This transcript documents a pre-bid question and answer session for solicitation 36C10F23R0102 from the Department of Veterans Affairs for construction services related to the Tampa Community Living Center. Key details include that the solicitation is for construction of a new four-story building to house 120 beds to replace an existing community living center. The period of performance is 730 calendar days. Subcontracting goals include 8% for small businesses. An attendance roster lists 24 attendees from various construction firms. The transcript covers 15 questions primarily clarifying technical requirements and contract terms. The agency also announced a two-week extension to the response date due to numerous requests.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RDM Org
| ROOM DATA MATRIX | ELECTRICAL | IT | INTERIOR CONSTRUCTION | DOORS AND HARDWARE | MECHANICAL | INTERIOR CONSTRUCTION | |||||||||||||||||||||||||||||||||||||||||||
| ROOM IDENTIFICATION | POWER | LIGHTING | FLOOR | WALLS | CEILING | NOTES | Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. | FLOOR | WALLS | CEILING | NOTES | ||||||||||||||||||||||||||||||||||||||
| Functional Area | DEPARTMENT | ROOM NAME | ROOM NAMES (VA) | FGI EQUIVALENT FOR ASHRAE 170 | FGI EQUIVALENT FOR TABLE 2.5-2 Minimum Noise Criteria (NC) | # Duplex Receptacles | # Quad Receptacles | Power - Notes | Fixture Type | Controls | Lighting - Special Requirements | Lighting - Notes | # Data Outlets (standard density WAO) | IT - Special Requirements | Floor Finish | Base | Wall Finish | Wainscot Material | Wainscot Height | STC | Ceiling Finish | Height | Notes | Size (Width) | Type | Material | Glazing | Rating | Hardware Group | Hardware Notes | Indoor Temperature Cooling F | Indoor Temperature Heating F | Indoor Relative Humidity % RH Max | Indoor Relative Humidity % RH Min | Minimum Total ACH | Minimum OA ACH | Room Air Return Gen. Exh G Spec Exh S | Maximum Noise Level NC | Room Air Balance | HVAC Notes | Floor Finish | Base | Wall Finish | Wainscot Material | Wainscot Height | STC | Ceiling Finish | Height | Notes |
| 1 | Community Center | LACTATION ROOM | 30 | 4 | -- | P2 | Downlights and accent/display | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | LVT | PRB [8] | P | _ | _ | AT | 3'-0" | 19 | Wood | _ | 2G | LVT | PRB | P | _ | _ | 45-55 | ACT | 9'-0" | |||||||||||||||||||
| 1 | Community Center | LOBBY | 45 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | PT/LRT | PT/ PRB [8] | GWB P | _ | _ | GWB P/ACT | 3'-0" | 1 | Wood | T | 4G | LVT | PT/ PRB | P | _ | _ | 40-50 | GWB P/ACT | 9'-0" | ||||||||||||||||||||
| 1 | Community Center | CONCIERGE STATION | 45 | 2 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | Floor data jacks for concierge desk. | CPT | PRB/RB | GWB P | _ | _ | GWB P/ACT | CPT | PRB/RB | P | _ | _ | GWB P/ACT | |||||||||||||||||||||||||
| 1 | Community Center | FAMILY TOILET | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P /CT | _ | _ | GWB P | 19 | Wood | _ | 2G | PT | PT | PT | PT | 4'-0" | 45-55 | 0 | 9'-0" | 1,2,8 | |||||||||||||||||||||
| 1 | Community Center | WHEELCHAIR ALCOVE | -- | N/A | VT | RB | P | RWC | 4'-0" | GWB P/ACT | X | 4'-0" | 11 | Wood | T | 5B | Match Adjacent | Match Adjacent | P | RWC | 4'-0" | GWB P/ACT | Match Adjacent | 8 | |||||||||||||||||||||||||
| 1 | Community Center | PATIENT EDUCATION WORKSTATION | 40 | 2 | -- | N/A | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT [6] | RB | GWB P | _ | _ | AT P | OPEN | CPT | RB | P | _ | _ | ACT P | Match Adjacent | ||||||||||||||||||||||||
| 1 | Community Center | AUTOMATED TELLER MACHINE | 1 | -- | N/A | Downlights | N/A | N/A | 1 | Coordinate data connection with firm installing ATM | LVT | RB | GWB P | _ | _ | GWB P | OPEN | Match Adjacent | Match Adjacent | P | _ | _ | GWB P | Match Adjacent | 8 | ||||||||||||||||||||||||
| 2 | Community Center | GREAT ROOM | 45 | 10 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 4 | coordinate locations | CPT | PRB/RB | GWB P | _ | _ | GWB P/ACT | LVT | PRB | P | _ | _ | GWB P/ACT | 10'-0" | ||||||||||||||||||||||||
| 2 | Community Center | THEATER | 30 | 8 | -- | P2 | Downlights and accent/display | Multilevel Switching, Dimming & Occupancy | N/A | L2 | CPT/LRT | PRB | GWB P | _ | _ | GWB P/ACT | CPT/LVT | PRB | P | _ | _ | GWB P/ACT | 10'-0" | ||||||||||||||||||||||||||
