3-2-CS27004-26353310-Approved Plans.pdf
PDF 7 MB Posted
- Solicitation number
- CS27004
- Issued by
- Box Elder County, Utah
About this file
This is an approved plans document for an electrical construction project issued by the State of Utah's Division of Facilities Construction and Management (DFCM) for the Brigham Regional Center located at 325 West 1100 South in Brigham City, Utah. The project, identified as DFCM Project No. 26353310, involves the redesigned installation of new exterior electrical disconnects and meters at the facility. The scope of work encompasses demolition of existing switchboard "MSB" and disconnect "EMD1," installation of a new main distribution panel (MDP) rated at 800 amperes with 120/208 volts three-phase service, provision of new current transformer (CT) meters and enclosures for both the Tech College and Beauty College services, relocation of existing electrical equipment to accommodate new ductwork, conversion of an existing electrical closet to standard closet space, and installation of new wall-mounted occupancy sensors and panic hardware on doors. The approved plans consist of eight sheets including cover sheets, abbreviations and legend, electrical site plans, power plans, one-line diagrams, and architectural details for the electrical room modifications. The plans were approved by DFCM on July 1, 2026, and were designed by Sine Source Engineering with coordination from SDG Studio Architects and C-Mech Engineering. An invitational bidding process is being conducted with five pre-selected contractors: BML (Rich Ulrich), Electric Works (Kade Archibald), Kendrick Electrical (Bryan Kendrick), Luminary Electric (Alex Rogers), and Paragon Electric (Richie Benson).
The construction cost estimate for the project is $122,000.00. The plans detail extensive electrical specifications including conductor and conduit schedules, grounding requirements per National Electrical Code (NEC) standards, utility coordination requirements with Brigham City Power, and procedures for temporary power maintenance during service switchover. Key technical requirements include installation of new underground secondary conduits and conductors by the contractor with primary conductors provided by the utility, core drilling into existing vaults with coordinated building shutdowns, reconnection to existing grounding electrodes with provisions for additional ground rods if necessary, and compliance with all applicable codes including the 2024 International Energy Conservation Code, 2023 International Fire Code, and 2020 National Electrical Code. The plans emphasize coordination with the building owner for all shutdowns, with work to be performed during non-business hours and power restoration required before the next scheduled working day. General contractor responsibilities include field verification of all panel clearances, submittal reviews (limited to two full reviews with additional reviews charged at engineer's standard billing rate), record drawing preparation in AutoCAD format, and comprehensive testing and commissioning of all electrical systems prior to project completion.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-4-CS27004-26353310-HazMat Survey.pdf | ||
| 4-1-CS27004-26353310-Solicitation.pdf | ||
| 2-3-CS27004-26353310-Approved Specs.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE LOCATION PLAN
N
PROJECT ENGINEER
DESIGN TEAM
DFCM Project No. - 26353310
BRIGHAM CITY, UTAH
95 WEST GOLF COURSE ROAD SUITE 102
PHONE: (435) 787-1445SINE SOURCE ENGINEERING
LOGAN, UTAH 84321
FAX: (877) 207-3199
CONTACT: ERIC RASMUSSEN
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
E
Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______
Guildelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code
Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Existing Building Code
YearYear
APPLICABLE CODES
A. Occupancy and Group: ________ ________ ________ ________ ________
CODE ANALYSIS
N/A
N/A
N/A X X
DRAWING INDEX BRIDGERLAND TECHNICAL COLLEGE
BRIGHAM REGIONAL CENTER EXTERIOR DISCONNECTS AND ELECTRICAL
UPGRADES
B
PROJECT
BOUNDARIES
US 89
US 89
I-15
PERRY, UT
BRIGHAM CITY, UT
ARCHITECT
PHONE: (630)-656-7779SDG STUDIO ARCHITECTS, LLC
CONTACT: BRIAN DIXON
MECHANICAL ENGINEER
C-MECH ENGINEERING
CONTACT: MARTY CARRILLO
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 8
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
BRIGHAM
REGIONAL
CENTER
EXTERIOR DISCONNECTS
& ELECTRICAL
UPGRADES
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 7/
1/
T
:\J O
BS
\2
B
R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R S
ER
VI
C E
U
PG
R
AD
E\
4A B
R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R S
ER
VI
C E
U
PG
R
AD
E R
ED
ES
IG
N
\0
D R
AW
IN
G S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U
R C
E
PR
O
JE
C T\
SH
EE
TS
\E
E0
C O
VE
R
S H
EE
T.
D W
G
MJR
#26353310
LA
ST
S
AV
ED
: 0
Ju l 2
BRIDGERLAND TECHNOLOGY
COLLEGE
325 WEST 1100 SOUTH
BRIGHAM CITY, UTAH 84302
ECR
DFCM APPROVAL
JULY 1, 2026
PERMIT SET
SSE
7/1/2026
COVER SHEET
EE000
ELECTRICAL
EE000 COVER SHEET
EE001 ABBREVIATIONS, G.P.N., LEGEND &
SHEET INDEX
ES101 ELECTRICAL SITE PLAN
EP101 TECH COLLEGE POWER PLAN
EP102 TECH COLLEGE ELECTRICAL ONE-LINE
DIAGRAM
EP103 BEAUTY COLLEGE ELECTRICAL ONE-LINE
DIAGRAM
EA101 ELECTRICAL ROOM ARCHITECTURAL
DETAILS
ME001 MECHANICAL GENERAL INFORMATION
MH111 MECHANICAL AND MECHANICAL DEMO
PLANS
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
THOMAS PETERSON
07/09/2026
SHEET INDEX
Sheet Number Sheet Title
EE000 COVER SHEET
EE001 ABBREVIATIONS, G.P.N., LEGEND & SHEET INDEX
ES101 ELECTRICAL SITE PLAN
EP101 TECH COLLEGE POWER PLAN
EP102 TECH COLLEGE ELECTRICAL ONE-LINE DIAGRAM
EP103 BEAUTY COLLEGE ELECTRICAL ONE-LINE DIAGRAM
EA101 ELECTRICAL ROOM ARCHITECTURAL DETAILS
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 8
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
BRIGHAM
REGIONAL
CENTER
EXTERIOR DISCONNECTS
& ELECTRICAL
UPGRADES
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 4/
/2
T:
\J
O
BS
\2
B R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R
S
ER
VI
C
E U
PG
R
AD
E\
4A
B R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R
S
ER
VI
C
E U
PG
R
AD
E
R
ED
ES
IG
N \0
D
R
AW
IN
G
S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U R
C E
PR
O
JE
C
T\
SH
EE
TS
\E E0
A
BB
R
EV
IA
TI
O
N S, G .P
.N
LE
G
EN
D
S
H
EE
T
IN
D
EX
.D W
G
MJR
#26353310
LA
ST
S
AV
ED
: 2
Ap r 2
BRIDGERLAND TECHNOLOGY
COLLEGE
325 WEST 1100 SOUTH
BRIGHAM CITY, UTAH 84302
ECR
DFCM APPROVAL
JULY 1, 2026
PERMIT SET
SSE
7/1/2026
ELEC
ELEV
EMER, EM
EMT
EOLR
EQUIP
EX, EXIST
FBO
FCU
FF
FIXT
FLEX
FLUOR
ELECTRICAL
ELEVATOR
EMERGENCY
ELECTRICAL METALLIC TUBING
END OF LINE RESISTOR
EQUIPMENT
EXISTING
FURNISHED BY OTHERS
FAN COIL UNIT
FINISHED FLOOR
FIXTURE
FLEXIBLE METALLIC CONDUIT (STEEL)
FLUORESCENT
MAX
