Text version

PM-723-R1

Mainline Propeller Meters Models 101/102

DESCRIPTION

Model: Sensus 101/102 Propeller Meters are primarily intended for accountability measurement of potable and non-potable cold water with flow in one direction only. Registration accuracy is 100% ± 2% of actual thruput within specified normal flow ranges. Because all appropriate parts are sealed for protection, the meters can be used in water containing particulate solids (such as sand), without causing undue wear.

Performance: The design of the Sensus 101/102 ropeller Meters permits continuous operation up to the maximum rated flow capacity listed for each size, without affecting long term accuracy or causing undue wear. For accurate measurement, a full flow of water through the meter and stated minimum flow rates are required.

Construction: The meter consists of two basic assemblies— the meter tube body and the meter head assembly. Integral straightening vanes in the meter tube body minimize the swirl upstream of the meter so as to direct the flow evenly to the propeller. The 3” through 12” meter tube bodies are internally and externally protected by a superior fusion-bonded epoxy coating for use in potable water systems. The 14” and larger sizes are protected with an epoxy painted finish.

The meter head assembly consists of the propeller, bronze gear box and sealed direct reading register.

Magnetic Drive: Direct magnetic drive eliminates mechanical gearing normally required to operate propeller meter type registers. A ceramic sleeve-type magnet in the propeller assembly drives a follower magnet located in a one piece, all bronze gear box.

This gear box is oil filled and factory sealed to provide lubrication and long life to the register drive shaft.

Propeller: The propeller and nut are made of polypropylene and rotate on a ceramic coated stainless steel spindle.

Registers: Sensus Model 101 Propeller Meters come equipped with a sealed direct reading (DR) register with low flow indicator. The Model 102 is equipped with an electronic rate of flow indicator (E-ROFI) register. The E-ROFI register is an hermetically sealed unit that electronically displays and transmits totalization and flow rate data to various Sensus act-pak instrumentation to monitor, control and record volume and rate of flow. Other register options available are the impulse contactor (IC) and high speed pickup (HSP).

6” Model 101 Propeller Meter

All registers can be positioned in any of four directions for reading ease. Refer to bulletin E-1116 for HSP and bulletin E-1110 for the E-ROFI register.

Installation: Sensus Propeller Meters can be installed in a horizontal, vertical or inclined position. Valves, fittings or other equipment that might create flow turbulence should be positioned at least 5 pipe diameters upstream of the meter and no less than 3 pipe diameters downstream.

Maintenance: The meter head assembly can be removed, repaired and/or replaced without disturbing the meter tube body in line. A spare meter head assembly can be utilized in the event maintenance is required. Cover plates are also available for maintaining service or flushing of lines when the meter head assembly is removed. Factory testing, repair and meter head assembly exchange programs are available.

Standard Sealed Register E-ROFI Register

150 psi (10 bar) Working Pressure Magnetic Drive Flanged Tube Type

PM-723-R1

P.O. Box 487 | 450 North Gallatin Avenue Uniontown, PA 15401 USA T: 1-800-638-3748 F: 1-800-888-2403 www.sensus.com/water h2oinfo@sensus.com

