This document contains a room data matrix and specifications for the Sarasota Outpatient Clinic (PACT ACT) project solicited by the Department of Veterans Affairs Office of Construction and Facilities Management under solicitation number 36C10F24R0007. The matrix includes over 100 individual rooms and spaces with requirements for interior finishes, doors, hardware, mechanical, electrical, and communications systems. Key areas covered include exam rooms, procedure rooms, imaging services, audiology, dental, pharmacy, physical therapy, laboratory, imaging, police services, logistics, and information technology infrastructure spaces. Specifications address acoustics, power and data requirements, lighting controls and interior construction details. The level of technical requirements indicates this is a design-build project for a new outpatient healthcare facility.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROOM IDENTIFICATION NOTES
Functional Area DEPARTMENT ROOM NAME ROOM NAMES (VA) FGI EQUIVALENT FOR
ASHRAE 170
FGI EQUIVALENT FOR TABLE
1.2-5 Minimum Sound Isolation
Fl oo r F in is h
B as e
W al l F in is h
W ai ns co t M at er ia l
W ai ns co t H ei gh t
ST
C
C ei lin g
Fi ni sh
H ei gh t
N ot es
Si ze
(W id th
Ty pe
M at er ia l
G la zi ng
R at in g
H ar dw ar e G ro up
H ar dw ar e N ot es
In do or
Te m pe ra tu re
C oo lin g F
In pe ra
H ea tin g F
In do or R el at iv e
H um id ity
R
H M ax
In do or R el at iv e
H um id ity
R
H M in
M in im um
T ot al
A
H
M in im um
O A
A C
H
R oo m A ir R et ur n G en . E xh G
S pe c Ex h S
M ax im um
N oi se
Le ve l N C
R oo m A ir B al an ce
VA
C N ot es
D up le x R ec ep ta cl es
Q ua d
R ec ep ta cl es
Po w er
N ot es
Fi xt ur e
Ty pe
C on tr ol s
Li gh tin g
- S pe ci
R eq ui re m en ts
Li gh tin g
- N ot es
D at a
O ut le ts
(s ta nd ar d de ns ity
W
O
IT
Sp ec ia l
R eq ui re m en ts
0 General Rooms/Spaces Exam Room PACT Exam EXAM EXAMINATION LVT RB P -- -- 55 AT 9'-0" 10
3'-0"
3'-6" Flush Wood _ _ 12 SE 3 8 1
Multilevel Switching, Dimming & Occupancy
Multi-level switching or manual dimming N/A 4 Tele-Health
0 General Rooms/Spaces Exam Room
Exam Room - Multi-Specialty, Exam / Treatment, Exam -
Consult, Consult Room - PACT, Exam/Consult Room (Mental
Health/Social Work), Exam Room EMG/EEG, Exam Room-
Cardiology, Exam/Consult, Nurse Practitioner, Women's Health
Exam, Tele-Health Exam, Optometry Exam Treatment
Room, Eye Lane, Tele-Retinal, TECHS, Applicance Fitting Room, Fitting Room, Physical Therapy Room, Occupational Treatment
Room
EXAM EXAMINATION LVT RB P -- -- 55 AT 9'-0" 10 3'-6" Flush Wood _ _ 12 S 8 1 Multilevel Switching, Dimming & Occupancy
Multi-level switching or manual dimming
At Eye Clinic, connect refraction desk dimming to room lighting control.
0 General Rooms/Spaces Consult Room
Consult Room, Audiology Rehabilitation Counceling Room, Dental Consult Room CONSULTATION LVT RB P -- -- 55 AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 75 70 60 - 4 2 Return 40 NR 6
Multilevel Switching, Dimming & Occupancy
Multi-level switching or manual dimming N/A 4
0 General Rooms/Spaces Procedure Room
Procedure Room, General, Specialty Care, Gynechology, Multi-Specialty Care, Cast Room
PROCEDURE TREATMENT WSF WSF EP RWC 4'-0" 55 AT 9'-0" 3
3'-0"
3'-6" Flush Wood -- -- 12 SE 3 7 P13
