existing wall blockout and facilitate handicapped access requirements.

2.6 SIGNALS

A. Hall Lantern, Elevators 1: Provide at each entrance to indicate travel direction of arriving car.

Illuminate up or down LED lights and sound tone once for up and twice for down direction prior to car arrival at floor. Sound level shall be adjustable from 20-80 dBA measured at 5'-0" in front of hall control station and 3'-0" off floor. Illuminate light until the car doors start to close.

Provide advanced notification to comply with ADA hall call notification time. Car direction lenses shall be arrow shaped with faceplates. Lenses shall be minimum 2-1/2" in their smallest dimension.

B. Car Position Indicator: digital indicator containing floor designations and direction arrows a minimum of 2" high to indicate floor served and direction of car travel. Locate fixture in each car operating panel. When a car leaves or passes a floor, illuminate indication representing position of car in hoistway. Illuminate proper direction arrow to indicate direction of travel.

C. Hall Position Indicator/Lantern Combo: Alpha-numeric digital indicator containing floor designations and direction arrows a minimum of 2" high to indicate floor served and direction of car travel. Mount integral with hall lanterns at each floor.

D. Faceplate Material and Finish: Stainless steel Satin finish all fixtures.

E. Floor Passing Tone: Provide an audible tone of no less than 20 decibels and frequency of no higher than 1500 Hz, to sound as the car passes or stops at a floor served.

F. Firefighters’ Control Panel, Cars 1-5 [Integrate cars 6-7 into the new Firefighters Control Panel.] Locate in building fire control room, or location as determined by owner. Fixture faceplate, stainless steel satin finish, including the following features:

1. Car position and direction indicator (digital-readout or color LCD Flat Panel Display).

Identify each position indicator with car number.

2. Indicator showing operating status of car.

3. Manual car standby power selection switches and power status indicators.

4. Two-position firefighters’ emergency return switches and indicators with engraved instructions filled red.

5. Firefighters’ telephone jack.

6. Firefighters Control Panel shall be located as directed by Consultant/Owner. Where applicable, identify all indicators and manual switches with appropriate engraving.

Provide conduit and wiring to control panel. Coordinate size and location with Owner.

G. Firefighters’ Key Box: Flush-mounted box with lockable hinged cover. Engrave instructions for use on cover per Local Fire Authority requirements.

PART 3 - EXECUTION

3.1 SITE CONDITION INSPECTION

A. Prior to beginning installation of equipment, examine hoistway and machine room areas. Verify no irregularities exist which affect execution of work specified.

B. Do not proceed with installation until work in place conforms to project requirements.

3.2 PRODUCT DELIVERY, STORAGE, AND HANDLING

A. Deliver material in Contractor’s original, unopened protective packaging.

B. Store material in original protective packaging. Prevent soiling, physical damage, or moisture damage.

C. Protect equipment and exposed finishes from damage and stains during transportation, erection, and construction.

3.3 INSTALLATION

A. Install all equipment in accordance with Contractor’s instructions, referenced codes, specification, and approved submittals.

B. Install machine room equipment with clearances in accordance with referenced codes, and specification.

C. Install all equipment so it may be easily removed for maintenance and repair.

D. Install all equipment for ease of maintenance.

E. Install all equipment to afford maximum accessibility, safety, and continuity of operation.

F. Remove oil, grease, scale, and other foreign matter from the following equipment and apply one coat of field-applied machinery enamel.

1. All exposed equipment and metal work installed as part of this work which does not have architectural finish.

2. Machine room equipment, and pit equipment.

3. Neatly touch up damaged factory-painted surfaces with original paint color. Protect machine-finish surfaces against corrosion.

G. Paint machine room and pit floors.

H. All fixtures must be designed to operate with existing Elevator Control System.

3.4 FIELD QUALITY CONTROL

A. Work at jobsite will be checked during course of installation. Full cooperation with reviewing personnel is mandatory. Accomplish corrective work required prior to performing further installation.