MCB
MECH
MFR
MIN
MLO
MTD
NEC
NECA
NEMA
N, NEUT
NFC
NC
MAXIMUM
MAIN CIRCUIT BREAKER
MECHANICAL
MANUFACTURER
MINIMUM
MAIN LUGS ONLY
MOUNTED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEUTRAL
NATIONAL FIRE CODE
NORMALLY CLOSED
SCHED
SECT
SP
SN
SPEC
SW
SWBD
SWGR
SYS
TEMP
TELE
TWP
TWSP
SCHEDULE
SECTION
SINGLE POLE
SOLID NEUTRAL
SPECIFICATION
SWITCH
SWITCHBOARD
SWITCH GEAR
SYSTEM
TEMPORARY
TELEPHONE
TWISTED PAIR
TWISTED SHEILDED PAIR
A
AF
AFF
AFG
AFI
AIC
AL
ARCH
AS
AWG
BLDG
BKBD
C
AMPERE
AMP FUSE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ARC-FAULT CIRCUIT-INTERRUPTER
AMPERE INTERRUPTING CAPACITY
ALUMINUM
ARCHITECT(URAL)
AMP SWITCH
AMERICAN WIRE GAUGE
BUILDING
BACKBOARD
CONDUIT
FT
GFI
G, GND
HP
HVAC
IG
IMC
IN
ISC
JB, J-BOX
KCMIL
KVA
KW
LTG
FEET OR FOOT
GROUND FAULT INTERRUPTER
GROUND
HORSEPOWER
HEATING, VENTILATING & AIR CONDITIONING
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
INCH(ES)
SHORT CIRCUIT AMPERES, KA
JUNCTION BOX
THOUSAND CIRCULAR MILS
KILOVOLT AMPERE
KILOWATT
LIGHTING
NIC
NL
NO
NTS
OCP
P
PH
PNL
PWR
QTY
RECEP
REQ'D
RGSC
RM
NOT IN CONTRACT
NIGHT LITE
NORMALLY OPEN
NOT TO SCALE
OVERCURRENT PROTECTION
POLE
PHASE
PANEL
POWER
QUANTITY
RECEPTACLE
REQUIRED
RIGID GALVANIZED STEEL CONDUIT
ROOM
XFMR
T-STAT
TYP
UBC
UL
UMC
UNO
V
VA
W W/
WG
WP
TRANSFORMER
THERMOSTAT
TYPICAL
UNIFORM BUILDING CODE
UNDERWRITERS LABORATORY
UNIFORM MECHANICAL CODE
UNLESS NOTED OTHERWISE
VOLT OR VOLTAGE
VOLT AMPERE
WATT
WITH
WIRE GUARD
UL LISTED WEATHERPROOF, NEMA 3R or 4
CAB
CAT
C/B
CKT
CLG
CO
COMM
CONN
CU
DEMO
DISC
DN
DWG
EA
CABINET
CATALOG/CATEGORY
CIRCUIT BREAKER
CIRCUIT
CEILING
CONDUIT ONLY
COMMUNICATION
CONNECTION
COPPER
DEMOLITION/DEMOLISH
DISCONNECT
DOWN
DRAWING
EACH
ELECTRICAL ABBREVIATIONS
J
WP
m MOTOR PROTECTIVE THERMAL SWITCH
SIMPLEX OUTLET
DUPLEX OUTLET
DUPLEX OUTLET: GROUND FAULT INTERRUPTER
DUPLEX OUTLET: EMERGENCY SOURCE
DUPLEX OUTLET: WEATHERPROOF
DOUBLE DUPLEX OUTLET
DOUBLE DUPLEX OUTLET: GROUND FAULT INTERRUPTER
DOUBLE DUPLEX OUTLET: EMERGENCY GROUND FAULT
INTERRUPTER
SPECIAL OUTLET: SEE PANEL SCHEDULE
JUNCTION BOX
DISCONNECT, 22KAIC MINIMUM
OVERCURRENT PROTECTIVE DISCONNECT
COMBINATION STARTER/OVERCURRENT PROTECTIVE DISCONNECT
QUANTITY OF CONDUCTORS: SHORT LINES = PHASE /SWITCH LONG
LINES = NEUTRAL
HOME-RUN
DISTRIBUTION PANEL
PANELBOARD
DOUBLE DUPLEX OUTLET: EMERGENCY SOURCE
SSU MOTOR PROTECTIVE FUSED THERMAL SWITCH
XA
YP
FEEDER SIZE (REFER TO CONDUIT AND CONDUCTOR SCHEDULE
UNLESS OTHERWISE NOTED)
GENERATOR ANNUNCIATOR
A
XA
YP
x-y
BREAKER: "x" = BREAKER AMPERAGE "y" = QUANTITY OF POLES
BRANCH PANEL
GROUND
CT AND METER
DIRECT METER
TRANSFORMER
GENERATOR
ATS ANNUNCIATOR
TRANSFER SWITCH (AUTOMATIC UNLESS OTHERWISE NOTED)
SURGE PROTECTIVE DEVICE
DISCONNECT SWITCH: "x" = SWITCH AMPERAGE "y" = QUANTITY OF
POLES
FUSE; "x" = FUSE TYPE; "y" = FUSE AMPERAGE;
CL= CURRENT LIMITING
MOTOR; hp = MOTOR HORSEPOWERhp
BRANCH PANEL WITH MAIN BREAKER
BRANCH PANEL WITH SUBFEED BREAKER
x
POWER AND DISTRIBUTION
BRANCH CIRCUITING
ELECTRICAL LEGEND
ONE-LINE
M
M
G
SIMPLEX OUTLET: GROUND FAULT INTERRUPTER
G
METER/METER SOCKET
DETAIL CALL-OUT; TOP "X" REFERS TO DETAIL NUMBER & BOTTOM
"XXX" REFERS TO SHEET NUMBER
ANNOTATIONS
XXX
X
GENERAL WALL-MOUNTED BOX HEIGHT DETAIL
BAR STRAPS
+XX = XX" = TOP OF BOX
XX = XX" = MIDDLE OF BOX
-XX = XX" = BOTTOM OF BOX
SITE ELECTRICAL
3-PHASE OVERHEAD PRIMARY POWER : EXISTING(E)3ØOP
3-PHASE UNDERGROUND PRIMARY POWER : EXISTING(E)3ØUP
3-PHASE UNDERGROUND PRIMARY POWER : ABANDONED(A)3ØUP
3-PHASE UNDERGROUND SECONDARY POWER : EXISTING(E)3ØUS
3ØUF 3-PHASE UNDERGROUND FEEDER
3ØOF 3-PHASE OVERHEAD FEEDER
3-PHASE UNDERGROUND SECONDARY POWER: DEMO(D)3ØUS
3ØUS 3-PHASE UNDERGROUND SECONDARY POWER
3ØUP 3-PHASE UNDERGROUND PRIMARY POWER
CL
1. ALL ELECTRICAL INSTALLATIONS TO CONFORM TO THE LATEST NEC AND LOCAL CODES.
2. REVIEW THE STATE DESIGN REQUIREMENTS MANUAL PRIOR TO BID. NOTIFY ENGINEER OF CONFLICTS BETWEEN
STATE REQUIREMENTS AND THESE DOCUMENTS PRIOR TO BID.
3. ELECTRICAL CONTRACTOR SHALL CONTACT POWER COMPANY WITHIN THE FIRST WEEK OF THE START OF CONSTRUCTION AND NOTIFY THEM OF THE PROBABLE DATE WHEN THE NEW ELECTRICAL SERVICE CONNECTION
WILL BE NEEDED.
4. CONTRACTOR SHALL LOCATE AND INSTALL TRANSFORMER PAD PER POWER COMPANY SPECIFICATIONS. VERIFY PROPER CLEARANCES FROM BUILDING AND OTHER EQUIPMENT BEFORE INSTALLATION. THE LOCATION OF THE
TRANSFORMER SHOWN ON THE PLANS IS AN APPROXIMATE LOCATION.
5. SUBMITTALS FOR EACH SYSTEM WILL BE REVIEWED BY ENGINEER UP TO TWO TIMES--ONE FULL SUBMITTAL FOR OVERALL COMPLIANCE AND ONE RESUBMITTAL. ADDITIONAL REVIEWS WILL BE CHARGED TO CONTRACTOR AT
ENGINEER'S STANDARD BILLING RATE.
6. SUBMITTALS TO ENGINEER SHALL INCLUDE ALL SPECIFIED SYSTEMS IN FIRST SUBMITTAL. PARTIAL SUBMITTALS WILL BE RETURNED TO CONTRACTOR AS INCOMPLETE AND WILL BE CONSIDERED ONE OF TWO INCLUDED
SUBMITTAL REVIEWS.
7. THE CLARITY OF RECORD DRAWING CHANGES MADE BY THE CONTRACTOR SHALL BE EQUAL TO THE ORIGINAL DRAWINGS AS JUDGED BY THE ARCHITECT OR THE RECORD SET WILL BE RETURNED TO THE CONTRACTOR FOR
CLARIFICATION.
8. “RECORD” OR “AS-BUILT” DRAWINGS SHALL BE FURNISHED BY THE CONTRACTOR AT JOB COMPLETION, THE CONTRACTOR SHALL BE REQUIRED TO FURNISH A COMPLETE SET OF “BLUE-PRINT READY” AUTOCAD ELECTRICAL DRAWINGS FOR ALL CONTRACTOR GENERATED CHANGES FROM THE DRAWINGS OF A CLARITY EQUAL TO THE ORIGINAL DRAWINGS AS JUDGED BY THE ENGINEER. CONTACT ENGINEER FOR REPRODUCIBLE ORIGINAL MEDIA.
PROVIDE DRAWINGS IN AUTOCAD FORMAT.
9. EMT IS NOT ALLOWED OUT OF DOORS.
10. MOUNTING HEIGHT OF GENERAL PURPOSE OUTLETS AND SWITCHES SHALL BE 16” TO BOTTOM AND 48” TO TOP
RESPECTIVELY UNLESS OTHERWISE NOTED.
11. ALL PARALLEL CONDUCTORS TO BE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 310.4. WIRE IS TO BE LAID ON A
FLAT SURFACE FOR MEASUREMENT. USE TORQUE WRENCH ON TERMINATIONS.
12. A GFI OUTLET SHALL BE INSTALLED AT EACH LOCATION DESIGNATED BY “GFI” ON THE DRAWINGS. DOWNSTREAM
PROTECTION BY A GFI OUTLET UPSTREAM IS NOT ALLOWED.
13. FIELD VERIFY CONDITIONS FOR NEW WIRING. SURFACE RACEWAYS OUTSIDE ELECTRICAL ROOM MUST RECEIVE PRIOR APPROVAL FROM THE ARCHITECT BEFORE BID AND MUST BE PAINTED TO MATCH THE SURFACE ON WHICH
THEY ARE MOUNTED. STRAP WIRE MOLD EVERY FOUR FEET.
14. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO FIELD VERIFY ALL PANEL CLEARANCES PER NEC 110.26
AND NOTIFY ELECTRICAL ENGINEER OF CONFLICTS.
15. CIRCUIT WIRE SIZES MUST, AT MINIMUM, MATCH BRANCH CIRCUIT BREAKERS PER NEC. VERIFY WITH PANEL
SCHEDULES BEFORE PULLING WIRE.
16. ALL ELECTRICAL EQUIPMENT SHALL BE LOCATED SO AS NOT TO INTERFERE WITH WOOD TRIM AND MOLDINGS.
17. THE ELECTRICAL CONTRACTOR SHALL RUN RACEWAYS IN A NEAT AND WORKMANLIKE MANNER.
18. ALL PATCH, REPAIR, REPAINT AND COVER UP REQUIRED AS A RESULT OF ELECTRICAL WORK IS TO BE THE RESPONSIBILITY OF THE TRADE CONTRACTOR, BUT ACTUAL WORK IS TO BE PERFORMED BY QUALIFIED PERSONNEL.
