3-2508-062 Duchesne Fair Grounds - North Restrooms Drawings 2026.03.26.pdf
PDF 44 MB Posted
- Solicitation number
- RA26-115
- Issued by
- Duchesne County, Utah
About this file
This is a complete set of architectural, structural, civil, mechanical, and plumbing drawings for the construction of a North Restroom Building at the Duchesne County Fairgrounds located at 60 W 400 S Street, Duchesne, Utah. The project, identified as 2508-062, involves the design of a single-story, 960 square foot restroom facility classified as occupancy type U construction with a 5B fire rating. The building will include men's and women's restroom spaces, a customer storage area, and a slop sink room. The facility is designed to accommodate plumbing fixtures including water closets, urinals, lavatories, drinking fountains, and service sinks in compliance with ADA accessibility requirements per ANSI A117.1-2017. A pre-bid conference is scheduled for Wednesday, April 8th, 2026 at 2:00 PM local time at the Duchesne County Centennial Event Center, with attendance encouraged but not required. Written questions must be submitted by April 10th, 2026 at 5:00 PM to the project manager. Bids are due electronically by Monday, April 17th, 2026 at 5:00 PM local time.
The project specifications require compliance with the 2021 International Building Code, International Mechanical Code, International Plumbing Code, and related standards. The facility will utilize pre-engineered wood trusses for roof support, concrete foundation systems, and 8-inch concrete masonry unit construction for exterior and interior walls. Mechanical systems include electric radiant heating panels and ceiling-mounted exhaust fans with variable speed controls and occupancy sensors. The domestic water system incorporates a pressure reducing valve station and recirculation pump, while the sanitary sewer system requires tie-ins to existing county infrastructure with specific separation requirements between water and sewer lines. Site utilities including water, sewer, and electrical connections must be coordinated with the existing Duchesne County infrastructure. All work must conform to local construction standards and permits must be obtained by the contractor prior to commencing work, with specific attention to utility coordination, testing and balancing of mechanical systems, and comprehensive submittals including shop drawings, product data, and operating manuals required within 15 days of contract award.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DUCHESNE COUNTY
FAIRGROUNDS NORTH RESTROOM BUILDING
DRAWINGS
MARCH 26, 2026
FOR BIDDING ONLY
Project #: (2508-062)
03/25/26
230 NORTH 1680 EAST, BUILDING V
ST GEORGE, UT 84790
(435).674.4800
1535 SOUTH 100 WEST
RICHFIELD, UT 84701
(435).896.8266
46 NORTH 200 EAST
ST GEORGE, UT 84770
(435).628.5969
SHEET NO. |PROJECT NO. |
ARCHITECT & CONSULTANTS
SHEET INDEXCODE REVIEW & DESIGN CRITERIA
PLUMBING FIXTURE COUNT
DEFERRED SUBMITTALS
CODE REQUIREMENT ACTUAL BUILDING DESIGNCODE ITEM -
REFERENCE
Is su e D at e:
SYMBOLS
ROOM NUMBER
DOOR NUMBER
EXTERIOR ELEVATION
WALL SECTION
BUILDING SECTION
WALL TAG
DETAIL NUMBER
TYPE
INSULATION
HEIGHT OFtda
FIRE RATING
WALLWALL1si
SHEET NUMBER
DETAIL
SHEET NUMBER
SHEET NUMBER
DETAIL NUMBER
SECTION NUMBER
000 WINDOW NUMBER
KEYNOTE0000 VIEW NUMBER
SHEET NUMBER
0' - 0" C-0
CEILING TYPE
CEILING HEIGHT
CEILING TAG
0 GRIDLINE
LEVEL ELEVATION
SPOT ELEVATION
VICINITY MAP
INTERIOR ELEVATION
VIEW NUMBER
SHEET NUMBER
3/
/2
2:
:2
PM
2508-062 G-001
DUCHESNE COUNTY
NORTH RESTROOM
60 W 400 S ST., DUCHESNE, UT 84021
### OCCUPANTS
Occupancy - Chapter 3 U U
Construction Type - Section 602 5B 5B
Allowable Floor Area - Table 506.2 5,500 SQ. FT. 960 SQ. FT.
Allowable Area Increase - Section 506 N/A N/A
Allowable Height - Tables 504.3 & 504.4 1 STORY, 40' - 0" 1 STORY, 16' - 1 1/2"
Allowable Height Increase - Section 504 N/A
Roof Covering - Section 1505 CLASS "C" FIRE RESISTANCE CLASS "C" FIRE RESISTANCE
Draft Stops - Section 717
N/A
Egress Width - Section 1005
Restroom Accesibility ANSI A117.1-2017
Accesible Entrance - Section 1105.1 At least 60% but not less than 1
PRE-ENGINEERD TRUSSES
3/24/2026
SHEET # DESCRIPTION
1-GENERAL
G-001 TITLE SHEET
2-CIVIL
C-001 CIVIL TITLE SHEET & LEGEND
C-002 SHEET SPECS
C-100 SITE & GRADING PLAN
C-101 UTILITY PLAN
C-102 ADA SCHEMATIC
C-501 DETAILS
3-STRUCTURAL
S-001 STRUCTURAL NOTES
S-101 STRUCTURAL PLANS, DETAILS, & SCHEDULES
S-701 TYPICAL STRUCTURAL DETAILS
4-ARCHITECTURAL
A-001 ACCESSIBILITY REQUIREMENTS
A-002 ACCESSIBILITY REQUIREMENTS
A-003 ACCESSIBILITY REQUIREMENTS
A-101 FLOOR PLAN
A-111 ROOF PLAN
A-120 REFLECTED CEILING PLAN
A-201 EXTERIOR ELEVATIONS
A-202 EXTERIOR ELEVATIONS
A-301 BUILDING SECTIONS
A-601 ARCHITECTURAL SCHEDULES
A-602 ROOM FINISH SCHEDULE & INTERIOR ELEVATIONS
5-MECHANICAL
M-001 MECHANICAL TITLE SHEET
M-101 LEVEL 1 MECHANICAL PLAN
M-102 ROOF RIDGE MECHANICAL PLAN
M-501 MECHANICAL DIAGRAMS
M-601 MECHANICAL SCHEDULES
M-701 MECHANICAL SPECIFICATIONS
6-PLUMBING
P-001 PLUMBING TITLE SHEET
P-101 LEVEL 1 PLUMBING PLAN
P-501 PLUMBING DIAGRAMS
P-601 PLUMBING SCHEDULES
P-701 PLUMBING SPECIFICATIONS
7-ELECTRICAL
E-001 ELECTRICAL TITLE SHEET
E-002 LEVEL 1 ELECTRICAL SITE PLAN
E-101 LEVEL 1 ELECTRICAL PLAN
E-501 ELECTRICAL DIAGRAMS
E-601 ELECTRICAL SCHEDULES
E-602 ELECTRICAL SCHEDULES
E-701 ELECTRICAL SPECIFICATIONS
WATER CLOSETS
MEN: XXX OCC. (1/150) = X
WOMEN: XXX OCC. (1/75) = X
LAVATORIES
MEN'S LAVATORIES
WOMEN'S LAVATORIES
DRINKING FOUNTAINS
1/1000, 2 REQUIRED
SERVICE SINK
SERVICE SINKS
PROVIDED
MEN: XX WATER CLOSETS, XX URINALS
WOMEN: XX WATER CLOSETS
MEN'S LAVATORIES - PROVIDED
WOMEN'S LAVATORIES - PROVIDED DRINKING FOUNTAINS -
PROVIDED SERVICE SINKS - PROVIDED
UNISEX: XX WATER CLOSETS UNISEX LAVATORIES - PROVIDED
THE 2021 EDITION OF THE IBC, IECC, IPC, IMC AND THE 2023 EDITION OF THE NEC ANSI A117
REQUIRED
PROJECT LOCATION
ES-101
M-102 ROOF RIDGE MECHANICAL PLAN
M-501 MECHANICAL DIAGRAMS
M-601 MECHANICAL SCHEDULES
M-701 MECHANICAL SPECIFICATIONS
6-PLUMBING
P-001 PLUMBING TITLE SHEET
P-101 LEVEL 1 PLUMBING PLAN
P-501 PLUMBING DIAGRAMS
P-601 PLUMBING SCHEDULES
P-701 PLUMBING SPECIFICATIONS
7-ELECTRICAL
E-001 ELECTRICAL TITLE SHEET
E-002 LEVEL 1 ELECTRICAL SITE PLAN
E-101 LEVEL 1 ELECTRICAL PLAN
E-501 ELECTRICAL DIAGRAMS
E-601 ELECTRICAL SCHEDULES
E-602 ELECTRICAL SCHEDULES
E-701 ELECTRICAL SPECIFICATIONS
ES-101
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
B
C
D
E
F
G
H
J
K
L
M
SUBMITTAL
JDE No.
STAMP
NO. DATE DESCRIPTION
REVISIONS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FOR BIDDING
Blue Stakes of
Bluestakes.org 1-800-662-4111
CALL BEFORE YOU DIG.
IT'S FREE AND IT'S THE LAW.
TITLE AND LEGEND
C-001
DUCHESNE
FAIRGROUNDS
RESTROOM
DUCHESNE
COUNTY
2508-062
Pr in t D at e:
3/
/2
9:
P M
F ile
P at h:
H :\2
8-
2\ dw g\
D
ES
IG
N
8-
2.
dw g
GENERAL NOTES
1. INFORMATION SHOWN FOR EXISTING UTILITIES IS BASED ON BEST AVAILABLE INFORMATION AND IS ACCORDING TO RECORDS SUPPLIED TO ENGINEER, HOWEVER ACCURACY
OF THIS INFORMATION CANNOT BE GUARANTEED. CONTRACTOR SHALL ACCEPT SITE AS IS, AND SHALL ASSUME ALL LIABILITY FOR FINAL LOCATION AND PRESERVATION OF ALL
UTILITIES.
2. WHEN AN EXISTING WATER LINE IS TO BE ABANDONED, COMPLETELY DISCONNECT FROM ANY PIPING THAT REMAINS PART OF THE WATER SYSTEM. VALVE BOXES ON ABANDONED WATER LINES SHALL BE FULLY REMOVED. WHERE WATERLINES ARE TO BE ABANDONED, CAP AND INSTALL THRUST BLOCK AT MAINLINE, VERIFY PROCEDURES
WITH OPERATOR.
3. WHEN NEW VALVES ARE INSTALLED ON WATER MAIN LINES, VALVES ARE TO BE LOCATED IMMEDIATELY ADJACENT TO CONNECTING FITTINGS.
4. CONTRACTOR IS REQUIRED TO OBTAIN ALL CONSTRUCTION AND ENCROACHMENT PERMITS NECESSARY FOR THE WORK. CONTRACTOR SHALL OBTAIN DUCHESNE COUNTY
APPROVED PERMISSION FOR TAPPING OF EXISTING WATER AND SEWER MAINS.
5. WHERE WATER LINE CROSSES OVER THE TOP OF A SEWER LINE A VERTICAL SEPARATION OF 18" SHALL BE MAINTAINED AND NO JOINTS IN PIPE ARE ALLOWED ON WATER LINES
WITHIN 10 FEET EACH SIDE OF CROSSING.
6. WHERE CULINARY WATERLINE PARALLELS SEWER LINE, A HORIZONTAL SEPARATION OF AT LEAST 10 FEET MUST BE MAINTAINED.
7. 24 HR. WRITTEN NOTICE MUST BE PROVIDED TO ALL HOME OWNERS AND BUSINESSES BEFORE ANY WATER SHUT OFFS. CONTRACTOR TO COORDINATE WITH DUCHESNE COUNTY REGARDING WATER SHUTOFF WITH AT LEAST THREE (3) DAYS ADVANCE NOTICE TO ISOLATE LINES...