B. Have Code Authority acceptance inspection performed and complete corrective work.

3.5 CLEANUP

A. Keep work areas orderly and free from debris during progress of project. Remove packaging materials on a daily basis.

B. Remove all loose materials and filings resulting from work.

C. Clean machine room equipment and floor.

D. Clean hoistways, car, car enclosure, entrances, operating and signal fixtures.

END OF SECTION

Sheffield-Woolley Structural Repairs/Additions – REBID II
Hinds Community College
Raymond Campus
Raymond, Mississippi 39154
HCC Bid #3195/Professional’s Project #018-40
Item #1: Pre-bid Meeting Minutes:
Here-in attached are the Pre-bid minutes and sign-in sheet held on 21 April 2020.
Item #2: Project Manual, Section 14240:
Add the here-in attached Section 14240 Electric Hydraulic Elevator Cab and Fixtures Upgrade to the Project Manual.
END OF ADDENDUM No. 1
018_40 14240 elevator spec rebid 2.pdf
Page 1
018_40 02260 FINISH GRADING.pdf
SECTION 02260 - FINISH GRADING
PART 1 – GENERAL
018_40 02281 soil poisoning.pdf
SECTION 02281 - SOIL POISONING:
PART 1 – GENERAL
018_40 02660 exterior water distribution.pdf
SECTION 02660 - EXTERIOR WATER DISTRIBUTION
PART 1 – GENERAL
018_40 02930 GRASSING.pdf
SECTION 02930 - GRASSING
PART 1 – GENERAL
018_40 03100 03200 03300 Concrete.pdf
Page 1
018_40 00100--InstructionstoBidders.pdf
PART 1 – GENERAL
PART 2 – PROPOSAL FORM
PART 3 – SUBMITTING THE PROPOSAL FORM
PART 4 - BID OPENING AND AWARD OF CONTRACT
PART 5 – BIDDER’S CHECKLIST
018_40 02100 site clearing.pdf
SECTION 02100 - SITE CLEARING, EXCAVATION AND GRADING
PART 1 – GENERAL
018_40 02260 FINISH GRADING.pdf
SECTION 02260 - FINISH GRADING
PART 1 – GENERAL
018_40 02281 soil poisoning.pdf
SECTION 02281 - SOIL POISONING:
PART 1 – GENERAL
018_40 02660 exterior water distribution.pdf
SECTION 02660 - EXTERIOR WATER DISTRIBUTION
PART 1 – GENERAL
018_40 02930 GRASSING.pdf
SECTION 02930 - GRASSING
PART 1 – GENERAL
018_40 03130 concrete patch.pdf
SECTION 03130 – ONE COMPONENT, FLOWABLE, FORM & POUR STRUCTURAL REPAIR MORTAR
F. ASTM C348 – Standard Test Method for Flexural Strength of Hydraulic-Cement Mortars.
018_40 04205 Unit Masonry.pdf
Page 1
Page 2
Page 3
Page 4
Page 5
Page 6
Page 7
018_40 05400 Cold formed metal framing.pdf
SECTION 05400 - COLD-FORMED METAL FRAMING
PART 1 – GENERAL
1.1 WORK INCLUDED: The work required under this Section consists of the furring at the ceiling and wall framing and related items to complete the work as indicated on the drawings and described in the Specifications.
018_40 05500 metal fabrications.pdf
SECTION 05500 - METAL FABRICATIONS
PART 1 – GENERAL
018_40 05515 stairs ladders and rungs.pdf
SECTION 05515 - STAIRS, LADDERS, AND RUNGS
PART 1 – GENERAL
018_40 05800 expansion control.pdf
SECTION 05800 - EXPANSION CONTROL
PART 1 – GENERAL
018_40 06100 rough carpentry.pdf
SECTION 06100 - ROUGH CARPENTRY
PART 1 – GENERAL
1.1 DESCRIPTION: Rough carpentry and finish carpentry.
018_40 06300 wood treatment.pdf
SECTION 06300 - WOOD TREATMENT
PART 1 – GENERAL
1.1 DESCRIPTION: This section of these specifications includes all wood treatment and preservatives as required for this project; the General Conditions and Division 1 govern all work.
018_40 07900 sealants.pdf
SECTION 07900 - SEALANTS
PART 1 – GENERAL
018_40 08710 door hardware.pdf
1.1 SUMMARY:
1.2 SUBSTITUTIONS:
1.3 SUBMITTALS:
1.4 QUALITY ASSURANCE
1.5 DELIVERY, STORAGE, AND HANDLING
1.6 PROJECT CONDITIONS:
1.7 WARRANTY:
1.8 OWNER’S INSTRUCTION:
1.9 MAINTENANCE:
PART 2 - PRODUCTS
2.1 MANUFACTURERS:
2.2 MATERIALS:
Precision Manufactured by Stanley Security Solutions
2.3 FINISH:
2.4 KEYS AND KEYING:
PART 3 - EXECUTION
3.1 EXAMINATION
3.2 HARDWARE LOCATIONS:
3.3 INSTALLATION:
3.4 FIELD QUALITY CONTROL AND FINAL ADJUSTMENT
3.5 SCHEDULE OF FINISH HARDWARE:
018_40 10400 identifing devices.pdf
PART 1 GENERAL
HCC Sheffield-Wooley CD ELEC Final Specs.pdf
01 Elec TOC
HCC Sheffield-Wooley CD ELEC Final Specs
Elec TOC
16010 - Electrical General
16012 - Electrical Submittals
16050 BASIC ELECTRICAL MATERIALS AND METHODS
1.1 SUMMARY
A. This Section includes the following:
1. Electrical equipment coordination and installation.
2. Sleeves for raceways and cables.
3. Sleeve seals.
4. Common electrical installation requirements.
1.2 QUALITY ASSURANCE
A. Test Equipment Suitability and Calibration: Comply with NETA ATS, "Suitability of Test Equipment" and "Test Instrument Calibration."
1.3 COORDINATION
A. Coordinate arrangement, mounting, and support of electrical equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other installations.
3. To allow right of way for piping and conduit installed at required slope.
4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.
B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.