19. REMOVE ALL UNUSED CONDUITS AND CIRCUITS AS THEY ARE IDENTIFIED AS UNUSED OR ABANDONED.
20. DO NOT SCALE FLOOR PLANS. FIELD VERIFY CONDITIONS FOR ACCURATE DIMENSIONS AND FLOOR PLANS.
21. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO FIELD VERIFY ALL PANEL CLEARANCES PER NEC 110.26
22. PANEL INDEXES SHALL INCLUDE ALL PERTINENT INFORMATION ON THE PANEL SCHEDULES INCLUDING INFORMATION ON LIGHTS AND OUTLETS. DO NOT SIMPLY COPY THE CIRCUIT DESCRIPTION COLUMN. INDEXES TO BE
TYPEWRITTEN.
23. BEFORE RUNNING CONDUITS, PLACING OUTLETS OR ORDERING EQUIPMENT, THE CONTRACTOR SHALL REVIEW THE SPECIFICATIONS AND SHOP DRAWINGS OF THE EQUIPMENT SERVED BY THE CONDUIT, OUTLETS, AND/OR
EQUIPMENT.
24. ELECTRICAL CONTRACTOR SHALL INSTALL A PULL STRING IN ALL UNUSED POWER AND LIGHTING CONDUITS.
25. DISCONNECT SWITCHES ARE SHOWN IN APPROXIMATE LOCATIONS ONLY. CONTRACTOR SHALL FIELD VERIFY LOCATION OF ALL ELECTRICAL SWITCHES AND MOTOR CONTROL FOR PROPER CODE CLEARANCES. NOTIFY ARCHITECT IMMEDIATELY OF ANY CONFLICTS WITH OTHER TRADES REGARDING PROPER EQUIPMENT CLEARANCES.
26. ALL OUTLETS MUST BE MOUNTED FLUSH WITH THE COVER PLATE AND SECURED FIRMLY TO THE OUTLET BOX.
27. IDENTIFY ALL EMERGENCY OUTLET COVER PLATES WITH THE PANEL AND CIRCUIT NUMBER.
28. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR, PULLED INTO THE CONDUIT WITH THE PHASE CONDUCTOR, IN
ALL SERVICE, FEEDER, AND BRANCH CIRCUITS.
29. PROVIDE A NEUTRAL CONDUCTOR FOR EACH BREAKER TRIP HANDLE. NEUTRALS SHALL NOT BE SHARED BETWEEN
BRANCH CIRCUITS.
30. ALL CIRCUITS TO BE MINIMUM #12 CU IN MINIMUM 3/4” CONDUIT UNLESS OTHERWISE NOTED.
31. MC CABLE IS NOT AN APPROVED ALTERNATE TO CONDUCTORS IN CONDUIT.
32. WHERE THERE ARE CONFLICTS IN THE DRAWINGS AND/OR SPECIFICATIONS THE CONTRACTOR SHALL NOTIFY THE ENGINEER PRIOR TO BID. WHERE NO NOTIFICATION IS GIVEN THE MORE STRINGENT INTERPRETATION (GENERALLY
INTERPRETED TO BE THE MORE COSTLY) WILL BE ENFORCED.
33. ALL PANEL AND SWITCHBOARD SHUTDOWNS SHALL BE COORDINATED IN ADVANCE WITH OWNER.
34. SHUTDOWNS SHALL BE DONE DURING OWNER'S NON-BUSINESS HOURS, GENERALLY CONSIDERED TO BE NIGHTS, WEEKENDS AND HOLIDAYS. POWER SHALL BE RESTORED TO AFFECTED AREAS PRIOR TO OWNER'S NEXT
SCHEDULED USE OF AREA.
35. CONTRACTOR SHALL IMPLEMENT METHODS TO MINIMIZE ALL SHUTDOWNS (SERVICE, FEEDERS & CIRCUITS)
DURATIONS.
36. CONTRACTOR SHALL NOTIFY OWNER A MINIMUM OF SEVEN DAYS PRIOR TO SHUTDOWN.
GENERAL PROJECT NOTES
ABBREVIATIONS, G.P.N
LEGEND & SHEET INDEX
EE001
Scale: N.T.S.B CONDUIT RISER DETAIL
Scale: N.T.S.A BOLLARD DETAIL
DETAIL KEYED NOTES
1. DO NOT SET RIGID COUPLINGS FLUSH WITH FINISH FLOOR. LOCATE MINIMUM OF 12" ABOVE GRADE IF NEEDED.
2. PROVIDE STEEL PLATE WITH SAME DIMENSIONS AS PANEL BOTTOM PLATE. PUNCH PLATE PER CONDUITS ENTERING PANEL TO
STRAIGHTEN/ORGANIZE CONDUITS PRIOR TO FINAL RISE INTO PANEL.
3. TRANSITION TO WRAPPED RIGID CONDUIT PRIOR TO RISING ABOVE FLOOR AS SPECIFIED.
PVC PVC
TYPICAL PANEL
STEEL PLATE
RIGID COUPLING
RIGID ELBOW, WRAPPED
CONCRETE FLOOR LEVEL
TYPICAL WRAPPED
RIGID RISER
STEEL CHANNEL SUPPORT(S)
RIGID RIGID
HIGH REFLECTIVE TAPE PER DFCM STANDARDS
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
1. EXISTING ELECTRICAL SERVICES, EQUIPMENT, AND UNDERGROUND LINES TO REMAIN.
PROTECT EQUIPMENT DURING CONSTRUCTION.
2. LOCATE NEW TECH COLLEGE MDP IN UPSTAIRS ELECTRICAL ROOM. SEE EP101.
3. PROVIDE NEW CT METER, CT ENCLOSURE, AND MAIN SERVICE DISCONNECT. SEE
ENLARGED VIEWS FOR ADDITIONAL INFORMATION.
SHEET KEYED NOTES
1. EXISTING ITEMS TO BE REMOVED ARE INDICATED AS BOLD/DASHED. ITEMS TO REMAIN
ARE SHOWN AS LIGHT/SOLID.
2. CIRCUIT ROUTING IS SCHEMATIC UNLESS OTHERWISE NOTED.
3. PANEL LOCATIONS INDICATED ARE APPROXIMATE. FIELD VERIFY EXACT LOCATIONS.
4. COMPLY WITH POWER UTILITY'S REQUIREMENTS FOR ALL UTILITY RELATED
INSTALLATIONS. REVIEW CURRENT UTILITY STANDARDS MANUAL PRIOR TO BID. NOTIFY
ENGINEER OF CONFLICTS PRIOR TO BID.
5. UTILITY DETAILS SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL REFER TO LATEST
UTILITY STANDARDS FOR ALL UTILITY INSTALLATIONS.
GENERAL SHEET NOTES
TO
UPSTAIRS TO
UPSTAIRS
TO
DOWN
STAIRS
WET
LAB
BREAK
ROOM
LOCKER
ROOM
OFFICE
OFFICEOFFICE
STORAGEOFFICECONFERENCE
ROOM
STORAGE
OFFICE OFFICEOFFICE
NAIL
LAB
(E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP (E)3ØOP
UT
M
MM
M
MM
EDP
GEN
SERVICE
DISCONNECTS
(E )3Ø
US
(E )3Ø
US
(E )3Ø
US UT
M M
SERVICE
DISCONNECTS
EP103
A,B
(E)3ØUS
(E)3ØUS
UT
NEW
TECH COLLEGE
MDP
EP102
A,B
(E)3ØUP
(E)3ØUP
M
NEW CT METER,
CT ENCLOSURE,
& DISCONNECT
1 M M
NEW CT METER
& MAIN
DISCONNECT
M
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 8
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
BRIGHAM
REGIONAL
CENTER
EXTERIOR DISCONNECTS
& ELECTRICAL
UPGRADES
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 7/
1/
T
:\J O
BS
\2
B
R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R S
ER
VI
C E
U
PG
R
AD
E\
4A B
R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R S
ER
VI
C E
U
PG
R
AD
E R
ED
ES
IG
N
\0
D R
AW
IN
G S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U
R C
E
PR
O
JE
C T\
SH
EE
TS
\E
S1
E
LE
C
TR
IC
AL
S
IT
E
PL
AN
.D
W G
MJR
#26353310
LA
ST
S
AV
ED
: 0
Ju l 2
BRIDGERLAND TECHNOLOGY
COLLEGE
325 WEST 1100 SOUTH
BRIGHAM CITY, UTAH 84302
ECR
DFCM APPROVAL
JULY 1, 2026
PERMIT SET
SSE
7/1/2026
ES101
ELECTRICAL SITE PLAN
Scale: N.T.S.1
N
W E
ELECTRICAL SITE PLAN
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
1. DEMO EXISTING SWITCHBOARD "MSB" AND DISCONNECT "EMD1" AFTER SWITCH OVER TO
NEW SERVICE.
2. EXISTING PANEL TO REMAIN. RE-FEED FROM NEW DISTRIBUTION.
3. EXISTING ATS TO REMAIN. RE-FEED FROM NEW DISTRIBUTION.
4. RELOCATE JUNCTION BOX AND CONDUIT SERVING LIGHT FIXTURES TO ALLOW
INSTALLATION OF NEW DUCT.
5. SEE SHEET EA101 FOR CONVERTING ELECTRICAL CLOSEST INTO STANDARD CLOSET.
6. SEE SHEET EA101 FOR UPSTAIRS ELECTRICAL ROOM IMPROVEMENTS.
7. PROVIDE NEW PANIC HARDWARE ON EXISTING DOOR PER SHEET EA101.
8. RELOCATE EXISTING DUCT TO MAINTAIN WORKING CLEARANCES OVER PANELS. SEE
SHEET ME001 AND MH111.