8. ALL IMPROVEMENTS AND MATERIALS SHALL BE IN ACCORDANCE WITH RICHFIELD CITY CONSTRUCTION STANDARDS AND SPECIFICATIONS.
9. COORDINATE SITE IMPROVEMENTS WITH ARCHITECTURAL DRAWINGS.
10.FOLLOW RECOMMENDATIONS OF GEOTECHNICAL EVALUATION REPORT.
11.COMPACT GRANULAR BORROW AND UNTREATED BASE COURSE TO AT LEAST 95 PERCENT OF MAXIMUM DRY DENSITY DETERMINED BY ASTM D1557. MAINTAIN MOISTURE
CONTENT WITHIN 2 PERCENT OF OPTIMUM UNLESS OTHERWISE NOTED.
12.GRANULAR BORROW SHALL BE AASHTO M145 A-1-A OR A-1-B MATERIAL WITH 4 INCH MAXIMUM GRADATION.
13.UNTREATED BASE COURSE SHALL BE CRUSHED ROCK WITH 1 INCH MAXIMUM GRADATION AND MEET UTAH DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATION.
14.USE CONCRETE WITH 3.5 INCH MAXIMUM SLUMP, 5 TO 7 PERCENT AIR CONTENT, AND 4,000 PSI MINIMUM COMPRESSIVE STRENGTH.
CONCRETE SLAB-ON-GRADE JOINTS
1. PROVIDE CONTROL JOINTS IN ALL REINFORCED AND UNREINFORCED SLABS-ON-GRADE ACCORDING TO TYPICAL CONCRETE JOINTS DETAIL.
2. CONTROL JOINTS MAY BE TOOLED INTO FRESH CONCRETE OR SAWED INTO HARDENED CONCRETE PER CONTRACTOR'S PREFERENCE.
3. SAW-CUTTING SHALL TAKE PLACE AS SOON AS POSSIBLE AFTER PLACEMENT, BEFORE SHRINKAGE CRACKS CAN DEVELOP.
4. PLACE CONTROL JOINTS TO PRODUCE PANELS THAT ARE AS SQUARE AS POSSIBLE AND NEVER EXCEEDING A LENGTH-TO-WIDTH RATIO OF 1.5 TO 1.
5. PLACE CONTROL JOINTS AT ALL ABRUPT CHANGES IN GEOMETRY.
6. AVOID WEDGE-SHAPED PANELS WITH INTERIOR ANGLES LESS THAN 45 DEGREES.
7. AVOID "T" SHAPED JOINTS.
8. CONTROL JOINTS SHALL BE ESTABLISHED TO A DEPTH OF ¼ THE SLAB THICKNESS.
9. MAXIMUM CONTROL JOINT SPACING SHALL CONFORM TO TABLE “MAXIMUM CONTROL JOINT SPACING”.
10. WHERE TWO REINFORCED SLABS ABUT, OR WHERE ONE REINFORCED SLAB IS DIVIDED INTO MULTIPLE POURS, PROVIDE PLATE DOWELS AT COLD JOINT PER TYPICAL
CONCRETE JOINTS DETAIL.
11. IF CONTROL JOINT LAYOUT VIOLATES THESE REQUIREMENTS, EVEN IF NO CRACKING IS VISIBLE, OWNER MAY REJECT WORK.
12. PROVIDE EXPANSION JOINTS BETWEEN REINFORCED SLABS AND UNREINFORCED SLABS (E.G. BETWEEN REINFORCED DRIVEWAY AND UNREINFORCED SIDEWALK).
13. PROVIDE EXPANSION JOINTS EVERY 25' IN UNREINFORCED SLABS (E.G. SIDEWALKS).
14. PROVIDE EXPANSION JOINTS AT BUILDING CORNERS IN BOTH DIRECTIONS IN SIDEWALKS TOUCHING BUILDING.
MAXIMUM CONTROL JOINT SPACING
SLAB THICKNESS, IN.
MAXIMUM JOINT SPACING, FT.
UNREINFORCED REINFORCED
EROSION & SEDIMENT CONTROL NOTES:
1. PROVIDE ADEQUATE WATER SUPPLY FOR DUST CONTROL AT ALL TIMES.
2. INSTALL EROSION AND SEDIMENT CONTROL MEASURES PRIOR TO STARTING ANY EARTH DISTURBING ACTIVITIES. RELOCATE SEDIMENT CONTROL MEASURES AS REQUIRED
DURING CONSTRUCTION.
3. INSPECT AND MAINTAIN EROSION AND SEDIMENT CONTROL MEASURES AT LEAST WEEKLY AND FOLLOWING ANY STORM EVENT.
4. REMOVE ACCUMULATED SEDIMENT AS NECESSARY FOR EROSION AND SEDIMENT CONTROL MEASURES TO CONTINUE TO FUNCTION PROPERLY
5. REPAIR AND CORRECT ANY BMP PROBLEM AREAS OR MEASURES WHICH ARE NOT FUNCTIONING.
6. USE ONLY ONE CONSTRUCTION ENTRANCE TO SITE. DAILY REMOVED SOIL TRACKED ONTO EXISTING PAVEMENTS.
7. KEEP EROSION AND SEDIMENT CONTROL MEASURES IN PLACE UNTIL AT LEAST 75 PERCENT OF SITE HAS BEEN FULLY DEVELOPED.
SITE UTILITY NOTES:
1. LOCATE & PROTECT EXISTING UTILITIES WHICH ARE TO REMAIN. AT CONNECTION POINTS AND UTILITY CROSSINGS, FIELD VERIFY LOCATION OF EXISTING UTILITIES.
2. COORDINATE UTILITIES WITH UTILITY COMPANIES. COORDINATE LOCATION OF UTILITY SERVICES WITH BUILDING DRAWINGS.
3. SEE SHEET C101 FOR LOCATION OF UTILITY LINES.
4. SEE SHEET C501 FOR UTILITY DETAILS.
5. CONSTRUCT CULINARY WATER AND SANITARY SEWER UTILITIES IN ACCORDANCE WITH DUCHESNE COUNTY CONSTRUCTION STANDARDS.
6. COMPACT PIPE BEDDING AND BACKFILL TO AT LEAST 95 PERCENT OF MAXIMUM DRY DENSITY (90 PERCENT FOR BACKFILL IN LANDSCAPE AREAS) DETERMINED BY ASTM D1557. MAINTAIN MOISTURE CONTENT OF BEDDING AND BACKFILL WITHIN 2 PERCENT OF OPTIMUM.
VICINITY MAP
UTILITY INFORMATION
UTILITY OWNER CONTACT
WATER
SEWER
POWER
TELEPHONE / DATA
NATURAL GAS
CABLE TELEVISION
SAN JUAN
KANEWASHINGTON
IRON GARFIELD
WAYNEPIUTEBEAVER
MILLARD
SEVIER
EMERY GRAND
SANPETE
CARBON
JUAB
UTAH
WASATCH
DUCHESNE
UINTAH
DAGGETTSUMMIT
SALT LAKE
TOOELE
DAVIS
MORGAN
WEBER
RICH
CACHE
BOX ELDER
IDAHO
WYOMING
C O
LO
R
AD
O
N
EV
AD
A
ARIZONA
DUCHESNE
N O
R T
H
N O
R T
H
DUCHESNE FAIRGROUNDS RESTROOM
EDGE OF ASPHALT
EDGE OF CONCRETE
EDGE OF GRAVEL SURFACING
EDGE OF DIRT SURFACING
EDGE OF ASPHALT SURFACING
CONCRETE SURFACING
ASPHALT SURFACING
STREET SIGN
SANITARY SEWER LINE
CULINARY WATER LINE
BURIED POWER LINE
FLOW LINE OF DITCH
BURIED TELEPHONE LINE
NATURAL GAS LINE
BURIED CABLE TV LINE
TREE
CONCRETE SURFACING
DELINEATOR POST
PROPERTY LINE
IRRIGATION LINE
EXISTING RIGHT OF WAY LINE
CULINARY WATER LINE
SANITARY SEWER LINE
SECTION LINE
PROPOSED RIGHT-OF-WAY LINE
SUBDIVISION BOUNDARY LINE
LOT LINES
QUARTER SECTION LINE
(P.U.E.) PUBLIC UTILITY EASEMENT
DEED LINE
FIRE HYDRANT
STRUCTURE
TOP OF CUT LIMITS
TOE OF FILL LIMITS
WATER METER
POWER POLE & GUY WIRE
STORM DRAIN / DRAINAGE CULVERT
SANITARY SEWER SERVICE
EXISTING FEATURES
PROPOSED FEATURES
MISC. FEATURES
(SIDEWALK, CURB, GUTTER, ETC.)
FENCE LINE (CHAIN LINK)
TELEPHONE PEDESTAL
OVERHEAD CABLE TV LINE
OVERHEAD POWER LINE
OVERHEAD TELEPHONE LINE
BURIED POWER LINE
OVERHEAD POWER LINE
BURIED TELEPHONE LINE
OVERHEAD TELEPHONE LINE
BURIED CABLE TV LINE
OVERHEAD CABLE TV LINE
NATURAL GAS LINE
IRRIGATION LINE
FENCE LINE (CHAIN LINK)
FIBER OPTIC LINE
FIBER OPTIC LINE
MAILBOX
EXISTING CITY BLOCK LINES
BLOCK LINE
EXISTING N/A LINE
WATER MANHOLE
LIGHT POLE
GAS METER
CABLE TV PEDESTAL
SANITARY SEWER CLEAN OUT
IRRIGATION MANHOLE
IRRIGATION METER
STORM DRAIN MANHOLE
FENCE LINE
(BARBED OR STOCKTIGHT)
FENCE LINE
(BARBED OR STOCKTIGHT)
TOP BACK OF CURB
LIP OF CURB
TOP OF SIDEWALK
TOP OF CONCRETE
TOP OF GRATE
EDGE OF ASPHALT
FLOW LINE OF GUTTER
FLOW LINE OF CULVERT
SIDEWALK
TOP OF ASPHALT
TBC
LOC
TSW
TOC
TOG
EOA
FLG
FLC
SW
TOA
ABBREVIATIONS & HATCHING
RIGHT-OF-WAY
LEFT
RIGHT
R/W
L / LT
R / RT
TEMPORARY T.C.E.
PUBLIC UTILITY EASEMENTP.U.E.
CONSTRUCTION EASEMENT
STATIONSTA
EXISTING GROUNDEG
FINISHED GRADEFG
CAST-IN-PLACECIP
STORM DRAIN / DRAINAGE CULVERT
CULINARY WATER VALVE
GAS VALVE
IRRIGATION VALVE
SANITARY SEWER MANHOLE
STREET SIGN
DELINEATOR POST
FIRE HYDRANT
WATER METER
POWER POLE & GUY WIRE
MAILBOX
WATER MANHOLE
LIGHT POLE
GAS METER
SANITARY SEWER CLEAN OUT
IRRIGATION MANHOLE
IRRIGATION METER
STORM DRAIN MANHOLE
CULINARY WATER VALVE
GAS VALVE
IRRIGATION VALVE
SANITARY SEWER MANHOLE
EPPG.W.