Multilevel Switching, Dimming & Occupancy
Wall mounted exam light N/A 4
0 General Rooms/Spaces Laboratory Laboratory (Typical) LABORATORY
WORKROOM __ WSF WSF EP -- -- 40 AT-SP 9'-0" 3 3'-0" Flush Wood _ _ 15 AG 4 6 P3, P4 Multilevel Switching, Dimming & Occupancy
N/A N/A 5
0 General Rooms/Spaces Conference Room
Conference Room, Multi-Purpose Room, Group Room, Shared Medical Appointment Room, Education Room, Staff Training Room, Classroom
__ LVT RB P RWC 4'-0" 40 AT 9'-0" 17 3'-6" Flush Wood _ _ 15 S _ M2 8 P14 Multilevel Switching, Dimming & Occupancy
Provide 4 scene preset dimmable lighting for a variety of tasks. Consider placement and optics to mitigate glare and ceiling reflections
N/A 4 Floor data for table
0 General Rooms/Spaces TOILET
General Toilet, Patient - Toilet, Toilet - Police, Toilet - Family, Toilet - Female Staff, Toilet - Male Staff, Toilet - Procedure
Room, Toilet - Public, Toilet - RF Patient, Toilet - Women's Health, Toilet - Female, Toilet - Family
Assist, Specimen Collection Toilet
TOILET ROOM TOILET ROOM PT PT P CT 7'-0" SEE FGI AT 9'-0" 1,2 3'-6" Flush Wood _ _ 11 _ 1 Downlights/Mirror or vanity Occupancy Sensor N/A N/A 4
0 General Rooms/Spaces OFFICE Any Office -- CONSULTATION LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS 4 1
Multilevel Switching, Dimming & Occupancy
N/A N/A 4
0 General Rooms/Spaces WAITING
Waiting - Family - PACT, Waiting - PACT 3, Waiting - General - 20 People, Waiting - General - 10 People, Waiting - General - 6
People, Waiting-General
EXAM - PUBLIC SPACE LVT RB P -- -- SEE FGI AT 9'-0" 10, 17 M4 -- --
Multilevel Switching, Dimming & Occupancy
N/A N/A 4
0 General Rooms/Spaces RECEPTION
Reception, Information Desk, Travel Window, Reception -
Accessible -- -- LVT RB P -- -- -- AT 9'-0" -- 3'-0" Flush w/ narrow vision Wood _ _ 12 CG 3 M4 1 1 Downlights, pendants, decorative, and accent
Multilevel Switching, Dimming & Occupancy
N/A N/A 10 Data/phone feeds to systems furniture
0 General Rooms/Spaces COPY ALCOVE
Copy Alcove, Copier - Workroom, Copy / Office Supply Room, Copy
Room -- -- Match
Adjacent Match
Adjacent P -- -- -- AT 9'-0" 6 _ _ _ _ _ _ 6 3 Multilevel Switching, Dimming & Occupancy
N/A N/A 4
0 General Rooms/Spaces CLEAN UTILITY
Clean Utility, Clean Supply, Clean Workroom, Clean Linen, Sterile
Storage, CBOC Steril Supply Storage Room, Clean Scope, Dental Clean Cart, Central Sterile
-- -- WSF WSF P RWC 4'-0" -- AT 9'-0" -- 3'-0" Flush Wood -- 45 MIN 121 AG _ 66 75 55 30 4 (+) 1 Occupancy Sensor N/A N/A 2
0 General Rooms/Spaces SOILED UTILITY
Soiled Utility Room, Recycled Material, Soiled Holding, Soiled Linen, Soiled Workroom, Soiled
Supply Soiled Cart
SOILED HOLDING /
SOILED WORK ROOM -- WSF WSF P RWC 4'-0" -- AT 9'-0" 3 3'-0" Flush Wood -- 45 MIN 121 AG _ 2 -- Occupancy Sensor N/A N/A 2
0 General Rooms/Spaces STORAGE
Storage - Medical Equipment, Storage - Shared Medical
Appointments, DME - Prosthetics Storage, Storage - Homeless, EMS Storage, Storage - Bistro/Coffee Bar, Storage -
Patient Clothing and Luggage, Laundry / Storage, Tray Cart Storage Area, Buld Storage, General Storage, Secure Storage
CLEAN
WORKROOM/CLEAN
SUPPLY
LVT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG
1 per wall, not to exceed 12' spacing. Plug mold used in medical equipment storage rooms.