9. PROVIDE NEW WALL OCCUPANCY SENSOR.
10. RELOCATE EXISTING LIGHT FIXTURE TO NEW LOCATION AND REFEED.
11. PROVIDE NEW CIRCUIT FROM PANEL "CF". INCLUDE NEW 20 AMP BREAKER IN EXISTING
PANEL, 3/4" CONDUIT, AND (3)#12THHN CONDUCTORS.
12. REMOVE EQUIPMENT AS NEEDED FOR CONSTRUCTION ABOVE GRID AND RE-INSTALL
PRIOR TO START OF OWNER'S NEXT REGULARLY SCHEDULED WORKING DAY.
13. EXISTING DEVICES CONNECTED TO THIS EMERGENCY OUTLET SHALL REMAIN
OPERATIONAL DURING ALL OUTAGES. PROVIDE A MINIMUM 7.5KW 120/240 1 PHASE
TEMPORARY INVERTER GENERATOR AND SUFFICIENT HEAVY DUTY CORDS (MINIMUM #10
THHN CONDUCTORS) TO KEEP EQUIPMENT POWERED DURING OUTAGES.
14. PROVIDE SURFACE MOUNTED OUTLET WITH HEAVY DUTY, METALLIC, WEATHER PROOF
IN-USE, LOCKABLE COVER.
15. PROVIDE FREE STANDING RACK PER DETAIL C/EP102.
1. MAINTAIN CIRCUIT CONTINUITY FOR DEVICES DOWNSTREAM OF ITEMS TO BE REMOVED.
2. EXISTING DRAWINGS ARE NOT AVAILABLE FOR UPSTAIRS AREA. APPROXIMATE OVERALL
AREA INDICATED.
GENERAL SHEET NOTES
SHEET KEYED NOTES
TO
UPSTAIRS
"MSB"
"EMD1"
DEMO MDP
& EMD1
EP101
2 5
M
WPIU
FROM
MSB
CLOSET
NEW CT METER,
CT ENCLOSURE,
AND DISCONNECT
EP101
A
TO
DOWN
STAIRS
RDB
PANEL KPANEL A
PANEL CF
PANEL WPTECH
PANEL "E"
TECH
ATS
A
A T S
"MDP"
J
J 4 J
TO NEW
SERVICE
OUTLET
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 8
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
BRIGHAM
REGIONAL
CENTER
EXTERIOR DISCONNECTS
& ELECTRICAL
UPGRADES
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 7/
1/
T
:\J O
BS
\2
B
R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R S
ER
VI
C E
U
PG
R
AD
E\
4A B
R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R S
ER
VI
C E
U
PG
R
AD
E R
ED
ES
IG
N
\0
D R
AW
IN
G S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U
R C
E
PR
O
JE
C T\
SH
EE
TS
\E
P1
T
EC
H C
O
LL
EG
E
PO
W
ER
P
LA
N
.D W
G
MJR
#26353310
LA
ST
S
AV
ED
: 0
Ju l 2
BRIDGERLAND TECHNOLOGY
COLLEGE
325 WEST 1100 SOUTH
BRIGHAM CITY, UTAH 84302
ECR
DFCM APPROVAL
JULY 1, 2026
PERMIT SET
SSE
7/1/2026
TECH COLLEGE POWER
PLAN
EP101
Scale: 1/16"=1'-0"1 N
WE
TECH COLLEGE POWER PLAN: MAIN LEVEL - OVERALL
Scale: 1/4"=1'-0"2 TECH COLLEGE POWER PLAN: UPSTAIRS - ENLARGED NEW
Scale: N.T.SA ENLARGED MSB ROOM: NEW CLOSET
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
1. PRIMARY AND SECONDARY CONDUIT, TRENCHING, BACKFILL AND SECONDARY
CONDUCTORS BY CONTRACTOR. PRIMARY CONDUCTORS BY UTILITY. SEE UTILITY DETAIL
E4 ON SHEET ES101.
2. CUT, PATCH, AND REPLACE ASPHALT FOR NEW POWER CONDUIT INSTALLATION..
3. PROVIDE NEW CT METER AND ENCLOSURE PER UTILITY DETAIL "E19" ON SHEET ES101.
4. LOCATE MDP IN UPSTAIRS ELECTRICAL ROOM. SEE EP101.
5. EXISTING UTILITY TRANSFORMER IS TO REMAIN.
6. EXISTING PANELS AND EQUIPMENT TO REMAIN OPERATIONAL UNTIL SWITCHOVER TO NEW
SERVICE.
7. REFEED EXISTING PANELS AND ATS FROM NEW MDP ONCE NEW SERVICE IS OPERATIONAL.
8. AFTER SWITCHOVER TO NEW SERVICE IS COMPLETE, DEMO SWITCHBOARD MSB, EM
DISCONNECT "EMD1", EXISTING CT METER, AND PANEL FEEDERS.
9. CORE DRILL INTO VAULT. COORDINATE BUILDING SHUTDOWN AS NEEDED.
10. RECONNECT TO EXISTING GROUNDING ELECTRODES WHERE ACCESSIBLE. PROVIDE
(2)ADDITIONAL GROUND RODS IF UFER IS NOT ACCESSIBLE.
11. OCPD SUPPLIER SHALL PROVIDE BREAKER COORDINATION TO COMPLY WITH NEC 700.32
FOR EMERGENCY DISTRIBUTION.
12. PROVIDE FREE STANDING RACK PER DETAIL C/EP102.
13. PROVIDE RIGID METALLIC CONDUIT RISER ON OUTSIDE OF BUILDING TO ENTER BUILDING
ABOVE INTERIOR DROP CEILING.
14. ALTERNATE PARALLEL CONDUCTOR CONFIGURATIONS ARE ALLOWED WITH ENGINEER'S
PRIOR APPROVAL.
SHEET KEYED NOTES
1. COMPLY WITH POWER UTILITY'S REQUIREMENTS FOR ALL UTILITY RELATED
INSTALLATIONS. REVIEW CURRENT UTILITY STANDARDS MANUAL PRIOR TO BID. NOTIFY
ENGINEER OF CONFLICTS PRIOR TO BID.
2. AIC RATINGS SHOWN INDICATE MINIMUM REQUIRED VALUES. SCCR RATINGS ARE TO
MATCH OR EXCEED AIC RATINGS.
3. FIELD MARK SERVICE EQUIPMENT WITH AVAILABLE FAULT CURRENT AND CALCULATION
DATE PER NEC 110.24(A).
4. RUN PORTIONS OF GROUNDING ELECTRODE CONDUCTORS NOT CONCEALED IN BUILDING
FINISHES IN CONDUIT.
5. ALL CONDUCTORS ARE CONSIDERED TO BE COPPER UNLESS SPECIFICALLY NOTED
OTHERWISE.
6. COORDINATE SHUTDOWNS WITH OWNER IN ADVANCE. DO NOT PROCEED WITH
SHUTDOWNS WITHOUT OWNER'S WRITTEN APPROVAL.
7. ALL SHUTDOWNS SHALL BE DONE DURING OWNER'S NON-WORKING HOURS, GENERALLY
CONSIDERED TO BE NIGHTS AND HOLIDAYS. POWER SHALL BE RESTORED TO AFFECTED
AREAS PRIOR TO NEXT REGULARLY SCHEDULED WORKING HOURS.
8. A FULL SIZE EQUIPMENT GROUNDING CONDUCTOR SIZED FOR THE OVERCURRENT
PROTECTIVE DEVICE PROTECTING THE CIRCUIT IS REQUIRED IN EACH RACEWAY OR CABLE
FOR PARALLELED CIRCUITS.
9. CONTRACTOR SHALL DOCUMENT FEEDER CONDUCTOR LENGTH ON FIELD REDLINE SET.
10. CONTRACTOR SHALL IDENTIFY EXISTING PHASE ROTATION DIRECTION OF ALL AFFECTED
PANELS PRIOR TO SHUTDOWN. CONTRACTOR SHALL VERIFY AFTER SWITCHOVER TO NEW
SERVICE THAT ALL PANELS MAINTAIN SAME PHASE ROTATION DIRECTION PRIOR TO
ENERGIZING BRANCH CIRCUITS.
GENERAL SHEET NOTES
2,447542
2,44/075039507532
2,445K42
2,450034"7605K32
2,444K42
2,440033.5"6704K32
2,4,843542
2,42/04/01/035036203532
2,44
3"
3K42
2,4,830035703K32
2,4,842542
2,43/0125035102532
2,444042
2,41/02/024/034604032
2,442.5"3042
2,43/034003032 1/03 22"2
2,447541
2,42/02/0275034757531
2,445K41
2,450034"3805K31
244K41
21/040033.5"3354K31
2,843541
21/0335033103531
3"
3K41
2,830032853K31
2,842541 225032552531
244041 22144/032304031
2.5"
23/032003031
242041 242/031752031 241041
21/032"1501031
2,84141
26613130131
241.5"241 222395231
24341 23331
233285321
24441 23431
2484270421
241.25"641
23631
266255621
24841
23831
28821"40821 24041 23031
2101010230021
2,341241
2,331231
2812121223/4"1201221
P/NCU
SE (NOTE 4)IGGSIZEQTYSIZEQTY
NOTESCONDUCTOR (NOTE 1,6,7)CONDUITAMPSYM
CONDUCTOR AND CONDUIT SCHEDULE
2 3"
CONDUIT AND CONDUCTOR SCHEDULE NOTES
1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH
MODIFICATIONS AS NOTED IN NOTE #5. ALL CONDUCTORS SHOWN ARE THWN
FOR CU OR THWN OR XHHW FOR AL UNLESS OTHERWISE NOTED.
2. PROVIDE EQUIPMENT GROUNDING CONDUCTORS PER NEC TABLE 250-122
WHEN CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING
SHOWN IN TABLE.
3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING
COMPUTERS.
4. GROUND (G) CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE
CONDUCTORS.