T
SCO
EPP
SCO
wmh sdm imh smh
SCO
SMH
SDM
WMH
IMH
GV
IV
GV
IV
OR
OR
W G I w g i
LIMITS OF DISTURBANCELOD
COMMUNICATION MANHOLECMM
COMMUNICATION MANHOLEcmm
STRUCTURE
INDEX TO SHEETS
Sheet Number Sheet Title
C-001 TITLE AND LEGEND
C-002 SHEET SPECS
C-100 SITE & GRADING PLAN
C-101 UTILITY PLAN
C-102 ADA SCHEMATIC
C-501 DETAILS
03/26/2026
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
B
C
D
E
F
G
H
J
K
L
M
SUBMITTAL
JDE No.
STAMP
NO. DATE DESCRIPTION
REVISIONS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FOR BIDDING
Blue Stakes of
Bluestakes.org 1-800-662-4111
CALL BEFORE YOU DIG.
IT'S FREE AND IT'S THE LAW.
SHEET SPECS
C-002
DUCHESNE
FAIRGROUNDS
RESTROOM
DUCHESNE
COUNTY
2508-062
Pr in t D at e:
3/
/2
9:
P at h:
H :\2
8-
2\ dw g\
D
ES
IG
N
8-
2.
dw g
SHEET SPECS.
GENERAL REQUIREMENTS
A.SUBMITTALS
1. PROVIDE MATERIAL AND PRODUCT SUBMITTALS FOR EACH TYPE OF MATERIAL
AND PRODUCT USED ON PROJECT.
B.TESTING
1. PROVIDE TESTING INDICATED IN SPECIFICATIONS
CONCRETE SIDEWALK
C.MATERIALS:
1. BASE: UNTREATED BASE COURSE IN ACCORDANCE WITH EARTHWORK
SPECIFICATIONS.
2.REINFORCING STEEL:
a. COMPLY WITH ASTM A615.
b. YIELD STRENGTH: 60-KIPS PER SQUARE INCH.
c. BILLET BARS: DEFORMED.
d.FINISH: UNCOATED.
3. CONCRETE: CLASS A, USE TYPE II MODERATE SULFATE RESISTANT.
A.SEALANT: USE ONE OF FOLLOWING.
1. COLD-POUR SINGLE COMPONENT SILICONE FOR USE WITH PORTLAND CEMENT
CONCRETE PAVEMENT.
2. ONE-COMPONENT, POLYURETHANE-BASED, ELASTOMERIC SEALANT SUCH AS
SIKAFLEX-1A.
3. OR EQUAL.
B.DETECTABLE WARNING SURFACE:
1. USE IN-LINE TRUNCATED DOME PATTERN THAT MEETS REQUIREMENTS OF
UDOT PA SERIES STANDARD DRAWINGS.
2.PROVIDE COLOR THAT CONTRASTS VISUALLY WITH ADJOINING SURFACES,
EITHER LIGHT-ON-DARK OR DARK-ON-LIGHT.
3. MINIMIZE NUMBER OF PANELS USED. ACCEPTABLE MODULAR PANEL SIZES
ARE:
a. 2-FEET BY 2-FEET.
b. 2-FEET BY 3-FEET.
c. 2-FEET BY 4-FEET.
d. 2-FEET BY 5-FEET
C.INSTALL DETECTABLE WARNING SURFACE ACCORDING TO MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
1. POLYMER COMPOSITE PANEL:
a. INSTALL CAST-IN-PLACE PANEL DIRECTLY INTO FINISHED CONCRETE
SURFACE. PROVIDE SMOOTH TRANSITION BETWEEN PANEL AND
SURROUNDING CONCRETE.
b. INSTALL SURFACE-APPLIED PANEL DIRECTLY ON EXISTING CONCRETE
SURFACE. USE MECHANICAL FASTENERS TO SECURE PANEL TO EXISTING
SURFACE. CAULK SMOOTH TRANSITION BEAD ALONG BEVELED PANEL EDGE
AND SURROUNDING CONCRETE SURFACE.
D.COMPACT SUBGRADE AND BACKFILL IN ACCORDANCE WITH EARTHWORK
SPECIFICATIONS.
1. ENSURE CONCRETE HAS CURED SUFFICIENTLY BEFORE PLACING BACKFILL TO
PREVENT DAMAGE.
EARTHWORK
A.MATERIALS:
1. IMPORTED FILL: A-1a THORUGH A-4 SOILS AS CLASSIFIED IN ACCORDANCE
WITH AASHTO M145.
2. TOPSOIL: USE TOP 6 INCHES OF EXISTING ONSITE SOIL.
3. GRANULAR BACKFILL BORROW: NON-PLASTIC, WELL GRADED, 2 INCH MAXIMUM
SIZE, A-1A SOIL AS CLASSIFIED IN ACCORDANCE WITH AASHTO M145.
a. PLACE AND COMPACT GRANULAR BACKFILL BORROW IN CONTINUOUS
LAYERS NOT EXCEEDING 6 INCHES COMPACTED DEPTH.
4.USE SUITABLE EXCAVATED SOIL FOR FILL DO NOT USE FROZEN MATERIALS,
ORGANIC MATERIALS, RUBBISH, DEBRIS, OR OTHER OBJECTIONABLE
MATERIALS.
5. DO NOT PLACE FILL OVER POROUS, WET, FROZEN, OR SPONGY SURFACES.
6. BASE COURSE MATERIAL: CRUSHED AGGREGATE FROM OWNER FURNISHED
PIT MEETING REQUIREMENTS AS FOLLOWS.
a. LIQUID LIMIT / PLASTIC INDEX: AASHTO T90, NON-PLASTIC.
b. FRACTURED FACES: AASHTO T335, MINIMUM 50 PERCENT WITH TWO.
c. GRADATION: AASHTO T27 AND T11.
B.TOLERANCES:
1. MOISTURE CONTENT: PLUS OR MINUS 2 PERCENT OF OPTIMUM. TEST IN
ACCORDANCE WITH ASTM D6938.
2.FINISH SUBGRADE SURFACE: PLUS OR MINUS .04 FEET OF REQUIRED
ELEVATION.
3. FINISH GRADE OF FILL SURFACE: PLUS OR MINUS .1 FEET OF REQUIRED
ELEVATION.
4.ENGINEER WILL TAKE RANDOM DENSITY TESTS. IF TESTS INDICATE WORK IS
NOT ACCEPTABLE, RE-COMPACT AND RETEST. IF NECESSARY, REMOVE AND
REPLACE WORK.
C.COMPACTION SCHEDULE:
1. FILL FOR NON-TRAVELED AREAS: COMPACT TO MINIMUM OF 90 PERCENT OF
MAXIMUM LABORATORY DENSITY. INCLUDES LANDSCAPE AREAS.
2.FILL FOR TRAVELED AREAS AND STRUCTURES: COMPACT TO MINIMUM 96
PERCENT MAXIMUM LABORATORY DENSITY. INCLUDES ROADS, PARKING LOTS,
CONCRETE FLATWORK, DRIVEWAYS AND STRUCTURES.
3. SUBGRADE: COMPACT TO MINIMUM 96 PERCENT OF MAXIMUM LABORATORY
DENSITY.
SITE WATER UTILITY SYSTEM
A.PIPE
1. POLYVINYL CHLORIDE (PVC) PIPE: 4-INCH DIAMETER AND LARGER.
a. CLASS: AWWA C900, DUCTILE IRON PIPE SIZE AND PRESSURE CLASS 165 (DR 25).
b. JOINTS: BELL AND SPIGOT WITH ELASTOMERIC GASKETS IN ACCORDANCE
WITH ASTM F477.
c. COLOR: BLUE.
d. CERTIFICATION: BE NSF 61 APPROVED AND BEAR NSF LABEL.
e.FITTINGS: AWWA C153, CLASS 350, DUCTILE IRON, COMPACT FITTINGS WITH
MECHANICAL JOINTS AND GASKETS.
B.SERVICE LINE: HIGH DENSITY POLYETHYLENE PIPE, IN ACCORDANCE WITH
AWWA C901.
a. IRON PIPE SIZE: 0.75- AND 1-INCH SERVICES.
b. COPPER TUBE SIZE: 1.5- AND 2-INCH SERVICES.
c. WORKING PRESSURE: 200 POUNDS PER SQUARE INCH.
d. CERTIFICATION: NSF 61 APPROVED AND BEAR NSF LABEL.
e. COLOR: BLUE.
C.SERVICES
1. TAP SADDLE: NYLON COATED SADDLE WITH STAINLESS STEEL STRAP.
MANUFACTURED BY ROMAC INDUSTRIES, INC. OR EQUAL.
a. PROVIDE FULL SUPPORT AROUND CIRCUMFERENCE OF PIPE.
b. PROVIDE MINIMUM 2-INCH-WIDE BEARING AROUND PIPE.
c. NOT HAVE LUGS WHICH WILL DIG INTO PIPE.
d. NOT HAVE U-BOLT TYPE STRAP.
2. CORPORATION STOP: BRONZE BODY, IN ACCORDANCE WITH AWWA C800.
PROVIDE STANDARD IRON PIPE THREADS AND COMPRESSION FITTINGS FOR
POLYETHYLENE PIPE WITH STAINLESS STEEL INSERT STIFFENERS. FORD
BALLCORP AS MANUFACTURED BY THE FORD METER BOX COMPANY, INC. OR
EQUAL.
3. SERVICE LINE: HIGH DENSITY POLYETHYLENE PIPE, IN ACCORDANCE WITH
NSF-14 AND AWWA C901.
a. IRON PIPE SIZE: ASTM D2239, ¾ AND 1 INCH SERVICES.
b. COPPER TUBE SIZE: ASTM D2737, 1.5 AND 2 INCH SERVICES.
c. WORKING PRESSURE: 200 POUNDS PER SQUARE INCH.
d. COLOR: BLUE.
4.FITTINGS: BRONZE, MUELLER 110 COMPRESSION FITTINGS.
5. COPPERSETTER: 18 INCH HEIGHT WITH BALL VALVE INLET AND DUAL CHECK
VALVE OUTLET. MANUFACTURED BY THE FORD METER BOX COMPANY, INC. OR
EQUAL.
a. 3/4 INCH: MODEL VBHC73-18W.
b.1 INCH: MODEL VBHC74-18W.
6. METER BARREL: 18 INCH DIAMETER BY 36 INCH HIGH, WHITE, HIGH DENSITY
POLYETHYLENE WITH CORRUGATED EXTERIOR AND SMOOTH INTERIOR.
PROVIDE LARGER SIZES WHERE INDICATED ON DRAWINGS.
7. METER BARREL RING AND LID: CAST IRON WITH WATER METER OR WATER
CAST ON LID.
8. METER: AWWA C700, DISPLACEMENT TYPE MAGNETIC DRIVE COLD WATER
METER WITH BRONZE MAIN CASE.
D.ACCESSORIES
1. THRUST RESTRAINT DEVICES: USE ONE OF FOLLOWING:
a. CONCRETE THRUST BLOCKS: CLASS B OR B(AE) CONCRETE IN ACCORDANCE
WITH ASTM C94, MINIMUM 2,500 POUNDS PER SQUARE INCH 28 DAY
COMPRESSIVE STRENGTH, MAXIMUM 5 INCH SLUMP AND 3 TO 6 PERCENT AIR
CONTENT.
b. RESTRAINED JOINTS:
1. PIPE: BELL AND SPIGOT JOINT RESTRAINT HARNESS OR CLAMP. RATED AT
PRESSURE CLASS OF PIPE OR GREATER.
2.PIPE FITTINGS: MECHANICAL JOINT WITH RESTRAINED FOLLOWER GLAND.