-- Surface or chain mounted 1' x 4' Occupancy Sensor N/A N/A 2
0 General Rooms/Spaces
JANITOR'S CLOSET Housekeeping Aides Closet
(HAC)
ENVIRONMENTAL
SERVICES ROOM
-- PT PT P FRP 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 34 A _ 1 -- Occupancy Sensor N/A N/A --
0 General Rooms/Spaces EQUIPMENT ALCOVE
AED Alcove, Height and Weight Alcove, Scale Alcove, Stretcher Alcove, Med Alcove, Portable
Patient Lift Alcove, Wheelchair Alcove, My Health eVet, Kiosk, -- -- Match Adjacent
Match Adjacent Match Adjacent RWC 4'-0" -- AT Match
Adjacent 3 -- -- -- -- -- 6 1 1 Quad receptacles at My Health eVet alcove
Multilevel Switching, Dimming & Occupancy
N/A N/A 2 My Heralth eVet
0 General Rooms/Spaces STAFF LOUNGE Staff Lounge -- -- LVT RB P -- -- 40 AT 9'-0" 4 3'-0" Flush w/ narrow vision Wood -- -- 13 _ Exh. (G) (-) 8 -- P7 Multilevel Switching, Dimming & Occupancy
N/A N/A 4
0 General Rooms/Spaces MEDICATION ROOM Medication Room MEDICATION ROOM -- LVT RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 34 5 1
Multilevel Switching, Dimming & Occupancy
N/A N/A 4
0 General Rooms/Spaces LACTATION ROOM Employee Wellness, Lactation
Room, Quiet Room -- -- LVT RB P -- -- 50 AT 9'-0" 10 3'-0" Flush Wood -- -- 12 CS 4 -- Multilevel Switching, Dimming & Occupancy
N/A N/A 2
0 General Rooms/Spaces LOCKER ROOM
Locker Room, Locker Room (Male/ Female) Locker - Staff
Personal Property, Locker Room - Staff
-- -- LVT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- Push/Pull Exh. (G) (-) 4 -- Multilevel Switching, Dimming & Occupancy
N/A N/A 2
0 General Rooms/Spaces
OFFICE, CUBICLE, Open Office
Cubicle - Administrative, Data Processing, Workstation -
Extended Team, Homeless, HBPC, HUD-VASH, Workstation -
MICHM, Workstation - Suicide Prevention, Workstation - VOC
Rehab, Workstation - Rad Tech, Workstation - Shipping / Receiving, Workstation, Administration (MSA MH; Rad, LPN), Workstation-Sleep Tech, Work Station, Call Center (MSA), Workstation-Cart Case Dispatch, Workstation-Clerical, -- -- CPT RB P -- -- -- AT 9'-0" * Workstations in HBPC 2 per workstation -- P-16
Multilevel Switching, Dimming & Occupancy
N/A N/A 2/workstaton
0 General Rooms/Spaces SUB-WAITING
Sub-Waiting, MRI Sub-Waiting, CT Sub-Waiting, Mammo Sub-
Waiting, Sub-Waiting - Diagnostic Patient, Sub-Waiting - Dilation Patient, CT Vestibule, Waiting, Waiting-Zone 1, Sub-Waiting-
Zone 2
-- -- LVT RB P -- -- -- AT 9'-0" 10, 17 -- -- -- -- -- - 6 M4 4 --
Multilevel Switching, Dimming & Occupancy
N/A N/A 2
0 General Rooms/Spaces VENDING Vending Machine Area LVT RB P -- -- -- AT 9'-0" -- -- -- -- -- -- 6 M4 8 --
Multilevel Switching, Dimming & Occupancy
N/A N/A 4
0 General Rooms/Spaces TOILET/SHOWER ROOM
Toilet/Shower-Staff, Toilet/Shower-Patient, Toilet/Shower-Female Staff, Toilet/Shower-Male Staff
TOILET ROOM TOILET ROOM PT PT CT -- -- SEE FGI GWB/P 9'-0" 2, 19 3'-6" Flush Wood -- -- 11 G 2 -- Multilevel Switching, Dimming & Occupancy
N/A N/A
0 General Rooms/Spaces CHANGING ROOM Dressing room RFT RB P -- -- 40 AT 9'-0" 3'-6" Flush Wood -- -- 11 K 75 70 60 - 4 2 Return NR NR 1 --
Multilevel Switching, Dimming & Occupancy
N/A N/A 1
3 Primary Care, Specialty Care, PACT
PACT TEAM WORK
SPACE
PACT Team Work Space, Team Work Area- Home Based Primary
Care -- CPT RB P -- AT 9'-0" -- _ _ _ _ _ 14 MP 6 M3 2 per workstation --
Multilevel Switching, Dimming & Occupancy
Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting
N/A 1 per workstation Data/phone feeds to systems furniture
3 Primary Care, Specialty Care, PACT EXAM ROOM Exam, Negative Pressure AII Room EXAMINATION WSF WSF P -- -- SEE FGI GWB:P 9'-0" 3,7 3'-6" Flush Wood -- -- 12 S 6 -- Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 2
5 Audiology and SLP AUDIOLOGY HEARING AID
TESTING
Hearing Aid Lab, Hearing Aid Processing, Hearing Aid Repair -- LVT RB P -- -- 40 AT 9'-0" -- 3'-0" Flush Wood _ _ 15 S _ 75 70 60 - Exh. (G) (-) 7 0 P4 Multilevel Switching, Dimming & Occupancy N/A N/A 4
5 Audiology and SLP AUDIOLOGY HEARING AID
FITTING
Audiology Programming / Fitting, Hearing Aid Fitting Room, Cerumen Management Room, Speech Language Pathology Assistive Technology Romm, Speech Language Pathology
