2D RLP 36C10F24R0007 Appendix A_3 Room Data Matrix RDM Sarasota FL OPC 1_26_2024.pdf

PDF 289 KB Posted

Attached to
X1DB--Sarasota Outpatient Clinic (PACT ACT) 131, 724 ANSI/BOMA
Solicitation number
36C10F24R0007
Issued by

About this file

This document contains a room data matrix and specifications for the Sarasota Outpatient Clinic (PACT ACT) project solicited by the Department of Veterans Affairs Office of Construction and Facilities Management under solicitation number 36C10F24R0007. The matrix includes over 100 individual rooms and spaces with requirements for interior finishes, doors, hardware, mechanical, electrical, and communications systems. Key areas covered include exam rooms, procedure rooms, imaging services, audiology, dental, pharmacy, physical therapy, laboratory, imaging, police services, logistics, and information technology infrastructure spaces. Specifications address acoustics, power and data requirements, lighting controls and interior construction details. The level of technical requirements indicates this is a design-build project for a new outpatient healthcare facility.

View the file

Other files

File Type Posted
36C10F24R0007_2.docx DOCX document
36C10F24R0007 - Sarasota FL OPC - RLP Amendment 2 - Q_A Matrix - 2.26.2024.pdf PDF
2D 36C10F24R0007 - Sarasota FL OPC - RLP Amendment No 2 - Room Data Matrix - 2.26.2024.xlsx XLSX spreadsheet
36C10F24R0007 - Sarasota FL OPC - RLP Amendment 2 - Pre-bid Meeting Presentation - 2.8.2024.pdf PDF
36C10F24R0007 - Sarasota FL OPC - RLP Amendment No 2 - 2.26.2024.pdf PDF
36C10F24R0007 - Sarasota FL OPC - RLP Amendment 2 - Pre-Bid Attendance Sheets - 2.8.2024.pdf PDF
36C10F24R0007 - Sarasota FL OPC - RLP Amendment 2 -Pre-Bid Meeting Transcript - 2.8.2024.pdf PDF
36C10F24R0007_1.docx DOCX document
36C10F24R0007 - Sarasota FL OPC - Amendment No 1 - 1 February 2024.pdf PDF
0 RLP 36C10F24R0007 RLP Sarasota FL OPC 1_26_2024.pdf PDF
36C10F24R0007.docx DOCX document
5 RLP 36C10F24R0007 Offering Entity Acknowledgement Form Sarasota FL OPC 1_26_2024.pdf PDF
2F RLP 36C10F24R0007 Appendix A_4_1 OIT Data Center Design Narrative Sarasota FL OPC 1_26_2024.pdf PDF
15 RLP 36C10F24R0007 GSA Template 3516 Solicitation Provisions Sarasota FL OPC 1_26_2024.pdf PDF
17 RLP 36C10F24R0007 GSA Form 12000 for Prelease FPLS Evaluation Sarasota FL OPC 1_26_2024.pdf PDF
14 RLP 36C10F24R0007 VA Handbook 6500_6 Appendix D VA Rules of Behavior Sarasota FL OPC 1_26_2024.pdf PDF
3 RLP 36C10F24R0007 Appendix A_6 Conceptual Floor Plan Sarasota FL OPC 1_26_2024.pdf PDF
8 RLP 36C10F24R0007 Attachment No 1 to GSA Form 1364 Sarasota FL OPC 1_26_.2024.xlsx XLSX spreadsheet
7 RLP 36C10F24R0007 Proposal to Lease Space GSA Form 1364 Sarasota FL OPC 1_26_2024.pdf PDF
2B RLP 36C10F24R0007 Appendix A_1 Project Contents List PRC Sarasota FL OPC 1_26_2024.pdf PDF
9 RLP 36C10F24R0007 GSA Form 1217 Lessors Annual Cost Statement Sarasota FL OPC 1_26_2024.pdf PDF
18 RLP 36C10F24R0007 Certification of Building Energy Performance Sarasota FL OPC 1_26_2024.pdf PDF
2G RLP 36C10F24R0007 Appendix A_5 Facility Level Security FSL II Sarasota FL OPC 1_26_2024.pdf PDF
2A RLP 36C10F24R0007 Appendix A Program for Design PFD Sarasota FL OPC 1_26_2024.pdf PDF
2 RLP 36C10F24R0007 Cover Page for Agency Specific Requirements ASR Sarasota FL OPC 1_26_2024.pdf PDF
13 RLP 36C10F24R0007 GSA Form 527 Contractors Quals and Financial Info Sarasota FL OPC 1_26_2024.pdf PDF
16 RLP 36C10F24R0007 GSA Template 3517B General Clauses Mod General Clauses Sarasota FL OPC 1_26_2024.pdf PDF
20 RLP 36C10F24R0007 Covered Telecom Equip or Services Rep Sarasota FL OPC 1_26_2024.pdf PDF
6 RLP 36C10F24R0007 Offeror Proposal Compliance Matrix Sarasota FL OPC 1_26_2024.pdf PDF
1 RLP 36C10F24R0007 Lease Sarasota FL OPC 1_26_2024.pdf PDF
12 RLP 36C10F24R0007 SF 330 Architect Engineer Qualifications Sarasota FL OPC 1_26_2024.pdf PDF
2E RLP 36C10F24R0007 Appendix A_4 VA CBOC Info Transp Sys Specs Sarasota FL OPC 1_26_2024.pdf PDF
2C.2 RLP 36C10F24R0007 Appendix A_2_2 Bay Pines VAHCS Fixtures Guide Sarasota FL OPC 1_26_2024.pdf PDF
19 RLP 36C10F24R0007 Sarasota County Wage Determination Sarasota FL OPC 1_26_2024.pdf PDF
4 RLP 36C10F24R0007 Appendix B VA Janitorial and Site Management Services Sarasota FL OPC 1_26_2024.pdf PDF
10 RLP 36C10F24R0007 Form VA 10091 VA FSC Vendor File Request Form Sarasota FL OPC 1_26_2024.pdf PDF
21 RLP 36C10F24R0007 Pre bid Conference Registration Form Sarasota FL OPC 1_26_2024.pdf PDF
2C.1 RLP 36C10F24R0007 Appendix A_2_1 Bay Pines VAHCS Finish Standards Dec 2023 Sarasota FL OPC 1_26_2024.pdf PDF
2C RLP 36C10F24R0007 Appendix A_2 Lease Design Narrative LDN Sarasota FL OPC 1_26_2024.pdf PDF
11 RLP 36C10F24R0007 Past Performance Questionnaire Sarasota FL OPC 1_26_2024.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ROOM IDENTIFICATION NOTES

Functional Area DEPARTMENT ROOM NAME ROOM NAMES (VA) FGI EQUIVALENT FOR

ASHRAE 170

FGI EQUIVALENT FOR TABLE

1.2-5 Minimum Sound Isolation

Fl oo r F in is h

B as e

W al l F in is h

W ai ns co t M at er ia l

W ai ns co t H ei gh t

ST

C

C ei lin g

Fi ni sh

H ei gh t

N ot es

Si ze

(W id th

Ty pe

M at er ia l

G la zi ng

R at in g

H ar dw ar e G ro up

H ar dw ar e N ot es

In do or

Te m pe ra tu re

C oo lin g F

In pe ra

H ea tin g F

In do or R el at iv e

H um id ity

R

H M ax

In do or R el at iv e

H um id ity

R

H M in

M in im um

T ot al

A

H

M in im um

O A

A C

H

R oo m A ir R et ur n G en . E xh G

S pe c Ex h S

M ax im um

N oi se

Le ve l N C

R oo m A ir B al an ce

VA

C N ot es

D up le x R ec ep ta cl es

Q ua d

R ec ep ta cl es

Po w er

N ot es

Fi xt ur e

Ty pe

C on tr ol s

Li gh tin g

- S pe ci

R eq ui re m en ts

Li gh tin g

- N ot es

D at a

O ut le ts

(s ta nd ar d de ns ity

W

O

IT

Sp ec ia l

R eq ui re m en ts

0 General Rooms/Spaces Exam Room PACT Exam EXAM EXAMINATION LVT RB P -- -- 55 AT 9'-0" 10

3'-0"

3'-6" Flush Wood _ _ 12 SE 3 8 1

Multilevel Switching, Dimming & Occupancy

Multi-level switching or manual dimming N/A 4 Tele-Health

0 General Rooms/Spaces Exam Room

Exam Room - Multi-Specialty, Exam / Treatment, Exam -

Consult, Consult Room - PACT, Exam/Consult Room (Mental

Health/Social Work), Exam Room EMG/EEG, Exam Room-

Cardiology, Exam/Consult, Nurse Practitioner, Women's Health

Exam, Tele-Health Exam, Optometry Exam Treatment

Room, Eye Lane, Tele-Retinal, TECHS, Applicance Fitting Room, Fitting Room, Physical Therapy Room, Occupational Treatment

Room

EXAM EXAMINATION LVT RB P -- -- 55 AT 9'-0" 10 3'-6" Flush Wood _ _ 12 S 8 1 Multilevel Switching, Dimming & Occupancy

Multi-level switching or manual dimming

At Eye Clinic, connect refraction desk dimming to room lighting control.

0 General Rooms/Spaces Consult Room

Consult Room, Audiology Rehabilitation Counceling Room, Dental Consult Room CONSULTATION LVT RB P -- -- 55 AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 - 4 2 Return 40 NR 6

Multilevel Switching, Dimming & Occupancy

Multi-level switching or manual dimming N/A 4

0 General Rooms/Spaces Procedure Room

Procedure Room, General, Specialty Care, Gynechology, Multi-Specialty Care, Cast Room

PROCEDURE TREATMENT WSF WSF EP RWC 4'-0" 55 AT 9'-0" 3

3'-0"

3'-6" Flush Wood -- -- 12 SE 3 7 P13

Multilevel Switching, Dimming & Occupancy

Wall mounted exam light N/A 4

0 General Rooms/Spaces Laboratory Laboratory (Typical) LABORATORY

WORKROOM __ WSF WSF EP -- -- 40 AT-SP 9'-0" 3 3'-0" Flush Wood _ _ 15 AG 4 6 P3, P4 Multilevel Switching, Dimming & Occupancy

N/A N/A 5

0 General Rooms/Spaces Conference Room

Conference Room, Multi-Purpose Room, Group Room, Shared Medical Appointment Room, Education Room, Staff Training Room, Classroom

__ LVT RB P RWC 4'-0" 40 AT 9'-0" 17 3'-6" Flush Wood _ _ 15 S _ M2 8 P14 Multilevel Switching, Dimming & Occupancy

Provide 4 scene preset dimmable lighting for a variety of tasks. Consider placement and optics to mitigate glare and ceiling reflections

N/A 4 Floor data for table

0 General Rooms/Spaces TOILET

General Toilet, Patient - Toilet, Toilet - Police, Toilet - Family, Toilet - Female Staff, Toilet - Male Staff, Toilet - Procedure

Room, Toilet - Public, Toilet - RF Patient, Toilet - Women's Health, Toilet - Female, Toilet - Family

Assist, Specimen Collection Toilet

TOILET ROOM TOILET ROOM PT PT P CT 7'-0" SEE FGI AT 9'-0" 1,2 3'-6" Flush Wood _ _ 11 _ 1 Downlights/Mirror or vanity Occupancy Sensor N/A N/A 4

0 General Rooms/Spaces OFFICE Any Office -- CONSULTATION LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS 4 1

Multilevel Switching, Dimming & Occupancy

N/A N/A 4

0 General Rooms/Spaces WAITING

Waiting - Family - PACT, Waiting - PACT 3, Waiting - General - 20 People, Waiting - General - 10 People, Waiting - General - 6

People, Waiting-General

EXAM - PUBLIC SPACE LVT RB P -- -- SEE FGI AT 9'-0" 10, 17 M4 -- --

Multilevel Switching, Dimming & Occupancy

N/A N/A 4

0 General Rooms/Spaces RECEPTION

Reception, Information Desk, Travel Window, Reception -

Accessible -- -- LVT RB P -- -- -- AT 9'-0" -- 3'-0" Flush w/ narrow vision Wood _ _ 12 CG 3 M4 1 1 Downlights, pendants, decorative, and accent

Multilevel Switching, Dimming & Occupancy

N/A N/A 10 Data/phone feeds to systems furniture

0 General Rooms/Spaces COPY ALCOVE

Copy Alcove, Copier - Workroom, Copy / Office Supply Room, Copy

Room -- -- Match

Adjacent Match

Adjacent P -- -- -- AT 9'-0" 6 _ _ _ _ _ _ 6 3 Multilevel Switching, Dimming & Occupancy

N/A N/A 4

0 General Rooms/Spaces CLEAN UTILITY

Clean Utility, Clean Supply, Clean Workroom, Clean Linen, Sterile

Storage, CBOC Steril Supply Storage Room, Clean Scope, Dental Clean Cart, Central Sterile

-- -- WSF WSF P RWC 4'-0" -- AT 9'-0" -- 3'-0" Flush Wood -- 45 MIN 121 AG _ 66 75 55 30 4 (+) 1 Occupancy Sensor N/A N/A 2

0 General Rooms/Spaces SOILED UTILITY

Soiled Utility Room, Recycled Material, Soiled Holding, Soiled Linen, Soiled Workroom, Soiled

Supply Soiled Cart

SOILED HOLDING /

SOILED WORK ROOM -- WSF WSF P RWC 4'-0" -- AT 9'-0" 3 3'-0" Flush Wood -- 45 MIN 121 AG _ 2 -- Occupancy Sensor N/A N/A 2

0 General Rooms/Spaces STORAGE

Storage - Medical Equipment, Storage - Shared Medical

Appointments, DME - Prosthetics Storage, Storage - Homeless, EMS Storage, Storage - Bistro/Coffee Bar, Storage -

Patient Clothing and Luggage, Laundry / Storage, Tray Cart Storage Area, Buld Storage, General Storage, Secure Storage

CLEAN

WORKROOM/CLEAN

SUPPLY

LVT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG

1 per wall, not to exceed 12' spacing. Plug mold used in medical equipment storage rooms.

-- Surface or chain mounted 1' x 4' Occupancy Sensor N/A N/A 2

0 General Rooms/Spaces

JANITOR'S CLOSET Housekeeping Aides Closet

(HAC)

ENVIRONMENTAL

SERVICES ROOM

-- PT PT P FRP 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 34 A _ 1 -- Occupancy Sensor N/A N/A --

0 General Rooms/Spaces EQUIPMENT ALCOVE

AED Alcove, Height and Weight Alcove, Scale Alcove, Stretcher Alcove, Med Alcove, Portable

Patient Lift Alcove, Wheelchair Alcove, My Health eVet, Kiosk, -- -- Match Adjacent

Match Adjacent Match Adjacent RWC 4'-0" -- AT Match

Adjacent 3 -- -- -- -- -- 6 1 1 Quad receptacles at My Health eVet alcove

Multilevel Switching, Dimming & Occupancy

N/A N/A 2 My Heralth eVet

0 General Rooms/Spaces STAFF LOUNGE Staff Lounge -- -- LVT RB P -- -- 40 AT 9'-0" 4 3'-0" Flush w/ narrow vision Wood -- -- 13 _ Exh. (G) (-) 8 -- P7 Multilevel Switching, Dimming & Occupancy

N/A N/A 4

0 General Rooms/Spaces MEDICATION ROOM Medication Room MEDICATION ROOM -- LVT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 34 5 1

Multilevel Switching, Dimming & Occupancy

N/A N/A 4

0 General Rooms/Spaces LACTATION ROOM Employee Wellness, Lactation

Room, Quiet Room -- -- LVT RB P -- -- 50 AT 9'-0" 10 3'-0" Flush Wood -- -- 12 CS 4 -- Multilevel Switching, Dimming & Occupancy

N/A N/A 2

0 General Rooms/Spaces LOCKER ROOM

Locker Room, Locker Room (Male/ Female) Locker - Staff

Personal Property, Locker Room - Staff

-- -- LVT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- Push/Pull Exh. (G) (-) 4 -- Multilevel Switching, Dimming & Occupancy

N/A N/A 2

0 General Rooms/Spaces

OFFICE, CUBICLE, Open Office

Cubicle - Administrative, Data Processing, Workstation -

Extended Team, Homeless, HBPC, HUD-VASH, Workstation -

MICHM, Workstation - Suicide Prevention, Workstation - VOC

Rehab, Workstation - Rad Tech, Workstation - Shipping / Receiving, Workstation, Administration (MSA MH; Rad, LPN), Workstation-Sleep Tech, Work Station, Call Center (MSA), Workstation-Cart Case Dispatch, Workstation-Clerical, -- -- CPT RB P -- -- -- AT 9'-0" * Workstations in HBPC 2 per workstation -- P-16

Multilevel Switching, Dimming & Occupancy

N/A N/A 2/workstaton

0 General Rooms/Spaces SUB-WAITING

Sub-Waiting, MRI Sub-Waiting, CT Sub-Waiting, Mammo Sub-

Waiting, Sub-Waiting - Diagnostic Patient, Sub-Waiting - Dilation Patient, CT Vestibule, Waiting, Waiting-Zone 1, Sub-Waiting-

Zone 2

-- -- LVT RB P -- -- -- AT 9'-0" 10, 17 -- -- -- -- -- - 6 M4 4 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 2

0 General Rooms/Spaces VENDING Vending Machine Area LVT RB P -- -- -- AT 9'-0" -- -- -- -- -- -- 6 M4 8 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 4

0 General Rooms/Spaces TOILET/SHOWER ROOM

Toilet/Shower-Staff, Toilet/Shower-Patient, Toilet/Shower-Female Staff, Toilet/Shower-Male Staff

TOILET ROOM TOILET ROOM PT PT CT -- -- SEE FGI GWB/P 9'-0" 2, 19 3'-6" Flush Wood -- -- 11 G 2 -- Multilevel Switching, Dimming & Occupancy

N/A N/A

0 General Rooms/Spaces CHANGING ROOM Dressing room RFT RB P -- -- 40 AT 9'-0" 3'-6" Flush Wood -- -- 11 K 75 70 60 - 4 2 Return NR NR 1 --

Multilevel Switching, Dimming & Occupancy

N/A N/A 1

3 Primary Care, Specialty Care, PACT

PACT TEAM WORK

SPACE

PACT Team Work Space, Team Work Area- Home Based Primary

Care -- CPT RB P -- AT 9'-0" -- _ _ _ _ _ 14 MP 6 M3 2 per workstation --

Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting

N/A 1 per workstation Data/phone feeds to systems furniture

3 Primary Care, Specialty Care, PACT EXAM ROOM Exam, Negative Pressure AII Room EXAMINATION WSF WSF P -- -- SEE FGI GWB:P 9'-0" 3,7 3'-6" Flush Wood -- -- 12 S 6 -- Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 2

5 Audiology and SLP AUDIOLOGY HEARING AID

TESTING

Hearing Aid Lab, Hearing Aid Processing, Hearing Aid Repair -- LVT RB P -- -- 40 AT 9'-0" -- 3'-0" Flush Wood _ _ 15 S _ 75 70 60 - Exh. (G) (-) 7 0 P4 Multilevel Switching, Dimming & Occupancy N/A N/A 4

5 Audiology and SLP AUDIOLOGY HEARING AID

FITTING

Audiology Programming / Fitting, Hearing Aid Fitting Room, Cerumen Management Room, Speech Language Pathology Assistive Technology Romm, Speech Language Pathology

Voice Treatment Room

EXAM -- LVT RB P -- -- 60 AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 Multilevel Switching, Dimming & Occupancy N/A N/A 4

5 Audiology and SLP AUDIOMETRIC EXAM

BOOTH

Audiometric Exam Suite, Exam - Audiometric Booth, Aud: Suite -

Audiometric Exam, Hearing/Diagnostics, Booth, 1-

Person

EXAM -- Pre-Fab Pre-Fab Pre-Fab -- -- SEE EQUIP LIST Pre-Fab 8'-0" -- 3'-0"

3'-6"

Pre-Fab Pre-Fab _ _ 1 2,4 9 P1

Typically pre-packaged unit including lighting and switching

N/A L1 5

5 Audiology and SLP ELECTROPHYSIOLOGY Electrophysiology, Posturography, Vestibulography EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 P2, P3, P14 Multilevel Switching, Dimming & Occupancy N/A N/A 4

6 Dental Service SPECIALTY EQUIPMENT

MECHANICAL ROOM

Dental Equipment Mech. Room, Mechanical Rooms - Electrical -- -- VT RB P -- -- 60 EXP 9'-0" 3'-6" Flush Wood -- -- 14 S Exh. (G) (-) 2 -- P3 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4

6 Dental Service DENTAL PROSTHETICS LABORATORY Laboratory, Dental Prosthetics -- RF RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 15 AG 75 70 60 20 6 2

Return Exh. (G) 45 (-) M13 7 -- Multilevel Switching, Dimming & Occupancy N/A N/A 5

6 Dental Service DENTAL TREATMENT

ROOM

Dental Treatment Room (DTR), Multi-Functional (4/Hygiene), Special Needs Patient, Bariatric EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS (+) 7 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

6 Dental Service DENTAL X-RAY ROOM X-Ray Room, Panoramic / Cephalometric (Cone Beam) CLASS 1 IMAGING ROOM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 17 AGL 8 7 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4

7 Optometry FITTING & DISPENSING, EYEGLASSES Fitting & Dispensing, Eyeglasses -- LVT RB P -- -- -- AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S 6 75 70 60 - 4 2 Return 40 NR 2 Downlights and accent/display Multilevel Switching, Dimming & Occupancy N/A N/A 4

7 Optometry LOW VISION EXAM/

THERAPY/ TRAINING

Low Vision Exam/ Therapy/ Training EXAM EXAMINATION LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting

N/A 4

7 Optometry PRE-TESTING/ INTAKE Pre-Testing/ Intake EXAM EXAMINATION LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 1 Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting

N/A 4

7 Optometry VISUAL FIELDS ROOM

Visual Fields Room, Photography Room, Ultrasound Room, Tomography Room, Imaging Room, OCT Laser

EXAM EXAMINATION LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 7 Multilevel Switching, Dimming & Occupancy

Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting

N/A 4

8 Mental Health QUIET ROOM Quiet Room for Patients EXAM TREATMENT CPT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

8 Mental Health BIOFEEDBACK TREATMENT ROOM Biofeedback Treatment Room EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 15 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

9 Specialty Care Services

PULMONARY FUNCTION

ROOM Pulmonary Function - Analysis EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 G 6 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

9 Specialty Care Services TREADMILL ROOM Treadmill Room EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 MS 6 -- P9 Multilevel Switching, Dimming & Occupancy N/A N/A 4

9 Specialty Care Services EKG TESTING ROOM EKG Testing Room EXAM EXAMINATION LVT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 12 S One per wall -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

9 Recreation Therapy GROUP THERAPY ROOM, MUSIC

Creative Arts - Group Therapy Room - Music -- TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

9 Recreation Therapy GROUP THERAPY ROOM, ART

Creative Arts - Group Therapy Room - Large -- TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

9 Recreation Therapy WEIGHT ROOM, SMALL Recreation Therapy Exercise / Weight Room - Small -- TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 34 AG 12 -- Multilevel Switching, Dimming & Occupancy N/A N/A 1

ROOM DATA MATRIX

FLOOR WALLS CEILING

IT

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING

INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

ROOM IDENTIFICATION NOTES

Functional Area DEPARTMENT ROOM NAME ROOM NAMES (VA) FGI EQUIVALENT FOR

ASHRAE 170

FGI EQUIVALENT FOR TABLE

1.2-5 Minimum Sound Isolation

Fl oo r F in is h

B as e

W al l F in is h

W ai ns co t M at er ia l

W ai ns co t H ei gh t

ST

C

C ei lin g

Fi ni sh

H ei gh t

N ot es

Si ze

(W id th

Ty pe

M at er ia l

G la zi ng

R at in g

H ar dw ar e G ro up

H ar dw ar e N ot es

In pe ra oo lin g F

In pe ra ea tin g F

In do or R el at iv e

H um id ity

R

H M ax

In do or R el at iv e

H um id ity

R

H M in

M in im um

T ot

H

M in im um

O A

A C

H

R oo m A ir R et ur n G en . E xh G

S pe c Ex h S

M ax im um

N oi se

Le ve l N C

R oo m A ir B al an ce

VA

C N ot es

D up le x R ec ep ta cl es

Q ua d

R ec ep ta cl es

Po w er

N ot es

Fi xt ur e

Ty pe

C on tr ol s

Li gh tin g

- S pe ci

R eq ui re m en ts

Li gh tin g

- N ot es

D at a

O ut le ts

(s ta nd ar d de ns ity

W

O

IT

Sp ec ia l

R eq ui re m en ts

ROOM DATA MATRIX

FLOOR WALLS CEILING

IT

Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING

INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL

10 PHYSICAL THERAPY PHYSICAL THERAPY GYM Treatment Exercise Area (includes workstations therapists) EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 14 S 14 -- P14 Multilevel Switching, Dimming & Occupancy N/A N/A 4

10 PHYSICAL THERAPY Activities Daily Living (ADL) Training

ADL Evaluation and Training Center, Toilet, Tub, Bed, Kitchen, Laundry EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 15 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

15 Imaging Services RADIOLOGY Radiology, ES: General Purpose Radiology Room

CLASS 1 IMAGING ROOM TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 LS 8 5 P3, P13 Fully dimmable, occupancy sensor

N/A L2 4

15 Imaging Services C.T. CONTROL ROOM CT Control Area, X-Ray - Computed Tomography - Control TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 3'-0" Flush Wood -- LEAD LINED 12 LS 45 M14 6 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4

15 Imaging Services C.T. EQUIPMENT ROOM CT Equipment Room, X-Ray -

Computed Tomography - Indep View Console

-- WSF WSF P -- -- -- AT 9'-0" 5 6'-0" Flush Wood -- -- 45 AG 7 50 M14 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4

15 Imaging Services C.T. SCAN ROOM CT Scanning Room (Ceiling Lift), X-Ray - Computed Tomography -

Scanner CLASS 1 IMAGING ROOM TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 ALG 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4

15 Imaging Services MAMMOGRAPHY SCAN

ROOM

Mammo - X-ray, Mammography Room CLASS 1 IMAGING ROOM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 12 LS 7 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4

15 Imaging Services RADIOGRAPHIC /

FLOURO SCAN ROOM

Radiographic / Fluoroscopic (R/F) Room CLASS 1 IMAGING ROOM TREATMENT WSF WSF P - - SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 15 AGL 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4

15 Imaging Services ULTRASOUND SCAN ROOM Ultrasound Room CLASS 1 IMAGING ROOM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 S 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4

15 Imaging Services PACS SERVER ROOM

X-Ray - Storage - Digital Files, Viewing Room - Picture Archiving and Communication System

(PACS)

-- LVT RB P - - - AT 9'-0" 3'-0" Flush Wood -- -- 15 GK 50 4 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4

16 Imaging Services MRI CONTROL ROOM MRI Control Room, X-Ray -

Magnetic Resonance - Control, MRI Zone 3

CLASS 1 IMAGING ROOM EXAM - MRI LVT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 45 M14 6 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4

16 Imaging Services MRI EQUIPMENT ROOM MRI System Component Room, X-

Ray - Magnetic Resonance - System Component

TREATMENT LVT RB P RWC 4'-0" AT 9'-0" 11 4'-0" Flush Wood -- -- 35 AG 40 50 M14 7 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4

16 Imaging Services MRI FERROMAGNETIC

DETECTION

X-Ray - Magnetic Resonance - Ferromagnetic Detection, MRI

Zone 2 MRI Viewing Room EXAM - MRI LVT RB P -- -- SEE FGI AT 9'-0" 11, 16 4'-0" Flush Wood -- -- 15 G 75 70 60 40 12 2 Return 40 NR 1 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4

16 Imaging Services MRI SCAN ROOM MRI Scanning, X-Ray - Magnetic Resonance - Scanner, EXAM - MRI WSF WSF P -- -- SEE FGI AT VARIES 11,13,16 4'-0" Flush Wood -- R/F Shielded 1 75 70 60 40 12 2 Return

Exh. (S) 50 NR M17 2 -- P3 Multilevel Switching, Dimming & Occupancy MRI rated fixtures N/A 4

16 Imaging Services READING ROOM MRI Viewing Room, X-Ray - Magnetic Resonance - Viewing -- CPT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 40 6 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 6

15 Imaging Services BONE DENSITOMETRY Bone Densitometer EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 7 -- P3 Multilevel Switching, Dimming & Occupancy

N/A N/A 4

13 Pathology and Laboratory Medicine SPECIMEN COLLECTION

Blood Specimen Collection, Alcove - Specimen Collection

Point of Care (also for Substance Abuse plus Coumadin), Blood Draw Alcove, Support Area, Laboratory-Satellite, Laboratory- Venipuncture, Blood Draw

EXAM __ WSF WSF EP -- -- -- AT 9'-0" 3 -- _ _ _ _ _ 6 4 Multilevel Switching, Dimming & Occupancy

Multi-level switching or manual dimming N/A 4

13 Pathology and Laboratory Medicine

SPECIMEN

ACCESSIONING,

PROCESSING &

DISTRIBUTION ROOM

Specimen Accessioning, Processing & Distribution Room

LABORATORY WORK

ROOM -- WSF WSF EP -- -- -- GYP/EP or

AT-SP

9'-0 3, 7 3'-6" Flush w/

Narrow Vision Wood Narrow Vision -- 15 AG One per wall, 6' spacing, one adjacent to sink One at each workstation Multilevel Switching, Dimming & Occupancy Gyp ceiling - lights to be sealed type/flange mounted N/A One at each workstation

2 Pharmacy Service PHARMACY Pharmacy, Pharmacy, PACT 3

(Controlled Substance) (w/3 AutoDispensing)

PHARMACY -- RF RB P -- -- -- AT 9'-0" -- 6'-0" Flush Metal - - 200 AS 7 15 P5 Multilevel Switching, Dimming & Occupancy N/A N/A 9

2 Pharmacy Service PHARMACY DISPENSING

WINDOW

Dispense/Consult Window, Workroom, Pharmacist PHARMACY -- RF RB P -- -- -- AT 9'-0" -- - - - - - - OPEN 12 Multilevel Switching, Dimming & Occupancy N/A N/A 5

2 Pharmacy Service CLEAN ROOM, COMPOUNDING

Pharmacy - Clean Room - Chemotherapy Compounding -- -- RF RB P -- -- -- GWB:P 9'-0" 3 7'-0"

Single Slide Auto Sliding

Door

Aluminum/ Glass Yes -- 850 68 68 60 20 30 2 Exh. (S) 55 (-) M12, M7 14 -- P10 Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 5

2 Pharmacy Service IV ADMIXTURE Pharmacy - IV Admixture - Low Volume -- -- RF RB P -- -- -- GWB:P 9'-0" 3 7'-0"

Single Slide Auto Sliding

Door

Aluminum/ Glass Yes -- 850 68 68 60 20 30 2 Return 55 (++) M12 14 -- P10 Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 5

2 Pharmacy Service PRESCRIPTION

DISPENSING AREA

Prescription Dispensing Area - OmniCell Station -- -- RF RB P -- -- -- AT 9'-0" 3 -- -- -- -- -- - 6 8 -- Multilevel Switching, Dimming & Occupancy N/A N/A 3

2 Pharmacy Service SECURE STORAGE VAULT Secure Storage, Vault CLEAN WORK ROOM/

CLEAN SUPPLY -- RF RB P RWC 4'-0" -- GWB:P 9'-0" 3'-0" Flush Hollow Metal -- -- 1 1 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

2 Pharmacy Service ANTEROOM Anteroom, Compound Sterile Preparation -- RF RB EP -- -- -- GWB:SP 9'-0" 3 7'-0"

Single Slide Auto Sliding

Door

Aluminum/ Glass Yes -- 850 68 68 60 20 30 2 Return 55 (+) M12 2 -- Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 2

19 Engineering BIOMED REPAIR SHOP Repair Shop Biomedical Eng -- -- LVT RB P -- -- -- AT 9'-0" 3'-6" Flush Wood -- -- 35 AG Exh (G) (-) M7 10 -- P4 P6 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4 20 Logistics LOADING DOCK Receiving/ Shipping Dock -- -- CS RB EP -- -- -- EXP -- 8 6'-0" Flush Wood -- -- 44 APW 7 - 60 - - Exh (G) (+) M5 2 -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4

20 Logistics MAIL ROOM Support: Mail Room and Dist.

Center, Mailing Room - Prosthetic Appliances

-- -- RF RB P RWC 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 15 G 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4

20 Logistics GAS CYLINDER

STORAGE

Storage - Gas Cylinders - MRI, Storage - Gas Cylinders - Interior -- -- WSF WSF P RWC 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- 45 MIN 34 G Exh. (S) (-) 1 -- Multilevel Switching, Dimming & Occupancy N/A N/A 2

20 Logistics BIO-HAZARD STORAGE Storage - Bio Hazardous Material, Storage - Hazardous Material, Infectious / Hazardous Waste

REGULATED WASTE -- WSF WSF EP RWC 4'-0" -- GWB:SP 9'-0" 3 3'-6" Flush Hollow Metal -- -- 34 G 1 -- Multilevel Switching, Dimming & Occupancy N/A N/A 2

20 Logistics STORAGE WAREHOUSE Bulk Storage, General Storage, Warehouse

CLEAN

WORKROOM/CLEAN

SUPPLY

VT RB P -- -- -- Exp 10'-0" 6'-0" Flush Wood -- -- 45 AG minimum, 1 per wall, not to exceed 12' spacing -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4

20 Logistics BREAK DOWN Break Down

CLEAN

WORKROOM/CLEAN

SUPPLY

VT RB EP -- -- -- AT 9'-0" 8 4'-0" Flush Wood -- -- 34 AG 1 -- Multilevel Switching, Dimming & Occupancy

N/A N/A 4

21 Police Service POLICE HOLDING ROOM Holding Room -- -- LVT RB P -- -- -- GWB-PT 9'-0" 3,15 3'-6" Flush Hollow Metal Half Glass w/

Laminated Glass

18 P 0 -- Multilevel Switching, Dimming & Occupancy Tamperproof fixture design N/A --

21 Police Service OPERATIONS ROOM Operations Room LVT RB P -- -- 40 AT 9'-0" 3'-6" Flush Hollow Metal -- -- 200 APS M15 0 8 Multilevel Switching, Dimming & Occupancy

N/A N/A 4

21 Police Service SECURE STORAGE Small Arms Armory, Storage - Secure

LVT RB P -- -- -- AT 9'-0" 3'-0" Flush Hollow Metal -- -- 200 P 75 70 60 - 4 2 Return NR NR M7 1 -- Multilevel Switching, Dimming & Occupancy

N/A N/A 4

22 VCS RETAIL AREA Retail Area EXAM - PUBLIC SPACE LVT RB P -- -- SEE FGI AT 9'-0 17 6'-0" Flush w/ Full Vision Wood Full Vision 47 KM 7, 9 M4 One per wall, 6' spacing -- Multilevel Switching, Dimming & Occupancy Track or adjustable accent lighting for retail displays. L5 3

24 OI&T TELECOMM.

Telecommunications Room/

Closet, IT Telecommunications Room

-- -- VT RB P -- -- -- EXP. 12'-0" 3'-6" Flush Wood -- -- 34 AS 64 75 55 30 - - - - NR 6 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4

24 OI&T SERVER ROOM Central Server Room -- -- VT RB P -- -- -- EXP 12'-0" 3'-6" Flush Wood -- -- 34 AS 72 81 60 6 M8 10 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4

24 OI&T I.T. WORKROOM IT Workroom, Equip.

Configuration/ Repair

-- -- SD RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG 10 -- P4, P6 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4

0 SPS STORAGE, CLEAN

SCOPE Storage, Clean Scope CLEAN SUPPLY -- RES RES EP RWC 4'-0" -- GYP-EP 9'-0 3, 7 3'-6" Flush w/

Narrow Vision Wood Narrow Vision -- 15 AG 66 75 55 30 4 (+) One per wall -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy

Gyp ceiling - lights to be sealed type/flange mounted N/A --

Interior Finishes Notes

General Notes A. Hollow metal frames and doors to be painted.

B. Window sills to be solid surface fabrication.

C. Resilient base to be 4", unless otherwise noted.

D. Provide painted finishes only on inside of exterior walls (no wall covering).

E. Floor material transitions to occur at centerline of door, unless otherwise noted.

F. Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color.

G. Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety.

H. Coordinate height of wall protection with wall-mounted devices.

I. Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks, reception desks and lobby/waiting areas.

J. Soffit above upper cabinets to be gypsum board.

K. Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials.

L. Solid surface countertops to have sides and backsplash at walls.

Schedule Notes

1. CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling.

2. Tile base to be coved.

3. Integral coved base 6" high tightly sealed to walls.

4. If sink is present, use hard suface flooring as noted.

5. Lead lined walls and control area view window.

6. Flooring and base to match adjacent area flooring material and base.

7. Use gasketed, clip down ACT/grid system

8. Use slip-retardant finish on floor material

9. Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads. Stair nosings to be a contrasting color for safety.

10. Note that if wall saver designed chairs are used, no wall protection is required.

11. Extend all room partitions to structural deck.

12. CT above countertop on wall.

13. Ceiling height as required to acommodate equipment.

14. Cove QT base, 6" high.

15. No separate trim at top of base, use alternate method to seal to wall.

16. Ceiling suspension system should be fabricated from nonferromagnetic material.

17. Aesthetic specialty materials may be used as accents where the design and budget permits.

18. Ceiling tile to meet USDA regulations.

19. Floors to be slip-resistant and meet ANSI 326.3 for measuring dynamic coefficient of friction for hard surfaces

20. Wall base on gyp board but not needed on any exterior materials such as brick, metal, or stone walls.

21. Wall CT and ceiling to meet building code light reflectancy standards.

22. Space may be room or area within a room. Coordinate finishes with adjacent spaces.

23. Provide 3/4" painted plywood where required by Telecommunications.

AT Acoustical Ceiling Tile AT-SP Acoustical Scrubbable Ceiling Tile (with sprayed plastic finish) CPT Carpet Tile CS Concrete, Sealed CT Ceramic Tile (Wall) EP Epoxy Paint EXP Exposed Ceiling LVT Luxury Vinyl Tile Flooring MAT Modular Carpet Walk Off Mat P Paint PT Porcelain Tile QT Quarry Tile RB Resilient Base RES Resinous Flooring and Base RF Rubber Flooring RFT Resilient Floor Tile RSF Resilient Sheet Flooring - Heterogeneous RWC Rigid Wall Covering (Wall Protection) SD Static Dissipative Tile S Solid Surface Fabrication WSF Welded Seam Sheet Flooring - Homogeneous

Finish Codes

Hardware Notes tes

Refer to Lease Design Narrative (LDN) Appendix for Hardware Groups and Modifiers which are added to numeric hardware group assignments to indicate a variation to the group.

All doors to be 7'-0" high, unless otherwise noted.

Coordinate acoustical requirements for doors with required wall acoustical ratings as shown in Room Data Matrix - Interior Finishes in Appendix.

otes

Hollow metal frame cased opening

Two door (in swing and swing out) acoustical door and frame assembly.

Two doors required at this room/space.

Narrow lite optional. Use insulated or laminated glass to meet acoustical criteria.

Provide STC 50 rated acoustical door.

No door in this room/space.

Equal leaf pair of doors.

Lead lined door and hardware.

Space may be a room or area within another room. Omit door if space is not a separate room.

ELECTRICAL NOTES

POWER NOTES LIGHTING NOTES

P1. Multiple receptacles above and below desk for device charging, receptacles provided with Pre-Fab system.

L1. EMI/RFI emissions to be controlled

P2. Receptacles on all walls L2. Dimmable to 5 fc

P3. Coordinate electrical connections with equipment to be installed.

Receptacles on all walls.

L3. May not have ceiling - then use industrial fixture type

P4. Plug strip at 44" above counters L4. May not have ceiling. If no ceiling, use industrial fixture type

P5. Multiple receptacles above and below desk for device charging L5. Treat like a store. Adjustable lighting, General lighting.

P6. Cord reel(s) for freestanding workbenches L6. No ceiling in these rooms. No prescription for lighting.

P7. All outlets on dedicated circuits.

P8. Cord reel(s) for freestanding workbenches

P9. Treadmill on dedicated circuit

P10. Each hood on dedicated circuit

P11. Provide receptacles per equipment plan

P12. Electrical to review redundancy requirements with OIT guidelines.

P13. Receptacle above ceiling for overhead lift P14. Recessed power quad floor box P15. L21-20R receptacle above each rack P16. Electrical to support 8 workstations 2 duplex per station.

MECHANICAL HVAC NOTES

M1. Intentionally Left Blank M2. Per ASHRAE 62 for ventilation, and FGI Guidelines for NC M3. General Open Office area M4. General Open/Public area M5. Per ASHRAE 62 for ventilation if interior enclosed space.

M6. Comply with ASHRAE 15 if Special Refrigeration Systems are used M7. If chemicals are used, provide specialized exhaust M8. Data Center M9. Transfer air to Food Prep Kitchen M10. Intentionally Left Blank M11. MEP Room M12. See USP-797 and -800 M13. Counter-height specialized exhaust system required M14. Provide air conditioning and ventilation per imaging manufacturer recommendations

M15. General Office Area M16. Verify specific vendor/manufacturer requirements.

M17. Non-ferrous construction M18. Provide cooling only air terminal unit to serve the manual equipment wash M19. Provide a dedicated wet exhaust system