C. Coordinate location of access panels and doors for electrical items that are behind finished surfaces or otherwise concealed. Access doors and panels are specified in Division 8 Section "Access Doors and Frames."
D. Coordinate electrical testing of electrical, mechanical, and architectural items, so equipment and systems that are functionally interdependent are tested to demonstrate successful interoperability.
PART 2 - PRODUCTS
2.1 SLEEVES FOR RACEWAYS AND CABLES
A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.
B. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.
C. Coordinate sleeve selection and application with selection and application of firestopping.
2.2 SLEEVE SEALS
A. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable.
1. Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit. Include type and number required for material and size of raceway or cable.
2. Pressure Plates: Plastic. Include two for each sealing element.
3. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of length required to secure pressure plates to sealing elements. Include one for each sealing element.
PART 3 - EXECUTION
3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1.
B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.
C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.
D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with...
E. Right of Way: Give to raceways and piping systems installed at a required slope.
3.2 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS
A. Electrical penetrations occur when raceways, cables, wireways, cable trays, or busways penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.
B. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 7 Section "Through-Penetration Firestop Systems."
C. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.
D. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.
E. Extend sleeves installed in floors 31T2 inches31T above finished floor level.
F. Size pipe sleeves to provide 31T1/4-inch31T annular clear space between sleeve and raceway or cable unless sleeve seal is to be installed.
G. Seal space outside of sleeves with grout for penetrations of concrete and masonry and with approved joint compound for gypsum board assemblies.
H. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Refer to Division 7 Section "Joint Sealants" for materials a...
I. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at raceway and cable penetrations. Install sleeves and seal raceway and cable penetration sleeves with firestop materials. Comply with Di...
J. Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible boot-type flashing units applied in coordination with roofing work.
K. Aboveground, Exterior-Wall Penetrations: Seal penetrations using sleeves and mechanical sleeve seals. Select sleeve size to allow for 31T1-inch31T annular clear space between pipe and sleeve for installing mechanical sleeve seals.
L. Underground, Exterior-Wall Penetrations: Install cast-iron "wall pipes" for sleeves. Size sleeves to allow for 31T1-inch31T annular clear space between raceway or cable and sleeve for installing mechanical sleeve seals.
3.3 FIRESTOPPING
A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly. Firestopping materials and installation requirements are specified in Division 7 Section "Through-Penetra...
16060 GROUNDING AND BONDING
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes methods and materials for grounding systems and equipment.
1.2 SUBMITTALS
A. Product Data: For each type of product indicated.
B. Field quality-control test reports.
1.3 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
B. Comply with UL 467 for grounding and bonding materials and equipment.
PART 2 - PRODUCTS
2.1 CONDUCTORS
A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction.
B. Bare Copper Conductors:
1. Solid Conductors: ASTM B 3.
2. Stranded Conductors: ASTM B 8.
3. Tinned Conductors: ASTM B 33.
4. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 31T1/4 inch31T in diameter.
5. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.
6. Bonding Jumper: Copper tape, braided conductors, terminated with copper ferrules; 31T1-5/8 inches31T wide and 31T1/16 inch31T thick.
7. Tinned Bonding Jumper: Tinned-copper tape, braided conductors, terminated with copper ferrules; 31T1-5/8 inches31T wide and 31T1/16 inch31T thick.
2.2 CONNECTORS
A. Listed and labeled by a nationally recognized testing laboratory acceptable to authorities having jurisdiction for applications in which used, and for specific types, sizes, and combinations of conductors and other items connected.
B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, bolted pressure-type, with at least two bolts.
1. Pipe Connectors: Clamp type, sized for pipe.