Voice Treatment Room
EXAM -- LVT RB P -- -- 60 AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 Multilevel Switching, Dimming & Occupancy N/A N/A 4
5 Audiology and SLP AUDIOMETRIC EXAM
BOOTH
Audiometric Exam Suite, Exam - Audiometric Booth, Aud: Suite -
Audiometric Exam, Hearing/Diagnostics, Booth, 1-
Person
EXAM -- Pre-Fab Pre-Fab Pre-Fab -- -- SEE EQUIP LIST Pre-Fab 8'-0" -- 3'-0"
3'-6"
Pre-Fab Pre-Fab _ _ 1 2,4 9 P1
Typically pre-packaged unit including lighting and switching
N/A L1 5
5 Audiology and SLP ELECTROPHYSIOLOGY Electrophysiology, Posturography, Vestibulography EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 P2, P3, P14 Multilevel Switching, Dimming & Occupancy N/A N/A 4
6 Dental Service SPECIALTY EQUIPMENT
MECHANICAL ROOM
Dental Equipment Mech. Room, Mechanical Rooms - Electrical -- -- VT RB P -- -- 60 EXP 9'-0" 3'-6" Flush Wood -- -- 14 S Exh. (G) (-) 2 -- P3 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4
6 Dental Service DENTAL PROSTHETICS LABORATORY Laboratory, Dental Prosthetics -- RF RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 15 AG 75 70 60 20 6 2
Return Exh. (G) 45 (-) M13 7 -- Multilevel Switching, Dimming & Occupancy N/A N/A 5
6 Dental Service DENTAL TREATMENT
ROOM
Dental Treatment Room (DTR), Multi-Functional (4/Hygiene), Special Needs Patient, Bariatric EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CS (+) 7 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
6 Dental Service DENTAL X-RAY ROOM X-Ray Room, Panoramic / Cephalometric (Cone Beam) CLASS 1 IMAGING ROOM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 17 AGL 8 7 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4
7 Optometry FITTING & DISPENSING, EYEGLASSES Fitting & Dispensing, Eyeglasses -- LVT RB P -- -- -- AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S 6 75 70 60 - 4 2 Return 40 NR 2 Downlights and accent/display Multilevel Switching, Dimming & Occupancy N/A N/A 4
7 Optometry LOW VISION EXAM/
THERAPY/ TRAINING
Low Vision Exam/ Therapy/ Training EXAM EXAMINATION LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 Multilevel Switching, Dimming & Occupancy
Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting
N/A 4
7 Optometry PRE-TESTING/ INTAKE Pre-Testing/ Intake EXAM EXAMINATION LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 6 1 Multilevel Switching, Dimming & Occupancy
Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting
N/A 4
7 Optometry VISUAL FIELDS ROOM
Visual Fields Room, Photography Room, Ultrasound Room, Tomography Room, Imaging Room, OCT Laser
EXAM EXAMINATION LVT RB P -- -- SEE FGI AT 9'-0" -- 3'-6" Flush Wood _ _ 12 S _ 7 Multilevel Switching, Dimming & Occupancy
Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting
N/A 4
8 Mental Health QUIET ROOM Quiet Room for Patients EXAM TREATMENT CPT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
8 Mental Health BIOFEEDBACK TREATMENT ROOM Biofeedback Treatment Room EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 15 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
9 Specialty Care Services
PULMONARY FUNCTION
ROOM Pulmonary Function - Analysis EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 G 6 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
9 Specialty Care Services TREADMILL ROOM Treadmill Room EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 MS 6 -- P9 Multilevel Switching, Dimming & Occupancy N/A N/A 4
9 Specialty Care Services EKG TESTING ROOM EKG Testing Room EXAM EXAMINATION LVT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 12 S One per wall -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
9 Recreation Therapy GROUP THERAPY ROOM, MUSIC
Creative Arts - Group Therapy Room - Music -- TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
9 Recreation Therapy GROUP THERAPY ROOM, ART
Creative Arts - Group Therapy Room - Large -- TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 CG 8 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
9 Recreation Therapy WEIGHT ROOM, SMALL Recreation Therapy Exercise / Weight Room - Small -- TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 34 AG 12 -- Multilevel Switching, Dimming & Occupancy N/A N/A 1
ROOM DATA MATRIX
FLOOR WALLS CEILING
IT
Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING
INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL
ROOM IDENTIFICATION NOTES
Functional Area DEPARTMENT ROOM NAME ROOM NAMES (VA) FGI EQUIVALENT FOR
ASHRAE 170
FGI EQUIVALENT FOR TABLE
1.2-5 Minimum Sound Isolation
Fl oo r F in is h
B as e
W al l F in is h
W ai ns co t M at er ia l
W ai ns co t H ei gh t
ST
C
C ei lin g
Fi ni sh
H ei gh t
N ot es
Si ze
(W id th
Ty pe
M at er ia l
G la zi ng
R at in g
H ar dw ar e G ro up
H ar dw ar e N ot es
In pe ra oo lin g F
In pe ra ea tin g F
In do or R el at iv e
H um id ity
R
H M ax
In do or R el at iv e
H um id ity
R
H M in
M in im um
T ot
H
M in im um
O A
A C
H
R oo m A ir R et ur n G en . E xh G
S pe c Ex h S
M ax im um
N oi se
Le ve l N C
R oo m A ir B al an ce
VA
C N ot es
D up le x R ec ep ta cl es
Q ua d
R ec ep ta cl es
Po w er
N ot es
Fi xt ur e
Ty pe
C on tr ol s
Li gh tin g
- S pe ci
R eq ui re m en ts
Li gh tin g
- N ot es
D at a
O ut le ts
(s ta nd ar d de ns ity
W
O
IT
Sp ec ia l
R eq ui re m en ts
ROOM DATA MATRIX
FLOOR WALLS CEILING
IT
Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. POWER LIGHTING
INTERIOR CONSTRUCTION DOORS AND HARDWARE MECHANICAL ELECTRICAL
10 PHYSICAL THERAPY PHYSICAL THERAPY GYM Treatment Exercise Area (includes workstations therapists) EXAM TREATMENT RF RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 14 S 14 -- P14 Multilevel Switching, Dimming & Occupancy N/A N/A 4
10 PHYSICAL THERAPY Activities Daily Living (ADL) Training
ADL Evaluation and Training Center, Toilet, Tub, Bed, Kitchen, Laundry EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0 3'-6" Flush Wood -- -- 15 S 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
15 Imaging Services RADIOLOGY Radiology, ES: General Purpose Radiology Room
CLASS 1 IMAGING ROOM TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 LS 8 5 P3, P13 Fully dimmable, occupancy sensor
N/A L2 4
15 Imaging Services C.T. CONTROL ROOM CT Control Area, X-Ray - Computed Tomography - Control TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 3'-0" Flush Wood -- LEAD LINED 12 LS 45 M14 6 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4
15 Imaging Services C.T. EQUIPMENT ROOM CT Equipment Room, X-Ray -
Computed Tomography - Indep View Console
-- WSF WSF P -- -- -- AT 9'-0" 5 6'-0" Flush Wood -- -- 45 AG 7 50 M14 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4
15 Imaging Services C.T. SCAN ROOM CT Scanning Room (Ceiling Lift), X-Ray - Computed Tomography -
Scanner CLASS 1 IMAGING ROOM TREATMENT WSF WSF P -- -- SEE FGI AT 9'-0" 5 4'-0" Flush Wood -- LEAD LINED 15 ALG 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4
15 Imaging Services MAMMOGRAPHY SCAN
ROOM
Mammo - X-ray, Mammography Room CLASS 1 IMAGING ROOM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 12 LS 7 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4
15 Imaging Services RADIOGRAPHIC /
FLOURO SCAN ROOM
Radiographic / Fluoroscopic (R/F) Room CLASS 1 IMAGING ROOM TREATMENT WSF WSF P - - SEE FGI AT 9'-0" 5 3'-6" Flush Wood -- LEAD LINED 15 AGL 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4
15 Imaging Services ULTRASOUND SCAN ROOM Ultrasound Room CLASS 1 IMAGING ROOM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 12 S 7 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4
15 Imaging Services PACS SERVER ROOM
X-Ray - Storage - Digital Files, Viewing Room - Picture Archiving and Communication System
(PACS)
-- LVT RB P - - - AT 9'-0" 3'-0" Flush Wood -- -- 15 GK 50 4 -- P3, P13 Multilevel Switching, Dimming & Occupancy N/A N/A 4
16 Imaging Services MRI CONTROL ROOM MRI Control Room, X-Ray -
Magnetic Resonance - Control, MRI Zone 3
CLASS 1 IMAGING ROOM EXAM - MRI LVT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 45 M14 6 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4
16 Imaging Services MRI EQUIPMENT ROOM MRI System Component Room, X-
Ray - Magnetic Resonance - System Component
TREATMENT LVT RB P RWC 4'-0" AT 9'-0" 11 4'-0" Flush Wood -- -- 35 AG 40 50 M14 7 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4
16 Imaging Services MRI FERROMAGNETIC
DETECTION
X-Ray - Magnetic Resonance - Ferromagnetic Detection, MRI
Zone 2 MRI Viewing Room EXAM - MRI LVT RB P -- -- SEE FGI AT 9'-0" 11, 16 4'-0" Flush Wood -- -- 15 G 75 70 60 40 12 2 Return 40 NR 1 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 4
16 Imaging Services MRI SCAN ROOM MRI Scanning, X-Ray - Magnetic Resonance - Scanner, EXAM - MRI WSF WSF P -- -- SEE FGI AT VARIES 11,13,16 4'-0" Flush Wood -- R/F Shielded 1 75 70 60 40 12 2 Return
Exh. (S) 50 NR M17 2 -- P3 Multilevel Switching, Dimming & Occupancy MRI rated fixtures N/A 4
16 Imaging Services READING ROOM MRI Viewing Room, X-Ray - Magnetic Resonance - Viewing -- CPT RB P -- -- 40 AT 9'-0" 3'-0" Flush Wood -- -- 12 GS 40 6 -- P3 Multilevel Switching, Dimming & Occupancy N/A N/A 6
15 Imaging Services BONE DENSITOMETRY Bone Densitometer EXAM TREATMENT LVT RB P -- -- SEE FGI AT 9'-0" 3'-6" Flush Wood -- -- 35 S 7 -- P3 Multilevel Switching, Dimming & Occupancy
N/A N/A 4
13 Pathology and Laboratory Medicine SPECIMEN COLLECTION
Blood Specimen Collection, Alcove - Specimen Collection
Point of Care (also for Substance Abuse plus Coumadin), Blood Draw Alcove, Support Area, Laboratory-Satellite, Laboratory- Venipuncture, Blood Draw
EXAM __ WSF WSF EP -- -- -- AT 9'-0" 3 -- _ _ _ _ _ 6 4 Multilevel Switching, Dimming & Occupancy
Multi-level switching or manual dimming N/A 4
13 Pathology and Laboratory Medicine
SPECIMEN
ACCESSIONING,
PROCESSING &
DISTRIBUTION ROOM
Specimen Accessioning, Processing & Distribution Room
LABORATORY WORK
ROOM -- WSF WSF EP -- -- -- GYP/EP or
AT-SP
9'-0 3, 7 3'-6" Flush w/
Narrow Vision Wood Narrow Vision -- 15 AG One per wall, 6' spacing, one adjacent to sink One at each workstation Multilevel Switching, Dimming & Occupancy Gyp ceiling - lights to be sealed type/flange mounted N/A One at each workstation
2 Pharmacy Service PHARMACY Pharmacy, Pharmacy, PACT 3
(Controlled Substance) (w/3 AutoDispensing)
PHARMACY -- RF RB P -- -- -- AT 9'-0" -- 6'-0" Flush Metal - - 200 AS 7 15 P5 Multilevel Switching, Dimming & Occupancy N/A N/A 9
2 Pharmacy Service PHARMACY DISPENSING
WINDOW
Dispense/Consult Window, Workroom, Pharmacist PHARMACY -- RF RB P -- -- -- AT 9'-0" -- - - - - - - OPEN 12 Multilevel Switching, Dimming & Occupancy N/A N/A 5
2 Pharmacy Service CLEAN ROOM, COMPOUNDING
Pharmacy - Clean Room - Chemotherapy Compounding -- -- RF RB P -- -- -- GWB:P 9'-0" 3 7'-0"
Single Slide Auto Sliding
Door
Aluminum/ Glass Yes -- 850 68 68 60 20 30 2 Exh. (S) 55 (-) M12, M7 14 -- P10 Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 5
2 Pharmacy Service IV ADMIXTURE Pharmacy - IV Admixture - Low Volume -- -- RF RB P -- -- -- GWB:P 9'-0" 3 7'-0"
Single Slide Auto Sliding
Door
Aluminum/ Glass Yes -- 850 68 68 60 20 30 2 Return 55 (++) M12 14 -- P10 Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 5
2 Pharmacy Service PRESCRIPTION
DISPENSING AREA
Prescription Dispensing Area - OmniCell Station -- -- RF RB P -- -- -- AT 9'-0" 3 -- -- -- -- -- - 6 8 -- Multilevel Switching, Dimming & Occupancy N/A N/A 3
2 Pharmacy Service SECURE STORAGE VAULT Secure Storage, Vault CLEAN WORK ROOM/
CLEAN SUPPLY -- RF RB P RWC 4'-0" -- GWB:P 9'-0" 3'-0" Flush Hollow Metal -- -- 1 1 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
2 Pharmacy Service ANTEROOM Anteroom, Compound Sterile Preparation -- RF RB EP -- -- -- GWB:SP 9'-0" 3 7'-0"
Single Slide Auto Sliding
Door
Aluminum/ Glass Yes -- 850 68 68 60 20 30 2 Return 55 (+) M12 2 -- Multilevel Switching, Dimming & Occupancy Sealed fixture, flat lens surface on exterior N/A 2
19 Engineering BIOMED REPAIR SHOP Repair Shop Biomedical Eng -- -- LVT RB P -- -- -- AT 9'-0" 3'-6" Flush Wood -- -- 35 AG Exh (G) (-) M7 10 -- P4 P6 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4 20 Logistics LOADING DOCK Receiving/ Shipping Dock -- -- CS RB EP -- -- -- EXP -- 8 6'-0" Flush Wood -- -- 44 APW 7 - 60 - - Exh (G) (+) M5 2 -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4
20 Logistics MAIL ROOM Support: Mail Room and Dist.
Center, Mailing Room - Prosthetic Appliances
-- -- RF RB P RWC 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- -- 15 G 4 -- Multilevel Switching, Dimming & Occupancy N/A N/A 4
20 Logistics GAS CYLINDER
STORAGE
Storage - Gas Cylinders - MRI, Storage - Gas Cylinders - Interior -- -- WSF WSF P RWC 4'-0" -- AT 9'-0" 3'-0" Flush Wood -- 45 MIN 34 G Exh. (S) (-) 1 -- Multilevel Switching, Dimming & Occupancy N/A N/A 2
20 Logistics BIO-HAZARD STORAGE Storage - Bio Hazardous Material, Storage - Hazardous Material, Infectious / Hazardous Waste
REGULATED WASTE -- WSF WSF EP RWC 4'-0" -- GWB:SP 9'-0" 3 3'-6" Flush Hollow Metal -- -- 34 G 1 -- Multilevel Switching, Dimming & Occupancy N/A N/A 2
20 Logistics STORAGE WAREHOUSE Bulk Storage, General Storage, Warehouse
CLEAN
WORKROOM/CLEAN
SUPPLY
VT RB P -- -- -- Exp 10'-0" 6'-0" Flush Wood -- -- 45 AG minimum, 1 per wall, not to exceed 12' spacing -- Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4
20 Logistics BREAK DOWN Break Down
CLEAN
WORKROOM/CLEAN
SUPPLY
VT RB EP -- -- -- AT 9'-0" 8 4'-0" Flush Wood -- -- 34 AG 1 -- Multilevel Switching, Dimming & Occupancy
N/A N/A 4
21 Police Service POLICE HOLDING ROOM Holding Room -- -- LVT RB P -- -- -- GWB-PT 9'-0" 3,15 3'-6" Flush Hollow Metal Half Glass w/
Laminated Glass
18 P 0 -- Multilevel Switching, Dimming & Occupancy Tamperproof fixture design N/A --
21 Police Service OPERATIONS ROOM Operations Room LVT RB P -- -- 40 AT 9'-0" 3'-6" Flush Hollow Metal -- -- 200 APS M15 0 8 Multilevel Switching, Dimming & Occupancy
N/A N/A 4
21 Police Service SECURE STORAGE Small Arms Armory, Storage - Secure
LVT RB P -- -- -- AT 9'-0" 3'-0" Flush Hollow Metal -- -- 200 P 75 70 60 - 4 2 Return NR NR M7 1 -- Multilevel Switching, Dimming & Occupancy
N/A N/A 4
22 VCS RETAIL AREA Retail Area EXAM - PUBLIC SPACE LVT RB P -- -- SEE FGI AT 9'-0 17 6'-0" Flush w/ Full Vision Wood Full Vision 47 KM 7, 9 M4 One per wall, 6' spacing -- Multilevel Switching, Dimming & Occupancy Track or adjustable accent lighting for retail displays. L5 3
24 OI&T TELECOMM.
Telecommunications Room/
Closet, IT Telecommunications Room
-- -- VT RB P -- -- -- EXP. 12'-0" 3'-6" Flush Wood -- -- 34 AS 64 75 55 30 - - - - NR 6 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4
24 OI&T SERVER ROOM Central Server Room -- -- VT RB P -- -- -- EXP 12'-0" 3'-6" Flush Wood -- -- 34 AS 72 81 60 6 M8 10 -- P15 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4
24 OI&T I.T. WORKROOM IT Workroom, Equip.
Configuration/ Repair
-- -- SD RB P -- -- -- AT 9'-0" 3'-0" Flush Wood -- -- 35 AG 10 -- P4, P6 Surface or chain mounted 1' x 4' Occupancy/vacancy N/A N/A 4
0 SPS STORAGE, CLEAN
SCOPE Storage, Clean Scope CLEAN SUPPLY -- RES RES EP RWC 4'-0" -- GYP-EP 9'-0 3, 7 3'-6" Flush w/
Narrow Vision Wood Narrow Vision -- 15 AG 66 75 55 30 4 (+) One per wall -- 2 X 2 recessed lensed Multilevel Switching, Dimming & Occupancy
Gyp ceiling - lights to be sealed type/flange mounted N/A --
Interior Finishes Notes
General Notes A. Hollow metal frames and doors to be painted.
B. Window sills to be solid surface fabrication.
C. Resilient base to be 4", unless otherwise noted.
D. Provide painted finishes only on inside of exterior walls (no wall covering).
E. Floor material transitions to occur at centerline of door, unless otherwise noted.
F. Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color.
G. Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety.
H. Coordinate height of wall protection with wall-mounted devices.
I. Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks, reception desks and lobby/waiting areas.
J. Soffit above upper cabinets to be gypsum board.
K. Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials.
