3 - Exhibit B - Agency Special Requirements Vero Beach PC.pdf
PDF 986 KB Posted
- Solicitation number
- 36C24826R0042
About this file
This document is an Agency Specific Requirements (ASR) for a Department of Veterans Affairs (VA) lease solicitation for the Vero Beach Primary Care Clinic. The VA seeks to lease 12,900 to 12,948 square feet of contiguous clinical space, located on the ground floor of a professional building. The space must be fully serviced, including janitorial services, basic cable, high-speed internet, security monitoring, and maintenance.
The solicitation provides detailed space requirements across multiple areas, including a waiting area, restrooms, reception area, management spaces, employee break room, laboratory, patient care rooms, and telecommunications infrastructure. Key specifications include specific room sizes, electrical and networking requirements, finishes, signage, HVAC design, and a generator quick connect provision. The space must accommodate various clinical functions such as patient care rooms, blood draw stations, staff workstations, storage areas, and must meet VA design standards for accessibility, technology infrastructure, and environmental controls. The lease will follow standard GSA lease specifications and requires VA approval of layout, finishes, and design details.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 1 of 12
RLP #36C248-26-R-0042 - Exhibit B Vero Beach Primary Care Clinic
AGENCY SPECIFIC REQUREMENTS (ASR)
The Department of Veterans Affairs is interested in leasing a minimum of 12,900 to a maximum of 12,948 contiguous clinical space for a clinical lease.
Space shall be available for use by Tenant (VA) for personnel, furnishings, and equipment to meet the needs for a primary care clinic. Space design will provide maximum co-location of the staff providing services to our patients.
The space shall be of contiguous space in a professional and aesthetically pleasing Building. Space offered must be in a quality building of sound and substantial construction, either a new, modernized building, or one that has undergone restoration or rehabilitation for the intended use. Space shall be located in a prime commercial office space with attractive, professional surroundings. Streets and public walkways shall be well maintained. Space shall be located on the ground floor.
The lease shall be fully serviced to include Janitorial, Basic Cable, Guest High Speed Internet Wi-Fi, Security Monitoring and Maintenance. The lease shall follow the standard specifications and requirements for a New/Replacing Lease as per the GSA Global Lease or Simplified Lease.
A. SPACE PLAN
Room Quantity Area Net Area
Gurney, wheelchair 1 72 72 Lactation room 2 113 225 Vet/guest seating 1 700 700 Refreshment station 1 60 60 Staff toilet 1 78 78 Staff toilet/shower 1 102 102 Patient toilet 1 90 90 Women vet patient toilet 1 90 90 Bariatric toilet 1 90 90 Single occupant toilet 1 78 78 Staff workroom/storage 1 120 120 Leadership office 2 120 240 Admin staff workstation 1 67 67 HAS workstation 3 67 202 Multipurpose/breakroom 1 300 300 Personal property locker 1 60 60 Recycling holding 1 48 48 Trash holding room 1 72 72 Receiving area 1 120 120 Breakdown area 1 120 120 Full gas cylinder 1 48 48
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 2 of 12
Empty gas cylinder 1 48 48 Logistics workstation 2 67 134 Medical Equip storage 1 144 144 Clinical supplies storage 1 200 200 Sterile supplies storage 1 180 180 Soiled utility 1 100 100 Clean utility 1 125 125 Patient height and weight station 1 60 60 Lab specimen toilet 1 78 78 Blood draw station 2 77 154 Bariatric blood draw station 1 90 90 Lab specimen processing 1 144 144 Lab clean supply storage 1 72 72 Lab soiled holding 1 72 72 Lab handwashing 1 12 12 Lab lead tech workstation 1 58 58 Women vet patient care room 1 168 168 General patient care room 14 150 2100 Bariatric patient care room 1 240 240 Counseling patient care room 4 144 576 Consult patient care room 4 144 576 Group room 1 288 288 POU equip, supply and medication alcove 1 84 84 Hoteling workstation 2 58 115 Clinical staff workstation 23 72 1656 Team copy/supply alcove 2 36 72 Demarc 1 96 80
TR 1 216 180
Housekeeping 2 0 0
ROOM REQUIREMENTS
B. WAITING AREA/VETERAN WELCOME AREA
1. One Gurney, wheelchair, mobile lift corral/parking 72 NUSF
2. One Lactation room 113 NUSF
3. One Veteran/Guest seating 700 NUSF
4. One Refreshment Station 60 NUSF
5. Front entrance door shall have a power assisted door that is operated by a push pad.
6. Direct window access to waiting area.
7. Restricted access or lockable door to clinical area.
8. Eight (8) quadraplex electrical outlets (16 to 18 inches from the floor), location as determined by VA.
9. Four (4) telecommunication outlets, location as determined by the VA.
10. Duress alarm.
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 3 of 12
11. One (1) dimmer light switch.
12. Luxury Vinyl Tile (LVT).
13. Luxury Vinyl Tile (LVT) to continue through hallway/corridors.
14. Corridors shall be at minimum of 5 feet in clear width.
15. All walls to have Chair Rail (28 to 32 inches) and vinyl corner guards, mounted at height determined by
VA.
16. Window coverings must have horizontal manual roller shades with solar glare and heat reduction.
17. Drinking Fountain. A wall hung stainless Bottle Filling Station & Single ADA Cooler will be provided in the suite waiting room. Complete cooler and bottle filling station in a consolidated space saving ADA compliant design.
18. Automated touchless sanitizer dispenser provided by the lessor.
19. Cable Television Service paid for/provided by the lessor through the annual rent.
20. Cable TV audio/video wall jack required backing and mounting materials for connection to a VA furnished television. Ensure that HDMI and telecommunication cabling is provided for computer hookup within wall connections. Mounting heights for power and data to be coordinated with the VA.
21. Guest high speed internet Wi-Fi paid for/provided by the lessor through the annual rent.
22. Layout shall be reviewed by the VA for final approval.
C. RESTROOMS (MALE AND FEMALE)
1. One universal staff toilet 78 NUSF
2. One universal staff toilet/shower 102 NUSF
3. One patient toilet 90 NUSF
4. One women veteran patient toilet 90 NUSF
5. One bariatric toilet 90 NUSF
6. One universal single occupant toilet 78 NUSF
7. One lab specimen collection toilet 78 NUSF
8. All bathrooms shall meet handicap accessibility codes and will include grab bars at commode.
9. All bathrooms shall have a power assisted door that is operatized by a push pad.
10. Minimum one (1) accessible commercial grade water closet and lavatory.
11. Toilet paper dispenser provided by the lessor installed within easy reach.
12. Mirror over sink, minimum of 24"x 36", shall be provided and installed by the lessor shall be installed.
13. Automated touchless soap dispenser provided by the lessor.
14. Automated touchless paper towel dispenser provided by the lessor.
15. Wall mounted coat rack shall be installed on the wall behind door.
16. Baby changing station.
17. One (1) GFCI duplex electrical outlet.
18. Duress Alarm to be hard-wired.
19. Porcelain Tile Flooring.
20. Porcelain Tile wall 4 foot up the wall with tile accent strip.
21. Layout shall be reviewed by the VA for final approval.
D. RECEPTION AREA/CHECK-IN
1. Twenty-two (22) quadraplex electrical outlets, location as determined by VA.
2. Twelve (12) telecommunication outlets, location as determined by the VA.
3. Minimum eight (8) foot-counter, with solid worksurface countertops utilizing concealed mounting brackets, where practicable. Under counter storage cabinets provided by VA furniture vendor.
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 4 of 12
4. Centralized for efficient utilization of staff. Separate check-in and check-out counters.
5. Reception area shall be strategically located to allow the office manager and/or team leader clear observation of waiting areas.
6. Reception area shall be adjacent with the Office Manager space.
7. Direct access to waiting area.
8. Duress alarm.
9. One (1) dimmer light switch.
10. Window coverings to have horizontal manual roller shades with solar glare and heat reduction.
11. Luxury Vinyl Tile (LVT).
12. Layout with counter, electrical, telecommunication outlets shall be reviewed by the VA for final approval.
E. MANAGEMENT AREA
1. One Staff workroom/storage room 120 NUSF each
2. Two Leadership office 120 NUSF each
3. One Administrative staff workstation 67 NUSF each
4. Three HAS workstation 67 each
5. Eight (8) quadraplex electrical outlets; one (1) per wall. Four power outlets at the desk meets the minimum requirement for monitors, docking station, wireless phone adapter, and accessory without the use of power strips.
6. Four (4) telecommunication outlets.
7. Power and data outlets should be at desk height when installed in modular furniture.
8. Duress Alarm.
9. One (1) Dimmer light switch.
10. Window coverings to have horizontal manual roller shades with solar glare and heat reduction.
11. Positioning furniture to ensure safety the of clinical staff; provided easy egress or exist. Reference the conceptual drawing for furniture placement.
12. All rooms (except IT Closet) should be master keyed, locking mechanism should be on the inside of the frame, and locking mechanism must be approved by the VA.
