3-MultiModal IT Data 14JAN26.pdf

PDF 1005 KB Posted

Attached to
Installation of Structured Voice and Data Cabling for the Multimodal Transit Facility
Solicitation number
260080
Issued by
Sedgwick County, Kansas

About this file

This is an architectural electrical power plan document for the Wichita Multimodal Transit Facility (also known as "The Hub"), a project undertaken by the City of Wichita's Information Technology Department. The document presents ground-level enlarged power plans for the facility and includes detailed keyed notes specifying electrical installation requirements throughout the building. The project encompasses comprehensive structured voice and data cabling installation, with a total cable count of 125 lines distributed across multiple systems including 70 data connections, 15 Wi-Fi Bus Bay connections, 38 camera feeds, and approximately 12 GameChanger connections on higher parking levels. The plans are drawn to scale (3/16" = 1'-0") and show multiple floor plan sections (West, North, and South) with designated electrical equipment locations, including server rooms, distribution systems, and various receptacle placements throughout offices, corridors, restrooms, and operational spaces.

The detailed specifications include 35 keyed notes addressing critical infrastructure requirements such as GFCI receptacles for specific appliances, dedicated power circuits for equipment including generators, fire alarm systems, elevator components, and security/access control panels. The installation requirements emphasize coordination with equipment vendors, adherence to fire safety codes, and compliance with applicable authority having jurisdiction (AHJ) standards. Notable specifications include routing of conduits to server rooms, provision of cable trays, generator installation with specific access requirements, and future capacity planning for photovoltaic equipment. The project document was finalized on the bid set date of April 23, 2024, with design work completed in September 2023, indicating the structured cabling installation represents a significant component of the multimodal transit facility's operational infrastructure development.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

J

J J

J

J

J

J

J

F A

C P

A B

DSS-1A

LBDS-1

G-1

MDP-2

MDP-1

WPI

ATS-SB

ATS-EM

H1SB

L1SB

L1EM

HA

LVC

TVC

TA

T1EM

T1SB

H1EM

STORAGE

ECB-SB

ECB-EM6

5L1EM:

LA

1LA:

1,3L1EM:

13L1EM: 9,11L1EM:

7L1EM:

LC-1

15L1EM:

MAIN ELEC

3LA:

E

CT

CT

CTCT

CT

3 3

DSS-4A

EWH-1

SERVER RM.

OFF. 1

SHARED OFF.

OFF. 2

OFF. 6

OFF. 4

OFF. 3

F. REST.

STOR.

OFF. 5

F. REST.

M. REST.

M. REST.

STOR.

COATS

CORRIDOR

DRIVER B.R.

DISPATCH

48"

G

1L2SB:

5LB:

7LB:

9L2SB:

7L2SB:

5L2SB:

3L2SB:

13L2SB:

11L2SB:

15LB:

15L2SB:

43L2SB:

47L2SB:

EBB-8

61,63L2SB:

45L2SB:

5L2EM: 23

53L2SB:

65L2SB:

3LB:

CT

4LB: 6LB: 8LB:

UCT

WPI

49L2SB:

51L2SB:

(ABOVE CEILING)

E X1 X2 X3

CT

CT

CT

CT

15 15

RCP-1

SP-1

LOBBY

CORRIDOR

M. REST.

F. REST.

ELEV

EL01

F. REST.

M. REST.

UNISEX

BUS TICK.

STAIR

S01

ELEV

EL02

JAN.

BUS OFF.