C. Welded Connectors: Exothermic-welding kits, Cadweld or approved equal.

2.3 GROUNDING ELECTRODES
A. Ground Rods: Copper-clad steel; 31T3/4 inch diameter by 10 feet31T in length.
PART 3 - EXECUTION
3.1 APPLICATIONS
A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for No. 6 AWG and larger, unless otherwise indicated.
B. Underground Grounding Conductors: Install bare copper conductor, No. 3/0 AWG minimum. Bury at least 31T24 inches31T below grade.
C. Isolated Grounding Conductors: Green-colored insulation with continuous yellow stripe. On feeders with isolated ground, identify grounding conductor where visible to normal inspection, with alternating bands of green and yellow tape, with at leas...
D. Conductor Terminations and Connections:
1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors.
2. Underground Connections: Welded connectors, except at test wells and as otherwise indicated.
3. Connections to Ground Rods at Test Wells: Bolted connectors.
4. Connections to Structural Steel: Welded connectors.
3.2 EQUIPMENT GROUNDING
A. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70:
1. Feeder circuits.
2. Single-phase motor and appliance branch circuits.
3. Three-phase motor and appliance branch circuits.
4. Flexible raceway runs.
5. Armored and metal-clad cable runs.

B. Metal Poles Supporting Outdoor Lighting Fixtures: Install grounding electrode and a separate insulated equipment grounding conductor in addition to grounding conductor installed with branch-circuit conductors.