| 2 | Community Center | HAIR CARE SALON / SHOP | 45 | 4 | 4 | P2, P18 | Downlights and accent/display | Multilevel Switching, Dimming & Occupancy | N/A | N/A | LRT/RSF | PRB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 1 | Wood | T | 4E | LVT/RSF | PRB | P | RWC | 4'-0" | 40-50 | GWB P/ACT | 9'-0" | 8, 23 | |||||||||||||||||||
| 2 | Community Center | SMALL HOUSE LIBRARY | 30 | 8 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT | PRB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 1 | Wood | T | 4J | CPT | PRB | P | _ | _ | 45-55 | GWB P/ACT | 10'-0" | |||||||||||||||||||
| 2 | Community Center | RESIDENT CARE UNIT CHAPEL / MEDITATION ROOM | 30 | 6 | -- | P2 | Downlights and accent/display | Multilevel Switching, Dimming & Occupancy | N/A | L2 | CPT [6] | PRB [8] | GWB P | _ | _ | GWB P/ACT | 3'-8" | 19 | Wood | T | 4J | CPT | PRB | P | _ | _ | 45-55 | GWB P/ACT | 10'-0" | ||||||||||||||||||||
| 2 | Community Center | RETAIL STORE | 45 | 8 | -- | P2 | Downlights and accent/display | Multilevel Switching, Dimming & Occupancy | N/A | L5 | 2 | LRT/CPT | PRB | GWB P | _ | _ | GWB P/ACT | LVT | PRB | P | _ | _ | 40-50 | GWB P/ACT | 10'-0" | 8 | |||||||||||||||||||||||
| 2 | Community Center | POST OFFICE | 45 | 1 | -- | N/A | Downlights and accent/display | N/A | L8 | 1 | RT/CPT | PRB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 19 | Wood | T | 3G | RFT | PRB | P | _ | _ | 40-50 | GWB P/ACT | 10'-0" | ||||||||||||||||||||
| 3 | Community Center | EQUIPMENT STORAGE ROOM | 1 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | VT | RB | GWB [54], P | RWC | 4'-0" | GWB P/AT | 3'-8" | 1 | Wood | T | LVT | RB | P | RWC | 4'-0" | GWB P/ACT | 9'-0" | |||||||||||||||||||||||
| 3 | Community Center | BIOMEDICAL ENGINEER WORKROOM | 40 | 8 | -- | P2, P4 | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | 2 | CPT [6] | RB | GWB P | _ | _ | AT | OPEN | ET | ET | EP | _ | _ | 45-55 | ACT P | 9'-0" | |||||||||||||||||||||||
| 3 | Community Center | EMPTY GAS CYLINDER STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | C[10] | RB | GWB P | RWC | 4'-0" | AT | 3'-8" | 11, 12 | Wood, Steel | F | 45 min | LVT | RB | P | RWC | 4'-0" | 40-50 | ACT | 9'-0" | |||||||||||||||||||||
| 3 | Community Center | MAILROOM | 45 | 6 | -- | P2 | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | 2 | SVT, RF | RB | GWB P | _ | _ | AT | 3'-6" | 3 | Wood | T | SVT, RSF | RB | P | _ | _ | 45-55 | ACT | 10'-0" | ||||||||||||||||||||
| 3 | Community Center | SML HS COMM CTR HAIR CARE SALON / SHOP STORAGE ROOM | 45 | 1 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RSF | RB | GWB P | SWP | GWB P/ACT | 3'-0" | 1 | Wood | T | 4E | RSF | RB | P | SWP | 40-50 | GWB P/ACT | 9'-0" | 23 | |||||||||||||||||||||
| 3 | Community Center | SML HS COMM CTR RECEIVING / LOADING | 2 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | L3 | RES | RB | GWB [54] P | RWC | 4'-0" | GWB P/ACT | 3'-8" | 11 | Wood | _ | 5F | CS | RB | P | RWC | 4'-0" | 40-50 | GWB P/ACT | 10'-0" | |||||||||||||||||||||
| 3 | Community Center | CLEAN LINEN STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | WSF | WSF | GWB [54], SC | RWC | 4'-0" | AT SP | SS | 11 | Wood | F | SH-9A | WSF | WSF | P | RWC | 4'-0" | 40-50 | ACT SP | 9'-0" | 3 | ||||||||||||||||||||
| 3 | Community Center | SOILED LINEN DISTRIBUTION ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | WSF | WSF | GWB [54], SC | RWC | 4'-0" | AT [9] SP | SS | 11 | Wood | T | 45 min | SH-9A | WSF | WSF | P | RWC | 4'-0" | 40-50 | ACT SP | 9'-0" | 3 | |||||||||||||||||||
| 3 | Community Center | SATELLITE PHARMACY | 40 | 8 | -- | P3,P17 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | LVT | PRB [8] | GWB SC | _ | _ | GWB P/AT | 3'-8" | 36 | Steel | T | SH-3D | WSF | WSF | P | _ | _ | 45-55 | GWB P/ACT | 10'-0" | 3 | ||||||||||||||||||
| 4 | Community Center | STAFF TOILET | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P/CT | _ | _ | GWB P | 3'-0" | 1 | Wood | _ | 2 [71], 4U [31] | PT | PT | PT/P | PT | 4'-0" | 45-55 | GWB P | 8'-0" | 1,2,8 | ||||||||||||||||||||
| 4 | Community Center | STAFF WORKROOM | 40 | 8 | -- | P2,P5 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 8 | Coordinate # of outlets with # of workstations. | RF | RB | GWB P/CT | _ | _ | AT | 3'-0" | 1 | Wood | T | 4J | CPT | RB | P | _ | _ | 45-55 | ACT | 9'-0" | ||||||||||||||||||
| 4 | Community Center | CHIEF NURSE OFFICE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT [6] | RB | GWB [64] P | _ | _ | AT | 3'-0" | 1 | Wood | T | 3E | CPT | RB | P | _ | _ | 45-55 | ACT | 9'-0" | |||||||||||||||||||
| 4 | Community Center | SML HS COMM CTR ASSOCIATE DIRECTOR OFFICE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT | PRB/RB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 19 | Wood | _ | 3E | CPT | PRB/RB | P | _ | _ | 45-55 | GWB P/ACT | 9'-0" | |||||||||||||||||||
| 4 | Community Center | SML HS COMM CTR DIRECTOR OFFICE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT | PRB/RB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 19 | Wood | _ | 3E | CPT | PRB/RB | P | _ | _ | 45-55 | GWB P/ACT | 9'-0" | |||||||||||||||||||
| 4 | Community Center | SHARED OFFICE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT | PRB/RB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 19 | Wood | _ | 3E | CPT | PRB/RB | P | _ | _ | 45-55 | GWB P/ACT | 9'-0" | |||||||||||||||||||
| 4 | Community Center | SML HS COMM CTR STAFF BREAKROOM | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | RT/RSF | PRB/RB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 22 | Wood | _ | 3E | LVT | PRB/RB | P | _ | _ | 45-55 | GWB P/ACT | 9'-0" | 8 | ||||||||||||||||||
| 4 | Community Center | SML HS COMM CTR COPY / SUPPLY ROOM | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | SVT | RB | GWB P | _ | _ | GWB P/AT | 3'-0" | 19 | Wood | T | 4G | LVT | RB | P | _ | _ | 40-50 | GWB P/ACT | 9'-0" | |||||||||||||||||||
| 4 | Community Center | SML HS COMM CTR NURSE MANAGER OFFICE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT [6] | RB | GWB [64] P | _ | _ | AT | 3'-0" | 1 | Wood | T | 3E | CPT | RB | P | _ | _ | 45-55 | ACT | 9'-0" | |||||||||||||||||||
| 1 | Food Preparation and Food Service | HOUSEKEEPING AIDES CLOSET (HAC) | 1 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | L3 | QT | QT [7] | CT [7] P | _ | _ | AT SP | OPEN | QT | QT | CT | _ | _ | 40-50 | ACT SP | 8'-0" | |||||||||||||||||||||||||
| 1 | Food Preparation and Food Service | CART WASHER ROOM | 2 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | L9 | RES | RES [7] | CT [7] | _ | _ | GWB SC | AS REQ'D | 12 | Steel | T | 10B | RES | RES | CT | _ | _ | 40-50 | GWB SC | AS REQ'D | |||||||||||||||||||||
| 1 | Food Preparation and Food Service | DIETITIAN AND ASSISTANT OFFICE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT [6] | RB | GWB, P | _ | _ | AT | 3'-0" | 19 | Wood | T | CPT | RB | P | _ | _ | 45-55 | ACT | 9'-0" | ||||||||||||||||||||
| 1 | Food Preparation and Food Service | FOOD PRODUCTION/SERVICE FOREMAN OFFICE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT [6] | RB | GWB, P | _ | _ | AT | OPEN | CPT | RB | P | _ | _ | 45-55 | ACT | 9'-0" | |||||||||||||||||||||||
| 1 | Food Preparation and Food Service | NOURISHMENT ROOM | 6 | -- | P2 | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | SVT, LVT | RB | GWB P | _ | _ | AT | 3'-0" | 1 | Wood | T | LVT | RB | P | _ | _ | 40-50 | ACT | 9'-0" | ||||||||||||||||||||||
| 1 | Food Preparation and Food Service | BULK FOOD CART ASSEMBLY AREA | 1 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | VT | RB | GWB | RWC | 4'-0" | AT | 3'-8" | 1 | Wood | _ | 4N | RES | RES | P SC | RWC | 4'-0" | 40-50 | ACT | 10'-0" | |||||||||||||||||||||
| 1 | Food Preparation and Food Service | FOOD CART (HOT / COLD) HOLDING ROOM | 1 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RES | RES [7] | CT [7] | _ | _ | AT SP | 3'-8" | 19 | Wood | T | RES | RES | CT | _ | _ | 40-50 | ACT SP | 10'-0" | ||||||||||||||||||||||
| 1 | Food Preparation and Food Service | CLEANING SUPPLY STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | VT | RB | GWB [54] P | RWC | 4'-0" | AT | 3'-6" | 1 | Wood | RSF | RES | P | RWC | 4'-0" | 40-50 | ACT | 10'-0" | |||||||||||||||||||||||
| 1 | Food Preparation and Food Service | NON-FOOD STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | VT | RB | GWB P | RWC | 4'-0" | AT | USVT | 11 | Wood | _ | 4N | RES | RES | P | RWC | 4'-0" | 40-50 | ACT | 10'-0" | |||||||||||||||||||||
| 1 | Food Preparation and Food Service | FOOD COURT RECEIVING | 2 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | L3 | SVT | RB | GWB P | _ | _ | AT | 9'-0" | MOTORIZED ROLL UP | 7 | RES | RES | P | _ | _ | 40-50 | ACT | 10'-0" | |||||||||||||||||||||||
| 1 | Food Preparation and Food Service | DRY-FOOD STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | SVT | RB | GWB P | _ | _ | AT | 3'-8" | 1 | Wood | _ | 5E | RES | RES | P | _ | _ | 40-50 | ACT | 10'-0" | |||||||||||||||||||||
| 1 | Food Preparation and Food Service | REFRIGERATED / FROZEN FOOD STORAGE ROOM | 4 | -- | P11 | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RES [63] | RES [7] | PRE-FAB [66] | _ | _ | PRE-FAB [66] | PRE-FAB [66] | N/A | RES | RES | PRE-FAB | _ | _ | 40-50 | PRE-FAB | AS REQ'D | ||||||||||||||||||||||||
| 1 | Food Preparation and Food Service | FOOD PREPARATION / PRODUCTION | 4 | -- | P11 | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RES [63] | RES [7] | CT [7] P | _ | _ | AT SP | OPEN | N/A | RES | RES | CT | _ | _ | 40-50 | ACT SP | 10'-0" | ||||||||||||||||||||||||
| 1 | Food Preparation and Food Service | DINING UTENSILS WASHING ROOM | 2 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | L9 | RES | RES [7] | CT [7] P | _ | _ | AT SP | OPEN | N/A | PT | PT | CT | _ | _ | 40-50 | ACT SP | 10'-0" | 1,3,8 | |||||||||||||||||||||||
| 1 | Food Preparation and Food Service | POT WASHING ROOM | 2 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | L9 | RES | RES [7] | CT [7] P | _ | _ | AT SP | OPEN | N/A | RES | RES | CT | _ | _ | 40-50 | ACT SP | 10'-0" | ||||||||||||||||||||||||
| 1 | Food Preparation and Food Service | SANITATION / RECYCLING ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RES | RES [7] | CT [7] | _ | _ | AT SP | 3'-8" | 1, 2 | Wood, Steel | T | 4M | RES | RES | CT | _ | _ | 40-50 | ACT SP | 10'-0" | |||||||||||||||||||||
| 1 | Food Preparation and Food Service | CAFETERIA SERVING AREA | 35 | 4 | -- | P11 | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | PT | PT [7] | GWB P | _ | _ | AT | 3'-8" | 3 | Wood | T | 4K | PT | PT | P | _ | _ | 40-50 | ACT | 10'-0" | ||||||||||||||||||||
| 1 | Neighborhood Center | LOBBY | 45 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | PT/LRT | PT/PRB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 1 | Wood | T | 4G | LVT | PRB | P | _ | _ | 40-50 | GWB P/ACT | AS REQ'D BY DESIGN | ||||||||||||||||||||
| 1 | Neighborhood Center | FAMILY TOILET | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P/CT | _ | _ | GWB P | 3'-0" | 19 | Wood | _ | 2 [71], 4U [31] | PT | PT | PT/P | PT | 4'-0" | 45-55 | GWB P | 8'-0" | 1,2,8 | ||||||||||||||||||||
| 1 | Neighborhood Center | UNIVERSAL NON-PATIENT TOILET | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P/CT | _ | _ | GWB P | 3'-0" | 19 | Wood | _ | 2 [71], 4U [31] | PT | PT | PT/P | PT | 4'-0" | 45-55 | GWB P | 8'-0" | 1,2,8 | ||||||||||||||||||||
| 2 | Neighborhood Center | KINESIOTHERAPY (KT) ROOM | 45 | 8 | -- | P2,P11 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | RF/LVT | PRB [8] | GWB [64] P | _ | _ | GWB P/ACT | SS | 19 | Wood | T | 10A | RF | RB | PT/P | _ | _ | 45-55 | GWB P/ACT | 10'-0" | 8 | |||||||||||||||||||
| 2 | Neighborhood Center | PHYSICAL THERAPY (PT) ROOM | 45 | 8 | -- | P2,P11 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | RT, LVT | PRB [8] | GWB [64] P | _ | _ | GWB P/AT | SS | 19 | Wood | T | 10A | RF | RB | PT/P | _ | _ | 45-55 | GWB P/ACT | 10'-0 | 8 | |||||||||||||||||||
| 2 | Neighborhood Center | MULTIPURPOSE ACTIVITY ROOM | 45 | 8 | -- | P2,P11 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | CPT/LRT | PRB | GWB P | _ | _ | GWB P/ACT | 3'-8" | 19 | Wood | T | 1Q | RF | RB | P | _ | _ | 55-60 | GWB P/ACT | 10'-0" | 8 | |||||||||||||||||||
| 2 | Neighborhood Center | KITCHENETTE | 45 | 4 | -- | P2,P11 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | PT | PT | PT/P | _ | _ | 40-50 | ACT | 9'-0" | 1,2,8 | ||||||||||||||||||||||||||||||
| 2 | Neighborhood Center | SNOEZELEN SENSORY THERAPY ROOM | 30 | 4 | -- | P2,P11 | Downlights and specialty lighting | Multilevel Switching, Dimming & Occupancy | N/A | N/A | CPT/LRT | PRB | GWB P | _ | _ | GWB P/ACT | 3'-8" | 19 | Wood | T | 1Q | PT | PT | PT/P | _ | _ | 55-60 | GWB P/ACT | 9'-0" | 1,2,8 | |||||||||||||||||||
| 2 | Neighborhood Center | NAMASTE SENSORY THERAPY ROOM | 30 | 4 | -- | P2,P11 | Downlights and specialty lighting | Multilevel Switching, Dimming & Occupancy | N/A | N/A | CPT/LRT | PRB | GWB P | _ | _ | GWB P/ACT | 3'-8" | 19 | Wood | T | 1Q | PT | PT | PT/P | _ | _ | 55-60 | GWB P/ACT | 9'-0" | 1,2,8 | |||||||||||||||||||
| 2 | Neighborhood Center | EXAM ROOM | 40 | 4 | -- | P3 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | RT/RSF | RB | GWB P | _ | _ | GWB P/ACT | 4'-0" | 19 | Wood | _ | 1L | LVT | RB | P | _ | _ | 55-60 | GWB P/ACT | 9'-0" | 8 | |||||||||||||||||||
