3-02 Maintenance Facility ElectricalPlans 20260901.pdf
PDF 3 MB Posted
- Attached to
- Township Maintenance Facility Addition Project
- Solicitation number
- Not on record
- Issued by
- Berks County, Pennsylvania
About this file
Electrical Demolition and Installation Plans for Longswamp Township Maintenance Facility
This document is a set of electrical demolition and installation plans prepared by Hanover Engineering Associates, Inc. for Longswamp Township, Berks County, Pennsylvania, as part of the Township Maintenance Facility Addition Project located at 102 Longsdale Drive. The plans detail comprehensive electrical work including the removal and salvage of existing lighting, receptacles, sensors, equipment, conduit, and wiring to accommodate truss removal and ceiling installation in a seven-bay maintenance facility structure. The scope encompasses demolition of existing electrical panels (Panel "EPP" and Panel "OF"), installation of new Panel "B5" serving Bays 5, 6, and 7, relocation of existing 8-foot LED luminaires, installation of new Lithonia LED lighting fixtures with motion sensors and photocells, replacement of all receptacles with new 20-ampere, 125-volt specification-grade devices, and coordination with fire alarm and video camera system providers (SAH Incorporated). The project also includes provisions for an optional backup generator system (Alternate #1) with an automatic transfer switch and propane-powered 48kW generator. Sealed proposals for Contract 2 - Electrical Components are due October 12, 2026, at 1:00 p.m. prevailing time via the PennBid program, with a non-mandatory pre-bid conference scheduled for September 25, 2026, at 9:00 a.m. at the facility location, and final questions due by 4:00 p.m. on October 2, 2026.
All work must comply with the National Electrical Code (NEC), NFPA standards, IBC 2018, OSHA requirements, and Pennsylvania prevailing wage regulations. The contractor is responsible for all permits, licenses, certifications, and state and local fees. Bidders must submit a 10 percent bid bond or certified check with their proposals, which remain valid for 60 calendar days from the opening date. The electrical plans specify materials including Square D panelboards, copper THWN wiring in EMT and PVC conduit, Lithonia LED luminaires with integral controls, GFCI-protected receptacles, and comprehensive grounding and bonding systems. The contractor must provide shop drawings, product data, operation and maintenance manuals, record drawings, power system studies including short circuit and arc flash analyses, and coordinate work with the fire alarm and video security system providers. A one-year unconditional warranty on all work, articles, materials, equipment, and workmanship from the date of owner acceptance is required.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
M
M
GFI
SS
M
S S
M
S sc scsc
EMERGENCY
FUEL SHUT-OFF
PANEL 'OF'
MTS
A
RECEPT
REEL
SUMP
PUMP
SUMP
PUMP
AIR
COMPRESSOR
EXHAUST
FAN
D
FIRE/SECURITY PANEL
E
S
S
S
S S
S
SS SS
S
S S
S S
S SS SS
B C B
C
C
Br od he ad
R oa d, S ui te
Be th le he m , P
A
7-
P :6
.6
.5
F:
0.
1.
H an ov er En g.
co m
Be th le he m O ffi ce
9165.003
1. ALL LIGHTING, RECEPTACLES, SENSORS, EQUIPMENT, CONDUIT, AND
WIRING LOCATED ON THE CEILING SHALL BE REMOVED TO
ACCOMMODATE TRUSS REMOVAL.
2. ALL EXISTING 8'-0" LONG, CEILING MOUNTED LED LUMINAIRES SHALL BE
REMOVED FROM CEILING AND STORED FOR FUTURE RE-INSTALLATION
ON NEW CEILING.
3. REFER TO SHEET KEYNOTES FOR ADDITIONAL ITEMS FOR SALVAGE TO
BE RE-INSTALLED.
GENERAL NOTES
A. REMOVE EXISTING PANELBOARD, PVC CONDUIT, AND CONDUCTORS BACK
TO PANEL 'OF' TO ACCOMMODATE NEW TRUSS INSTALLATION.
B. SALVAGE EXIT SIGN, EMERGENCY BATTERY HEAD, AND EXTERIOR
EMERGENCY HEAD FOR RE-INSTALLATION.
C. EQUIPMENT TO REMAIN AND BE RE-CONNECTED TO UPON TRUSS
INSTALLATION.
D. ALL DEVICES IN OFFICE TO REMAIN.
E. ALTERNATE #1: REMOVE EXISTING MANUAL TRANSFER SWITCH.
SHEET KEYNOTES
Scale:1 3/16" = 1'-0"
DEMOLITION PLAN - POWER
0 8'4'2'1'
Scale:2 3/16" = 1'-0"
DEMOLITION PLAN - LIGHTING
0 8'4'2'1'
ED
-1
013. DEMOLITION SHALL BE PERFORMED IN AN ORDERLY FASHION. ALL
NECESSARY PRECAUTIONS SHALL BE TAKEN TO PROTECT EXISTING
FACILITIES FROM DAMAGE DURING CONSTRUCTION.
4. PROTECT ALL ITEMS TO REMAIN IN SERVICE FROM DAMAGE DURING
THE DEMOLITION OR REMOVAL PORTION OF THIS PROJECT.
5. THE CONTRACTOR SHALL REVIEW ALL ELECTRICAL DEMOLITION WORK
WITH THE OWNER PRIOR TO START OF DEMOLITION WORK.
GENERAL DEMOLITION NOTES
1. THE FOLLOWING DEFINITIONS APPLY TO THE WORK:
A. REMOVE: REMOVE AND LEGALLY DISPOSE OF ITEMS EXCEPT
THOSE INDICATED TO BE REINSTALLED, SALVAGED OR TO REMAIN
THE OWNER'S PROPERTY.
B. REMOVE AND SALVAGE: ITEMS INDICATED TO BE REMOVED AND
SALVAGED MUST BE COVERED, PROTECTED, AND RELOCATED TO
THE OWNER'S DESIGNATED STORAGE AREA. IDENTIFY CONTENTS
OF ALL REMOVED AND SALVAGED ITEMS.
C. REMOVE AND REINSTALL: REMOVE ITEMS INDICATED: CLEAN,
SERVICE AND OTHERWISE PREPARE THEM FOR REUSE; STORE AND
PROTECT THEM AGAINST DAMAGE. REINSTALL ITEMS IN THE SAME
LOCATIONS OR IN LOCATIONS INDICATED.
D. EXISTING TO REMAIN: PROTECT CONSTRUCTION INDICATED TO
REMAIN AGAINST DAMAGED AND SOILING DURING SELECTIVE
DEMOLITION. WHEN PERMITTED BY THE OWNER'S
REPRESENTATIVE, ITEMS MAY BE REMOVED TO A SUITABLE,
PROTECTED STORAGE LOCATION DURING SELECTIVE DEMOLITION
AND THEN CLEANED AND REINSTALLED IN THEIR ORIGINAL
LOCATIONS.
2. THE OWNER RESERVES THE RIGHT TO SALVAGE ANY ITEMS IDENTIFIED
TO BE REMOVED. AT THE BEGINNING OF DEMOLITION WORK THE
OWNER'S REPRESENTATIVE SHALL IDENTIFY ALL ITEMS TO BE
SALVAGED.
GENERAL DEMOLITION NOTES
AutoCAD SHX Text
BAY 4
AutoCAD SHX Text
BAY 3
AutoCAD SHX Text
BAY 2
AutoCAD SHX Text
BAY 1
AutoCAD SHX Text
BAY 5
AutoCAD SHX Text
BAY 6
AutoCAD SHX Text
BAY 7
AutoCAD SHX Text
BAY 6
AutoCAD SHX Text
BAY 7
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
REST ROOM
AutoCAD SHX Text
NEMA
AutoCAD SHX Text
NEMA
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
HC
AutoCAD SHX Text
HC
AutoCAD SHX Text
NEMA
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text F
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text
BAY 4
AutoCAD SHX Text
BAY 3
AutoCAD SHX Text
BAY 2
AutoCAD SHX Text
BAY 1
AutoCAD SHX Text
BAY 5
AutoCAD SHX Text
BAY 6
AutoCAD SHX Text
BAY 7
AutoCAD SHX Text
BAY 6
AutoCAD SHX Text
BAY 7
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
REST ROOM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
PLAN TITLE:
AutoCAD SHX Text
PROJECT TITLE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 01/14/25
AutoCAD SHX Text L22-24
AutoCAD SHX Text
TOWNSHIP MAINTENANCE FACILITY
AutoCAD SHX Text
LONGSWAMP TOWNSHIP BERKS COUNTY PENNSYLVANIA
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 02-11-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR PERMITS
AutoCAD SHX Text
102 LONGSDALE DRIVE BUILDING ADDITION
AutoCAD SHX Text
SEAL:
AutoCAD SHX Text 09-01-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR BIDDING
AutoCAD SHX Text
CJD
AutoCAD SHX Text
CRS
AutoCAD SHX Text
ELECTRICAL - DEMOLITION
B,B5-7
A,b B5-3
B,B5-7
B2,B5-7
A,f
OF-26
X,B5-3
C,B5-3
X,B5-3 X,B5-3X,B5-3
X,B5-3X,B5-3
S
S
S
S
A,b B5-3
A,b B5-3
A,b B5-3
A,b B5-3
A,b B5-3
A,b B5-3
A,b B5-3
X,a B5-5
X,a B5-5
X,a B5-5
X,a B5-5
X,a B5-5
X,a B5-5
S
S
S
X,c B5-5
X,c B5-5
X,c B5-5
X,c B5-5
PANEL 'B5'
S S
X B5-5
X B5-5
X,d
OF-22
X,d
OF-22
X,d
OF-22
X,d
OF-22
X,d
OF-22
X,d
OF-22
X,d
OF-22
X,d
OF-22
S
X,e
OF-4
S
X,e
OF-4
X,e
OF-4
X,e
OF-4
X,e
OF-4
S
A,f
OF-26
A,f
OF-26
A,f
OF-26
A,f
OF-26
A,f
OF-26
A,f
OF-26
A,f
OF-26
A,f
OF-26
A,f
OF-26
S
S
S
A,b B5-3
B,B5-7 B,B5-7B,B5-7
X X
X
A,b B5-3
B,B5-7 B,B5-7
B,B5-7B,B5-7
B2,B5-7
B3,B5-7
B3,B5-7
PANEL 'OF'
1. REFER TO SHEET E-601 FOR PANEL SCHEDULES.
2. REFER TO SHEET E-602 FOR SPECIFICATIONS.
GENERAL NOTES
1. EXISTING LUMINAIRE RELOCATED FROM BAY #3.
2. EXISTING LUMINAIRE RELOCATED FROM BAY #4.
3. EXISTING LUMINAIRE RELOCATED FROM BAY #5.
SHEET KEYNOTES
Br od he ad
R oa d, S ui te
Be th le he m , P
A
7-
.6
.5
F:
0.
1.
H an ov er En g.
co m
Be th le he m O ffi ce
9165.003
Scale:1 3/16" = 1'-0"
PROPOSED LIGHTING - PLAN
0 8'4'2'1'
LUMINAIRE SCHEDULE
TYPE MANUFACTURER CATALOG NUMBER LUMENS WATTAGE CCT CRI MOUNTING VOLTAGE RMK. DESCRIPTION
A LITHONIA FEM-L96-15000LM-IMAFD-WD-MVOLT-GZ10-40K-80CRI- 15,912 94 4,000 80 C,S 120 -- 8'-0" LED ENCLOSED AND GASKETED INDUSTRIAL
B LITHONIA WDGE2-LED-P3SW-30K-80CRI-VF-MOVLT-SRM-PIR1FC3V-DDBXD 2,000 23 3,000 80 W 120 4,5 LED ARCHITECTURAL WALL SCONCE W/ VISUAL COMFORT LENS, MOTION SENSOR/PHOTOCELL
B2 LITHONIA WDGE2-LED-P3SW-30K-80CRI-VW-MOVLT-SRM-PIR1FC3V-DDBXD 2,000 23 3,000 80 W 120 4,5 LED ARCHITECTURAL WALL SCONCE W/ VISUAL COMFORT LENS, MOTION SENSOR/PHOTOCELL
B3 LITHONIA WDGE2-LED-P5-30K-80CRI-VF-MOVLT-SRM-PE-DDBXD 6,000 48 3,000 80 W 120 4,6 LED ARCHITECTURAL WALL SCONCE W/ VISUAL COMFORT LENS, PHOTOCELL
C LITHONIA LHQM-S-W-RG-MVOLT-HO 2,855 37 - - W 120 2 LED EXIST SIGN W/ BATTERY BACK, EMERGENCY HEADS, HIGH OUTPUT BATTERY
C1 LITHONIA ELMRW-LP220L-DNAXD-T - 2.4 - - W 7.2 3 LED WET LOCATION EMERGENCY REMOTE TWIN HEAD
X EXISTING - - - - - - 120 1 EXISTING LUMINAIRE/DEVICE TO BE RELOCATED
MOUNTING LEGEND NOTES
C = CEILING R = RECESSED 1.) ALL LUMINAIRES SHALL BE PROVIDED WITH A MINIMUM 5 YEAR WARRANTY.
S = SURFACE P = PENDANT
W = WALL B = BOLLARD
T = TRACK AC= AIRCRAFT CABLE
REMARKS
1. RE-INSTALL AT SAME LOCATION UPON NEW TRUSS/CEILING INSTALLATION. CLEAN LENS AND INTERNAL LED AREA PRIOR TO RE-INSTALLATION.
2. CONNECT TO UNSWITCHED SOURCE OF LOCAL LIGHTING CIRCUIT.
3. CONNECT TO LOCAL EXIT SIGN.
4. CONNECT TO UNSWITCHED SOURCE OF CIRCUIT SHOWN.
5. MOUNT TOP OF LUMINAIRE AT 13'-6" A.F.F.
6. MOUNT TOP OF LUMINAIRE AT 18' A.F.F.
EL
-1
AutoCAD SHX Text 3a
AutoCAD SHX Text 3a
AutoCAD SHX Text 3b
AutoCAD SHX Text 3b
AutoCAD SHX Text 4c
AutoCAD SHX Text 3c
AutoCAD SHX Text 3c
AutoCAD SHX Text 3d
AutoCAD SHX Text 3e
AutoCAD SHX Text 3d
AutoCAD SHX Text 3e
AutoCAD SHX Text 3f
AutoCAD SHX Text 3f
AutoCAD SHX Text 4d
AutoCAD SHX Text 4f
AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
PLAN TITLE:
AutoCAD SHX Text
PROJECT TITLE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 01/14/25
AutoCAD SHX Text L22-24
AutoCAD SHX Text
TOWNSHIP MAINTENANCE FACILITY
AutoCAD SHX Text
LONGSWAMP TOWNSHIP BERKS COUNTY PENNSYLVANIA
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 02-11-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR PERMITS
AutoCAD SHX Text
102 LONGSDALE DRIVE BUILDING ADDITION
AutoCAD SHX Text
SEAL:
AutoCAD SHX Text 09-01-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR BIDDING
AutoCAD SHX Text
CJD
AutoCAD SHX Text
CRS
ELECTRICAL - LIGHTING
PANEL 'B5'
S B5-1
S B5-4
S B5-2
S B5-2
S B5-1
S
OF-9
S
OF-9
OF-18
AIR
COMPRESSOR
OF-5
M
M
M
M
S
B5-10
NEMA 10-50R
B5-10
NEMA 10-50R B5-9,GFI,36"B5-9,GFI,36"
B5-9,GFI,36"
B5-9,GFI,36"
B5-9,GFI,36"
B5-11,GFI,36"
B5-11,GFI,36" B5-11,GFI,36" B5-11,GFI,36"
B5-11,GFI,36"
B5-13,GFI,36"
B5-8,GFI,36" B5-8,GFI,36"
B5-8,GFI,36"
B5-8,GFI,36"
B5-8, GFI,36"
B5-6,GFI,WP
M
M
M
M
B5-15 B5-15
B5-17 B5-17 B5-19
B5-19 OF-6
B5-16,GFI,36"
B5-14 B5-14 B5-14
OF-6
SS
S S S S
SSSSS
CORD REEL
OF-28,GFI,36" OF-28,GFI,36"
B5-11,GFI,36"
OF-28,GFI,36"
OF-28,GFI,36"
OF-28,GFI,36"B5-16,GFI,36"B5-16,GFI,36"
B5-16,GFI,36"
OF-4,GFI
OF-21,GFI OF-21,GFI
OF,GFI-23
OF-16,GFI
B5-18, GFI
B5-18, GFI
B5-18, GFI
OF-30,GFI
OF-30,GFI
B5-11,GFI,WP OF-28,GFI,WP
OF-28,
GFI,WP
sc sc sc
UH
UH
UH
UH
UH
UH
GARAGE DOOR OPENER (TYPICAL FOR 11)
B5-20,GFI,WP,36"
PANEL 'OF'
ATS-13
GENERATOR
1. REFER TO SHEET E-601 FOR PANEL SCHEDULES.
2. REFER TO SHEET E-602 FOR SPECIFICATIONS.
3. ALL EXISTING RECEPTACLES SHALL BE REPLACED WITH NEW
RECEPTACLES. WIRE AND CONDUIT SHALL BE UTILIZED TO THE
GREATEST EXTENT POSSIBLE.
GENERAL NOTES
1. PROVIDE HEAVY DUTY, NEMA-12, 2P.30A, 208VAC NON-FUSED DISCONNECT
SWITCH.
2. RE-CONNECT TO EXISTING CIRCUIT.
3. ALTERNATE #1: PROVIDE AUTOMATIC TRANSFER SWITCH AND GENERATOR.
REFER TO ONELINE DIAGRAM AND SPECIFICATIONS FOR MORE
INFORMATION. REFER TO SITE PLANS FOR EXACT GENERATOR LOCATION.
4. ALTERNATE #1: PROVIDE GENERATOR EMERGENCY SHUTDOWN MEANS AT
THIS LOCATION IN ACCORDANCE WITH NEC 445.18(C) AND NFPA 110.
EMERGENCY STOP SHALL BE READILY ACCESSIBLE, IDENTIFIED, AND
LOCATED OUTSIDE THE GENERATOR ENCLOSURE
SHEET KEYNOTES
Br od he ad
R oa d, S ui te
Be th le he m , P
A
7-
.6
.5
F:
0.
1.
H an ov er En g.
co m
Be th le he m O ffi ce
9165.003
Scale:1 3/16" = 1'-0"
PROPOSED POWER - PLAN
0 8'4'2'1'
EP
-1
FIRE ALARM/SECURITY
1. SECURE THE SERVICES OF LONGSWAMP TOWNSHIP'S FIRE ALARM
SYSTEM PROVIDER TO PROVIDE A COMPLETE AND OPERATING FIRE
ALARM SYSTEM.
SAH INCORPORATED.
JIM BUCCIAGLIA
50 S. MUSEUM ROAD
READING, PA 19607
610-372-8872
JIMB@SAHINC.COM
2. THE EXISTING FIRE ALARM PANEL (SAH) SHALL BE RETAINED IN THE
EXISTING OFFICE. ALL EXISTING DETECTORS SHALL BE REMOVED AND
RE-INSTALLED AT SAME LOCATIONS NEW DETECTORS SHALL BE
INSTALLED IN ADDITIONAL BAYS NOTED.
3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
OUTLET BOXES AND ACCESS PATHWAYS REQUIRED FOR THE FIRE
ALARM SYSTEM MODIFICATIONS WITHIN THE BUILDING.
4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE
WORK AND CONSTRUCTION SCHEDULE WITH SUBCONTRACTORS.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR A FINAL
COMPLETE AND OPERATING FIRE ALARM SYSTEM.
VIDEO CAMERA SYSTEM
1. SECURE THE SERVICES OF LONGSWAMP TOWNSHIP'S VIDEO CAMERA
SYSTEM PROVIDER TO PROVIDE A COMPLETE AND OPERATING VIDEO
CAMERA SYSTEM.
SAH INCORPORATED.
JIM BUCCIAGLIA
50 S. MUSEUM ROAD
READING, PA 19607
610-372-8872
JIMB@SAHINC.COM
2. THE EXISTING VIDEO CAMERA SYSTEM SHALL BE REMOVED AND
RETAINED FROM THE EXISTING BUILDING SCHEDULED FOR
RENOVATIONS. THE VIDEO CAMERA SYSTEM SHALL BE REINSTALLED IN
THE RENOVATED BUILDING. NEW CAMERAS SHALL BE ADDED TO THE
SYSTEM TO ACCOMMODATE THE NEW BUILDING ADDITION. THE
EXISTING CAMERAS SHALL BE RE-INSTALLED AT THE SAME RESPECTIVE
LOCATIONS.
3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
OUTLET BOXES AND ACCESS PATHWAYS REQUIRED FOR VIDEO
SECURITY SYSTEMS WITHIN THE BUILDING AND THE SITE. SINGLE GANG
OUTLET BOXES & 3/4" CONDUIT WITH CAT6A CABLING AND A
PULLSTRINGS SHALL BE PROVIDED FROM THE CAMERA LOCATION BACK
TO THE DATA CLOSET BUILDING. OUTLET BOX HEIGHTS (INCLUDING
FINAL LOCATION) AND ACCESS PATHWAY ROUTING SHALL BE
COORDINATED WITH THE OWNER, ARCHITECT, AND SYSTEM PROVIDER
PRIOR TO INSTALLATION. CONDUIT SIZE SHALL BE 3/4" IN BUILDINGS, 1"
UNDERGROUND UNLESS AN ALTERNATE SIZE IS INDICATED ON PLANS.
4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE
WORK AND CONSTRUCTION SCHEDULE WITH SUBCONTRACTORS. ALL
CAMERAS SHALL BE AIMED TO SATISFY OWNER. ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR A FINAL COMPLETE AND
OPERATING VIDEO CAMERA SYSTEM.
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
NEMA 10-50R
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
PLAN TITLE:
AutoCAD SHX Text
PROJECT TITLE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 01/14/25
AutoCAD SHX Text L22-24
AutoCAD SHX Text
TOWNSHIP MAINTENANCE FACILITY
AutoCAD SHX Text
LONGSWAMP TOWNSHIP BERKS COUNTY PENNSYLVANIA
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 02-11-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR PERMITS
AutoCAD SHX Text
102 LONGSDALE DRIVE BUILDING ADDITION
AutoCAD SHX Text
SEAL:
AutoCAD SHX Text 09-01-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR BIDDING
AutoCAD SHX Text
CJD
AutoCAD SHX Text
CRS
ELECTRICAL - POWER
1. UTILIZE EXISTING 2P.100A BREAKER FOR NEW PANEL 'B5' FEED.
2. REMOVE EXISTING PANEL 'EPP', PANEL FEEDER TO PANEL 'OF', AND ALL
BRANCH CIRCUITS.
3. ALTERNATE #1: PROVIDE ALL COST ASSOCIATED WITH ADD ALTERNATE
NO.1 FOR A BACKUP GENERATOR. REMOVE EXISTING MANUAL TRANSFER
SWITCH AND PROVIDE NEW AUTOMATIC TRANSFER SWITCH. PROVIDE NEW
GENERATOR, CONCRETE PAD, CONNECTION TO EXISTING PROPANE TANK,
AND ALL ASSOCIATED APPURTENANCES REQUIRED FOR A COMPLETE
OPERATING AND CODE COMPLAINT BACKUP GENERATOR SYSTEM.
COORDINATE WITH UTILITY COMPANY.
4. ALTERNATE #1: PROVIDE TWO 1P.20A BREAKER IN EXISTING PANEL FOR
BACKUP GENERATOR SHORE POWER. CONFIRM VOLTAGE AND AMPERAGE
REQUIREMENTS WITH MANUFACTURER.
SHEET KEYNOTES
Scale:1 none
EXISTING ONE-LINE DIAGRAM
Br od he ad
R oa d, S ui te
Be th le he m , P
A
7-
.6
.5
F:
0.
1.
H an ov er En g.
co m
Be th le he m O ffi ce
9165.003
PANEL
"EPP"
125A
240/120V, 1Ø,3W
MLO.
12 CKT.
BAY #5
PANEL
"OF"
200A
240/120V, 1Ø,3W
200A MCB.
30 CKT.
BAY #1 OFFICE
100A
PLUG FOR
TEMP
GENERATOR
200A SIEMENS
MANUAL
TRANSFER
SWITCH (MTS)
MET -ED
METER #
5-001-403-3337
MET -ED
POLE #
58299-43008
EXISTING PANEL SCHEDULE "OF" (TO REMAIN)
CKT # LOAD DESCRIPTION
FEEDER
GRD COND. AMPS POLE
WATTS PER PHASE
POLE AMPS COND. GRD
FEEDER
LOAD DESCRIPTION CKT #
QTY SIZE A B A B SIZE QTY
1 PANEL 'EPP' 3 3 8 1 100 2 0 1 20 3/4 12 12 2 #5 LTS/REC, EXT LTS5/6, CLOCK REC3/4 2
3 - - - 500 1 20 3/4 12 12 2 #1 LIGHTS&REC , OUTSIDE CORNER LT 4
5 COMPRESSOR 2 10 10 3/4 30 2 3360 480 1 20 3/4 12 12 2 #1 GARAGE DOOR 6
7 - - - 3360 250 1 20 3/4 12 12 2 DOOR RECEPT, LIGHTS IN OFFICE 8
9 GAS HEATERS 2 12 12 3/4 20 1 1620 720 1 20 3/4 12 12 2 FUEL PUMPS 10
11 BASEBOARD HEAT 2 12 12 3/4 20 2 1000 180 1 20 3/4 12 12 2 RECEPT AT DESK 12
13 - - - 1000 0 1 20 3/4 12 12 2 ASH SHED 14
15 OFFICE FAN & #4 RECEPT 2 12 12 3/4 20 1 360 300 1 15 3/4 12 12 2 SHOP FAN #1 16
17 WATER PUMP 2 12 12 3/4 15 2 960 3600 2 50 3/4 10 8 2 WELDER RECEPT 18
19 - - - 960 3600 - - - 20
21 WORK BENCH RECEPT & LIGHTS 2 12 12 3/4 20 1 180 800 1 20 3/4 12 12 2 LIGHTS #2, #3, #4 22
23 WATER HEATER & RECEPT 2 12 12 3/4 20 1 1200 180 1 20 3/4 12 12 2 PANEL RECEPT 24
25 GENERATOR BATTERY CHARGER 2 12 12 1 20 1 600 970 1 20 3/4 12 12 2 LIGHTS BAY 1,2,3,4 WEST ** 26
27 GENERATOR HEATER 2 12 12 1 20 1 1200 900 1 20 3/4 12 12 2 RECEPT BAY 1 WEST ** 28
29 SPACE 360 1 20 3/4 12 12 2 RECEPT BAY 1/2 COMMON WALL ** 30
TOTAL WATTS PER PHASE 7720 8080 6930 5910
TOTAL A Ø WATTS 14650 TOTAL A Ø AMPS 122.08 VOLTAGE: 120/ 240V 1P, 3W LOCATION: UTILITY 100, PUMP HS NOTES: EXISTING SIEMENS SERIES 'E' PANEL.
NEMA TYPE 1.
TOTAL C Ø WATTS 13990 TOTAL C Ø AMPS 116.58 AMPACITY: 200 MAIN BREAKER: BREAKER
AIC RATING: 10,000 MOUNTING: SURFACE
TOTAL 1 Ø WATTS 28640 TOTAL 1 Ø AMPS 119.33 FED FROM MET-ED SERVICE VIA MANUAL TRANSFER SWITCH
REMARKS: ** PROVIDE SIEMENS 1P.20A TYPE 'QP' BREAKER
EXISTING PANEL SCHEDULE "EPP" (SCHEDULED FOR DEMOLITION)
CKT # LOAD DESCRIPTION
FEEDER
GRD COND. AMPS POLE
WATTS PER PHASE
POLE AMPS COND. GRD
FEEDER
LOAD DESCRIPTION CKT #
QTY SIZE A B A B SIZE QTY
1 GAS HEATER BAY 6 15 1 180 798 1 15 - 2
3 - 20 1 180 627 1 15 - 4
5 - 20 1 180 267 1 15 EXTERIOR OUTLETS 6
7 SPACE 1 360 0 1 20 INTERIOR OUTLETS 8
9 - 15 1 180 0 2 50 WASHING COMPRESSOR OUTLETS 10
11 GARAGE OUTLETS 20 1 180 960 - - 12
TOTAL WATTS PER PHASE 540 720 1065 1587
TOTAL A Ø WATTS 1605 TOTAL A Ø AMPS 13.38 VOLTAGE: 120/ 240V 1P, 3W LOCATION: BAY #5 NOTES: EXISTING CROUSE-HINDS TYPE 'F'
PANEL. NEMA TYPE 1.
TOTAL C Ø WATTS 2307 TOTAL C Ø AMPS 19.23 AMPACITY: 125 MAIN BREAKER: LUG
AIC RATING: 10,000 MOUNTING: SURFACE
TOTAL 1 Ø WATTS 3912 TOTAL 1 Ø AMPS 16.30 FED FROM PANEL 'OF'
REMARKS:
E-
PROPOSED PANEL SCHEDULE "B5"
CKT # LOAD DESCRIPTION
FEEDER
GRD COND. AMPS POLE
WATTS PER PHASE
POLE AMPS COND. GRD
FEEDER
LOAD DESCRIPTION CKT #
QTY SIZE A B A B SIZE QTY
1 GAS HEATERS BAY 6 & 7 2 12 12 3/4 20 1 1620 1620 1 20 3/4 12 12 2 GAS HEATERS BAY 4 2
3 LIGHTS BAY 5, 6, 7 WEST 2 12 12 3/4 20 1 970 810 1 20 3/4 12 12 2 GAS HEATER BAY 5 4
5 LIGHTS BAY 5, 6, 7 EAST 2 12 12 3/4 20 1 800 180 1 20 3/4 12 12 2 EXTERIOR OUTLETS 6
7 LIGHTS EXTERIOR 2 12 12 3/4 20 1 206 900 1 20 3/4 12 12 2 RECEPT BAY 5 8
9 RECEPT BAY 6&7 EAST 2 12 12 3/4 20 1 900 3600 2 50 3/4 10 8 2 WASHING COMPRESSOR OUTLETS 10
11 RECEPT BAY 5,6&7 WEST 2 12 12 3/4 20 1 900 3600 - - 12
13 RECEPT BAY 5 AT PANEL B5 2 12 12 3/4 20 1 180 900 1 20 3/4 12 12 2 GARAGE DOORS 2,3, & 4 EAST 14
15 GARAGE DOORS 6 & 7 EAST 2 12 12 3/4 20 1 900 720 1 20 3/4 12 12 2 RECEPT BAY 2,3,4 WEST 16
17 GARAGE DOORS 6 & 7 WEST 2 12 12 3/4 20 1 900 900 1 20 3/4 12 12 2 RECEPT BAY 2,3,4 EAST 18
19 GARAGE DOORS BAY 5 2 12 12 3/4 20 1 900 180 1 20 3/4 12 12 2 RECEPT EXTERIOR SOUTH 20
21 SPARE 20 1 1 20 SPARE 22
23 SPARE 20 1 1 20 SPARE 24
25 SPARE 20 1 1 20 SPARE 26
27 SPARE 20 1 1 20 SPARE 28
29 SPARE 20 1 1 20 SPARE 30
TOTAL WATTS PER PHASE 4400 3876 7200 6210
TOTAL A Ø WATTS 11600 TOTAL A Ø AMPS 96.67 VOLTAGE: 120/ 240V 1P, 3W LOCATION: BAY #5 NOTES: BASIS OF DESIGN SQUARE-D NQ, NEMA
TYPE 12. TURN OFF ALL SPARE BREAKERS
TOTAL C Ø WATTS 10086 TOTAL C Ø AMPS 84.05 AMPACITY: 100 MAIN BREAKER: LUG
AIC RATING: 10,000 MOUNTING: SURFACE
TOTAL 1 Ø WATTS 21686 TOTAL 1 Ø AMPS 90.36 FED FROM PANEL 'OF' IN OFFICE (BAY #1)
REMARKS:
Scale:2 none
PROPOSED ONE-LINE DIAGRAM
PANEL
"B5" 100A
240/120V, 1Ø,3W
MLO.
30 CKT.
BAY #5
PANEL
"OF"
200A
240/120V, 1Ø,3W
200A MCB.
30 CKT.
BAY #1 OFFICE
100A
MET -ED
METER #
5-001-403-3337
MET -ED
POLE #
58299-43008
3#3 & 1 #8GRD.,
1" EMT CONDUIT
1. ALL BRANCH CIRCUIT WIRING SHALL BE COPPER, THWN, 2#12 & 1#12
GRD., 3/4" CONDUIT, 1" CONDUIT UNDERGROUND (PVC) OR WITHIN
FLOOR, UNLESS NOTED OTHERWISE. PROVIDE SEPARATE NEUTRALS
AND SEPARATE GREEN INSULATED EQUIPMENT GROUNDING
CONDUCTORS FOR ALL FEEDER AND BRANCH CIRCUITS. TERMINATE
EACH GROUNDING CONDUCTOR ON A GROUNDING LUG, BUS, OR
BUSHING. ALL BRANCH CIRCUIT WIRING IS SHOWN DIAGRAMMATICALLY,
CONTRACTOR SHALL COORDINATE ACTUAL CIRCUIT ROUTING WITH
OTHER TRADES AND BUILDING CONSTRUCTION.
2. SEAL ALL CONDUIT PENETRATIONS THROUGH WALLS WITH
APPROPRIATE SEALANT. PENETRATIONS THROUGH FIRE RATED WALLS
AND FLOORS SHALL BE SEALED WITH A FIRE RATED SEALANT THAT IS
EQUAL OR BETTER THAN THE FIRE RATED MATERIAL THROUGH WHICH IT
PASSES.
3. ALL NEW WIRING SHALL BE ROUTED CONCEALED WITHIN NEW WALLS OR
CEILING SPACE. WIRING ON EXISTING WALLS SHALL BE SURFACE
MOUNTED RACEWAY. PROVIDE PULL BOXES AT LOCATIONS NEEDED,
AND ADEQUATELY SIZED AS REQUIRED FOR THE EQUIPMENT SERVED.
4. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL EQUIPMENT/DEVICE
REQUIREMENTS FOR EQUIPMENT PROVIDED BY OTHERS. CONTRACTOR
SHALL BE RESPONSIBLE FOR ALL ASSOCIATED EQUIPMENT &
TERMINATIONS TO EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S
REQUIREMENTS.
5. COORDINATE ALL POWER OUTAGES WITH THE OWNER PRIOR TO START
OF WORK. PROVIDE TEMPORARY POWER FOR BUILDING SERVICE,
CRITICAL LOADS, LIGHTING AND MISCELLANEOUS POWER
REQUIREMENTS FOR THE CONSTRUCTION AREA. PROVIDE GROUND
FAULT PROTECTION FOR TEMPORARY POWER. TEMPORARY FEEDER
AND BRANCH CIRCUIT CONDUIT & WIRING SHALL BE PROVIDED TO KEEP
CRITICAL LOADS OPERATIONAL DURING CONSTRUCTION. TEMPORARY
CONDUIT & WIRING SHALL MATCH EXISTING CONDUIT & WIRING
CURRENTLY SERVING CRITICAL LOADS IN ACCORDANCE WITH NEC
REQUIREMENTS.
6. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED, AND
SHALL MEET THE REQUIREMENTS OF BOTH THE NATIONAL ELECTRICAL
CODE (ARTICLE 250), AND THE EQUIPMENT/SYSTEM MANUFACTURER'S
REQUIREMENTS FOR TYPES, SIZES, AND QUANTITIES OF EQUIPMENT
GROUNDING CONDUCTORS, EXCEPT WHERE SPECIFIC TYPES, LARGER
SIZES, OR MORE CONDUCTORS THAN REQUIRED BY NEC ARE INDICATED.
7. INSTALLATION OF ALL LUMINAIRES SHALL BE COORDINATED WITH THE
ARCHITECT AND MANUFACTURER'S REQUIREMENTS PRIOR TO
INSTALLATION. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ALL NECESSARY MOUNTING & SUPPORT HARDWARE FOR A COMPLETE &
WORKING INSTALLATION.
8. THE CONTRACTOR SHALL VERIFY DIMENSIONS AND EXISTING
CONDITIONS PRIOR TO THE START OF THE WORK, NOTIFY THE
ENGINEER OF ANY SIGNIFICANT CHANGES IN DIMENSIONS AND
CONDITIONS.
9. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, TOOLS, EQUIPMENT,
AND NECESSARY FACILITIES, AND PERFORM ALL LABOR AND SERVICES
OF EVERY DESCRIPTION AS MAY BE NECESSARY TO COMPLETE THE
SCOPE OF THE WORK DEFINED IN THE CONTRACT DOCUMENTS.
10. FABRICATE AND INSTALL ALL WORK IN STRICT ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE (NEC), THE NATIONAL ELECTRICAL SAFETY
CODE (NESC), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA),
INTERNATIONAL BUILDING CODE (IBC), AMERICANS WITH DISABILITIES
ACT (ADA), NECA STANDARD OF INSTALLATION, OSHA, ALL APPLICABLE
STATE AND LOCAL CODES, GENERAL CONDITIONS AND SUPPLEMENTAL
TERMS OF THE CONTRACT. ALL EQUIPMENT SHALL BE UNDERWRITERS
LABORATORIES (U.L.) LISTED FOR ITS APPLICATION WHERE SUCH ITEMS
ARE REQUIRED.
11. ALL CONTRACTORS AND SUB-CONTRACTORS SHALL BE RESPONSIBLE
FOR THE PROPER PERFORMANCE OF THEIR WORK, COORDINATION WITH
OTHER TRADES, MEANS AND METHODS OF CONSTRUCTION, AND
SAFETY AND SECURITY WHILE ON SITE.
12. PROTECT EXISTING PROPERTY DURING CONSTRUCTION. REPAIR OR
REPLACE, WITHOUT ADDITIONAL CHARGE TO THE OWNER, ANY EXISTING
WORK DAMAGED DURING THE COURSE OF CONSTRUCTION.
13. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO
CONVEY, IN A GENERAL WAY, THE SCOPE OF THE WORK. THEY ARE NOT
INTENDED TO ILLUSTRATE ALL CONDITIONS WHICH MAY BE
ENCOUNTERED AT THE SITE.
14. REFER TO ARCHITECTURAL BUILDING PLANS FOR PROPER DIMENSIONS.
15. PUSH-ON WIRE CONNECTORS, OTHER THAN FOR LUMINAIRE
DISCONNECTS, SHALL NOT BE ALLOWED.
16. ALL GENERAL USE RECEPTACLES SHALL BE INSTALLED AT HEIGHTS
NOTED ABOVE FINISHED FLOOR AND SHALL BE RATED 20A, 125V, NEMA
5-20R, U.L. LISTED, UNLESS NOTED OTHERWISE. COORDINATE LOCATION
OF RECEPTACLES WITH OTHER DEVICES AND TELECOMMUNICATIONS
OUTLETS IN ROOM. SPECIFIC EQUIPMENT & DEVICE RECEPTACLE
MOUNTING HEIGHTS WITH EQUIPMENT & DEVICES TO BE INSTALLED.
(EXAMPLE: PROJECTORS AND AUDIO/VISUAL EQUIPMENT)
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND
PATCHING ASSOCIATED WITH THE INSTALLATION AND REMOVAL OF
ELECTRICAL EQUIPMENT.
18. CIRCUIT BREAKERS PROVIDED WITHIN EXISTING PANELBOARDS SHALL
BE COMPATIBLE WITH PANELBOARD AND SHALL HAVE THE
INTERRUPTING CAPACITY TO MEET THE AVAILABLE FAULT CURRENTS OF
THE EXISTING EQUIPMENT.
19. RECEPTACLE LABELING: ALL RECEPTACLES SHALL BE LABELED WITH
SELF-ADHESIVE CLEAR LABELS WITH 3/32” BLACK LETTERING ON THE FRONT
COVERPLATE OF THE RECEPTACLE. RECEPTACLE LABELING SHALL IDENTIFY
PANEL NAME AND CIRCUIT NUMBER FROM WHERE IT IS SERVED (EXAMPLE:
B5-13).
20. PROVIDE A POWER SYSTEM STUDY CONSISTING OF SHORT CIRCUIT,
EQUIPMENT DUTY, COORDINATION, AND ARC FLASH HAZARDS
ANALYSES FOR ALL ELECTRICAL DISTRIBUTION EQUIPMENT. THE
CONTRACTOR IS RESPONSIBLE TO OBTAIN ALL DATA NECESSARY FOR
PROPER COMPLETION OF THE STUDIES.
21. THE CONTRACTOR IS RESPONSIBLE TO PROVIDE COMPLETELY
COORDINATED EQUIPMENT. ALL EQUIPMENT MUST BE ADEQUATELY
RATED FOR THE AVAILABLE FAULT CURRENTS AT THE INSTALLATION
LOCATION. ENSURE POWER SYSTEM STUDY AND SHOP DRAWINGS FOR
ELECTRICAL DISTRIBUTION EQUIPMENT ARE SUBMITTED AT THE SAME
TIME FOR REVIEW BY THE ENGINEER OF RECORD.
22. PROVIDE A LABEL ON ALL SERVICE EQUIPMENT STATING THE MAXIMUM
AVAILABLE FAULT CURRENT AS CALCULATED BY THE POWER SYSTEM
STUDY. THE LABEL SHALL ALSO DISPLAY THE DATE THE CALCULATION
WAS PERFORMED.
GENERAL ELECTRICAL NOTES
LEGEND
LUMINAIRE, TYPE AS INDICATED ON PLAN. REFER TO EL-101
FOR SCHEDULE CONNECT TO CIRCUITS SHOWN ON PLAN.A,b
LUMINAIRE TYPE
SWITCHING ZONE, IF NONE CONNECT TO ALL
LUMINAIRES IN THE ROOM
B5-# PANEL-CIRCUIT NUMBER
IN-WALL, SINGLE POLE SWITCH
IN-WALL, THREE-WAY SWITCHS
S
EXISTING WALL MOUNTED EXIT SIGN
PROVIDE NEW 20A, 120VAC, DUPLEX RECEPTACLE, HEAVY DUTY
SPECIFICATION GRADE, NEMA 5-20R. PROVIDE TYPED LABEL ON
EACH RECEPTACLE COVERPLATE W/PANELBOARD NAME AND
CIRCUIT NUMBER. SAMPLE 'B5-5'. CLEAR LABEL W/ BLACK
LETTER, 3/32" HIGH. CONNECT TO CIRCUIT SHOWN.
PROVIDE NEW NEMA TYPE RECEPTACLE SHOWN, PROVIDE NEMA
TYPE RECEPTACLE AS NOTED ON PLAN VIEW. PROVIDE TYPED
LABEL ON EACH RECEPTACLE COVERPLATE W/PANELBOARD
NAME AND CIRCUIT NUMBER. CLEAR LABEL W/ BLACK LETTER,
3/32" HIGH. CONNECT TO CIRCUIT SHOWN.
NEMA #-##R,
NO DENOTE = NEW OUTLET AT 18",
AC = NEW OUTLET, MOUNT 8" ABOVE COUNTER TOP
##" = HEIGHT ABOVE FINISH FLOOR
GFI = GROUND FAULT CIRCUIT INTERRUPTER.
WP = WEATHER-RESISTANT W/ INTEGRAL GROUND FAULT
CIRCUIT INTERRUPTER MOUNTED IN LOCKABLE, WATER
PROOF WHILE IN USE ENCLOSURE. INTERMATIC MODEL
#WP1010HMC, OR APPROVED EQUAL.
EXISTING EMERGENCY BATTERY PACK
EXISTING EMERGENCY HEAD
IN-WALL, FOUR-WAY SWITCHS
FRACTIONAL HORSEPOWER MANUAL STARTER W/ RED PILOT
LIGHT, ONE POLE FOR 120 VOLT CIRCUIT, TWO POLE FOR 208 VOLT
CIRCUIT. PROPERLY SIZE CLASS 20 OVERLOAD AT 125%
OF FULL LOAD AMP OF EQUIPMENT.
S
CEILING MOUNTED RECEPTACLE
WIRED GARAGE DOOR OPERATOR
MOTOR, # = HORSEPOWER, F = FRACTIONAL
EXISTING DEVICE (SHOWN DASHED) TO BE REMOVED/SALVAGED/DEMO
EXISTING DEVICE (SHOWN LIGHT) TO REMAIN/REINSTALLED
PROVIDE NEW DEVICE/EQUIPMENT (SHOWN RED)
SWITCHING ZONE, IF NONE CONNECT TO ALL
LUMINAIRES IN THE ROOM
sc SECURITY CAMERA
MOTION SENSOR
HEAT DETECTOR
M
G
ATS-1, NEW INTERIOR TYPE 1,
120/240V,1P,3W, 200A, 3 POLE, SERVICE
ENTRANCE RATED, ATS DESIGN BASIS:
GENERAC:TX301, OR APPROVED EQUAL. 200A
3#3/0 & 1#4
GRD., 2" C.
200A
3#3/0 & 1#4
GRD., 2" C.
AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
PLAN TITLE:
AutoCAD SHX Text
PROJECT TITLE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 01/14/25
AutoCAD SHX Text L22-24
AutoCAD SHX Text
TOWNSHIP MAINTENANCE FACILITY
AutoCAD SHX Text
LONGSWAMP TOWNSHIP BERKS COUNTY PENNSYLVANIA
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 02-11-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR PERMITS
AutoCAD SHX Text
102 LONGSDALE DRIVE BUILDING ADDITION
AutoCAD SHX Text
SEAL:
AutoCAD SHX Text 09-01-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR BIDDING
AutoCAD SHX Text
CJD
AutoCAD SHX Text
CRS
AutoCAD SHX Text
ELECTRICAL-ONELINE & SCHEDULES
AutoCAD SHX Text
AutoCAD SHX Text 4,b
AutoCAD SHX Text T
AutoCAD SHX Text F
H
Br od he ad
R oa d, S ui te
Be th le he m , P
A
7-
.6
.5
F:
0.
1.
H an ov er En g.
co m
Be th le he m O ffi ce
9165.003
E-
16.1 GENERAL DESCRIPTION
1. PLANS AND SPECIFICATIONS
A. THE PLANS AND SPECIFICATIONS ARE CONTRACT BID DOCUMENTS, AND ARE FOR THE PURPOSE OF ILLUSTRATING THE GENERAL CHARACTER AND SCOPE OF WORK FOR CONTRACTORS TO PREPARE A BID PROPOSAL. THE PLANS ARE NOT SHOP DRAWINGS AND DO NOT DISMISS THE CONTRACTOR FROM THE RESPONSIBILITY OF PREPARING FABRICATION AND INSTALLATION SHOP DRAWINGS, NOR DO THEY RELIEVE THE CONTRACTOR FROM THE RESPONSIBILITY OF COORDINATING WITH THE WORK OF OTHER TRADES AND THE BUILDING
STRUCTURE.
2. SUBMITTALS
A. COORDINATION: COORDINATE PREPARATION AND PROCESSING OF SUBMITTALS WITH PERFORMANCE OF CONSTRUCTION ACTIVITIES.
TRANSMIT EACH SUBMITTAL SUFFICIENTLY IN ADVANCE OF PERFORMANCE OF RELATED CONSTRUCTION ACTIVITIES TO AVOID DELAY.
B. SUBMITTAL PREPARATION: PLACE A PERMANENT LABEL OR TITLE BLOCK ON EACH SUBMITTAL FOR IDENTIFICATION. INDICATE THE NAME
OF THE ENTITY THAT PREPARED EACH SUBMITTAL ON THE LABEL OR TITLE BLOCK.
C. COLLECT PRODUCT DATA INTO A SINGLE SUBMITTAL FOR EACH ELEMENT OF CONSTRUCTION OR SYSTEM. PRODUCT DATA INCLUDES PRINTED INFORMATION, SUCH AS MANUFACTURER'S INSTALLATION INSTRUCTIONS, CATALOG CUTS, STANDARD COLOR CHARTS, ROUGHING-IN DIAGRAMS AND TEMPLATES, STANDARD WIRING DIAGRAMS, AND PERFORMANCE CURVES. WHERE PRODUCT DATA MUST BE SPECIALLY PREPARED BECAUSE STANDARD PRINTED DATA IS NOT SUITABLE FOR USE, SUBMIT AS "SHOP DRAWINGS." SUBMIT PRODUCT
DATA FOR THE FOLLOWING:
1) LIGHTING LUMINAIRES
2) LIGHTING CONTROLS
3) WIRING DEVICES
4) PANELBOARDS
5) WIRE AND CABLE
6) CONDUIT RACEWAYS
D. SUBMIT OPERATION AND MAINTENANCE DATA FOR EACH TYPE OF PRODUCT SPECIFIED IN 1) TO 6) ABOVE FOR INCLUSION IN AN OPERATION
AND MAINTENANCE MANUAL.
E. INCLUDE FM GLOBAL DATA SHEETS FOR EQUIPMENT.
F. RECORD DRAWINGS: SUBMIT TWO COPIES OF AS-BUILT DRAWINGS.
3. WARRANTY
A. THE CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE, IN WRITING, ALL WORK, ARTICLES, APPLIANCES, MATERIALS, EQUIPMENT, AND WORKMANSHIP FURNISHED, INSTALLED, OR SUPPLIED UNDER THIS CONTRACT FOR A PERIOD OF ONE YEAR FROM THE DATE OF
ACCEPTANCE BY THE OWNER.
B. THE CONTRACTOR SHALL ADJUST, REPAIR, OR REPLACE ANY DEFECTIVE PART OF THE SYSTEM WITHOUT COST TO THE OWNER.
4. CODES AND STANDARDS
A. PROVIDE EQUIPMENT AND INSTALLATION IN ACCORDANCE WITH THIS SPECIFICATION AND APPLICABLE REQUIREMENTS OF THE FOLLOWING:
a. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
b. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)
c. AMERICANS WITH DISABILITIES ACT (PUBLIC LAW 101-336)
d. AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
e. NATIONAL ELECTRICAL CODE (NEC)
f. OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA)
g. UNDERWRITERS LABORATORIES INC. (UL)
h. NATIONAL FIRE PROTECTION ASSOCIATION: NATIONAL FIRE CODES (NFPA)
i. IBC 2018, ALL LOCAL CODES AND ORDINANCES
B. THE CONTRACTOR SHALL OBTAIN ALL PERMITS, LICENSES, AND APPROVALS WITH THE DEPARTMENTS HAVING JURISDICTION, PAY ALL CHARGES AND FEES, FILE ALL NECESSARY PLANS, AND GIVE ALL NOTICES NECESSARY AND INCIDENT TO DO THE LAWFUL PROSECUTION OF THE WORK. CONTRACTOR SHALL OBTAIN AND FURNISH TO THE OWNER ALL CERTIFICATES FOR WORK FOR WHICH CERTIFICATES ARE REQUIRED. THE CONTRACTOR SHALL PAY FOR ALL STATE, COUNTY, BOROUGH, AND TOWNSHIP FEES, PERMITS, LICENSES, LAWS, AND/OR OTHER FEES WHICH MAY BE REQUIRED IN THE PERFORMANCE OF HIS CONTRACT AND NOT OTHERWISE PROVIDED FOR.
16.2 CONDUIT
1. ELECTRICAL METALLIC TUBING SHALL BE GALVANIZED STEEL MEETING REQUIREMENTS OF ANSI C80.3. FITTINGS SHALL BE
CORROSION-RESISTANT COMPRESSION TYPE.
2. SHEET METAL BOXES SHALL BE NEMA TYPE 1 GALVANIZED STEEL ENCLOSURE WITH SCREW COVER.
3. CONCEALED OR EXPOSED INTERIOR LOCATIONS: UTILIZE ELECTRICAL METALLIC TUBING ABOVE 10'-0" A.F.F., MINIMUM 3/4" .
4. UNDERGROUND OR IN CONCRETE: UTILIZE PVC, MINIMUM 1".
5. CONDUIT SIZE SHALL BE 3/4", MINIMUM. WHERE SIZE IS NOT SHOWN ON THE DRAWING, INSTALL 3/4" CONDUIT UNLESS RECOMMENDED
OTHERWISE BY THE EQUIPMENT MANUFACTURER.
6. LISTING AND LABELING: METAL CONDUITS, TUBING, AND FITTINGS SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED
TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION.
7. GALVANIZED STEEL RIGID CONDUIT SHALL COMPLY WITH ANSI C80.1 AND UL 6, AND SHALL BE USED SURFACE MOUNTED CONDUIT FROM 0'-0" TO
10'-0" A.F.F. AND FOR ALL EXTERIOR AREAS.
8. LIQUID-TIGHT FLEXIBLE METAL CONDUIT SHALL EMPLOY PVC JACKET, COMPLY WITH UL 360, AND SHALL BE INSTALLED FOR FINAL CONNECTION TO
EQUIPMENT AND INSTRUMENTATION.
9. MAINTAIN MINIMUM 12 INCH CLEARANCE BETWEEN CONDUIT AND HEAT PRODUCING EQUIPMENT. SUPPORT CONDUIT AT DISTANCES NOT
EXCEEDING NEC RECOMMENDATIONS FOR SPECIFIC CONDUIT TYPES INSTALLED.
10. WHERE CONDUIT PENETRATES AN EXTERIOR WALL, THE PENETRATION SHALL BE SEALED WATERTIGHT. WHERE CONDUIT PENETRATES A FIRE RATED WALL, THE PENETRATION SHALL BE SEALED WITH FIRE RESISTANT SEALANT TO MATCH OR EXCEED THE RATING OF THE WALL.
11.CONDUIT ENTRY TO ENCLOSURES, PULL BOXES, OR EQUIPMENT SHALL BE VIA CONDUIT HUB - LISTED FOR INSTALLATION WITH RACEWAY
SYSTEM. DOUBLE LOCKNUTS ARE NOT SUITABLE FOR RACEWAY ENTRANCES.
16.3 WIRE AND CABLE
1. BUILDING WIRE
A. FEEDERS AND BRANCH CIRCUITS: COPPER, STRANDED CONDUCTOR, 600 VOLT INSULATION, TYPE THWN, COMPLYING WITH UL 83.
B. ALL WIRING SHALL BE INSTALLED IN RACEWAY.
2. WIRING CONNECTIONS AND TERMINATIONS
A. SPLICE ONLY IN ACCESSIBLE JUNCTION BOXES.
B. USE SOLDERLESS PRESSURE CONNECTORS WITH INSULATING COVERS FOR STRANDED TO STRANDED WIRE AND INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR SOLID TO STRANDED AND SOLID TO SOLID COPPER WIRE SPLICES AND TAPS, NO. 8 AWG AND
SMALLER.
C. TAPE UNINSULATED CONDUCTORS AND CONNECTORS WITH ELECTRICAL TAPE TO 150 PERCENT OF THE INSULATION VALUE OF THE
CONDUCTOR.
3. WIRE/CABLE IDENTIFICATION
A. LABEL EACH WIRE AT ALL TERMINATION POINTS.
B. THE FOLLOWING COLOR CODING SHALL BE USED THROUGHOUT:
480/277V - 3 PHASE 120/208V - 3 PHASE:
PHASE A - BROWN PHASE A - BLACK
PHASE B - ORANGE PHASE B - RED
PHASE C - YELLOW PHASE C - BLUE
NEUTRAL - WHITE/GRAY NEUTRAL - WHITE
GROUND - GREEN GROUND - GREEN
120/240V - 1 PHASE:
PHASE A - BLACK
PHASE B - RED
NEUTRAL - WHITE
GROUND - GREEN
4. METAL CLAD CABLE
A. FACTORY ASSEMBLY OF ONE OR MORE CURRENT-CARRYING INSULATED CONDUCTORS IN AN OVERALL METALLIC SHEATH.
B. COMPLY WITH UL 1569
C. LISTED AND LABELED AS DEFINED IN NFPA 70.
D. CONDUCTOR INSULATION TYPE THHN/THWN-2; COMPLY WITH UL 83.
5. CABLE TESTING
A. ALL NEW CABLES, INCLUDING ALL TERMINATIONS SHALL BE TESTED AFTER INSTALLATION, AND PRIOR TO BEING ENERGIZED.
B. CABLE TEST SHALL CONSIST OF A CONDUCTOR CONTINUITY TEST FOR ALL CABLES 600 VOLTS AND BELOW.
C. TORQUE TEST ALL CONDUCTOR TERMINATIONS AND CONNECTIONS TO CABLE AND EQUIPMENT PER MANUFACTURER'S SPECIFICATIONS.
D. CORRECT MALFUNCTIONING PRODUCTS AT SITE, WHERE POSSIBLE, AND RETEST TO DEMONSTRATE COMPLIANCE; OTHERWISE, REMOVE
AND REPLACE WITH NEW AND RETEST.
6. APPLICATIONS
A. CONCEALED INTERIOR LOCATIONS: BUILDING WIRE IN RACEWAYS, OR MC CABLE IN ACCORDANCE WITH NEC REQUIREMENTS.
B. EXPOSED INTERIOR LOCATIONS: BUILDING WIRE IN RACEWAYS. EMT ABOVE 10'-0"A.F.F., RGS BELOW 10'-0" A.F.F.
C. EXTERIOR LOCATIONS: BUILDING WIRE IN RACEWAYS (RIGID GALVANIZED STEEL (RGS) CONDUIT).
16.4 PANELBOARDS
1. BASIS OF DESIGN: SQUARE D
2. BUS STRUCTURE AND MAIN LUGS AS SHOWN ON ONE-LINE DIAGRAM AND PANEL SCHEDULE.
3. CIRCUIT BREAKERS SHALL BE BOLT-ON, THERMAL-MAGNETIC, MOLDED CASE CIRCUIT BREAKERS. BREAKERS SHALL BE 1, 2, OR 3 POLES WITH AN INTEGRAL CROSSBAR TO ASSUME SIMULTANEOUS OPENING OF ALL POLES IN MULTIPLE POLE CIRCUIT BREAKERS. CIRCUIT BREAKERS SERVING
MECHANICAL LOADS SHALL BE UL LISTED TYPE HACR.
4. SHORT CIRCUIT RATING SHALL BE MINIMUM 10,000 RMS SYMMETRICAL AMPERES @ 120/208V, AND 14,000 RMS SYMMETRICAL AMPERES @ 277/480V.
5. BRANCH CIRCUIT PANELBOARDS SHALL BE LISTED BY UNDERWRITER'S LABORATORIES AND SHALL BEAR THE UL LABEL.
6. CIRCUIT BREAKERS PROVIDED FOR EXISTING PANELBOARDS SHALL BE COMPATIBLE WITH EXISTING PANELBOARD AND SHALL MEET THE SHORT
CIRCUIT RATING OF THE EXISTING PANELBOARD.
16.5 BOXES
1. PROVIDE ELECTRICAL BOXES AS REQUIRED FOR SPLICES, TAPS, EASE OF WIRE PULLING, EQUIPMENT CONNECTIONS, AND CODE COMPLIANCE, WHETHER OR NOT SPECIFICALLY SHOWN ON THE DRAWINGS. VERIFY AND COORDINATE THE LOCATION OF ALL BOXES AND OUTLETS WITH OTHER
TRADES.
16.6 LIGHTING
1. PROVIDE LIGHTING LUMINAIRES AND ASSOCIATED CONTROLS AS INDICATED ON THE CONTRACT DRAWINGS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR TRAINING OWNER'S PERSONNEL FOR OPERATION AND MAINTENANCE OF ALL LUMINAIRES AND
ASSOCIATED CONTROLS PROVIDED AS PART OF THIS PROJECT. CONTRACTOR SHALL COORDINATE TRAINING REQUIREMENTS WITH SUPPLIER IF
NECESSARY.
3. AFTER INSTALLING LUMINAIRES, SWITCHES, AND ACCESSORIES, AND AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED, TEST UNITS TO
CONFIRM PROPER OPERATION.
4. TEST FOR EMERGENCY LIGHTING: INTERRUPT POWER SUPPLY TO DEMONSTRATE PROPER OPERATION. VERIFY TRANSFER FROM NORMAL POWER
TO EMERGENCY POWER.
16.6.2 WIRING DEVICES
1. RECEPTACLES SHALL BE SPECIFICATION GRADE. THE FACE AND BACKBODY OF THE RECEPTACLE SHALL BE OF HIGH-IMPACT THERMOPLASTIC.
THE CONTACTS SHALL BE TRIPLE WIPE, T-SLOT, ONE-PIECE COPPER ALLOY DESIGN. THE RECEPTACLE SHALL INCLUDE A GREEN GROUND SCREW ATTACHED TO THE INTO THE BODY OF THE RECEPTACLE. RECEPTACLES SHALL BE RATED 20-AMPERE, 125-V AC, NEMA CONFIGURATION 5-20R, SIDE WIRED WITH AN BLACK FINISH.
2. GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLES (GFCI) SHALL HAVE A NYLON FACE AND A THERMOPLASTIC BACKBODY. GFCI RECEPTACLES SHALL BE UL CLASS A WITH A 5-MILLIAMPERE, GROUND-FAULT TRIP LEVEL. GFCI RECEPTACLES SHALL BE RATED 20-AMPERE, 125-V AC, NEMA CONFIGURATION 5-20R, SIDE WIRED WITH AN BLACK FINISH.
3. WALL SWITCHES SHALL BE HARD USAGE, SPECIFICATION GRADE, QUIET TYPE. THE BODY OF THE SWITCH SHALL BE CONSTRUCTED OF AN ARC-RESISTANT THERMOSET MATERIAL. THE TOGGLE SWITCH HANDLE SHALL BE CONSTRUCTED OF A THERMOPLASTIC MATERIAL SUCH AS "LEXAN". THE CONTACT ARMS SHALL BE OF A ONE-PIECE COPPER ALLOY MATERIAL. THE SWITCH SHALL ALSO INCLUDE A GREEN GROUND SCREW ATTACHED TO THE MOUNTING STRAP. SWITCHES SHALL BE RATED 20-AMPERE, 120-277-V AC, SIDE WIRED WITH AN BLACK FINISH.
4. GENERAL USE WALL PLATES SHALL BE TYPE 302 SATIN STAINLESS STEEL. THE PLATE SHALL BE OF A MODERN DESIGN WITH ROUNDED EDGES
AND CORNERS.
5. REPLACE RECEPTACLES AT EXISTING LOCATIONS.
16.7 SECONDARY GROUNDING
1. ELECTRICAL GROUNDING SYSTEM SHALL FULLY COMPLY WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE - ARTICLE 250.
2. CONNECT ALL NONCURRENT CARRYING METAL PARTS SUCH AS METAL CONDUITS, RACEWAYS, OUTLET BOXES, CABINETS, SUPPORTS, AND
SIMILAR PARTS OF ALL ELECTRICAL EQUIPMENT AND APPARATUS TO THE GROUNDING SYSTEM.
3. EQUIPMENT GROUNDING CONDUCTORS: COMPLY WITH NEC ARTICLE 250 FOR TYPES, SIZES, AND QUANTITIES OF EQUIPMENT GROUNDING CONDUCTORS, EXCEPT WHERE SPECIFIC TYPES, LARGER SIZES, OR MORE CONDUCTORS THAN REQUIRED BY NEC ARE INDICATED.
4. PROVIDE A SEPARATE, GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR FOR ALL FEEDER AND BRANCH CIRCUITS. TERMINATE EACH ON
A GROUNDING LUG, BUS, OR BUSHING.
16.8 ELECTRICAL IDENTIFICATION
1. ALL WIRE AND CABLE SHALL BE MARKED. POWER CABLES SHALL BE COLOR CODED AS NOTED IN PARAGRAPH 16.3.3.B. CONTROL AND
INSTRUMENTATION WIRE SHALL BE NUMBERED AT BOTH ENDS.
2. ENGRAVED THREE-LAYER LAMINATED PLASTIC, BLACK LETTERS ON A WHITE BACKGROUND.
3. PROVIDE NAMEPLATES TO IDENTIFY ALL ELECTRICAL DISTRIBUTION AND CONTROL EQUIPMENT, AND LOADS SERVED. PANELBOARDS SHALL HAVE PANEL NAME, AMPERAGE, AND VOLTAGE PROVIDED ON FRONT COVER OF PANEL. PANELS SHALL BE PROVIDED WITH TYPED CIRCUIT
DIRECTORIES IDENTIFYING ALL LOADS SERVED.
4. ALL NEW LIGHTING CONTROL EQUIPMENT SHALL BE PROPERLY IDENTIFIED.
5. PROVIDE SELF-ADHESIVE WARNING LABELS, FACTORY PRINTED, MULTICOLOR, CONFIGURED FOR DISPLAY ON FRONT COVER, DOOR OR OTHER ACCESS TO EQUIPMENT. WARNING LABELS AND SIGNS SHALL INCLUDE THE FOLLOWING LEGENDS:
A. EACH NEW PANELBOARD: "WARNING: POTENTIAL ARC-FLASH HAZARDS EXIST WHILE WORKING ON THIS ENERGIZED EQUIPMENT".
B. WORKSPACE CLEARANCE: "WARNING: OSHA REGULATION - AREA IN FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 42
INCHES".
16.9 GENERATOR AND AUTOMATIC TRANSFER SWITCH
1. BASIS OF DESIGN; GENERAC: GENERATOR:XG04845 48kW, 200AMP, 120/240VAC, SINGLE PHASE, 3 WIRE, TYPE 3R QUIET ENCLOSURE (58dB
@OPERATING SPEED, NO LOAD @23FT); OR APPROVED EQUAL.
2. PACKAGED PROPANE ENGINE GENERATOR SYSTEM SHALL INCLUDE ENGINE GENERATOR, ATS, COOLING SYSTEM, COMBUSTION AIR INTAKE AND ENGINE EXHAUST SYSTEMS, STARTING SYSTEM, AND THE FOLLOWING ADDITIONAL FEATURES: BATTERY CHARGER, GENERATOR SET MAIN CIRCUIT BREAKER, ENGINE BLOCK HEATER, REMOTE E-STOP, BASEFRAME BLOCKOFF KIT, ENGINE FLUID CONTAINMENT KIT, AND ENGINE
EXHAUST PIPING AND INSULATION.
3. POWERZONE 410 CONTROLLER, NFPA 110 SYSTEM CAPABLE, CORROSION RESISTANT ALUMINUM ENCLOSURE, ELECTRO-GALVANIZED BASEFRAME W/ STAINLESS STEEL EXHAUST SYSTEM. EPA EMISSION CERTIFIED, UL 2200 LISTED, HIGH MOTOR STARTING AND SURGE CAPACITY, RATINGS: 48 KW, 120/240 VAC, 200AMP, SINGLE PHASE, 60 Hz. 5 YEAR/2,000 HOUR LIMITED WARRANTY.
4. ENGINE: THE ENGINE SHALL BE 4 CYCLE, RADIATOR AND FAN COOLED. GOVERNOR:ELECTRONIC, FREQUENCY REGULATION: ISOCHRONOUS.
5. AC GENERATOR: SYNCHRONOUS, ROTOR INSULATION CLASS 'F', STATOR INSULATION CLASS 'H', SEALED BEARING, FLEXIBLE DISC COUPLING, DIRECT EXCITATION SYSTEM, TOTAL HARMONIC DISTORTION <5%. DIGITAL VOLTAGE REGULATION, SENSING OF ALL PHASES, REGULATION 1%
ABOVE OR BELOW RATED VOLTAGE.
6. COOLING SYSTEM: WATER PUMP BELT DRIVEN, SKID MOUNTED RADIATORS RATED FOR FULL LOAD OPERATION IN 122°F AMBIENT AS MEASURED AT THE GENERATOR AIR INLET. RADIATOR W/ ELECTRIC FAN SHALL BE BY 50/50 ETHYLENE GLYCOL/WATER MIXTURE BY THE EQUIPMENT
SUPPLIER.
7. FUEL SUPPLY SYSTEM: PROPANE.
8. STARTING AND CONTROL BATTERIES: 12 VOLT. STARTING BATTERY BANK FLOODED LEAD ACID, GROUP 27, 600 CCA MIN.
BATTERY CHARGER: 5 AMP.
9. GENERATOR MAIN CIRCUIT BREAKER: SET MOUNTED & WIRED; UL LISTED, MOLDED CASE 200 AMP, 42,000AIC.
10. SURGE CAPACITY 15% VOLTAGE DIP 220A, 30% VOLTAGE DIP 340A.
11.COLOR: METRO GRAY
AUTOMATIC TRANSFER SWITCH
12. BASIS OF DESIGN: GENERAC TX301, 200AMP, 120/240VAC, SINGLE PHASE, TYPE 1, 3 POLE, SERVICE ENTRANCE RATED W/ 200A, 42,000 AIC MOLDED
CASE CIRCUIT BREAKER ; OR APPROVED EQUAL.
13. TRANSFER SWITCH COMPLETE WITH ACCESSORIES SHALL BE UL LISTED. SOLID STATE CONTROLS: REPETITIVE ACCURACY OF ALL SETTINGS
PLUS OR BETTER OVER AN OPERATING TEMPERATURE RANGE OF MINUS -20°C TO 70°C.
14. TRANSFER SWITCH FEATURES:
A. SMALL FOOTPRINT, RESULTS IN EASY MOUNTING AND
B. INSTALLATION FOR REDUCED TIME AND COSTS
C. DOUBLE-THROW, STORED ENERGY TRANSFER MECHANISM
D. CAN BE ELECTRICALLY ISOLATED WHILE ENERGIZED
E. GRAPHICAL LCD-BASED DISPLAY FOR PROGRAMMING, SYSTEM DIAGNOSTICS AND HELP MENU DISPLAY MIMIC
F. DIAGRAM WITH SOURCE AVAILABLE AND CONNECTED LED INDICATOR
G. METHOD OF TRANSFER: OPEN WITH INPHASE TRANSITION
H. MECHANICALLY INTERLOCKED TO PREVENT CONNECTION OF BOTH SOURCES
I. MODBUS® RTU COMMUNICATIONS
J. TXC 100 CONTROLLER
K. OPERATING TEMPERATURE -4 ° TO 158 °F
L. REMOVABLE TOP AND BOTTOM PLATES FOR EASE OF ENTRY
M. HIGH WITHSTAND AND CLOSING RATINGS
N. AUXILIARY OUTPUT INCLUDES: TWO WIRE START, SIGNAL BEFORE TRANSFER, FAULT, AND A PROGRAMMABLE RELAY OUTPUT
O. AUXILIARY INPUT INCLUDES: PERMISSIVE INPUTS (24 VDC)
P. GENERAL ALARM INDICATION
Q. 2 YEAR STANDARD WARRANTY
R. IBC 2018, 2015, 2012, 2009
16.10 TESTING
1. AFTER ELECTRICAL INSTALLATION IS COMPLETE, MAKE TESTS TO DEMONSTRATE THAT ENTIRE SYSTEM IS IN PROPER WORKING ORDER AND IN ACCORDANCE WITH DRAWINGS AND SPECIFICATIONS. MAKE NO TESTS LESS THAN OUTLINED HEREAFTER, UNLESS REQUESTED IN WRITING AND APPROVED BY THE OWNER. TESTS ARE IN ADDITION TO AND NOR A SUBSTITUTION FOR TESTS OF INDIVIDUAL ITEMS.
2. TESTING SHALL BE PER NETA ATS.
3. PAY ALL COSTS FOR TESTS, INCLUDING COSTS TO RETEST OCCASIONED BY DEFECTS AND FAILURES OF EQUIPMENT TO MEET SPECIFICATIONS.
A. REPLACE WIRING AND EQUIPMENT FOUND DEFECTIVE, OR FAILING TO MEET SPECIFIED REQUIREMENTS, WITHOUT CHARGE, UNLESS
WRITTEN ACCEPTANCE FOR REPAIR IS GIVEN BY OWNER.
B. FURNISH THREE COPIES OF ALL TEST RESULTS TO OWNER.
4. CALIBRATION: FURNISH SUITABLE ELECTRICAL INSTRUMENTS, INCLUDING VOLTMETERS, AMMETERS, WATTMETERS, AND ALL OTHER EQUIPMENT NECESSARY TO PERFORM TESTS SPECIFIED. MAKE NECESSARY OPENINGS IN CIRCUITS FOR TESTING INSTRUMENTS AND PLACE AND CONNECT ALL INSTRUMENTS, EQUIPMENT, AND DEVICES, NECESSARY FOR THE TESTS. UPON COMPLETION OF TESTS, REMOVE INSTRUCTIONS AND INSTRUMENT CONNECTIONS AND RESTORE ALL CIRCUITS TO PERMANENT CONDITION. CONDUCT TESTS IN PRESENCE OF OWNER.
5. TESTS:
A. INSULATION RESISTANCE TESTS OF CIRCUITS, 600 VOLTS AND BELOW:
B. DO NOT SUBJECT CONDUCTORS RATED 600 VOLTS AND BELOW TO HIGH POTENTIAL DIELECTRIC TESTS. TEST COMPLETE FEEDER AND
BRANCH CIRCUIT OF 600 VOLTS OR BELOW WITH EVERYTHING BUT POWER SUPPLY AND POWER-CONSUMING EQUIPMENT, CONNECTED
THERETO.
C. DETERMINE INSULATION RESISTANCE VALUES WITH ALL SWITCHES AND OVERCURRENT DEVICES IN PLACE.
D. USE MEGOHMETER HAVING OUTPUT OF AT LEAST 500 VOLTS TO DETERMINED INSULATION RESISTANCE VALUE FOR 600 VOLT RATED
CONDUCTORS.
E. ALL CABLES FAILING INSULATION TEST SHALL BE REMOVED, REPLACED, AND RE-TESTED.
F. WHERE TESTS OF ANY OF THE ABOVE-REFERENCED EQUIPMENT ARE INCLUDED IN OTHER SECTIONS OF SPECIFICATIONS, COORDINATE
TESTING, AS DIRECTED BY OWNER, TO AVOID DUPLICATION AND CONFLICT BETWEEN TESTS.
G. PERFORM ABOVE TESTS IN ADDITION TO, AND NOT IN SUBSTITUTION FOR REQUIRED MANUFACTURER'S FACTORY TESTS.
5. OPERATING TESTS:
A. OPERATE CIRCUIT BREAKERS AND CONTROL DEVICES TO SHOW CORRECT AND SATISFACTORY OPERATIONS.
B. WHERE TESTS OF ANY OF THE ABOVE-REFERENCED EQUIPMENT ARE INCLUDED IN OTHER SECTIONS OF SPECIFICATIONS, COORDINATE
TESTING, AS DIRECTED BY OWNER, TO AVOID DUPLICATION AND CONFLICT BETWEEN TESTS.
AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
PLAN TITLE:
AutoCAD SHX Text
PROJECT TITLE:
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text 01/14/25
AutoCAD SHX Text L22-24
AutoCAD SHX Text
TOWNSHIP MAINTENANCE FACILITY
AutoCAD SHX Text
LONGSWAMP TOWNSHIP BERKS COUNTY PENNSYLVANIA
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text 02-11-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR PERMITS
AutoCAD SHX Text
102 LONGSDALE DRIVE BUILDING ADDITION
AutoCAD SHX Text
SEAL:
AutoCAD SHX Text 09-01-26
AutoCAD SHX Text
AutoCAD SHX Text
ISSUED FOR BIDDING
AutoCAD SHX Text
CJD
AutoCAD SHX Text
CRS
ELECTRICAL-SPECIFICATIONS
| Sheets and Views |
| ED-101-paper |
| EL-101-paper |
| EP-101-paper |
| E-601-paper |
| E-602-paper |