5. SYMBOL SUBSCRIPTS:
· "IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)
SCHEDULED ALONG WITH THE GROUND OF EQUIPMENT GROUND
CONDUCTOR.
· "SE": SUBSTITUTE "SE" CONDUCTOR FOR "G" CONDUCTOR SHOWN,
WHICH IS SIZED FOR THE GROUNDING OF THE SECONDARY OF
THE SEPARATELY DERIVED SYSTEM.
· "2N": INCLUDE TWO NEUTRAL CONDUCTORS, SIZED AS SCHEDULED
FOR PHASED AND NEUTRAL CONDUCTORS.
· "R": RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.
· "V(#)": PHASE AND NEUTRAL CONDUCTORS UPSIZED FOR VOLTAGE
DROP. UPSIZE GROUNDING CONDUCTOR(G) TO SIZE INDICATED
BY (#) PER NEC 250.122(B).
· "A": ALUMINUM CONDUCTORS ALLOWED FOR FEEDER INDICATED.
ALUMINUM CONDUCTORS ARE NOT TO BE USED FOR
CONNECTIONS TO MOTORS OR MOTOR DRIVEN EQUIPMENT.
6. A FULL SIZE GROUNDING CONDUCTOR (SE OR G AND/OR IG) SHALL BE
INSTALLED IN EACH RACEWAY OR CABLE FOR PARALLELED CIRCUITS.
7. GROUNDING CONDUCTORS (G, IG, AND SE) SHALL BE OF THE SAME
CONDUCTOR MATERIAL AS THE CORRESPONDING PHASE CONDUCTORS TO
KEEP TABLE CALCULATIONS IN 7 . ACCORDANCE WITH NEC REQUIREMENTS.
8. INCREASE CONDUIT TO NEXT LARGEST STANDARD CONDUIT SIZE WHEN IG IS
USED.
* -CONDUIT SIZED FOR COMPACT ALUMINUM CONDUCTORS. USE COPPER CONDUIT
SIZE FOR STANDARD SIZE CONDUCTORS
SUBSCRIPTS (SEE NOTE 5)XX
#### SCHEDULE NUMBER
CONDUCTOR MATERIALS1
S2
SIZE OF CONDUCTORS
QUANTITY OF PARALLEL RUNS
QUANTITY OF PHASE/
NEUTRAL CONDUCTORS
4K43 1005 3 3.5" 4 400 2/0 4/0 3/0 4
SWITCHBOARD "MSB"
1200A, 120/208V, 3Ø, 4W, 50K SCCR
PANEL "CF"PANEL "K" PANEL "WP"
200A 200A
3P
150A 200A
3P
225A 400A
3P
LABELED
"ROOF AC"
600A 600A
3P LABELED
PANEL 'G'
PANEL "A"
TECH COLLEGE AUTOMATIC
TRANSFER SWITCH
100A, 120/208V, 4-POLE, 12KAIC
TECH
POWER
"E" 7
100A 3P
100A 3P
100A, 120/280V, 3Ø
EM DISCONNECT
"EMD1" 50K SCCR
EXISTING
UTILITY POLE
BRIGHAM
CITY POWER
#D555FUSE 21
PANEL "MDP"
800A, 120/208V, 3Ø, 4W, 32KAIC
100A 3P
200A 3P
225A 3P
225A 3P
600A 3P m
MAIN DISCONNECT
800A, 120/208V, 3Ø, 4W,42KAIC
UTILITY APPROVED
CT ENCLOSURE
RODWATERSTEEL UFER
#2/0 CU #6 CU
800A
3P
GN
#2/0 CU
(D )3
ØU
S
RDB 8
EXISTING 500KVA
12470-120/208, 3Ø, 4W
XFMR "(E)UT4"5
CU
CU
CU
CU
CU
100A 3P
PANEL SB
CUSE EXISTING
VAULT
m 8
FROM
GENERATOR
ROD
#2/0 CU
#4 CU
CU
CUSE
225A 3P
(2)SPACES
60A 3P
150KA/PHASE
SPD
CL
(D)3ØUS
(D)3ØUS (D)3ØUS (D)3ØUS
(E)3ØUP (E)3ØUP (E)3ØUP (E)3ØUP
(E)3ØUP
(E)3ØUP
(E)3ØUP
EXISTING
XFMR M
8 NEW CT METER
CT ENCLOSURE
& DISCONNECT
M
6'
4'
2'
10'
PER EQUIP
PER EQUIP
6"
1. PROVIDE FREE-STANDING METAL CHANNEL RACK.
2. PROVIDE 6" DEEP CONCRETE BASE EXTENDING THE LENGTH OF THE RACK.
3. VERIFY DIMENSIONS WITH ACTUAL EQUIPMENT PRIOR TO CONSTRUCTING RACK.
4. PROVIDE VERTICAL SUPPORT AT CENTER OF RACK.
5. PROVIDE HORIZONTAL AND VERTICAL SUPPORTS AS REQUIRED BY EQUIPMENT.
6. PROVIDE 12"Øx2' DEEP BASES AT EACH VERTICAL POST.
7. EXTEND VERTICAL POSTS DOWN INTO GROUND PAST BOTTOMS OF CONCRETE SUPPORTS.
DETAIL KEYED NOTES
3" GALVANIZED
STEEL VERTICAL
POSTS (ENDS AND
CENTER)
UNI-STRUT
FRAMING
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 8
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
BRIGHAM
REGIONAL
CENTER
EXTERIOR DISCONNECTS
& ELECTRICAL
UPGRADES
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 7/
1/
T
:\J O
BS
\2
B
R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R S
ER
VI
C E
U
PG
R
AD
E\
4A B
R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R S
ER
VI
C E
U
PG
R
AD
E R
ED
ES
IG
N
\0
D R
AW
IN
G S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U
R C
E
PR
O
JE
C T\
SH
EE
TS
\E
P1
T
EC
H C
O
LL
EG
E
EL
EC
TR
IC
AL
O
N E-
LI
N
E D
IA
G
R
AM
.D W
G
MJR
#26353310
LA
ST
S
AV
ED
: 0
Ju l 2
BRIDGERLAND TECHNOLOGY
COLLEGE
325 WEST 1100 SOUTH
BRIGHAM CITY, UTAH 84302
ECR
DFCM APPROVAL
JULY 1, 2026
PERMIT SET
SSE
7/1/2026
TECH COLLEGE
ELECTRICAL ONE-LINE
DIAGRAM
EP102
Scale: N.T.S.1 TECH COLLEGE ELECTRICAL ONE-LINE DIAGRAM
UT
(E)3ØUP
(E)3ØUP
M
3ØOF
M
NEW CT METER,
CT ENCLOSURE,
& DISCONNECT
(D)3ØUS
(D)3ØUS
SEE
EP101
DEMO
TECH COLLEGE
MSB & EMD1
3ØUS
3ØUF
A SCALE: NO SCALE
TECH COLLEGE SERVICE: ENLARGED NEW
B SCALE: NO SCALE
TECH COLLEGE SERVICE: SIDE VIEW
C SCALE: NO SCALE
FREE STANDING RACK DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
THOMAS PETERSON
07/09/2026
./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG
1. EXISTING ELECTRICAL EQUIPMENT TO REMAIN. PROTECT EQUIPMENT
DURING CONSTRUCTION.
2. SECONDARY CONDUIT, TRENCHING, BACKFILL AND SECONDARY
CONDUCTORS BY CONTRACTOR. SEE UTILITY DETAIL E4 ON SHEET ES101.
3. CUT, PATCH & REPAIR OR TUNNEL UNDER EXISTING HARDSCAPE FOR NEW
CONDUIT INSTALLATION.
4. PROVIDE NEW UTILITY APPROVED CT METER AND ENCLOSURE PER UTILITY
DETAIL "E19" ON SHEET ES101. SUBMIT CT ENCLOSURE CUT SHEETS TO
UTILITY FOR APPROVAL PRIOR TO ORDERING.
5. EXISTING PANELS AND EQUIPMENT TO REMAIN OPERATIONAL UNTIL
SWITCHOVER TO NEW SERVICE IS OPERATIONAL.
6. REFEED EXISTING MDP FROM NEW SERVICE DISCONNECT.
7. INTERCEPT EXISTING SERVICE ENTRANCE CONDUIT AND RE-ROUTE CONDUIT
THROUGH NEW CT ENCLOSURE AND DISCONNECT. REPLACE EXISTING
SERVICE ENTRANCE CONDUCTORS WITH NEW CONDUCTORS COMPLETE
FROM TRANSFORMER TO MDP.
8. PROVIDE BOLLARDS IN FRONT OF EQUIPMENT.
9. DEMO EXISTING CT METER AFTER NEW SERVICE IS OPERATIONAL.
10. RECONNECT TO EXISTING GROUNDING ELECTRODES WHERE ACCESSIBLE.
PROVIDE (2)ADDITIONAL GROUND RODS INDICATED IF UFER IS NOT
ACCESSIBLE.
11. EXISTING BEAUTY COLLEGE MDP AND ALL DOWNSTREAM PANELS TO REMAIN.
12. MAINTAIN 36" CLEARANCE BETWEEN ELECTRICAL SERVICE AND EXISTING
GAS METER.
13. OCPD SUPPLIER SHALL PROVIDE BREAKER/FUSE COORDINATION TO COMPLY
WITH NEC 700.32 FOR EMERGENCY DISTRIBUTION.
SHEET KEYED NOTES
1. COMPLY WITH POWER UTILITY'S REQUIREMENTS FOR ALL UTILITY RELATED
INSTALLATIONS. REVIEW CURRENT UTILITY STANDARDS MANUAL PRIOR TO
BID. NOTIFY ENGINEER OF CONFLICTS PRIOR TO BID.
2. AIC RATINGS SHOWN INDICATE MINIMUM REQUIRED VALUES. SCCR RATINGS
ARE TO MATCH OR EXCEED AIC RATINGS.
3. FIELD MARK SERVICE EQUIPMENT WITH AVAILABLE FAULT CURRENT AND
CALCULATION DATE PER NEC 110.24(A).
4. RUN PORTIONS OF GROUNDING ELECTRODE CONDUCTORS NOT
CONCEALED IN BUILDING FINISHES IN CONDUIT.
5. ALL CONDUCTORS ARE CONSIDERED TO BE COPPER UNLESS SPECIFICALLY
NOTED OTHERWISE.
6. COORDINATE SHUTDOWNS WITH OWNER IN ADVANCE. DO NOT PROCEED
WITH SHUTDOWNS WITHOUT OWNER'S WRITTEN APPROVAL.
7. ALL SHUTDOWNS SHALL BE DONE DURING OWNER'S NON-WORKING HOURS,
GENERALLY CONSIDERED TO BE NIGHTS AND HOLIDAYS. POWER SHALL BE
RESTORED TO AFFECTED AREAS PRIOR TO NEXT REGULARLY SCHEDULED
WORKING HOURS.
8. AIC RATINGS SHOWN INDICATE MINIMUM REQUIRED VALUES. SCCR RATINGS
ARE TO MATCH OR EXCEED AIC RATINGS.
9. A FULL SIZE EQUIPMENT GROUNDING CONDUCTOR SIZED FOR THE
OVERCURRENT PROTECTIVE DEVICE PROTECTING THE CIRCUIT IS
REQUIRED IN EACH RACEWAY OR CABLE FOR PARALLELED CIRCUITS.
10. CONTRACTOR SHALL DOCUMENT FEEDER CONDUCTOR LENGTH ON FIELD
REDLINE SET.
11. CONTRACTOR SHALL MARK EXISTING ROTATION ON PANEL PRIOR TO
SWITCH OVER AND NEW SERVICE SHALL MAINTAIN SAME ROTATION.
GENERAL SHEET NOTES
2,447542
2,44/075039507532
2,445K42
2,450034"7605K32
2,444K42
2,440033.5"6704K32
2,4,843542
2,42/04/01/035036203532
2,44
3"
3K42
2,4,830035703K32
2,4,842542
2,43/0125035102532
2,444042
2,41/02/024/034604032
2,442.5"3042
2,43/034003032 1/03 22"2
2,447541
2,42/02/0275034757531
2,445K41
2,450034"3805K31
244K41
21/040033.5"3354K31
2,843541
21/0335033103531
3"
3K41
2,830032853K31
2,842541
225032552531
244041 22144/032304031
2.5"
23/032003031
242041 242/031752031
241041
21/032"1501031
2,84141
26613130131
241.5"241
222395231
24341
23331
233285321
24441 23431 2484270421
241.25"641
23631
266255621
24841
23831
28821"40821 24041
23031
2101010230021
2,341241
2,331231
2812121223/4"1201221
P/NCU
SE (NOTE 4)IGGSIZEQTYSIZEQTY
NOTESCONDUCTOR (NOTE 1,6,7)CONDUITAMPSYM
CONDUCTOR AND CONDUIT SCHEDULE
2 3"
CONDUIT AND CONDUCTOR SCHEDULE NOTES
1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH
MODIFICATIONS AS NOTED IN NOTE #5. ALL CONDUCTORS SHOWN ARE THWN
FOR CU OR THWN OR XHHW FOR AL UNLESS OTHERWISE NOTED.
2. PROVIDE EQUIPMENT GROUNDING CONDUCTORS PER NEC TABLE 250-122
WHEN CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING
SHOWN IN TABLE.
3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING
COMPUTERS.
4. GROUND (G) CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE
CONDUCTORS.
5. SYMBOL SUBSCRIPTS:
· "IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)
SCHEDULED ALONG WITH THE GROUND OF EQUIPMENT GROUND
CONDUCTOR.
· "SE": SUBSTITUTE "SE" CONDUCTOR FOR "G" CONDUCTOR SHOWN,
WHICH IS SIZED FOR THE GROUNDING OF THE SECONDARY OF
THE SEPARATELY DERIVED SYSTEM.
· "2N": INCLUDE TWO NEUTRAL CONDUCTORS, SIZED AS SCHEDULED
FOR PHASED AND NEUTRAL CONDUCTORS.
· "R": RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.
· "V(#)": PHASE AND NEUTRAL CONDUCTORS UPSIZED FOR VOLTAGE
DROP. UPSIZE GROUNDING CONDUCTOR(G) TO SIZE INDICATED
BY (#) PER NEC 250.122(B).
· "A": ALUMINUM CONDUCTORS ALLOWED FOR FEEDER INDICATED.
ALUMINUM CONDUCTORS ARE NOT TO BE USED FOR
CONNECTIONS TO MOTORS OR MOTOR DRIVEN EQUIPMENT.
6. A FULL SIZE GROUNDING CONDUCTOR (SE OR G AND/OR IG) SHALL BE
INSTALLED IN EACH RACEWAY OR CABLE FOR PARALLELED CIRCUITS.
7. GROUNDING CONDUCTORS (G, IG, AND SE) SHALL BE OF THE SAME
CONDUCTOR MATERIAL AS THE CORRESPONDING PHASE CONDUCTORS TO
KEEP TABLE CALCULATIONS IN 7 . ACCORDANCE WITH NEC REQUIREMENTS.
8. INCREASE CONDUIT TO NEXT LARGEST STANDARD CONDUIT SIZE WHEN IG IS
USED.
* -CONDUIT SIZED FOR COMPACT ALUMINUM CONDUCTORS. USE COPPER CONDUIT
SIZE FOR STANDARD SIZE CONDUCTORS
SUBSCRIPTS (SEE NOTE 5)XX
#### SCHEDULE NUMBER
CONDUCTOR MATERIALS1
S2
SIZE OF CONDUCTORS
QUANTITY OF PARALLEL RUNS
QUANTITY OF PHASE/
NEUTRAL CONDUCTORS
200A
225KVA
12470-120/208V, 3ɸ, 4W
XFMR "T-2"
EXISTING
UTILITY POLE
BRIGHAM
CITY POWER
#D55
FUSE 14.4
(D)3ØUS
(D)3ØUS
(D)3ØUS
PANEL "MDP"
600A, 120/208V, 3Ø, 4W, 42K SCCR
600A 3P
225A 3P
225A 3P
100A 3P
200A 3P
PANEL "D"
SECTION 1
PANEL "C"PANEL "B"PANEL "A"
DISCONNECT
400A 3P
GUTTER WITH TAPS
PANEL
"AUTOMATION"
PANEL
"HEAT
TAPE"
PANEL
"P2"
PANEL
"P1"
CT CAN
METER
#88517872
M
M
200A200A
M
CT METER
PANEL "D"
SECTION 2
CT METER
20A 2P
600A 3P
CU
M
UTILITY
APPROVED
CT METER
& ENCLOSURE
CU
3ØUS
(E)3ØUS
NEW SERVICE
DISCONNECT
600A, 120/208V, 3Ø
4W, 50KAIC
CUSE
GN
2/0 CU
1 1
RODWATERSTEEL UFER
#2/0 CU #6 CU
ROD
#2/0 CU
#4 CU
CL
60A 3P
BEAUTY
COLLEGE
EMERGENCY
PANEL "E"
60A 3P
SE
FROM
GENERATOR
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 8
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
BRIGHAM
REGIONAL
CENTER
EXTERIOR DISCONNECTS
& ELECTRICAL
UPGRADES
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 4/
/2
T:
\J
O
BS
\2
B R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R
S
ER
VI
C
E U
PG
R
AD
E\
4A
B R
IG
H
AM
R
EG
IO
N
AL
C
EN
TE
R
S
ER
VI
C
E U
PG
R
AD
E
R
ED
ES
IG
N \0
D
R
AW
IN
G
S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U R
C E
PR
O
JE
C
T\
SH
EE
TS
\E P1
B
EA
U
TY
C
O
LL
EG
E
EL
EC
TR
IC
AL
O
N E-
LI
N
E D
IA
G
R
AM
.D W
G
MJR
#26353310
LA
ST
S
AV
ED
: 2
Ap r 2
BRIDGERLAND TECHNOLOGY
COLLEGE
325 WEST 1100 SOUTH
BRIGHAM CITY, UTAH 84302
ECR
DFCM APPROVAL
JULY 1, 2026
PERMIT SET
SSE
7/1/2026
BEAUTY COLLEGE
ELECTRICAL ONE-LINE
DIAGRAM
EP103
Scale: N.T.S.1 BEAUTY COLLEGE ELECTRICAL ONE-LINE DIAGRAM
(E)3ØUS
UT
EXISTING
UTILITY
TRANSFORMER
(E)UT2
DEMO
EXISTING
METER
NEW CT METER
& ENCLOSURE
(E)3ØUS
(E)3ØUS
UT
EXISTING
UTILITY
TRANSFORMER
(E)UT2
M DEMO
EXISTING
METER
9M
(E)3ØUS
3 (D)3ØUS
M
NEW
DISCONNECT
8 8 8 M
TO
UPSTAIRS
WET LAB
EXISTING
COSMETOLOGY
MDP, PANELS A & B
NEW CT METER,
CT ENCLOSURE,
& DISCONNECT
1 1
B
B
B
A BEAUTY COLLEGE SERVICE: SIDE VIEW
SCALE: NO SCALEB BEAUTY COLLEGE SERVICE: ENLARGED
SCALE: NO SCALE
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
THOMAS PETERSON
07/09/2026
./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-OVERALL.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/2L1/Panel 2L1/Sub-Disconnect/DC1-FUSE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/1ML1/Panel 1ML1/1L3/1L3 Panel/1L3 NAMEPLATE.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 8
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
BRIGHAM
REGIONAL
CENTER
EXTERIOR DISCONNECTS
& ELECTRICAL
UPGRADES
LA
S
T S
AV
E
3/
/2
T:
\J O
B S
\2
B R
IG
H
A M
R E
G
IO
N A
L C
E N
TE
R
S E
R V
IC
E
U P
G R
A D
E \0
D
R
AW
IN
G
S \0
E
LE
C
TR
IC
A L\
S
IN
E S
O U
R C
E P
R O
JE
C
T\ E
LE
M
E N
TS
\2
4X
D
FC
M -T
B -G
E N
.D W
G
BWD
#26353310
LA
S
T S
AV
E
D :1
M ar
BRIDGERLAND TECHNOLOGY
COLLEGE
325 WEST 1100 SOUTH
BRIGHAM CITY, UTAH 84302
ECR
DFCM APPROVAL
7/1/2026
PERMIT SET
SSE
4/17/2026
SDG STUDIO
ARCHITECTS, LLC
Architectural Details
EA101
RDB
PANEL KPANEL A
PANEL CF
PANEL WP "MDP"
TECH
PANEL "E"
TE
CH
J-BOX
AT
S
(EXISTING FLOOR IS CONCRETE, NO CHANGE
NEEDED TO ACHIEVE 2 HOUR RATING)
PROVIDE NEW PANIC
HARDWARE AND
DOOR CLOSER ON
EXISTING DOOR
EXISTING MASONRY (CMU) WALL
CONTRACTOR TO PATCH ANY EXISTING
DRYWALL HOLES IN THIS ROOM
TO
UPSTAIRS
4' -0
/4
" V
IF
6'-2 3/4" VIF
NEW FURRED WALL
(2X4 STUDS @ 16" O.C. COVERED W/
7/16" OSB, AND FINISH LAYER OF
5/8" TYPE X GYPSUM BOARD)
DEMO/REPLACE EXISTING CEILING
GRID/CEILING TILES (2 ROWS OF
CEILING TILE) FOR CONDUIT
INSTALL
DEMO/REPLACE EXISTING CEILING
GRID/CEILING TILES (2 ROWS OF
CEILING TILE) FOR CONDUIT
INSTALL
DEMO/REPLACE EXISTING CEILING
GRID/CEILING TILES (4 ROWS OF
CEILING TILE) FOR CONDUIT
INSTALL
PROVIDE NEW MATCHING DROPPED
2X2 CEILING GRID/TILES IN CLOSET
(MATCH EXTERIOR ROOM CEILING
HEIGHT IF NO OBSTRUCTIONS).
MINIMUM CEILING HEIGHT: 7'-0".
INSTALL PER MANUFACTURER
GUIDELINES.
PATCH ANY EXISTING
DRYWALL HOLES
PROVIDE MATCHING
CARPET IN CLOSET
2 SECOND FLOOR PROPOSED PLAN 1/4" = 1'-0"
1 FIRST FLOOR REMODEL & PROPOSED PLAN 1/4" = 1'-0"
1. FIRST FLOOR CEILING REPLACEMENT: MATCH EXISTING CEILING GRID AND
CEILING TILE TYPE/COLOR. PROVIDE SPLAY WIRE TO STRUCTURE AT
FREQUENCY PER MANUFACTURER INSTALLATION GUIDELINES.
CEILING NOTES:
1. NEW WALL DIMENSIONS PROVIDED ARE FROM FACE OF STUD.
2. MODIFIED WALL DIMENSIONS (WHEN WALL IS REQUIRED TO BE STRIPPED TO
STUD), ARE FROM FACE OF STUD.
3. DIMENSIONS FROM EXISTING WALLS ARE TO FACE OF EXISTING FINISH.
4. EXISTING ROOM DIMENSIONS SHALL BE VERIFIED IN FIELD.
PLAN DIMENSIONS:
1. ALL GYPSUM TO BE INSTALLED TO LEVEL 4 SMOOTH FINISH.
GYPSUM WALLS/CEILINGS:
1. THE EXISTING FIRE SPRINKLER SYSTEM/FIRE ALARM SYSTEM SHALL BE
MODIFIED/ADDED TO, AND SUBMITTED AS A DEFERRED SUBMITTAL AND
APPROVED, PRIOR TO ANY RELATED INSTALLATION WORK OF THE SYSTEM.
2. THE FIRE SPRINKLER SYSTEM SHALL BE DESIGNED AND INSTALLED
ACCORDING TO THE NFPA-13.
3. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED ACCORDING
TO THE 2018 INTERNATIONAL FIRE CODE
FIRE SPRINKLER & FIRE ALARM DESIGN (DEFERRED SUBMITTAL):
1. "VIF" = VERIFY IN FIELD
NOMENCLATURE:
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
233713 DIFFUSERS, REGISTERS,
AND GRILLES
230700 HVAC INSULATION
230050 HVAC DESIGN CRITERIA
233300 AIR DUCT ACCESSORIES
233113 METAL DUCTS
SHEET OF 8
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
DESCRIPTIONMARK DATE
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
BRIGHAM
REGIONAL
CENTER
EXTERIOR DISCONNECTS
& ELECTRICAL
UPGRADES
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 4/
/2
C :\U
SE
R
S\
SA
BR
AR
O C
H A\
C -M
EC
H
E N
G
IN
EE
R
IN
G
, L
LC
\M
AR
TI
N
C
AR
R
IL
LO
- C -M
EC
H
P R
O
JE
C
TS
\2
6\
- B R
C E
LE
C
TR
IC
AL
R
O O
M (S
SE
)\3
C
AD
\2
BR
C E
LE
C
R M
M
EC
H
.D W
G
S.ROCHA
#26010
LA
ST
S
AV
ED
: 1
Ap r 2
BRIDGERLAND TECHNOLOGY
COLLEGE
325 WEST 1100 SOUTH
BRIGHAM CITY, UTAH 84302
M.CARILLO
JUN. 29, 2026
CD SET
C-MECH ENGINEER
PR
OF
ESS IONAL ENGINEER
STATE OF UTAH
MARTIN
THOMAS
CARRILLO
# 6136918-2202
06/29/2026
ME001
MECHANICAL GENERAL
INFORMATION
SHEET INDEX
SHEET NUMBER SHEET NAME
POSITIVE PRESSURE DUCT (SUPPLY) - UP
POSITIVE PRESSURE DUCT (SUPPLY) - DOWN
NEGATIVE PRESSURE DUCT (RETURN) - UP
NEGATIVE PRESSURE DUCT (RETURN) - DOWN
ROUND DUCT - UP
ROUND DUCT - DOWN
UNDER FLOOR DUCT
RECTANGULAR 90° WITH TURNING VANES
R=1.5W ROUND DUCT SIMILAR TO RECTANGULAR
FLAT OVAL DUCT WITH NET INSIDE DIMENSIONS IN INCHES
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
FIRE DAMPER IN DUCT, WITH ACCESS PANEL REQUIRED
ACCESS PANEL IN DUCT OR PLENUM
CEILING DIFFUSER WITH FLEXIBLE DUCT
CEILING RETURN AIR GRILLE WITH SOUND BOOT
FD
OR
20⌀
20/12 FO
RW
ABBREVIATIONS
AD ACCESS DOOR
AIR CONDITION(-ING, -ED) COND
APD AIR PRESSURE DROP
BD BALANCING DAMPER
BHP BRAKE HORSE POWER
BTU BRITISH THERMAL UNIT
BTU/H BTU/HOUR
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CLG COOLING
COMP COMPONENT
COND CONDENS(-ER, -ING, -ATION)
CV CONTROL VALVE
CW COLD WATER
DIA DIAMETER
DISCH DISCHARGE
DP DEPTH OR DEEP
DB DRY BULB TEMPERATURE
(E) EXISTING
EER ENERGY EFFICIENCY RATIO
EFF EFFICIENCY
EG ETHYLENE GLYCOL
ELEC ELECTRIC
ELEV ELEVATION
ENT ENTERING
EVAP EVAPORAT(-E, -ING, -ED, -OR)
EWT ENTERING WATER TEMP
EXT EXTERNAL
(F) FUTURE
F FAHRENHEIT
FC FLEXIBLE CONNECT(-OR, -ION)
FD FIRE DAMPER
FLA FULL LOAD AMPS
FPI FINS PER INCH
FPM FEET PER MINUTE
FPS FEET PER SECOND
FSD FIRE SMOKE DAMPER
FT FEET
GAL GALLON(-S)
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HD HEAD
HG MERCURY
HR HOUR
HT HEIGHT
HTG HEATING
HP HORSE POWER
HW HOT WATER
HX HERTZ (FREQUENCY)
ID INSIDE DIAMETER
IN INCH
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LG LENGTH
LH LATENT HEAT
LRA LOCKED ROTOR AMPS
LVG LEAVING
LWT LEAVING WATER
MAX TEMPERATURE MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPS
MFR MANUFACTURER
NOTE: ALL ABBREVIATIONS MAY NOT BE USED
MIN MINIMUM
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NC NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
OZ OUNCE
PD PRESSURE DROP
PD PRESSURE DIFFERENCE
PG PROPYLENE GLYCOL
PH PHASE
PPM PARTS PER MILLION
PRESS PRESSURE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIA PSI ABSOLUTE
PSIG PSI GAUGE
R THERMAL RESISTANCE
RA RETURN AIR
RECIRC RECIRCULATEE
REFR REFRIGERATION
REQD REQUIRED
RLA RATED --- AMPS
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SA SUPPLY AIR
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FT / MINUTE
SCW SOFT COLD WATER
SF SAFETY FACTOR
SH SENSIBLE HEAT
SL SEA LEVEL
SP STATIC PRESSURE
SPECS SPECIFICATIONS(-S)
SQ SQUARE
STD STANDARD
STM STEAM
TEMP TEMPERATURE
TD TEMP DROP
TD TEMP DIFFERENCE
THERM THERMAL
TOT TOTAL
TSTAT THERMOSTAT
V VOLT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VENT VENTILATION
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
WC WATER COLUMN
WG WATER GAUGE
WPD WATER PRESSURE DROP
WTR WATER
WT WEIGHT
WB WET BULB TEMPERATURE
YR YEAR
PLUMBING FIXTURES
ANNOTATIONS
POINT OF CONNECTION
SECTION TAG -
TOP FIGURE IS SECTION NUMBER
BOTTOM FIGURE IS SHEET NUMBER
DETAIL TAG -
TOP FIGURE IS DETAIL NUMBER
BOTTOM FIGURE IS SHEET NUMBER
DIFFUSER/GRILLE TAG -
TOP NOTE IS SIZE/TYPE
BOTTOM FIGURE IS CFM
EQUIPMENT IDENTIFICATION
KEYED NOTE IDENTIFICATION
A
ME501
SWITCH
SENSOR
THERMOSTAT
NIGHT THERMOSTAT
BREAK, ROUND
BREAK, STRAIGHT
T
S
SYMBOL DESCRIPTION
A101
T N
S
EQU-1
EQUI-1
2500 CFM
12"/12"
(1)
EQU-1
DUCT WORK/GRILLES SYMBOLS
SYMBOL DESCRIPTION
CEILING SUPPLY DIFFUSER
CEILING RETURN REGISTER
CEILING EXHAUST REGISTER
SIDEWALL SUPPLY REGISTER
SIDEWALL EXHAUST, LOUVER, OR RETURN REGISTER
RECTANGULAR DUCT WITH NET INSIDE DIMENSIONS IN INCHES
ROUND DUCT WITH NET INSIDE DIMENSIONS IN INCHES
20/12
DUCT TRANSFORMATION MAX 15°
HIGH EFFICIENCY FITTING
TAP ENTRY AREA EQUALS 150% OF BRANCH AREA
D 45° D
ME001
MH111 MECHANICAL AND MECHANICAL DEMO PLAN
MECHANICAL GENERAL INFORMATION
REVISION DELTA NUMBER
MECHANICAL GENERAL NOTES
1. ALL SUPPLY GRILLES ARE CD-1, CFM AS NOTED, UNLESS
OTHERWISE NOTED. REFER TO DETAIL FOR GRILLE & DIFFUSER
CONNECTION.
2. ALL RETURN GRILLES SHOWN AS SUCH ARE RG-1 UNLESS
OTHERWISE NOTED. RETURN GRILLES LOCATED IN ACOUSTICAL
CEILING TILE SHALL BE INSTALLED WITH RETURN AIR SOUND
BOOT UNLESS OTHERWISE INDICATED.
3. BRANCH DUCTWORK SHALL BE SIZED TO MATCH NECK INLET
SIZE OF DIFFUSER, GRILLE, OR REGISTER SERVED UNLESS
NOTED OTHERWISE.
4. COORDINATE EXACT LOCATION OF THERMOSTAT WITH OWNER.
5. DO NOT ROUTE DUCTS AND PIPES ABOVE ELECTRICAL PANELS.
ALL ELECTRICAL PANELS MUST HAVE CLEAR ACCESS SPACE IN
FRONT OF PANEL 4'-0" DEEP AND 6'-6" HIGH. DO NOT ROUTE
DUCTS AND PIPES IN ELECTRICAL ROOMS, EXCEPT DUCTS AND
PIPES SERVING THE ROOM.
6. COORDINATE EXACT LOCATIONS OF GRILLES WITH
ARCHITECTURAL PLANS.
7. ALL DUCT DIMENSIONS ARE INSIDE FREE AREA DIMENSIONS.
ADJUST SHEET METAL DIMENSION FOR LINED DUCT.
8. PROVIDE CEILING ACCESS PANELS AS REQUIRED WHERE
MECHANICAL EQUIPMENT, VALVES, FIRE DAMPERS, ETC. ARE
LOCATED ABOVE INACCESSIBLE CEILINGS.
9. ROOF DECK SHALL NOT BE USED TO SUPPORT LOADS FROM
PIPING, DUCTWORK OR EQUIPMENT, UNLESS NOTED
OTHERWISE. HANGER LOADS LESS THAN 50 LBS. MAY BE HUNG
FROM THE STEEL ROOF DECK IN CASES WHEN HANGING FROM
THE STEEL ROOF DECK CANNOT BE AVOIDED; THE
ATTACHMENT METHOD MUST DISTRIBUTE THE LOAD ACROSS
THE DECK AS APPROVED BY THE STRUCTURAL ENGINEER.
10. COORDINATE INSTALLATION OF NEW MECHANICAL EQUIPMENT
WITH EXISTING CONDITIONS.
11. ALL SURFACES DAMAGED AS A RESULT OF NEW
CONSTRUCTION SHALL BE PATCHED AND REPAIRED AS
REQUIRED TO MATCH EXISTING SURFACES.
12. PROVIDE MANUFACTURER'S RECOMMENDED SERVICE
CLEARANCE AROUND ALL SIDES OF MECHANICAL EQUIPMENT.
13. THERMOSTATS SHALL NOT BE LOCATED ON EXTERIOR WALLS.
COORDINATE EXACT MOUNTING LOCATION OF ALL
THERMOSTATS WITH LATEST REVISION OF ARCHITECTURAL
ELEVATION AND FURNISHINGS PLANS, TYPICAL.
14. LOCATE ALL EXHAUST VENTS AND PLUMBING VENTS MINIMUM
10 FT. FROM ALL BUILDING INTAKES.
15. INSTALL WATER, GAS, AND VENT PIPING SHOWN ABOVE THE
CEILING UNLESS NOTED OTHERWISE.
16. INSTALL WASTE PIPING SHOWN BELOW THE FLOOR UNLESS
NOTED OTHERWISE.
17. PROVIDE 2" MINIMUM WASTE PIPING BELOW GRADE.
18. COORDINATE EXACT LOCATION OF FIXTURES AND DRAINS WITH
ARCHITECTURAL DRAWINGS.
19. PROVIDE 3" MINIMUM VENT THROUGH ROOF. INCREASE VENT
LINE 12" BELOW BUILDING INSULATION.
20. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
CAULKING AND SEALING ALL PENETRATIONS IN FIRE AND
SMOKE RATED PARTITIONS TO MAINTAIN RATINGS. SEE
SPECIFICATION, TYPICAL.
21. THE MECHANICAL CONTRACTOR SHALL PROVIDE FIRE, SMOKE
OR COMBINATION FIRE/SMOKE DAMPERS AT ALL LOCATIONS
SHOWN ON THE CONTRACT DOCUMENTS AND AS REQUIRED TO
MEET THE INTEGRITY OF ALL SMOKE AND FIRE PARTITIONS. THE
CONTRACTOR SHALL REFER TO THE LATEST ARCHITECTURAL
LIFE SAFETY PLANS FOR ALL FIRE AND SMOKE PARTITION
LOCATIONS. DAMPERS ARE TO BE PROVIDED WITH
SHUTOFF/TEST SWITCH AT EACH LOCATION.
22. PROVIDE AND INSTALL TURNING VANES IN ALL SQUARE LOW
PRESSURE DUCTWORK AT ELBOWS OR TEES, TYPICAL.
23. INSTALL ALL TERMINAL BOXES IN EASILY ACCESSIBLE AND
SERVICEABLE LOCATIONS, MEETING ALL MANUFACTURERS
REQUIRED CLEARANCES ON EACH SIDE, SEE DETAILS, TYPICAL.
24. CONTRACTOR SHALL OFF-SET, TRANSITION AND PROVIDE
CHANGES AS REQUIRED FOR COORDINATION WITH OTHER
TRADES, TYPICAL.
25. DUCTWORK SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
REFER TO MECHANICAL SPECIFICATIONS FOR EXTENT OF DUCT
INSULATION AND LINER.
26. PROVIDE AND INSTALL REMOTE DAMPER OPERATORS FOR ALL
DAMPERS INSTALLED ABOVE INACCESSIBLE CEILINGS, SEE
MECHANICAL SPECIFICATIONS FOR EQUIPMENT
REQUIREMENTS, TYPICAL.
27. PROVIDE AND INSTALL HIGH EFFICIENCY TAKE-OFF FITTINGS
AND BALANCING DAMPER AT ALL BRANCH CONNECTIONS TO
LOW PRESSURE DUCTWORK.
28. PROVIDE AND INSTALL HIGH EFFICIENCY OR CONICAL
TAKE-OFFS AT ALL BRANCH CONNECTIONS TO MEDIUM
PRESSURE DUCTWORK.
29. WHERE DUCTWORK CROSSES, SUPPLY DUCTWORK IS USUALLY
BELOW RETURN AND EXHAUST DUCT. RETURN DUCTWORK IS
USUALLY BELOW EXHAUST DUCTS.
30. EXCEPT WHERE DIRECTED TO PLACE ITEMS OF WORK AT THE
APPROXIMATE LOCATION SHOWN; DO NOT SCALE DRAWINGS
FOR DIMENSIONAL INFORMATION. ALL ELEMENTS OF THE
DRAWINGS MAY NOT BE DRAWN TO EXACT SCALE. ALL
DIMENSIONS REQUIRED ARE SHOWN OR MAY BE DERIVED FROM
THOSE SHOWN ON THE FLOOR PLANS, DETAIL PLANS,
ELEVATIONS, SECTION, DETAILS, SCHEDULES, AND
SPECIFICATIONS. IF CONCERNS ARISE, THE CONTRACTOR
SHALL NOTIFY THE DESIGNER SO THAT A CLARIFICATION CAN
BE ISSUED.
31.…