RATED AT PRESSURE CLASS OF PIPE OR GREATER. MEGALUG, OR EQUAL.
2. TRACER WIRE: 14/1 UF DIRECT BURIAL WIRE.
a. SPLICES: 3M COMPANY, CAT. NO. MH14 BCX HEAT SHRINK BUTT SPLICE OR
EQUAL.
b. COLOR: BLUE.
E.INSTALLATION
1. INSTALL PIPE AND FITTINGS. SEAL JOINTS WATERTIGHT. ROUTE PIPE IN
STRAIGHT LINE.
2.PLACE BEDDING MATERIAL AT SIDES OF PIPE AND OVER PIPE IN LAYERS NOT
EXCEEDING 6 INCHES COMPACTED DEPTH. PLACE BEDDING TO MINIMUM
COMPACTED THICKNESS OF 12 INCHES ABOVE TOP OF PIPE.
3. IF EXCAVATED MATERIAL IS UNSUITABLE FOR BEDDING OR TRENCH BOTTOM IS
UNSUITABLE TO SUPPORT PIPE, IMPORT GRANULAR BEDDING.
4. COMPACT BEDDING TO 96 PERCENT OF MAXIMUM LABORATORY DENSITY.
MAINTAIN MOISTURE CONTENT OF BEDDING MATERIAL WITHIN PLUS OR MINUS
2 PERCENT OF OPTIMUM TO ATTAIN REQUIRED COMPACTION DENSITY.
5. INSTALL TRACER WIRE CONTINUOUS BELOW SPRING LINE OF PIPE. INSTALL
TRACER WIRE WITH NEW TRANSMISSION, OUTLET AND MAIN LINES. CONNECT
TRACER WIRE TO PIPE MARKERS AT 1,000 FEET MAXIMUM INTERVALS. WHERE
THERE IS EXISTING TRACER WIRE, CONNECT NEW TRACER WIRE TO EXISTING
TRACER WIRE. IF SPLICES ARE REQUIRED, MAKE WATERTIGHT CONNECTION.
6. PLACE RESTRAINING DEVICES ACCORDING TO MANUFACTURERS'
RECOMMENDATIONS OR CONCRETE THRUST BLOCKS AT ANY CHANGE OF PIPE
DIRECTION AND FITTINGS. USE MECHANICAL JOINT RESTRAINT DEVICES ON
FITTINGS FOR LIVE TIE-INS WHEN THERE IS NOT ADEQUATE TIME FOR
CONCRETE THRUST BLOCKS TO CURE.
7. BACKFILL TRENCH IN ACCORDANCE WITH EARTHWORK SECTION.
8. SET VALVES ON SOLID BEARING. CENTER AND PLUMB VALVE BOX OVER VALVE.
SET BOX COVER FLUSH WITH FINISHED GRADE.
9. SET HYDRANTS ON SOLID BEARING AND PLUMB. LOCATE PUMPER NOZZLE
PERPENDICULAR TO AND FACING ROADWAY. INSTALL VALVE NEXT TO FIRE
HYDRANT AND PLACE VALVE BOX TO GRADE. PROVIDE DRAINAGE ROCK
AROUND FIRE HYDRANT.
10. RELOCATE EXISTING FIRE HYDRANTS AS INDICATED ON DRAWINGS.
CONNECT EXISTING FIRE HYDRANTS, WHICH ARE TO REMAIN, TO NEW MAIN
LINES. IF EXISTING PIPE TO EXISTING FIRE HYDRANT IS SMALLER THAN 6 INCH
DIAMETER, REPLACE PIPE AND CONNECTION TO MAIN LINE.
11. INSTALL NEW SERVICE LINES AND FITTINGS AS NEEDED TO CONNECT
EXISTING SERVICES TO NEW WATER LINES.
12. IF EXISTING SERVICE LINE IS IN POOR CONDITION AS DETERMINED BY
ENGINEER, INSTALL NEW SERVICE LINE TO EXISTING METER SETTER, YOKE OR
EQUIVALENT. INSTALL FITTINGS AS NEEDED TO MAKE CONNECTIONS.
REPLACE ALL GALVANIZED STEEL SERVICE LINES.
13. IF SERVICE LINE IS REPLACED, INSTALL TRACER WIRE WITH NEW SERVICE
LINE.
14. WHERE INDICATED ON DRAWINGS, INSTALL NEW SERVICE METER.
15. IF EXISTING METER BARREL IS IN POOR CONDITION AS DETERMINED BY
ENGINEER, REPLACE METER BARREL. RE-USE EXISTING RING AND LID.
F. WATER PIPING PRESSURE TEST
1. PRESSURE TEST NEW PIPING AS FOLLOWS:
a. TEST WATER PIPING AT PRESSURE RATING OF PIPE.
b. FILL PIPE WITH WATER AND PLACE UNDER SLIGHT PRESSURE FOR AT LEAST
48 HOURS.
c. BRING PIPE PRESSURE TO TEST PRESSURE AND MAINTAIN FOR 4 HOURS
MINIMUM.
d. PROVIDE ACCURATE MEANS FOR MEASURING QUANTITY OF WATER NEEDED
TO MAINTAIN TEST PRESSURE ON PIPE FOR TEST PERIOD.
e. IF VOLUME OF WATER ADDED TO PIPE IS 10 GALLONS PER INCH OF PIPE
DIAMETER PER MILE OF PIPE PER 24 HOURS OR LESS, PIPE PASSES TEST.
f. IF PIPE DOES NOT PASS TEST, FIND SOURCE OF LEAKAGE, REPAIR OR
REPLACE, AND RETEST. CORRECT ANY VISIBLE LEAKAGE. REPEAT UNTIL
PIPE PASSES TEST.
G.WATER PIPING DISINFECTION
1. AFTER COMPLETING PRESSURE TEST, FLUSH PIPE TO REMOVE DIRT OR OTHER
FOREIGN OBJECTS.
2. ADD LIQUID CHLORINE OR LIQUID CALCIUM HYPOCHLORITE TO PIPE TO OBTAIN
50 PPM CONCENTRATION OF CHLORINE. MAINTAIN 25 PPM CHLORINE RESIDUAL
AT END OF 24 HOURS. DISINFECT PIPING IN ACCORDANCE WITH UTAH STATE
RULES FOR PUBLIC DRINKING WATER SYSTEMS AND AWWA C651.
3. FLUSH CHLORINATED WATER FROM PIPE. DISPOSED OF CHLORINATED WATER
IN ACCORDANCE WITH UTAH WATER QUALITY BOARD RULES. SEE R317 OF
UTAH ADMINISTRATIVE CODE.
4. AFTER FLUSHING CHLORINATED WATER, SAMPLE AND COMPLETE
BACTERIOLOGICAL TESTING.
a.FREQUENCY: FOR EVERY 1,200 FEET OF NEW MAIN PIPING, TAKE TWO
CONSECUTIVE SAMPLES 24 HOURS APART. USE STERILE SAMPLE BOTTLES
FURNISHED BY TESTING LABORATORY.
b. ACCEPTANCE: ABSENCE OF COLIFORM BACTERIA IN TWO CONSECUTIVE
SAMPLES TAKEN 24 HOURS APART.
c. IF NECESSARY RE-CHLORINATE UNTIL SATISFACTORY BACTERIOLOGICAL
TESTS ARE OBTAINED.
d. DO NOT PUT PIPING INTO SERVICE UNTIL TEST RESULTS ARE SATISFACTORY.
5. IF SERVICE LINES ARE NOT DISINFECTED WITH MAIN LINE, FLUSH SERVICE
LINES WITH CHLORINATED WATER PRIOR TO CONNECTING AND PUTTING INTO
USE.
H.PROTECTION
1. PROTECT PIPE AND ACCESSORIES FROM DAMAGE OR DISPLACEMENT.
2.PREVENT MUD, SILT, GRAVEL, AND OTHER FOREIGN MATERIALS FROM
ENTERING PIPE AND KEEP OFF JOINT SURFACES.
3. INSTALL PLUG IN PIPE END WHEN PIPE LAYING IS NOT IN PROGRESS.
SANITARY SEWERAGE GRAVITY PIPING
A.REGULATORY REQUIREMENTS
1. CONFORM TO REQUIREMENTS OF UTAH DEPARTMENT OF ENVIRONMENTAL
QUALITY.
2. INSTALL SEWER PIPES WITH MINIMUM OF 10 FEET HORIZONTAL OR 18 INCHES
VERTICAL SEPARATION FROM WATER PIPES. MEASURE DISTANCE FROM
OUTSIDE EDGE OF PIPE TO OUTSIDE EDGE OF PIPE. INSTALL SEWER PIPES
BELOW WATER PIPES.
B.SEWER PIPE MATERIALS
1. MAIN COLLECTION LINES AND SERVICE LINES: POLYVINYL CHLORIDE (PVC)
GRAVITY SEWER PIPE:
a. ASTM D3034 FOR DIAMETERS FROM 4 INCHES TO 15 INCHES.
b. PVC MATERIAL CONFORMING TO ASTM D1784.
c. MINIMUM PIPE STIFFNESS OF 46 PSI ACCORDING TO ASTM D2412.
d. SDR OF 35.
2.PIPE JOINTS: BELL AND SPIGOT STYLE WITH ELASTOMERIC GASKETS
CONFORMING TO ASTM F477.
3. FITTINGS: SAME MATERIAL AS PIPE MOLDED OR FORMED TO SUITE PIPE SIZE
AND END DESIGN, IN REQUIRED TEE, BENDS, ELBOWS, CLEANOUTS,
REDUCERS, TRAPS AND OTHER CONFIGURATIONS REQUIRED.
4. CLEANOUT RING AND LID: CAST IRON, TRAFFIC RATED.
5. WARNING TAPE: PLASTIC, BRIGHT GREEN COLOR, CONTINUOUSLY PRINTED
WITH “SANITARY SEWER PIPE BELOW”, MINIMUM 6 INCHES WIDE BY 4 MIL THICK,
MANUFACTURED FOR DIRECT BURIAL.
C.BEDDING:
1. EXCAVATED MATERIALS CONSISTING OF EARTH, LOAM, SANDY CLAY, SAND,
AND GRAVEL WHICH ARE FREE FROM CLODS OF EARTH, ROCKS LARGER THAN
¾-INCH, FROZEN MATERIAL, ORGANIC MATERIAL AND DEBRIS.
2. IF EXCAVATED MATERIAL IS UNSUITABLE FOR BEDDING, IMPORT BEDDING
CONSISTING OF PITRUN GRAVEL, SAND, OR OTHER SUITABLE MATERIAL WITH
¾-INCH MAXIMUM SIZE GRADATION.
3. LAY PIPE AT SLOPE INDICATED ON DRAWINGS OR NOT LESS THAN 2.0 PERCENT
FOR SERVICE LINES.
4. INSTALL SERVICE LINES AS INDICATED ON DRAWINGS.
5. PLACE BEDDING AT SIDES AND OVER TOP OF PIPE IN LIFTS NOT EXCEEDING 6
INCHES COMPACTED DEPTH. PLACE BEDDING TO MINIMUM COMPACTED
THICKNESS OF 12 INCHES ABOVE TOP OF PIPE.
6. COMPACT BEDDING TO 96 PERCENT OF MAXIMUM LABORATORY DENSITY.
MAINTAIN OPTIMUM MOISTURE CONTENT TO ATTAIN REQUIRED DENSITY.
7. CLEAN SEWER PIPE.
E.LOW PRESSURE AIR TEST: UNI-B-6.