3.3 INSTALLATION
A. Grounding Conductors: Route along shortest and straightest paths possible, unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.
B. Provide separate grounding conductor for all circuits to insure adequate ground fault return path.
C. Separate individual ground conductors shall be installed in conduit.
D. Bond grounding conductors to equipment enclosure at source and at apparatus served.
E. Maintain electrical continuity of conduit systems by threaded fittings with joints made-up wrench tight. Install insulated bushing and locknuts on terminating conduits. Provide conduits containing ground wires with grounding bushings bonded to grou...
F. Ground Rods: Drive rods until tops are 31T2 inches31T below finished floor or final grade, unless otherwise indicated.
1. Interconnect ground rods with grounding electrode conductor below grade by means of irreversible exothermic weld. Make connections without exposing steel or damaging coating, if any.
G. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance, except where routed through short lengths of conduit.
1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts.
2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install so vibration is not transmitted to rigidly mounted equipment.
H. Grounding and Bonding for Piping:
1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water ser...
2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector.
3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve.
3.4 FIELD QUALITY CONTROL
A. Perform the following tests and inspections and prepare test reports:
1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.
2. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal, and at ground test wells.
a. Measure ground resistance not less than two full days after last trace of precipitation and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natura...
b. Perform tests by fall-of-potential method according to IEEE 81.
B. Install ground rods in quantity to provide a maximum of 5 ohms ground resistance.
C. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect promptly and include recommendations to reduce ground resistance.
16075 ELECTRICAL IDENTIFICATION
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. Identification for conductors and communication and control cable.
2. Warning labels and signs.
3. Equipment identification labels.
1.2 QUALITY ASSURANCE
A. Comply with ANSI A13.1.
1.3 COORDINATION
A. Coordinate identification names, abbreviations, colors, and other features with requirements in the Contract Documents, Shop Drawings, manufacturer's wiring diagrams, and the Operation and Maintenance Manual, and with those required by codes, stand...
PART 2 - PRODUCTS
2.1 CONDUCTOR AND COMMUNICATION- AND CONTROL-CABLE IDENTIFICATION MATERIALS
A. Marker Tape: Vinyl or vinyl -cloth, self-adhesive wraparound type, with circuit identification legend machine printed by thermal transfer or equivalent process.
2.2 WARNING LABELS AND SIGNS
A. Comply with NFPA 70 and 29 CFR 1910.145.
B. Self-Adhesive Warning Labels: Factory printed, multicolor, pressure-sensitive adhesive labels, configured for display on front cover, door, or other access to equipment, unless otherwise indicated.
C. Baked-Enamel Warning Signs: Preprinted aluminum signs, punched or drilled for fasteners, with colors, legend, and size required for application. 31T1/4-inch31T40T (6.4-mm)40T grommets in corners for mounting. Nominal size, 31T7 by 10 inches31T40...
D. Metal-Backed, Butyrate Warning Signs: Weather-resistant, non-fading, preprinted, cellulose-acetate butyrate signs with 31T0.0396-inch31T40T (1-mm)40T galvanized-steel backing; and with colors, legend, and size required for application. 31T1/4-inc...
E. Fasteners for Signs: Self-tapping, stainless-steel screws or stainless-steel machine screws with nuts and flat and lock washers.
F. Warning label and sign shall include, but are not limited to, the following legends:
1. Workspace Clearance Warning: "WARNING - OSHA REGULATION - AREA IN FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 31T36 INCHES31T40T (915 mm)40T."
2.3 EQUIPMENT IDENTIFICATION LABELS
A. Self-Adhesive, Engraved, Laminated Acrylic or Melamine Label: Adhesive backed, with white letters on a dark-gray background. Minimum letter height shall be 31T3/8 inch31T40T (10 mm)40T.
PART 3 - EXECUTION
3.1 APPLICATION
A. Auxiliary Electrical Systems Conductor and Cable Identification: Use marker tape to identify field-installed alarm, control, signal, sound, intercommunications, voice, and data wiring connections.
1. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, and cable pull points. Identify by system and circuit designation.
2. Use system of designations that is uniform and consistent with system used by manufacturer for factory-installed connections.
B. Warning Labels for Indoor Cabinets, Boxes, and Enclosures for Power and Lighting: Comply with 29 CFR 1910.145 and apply baked-enamel warning signs. Identify system voltage with black letters on an orange background. Apply to exterior of door, co...
1. Equipment with Multiple Power or Control Sources: Apply to door or cover of equipment including, but not limited to, the following:
a. Power transfer switches.
b. Controls with external control power connections.

2. Equipment Requiring Workspace Clearance According to NFPA 70: Unless otherwise indicated, apply to door or cover of equipment but not on flush panelboards and similar equipment in finished spaces.