13. Layout shall be reviewed by the VA for final approval.
F. EMPLOYEE BREAK ROOM
1. One staff multipurpose room/breakroom 300 NUSF
2. One Staff personal property locker alcove 60 NUSF
3. Six (6) duplex electrical outlets (refrigerator, microwave oven, two counter height, two 16” to 18” from floor)
4. Minimum of ten (10) feet of counter with base and overhead cabinets; double compartment sink.
5. Luxury Vinyl Tile (LVT)
6. Automated touchless sanitizer dispenser provided by the lessor.
7. One (1) Dimmer light switch.
8. Space shall be large enough to accommodate lockers, table and chairs
9. Layout shall be reviewed by the VA for final approval.
G. JANITORIAL / UTILITY CLOSET
1. Two Housekeeping Aides Closet (HAC) 0 NUSF (Lessor space)
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 5 of 12
2. Mop Sink.
3. Two (2) duplex electrical outlets.
4. Adjustable wire shelving on two walls.
5. Tile flooring
H. SUPPLY/STORAGE/SUPPORT ROOMS
1. One Recycling Holding Station 48 NUSF
2. One Trash Holding Room 72 NUSF
3. One Receiving Area 120 NUSF
4. One Breakdown Area 120 NUSF
5. One Full Gas Cylinder Storage Room 48 NUSF
6. One Empty Gas Cylinder Storage Room 48 NUSF
7. One Logistics Staff Workstation 67 NUSF
8. One Soiled utility 100 NUSF
9. One clean utility 125 NUSF
10. Six (6) duplex electrical outlets (two counter height, four 16” to 18” from floor)
11. Two (2) telecommunication outlets.
12. Luxury Vinyl Tile (LVT)
13. Layout shall be reviewed by the VA for final approval.
I. CLEAN SUPPLY ROOM/STERILE SUPPLY STORAGE
1. One Medical Equipment Storage Room 144 NUSF
2. One Clinical Supplies Storage Room 200 NUSF
3. One Sterile Supplies Storage Room 180 NUSF
4. Four (4) duplex electrical outlets (two counter height, two 16” to 18” from floor)
5. Two (2) telecommunication outlets.
6. Welded Seam Sheet Flooring (Heat Welded with Rod)
7. Layout shall be reviewed by the VA for final approval.
J. LABORATORY AREA
1. Two Blood draw station 77 NUSF
2. One Bariatric blood draw station 90 NUSF
3. One Laboratory specimen processing 144 NUSF
4. One Laboratory clean supply storage room 72 NUSF
5. One Laboratory soiled holding room 72 NUSF
6. One Handwashing station 12 NUSF
7. One Laboratory lead tech workstation 58 NUSF
8. Luxury Vinyl Tile (LVT)
9. Space requires sink
10. Layout shall be reviewed by the VA for final approval.
K. PATIENT CARE AREA
1. One Women veteran patient care room 168 NUSF
2. Fifteen General patient care room 150 NUSF each
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 6 of 12
3. One Bariatric patient care room 240 NUSF
4. Four Counseling patient care room 144 NUSF
5. One Accessible patient height and weight station 60 NUSF
6. Four Consult patient care room 144 NUSF each
7. One Group Room 288 NUSF
8. One Point of use equipment, supply and medication alcove 84 NUSF
9. Two Hoteling workstation 58 NUSF each
10. 23 Clinical staff workstation 72 NUSF each
11. Two Team copy/supply alcove 36 each
12. Each patient care room requires a sink and upper cabinet casework
13. Luxury Vinyl Tile (LVT)
14. Layout shall be reviewed by the VA for final approval.
L. TELECOMMUNICATIONS ROOM
1. The Lessor shall ensure all below requirements from the VA Office of Electronic Healthcare
Modernization Site Infrastructure and End User Device Requirements are met.
2. Minimum of 80 square feet (8’x10’ form factor) for a one-rack telecommunications room (TR) and an additional 20 square feet for each additional rack required. Health care facility TRs shall be a minimum of 180 square feet. One Demarc Room 96 NUSF
3. Local Area Network (LAN)
i. Reference: Infrastructure Standard for Telecommunications Spaces, Version 3.1, https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecomSpaces.pdf.
ii. Horizontal cabling shall be Category 6 (Cat6) or higher (American National Standards Institute
(ANSI)/Technology Industries Association (TIA)-1179 Healthcare Facility Telecommunications Infrastructure). If existing horizontal cabling is not minimally Cat6, Lessor shall upgrade to Category 6A (Cat 6A).
iii. Telecommunications outlets/connectors and the horizontal cross-connects (patch panels) shall be of equal or greater Category to connected horizontal cable.
iv. Installation shall be compliant with the BICSI standards (ANSI/NECA/BICSI 568, Standard for Installing Commercial Building Telecommunications Cabling and ANSI/TIA-1179-A Healthcare Facility Telecommunications Infrastructure for new installations).
1. New cable installations additionally shall be compliant with TIA 568.2-D, TIA TSB-184-A, and NFPA-70 Section 725.144 to prevent PoE heat accumulation. Provide certification reports to the COR.
2. Alternatively, new UTP cabling shall carry a UL listed "LP" (Limited Power) rating.
3. Cat6A cable shall be terminated to a CAT6A RJ-45 patch panel in IT closet and CAT6A RJ-45 jack at wall plate and labeled at both ends.
4. Use a cable analyzer to determine cable length (max cable length 90M/295 linear feet) and certify that cable meets or exceeds TIA-EIA-568-C.2.
5. Cables shall be installed in continuous lengths from origin to destination, no splices with a 1’ service loop.
v. All patch cables shall be Category 6A for copper, OM4 for multi-mode fiber or OS2 level for single mode fiber.
https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecomSpaces.pdf
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 7 of 12
vi. Cable management shall be implemented for all patch cables in accordance with the latest version of Infrastructure Standard for Telecommunications Spaces, ensuring proper bend radius, bundling, airflow, support and labeling.
vii. 1 GbE connectivity to desktops, and other End User Devices.
viii. End-to-End latency from the user desktop to Cerner Data Center of equal to or less than 90ms for
Citrix connection.
ix. Provide additional data drops and network ports in Telecommunication Rooms (TR) to support required network printers and medical devices per Cerner Current State Review (CSR). If the CSR is not provided as an attachment to this document, an additional Lease Amendment may be required.
x. Copper structured cabling shall be certified as meeting or exceeding TIA-EIA-568.1-D (max fixed cable length 90M/295 linear feet) independent of media type.
xi. Lessors shall provide service with a minimum of 10 GbE fiber or better.
xii. Network Infrastructure devices supported by UPS and/or //Emergency Power / Backup Generator as described below in 2.3//.
4. Power
i. UPS Functional Requirements: This Scope of Work includes UPS requirements for OIT equipment only. All OIT equipment in the Telecommunications Room shall be connected to the UPS.
1. All UPS units supporting Information Technology infrastructure shall be functional and maintain a 10-minute run-time.
2. UPS shall be managed and report the following information to a management system.
a. Overload
b. Battery Temperature High
c. Battery Charge Low
d. Battery Failure
e. Critical Condition (fan failure, low output voltage, etc)
ii. UPS shall support both monitoring and remote management to include full compliance with RFC- 1628 – UPS Management Information Base Support for Simple Network Management Protocol (SNMP) v3.0, BaCnet and Modbus protocols.
iii. UPS shall be connected to a monitoring system by Ethernet (wired or wireless) or serial interface (RS- 232 or RS-485).
iv. All units within one (1) year of end of life by facility Go-Live shall be replaced with new units.
1. End of Life for stand-alone units assumed to be six (6) years from date placed into service.
2. End of Life for UPS batteries assumed to be three (3) years from date replaced.
v. Upstream bonding requirements to the Secondary Bonding Busbar or Primary Bonding Busbar must use two lugs. Bonding for telecommunications equipment must be performed per manufacturer's specifications. All grounding shall comply with ANSI/NECA/BICSI 607-C, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, November 2015.
5. Heating, Ventilation, and Air Conditioning (HVAC) Design Requirements
i. Reference: U.S. Department of Veterans Affairs Office of Construction & Facilities Management HVAC
Design Manual, dated May 1, 2019, https://www.cfm.va.gov/til/dManual/dmHVAC.pdf.
ii. Telecommunications Rooms, Class B space temperature range 41°F to 95°F, relative humidity: 8 to
80% noncondensing.
1. Temperature and humidity shall be monitored in proximity to the OIT equipment rack. Place sensors either on populated rack or within 6 feet of rack.
2. Temperature and humidity shall be connected to a monitoring system by Ethernet (wired or wireless) or serial interface (RS-232 or RS-485).
https://www.cfm.va.gov/til/dManual/dmHVAC.pdf
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 8 of 12
3. In areas where there are environmental issues (e.g., steam pipes, lack of ventilation, etc.), the use of thermal curtains and additional vents will be considered as a temporary alternative, not permanent resolution. Any existing temporary alternatives, such as thermal curtains and door vents, shall be corrected with an approved, engineered solution.
6. Physical Security Design Requirements
i. Reference: Infrastructure Standard for Telecommunications Spaces, https://www.cfm.va.gov/til/dManual/dmTelecomm.pdf.
ii. Provide an electronic Security Management System (SMS) with a Physical Access ContrMost ol System (PACS).
iii. Doors shall include a mechanical spring loaded “deadlocking feature” (not separate “deadbolt” lock), PACS associate electronic Personal Identity Verification (PIV) card access device with keypad, electric strike and digital Closed Caption Television (CCTV) color camera routed to and directly controlled by the facility SMS.
iv. Telecommunication Room security system shall be connected to a UPS or emergency backup power system.
v. Facility programmable door controller shall be fully functional in a standalone status if connection to the SMS is lost. Once the connection is restored, the local door control system shall update the SMS, regarding all operations that occurred after the connection was interrupted. Then, the SMS shall update the local door control units to current operational function.
vi. The PACS and SMS shall be fully compliant with VA’s PII, PIV "Smart" ID Card and at a minimum, FIPS 201-1 and NRTL (i.e. UL) listed and labeled.
7. Access to the Telecommunications Room will be restricted to include only those persons specifically authorized by VA OIT, including facility lessors.
8. All perimeter walls shall extend from floor slab to structural system (deck) to prevent up and over access.
9. The Telecommunications Room shall be secured to VA access only and not be shared with any other tenant. Core should be locked to the VA OIT TR key.
10. Please refer to the OIT Enterprise Facility IT Support Infrastructure Standards for details
11. Questions about telecommunications infrastructure guidance can be directed to OIT.
12. Layout shall be reviewed by the VA for final approval.
M. TELECOMMUNICATIONS OUTLETS (TO CONNECT INTO THE VHA NETWORK)
1. Standard Data Outlets: Each data outlet/device location will have four (4) cable runs that terminate on the high- density rack mounted patch panel in the Telecommunications Room. Each typical data outlet will be on a four-port base plate.
2. Wall Mounted Phones: Any jacks for wall mounted phones should have 1 data cable to support VoIP, and be on a 1 port metal plate, and accommodate RJ45.Cabling must be installed according to BISCI standards.
https://www.cfm.va.gov/til/dManual/dmTelecomm.pdf
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 9 of 12
3. All permanent link cabling from the Telecommunications Room to the outlet shall be continuous runs with no splices and be less than 295’.
4. Patch Panels, jacks, and cable shall all be rated at Cat 6A and be tested and certified. A copy of the test results will be provided to the COR as a deliverable.
5. Must have the capability to add additional data locations as determined by occupants to be provided by the lessor within ten days from request.
6. VAMC can suggest a cable contractor if necessary.
7. Location of Data Outlets:
a. If the construction at the location of the data outlet is drywall, provide flush-mounted single-gang outlet boxes with four-port base plates and applicable wall device faceplates (cable to be installed behind drywall).
b. If the construction at the location of the data outlet is a solid wall, provide surface-mounted single-gang outlet boxes with four-port base plates and applicable wall device faceplates (cable to be installed in plastic wall mold equipped with protective insulator or sleeve).
c. Where modular furniture is used, the location of the data outlet will be in the baseboard of the furniture, where the networked equipment (computers, printers, etc.) will be located. Provide flush-mounted single gang outlet boxes with four-port base plates and applicable wall device faceplates. If flush-mounted single-gang outlet boxes cannot be used, then modular surface mount boxes will be used with four-port inserts. All cable runs in modular furniture will be through furniture wire baseboard ducts/conduit.
8. The contractor shall follow VA naming and labeling conventions as detailed in section 5.1.5, Information Transport Systems Equipment and Component Labeling, of the Infrastructure Standard for Telecommunications Spaces. Labels shall be attached at both the patch panel and wall plate. All labeling shall be easily visible and printed; hand-written labeling is prohibited.
9. Layout shall be reviewed by the VA for final approval.
N. FINISHES
1. All finish selections shall be reviewed and approved by the VA.
2. Color Board/Finish options are available, provided by VA.
3. Lessor to provide samples of their specific manufacturer finishes for VA approval.
4. Brand Name or Equal. Characteristics and level of quality that will satisfy the Government’s needs.
a. Carpet Tile (offices, group rooms, family/multi-purpose) – INTERFACE
b. Luxury Vinyl Tile Flooring (waiting, corridors, kitchen) 5mm commercial grade thickness –
ARMSTRONG
c. Sheet Vinyl, homogeneous (storage) 6.58” x 98.4’ x 0.80 – ARMSTRONG
d. Solid Surface Counter - AVONITE
e. Casework Laminate (kitchen, built ins) - WILSONART
f. Doors Oil Based Stain - MINWAX
g. Wall Base - INPRO
h. Seven (7) paint colors with five (5) serving as accent wall color, one (1) field color, one (1) color for trim – BENJAMIN MOORE https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecommSpaces.pdf https://www.cfm.va.gov/til/dguide/OIT-InfrastrucStdTelecommSpaces.pdf
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 10 of 12
i. Restroom: Porcelain Tile Floor, Porcelain Tile Wall (4’ up the wall), Ceramic Tile Accent Strip –
DALTILE
j. Acoustical Ceiling Attenuation System with 0.75 Noise Reduction Coefficient (NRC)/Ceiling Attenuation Class (CAC)
O. SIGNAGE
1. Interior Signage.
a. Lessor shall provide interior signage for a standard wall sign.
b. Lessor shall provide samples for the VA to review and approve.
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 11 of 12
c. VA to approve sign design schematic prior to fabrication/installation.
d. VA Interior Signage Manual PG-18-10 VA Signage Design Manual
e. Mounting heights are 5’-0” to top of sign and 2” from door frame.
2. Exterior Signage.
a. Lessor shall provide Exterior Signage on the building suite
b. Lessor shall provide VA logo on marquee or monument sign.
c. Lessor shall provide samples for the VA to review and approve.
d. VA to approve sign design schematic prior to fabrication/installation.
e. Lessor shall develop, provide, deliver, stage/move, and install the new exterior sign
f. Lessor shall provide all the equipment, cabling, labor, materials, and sign.
g. Signage shall comply with local municipality’s codes and specifications.
h. Signage shall be legible from main serving road.
i. Size: Minimum of 4ft by 8ft
j. Lighting/Electrical:
• Internally lighted sign using channel lettering
• LED
• Dusk to Dawn Photocell
• Each part of the stencil style font is like a separate sign
3. Main Entry Door Decal.
a. VA to approve sign design schematic prior to fabrication/installation.
b. Lessor shall provide signage on the main entrance door.
c. Decal Information to include:
• Name
• Address
• Open Monday – Friday 7:30AM–4:00PM
• Phone Number
• After Hours Call Center
• Veterans Crisis Line Call 1-800-273-8255 and Press 1 to receive confidential support 24 hours a day.
• VA Seal:
Special Topic Criteria - Office of Construction & Facilities Management (va.gov) SD101400-03.pdf (va.gov) Color Specifications for the Department of Veterans Affairs Seal (va.gov)
4. Entrance Signs.
d. Lessor shall provide the mandatory entrance signage. VA Signage Design Guide
e. VA to approve sign design schematic prior to fabrication/installation.
f. No Smoking, IN-02.02, 18”-20”
g. No Weapons Permitted, IN-02.10, 6” x20”
h. Sample Illustration.
https://www.cfm.va.gov/til/dManual/dmSignage.pdf https://www.cfm.va.gov/til/spclRqmts.asp#PS https://www.cfm.va.gov/til/sDetail/Div10Specialties/SD101400-03.pdf https://www.cfm.va.gov/til/etc/VASealColors.pdf https://www.cfm.va.gov/til/signs/Signage07-Mandatory.pdf
Government Offeror Vero Beach Primary Care Clinic - ASR - Page 12 of 12
P. HVAC Design:
1. Lessor must adhere to VA HVAC Design Guide and HVAC Design Manual, VA Technical Information
Library
2. Temperature, humidity and pressure requirements, for the types of rooms listed below, must be monitored and recorded from a building automation system in accordance with ASHRAE 111, 170 and
180. The building automation system must electronically alert the space owner when conditions are out of range within specified timelines in accordance with ASHRAE 111, 170 and 180.
i. Clean utility
ii. Storage
iii. Clinical supply storage
iv. Sterile supply storage
v. Supply storage
vi. Clean supply storage
Q. Generator quick connect
1. Lessor shall provide inclusion of a portable electric generator quick connection and associated transfer switch. The lessor shall provide a design to include the specifications, location and characteristics of a portable electric generator quick connection and associated transfer switch that will comply with building infrastructure/equipment needs for return to normal operations in the event of loss of normal power. A 525 gallon portable electric generator will be provided by the VA. Spec sheet included below
Cat® XQ425 Rental Generator Set
Standby 375 kW, 469 kVA Prime 340 kW, 425 kVA
U.S. EPA Tier 4 Final 50/60 Hz Switchable
1500-1800 rpm
Cat® C13 ACERT™ Diesel Engine Metric Imperial (English)
Configuration I-6, 4-Stroke-Cycle Water Cooled Diesel
Bore 130 mm 5.1 in
Stroke 157 mm 6.2 in
Displacement 12.5 L 763 in3
Aspiration Turbocharged-Aftercooled
Compression Ratio 17.0:1
Fuel System MEUIC
Governor Type ADEM™ A4
Aftercooler ATAAC
Turbocharger Single
Fuel Requires ULSD
Specification
Image shown may not reflect actual configuration
LEHE1123-06
Generator Frequency Speed rpm Voltage Standby kW (kVA) Prime kW (kVA) Phase Amp (A)
Standard
60 Hz 1800 480/277V 375 (469) 340 (425) 3-phase 511.19
60 Hz 1800 240/139V 375 (469) 340 (425) 3-phase 1110.29
60 Hz 1800 208/120V 350 (438) 320 (400) 3-phase 1022.39
50 Hz 1500 400/230V 320 (400) 290 (363) 3-phase 523.22
Optional 60 Hz 1800 600V 375 (469) 340 (425) 3-phase 408.96
60 Hz 1800 480V 320 (400) 292 (365) 3-phase 439.03
Benefits & Feature Fuel/Emissions Strategy
• �Meets U.S. EPA Tier 4 Final and CARB
Certified for Non-Road Mobile applications at all 50 and 60 Hz ratings
Single-source Supplier
• �Factory designed and fully prototype tested with certified torsion vibration analysis available
• �ISO 9001:2000 compliant facility
Cat C13 ACERT Tier 4 Final Diesel Engine
• �Uses ACERT Technology and Cat NOx
Reduction System (NRS)
• �Four-stroke diesel engine combines consistent minimum weight
Cat CEM (Clean Emissions Module)
Diesel Exhaust Fluid (DEF) Tank
• �12 gallon DEF tank with on tank fill and integrated pump, level sensor and heating elements
• �Electrically heated DEF lines from DEF tank to CEM
Cat EMCP 4.2 Control Panel
• �Fully featured power metering, protective relaying and engine/generator control and monitoring
| • | �Simple user friendly interface and navigation |
| • | �Automatic set-point adjustment integrated with |
voltage and frequency changes
Cat SR4B Series Generator
• �Designed to match performance and output characteristics of Cat diesel engines
| • | �Permanent magnet excitation |
| • | �Segregated AC/DC, low voltage accessory |
box provides single-point access to accessory connections
Cat Digital Voltage Regulator (Cat DVR)
| • | �Three-phase sensing |
| • | �Adjustable volts-per-hertz regulation |
| • | �Provides precise control, excellent block |
loading, and constant voltage in the normal operating range
Enclosure
• �Highly corrosion-resistant 12-gauge sheet steel construction
| • | �Two-coat polyester powder-coated finish |
| • | �7 doors and 3 access doors for ease of |
maintenance
• �Secure and safe design with safety glass control panel viewing window with lockable access door
• �Fuel fill and battery can only be reached through lockable access doors
Distribution Panel*
• �Switchable via linkboard from 480/277V
3-phase to 240/139V 3-phase (can be adjusted down to 208/120V 3-phase)
Rear Customer Access
• �Separate control panel and distribution panel access doors
| • | �Hinged door over main bus connectors |
| • | �Emergency stop on panel |
| • | �Remote start/stop contacts |
Reduced Environmental Impact
| • | �EPA Tier 4 Final technology |
| • | �110% spill containment of onboard engine fluids |
| • | �Meets 76 dB(A) at 7 m per SAE J1074 |
Rental Ready Features
• �Anti-condensation heater 110-120 VAC
• Coolant heater 110-120 VAC
• UL Listed battery charger
• Solar powered battery maintainer
*N/A for 600V
LEHE1123-06
performance and excellent fuel economy with
Electronic engine controller
Aftertreatment module consists of Caterpillar Regeneration System (CRS), Diesel Oxidation Catalyst (DOC), Diesel Particulate Filter (DPF), and Selective Catalytic Reduction (SCR)
Single-point lift designed to lift complete package measurement procedure at 75% prime loads
• Variable speed cooling fan for reduced fuel consumption and reduced sound as part load
Factory-installed Standard Equipment Air Inlet
• �Air cleaner, two-stage cyclonic/paper with dust cup and service indicator
• �Turbocharger and air-to-air aftercooler
Charging System
• �UL/CSA listed 120V, 20A battery charger, shock mounted and enclosed in dust-proof housing
• �Charging alternator; 24V-45A, heavy-duty with integral regulator and belt guards
Control Panel
• �EMCP 4.2 generator set mounted controller
• NEMA 2, IP23 dust-proof enclosure, UL508 listed
• Idle/rated and 50/60 Hz frequency switches
• Generator protection features: 32, 32RV, 46, 50/51, 27/59, 81 O/U
• Metering display: voltage, current, frequency, power factor, kW, WHM, and kVAR
• Panel illumination lights and emergency stop switch
Cooling System
• �Package-mounted radiator with vertical air
| • | �Blower fan, fan drive, fan guard, and belt guards |
| • | �120VAC coolant heater, fuse protected, |
thermostatically controlled, automatically disconnected on start-up
| • | �Coolant sight gauge, level switch, and shutdown |
| • | �50% coolant antifreeze with corrosion inhibitor |
Distribution System
• �NEMA 1 steel enclosure, separate hinged, lockable door with rust-resistant pinned hinges
• �Main bus connections with hinged load cover with Plexiglas window closed for operation
• �Main circuit breaker 3-pole, 240/480V-1600A with
24V DC shunt trip wired to load door safety switch
| • | �Current transformers, hard mounted |
| • | �Multiple duplex and twist-lock receptacles with |
individual circuit breakers
• �Two-wire remote start/stop terminals and 120 VAC shore power connection for rapid starting
Enclosure
• Sound attenuating, 12-gauge sheet metal enclosure
• Modular panel construction and one-piece welded roof design with 2 degree pitch
• �Interior walls and ceilings insulated with flame retardant, precision cut foam materials meeting
NFPA220
• �Black stainless steel pad-lockable latches, doorkeepers on all doors and zinc die-cast hinges/grab handles
| • | �Single-point lifting |
| • | �Painted Cat power module white with Cat |
rental decals Engine
• �EPA Tier 4 Final certified Cat C13 ACERT
ATAAC heavy duty diesel engine
• �Electronic ADEM A4 controls
CEM
• Cat CEM comes with integrated DOC, DPF, and
SCR and is located in separate compartment
DEF System
• �DEF tank is equipped with integrated pump, level sensor to display the DEF level in EMCP panel, and electrically heated lines from DEF tank to CEM
• �Equipped with low and critically low level alarms with a critically low shutdown
Fuel System
• �520 gal (1970 L) double wall fuel tank, UL142,
| • | �Switch operated, electric priming pump |
| • | �Auxiliary connections for customer supplied fuel |
transfer system with 6-way fuel transfer valve
LEHE1123-06
discharge provides 43°C ambient capability base-frame Coolant drain line with shut off valve piped to
12 gal plastic DEF tank provides 33 hours run time @ 75% Prime
ULC, and Transport Canada certified, 29 hours run time @ 75% prime Engine mounted primary and secondary fuel filter with water separator
• Radiator mounted fuel cooler
LEHE1123-06 Page 4 of 8
Factory-installed Standard Equipment (continued) Generator
• �SR4B 450 frame, three-phase, random wound, 12-lead design, permanent magnet excited,
0.750 pitch
• �240-480 volt link board built into distribution system provides either 480/277 volt or 240/139 volt*
| • | �Coastal insulation protection |
| • | �Windings impregnated in a triple dip, thermo- |
setting moisture, oil and acid resisting polyester varnish; heavy coat of anti-tracking varnish for additional protection
• Cat DVR with VAR/PF control, RFI suppression, exciter diode monitor
• 120VAC anti-condensation heater
Lube System
• Pump, integral oil cooler, lube oil, filter, filler and dipstick, and oil sampling valve
• Open crankcase breather with 75% filter
• Oil drain line with internal brass ball valve routed to connection point accessible from exterior
• 500-hour oil change intervals
Mounting System
• Generator set soft mounted to the heavy-duty, fabricated steel base frame
• Skiddable steel base frame with tie-down eyes contains integral fuel tank
• Provides 110% spill containment of all engine fluids
Starting System
• Single electric starting motor, 24V
• Dual 12V (1400 CCA) maintenance free batteries with disconnect switch, battery rack, and cables
• UL listed, 120V single-phase jacket water heater with thermostat and shut-off valves
General
• Canadian Standards Authority (CSA) certified
• Factory testing of standard generator set
• Full manufacturer’s warranty
• O&M manuals
Optional Equipment Available Options
• Tandem axle trailer with electric brakes
Cat EMCP 4.4 Control Panel
• Simple user-friendly interface and navigation
• Automatic set-point adjustment integrated with voltage and frequency selection
• UL508A recognized
• Convenient service access for Cat service tools
(not included)
• Integration with the Cat DVR provides enhanced system monitoring
• Ability to view and reset diagnostics of all controls networked on primary CAN data link eliminates need for separate service tools for troubleshooting
• True RMS AC metering, 3-phase
• Multiple stored setpoint group selection via switched input eliminates need to reprogram control when switching voltages and frequencies
EMCP 4.4 Engine Operator Interface
• Controls
- Run/Auto/Stop - Emergency stop
- Speed adjust - Cycle crank
- Voltage adjust - Cool-down timer
• Digital indication for
- RPM - DC volts
- Operating hours - Oil pressure
- Coolant temperature - Oil temperature
- L-L volts, L-N volts, phase amps, Hz
- ekW, kVA, kVAR, kW-hr, %kW, PF
• Shutdowns with common indicating light for
- Low oil pressure - Overspeed
- High coolant temp - High oil temp
- Failure to start (overcrank) - Emergency stop
- Low coolant level
• Emergency stop pushbutton
• Panel illuminating lights
• Display navigation keys including two shortcut keys for engine parameters, generator parameters, control, and main menu
• Fuel level monitoring and control
EMCP 4.4 Generator Protective Relaying
• Phase over/under voltage (device 27/59)
• Over/under frequency (device 81 O/U)
• Reverse power (device 32/32RV)
• Current balance (46)
• Overcurrent (device 50/51)
• Bus phase sequence
*N/A for 600V
Technical Data Cat Generator
Frame size SR4B – 450 Pitch 0.750 No. of poles 4 Excitation Static regulated brushless PM excited Number of bearings Single bearing, close coupled Insulation Class H Temperature rise 105°C Enclosure Drip proof IP23 Overspeed capability – % of rated 125% of rated Voltage regulator 3-phase sensing with volts-per-hertz
Voltage regulation Less than ± 1/2% voltage gain (adjustable to compensate for engine speed droop and line loss)
Wave form deviation 3% Telephone Influence Factor (TIF Less than 50% Harmonic Distortion (THD) Less than 5%
Modes Of Operation
• Provides for:
- Single unit standalone mode
- �Island mode paralleling and load sharing (multi-unit mode) with other EMCP4.4 product
• Single unit standalone mode
- �The utility is providing power for the plant loads
- The PM generator breaker is open
- �The PM is in automatic standby mode to respond to a utility failure
• Multi-unit mode
- �Features auto synchronization (voltage and phase matching), load sharing (kW) analog signal (like units only), and load sharing (kVAR) analog signal (like units only)
- �The customer protective relaying senses a utility abnormal condition
- �A run request is sent to the PM generator plant
- �The first PM generator to reach rated to voltage and frequency is closed to the bus and remaining units are paralleled to the bus as they reach rated voltage and frequency
- �Plant load is transferred to the power modules, which share load equally via load share lines
Optional Equipment (continued)
LEHE1123-06
Weights and Dimensions
Model Length mm (in)
Width mm (in)
Height mm (in)
Weight with Lube Oil & Coolant kg (lbs)
Weight with Fuel, Lube Oil, & Coolant kg (lbs)
XQ425
without trailer
(208.7) (60)
(104)
(14,700)
(18,900)
XQ425
with trailer
(283.7)
(102)
(126.1)
(17,930)
10 036 (22,130)
LEHE1123-06
Technical Data (continued) Cat Generator Set
Units 50 Hz 60 Hz
Standby Prime Standby Prime
Performance Specification EM0677 EM0678 EM0675 EM0676 Power Rating kW (kVA) 320 (400) 290 (360) 375 (468) 340 (425)
Lubricating System
Total oil pan capacity L (gal) 37 (9.8) Fuel System
Fuel Consumption – 100% Load 75% Load 50% Load
Fuel Tank Capacity Running Time @ 75% rating
L/hr (gal/hr) L/hr (gal/hr) L/hr (gal/hr)
L (gal) Hr
82.1 (21.6)
62.4 (16.4)
43.9 (11.5) 1970 (520)
75.3 (19.8)
57.3 (15.1)
40.2 (10.6) 1970 (520)
95.7 (25.1)
73.4 (19.2)
52.3 (13.6) 1970 (520)
88.0 (23.1)
67.9 (17.7)
48.6 (12.7) 1970 (520)
DEF System
DEF Tank Capacity DEF Consumption – 100% Load
75% Load Running Time @ 75% rating
L (gal) L/hr (gal/hr) L/hr (gal/hr)
Hr
48 (12)
48 (12)
48 (12)
2.5 (0.7)
1.8 (0.5)
48 (12)
2.4 (0.6)
1.5 (0.4)
Cooling System
Ambient capability Engine & radiator coolant capacity
°C (°F)
L (gal)
61 (16.2)
Air Requirements
Combustion air flow m3/min (cfm) 19.7 (693.2) 18.3 (646.1) (828.3) (803.3) Exhaust System
Exhaust flow at rated (dry exhaust Exhaust temperature at rated kW m3/min (cfm) °C (°F)
13.8 (485.1)
496.4 (924.7)
13.1 (460.3)
488.9 (911.8)
16.0 (565.7)
473.4 (880)
15.9 (558.9)
454.1 (846.9)
Noise rating @ 7 meters and 75% load
25⁰C, Sea Level 43⁰C, 500m dB(A) dB(A)
Emissions (not to exceed data)
NOx
CO
HC
PM
g/hp-hr g/hp-hr g/hp-hr g/hp-hr
1.42 0.08 0.01 0.02
1.28 0.07 0.01 0.02
1.55 0.08 0.02 0.01
1.56 0.07 0.02 0.02
Standard Features
• NEMA 2, IP23 dust-proof enclosure with hinged lockable door and viewing window
• EMCP 4.2 display
• Panel light on/off switch
• Emergency stop pushbutton
• Lamp test/reset pushbutton
• Voltage adjust potentiometer
• Alarm and shutdown indicators
• Idle/rated switch
• Regeneration alarm indications for DPF 80% soot level and high exhaust temperature
• 50/60 Hz frequency adjustment
• Fuel level display
• Convenient service access for Cat dealers
(service tools not included)
EMCP 4.2 Engine Operator Interface
• Controls
- Run/Auto/Stop - Emergency stop
- Speed adjust - Cycle crank
- Voltage adjust - Cool-down timer
• Engine monitoring
- RPM - DC volts
- Operating hours - Oil pressure
- Coolant temperature - Oil temperature
- Crank attempt and successful start counter
• Generator monitoring
- L-L volts, L-N volts, current (phase)
- Average volts, amps, frequency
- ekW, kVA, kVAR, kW-hr
- Power factor (average, phase)
- kW-hr, kVA-hr (total)
- Excitation voltage and current (with Cat DVR)
• Shutdowns with common indicating light for
- Low oil pressure - Overspeed
- High coolant temp - High oil temp
- Failure to start (overcrank) - Emergency stop
- Low coolant level
EMCP 4.2 Generator Protective Relaying
• Generator phase sequence
• Over/under voltage (27/59)
• Over/under frequency (81 O/U)
• Reverse power (kW) (32)
• Reverse reactive power (kVAR) (32RV)
• Over current (50/51)
Distribution Panel
• Separate load and control sections
• Access using a hinged padlock-able door
• Main busbar with hinged cover door with a clear
Plexiglas window
• Customer convenience power receptacles protected by miniature circuit breaker:
1 – 240V, 50A California-style twist lock 1 – 240V, 20A twist lock 2 – 120V, 20A ground fault interrupters 2 – 120V, 15A duplex receptacles with GFI
Circuit Breaker
• Includes DC shunt trip coil activated on any monitored engine or electrical fault
• 100 KA-interrupting capacity at 480 VAC
• Undervoltage release
• 1600A fixed type, 3 poles, generator set mounted*
• 600A fixed type 3 poles, generator set mounted
(600 V only)
Link Board Assembly*
• High/low voltage output reconnection via movable link board
• Includes switch providing voltage setting input to the EMCP 4.2 for automatic set point configuration
*N/A for 600V
LEHE1123-06
www.cat.com/rentalpower ©2021 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, "Caterpillar Corporate Yellow", the "Power Edge" and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission. LEHE1123-06 (01/21)
Meets or Exceeds International Specifications:
CSA 22.0 No. 100, IEC60034-22, ISO3046, ISO8528, NEMA MG1-22, NEMA MG1-16, UL1004B, NEC,CEC, 2006/42/EEC, 2006/95/EC, 2004/108/EC, 2000/EC/14, UL142, Ulc601, IBC
CGSB43, API 546, EGSA 101P, IEEE 43, DEFRA,
UL1741, NFPA 99/110, OSHA, 97/68/EC, BS4999,
BS5000, IEC60034-5.
Fuel Rates are based on fuel oil of 35° API [16°C (60°F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29°C (85°F) and weighing 838.9 g/liter (7.001 lb/U.S. gal).
Additional ratings may be available for specific customer requirements, contact your Caterpillar representative for details. For information regarding low sulfur fuel and biodiesel capability, consult your Cat dealer.
Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions.
Standby – Applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The generator on the generator set is peak prime rated (as defined in ISO8528 at 30°C (86°F).
Prime – Applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation on the annual hours of operation and the generator can supply 10% overload power.
Ratings Definitions and Condition www.Cat.com/rentalpower
| 3 - Exhibit B - Agency Special Requirements |
| Generator specifications |
File details come from the government source that posted it. Updated .