1. PERFORM ON NEW SECTION OF MAIN PIPE LINE AND SERVICE PIPE LINE. NOT
REQUIRED ON REMOVE AND REPLACE SEWER LINES.
2.PERFORM AFTER SEWER LINE HAS BEEN BACKFILLED AND CLEANED.
3. CAP AND BRACE ALL WYES, TEES, AND LATERAL STUBS TO WITHSTAND TEST
PRESSURES.
4.PLUG PIPE IN MANHOLES OR AT ENDS OF PIPE.
5. USE ACCURATE GAUGE TO MEASURE INTERNAL GAUGE PRESSURE IN TENTHS
OF POUNDS PER SQUARE INCH. TEST PRESSURES ARE MEASURED AS GAUGE
PRESSURE.
6. DETERMINE REQUIRED TEST TIME FOR SEWER LINE BASED ON LENGTH AND
SIZE OF PIPE SHOWN IN ATTACHED TABLE.
7. BEFORE STARTING AIR TEST, DETERMINE GROUNDWATER LEVEL. IF
GROUNDWATER LEVEL IS BELOW SEWER PIPE INVERT, PERFORM TEST AT AIR
PRESSURE INDICATED IN SUBPARAGRAPHS 8, 9, & 10. IF GROUNDWATER LEVEL
IS ABOVE SEWER PIPE INVERT, INCREASE AIR PRESSURE FOR TEST.
CALCULATE REQUIRED AIR PRESSURE FOR TEST AS FOLLOWS:
a. DETERMINE AVERAGE VERTICAL HEIGHT IN FEET OF GROUNDWATER ABOVE
SEWER PIPE INVERT.
b. DIVIDE VERTICAL HEIGHT BY 2.31. RESULT IS AIR PRESSURE CORRECTION IN
POUNDS PER SQUARE INCH.
c. ADD AIR PRESSURE CORRECTION TO NORMAL STARTING PRESSURE OF 3.5
POUNDS PER SQUARE INCH TO DETERMINE AIR PRESSURE FOR TEST.
d. DO NOT EXCEED 9 POUNDS PER SQUARE INCH FOR STARTING TEST
PRESSURE.
8. SLOWLY INTRODUCE LOW PRESSURE AIR INTO PIPE UNTIL INTERNAL AIR
PRESSURE REACHES 4.0 POUNDS PER SQUARE INCH.
9. AFTER CONSTANT PRESSURE OF 4.0 POUNDS PER SQUARE INCH IS REACHED,
THROTTLE AIR SUPPLY FOR AT LEAST 2 MINUTES TO ALLOW AIR TEMPERATURE
TO EQUALIZE.
1. 10. WHEN TEMPERATURE HAS EQUALIZED AND PRESSURE HAS STABILIZED
AT 4.0 POUNDS PER SQUARE INCH OR ANY CONVENIENT PRESSURE BETWEEN
4.0 TO 3.5 POUNDS PER SQUARE INCH, START TIMING WITH STOP WATCH.
11. RECORD DROP IN PRESSURE FOR TEST PERIOD.
12. IF PRESSURE DROP IS 0.5 POUND PER SQUARE INCH OR LESS DURING
TEST PERIOD, SEWER LINE PASSES TEST.
13. IF PRESSURE DROP IS GREATER THAN 0.5 POUND PER SQUARE INCH
DURING TEST PERIOD, SEWER LINE FAILS TEST. FIND SOURCE OF LEAKAGE,
REPAIR OR REPLACE, AND RETEST. REPEAT TEST UNTIL SEWER LINE PASSES
TEST.
DEFLECTION TEST:
1. PERFORM ON EACH NEW SECTION OF MAIN PIPE BETWEEN MANHOLES. NOT
REQUIRED ON REMOVE AND REPLACE SEWER LINES.
2. TEST MAIN SEWER PIPE LINES BY ONE OF FOLLOWING METHODS:
a. DEFLECTOMETER WHICH PRODUCES CONTINUOUS RECORD OF PIPE
DEFLECTION.
b. MANDREL GO/NO-GO DEVICE WITH DIAMETER SET AT 95 PERCENT OF
NOMINAL PIPE DIAMETER.
3. NO MECHANICAL PULLING DEVICES PERMITTED.
4. COMPLETE TEST AFTER FINAL BACKFILL HAS BEEN IN PLACE FOR MINIMUM 30
DAYS.
5. IF RING DEFLECTION IS 5 PERCENT OR LESS OF VERTICAL PIPE DIAMETER,
SEWER PIPE PASSES TEST.
6. IF RING DEFLECTION IS GREATER THAN 5 PERCENT OF VERTICAL INTERNAL
PIPE DIAMETER, SEWER PIPE FAILS TEST. RELAY OR REPLACE PIPE AND
RETEST AFTER 30 DAY PERIOD. REPEAT TEST UNTIL PIPE PASSES TEST.
44.00'
N O
R T
H
-8 .6
-4 .6
%-1.0%
-2 .4
-2.6%
-0 .2
-1 .0
-0.0%
0.0%
-0 .5
-1 .6
-1.1%
TOC:5513.95
TOC:5513.95
TOC:5513.95
TOC:5513.95
TOC:5513.80
TOC:5513.77
TOC:5513.74
TOC:5513.69
TOC:5512.54
TOC:5512.63
5513.50
TOC:5513.87
TOC:5513.78
TOC:5513.78
TOC:5513.95TOC:5513.95
5513.00
37.94'
9.93' 4.00'
8.05'
4.00'
16.00'
-5.1%
-1.1%
-1.0%
EG:5512.63
EG:5513.95
EG:5513.69
EG:5512.54
TOC:5513.91
EG:5513.91
TOC:5513.43
EG:5513.43
TOC:5513.89
EG:5513.89
TOC:5512.83
EG:5512.83
TOC:5513.12
EG:5513.12
TOC:5513.32
EG:5513.32
TOC:5513.51
EG:5513.51
TOC:5513.88
EG:5513.82
TOC:5513.82
EG:5513.88
TOC:5513.80
EG:5513.80
TOC:5513.77
EG:5513.77
TOC:5513.72
EG:5513.72
-0 .6
-0.9%
1.
6%
1.
6%
-1.7%
-1.6%
-2.0%
WMH
SMH
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
B
C
D
E
F
G
H
J
K
L
M
SUBMITTAL
JDE No.
STAMP
NO. DATE DESCRIPTION
REVISIONS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FOR BIDDING
Blue Stakes of
Bluestakes.org 1-800-662-4111
CALL BEFORE YOU DIG.
IT'S FREE AND IT'S THE LAW.
SITE & GRADING PLAN
C-100
DUCHESNE
FAIRGROUNDS
RESTROOM
DUCHESNE
COUNTY
2508-062
Pr in t D at e:
3/
/2
9:
P at h:
H :\2
8-
2\ dw g\
D
ES
IG
N
8-
2.
dw g
EXISTING BATHROOMS
EXISTING SEWER MANHOLE
REPLACE EXISTING FENCE
AS NECESSARY, TIE INTO EXISTING
FENCE
4" THICK CONCRETE FLATWORK
EXISTING WATER LINE
LOCATION FIELD VERIFY
LOCATION, SIZE, TYPE
FFE - 5513.95
5'0 2.5'
1 Inch = 5 Feet
10'
FFE - 5513.78
COORDINATE FOOTING
ELEVATIONS WITH
STRUCTURAL
FOOTING DEPTH CHANGES
AT THIS WALL
SAWCUT CONCRETE REPLACE CONCRETE
SAWCUT CONCRETE
CONCRETE REPAIR
O
R T
H
INSTALL 4-IN SEWER PIPE
36.40' @ -1.05%
37.94'
9.93'
4.00'
8.05'
4.00'
16.00'
SCO
INSTALL SEWER CLEANOUT
RIM:5513.26
INV IN 5509.67 (4") (S)
INV OUT 5509.57 (4") (W)
WMH
SMH
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
B
C
D
E
F
G
H
J
K
L
M
SUBMITTAL
JDE No.
STAMP
NO. DATE DESCRIPTION
REVISIONS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FOR BIDDING
Blue Stakes of
Bluestakes.org 1-800-662-4111
CALL BEFORE YOU DIG.
IT'S FREE AND IT'S THE LAW.
UTILITY PLAN
C-101
DUCHESNE
FAIRGROUNDS
RESTROOM
DUCHESNE
COUNTY
2508-062
Pr in t D at e:
3/
/2
9:
P at h:
H :\2
8-
2\ dw g\
D
ES
IG
N
8-
2.
dw g
TIE INTO EXISTING SEWER MAIN-LINE
TIE INTO EXISTING WATER LINE
(FIELD VERIFY WATER LINE
DEPTH AND LOCATION)
TIE INTO EXISTING POWER
90-DEG FITTING REQ'D3" C900 WATER LINE REQ'D
(CONTRACTOR TO VERIFY INCOMING PIPE
IS A MIN. OF 2 1
2" PIPE)
INSTALL WATER METER
5'0 2.5'
1 Inch = 5 Feet
10'
BURIED ELECTRICAL
FFE - 5513.95
FFE - 5513.78
O
R T
H
-8 .6
-4 .6
%-1.0%
-2 .4
-2.6%
-0 .2
-1 .0
-0.0%
0.0%
-0 .5
-1 .6
-1.1%
TOC:5513.95
TOC:5513.95
TOC:5513.95
TOC:5513.95
TOC:5513.80
TOC:5513.77
TOC:5513.74
TOC:5513.69
TOC:5512.54
TOC:5512.63
5513.50
TOC:5513.87
TOC:5513.78
TOC:5513.78
TOC:5513.95TOC:5513.95
5513.00
37.94'
9.93'
4.00'
8.05'
4.00'
16.00'
-5.1%
-1.1%
-1.0%
EG:5512.63
EG:5513.95
EG:5513.69
EG:5512.54
TOC:5513.91
EG:5513.91
TOC:5513.43
EG:5513.43
TOC:5513.89
EG:5513.89
TOC:5512.83
EG:5512.83
TOC:5513.12
EG:5513.12
TOC:5513.32
EG:5513.32
TOC:5513.51
EG:5513.51
TOC:5513.88
EG:5513.82
TOC:5513.82
EG:5513.88
TOC:5513.80
EG:5513.80
TOC:5513.77
EG:5513.77
TOC:5513.72
EG:5513.72
-0 .6
-0.9%
1.
6%
1.
6%
-1.7%
-1.6%
-2.0%
WMH
SMH
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
B
C
D
E
F
G
H
J
K
L
M
SUBMITTAL
JDE No.
STAMP
NO. DATE DESCRIPTION
REVISIONS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FOR BIDDING
Blue Stakes of
Bluestakes.org 1-800-662-4111
CALL BEFORE YOU DIG.
IT'S FREE AND IT'S THE LAW.
ADA SCHEMATIC
C-102
DUCHESNE
FAIRGROUNDS
RESTROOM
DUCHESNE
COUNTY
2508-062
Pr in t D at e:
3/
/2
9:
P at h:
H :\2
8-
2\ dw g\
D
ES
IG
N
8-
2.
dw g
EXISTING SEWER MANHOLE
CONCRETE SIDEWALK
EXISTING WATER LINE
LOCATION FIELD VERIFY
LOCATION, SIZE, TYPE
5'0 2.5'
1 Inch = 5 Feet
10'
FFE - 5513.95
FFE - 5513.78
ACCESSIBLE ROUTE
EXISTING RESTROOMS
ACCESSIBLE ROUTE
INSTALL PLUG ON NEW
SERVICE. FOR EXISTING
SERVICE CONNECT
TO EXISTING SERVICE LINE.
COMPACTED BEDDING
AROUND PIPE (TYP.)
SERVICE CONNECTION
SEWER MANHOLE
1' LENGTH OF PIPE BETWEEN
WYE AND ELBOW
PA
YL
IN
E
PA
YL
IN
E
INSTALL CLEANOUT
WITHIN RIGHT-OF-WAY
PAYLINE FOR SEWER
SERVICE LINE
NOTES:
1. USE 4-INCH SDR 35 PVC PIPE & FITTINGS FOR SERVICE CONNECTIONS, UNLESS NOTED OTHERWISE.
2. TERMINATE CLEANOUT AT FINISHED GRADE IN ACCORDANCE WITH DETAIL J5.
2.08% MIN. SLOPE
4" PVC PIPE
4" PVC PIPE
4" PVC PIPE
SMH
FINISHED GRADE
SLOPE
45° BEND
D
EP
TH
V
AR
IE
S
CLEANOUT RISER
45° WYE
PIPE (SIZE AS NOTED)
CAST IRON RING AND COVER
(D&L SUPPLY H-8020)
8"
24" Ø CONCRETE COLLAR
SEE NOTE 3
THREADED PVC PLUG
CAP OR PLUG
AT END OF LINE
1" LENGTH OF PIPE BETWEEN
WYE AND ELBOW
EXPANSION JOINT
CONTROL JOINT
SAW CUT OR SCORE.
T
NOTES:
1. FOR FLATWORK, PLACE AT SPACING EQUAL TO SLAB WIDTH, BUT NOT GREATER THAN INDICATED
ON TABLE BELOW.
NOTES:
1. USE FOR FLATWORK, PLACE AT 50' INTERVALS.
2. FOR CURB, CURB & GUTTER, PLACE AT 50' INTERVALS, EXCEPT WHEN USING SLIP
FORM MACHINE, PLACE AT BEGINNING AND END OF EACH CONTINUOUS RUN.
PRE-FORMED
JOINT FILLER.
1/2"
1/4" MAX.T/3
MAXIMUM CONTROL JOINT SPACING
SLAB THICKNESS, IN.MAXIMUM JOINT SPACING, FT.
UNREINFORCED REINFORCED
4 8 10 5 10 12 6 12 15 8 16 20
NOTES:
1. INSTALL TRACER WIRE WITH ALL SERVICE LINES.
2. TERMINATE TRACER WIRE WITH LOOP INSIDE METER BARREL OR BOX.
3. SIZE METER BARREL OR BOX TO FIT METER SIZE AND SITE CONDITIONS.
4. USE TRAFFIC RATED BARREL OR BOX IN TRAFFIC AREAS.
5. RELATED SPEC SECTION 33 14 12.
CAST IRON LID WITH WORDS
"WATER METER" CAST IN LID.
PROVIDE 1-3/4" DIA. HOLE
FOR PIT MODULE.
CAST IRON RING.
METER BARREL
OR BOX
GATE VALVE
REDUCER AS
NECESSARY
PVC PIPEPVC PIPE
REDUCER AS
NECESSARY 1' - 6" MIN.
12" CLEAN GRAVEL BASE
1' - 6" MIN.
COMPOUND
METER
6" LONG FLG X FLG SPOOL
CHECK VALVE
GATE VALVE
BU
R
IA
L
D
EP
TH
(S
EE
T
R
EN
C H
D
ET
AI
L)
4" 3"
METER SIZE BARREL SIZE (D)LENGTH
METER BARREL SCHEDULE
96" MIN.6"
78" MIN. 36" MIN
84" MIN. 36" MIN
36" MIN
12"± 12"±
D
FLOW FLOW
NOTES:
1. SEE DETAIL FOR CONCRETE JOINTS.
4" DEPTH CONCRETE
SIDEWALK.
2% MAX.
BACKFILL BEHIND
SIDEWALK.
4" MIN. UNTREATED BASE COURSE
BACKFILL BEHIND
SIDEWALK.
4' MINIMUM
CONCRETE FLATWORK
/1 6"
M
IN
4" DEPTH UNTREATED
BASE COURSE MATCH EXISTING
DEPTH, BUT NO LESS
THAN 6" DEPTH
UNTREATED BASE
COURSE
CONCRETE FLATWORK
(EQUAL TO EXISTING
CONCRETE DEPTH, BUT
NOT LESS THAN 6")
VA
R
IE
S
EXIST. GROUND
12" MIN. (TYP.)
CLEAN GRAVEL (MATCH
EXISTING DEPTH, BUT NOT
LESS THAN 2")
12" MIN. (TYP.)
EXIST. GROUND
CLASS D
(GRAVEL SURFACING)
VARIES
M
AX
P
AY
LI
N
E
M
AX
P
AY
LI
N
E
VARIES
M
AX
P
AY
LI
N
E
M
AX
P
AY
LI
N
E
BACKFILL (SEE
UTILITY TRENCH
DETAIL)
BACKFILL (SEE
UTILITY TRENCH
DETAIL)
SAWCUT EXISTING
CONCRETE PRIOR TO
EXCAVATION (TYP.)
CONCRETE
EDGE OF PAVEMENT AFTER COMPACTION
TACK COAT
HMA PAVEMENT
UNTREATED BASE COURSE
1/ 4"
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
A
B
C
D
E
F
G
H
J
K
L
M
SUBMITTAL
JDE No.
STAMP
NO. DATE DESCRIPTION
REVISIONS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
FOR BIDDING
Blue Stakes of
Bluestakes.org 1-800-662-4111
CALL BEFORE YOU DIG.
IT'S FREE AND IT'S THE LAW.
DETAILS
C-501
DUCHESNE
FAIRGROUNDS
RESTROOM
DUCHESNE
COUNTY
2508-062
Pr in t D at e:
3/
/2
9:
P at h:
H :\2
8-
2\ dw g\
D
ES
IG
N
8-
2.
dw g
J1 C501
SEWER SERVICE CONNECTION
J5
C501
SEWER CLEAN OUT
J9 C501
SIDEWALK CONTROL JOINT
E1 C501
3-INCH WATER METER
E5
C501
SIDEWALK
E9
C501
TRENCH DETAIL & CONCRETE REPAIR
A1 C501
PAVEMENT EDGE
STRUCTURAL PLAN LEGEND
STEEL COLUMN
JOIST OR TRUSS
BEAM OR GIRDER
CONCRETE COLUMN
NON-BEARING STRUCTURAL WALL
RECESSED FOUNDATION WALL
CONCRETE FOOTING
MASONRY COLUMN
STEEL STRAP
BEAM IN WALL
BEARING WALL
PURLIN
STEEL DECK
OWS JOIST CROSS BRIDGING
HOLDOWN, SEE HOLDOWN SCHEDULE.
"H" INDICATES LOCATION OF HOLDOWN
IDENTIFIED ON LEVEL ABOVE.
SNOW DRIFT AREA AND LOAD, ON TOP OF
BASE SNOW LOAD. DRIFT LOAD IS 0 PSF
AT DOTTED LINE AND INCREASES
LINEARLY TO MAXIMUM LOAD.10' - 0"
45 psf
SHEATHING
SHEARWALL TYPE AND LENGTH,
SEE SHEARWALL SCHEDULE
STEEL JOIST CROSS BRIDGING
PERMANENT EQUIPMENT
CF-1
100" - 0"
MARK
TOP OF FOOTING
ELEVATION
FOOTING TAG, SEE FOOTING SCHEDULE
4' - 0"
1.
2.
3.
4.
5.
REFER TO TYPICAL NOTES, DETAILS, & SCHEDULES.
SEE CIVIL PLANS FOR EXTERIOR CONCRETE WORK AND
SITE GRADING.
SEE ARCHITECTURAL DRAWINGS FOR SLAB SLOPES,
DIMENSIONS, AND ELEVATIONS.
PLACE STRUCTURAL FILL BENEATH FOOTINGS &
BUILDING SLABS PER TYPICAL DETAIL "STRUCTURAL FILL
PLACEMENT" AND PER EARTHWORK NOTES.
PROVIDE TEMPORARY SHORING UNTIL MAIN FLOOR
FRAMING IS COMPLETE FOR ANY WALL OVER 6' TALL THAT
RETAINS SOIL TO RESIST INDUCED LATERAL LOADS.
FOUNDATION NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
REFER TO TYPICAL NOTES, DETAILS, & SCHEDULES.
SEE ARCHITECTURAL DRAWINGS FOR INFORMATION NOT
SHOWN.
DIMENSIONS FOR SHEARWALLS ARE TO EDGE OF
SHEARWALL, NOT LOCATION OF HOLDOWN.
INSTALL ALL HANGERS, CLIPS, ANCHORS, AND OTHER
HARDWARE PER MANUFACTURER'S RECOMMENDATIONS.
SHOP-FABRICATED WOOD TRUSSES SHALL BE DESIGNED
FOR THE UNIFORM LOADS SPECIFIED IN THE SHOP-
FABRICATED WOOD TRUSSES NOTES AND ANY
CONCENTRATED GRAVITY AND LATERAL LOADS
INDICATED ON THE STRUCTURAL FRAMING PLANS.
NOTATION AND SYMBOLS FOR LOADS SHOWN ARE PER
ASCE 7.
ALL TRUSSES SHALL BE DESIGNED TO TRANSFER AN
OUT-OF-PLANE SERVICE SEISMIC OR WIND LOAD OF 0.7
KIPS (Fp) FROM THE HEEL TO THE DIAPHRAGM AT
BEARING LOCATIONS.
FORM UP & FILL ALL BEAM & JOIST POCKETS W/ NON-
SHRINK GROUT PRIOR TO PLACING FINISHES, UNO.
COORDINATE MECHANICAL UNIT WEIGHTS AND
LOCATIONS WITH JOIST MANUFACTURER
PROVIDE BRIDGING AS REQ'D TO PREVENT CHORD
BUCKLING.
PROVIDE TRUSS BLOCKING AT ALL BEARING WALLS
WHERE TRUSS HEEL HEIGHT PROHIBITS USE OF 2X
BLOCKING.
TRUSS BLOCKING SHALL BE ABLE TO RESIST A LATERAL
LOAD (WIND OR SEISMIC) OF 250 PLF.
FRAMING NOTESDESIGN CRITERIA
BUILDING CODE: 2021 INTERNATIONAL BUILDING CODE
CLASSIFICATION: RISK CATEGORY II
LIVE LOADING
ROOF: 20 PSF (REDUCIBLE)
DEAD LOADING
ROOF: 20 PSF (INCLUDES 5 PSF FOR SELF WEIGHT OF
TRUSSES)
SNOW LOADING (BASED ON 2018 UTAH GROUND SNOW LOAD
MAP)
ELEVATION: 5,600 FT (APPROX.)
GROUND SNOW LOAD: Pg = 41 PSF EXPOSURE FACTOR: Ce = 0.9 SNOW IMPORTANCE FACTOR: Is = 1.0 THERMAL FACTOR: Ct = 1.0 CALCULATED SNOW LOAD: Pf = 25.83 PSF
MIN. SNOW LOAD DESIGNATED BY BUILDING OFFICIAL: 24 PSF
DESIGN SNOW LOAD: Pf = 26 PSF SLOPE FACTOR: Cs = 1.0
WIND LOADING
WIND EXPOSURE: C
WIND SPEED: 105 MPH
WIND IMPORTANCE FACTOR: lw = 1.0
SEISMIC LOADING
LOCATION: 40.158349° LAT., -110.401528° LON.