AUTHORIZED SENSUS DISTRIBUTOR

LowFlowNormalRangeShipping
MeterGPMm3/hGPMm3/hABCDEFGHKWeight
Size12inmminmminmminmminmm#inmminmminmmPoundskg
3”80GPM100-250GPM16”7-1/2”3/4”6-1/2”6”45/8”3-3/8”5”70lbs.
DN80mm18.2m3/h23-57m3/h406mm190mm19mm165mm152mm16mm86mm127mm32kg
4”82125-50018”9”5/8”7-1/2”7-1/2”85/8”3-7/8”7-1/2”85lbs.
DN100mm18.628-114457mm229mm16mm190mm190mm16mm99mm190mm39kg
6”160220-120022”11”11/16”9”9-1/2”83/4”5”9”115lbs.
DN150mm36.350-273559mm279mm17mm229mm241mm19mm127mm229mm52kg
8”190250-165024”13-1/2”11/16”9”11-3/4”83/4”6”9”150lbs.
DN200mm43.257-375610mm343mm17mm229mm298mm19mm152mm229mm68kg
10”260330-250026”16”11/16”10”14-1/4”127/8”7-3/8”11”200lbs.
DN250mm59.075-568660mm406mm17mm254mm362mm22mm187mm279mm91kg
12”275350-350028”19”13/16”10”17”127/8”8-3/8”11”290lbs.
DN300mm62.480-795711mm483mm21mm254mm432mm22mm213mm279mm132kg
14”350450-450042”21”1-3/8”12”18-3/4”121”9-1/4”13-1/2”450lbs.
DN350mm79.5102-10221067mm533mm35mm305mm476mm25mm235mm343mm204kg
16”450550-550048”23-1/2”1-7/16”12”21-1/4”161”10-1/4”13-1/2”550lbs.
DN400mm102.2125-12491219mm597mm37mm305mm504mm25mm260mm343mm249kg
18”550752-725054”25”1-9/16”15”22-3/4”161-1/8”11-5/8”13-1/2”620lbs.
DN450mm124.9165-16471372mm635mm40mm381mm578mm29mm295mm343mm281kg
20”700850-900060”27-1/2”1-11/16”15”25”201-1/8”12-5/8”13-1/2”820lbs.
DN500mm159.0193-20441524mm699mm43mm381mm635mm29mm321mm343mm372kg
24”10001300-1300072”32”1-7/8”18”29-1/4”201-1/4”12-5/8”13-1/2”1000lbs.
DN600mm227.1259-25921829mm813mm48mm457mm749mm32mm321mm343mm454kg
30”16002100-1860084”38-3/4”2-1/8”18”36”281-1/4”12-5/8”13-1/2”1150lbs.
DN750mm363.4477-42242123mm984mm54mm457mm914mm32mm321mm343mm522kg
36”24003000-2400096”46”2-5/8”20”42-3/4”321-1/2”12-5/8”13-1/2”1350lbs.
DN900mm545.0681-54502438mm1168mm67mm508mm1086mm38mm321mm343mm613kg

1 Low Flow — 95% minimum accuracy 2 Intermittent Flow — 25% over maximum rated capacity

SPECIFICATIONS

SERVICEMeasurementofcoldwater(potableandnon-potable)
upto100°F(38°C)withflowinonedirectiononly.
OPERATINGContinuousFlows:Refertothechartabove
RANGEIntermittentFlows:25%overthemaximumrated
capacityofanygivensize.
ACCURACY100%±2%ofactualthruput
LOWFLOWRefertothechartabove
MAXIMUM150psi(10bar)

OPERATION

PRESSURE

FLANGE3”Size:Round,AWWA150Class
4”-12”Sizes:Round,AWWAClassD
14”-36”Sizes:Round,AWWA150Class
REGISTERHermeticallySealedDirectReadingRegister
withLowFlowIndicator
METERStandard:Sixdigit,straightreadingtypewithLowFlow
REGISTRATIONIndicator.Full3”dialfacewith100divisionincrements
andacentersweephand.
E-ROFI:Twinsixdigit,LCDtotalizerandrateofflowdisplay.
Poweredbya“C”sizelithiumbatteryfactorysealedinan
hermeticallysealedregister.Registerreplacementis
recommendedeveryfive(5)years.
MATERIALS—3”and4”Size:DuctileIron
METERTUBE6”-36”Sizes:FabricatedSteel

BODY

STRAIGHTENING Fabricated Steel

VANES

COATINGS3”-12”Sizes:Fusion-BondedEpoxy
14”-36”Sizes:EpoxyPaint
METERHEADDuctileIron
PROPELLERANDPolypropylene

NUT

PROPELLER Ceramic Coated Stainless Steel

SPINDLE

GEARHOUSINGOnePieceCastBronze
TRIMStainlessSteel
MAGNETSCeramic

K

4" 108mm

Model 101 Model 102

H

E –Bolt Circle F –No. of Bolts G–Size of Bolts{

31⁄8" 89mm

B

C

D

A

File details come from the government source that posted it. Updated .