C. Equipment Identification Labels: On each unit of equipment, install unique designation label that is consistent with wiring diagrams, schedules, and Operation and Maintenance Manual. Apply labels to disconnect switches and protection equipment, c...
1. Labeling Instructions:
a. Indoor Equipment: Self-adhesive, engraved, laminated acrylic or melamine label. Unless otherwise indicated, provide a single line of text with 31T1/2-inch-31T40T (13-mm-)40T high letters on 31T1-1/2-inch-31T40T (38-mm-)40T high label; where 2 lin...
b. Outdoor Equipment: Engraved, laminated acrylic or melamine label, drilled for screw attachment.
c. Elevated Components: Increase sizes of labels and legend to those appropriate for viewing from the floor.
2. Equipment to Be Labeled:
a. Panelboards, electrical cabinets, and enclosures.
b. Disconnect switches.
c. Enclosed circuit breakers.
d. Transformers
e. Contactors.
3.2 INSTALLATION
A. Verify identity of each item before installing identification products.
B. Location: Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment.
C. Apply identification devices to surfaces that require finish after completing finish work.
D. Self-Adhesive Identification Products: Clean surfaces before application, using materials and methods recommended by manufacturer of identification device.
E. Attach nonadhesive signs and plastic labels with screws and auxiliary hardware appropriate to the location and substrate.
F. Color-Coding for Phase Identification, 600 V and Less: Use the colors listed below for ungrounded service, feeder, and branch-circuit conductors.
1. Color shall be factory applied.
2. Colors for 120/208-V Circuits:
a. Phase A: Black.
b. Phase B: Red.
c. Phase C: Blue.
3. Colors for 277/480-V Circuits:
a. Phase A: Brown.
b. Phase B: Orange.
c. Phase C: Yellow.
16120 CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. Building wires and cables rated 600 V and less.
2. Connectors, splices, and terminations rated 600 V and less.
3. Sleeves and sleeve seals for cables.
1.2 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
B. Comply with NFPA 70.
PART 2 - PRODUCTS
2.1 CONDUCTORS AND CABLES
A. Copper Conductors: Comply with NEMA WC 70.
B. Conductor Insulation: Comply with NEMA WC 70 for Types THHN-THWN and SO.
2.2 CONNECTORS AND SPLICES
A. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated.
2.3 SLEEVES FOR CABLES
A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.
B. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.
C. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 7 Section "Through-Penetration Firestop Systems."
PART 3 - EXECUTION
3.1 CONDUCTOR MATERIAL APPLICATIONS
A. Feeders: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.
B. Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.
3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRING METHODS
A. Service Entrance: Type THHN-THWN, single conductors in raceway.
B. Exposed Feeders: Type THHN-THWN, single conductors in raceway.
C. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN-THWN, single conductors in raceway.
D. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN-THWN, single conductors in raceway.
E. Exposed Branch Circuits, Including in Crawlspaces: Type THHN-THWN, single conductors in raceway.
F. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN-THWN in EMT conduit.
G. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN-THWN, single conductors in non-metallic raceway.
H. Cord Drops and Portable Appliance Connections: Type SO, hard service cord with stainless-steel, wire-mesh, strain relief device at terminations to suit application.
I. Class 1 Control Circuits: Type THHN-THWN, in raceway.
J. Class 2 Control Circuits: Power-limited cable, concealed in building finishes.
3.3 INSTALLATION OF CONDUCTORS AND CABLES
A. Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated.
B. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
C. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.
D. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.
E. Support cables with approved hangars to prevent laying on ceiling grid or any other structure.
F. Identify and color-code conductors and cables according to Division 16 Section "Electrical Identification."
G. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.
H. Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.
I. Wiring at Outlets: Install conductor at each outlet, with at least 31T6 inches31T of slack.
3.4 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS
A. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 7 Section "Through-Penetration Firestop Systems."
B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.
C. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.
D. Extend sleeves installed in floors 31T2 inches31T above finished floor level.
E. Size pipe sleeves to provide 31T1/4-inch31T annular clear space between sleeve and cable unless sleeve seal is to be installed.
F. Seal space outside of sleeves with grout for penetrations of concrete and masonry and with approved joint compound for gypsum board assemblies.
G. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and cable, using joint sealant appropriate for size, depth, and location of joint according to Division 7 Section "Joint Sealants."
H. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at cable penetrations. Install sleeves and seal with firestop materials according to Division 7 Section "Through-Penetration Firestop Syst...
I. Roof-Penetration Sleeves: Seal penetration of individual cables with flexible boot-type flashing units applied in coordination with roofing work.
J. Aboveground Exterior-Wall Penetrations: Seal penetrations using sleeves and mechanical sleeve seals. Size sleeves to allow for 31T1-inch31T annular clear space between pipe and sleeve for installing mechanical sleeve seals.
K. Underground Exterior-Wall Penetrations: Install cast-iron "wall pipes" for sleeves. Size sleeves to allow for 31T1-inch31T annular clear space between cable and sleeve for installing mechanical sleeve seals.
3.5 SLEEVE-SEAL INSTALLATION
A. Install to seal underground exterior-wall penetrations.
B. Use type and number of sealing elements recommended by manufacturer for cable material and size. Position cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between cable and sleeve. Tighten bolts against pr...
3.6 FIRESTOPPING
A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to Division 7 Section "Through-Penetration Firestop Systems."
3.7 FIELD QUALITY CONTROL
A. Perform tests and inspections and prepare test reports.
B. Tests and Inspections:
1. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.

C. Remove and replace malfunctioning units and retest as specified above.

16130 RACEWAYS AND BOXES
PART 1 - GENERAL
1.1 SUMMARY

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .