2609 Drawings.pdf
PDF 9 MB Posted
- Attached to
- New Anderson County Animal Shelter
- Solicitation number
- 2609
- Issued by
- Anderson County, Tennessee
About this file
The provided document is a comprehensive set of architectural and engineering design drawings for the Anderson County Animal Shelter project, prepared by Blankenship & Partners, LLC, an architectural and engineering firm. The project involves designing a new animal shelter facility, with detailed plans spanning multiple disciplines including structural, mechanical, electrical, plumbing, and fire protection systems. The drawings provide extensive technical specifications, including structural notes, foundation plans, roof framing, truss designs, site electrical layouts, HVAC configurations, and fire protection strategies.
The design documents suggest a complex, modern animal shelter with multiple functional areas such as kennels, surgery rooms, intake areas, administrative spaces, and support facilities. The structural drawings indicate a building with concrete foundations, steel framing, and roof trusses, designed to meet the 2021 International Building Code. The mechanical and electrical plans show sophisticated systems for climate control, lighting, power distribution, and communications infrastructure. Notably, the fire protection plans include comprehensive sprinkler systems and fire alarm configurations. While no specific budget is directly stated, the level of detail and professional engineering suggests a significant municipal infrastructure investment aimed at providing a state-of-the-art animal care facility for Anderson County.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Checked By:
Drawn By:
Date:
SDL Project Number:
Drawing No.:
SealSeal
Revisions
Date:No.
Drawing Title:
D R
A W
IN
G
F
IL
E
P
LO
TT
E D
O N
ANDERSON
COUNTY
ANIMAL
SHELTER
Blankenship & Partners, LLC
1112 Weisgarber Rd, Knoxville, TN 37909
Structural
C
Mechanical/Plumbing/Fire Protection
COPYRIGHT Blankenship & Partners, LLC
This drawing is the property of Blankenship & Partners, LLC and shall not be reproduced in whole or in part. It shall not be used for any other project. This drawing is an instrument of service only and shall be returned to the
Architect upon request.
Contact Name:
Contact Name:
Architects and Planners
Office: 865.251.2585
Project Name:
Owner:
100 N Main Street, Suite 208
Contact Name: Mayor Terry Franks
Contact Name: William R. Blankenship
Consultants:
Electrical
Contact Name: Chris Lay, P.E.
T [865] 745-4401
Knoxville, TN 37939
P.O. Box 10645
Vreeland Engineers, Inc.
Contact Name:
Civil
Anderson County
Clinton, Tennessee 37716
T [865] 457-6200
Randy Corlew, P.E.
T (423) 312.8371
Morristown, Tennessee 37814
376 Lochmere Drive
Welroc Enterprises, LLC
T (615) 320-1735
Brentwood, Tennessee 37027
750 Old Hickeory Blvd Building 1 Suite 175
Stanley D. Lindsey & Associates
T (865) 522-0393
Knoxville, Tennessee 37915
900 E Hill Ave. #350
Engineering Services Group
Rusty Whillock, P.E.
Jason D. Perry, P.E.
C
S D
L\ R
E V
IT
LO
C A
L_
FI
LE
S
-A n d e rs o n C n ty
A n im a l_
S h e lt e r- S D
L2 ja so n p e rr y .r v t
/4
/2
:2 :4
A
M
S0.1
Structural AXON Views
05/30/25
DP
GR & JDP
25021.00
FRONT AXON VIEW
(FOR REFERENCE ONLY - N.T.S.)
REAR AXON VIEW
(FOR REFERENCE ONLY - N.T.S.)
C
OM MERC
E
R
EE
NI
GNE DERETSI
G
E R
AGRICULTURE
E
ESSENNET FO E
T A
T S
Y R
REP .D NO
S
A J
502111 .o N
05.30.25
STRUCTURAL NOTES
A. GENERAL
1. NO PROVISION OF ANY REFERENCED STANDARD SPECIFICATION, MANUAL OR CODE (WHETHER OR NOT SPECIFICALLY INCORPORATED BY REFERENCE IN THE CONTRACT DOCUMENTS) SHALL BE
EFFECTIVE TO CHANGE THE DUTIES AND RESPONSIBILITIES OF OWNER, CONTRACTOR,
ENGINEER, SUPPLIER, OR ANY OF THEIR CONSULTANTS, AGENTS, OR EMPLOYEES FROM THOSE
SET FORTH IN THE CONTRACT DOCUMENTS. NOR SHALL IT BE EFFECTIVE TO ASSIGN TO THE
STRUCTURAL ENGINEER OR ANY OF THE STRUCTURAL ENGINEER'S CONSULTANTS, AGENTS, OR
EMPLOYEES ANY DUTY OR AUTHORITY TO SUPERVISE OR DIRECT THE FURNISHING OR
PERFORMANCE OF THE WORK OR ANY DUTY OR AUTHORITY TO UNDERTAKE RESPONSIBILITIES
CONTRARY TO THE PROVISIONS OF THE CONTRACT DOCUMENTS.
2. CONTRACT DOCUMENTS INCLUDE, BUT ARE NOT LIMITED TO, THE STRUCTURAL DOCUMENTS
(DRAWINGS AND SPECIFICATIONS), BUT DO NOT INCLUDE SHOP DRAWINGS, VENDOR DRAWINGS, OR MATERIAL PREPARED AND SUBMITTED BY THE CONTRACTOR.
3. REFERENCE TO STANDARD SPECIFICATIONS OF ANY TECHNICAL SOCIETY, ORGANIZATION, OR
ASSOCIATION OR TO CODES OF LOCAL OR STATE AUTHORITIES, SHALL MEAN THE LATEST
STANDARD, CODE, SPECIFICATION OR TENTATIVE SPECIFICATION ADOPTED AT THE DATE OF
TAKING BIDS, UNLESS SPECIFICALLY STATED OTHERWISE.
4. CONTRACT DOCUMENTS SHALL GOVERN IN THE EVENT OF A CONFLICT WITH THE CODE OF
PRACTICE OR SPECIFICATIONS OF ACI, PCI, AISC, SJI OR OTHER STANDARDS. WHERE A CONFLICT
OCCURS WITHIN THE CONTRACT DOCUMENTS, THE STRICTEST REQUIREMENT SHALL GOVERN.
5. MATERIAL, WORKMANSHIP, AND DESIGN SHALL CONFORM TO THE REFERENCED BUILDING CODE.
6. CONTRACTOR SHALL COORDINATE THE STRUCTURAL DOCUMENTS WITH THE ARCHITECTURAL,
MECHANICAL, ELECTRICAL, PLUMBING AND CIVIL DOCUMENTS. ARCHITECT/STRUCTURAL
ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCY OR OMISSION. FOR DIMENSIONS NOT
SHOWN ON THE STRUCTURAL DRAWINGS SEE THE ARCHITECTURAL DRAWINGS.
7. CONTRACTOR SHALL OBTAIN AND COORDINATE EDGE OF SLAB DIMENSIONS, OPENING
LOCATIONS AND DIMENSIONS, DEPRESSED SLAB LOCATIONS AND EXTENTS, SLAB SLOPES, CURB LOCATIONS, AND CMU WALL LOCATIONS. ARCHITECT/STRUCTURAL ENGINEER SHALL BE NOTIFIED
OF ANY DISCREPANCY OR OMISSION.
8. CONTRACTOR SHALL VERIFY EXISTING DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE STARTING WORK. ARCHITECT/STRUCTURAL ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCY.
9. CONTRACTOR SHALL VERIFY THAT MISCELLANEOUS FRAMING SHOWN ON THE STRUCTURAL
DRAWINGS FOR MECHANICAL EQUIPMENT, OWNER-FURNISHED ITEMS, PARTITIONS, ETC. IS
CONSISTENT WITH THE REQUIREMENTS OF SUCH ITEMS. CONTRACTOR SHALL VERIFY
EQUIPMENT WEIGHTS, REQUIRED OPENING SIZES AND LOCATIONS IDENTIFIED ON THE
STRUCTURAL DRAWINGS ARE IN AGREEMENT WITH FINAL ARCHITECTURAL AND MECHANICAL
SHOP DRAWINGS AND SUBMITTALS.
10. CONTRACTOR HAS SOLE RESPONSIBILITY FOR MEANS, METHODS, SAFETY, TECHNIQUES,
SEQUENCES, AND PROCEDURES OF CONSTRUCTION. CONTRACTOR HAS SOLE RESPONSIBILITY
TO COMPLY WITH ALL OSHA REGULATIONS.
11. THE STRUCTURE IS STABLE ONLY IN ITS COMPLETED FORM. TEMPORARY SUPPORTS REQUIRED
FOR STABILITY DURING ALL INTERMEDIATE STAGES OF CONSTRUCTION SHALL BE DESIGNED,
FURNISHED, AND INSTALLED BY THE CONTRACTOR. CONTRACTOR IS RESPONSIBLE FOR
CONSTRUCTABILITY ANALYSIS, AND ERECTION PROCEDURES, INCLUDING DESIGN AND ERECTION
OF FALSEWORK, TEMPORARY BRACING, ETC.
12. REPRODUCTION OF STRUCTURAL DRAWINGS FOR SHOP DRAWINGS IS NOT PERMITTED.
13. SUBMIT SHOP DRAWINGS WHICH ADEQUATELY DEPICT THE STRUCTURAL ELEMENTS AND
CONNECTIONS SHOWN IN THE CONTRACT DOCUMENTS. REVIEW OF SHOP DRAWINGS SHALL BE
FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS REGARDING ARRANGEMENT AND SIZES
OF MEMBERS AND THE CONTRACTOR'S INTERPRETATION OF THE DESIGN LOADS AND CONTRACT
DOCUMENT DETAILS. REVIEW OF SUBMITTALS OR SHOP DRAWINGS BY THE ARCHITECT /
STRUCTURAL ENGINEER DOES NOT RELIEVE THE CONTRACTOR OF THE SOLE RESPONSIBILITY TO
REVIEW AND CHECK ALL SUBMITTALS AND SHOP DRAWINGS BEFORE SUBMITTING TO THE
STRUCTURAL ENGINEER. REVIEW OF SUBMITTALS OR SHOP DRAWINGS BY THE ARCHITECT /
STRUCTURAL ENGINEER DOES NOT RELIEVE THE CONTRACTOR OF FULL RESPONSIBILITY FOR
COMPLIANCE WITH THE CONTRACT DOCUMENTS. CONTRACTOR REMAINS SOLELY RESPONSIBLE
FOR ERRORS AND OMISSIONS ASSOCIATED WITH THE PREPARATION OF SHOP DRAWINGS AS
THEY PERTAIN TO MEMBER SIZES, DETAILS, AND DIMENSIONS SPECIFIED IN THE CONTRACT
DOCUMENTS.
14. WHERE A SECTION OR DETAIL IS SHOWN OR DETAILED FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE CONDITIONS. DETAILS LABELED "TYPICAL" OR "TYP." ON THE STRUCTURAL
DRAWINGS APPLY TO ALL SITUATIONS OCCURRING ON THE PROJECT THAT ARE THE SAME OR
SIMILAR. THE CONTRACTOR SHALL CONSIDER ALL OF THE CONTRACT DOCUMENTS IN
DETERMINING SIMILAR AND LIKE CONDITIONS.
15. USE ONLY DIMENSIONS INDICATED ON THE CONTRACT DOCUMENTS. DO NOT SCALE DRAWINGS
OR MEASURE OBJECTS IN ELECTRONIC FILES. NOTIFY STRUCTURAL ENGINEER AND ARCHITECT
OF ANY DISCREPANCIES.