| 2 | Neighborhood Center | SPECIALTY CONSULT ROOM | 40 | 4 | -- | P3 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | RT/RSF | RB | GWB P | _ | _ | GWB P/ACT | 4'-0" | 19 | Wood | _ | 1L | PT | PT | PT/P | _ | _ | 55-60 | GWB P/ACT | 9'-0" | 1,2,8 | |||||||||||||||||||
| 3 | Neighborhood Center | GENERAL STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RT/RSF | RB | GWB P | _ | _ | GWB P/ACT | 3'-8" | 11 | Wood | F | 5B | LVT | RB | PT/P | _ | _ | 40-50 | GWB P/ACT | 9'-0" | 8 | ||||||||||||||||||||
| 3 | Neighborhood Center | SOILED UTILITY ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RSF | SCB | GWB EP | _ | _ | GWB P/ACT | 3'-8" | 11 | Wood | T | SH-3C | WSF | WSF | PT/P | _ | _ | 40-50 | GWB P/ACT | 9'-0" | 3,8 | ||||||||||||||||||||
| 3 | Neighborhood Center | CLEAN LINEN ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RSF | SCB | GWB EP | _ | _ | GWB P/ACT | WSF | WSF | PT/P | _ | _ | 40-50 | GWB P/ACT | 9'-0" | 3,8 | |||||||||||||||||||||||||
| 4 | Neighborhood Center | SUPERVISOR OFFICE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT [6] | RB | GWB P | _ | _ | GWB P/AT | 3'-0" | 1 | Wood | T | 3E | PT | PT | PT/P | _ | _ | 45-55 | GWB P/ACT | 9'-0" | 1,2,8 | ||||||||||||||||||
| 4 | Neighborhood Center | STAFF WORKSTATION | 40 | 1 | -- | N/A | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT [6] | RB | GWB P | RWC | 4'-0" | GWB P/AT | 3'-0" | 19 | Wood | _ | CPT | RB | PT/P | _ | _ | 45-55 | 24 | |||||||||||||||||||||
| 4 | Neighborhood Center | CONFERENCE ROOM | 35 | 4 | 1 | P2,P14 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | Provide data outlet with quad power outlet in floor box. | CPT, LVT | RB | GWB [42, 64] P | _ | _ | GWB P/AT | 3'-8" | 19 | Wood | T | 4J | PT | PT | PT/P | _ | _ | 55-60 | GWB P/ACT | 9'-0" | 1,2,8 | |||||||||||||||||
| 1 | Resident House | FOYER | 45 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | PT/LRT | PT/PRB | GWB P | _ | _ | GWB P/ACT | LVT | RB | PT/P | _ | _ | 40-50 | GWB P/ACT | 9'-0" | 8 | ||||||||||||||||||||||||
| 1 | Resident House | UNIVERSAL NON-PATIENT TOILET | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P/CT | _ | _ | GWB P | 3'-0" | 19 | Wood | _ | 2 [71], 4U [31] | PT | PT | PT/P | PT | 4'-0" | 45-55 | GWB P | 9'-0" | 1,2,8 | ||||||||||||||||||||
| 2 | Resident House | SINGLE UNIVERSAL BEDROOM | 40 | 4 | -- | P2 | Downlights | Occupancy Sensor | N/A | N/A | CPT [6], LVT | PRB [8] | GWB P | _ | _ | GWB P/AT | 4'-0" | 1 | Wood | T | R1 | LVT | RB | PT/P | PT | _ | 55-60 | GWB P/ACT | 9'-0" | 8 | |||||||||||||||||||
| 2 | Resident House | BEDROOM CLOSET | -- | -- | N/A | None | N/A | N/A | N/A | LVT | RB | PT/P | PT | _ | 45-50 | GWB P/ACT | 8'-0" | 8 | |||||||||||||||||||||||||||||||
| 2 | Resident House | SITTING ALCOVE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | CPT/LRT | PRB | GWB P | _ | _ | GWB P/ACT | Match Adjacent | Match Adjacent | PT/P | PT | _ | 40-50 | GWB P/ACT | 8'-0" | 1,2,8 | ||||||||||||||||||||||||
| 2 | Resident House | LIVING ROOM | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | CPT [6], LVT | PRB [8] | P | _ | _ | GWB P/ACT | 3'-8" | 19 | Wood | T | R7 | LVT | RB | PT/P | PT | _ | 45-55 | GWB P/ACT | 10'-0" | 8 | |||||||||||||||||||
| 2 | Resident House | DINING ROOM | 35 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | LVT | PRB [8] | P | _ | _ | GWB P/ACT | SS | 1 | Wood | T | R2C | LVT | RB | PT/P | PT | _ | 45-55 | GWB P/ACT | 10'-0" | 8 | |||||||||||||||||||
| 2 | Resident House | KITCHEN | 40 | 4 | -- | P2,P3 | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | PT/LRT/ET | PT/PRB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 1 | Wood | _ | R2 | PT | Match Adjacent | PT/P | PT | _ | 45-55 | GWB P/ACT | 9'-0" | 1,2,8 | |||||||||||||||||||
| 2 | Resident House | PANTRY | 1 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | PT/LRT/ET | PT/PRB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 1 | Wood | _ | R2 | PT | CT | CT | _ | _ | 45-55 | GWB P/ACT | 9'-0" | 1,2,8 | ||||||||||||||||||||
| 2 | Resident House | DEN | 40 | 4 | -- | P2 | Downlights | Occupancy Sensor | N/A | N/A | CPT/LRT | PRB | GWB P | _ | _ | GWB P/ACT | PT | Match Adjacent | PT/P | PT | _ | 45-55 | GWB P/ACT | 9'-0" | 1,2,8 | ||||||||||||||||||||||||
| 2 | Resident House | LAUNDRY ROOM | 4 | -- | P2,P3 | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RT/RSF | RB/PRB | GWB P | _ | _ | GWB P/ACT | 3'-8" | 1 | Wood | T | 4K | WSF | WSF | PT/P | PT | _ | 45-55 | GWB P/ACT | 9'-0" | 3 | ||||||||||||||||||||
| 2 | Resident House | SMALL HOUSE SINGLE-USER PATIENT BATHROOM (ADJACENT TO BATHING SUITE) | 40 | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P/CT | _ | _ | GWB P | 4'-0" | 1 | Wood | T | R3 | PT | PT | PT/P | PT | _ | 55-60 | GWB P | 9'-0" | 1,2,8 | |||||||||||||||||||
| 2 | Resident House | SMALL HOUSE SINGLE-USER PATIENT BATHING ROOM | 40 | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P/CT | _ | _ | GWB P | 4'-0" | 1 | Wood | T | R3 | PT | PT | PT/P | PT | _ | 55-60 | GWB P | 9'-0" | 1,2,8 | |||||||||||||||||||
| 2 | Resident House | UNIVERSAL PATIENT TOILET | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P/CT | _ | _ | GWB P | 3'-0" | 19 | Wood | _ | 2 [71], 4U [31] | PT | Match Adjacent | PT/P | PT | 4'-0" | 55-60 | GWB P | 9'-0" | 1,2,8 | ||||||||||||||||||||
| 2 | Resident House | KITCHEN HOUSEKEEPING CLOSET | 1 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | L3 | QT | QT [7] | CT [7] P | _ | _ | AT SP | OPEN | _ | PT | Match Adjacent | PT/P | _ | _ | 40-50 | ACT SP | 8'-0" | 1,2,8 | |||||||||||||||||||||||
| 2 | Resident House | CLEAN LINEN ALCOVE | -- | -- | N/A | None | N/A | N/A | N/A | LVT | RB | GWB [54] P | RWC | 4'-0" | AT | OPEN | _ | Match Adjacent | Match Adjacent | PT/P | _ | 4'-0" | 40-50 | ACT SP | 8'-0" | 1,2,8 | |||||||||||||||||||||||
| 3 | Resident House | SPECIALTY STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RT/RSF | RB | GWB P | SWP | GWB P/ACT | LVT | RB | PT/P | _ | 4'-0" | 40-50 | GWB P/ACT | 8'-0" | 8 | ||||||||||||||||||||||||||
| 3 | Resident House | CLEAN MED EQUIPMENT STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | VT | RB | GWB [54] P | RWC | 4'-0 | GWB P/AT | 3'-8" | 1 | Wood | T | WSF | WSF | PT/P | _ | 4'-0 | 40-50 | GWB P/ACT | 8'-0" | 3,8 | |||||||||||||||||||||
| 3 | Resident House | GARAGE / RECEIVING | 2 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | L3 | RT/RSF/EP | RP/EP | GWB P | _ | _ | GWB P | 3'-8" | 11 | Wood | 5F | RES | RES | PT/P | _ | _ | 55-60 | GWB P | 9'-0" | 8 | |||||||||||||||||||||
| 3 | Resident House | GAS MANIFOLD ROOM | 1 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | EP | ECB | GWB P | _ | _ | GWB P | PT | PT | PT/P | _ | _ | 40-50 | GWB P | 9'-0" | 1,2,8 | |||||||||||||||||||||||||
| 3 | Resident House | FULL GAS CYLINDER STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | C[10] | RB | GWB [54] P | RWC | 4'-0" | AT | 3'-8" | 11, 12 | Wood, Steel | F | 45 min | 5B | RES | RES | PT/P | _ | 4'-0" | 40-50 | ACT | 9'-0" | 8 | |||||||||||||||||||
| 3 | Resident House | EMPTY GAS CYLINDER STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | C[10] | RB | GWB [54] P | RWC | 4'-0" | AT | 3'-8" | 11, 12 | Wood, Steel | F | 45 min | 5B | LVT | RB | PT/P | _ | 4'-0" | 40-50 | ACT | 9'-0" | 8 | |||||||||||||||||||
| 3 | Resident House | GENERAL STORAGE ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RT/RSF | RB | GWB P | SWP | GWB P/ACT | 3'-8" | 11 | Wood | F | 5B | LVT | RB | PT/P | _ | 4'-0" | 40-50 | GWB P/ACT | 9'-0" | 8 | |||||||||||||||||||||
| 3 | Resident House | SML HS RECEIVING / BREAKDOWN ROOM | 2 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | L3 | RT/RSF/EP | RB/EP | GWB P | _ | _ | GWB P | 3'-8" | 11 | Wood | _ | 5F | RES | RES | PT/P | _ | _ | 45-55 | GWB P | 9'-0" | 8 | ||||||||||||||||||||
| 3 | Resident House | CLEAN UTILITY ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RSF | SCB | GWB P | _ | _ | GWB P/ACT | 3'-8" | 11 | Wood | F | 45 min | SH-3C | WSF | WSF | PT/P | _ | _ | 40-50 | GWB P/ACT | 9'-0" | 3,8 | |||||||||||||||||||
| 3 | Resident House | SOILED CART STAGING ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | WSF | ESF | GWB SC | RWC | 4'-0" | GWB P, AT [9] SP | 3'-8" | 1 | Wood | T | SH-3C | PT | PT | PT/P | _ | 4'-0" | 40-50 | GWB P, ACT, SP | 9'-0" | 1,2,8 | ||||||||||||||||||||
| 3 | Resident House | CLEAN LINEN ROOM | -- | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | RSF | SCB | GWB EP | _ | _ | GWB P/ACT | 3'-8" | 11 | Wood | _ | SH-3C | WSF | WSF | PT/P | _ | _ | 40-50 | GWB P/ACT | 9'-0" | 3,8 | ||||||||||||||||||||
| 3 | Resident House | MEDICATION ROOM | 35 | 2 | -- | P3,P17 | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | VT | RB | GWB P | _ | _ | GWB P/ACT | 3'-0" | 1 | Wood | T | SH-3D | LVT | RB | PT/P | _ | _ | 40-50 | GWB P/ACT | 9'-0" | 8 | |||||||||||||||||||