CONF. ROOM

PRINT AREA

SECURITY

TICKETING BR

CLG CLG

60"

60"

EBB-6

EBB-5

EBB-3

EBB-2

EBB-1

EBB-4

H2SB

L2SB

LB

T2SB

L2EM

GWH-1

EBB-7

H2EM

T2EM

MEP

13LB:

11LB:

9LB:

19L2SB:

21L2SB:

23L2SB:

25L2SB:

59L2SB:

57L2SB:

TB17

27L2SB:

29L2SB:

31L2SB:

33L2SB:

35L2SB:

37L2SB:

39L2SB:

CT CT CT

17L2SB:

27LB:

31LB:

29LB:

33LB:

35LB:

25LB:

41L2SB:

14L2SB:

1LB:

20LB:

HB

CLG

A

LC-2

1L2EM:

60"

CORRIDOR

T T

R R

D D

DSS-6A

3L2EM:

LC-3

17HB:

WPI

CT

CT

UCT

48"

(ABOVE

CEILING)

28L2SB: 30L2SB:

IF THIS DRAWING IS LESS THAN 30" X 42" IT IS A REDUCED SIZE DRAWING

C O

N S

U L T

A N

T S

R

E V

IS

IO

N S

PROJ NO:

SCALE:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SHEET TITLE:

SHEET NO.

SHEET OF

W

IC

H

IT

A M

U L T

I- M

O D

A L

T R

A N

S

IT

F A

C

IL

IT

Y

PROJECT NO: 2101060268

AS INDICATED

S

O U

T H

R

IV

E R

S

ID

E P

L A

Z A

S

U

IT

E

C H

IC

A

G O

IL

P H

O N

E -6

-9

F A

X -6

-9

/7

/2

:0 :3

P

M

GROUND LEVEL -

ENLARGED

POWER PLANS

E-211

P125200012

2023-09-14

GAKH

JAC

GAKH

4'2' 10'0' 6'

SCALE: 3/16" = 1'-0"

A

GROUND LEVEL POWER PLAN - WEST

4'2' 10'0' 6'

SCALE: 3/16" = 1'-0"

C

GROUND LEVEL POWER PLAN - SOUTH

KEYED NOTES

N N

1. PROVIDE AND INSTALL DEDICATED GFCI RECEPTACLE FOR REFRIGERATOR.

2. PROVIDE WALL BOX FOR POWER AND DATA CONNECTION TO OPEN OFFICE

FURNITURE. COORDINATE WITH REQUIREMENTS WITH OWNER PRIOR TO

ROUGH-IN. MAKE FINAL CONNECTIONS AS REQUIRED TO FURNITURE. ROUTE 2"

C. WITH INSULATED BUSHINGS & PULL CORD FOR DATA.

3. ROUTE 4" PVC SLEEVE BETWEEN SERVER ROOM AND ACCESSIBLE CEILING IN

CORRIDOR 113. FIREPROOF AS NECESSARY.

4. ROUTE (2)-4" CONDUITS WITH PULL STRING TO EASEMENT. REFER TO SITE

PLAN.

5. PROVIDE POWER FOR INTERNALLY LIT SIGN. COORDINATE INSTALLATION

REQUIREMENTS WITH SIGN VENDOR.

6. PROVIDE POWER TO SINGLE POINT CONNECTION FOR GENERATOR

ACCESSORIES. ROUTE WITH (3)-#4, #6 G. IN 1" C.

7. MOUNT GENERATOR ANNUNCIATOR PANEL ON WALL. CONFIRM FINAL

LOCATION WITH OWNER.

8. PROVIDE AND INSTALL SMOKE DETECTOR FOR ELEVATOR RECALL.

9. PROVIDE AND INSTALL CONVENIENCE GFCI RECEPTICAL IN ELEVATOR SHAFT

PER ELEVATOR MANUFACTURER REQUIREMENTS.

10. PROVIDE RECEPTACLE, DATA DROP, AND A/V BACK BOX FOR TELEVISION.

REFER TO DETAIL '10' ON SHEET E-402.

11. PROVIDE AND INSTALL DEDICATED RECEPTACLE AND DATA FOR COPIER.

12. CONNECT ELEVATOR PIT LIGHTING TO SAME CIRCUIT SERVING RECEPTACLES

IN ELEVATOR PIT.

13. PROVIDE SIMPLEX RECEPTACLE FOR SUMP PUMP. PROVIDE GFCI RECEPTACLE

IF REQUIRED BY AHJ.