SEISMIC IMPORTANCE FACTOR: Ie = 1.00
MAPPED SPECTRAL RESPONSE ACCELERATIONS:
SS = 0.316g S1 = 0.099g
SITE CLASS: D
SPECTRAL RESPONSE COEFFICIENTS:
SDS = 0.326g SD1 = 0.159g
SEISMIC DESIGN CATEGORY: C
SEISMIC FORCE RESISTING SYSTEM: SPECIAL REINFORCED
MASONRY SHEAR WALLS
OUT-OF-PLANE FORCE: Fp = 0.1304 Wp SEISMIC RESPONSE COEFFICIENT: Cs=0.065
RESPONSE MODIFICATION FACTOR: R=5
OVERSTRENGTH FACTOR: Ω = 2.5
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE
METHOD
SOILS
SOIL BEARING PRESSURE: 1,500 PSF
PROJECT GEOTECHNICAL INVESTIGATION: NONE
STRUCTURAL QA PLAN
1.
2.
3.
4.
A.
B.
C.
A.
B.
C.
D.
E.
F.
A.
B.
C.
D.
A.
1.
2.
3.
4.
5.
1.
2.
QUALITY ASSURANCE AGENCY (QAA) REQUIREMENTS:
THE OWNER OR REGISTERED DESIGN PROFESSIONAL IN
RESPONSIBLE CHARGE ACTING AS THE OWNER'S AGENT
SHALL ENGAGE A QUALIFIED QUALITY ASSURANCE
AGENCY TO PROVIDE ALL SPECIAL INSPECTION AND
QUALITY ASSURANCE TESTING FOR THE PROJECT. ALL
QUALITY ASSURANCE PERSONNEL ASSIGNED TO THE
PROJECT SHALL PROVIDE WRITTEN DOCUMENTATION TO
THE BUILDING OFFICIAL DEMONSTRATING HIS OR HER
COMPETENCE AND RELEVANT EXPERIENCE OR TRAINING.
PRIOR TO CONSTRUCTION, THE QAA SHALL PREPARE A
WRITTEN QUALITY ASSURANCE IMPLEMENTATION PLAN
FOR THE PROJECT. THE PLAN SHALL INCLUDE A LIST OF
PERSONNEL ASSIGNED TO THE PROJECT INCLUDING
MANAGEMENT PERSONNEL, INSPECTION PROCEDURES
AND FREQUENCY, PROPOSED TESTING METHODS AND
FREQUENCY OF TESTING, AND REPORTING
PROCEDURES. THE PLAN SHALL ALSO OUTLINE
METHODS OF DOCUMENTING DEFICIENCIES AND
REPORTING CORRECTIONS. A COPY OF THE PLAN SHALL
BE GIVEN TO THE CONTRACTOR FOR REVIEW AND
COORDINATION WITH SUBCONTRACTORS.
THE SPECIAL INSPECTOR SHALL INSPECT THE WORK PER
CHAPTER 17 OF THE IBC FOR CONFORMANCE WITH THE
CONTRACT DOCUMENTS. THE SPECIAL INSPECTOR
SHALL SEND REPORT TO THE OWNER, BUILDING
OFFICIAL, ARCHITECT, ENGINEER, AND CONTRACTOR.
ALL NOTED DEFICIENCIES SHALL BE NOTED IN THE
REPORT AND SHALL BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE CONTRACTOR FOR CORRECTION.
THE QAA SHALL SUBMIT A FINAL SIGNED REPORT
STATING THAT THE SPECIAL INSPECTION WORK WAS, TO
THE BEST OF THEIR KNOWLEDGE, IN CONFORMANCE
WITH THE PLANS, SPECIFICATIONS AND APPLICABLE
WORKMANSHIP PROVISIONS OF THE IBC.
CONTRACTOR IS ADVISED THAT ADDITIONAL SPECIAL
INSPECTIONS AND TESTING MAY BE REQUIRED BY THE
AUTHORITY HAVING JURISDICTION.
SEISMIC FORCE RESISTING SYSTEMS:
ELEMENTS THAT ARE PART OF THE MAIN SEISMIC FORCE
RESISTING SYSTEM FOR THE STRUCTURE MAY REQUIRE
INCREASED QUALITY ASSURANCE INSPECTION AND
TESTING. CONTACT ENGINEER OF RECORD REGARDING
WHICH ELEMENTS ARE PART OF THE MAIN SEISMIC FORCE
RESISTING SYSTEM FOR THE STRUCTURE MAY INCLUDE
THE FOLLOWING ELEMENTS:
CONCRETE WALLS
FOOTING AND FOUNDATION SYSTEM
CONNECTIONS BETWEEN ELEMENTS REFERENCED
ABOVE.
SPECIAL INSPECTION: SPECIAL INSPECTION SHALL BE
PROVIDED FOR THE FOLLOWING ITEMS PER IBC 1704 AND
1707.
1.SOILS: SITE SOIL CONDITIONS, FILL PLACEMENT AND
LOAD-BEARING REQUIREMENTS SHALL BE INSPECTED AS
REQUIRED BY IBC 1705.6, THE APPROVED GEOTECHNICAL
REPORT, AND THE CONSTRUCTION DOCUMENTS
PREPARED BY THE REGISTERED DESIGN PROFESSIONALS.
SPECIAL INSPECTION OF SOILS SHALL INCLUDE THE
FOLLOWING:
VERIFY MATERIALS BELOW SHALLOW FOUNDATION
ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING
CAPACITY.
VERIFY EXCAVATIONS ARE EXTENDED TO PROPER
DEPTH AND HAVE REACHED PROPER MATERIAL.
PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS.
VERIFY USE OF PROPER MATERIALS, DENSITIES AND
LIFT THICKNESS DURING PLACEMENT AND
COMPACTION OF COMPACTED FILL.
PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE
SUBGRADE AND VERIFY THAT SITE HAS BEEN
PREPARED PROPERLY.
SOILS SHALL RECEIVE CONTINUOUS SPECIAL
INSPECTION DURING PLACEMENT OF MATERIALS TO
VERIFY PROPER MATERIALS, DENSITIES, AND LIFT
THICKNESS.
2.CONCRETE AND EMBEDDED ITEMS IN CONCRETE SHALL
BE SPECIAL INSPECTED PRIOR TO AND DURING PLACEMENT
OF CONCRETE. SPECIAL INSPECTION OF CONCRETE SHALL
INCLUDE THE FOLLOWING:
REINFORCING STEEL GRADE, SIZE AND PLACEMENT.
SURFACE PREPARATION AT COLD JOINTS INCLUDING
PLACEMENT OF KEYWAYS.
BOLT AND EMBED SIZE, CONFIGURATION AND
PLACEMENT.
CONCRETE SHALL RECEIVE CONTINUOUS SPECIAL
INSPECTION DURING PLACEMENT, AND PERIODIC
INSPECTION AFTER PLACEMENT TO ENSURE PROPER
CURING AND WEATHER PROTECTION PROCEDURES.
3.POST-INSTALLED ANCHORS, INCLUDING BUT NOT LIMITED
TO EXPANSION ANCHORS, ADHESIVE ANCHORS AND REBAR
DOWELS, AND LOW VELOCITY FASTENERS, SHALL RECEIVE
SPECIAL INSPECTION PER THE CODE EVALUATION
REPORTS FOR THE ANCHORS.
CONTINUOUS SPECIAL INSPECTION IS REQUIRED
DURING THE INSTALLATION OF ALL ADHESIVE ANCHORS
AND REBAR DOWELS. SPECIAL INSPECTOR SHALL
VERIFY THE FOLLOWING:
ANCHOR SIZE AND STEEL GRADE.
HOLE DIAMETER, LOCATION AND TYPE OF DRILL BIT.
CLEANLINESS OF HOLE AND ANCHOR.
ADHESIVE APPLICATION.
ANCHOR EMBEDMENT.
STRUCTURAL TESTING: THE FOLLOWING MATERIALS SHALL
BE TESTED PER IBC 1705. THE OWNER RESERVES THE
RIGHT TO TEST ANY AND ALL MATERIALS USING ANY
APPROPRIATE NON-DESTRUCTIVE PROCEDURE. ANY ITEMS
FOUND TO BE DEFICIENT SHALL BE CORRECTED AND
RETESTED AT NO ADDITIONAL COST TO THE OWNER.
EARTHWORK: ALL COMPACTED STRUCTURAL FILL
SHALL BE TESTED TO VERIFY SOIL GRADATION, LIFT
THICKNESS, AND COMPACTION REQUIREMENTS. SEE
THE PROJECT SPECIFICATIONS FOR TESTING
FREQUENCY AND ACCEPTABILITY CRITERIA.
CONCRETE STRENGTH VERIFICATION AND TESTING.
ALL CONCRETE SHALL BE TESTED TO VERIFY
STRENGTH, SLUMP, UNIT WEIGHT, AIR CONTENT, AND
TEMPERATURE. SEE THE PROJECT SPECIFICATIONS
FOR TESTING CRITERIA, TESTING FREQUENCY AND
ACCEPTABILITY CRITERIA.
EARTHWORK
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
A.
B.
C.
D.
E.
F.
13.
14.
ENGINEER SHALL VERIFY CONDITION AND/OR ADEQUACY
OF ALL SUBGRADES, FILLS, AND BACK FILLS, ETC.
SHORE AND BRACE AS REQUIRED.
DE-WATER AS REQUIRED TO REMOVE STANDING WATER
FROM EXCAVATIONS.
FOUNDATIONS ARE SHOWN AND DIMENSIONED AS BEING
FORMED. INCREASE FOOTING WIDTHS BY 2" FOR
FOOTINGS PLACED IN NEAT EXCAVATIONS.
CLEAN ALL DEBRIS FROM EXCAVATIONS.
NOTIFY ENGINEER 48 HOURS IN ADVANCE OF PLACING
CONCRETE.
PROVIDE 30" MINIMUM FOOTING EMBEDMENT FROM FINISH
GRADE FOR FROST PROTECTION AT EXTERIOR FOOTINGS.
SCARIFY SOILS IN BOTTOM OF EXCAVATIONS 6",
MOISTURE CONDITION TO WITHIN 2% OF OPTIMUM
MOISTURE, AND COMPACT TO 95% OF MAXIMUM DRY
DENSITY AS DETERMINED BY ASTM D1557 PRIOR TO
PLACEMENT OF STRUCTURAL FILL.
COUNTY TO PROVIDE GEOFABRIC ON PREPARED EARTH
PRIOR TO PLACEMENT OF STRUCTURAL FILL.
COUNTY TO PROVIDE 18" OF STRUCTURAL FILL BENEATH
ALL FOOTINGS.
EXTEND STRUCTURAL FILL LATERALLY A DISTANCE
EQUAL TO 1/2 THE STRUCTURAL FILL DEPTH BEYOND
EDGE OF FOOTING ON EACH SIDE.
IMPORTED STRUCTURAL FILL USED FOR SUPPORT OF
FOUNDATIONS AND FLOOR SLABS:
WELL-GRADED
NON-EXPANSIVE
FREE OF ORGANICS AND ALL DELETERIOUS MATERIALS
PERCENT PASSING NO. 200 SIEVE: 30% MAX
LIQUID LIMIT: 30 OR LESS
PLASTICITY INDEX: 10 OR LESS
COMPACT STRUCTURAL FILL BENEATH FOOTINGS TO 95%
OF MAXIMUM DRY DENSITY DETERMINED BY ASTM D1557.
PLACE STRUCTURAL FILL IN MAXIMUM EIGHT-INCH THICK
LOOSE LIFTS TO ACHIEVE ADEQUATE COMPACTION.