| 4 | Resident House | FEMALE NON-PATIENT TOILET | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P/ CT | PT/CT | PT/CT | GWB P | 3'-0" | 19 | Wood | _ | PT | PT | PT/P | PT | 4'-0" | 55-60 | GWB P | 8'-0" | 1,2,8 | |||||||||||||||||||||
| 4 | Resident House | MALE NON-PATIENT TOILET | 1 | -- | N/A | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | PT/CT | PT/CT | GWB P/ CT | PT/CT | PT/CT | GWB P | 3'-0" | 19 | Wood | _ | PT | PT | PT/P | PT | 4'-0" | 55-60 | GWB P | 8'-0" | 1,2,8 | |||||||||||||||||||||
| 4 | Resident House | SUPERVISOR OFFICE | 40 | 4 | -- | P2 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | CPT [6] | RB | GWB P | _ | _ | GWB P/AT | 3'-0" | 1 | Wood | T | 3E | CPT | RB | P | _ | _ | 45-55 | GWB P/ACT | 9'-0" | |||||||||||||||||||
| 4 | Resident House | PERSONAL PROPERTY LOCKER | 1 | -- | N/A | 2 x 2 recessed lensed | Occupancy Sensor | N/A | N/A | PT | PT | GWB SC | PT [7], CT [7] | 4'-0" | AT | 3'-0" | 1 | Wood | _ | SH-4 | PT | PT | SC | PT, CT | 4'-0" | 40-50 | ACT | 9'-0" | 1,3,8 | ||||||||||||||||||||
| 4 | Resident House | BREAKROOM | 40 | 4 | -- | P2,P11 | 2 x 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | N/A | N/A | SVT | RB | GWB P | _ | _ | AT | 3'-0" | 1 | Wood | _ | SH-4 | LVT | RB | P | _ | _ | 55-60 | ACT | 9'-0" | 8 |
Interior Finishes Notes
| Interior Finishes Notes | |
| General Notes | |
| A. | Hollow metal frames and doors to be painted. |
| B. | Window sills to be solid surface fabrication. |
| C. | Resilient base to be 4", unless otherwise noted. |
| D. | Provide painted finishes only on inside of exterior walls (no wall covering). |
| E. | Floor material transitions to occur at centerline of door, unless otherwise noted. |
| F. | Wall brackets, grills, fire extinguisher cabinets, fin tube radiation, etc. to be painted to match adjacent wall color. |
| G. | Interior stairwell treads to be concrete with rubber nosings and RFT, LVT or RF landings. Stair nosings to be a contrasting color for safety. |
| H. | Coordinate height of wall protection with wall-mounted devices. |
| I. | Gypsum board soffits may be substituted for ACT above locations such as nurse stations, patient transaction/consultation desks, reception desks and |
| lobby/waiting areas. | |
| J. | Soffit above upper cabinets to be gypsum board. |
| K. | Refer to FGI recommendations regarding indoor air quality, sustainability and life cycle of materials. |
| Schedule Notes | |
| 1 | CT tile to 7'-0" on plumbing and adjacent wall(s) with paint above to ceiling. |
| 2 | Tile base to be coved. |
| 3 | Integral coved base 6" high tightly sealed to walls. |
| 4 | If sink is present, use hard suface flooring as noted. |
| 5 | Lead lined walls and control area view window. |
| 6 | Flooring and base to match adjacent area flooring material and base. |
| 7 | Use gasketed, clip down ACT/grid system |
| 8 | Use slip-resistant finish on floor material |
| 9 | Public and exposed open stairways to be treated similar to adjacent spaces using CT/PT/RF on treads. Stair nosings to be a contrasting color for safety. |
| 10 | Note that if wall saver designed chairs are used, no wall protection is required. |
| 11 | Extend all room partitions to structural deck. |
| 12 | CT above countertop on wall. |
| 13 | Ceiling height as required to acommodate equipment. |
| 14 | Cove QT base, 6" high. |
| 15 | No separate trim at top of base, use alternate method to seal to wall. |
| 16 | Ceiling suspension system should be fabricated from nonferromagnetic material. |
| 17 | Aesthetic specialty materials may be used as accents where the design and budget permits. |
| 18 | Ceiling tile to meet USDA regulations. |
| 19 | Floors to be slip-resistant and meet ANSI 326.3 for measuring dynamic coefficient of friction for hard surfaces |
| 20 | Wall base on gyp board but not needed on any exterior materials such as brick, metal, or stone walls. |
| 21 | Wall CT and ceiling to meet building code light reflectancy standards. |
| 22 | Space may be room or area within a room. Coordinate finishes with adjacent spaces. |
| 23 | Chemical resistant flooring material |
| 24 | Floor and base finishes are for space product occupies, oterwise, mfr standard. |
| Finish Codes | |
| ACT | Acoustical Ceiling Tile |
| ACT-SP | Acoustical Scrubbable Ceiling Tile (with sprayed plastic finish) |
| C | Concrete |
| CPT | Carpet Tile |
| CS | Concrete, Sealed |
| CT | Ceramic Tile (Wall) |
| EP | Epoxy Paint |
| ET | Epoxy Terrazzo (Tile or Poured) |
| EXP | Exposed Ceiling |