14. PROVIDE AND INSTALL DEDICATED GFCI RECEPTACLE FOR WATER COOLER.

15. ROUTE 4" PVC SLEEVE BETWEEN SERVER ROOM AND ACCESSIBLE CEILING IN

CORRIDOR 113. FIREPROOF AS NECESSARY.

16. PROVIDE AND INSTALL DEDICATED RECEPTACLE FOR TICKET VENDING

MACHINE.

17. PROVIDE STRUT SYSTEM TO STACK TRANSFORMER 'TB' ABOVE TRANSFORMER

'T2SB'.

18. PROVIDE AND INSTALL DEDICATED GFCI RECEPTACLE UNDER COUNTOP FOR

GARBAGE DISPOSAL. PROVIDE AND INSTALL TOGGLE SWITCH ADJACENT TO

SINK.

19. PROVIDE AND INSTALL DEDICATED GFCI RECEPTACLE FOR COFFEE MAKER.

20. PROVIDE AND INSTALL DEDICATED GFCI RECEPTACLE FOR MICROWAVE.

21. ORIENT GENERATOR FOR ACCESS TO BREAKER AND CONTROL PANEL ON

SOUTH SIDE.

22. PROVIDE POWER TO GFCI RECEPTACLE AND BATTERY CHARGER RECEPTACLE

PROVIDED AS PART OF LOAD BANK DOCKING STATION.

23. PROVIDE POWER TO SECURITY/ACCESS CONTROL PANEL.

24. PROVIDE AND INSTALL RECEPTACLE AND DATA ON CEILING FOR PROJECTOR.

25. PROVIDE POWER FOR INTERNALLY LIT SIGN. COORDINATE INSTALLATION

REQUIREMENTS WITH SIGN VENDOR. DO NOT ROUTE CONDUIT WITHIN STAIR

TOWER OR ELEVATOR CAVITY.

26. KEEP SPACE AVAILABLE FOR FUTURE PHOTOVOLTAIC EQUIPMENT.

27. PROVIDE FIRE ALARM SYSTEM FOR ELEVATOR PHASE I RECALL.

28. PROVIDE DUCT DETECTORS, SHUTDOWN RELAY & REMOTE TEST SWITCH

MOUNTED IN CEILING TILE FOR 'RTU-5'.

29. PROVIDE HEAT DETECTOR IN ELEVATOR PIT.

30. ROUTE 2" C. WITH PULL-STRING FROM SERVER ROOM TO STORAGE ROOM FOR

DATA.

31. PROVIDE GFCI RECEPTACLE FOR IRRIGATION CONTROLLER. COORDINATE

LOCATION WITH IRRIGATION CONTRACTOR PRIOR TO ROUGH-IN.

32. ROUTE 2" C. WITH INSULATED BUSHINGS FROM IT SERVER ROOM TO GARAGE

SPACE. FIRE AND WEATHERPROOF PENETRATION.

33. PROVIDE RECEPTACLE, DATA DROP, AND A/V BACK BOX FOR TELEVISION.

REFER TO DETAIL '10' ON SHEET E-402.

34. PROVIDE 12"W BY 4"D WIRE BASKET CABLE TRAY. MOUNT HIGH ON WALL JUST

BELOW CONDUIT PENETRATIONS.

35. PROVIDE EPO BUTTON FOR GENERATOR SHUT OFF ADJACENT TO DOOR.

PROVIDE WEATHERPROOF ENCLOSURE. COORDINATE FINAL LOCATION WITH

AHJ AND OWNER.

4'2' 10'0' 6'

SCALE: 3/16" = 1'-0"

B

GROUND LEVEL POWER PLAN - NORTH

N

M A

R K

D A

T E

D E

S C

R

IP

T

IO

N

04/23/2024

/2

3/

BI

D S

ET

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Group Computer data outlet, place edge against wall

SKeene Line

SKeene Text Box 70 Data 2 Wifi

Bus Bay - 15 Data Cameras - 38 GameChanger on higher parking levels ~12

Total Cable count: 125