L. Solid surface countertops to have sides and backsplash at walls.
Schedule Notes
1. CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling.
2. Tile base to be coved.
3. Integral coved base 6" high tightly sealed to walls.
4. If sink is present, use hard suface flooring as noted.
5. Lead lined walls and control area view window.
6. Flooring and base to match adjacent area flooring material and base.
7. Use gasketed, clip down ACT/grid system
8. Use slip-retardant finish on floor material
9. Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads. Stair nosings to be a contrasting color for safety.
10. Note that if wall saver designed chairs are used, no wall protection is required.
11. Extend all room partitions to structural deck.
12. CT above countertop on wall.
13. Ceiling height as required to acommodate equipment.
14. Cove QT base, 6" high.
15. No separate trim at top of base, use alternate method to seal to wall.
16. Ceiling suspension system should be fabricated from nonferromagnetic material.
17. Aesthetic specialty materials may be used as accents where the design and budget permits.
18. Ceiling tile to meet USDA regulations.
19. Floors to be slip-resistant and meet ANSI 326.3 for measuring dynamic coefficient of friction for hard surfaces
20. Wall base on gyp board but not needed on any exterior materials such as brick, metal, or stone walls.
21. Wall CT and ceiling to meet building code light reflectancy standards.
22. Space may be room or area within a room. Coordinate finishes with adjacent spaces.
23. Provide 3/4" painted plywood where required by Telecommunications.
AT Acoustical Ceiling Tile AT-SP Acoustical Scrubbable Ceiling Tile (with sprayed plastic finish) CPT Carpet Tile CS Concrete, Sealed CT Ceramic Tile (Wall) EP Epoxy Paint EXP Exposed Ceiling LVT Luxury Vinyl Tile Flooring MAT Modular Carpet Walk Off Mat P Paint PT Porcelain Tile QT Quarry Tile RB Resilient Base RES Resinous Flooring and Base RF Rubber Flooring RFT Resilient Floor Tile RSF Resilient Sheet Flooring - Heterogeneous RWC Rigid Wall Covering (Wall Protection) SD Static Dissipative Tile S Solid Surface Fabrication WSF Welded Seam Sheet Flooring - Homogeneous
Finish Codes
Hardware Notes tes
Refer to Lease Design Narrative (LDN) Appendix for Hardware Groups and Modifiers which are added to numeric hardware group assignments to indicate a variation to the group.
All doors to be 7'-0" high, unless otherwise noted.
Coordinate acoustical requirements for doors with required wall acoustical ratings as shown in Room Data Matrix - Interior Finishes in Appendix.
otes
Hollow metal frame cased opening
Two door (in swing and swing out) acoustical door and frame assembly.
Two doors required at this room/space.
Narrow lite optional. Use insulated or laminated glass to meet acoustical criteria.
Provide STC 50 rated acoustical door.
No door in this room/space.
Equal leaf pair of doors.
Lead lined door and hardware.
Space may be a room or area within another room. Omit door if space is not a separate room.
ELECTRICAL NOTES
POWER NOTES LIGHTING NOTES
P1. Multiple receptacles above and below desk for device charging, receptacles provided with Pre-Fab system.
L1. EMI/RFI emissions to be controlled
P2. Receptacles on all walls L2. Dimmable to 5 fc
P3. Coordinate electrical connections with equipment to be installed.
Receptacles on all walls.
L3. May not have ceiling - then use industrial fixture type
P4. Plug strip at 44" above counters L4. May not have ceiling. If no ceiling, use industrial fixture type
P5. Multiple receptacles above and below desk for device charging L5. Treat like a store. Adjustable lighting, General lighting.
P6. Cord reel(s) for freestanding workbenches L6. No ceiling in these rooms. No prescription for lighting.
P7. All outlets on dedicated circuits.
P8. Cord reel(s) for freestanding workbenches
P9. Treadmill on dedicated circuit
P10. Each hood on dedicated circuit
P11. Provide receptacles per equipment plan
P12. Electrical to review redundancy requirements with OIT guidelines.
P13. Receptacle above ceiling for overhead lift P14. Recessed power quad floor box P15. L21-20R receptacle above each rack P16. Electrical to support 8 workstations 2 duplex per station.
MECHANICAL HVAC NOTES
M1. Intentionally Left Blank M2. Per ASHRAE 62 for ventilation, and FGI Guidelines for NC M3. General Open Office area M4. General Open/Public area M5. Per ASHRAE 62 for ventilation if interior enclosed space.
M6. Comply with ASHRAE 15 if Special Refrigeration Systems are used M7. If chemicals are used, provide specialized exhaust M8. Data Center M9. Transfer air to Food Prep Kitchen M10. Intentionally Left Blank M11. MEP Room M12. See USP-797 and -800 M13. Counter-height specialized exhaust system required M14. Provide air conditioning and ventilation per imaging manufacturer recommendations
M15. General Office Area M16. Verify specific vendor/manufacturer requirements.
M17. Non-ferrous construction M18. Provide cooling only air terminal unit to serve the manual equipment wash M19. Provide a dedicated wet exhaust system