| GWB | Gypsum Wallboard Systems |
| LVT | Luxury Vinyl Tile |
| P | Paint |
| PRB | Profile Base |
| PT | Porcelain Tile |
| QT | Quarry Tile |
| RAF | Resilitent Athletic Flooring |
| RB | Resilient Base |
| RES | Resinous Flooring and Base |
| RES-W | Resinous/Epoxy Wall/Ceiling |
| RF | Rubber Flooring |
| RFT | Resilient Floor Tile |
| RSF | Resilient Sheet Flooring - Heterogeneous |
| RWC | Rigid Wall Covering (Wall Protection) |
| S | Solid Surface Fabrication |
| SC | High Build Glazed Coating (Special Coating) |
| SD | Static Dissipative Tile |
| SVT | Solid Vinyl Floor Tile |
| SWP | Sheet Wall Protection |
| VT | Vinyl Tile (High Content Vinyl) |
| WSF | Welded Seam Sheet Flooring - Homogeneous |
Doors and Hardware Notes
| Doors and Hardware Notes | |
| General Notes | |
| A. | Refer to Lease Design Narrative (LDN) Appendix for Hardware Groups and Modifiers which are added to numeric hardware group assignments to indicate a variation to the group. |
| B. | All doors to be 7'-0" high, unless otherwise noted. |
| C. | Coordinate acoustical requirements for doors with required wall acoustical ratings as shown in Room Data Matrix - Interior Finishes in Appendix. |
| D. | Refer to VA Door Hardware Specifications Section 08 71 00 for Hardware Groups and Modifiers. |
| Schedule Notes | |
| 1 | Hollow metal frame cased opening |
| 2 | Two door (in swing and swing out) acoustical door and frame assembly. |
| 3 | Two doors required at this room/space. |
| 4 | Narrow lite optional. Use insulated or laminated glass to meet acoustical criteria. |
| 5 | Provide STC 50 rated acoustical door. |
| 6 | No door in this room/space. |
| 7 | Equal leaf pair of doors. |
| 8 | Lead lined door and hardware. |
| 9 | Space may be a room or area within another room. Omit door if space is not a separate room. |
Electrical Notes
ELECTRICAL NOTES
POWER NOTES LIGHTING NOTES
| P1. | Multiple receptacles above and below desk for device charging, receptacles provided with Pre-Fab system. | L1. | EMI/RFI emissions to be controlled |
| P2. | Receptacles on all walls | L2. | Dimmable to 5 fc |
| P3. | Coordinate electrical connections with equipment to be installed. Receptacles on all walls. | L3. | May not have ceiling - then use strip fixture type |
| P4. | Plug strip at 44" above counters | L4. | May not have ceiling. If no ceiling, use industrial fixture type |
| P5. | Multiple receptacles above and below desk for device charging | L5. | Treat like a store. Adjustable lighting, General lighting. |
| P6. | Cord reel(s) for freestanding workbenches | L6. | No ceiling in these rooms. No prescription for lighting. |
| P7. | All outlets on dedicated circuits. | L7. | Provide task lighting at work counters if not already part of workstation furniture. |
| P8. | Cord reel(s) for freestanding workbenches | L8. | Connect lighting to corridor circuit. |
| P9. | Treadmill on dedicated circuit | L9. | Provide lighting suitable for damp environment. |
| P10. | Each hood on dedicated circuit | ||
| P11. | Provide receptacles per equipment plan | ||
| P12. | Electrical to review redundancy requirements with OIT guidelines. | ||
| P13. | Receptacle above ceiling for overhead lift | ||
| P14. | Recessed power quad floor box | ||
| P15. | L21-20R receptacle above each rack | ||
| P16. | Provide connections to cubicle furniture | ||
| P17. | Coordinate ESS power requirements for equipment and receptacles. | ||
| P18. | Provide quad at each haircutting station. |
Mechanical Notes
MECHANICAL HVAC NOTES
| M1. | Intentionally Left Blank |
| M2. | Per ASHRAE 62 for ventilation, and FGI Guidelines for NC |
| M3. | General Open Office area |
| M4. | General Open/Public area |
| M5. | Per ASHRAE 62 for ventilation if interior enclosed space. |
| M6. | Comply with ASHRAE 15 if Special Refrigeration Systems are used |
| M7. | If chemicals are used, provide specialized exhaust |
| M8. | Data Center |
| M9. | Transfer air to Food Prep Kitchen |
| M10. | Intentionally Left Blank |
| M11. | MEP Room |
| M12. | See USP-797 and -800 |
| M13. | Counter-height specialized exhaust system required |
| M14. | Provide air conditioning and ventilation per imaging manufacturer recommendations |
| M15. | General Office Area |
| M16. | Verify specific vendor/manufacturer requirements. |
| M17. | Non-ferrous construction |
| M18. | Provide cooling only air terminal unit to serve the manual equipment wash room. |
| M19. | Provide a dedicated wet exhaust system |