SHOP-FABRICATED WOOD
TRUSSES
1.
2.
3.
4.
5.
A.
a.
b.
c.
d.
e.
B.
a.
b.
C.
6.
A.
B.
7.
A.
B.
8.
9.
10.
11.
DESIGN AND FABRICATE TRUSSES IN ACCORDANCE WITH
2021 IBC.
NOTATION AND SYMBOLS FOR LOADS SHOWN ARE PER
ASCE 7-16 SECTION 2.2.
PROVIDE STAMPED CALCULATIONS AND ERECTION
DRAWINGS FOR ALL TRUSS-TO-TRUSS CONNECTIONS,
BEARING ENHANCERS, ETC.
DESIGN AND FABRICATE ALL REQUIRED TRUSS BRACING.
ROOF TRUSS LOADING
TOP CHORD:
DEAD LOAD: 10.0 PSF (INCLUDES TRUSS SELF-
WEIGHT).
LIVE ROOF LOAD: 20 PSF.
WIND LOAD: USE COMPONENT AND CLADDING WIND
LOADING PER ASCE 7-16.
SNOW LOADING: USE SNOW LOADING PER ASCE 7-16.
REFER TO ROOF FRAMING PLANS FOR DRIFT LOADS
AS APPLICABLE.
DRAG LOADS: REFER TO ROOF FRAMING PLANS.
BOTTOM CHORD
DEAD LOAD: 10.0 PSF.
LIVE LOAD: 10.0 PSF (BOTTOM CHORD LIVE LOAD IS
NOT CONCURRENT WITH ROOF LIVE LOAD).
DESIGN ALL TRUSSES TO TRANSFER AN OUT-OF-PLANE
SERVICE SEISMIC OR WIND LOAD OF 0.7 KIPS (Fp) FROM
HEEL TO DIAPHRAGM AT BEARING LOCATIONS.
MAXIMUM DEFLECTION
ROOF TRUSSES: TL/180 OR LL/240.
FLOOR TRUSSES: TL/240 OR LL/360.
MINIMUM MEMBER SIZES:
TOP CHORDS: 2X6
WEBS AND BOTTOM CHORD: 2X4
ALLOWABLE STRESS INCREASE FOR LOAD DURATION:
15% MAXIMUM.
DO NOT USE REPETITIVE MEMBER INCREASE FOR
GIRDER TRUSSES.
CONSIDER EFFECTIVE ECCENTRIC LOADING IN ALL
JOINTS.
FABRICATOR: AN APPROVED FABRICATOR AS
CURRENTLY LISTED BY THE ICBO.
CONCRETE
1.
2.
3.
A.
B.
C.
4.
5.
6.
A.
a.
b.
c.
B.
a.
b.
c.
7.
8.
9.
10.
11.
12.
A.
B.
C.
13.
14.
15.
16.
17.
18.
19.
20.
21.
CONSTRUCT CONCRETE ACCORDING TO ACI 318 (LATEST
VERSION).
DETAIL, FABRICATE, AND INSTALL REINFORCING STEEL
ACCORDING TO "MANUAL OF STANDARD PRACTICE OF
REINFORCED CONCRETE CONSTRUCTION" BY CONCRETE
REINFORCING STEEL INSTITUTE (CRSI).
GENERAL
DO NOT PLACE PIPES OR DUCTS IN CONCRETE SLABS
OR WALLS UNLESS SPECIFICALLY DETAILED.
REFER TO ARCHITECTURAL, STRUCTURAL, CIVIL,
ELECTRICAL AND MECHANICAL DRAWINGS FOR ALL
MOLDS, GROOVES, ORNAMENTS, CLIPS AND GROUNDS
TO BE CAST IN CONCRETE.
DIMENSIONS SHOWN FOR LOCATION OF REINFORCING
ARE TO FACE OF MAIN BARS AND DENOTE CLEAR
COVERAGE.
SUBMIT CONCRETE PLACEMENT PLAN TO ENGINEER 48
HOURS PRIOR TO EACH CONCRETE PLACEMENT.
CONCRETE MIX DESIGN: PREPARED BY INDEPENDENT
LABORATORY AND APPROVED BY ENGINEER OF RECORD.
CONCRETE
LEAN CONCRETE FILL
MINIMUM COMPRESSIVE STRENGTH: 1,500 PSI.
CEMENT: ASTM C-150, TYPE II.
MAXIMUM WATER-CEMENT RATIO: 0.55.
STRUCTURAL CONCRETE
MINIMUM COMPRESSIVE STRENGTH: 4,000 PSI.
CEMENT: ASTM C-150, TYPE II.
MAXIMUM WATER-CEMENT RATIO: 0.45.
CONCRETE EXPOSED TO EXTERIOR CONDITIONS: AIR
ENTRAINED TO 5%-7% AIR CONTENT.
CONCRETE AGGREGATES: NATURAL SAND AND ROCK
AGGREGATES CONFORMING TO ASTM C-33 (3/4" MAX).
REINFORCING STEEL: ASTM A615 GRADE 60 UNO.
WIRE FABRIC: ASTM A-185.
WELDING OF REINFORCING STEEL: CONFORM TO AWS
D1.4 USING PROPER LOW HYDROGEN ELECTRODES. DO
NOT TACK WELD TO REBAR. SEE REBAR WELDING NOTE.
CONCRETE CLEAR COVERAGE, UNO:
CONCRETE PLACED AGAINST FORMS (INCLUDING
CONCRETE TO BE BACKFILLED): 2"
CONCRETE PLACED AGAINST GROUND: 3"
SLABS (ON GROUND): CENTER BAR IN SLAB.
PROVIDE CLASS B LAP SPLICE UNO. SEE TABLE
"CONCRETE REINFORCEMENT LAP SPLICES".
CONSTRUCT CONSTRUCTION JOINTS ROUGH, OR
ROUGHEN JOINTS BY CHIPPING ENTIRE SURFACE,
SANDBLASTING, OR HOSING SURFACE 4 TO 6 HOURS
AFTER PLACEMENT WITH FINE SPRAY. REMOVE ALL
LAITANCE FROM SURFACE.
REMOVE ALL DEBRIS FROM FORMS BEFORE PLACING
ANY CONCRETE.
SECURELY POSITION REINFORCING DOWELS, BOLTS,
ANCHORS, SLEEVES, ETC. TO BE EMBEDDED IN
CONCRETE BEFORE PLACING CONCRETE (WET SETTING
IS PROHIBITED).
OBTAIN APPROVAL OF ALL AFFECTED TRADES PRIOR TO
PLACING CONCRETE.
MAXIMUM FREE FALL OF CONCRETE: 5'-0".
DO NOT USE WOOD SPREADERS. DO NOT USE WOOD
STAKES IN AREAS TO BE CONCRETED.
FOLLOW ACI HOT OR COLD WEATHER PLACEMENT
RECOMMENDATIONS FOR CONCRETE PLACEMENT AND
CURING.
EXERCISE SPECIFIC CARE DURING PLACEMENT AND
CURING OF CONCRETE SLABS AND EXPOSED CONCRETE
FINISHES.
SPLICE LENGTH (IN.) FOR F'c = 4000 PSI
LOCATION
REINFORCEMENT SIZE
#11
TOP
OTHER
#10
#9
#8
#7
#6
#5
#4
#3
CONCRETE REINFORCEMENT
LAP SPLICES
1.
2.
3.
4.
5.
6.
TENSION DEVELOPMENT LENGTHS AND TENSION LAP
SPLICE LENGTHS ARE BASED ON ACI 318-19, SECTIONS
25.4.2 AND 25.5.2 RESPECTIVELY. TABULATED VALUES
FOR BEAMS OR COLUMNS ARE BASED ON TRANSVERSE
REINFORCEMENT AND CONCRETE COVER MEETING
MINIMUM CODE REQUIREMENTS.
LAP SPLICE LENGTHS SHOWN ARE FOR CLASS B AND
CASE 1.
TOP REINFORCEMENT IS HORIZONTAL REINFORCEMENT
THAT HAS MORE THAN TWELVE INCHES OF FRESH
CONCRETE CAST BELOW IT. THIS INCLUDES HORIZONTAL
REINFORCEMENT IN WALLS. ALL VERTICAL BARS ARE
CONSIDERED AS "OTHER".
FOR LIGHTWEIGHT CONCRETE AGGREGATE CONCRETE,
MULTIPLY TABULATED VALUES BY 1.3.
REINFORCEMENT IS ASSUMED TO BE UNCOATED OR
GALVANIZED.
FOR BARS WITH COVER OF LESS THAN 1 BAR DIAMETER
OR WITH CLEAR SPACING OF LESS THAN 2 BAR
DIAMETERS, MULTIPLY TABULATED VALUES BY 2.0.
MASONRY
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
ALL MASONRY CONSTRUCTION SHALL CONFORM TO THE
SPECIFICATION FOR MASONRY STRUCTURES ACI
530-13/ASCE 6-13/TMS 402-13.
CONCRETE BLOCK UNITS SHALL BE LIGHT WEIGHT GRADE
N (85-105 PCF). TYPE 1 WITH MIN. COMPRESSIVE
STRENGTH OF 2000 PSI ON AVERAGE NET AREA. (F'M=2000
PSI).
MORTAR SHALL BE TYPE S CONFORMING TO APPLICABLE
STANDARDS PER SPECIFICATION FOR MASONRY
STRUCTURES.
GROUT SHALL HAVE COMPRESSIVE STRENGTH OF 2000
PSI AND CONFORM TO APPLICABLE STANDARDS
REINFORCING STEEL SHALL COMPLY WITH THE
"CONCRETE NOTES" UNO.
LAP ALL BARS AS INDICATED IN THE MASONRY
REINFORCING BAR LAP SPLICE SCHEDULE.
BEFORE BLOCK IS PLACED ON CONCRETE, THOROUGHLY
CLEAN CONCRETE OF ALL LAITANCE AND ALL LOOSE
MATERIAL, ROUGHEN AS DIRECTED IN "CONCRETE
NOTES".
CONCRETE BLOCK MASONRY SHALL BE BUILT TO
PRESERVE THE UNOBSTRUCTED CONTINUITY OF THE
VERTICAL CELLS. WALLS AND CROSS WEBS FORMING
SUCH CELLS SHALL BE FULLY BEDDED IN MORTAR. ALL
HEAD OR END JOINTS SHALL BE SOLIDLY FILLED WITH
MORTAR FOR A DISTANCE IN FROM THE FACE OF THE
WALL OR UNITS NOT LESS THAN THE THICKNESS OF THE
LONGITUDINAL FACE SHELLS.
VERTICAL CELLS SHALL HAVE VERTICAL ALIGNMENT
SUFFICIENT TO MAINTAIN A CLEAR UNOBSTRUCTED
CONTINUOUS VERTICAL CELL MEASURING NOT LESS
THAN 3"x3".
CLEAN OUT OPENINGS SHALL BE PROVIDED AT THE
BOTTOMS OF ALL CELLS TO BE POURED AT EACH LIFT OR
POUR OF GROUT WHERE SUCH LIFT OR POUR OF GROUT
IS IN EXCESS OF 4'-0" IN HEIGHT. ANY OVERHANGING
MORTAR OR OTHER OBSTRUCTION OR DEBRIS SHALL BE
REMOVED FROM INSIDE OF SUCH CELLS. THE CLEANOUTS
SHALL BE SEALED AFTER INSPECTION AND…
This is the start of the file's text. The full file is on GovTribe.