16. THE OWNER SHALL ESTABLISH A PERIODIC MAINTENANCE PROGRAM TO PROTECT THE
STRUCTURE FROM DETERIORATION. THE MAINTENANCE PROGRAM IS THE RESPONSIBILITY OF
THE OWNER AND SHOULD INCLUDE, BUT IS NOT LIMITED TO, THE FOLLOWING:
PAINTING OF EXPOSED STEEL THAT IS NOT GALVANIZED.
INSPECTION AND MAINTENANCE OF PROTECTIVE COATINGS, SEALANTS, CAULKED JOINTS,
EXPANSION JOINTS, AND CONTROL JOINTS.
REPAIR OF SPALLS AND CRACKS IN CONCRETE ELEMENTS.
REPAIR AND RESTORATION OF CORRODED ELEMENTS.
CLEANOUT OF DRAINS INCLUDING ALL ROOF AND TRENCH DRAINS AND SCUPPERS.
CLEANING OF STRUCTURAL ELEMENTS EXPOSED TO HARSH CHEMICALS INCLUDING DE-ICING
CHEMICALS.
17. THE USE OF STRUCTURAL BIM OR CAD FILES IS PROHIBITED WITHOUT WRITTEN CONSENT FROM
THE STRUCTURAL ENGINEER.
B. CODE/DESIGN CRITERIA
1. STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE, 2021
EDITION.
2. GRAVITY LOADS
2.1. UNIFORM FLOOR LIVE LOADS (REDUCED AS ALLOWED BY THE BUILDING CODE):
GENERAL AREAS 100 PSF (INCLUDES PARTITIONS)
MECHANICAL ROOMS 150 PSF (NON-REDUCIBLE)
STAIRS 100 PSF
STORAGE — LIGHT 125 PSF (NON-REDUCIBLE)
2.2. UNIFORM ROOF LIVE LOADS (REDUCED AS ALLOWED BY THE BUILDING CODE):
ROOF 20 PSF
GROUND SNOW LOAD, pg 10 PSF RAIN INTENSITY (15-MIN. STORM DURATION), i 6.0 IN/HR
PONDING AND DRIFT EFFECTS HAVE BEEN INCLUDED IN THE DESIGN.
2.3. CONCENTRATED FLOOR LOADS - DISTRIBUTED OVER AN AREA OF 2.5 FT2, UNLESS NOTED
OTHERWISE:
OFFICE 2,000 LB
3. WIND LOADS:
BASIC DESIGN WIND SPEED, V 105 MPH
ALLOWABLE STRESS DESIGN WIND SPEED, Vasd 81 MPH
EXPOSURE B
RISK CATEGORY II
INTERNAL PRESSURE COEFFICIENT, GCpi ± 0.18
4. EARTHQUAKE LOADS:
RISK CATEGORY II
SEISMIC IMPORTANCE FACTOR, Ie 1.0
MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SS 0.510 g S1 0.121 g
SITE CLASS C
DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SDS 0.441 g SD1 0.121 g
SEISMIC DESIGN CATEGORY C
BASIC SEISMIC-FORCE-RESISTING SYSTEM:
ORDINARY REINFORCED MASONRY SHEAR WALLS AND STRUCTURAL STEEL
SYSTEM NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE
RESPONSE MODIFICATION FACTOR, R 2
SEISMIC RESPONSE COEFFICIENT, Cs 24 %
DESIGN BASE SHEAR 900 KIPS
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE
5. MAXIMUM ESTIMATED DEFLECTIONS LISTED BELOW ARE EXPECTED TO OCCUR AND SHALL BE
CONSIDERED BY THE CONTRACTOR AND CLADDING DESIGNERS IN THE PERFORMANCE OF THE
WORK:
5.1. MAXIMUM ESTIMATED DEFLECTIONS (IN INCHES) ARE AS FOLLOWS:
LIVE LOAD DEAD + LIVE LOAD
FLOOR MEMBERS: L/360 L/240
WHERE, L = SPAN LENGTH (IN INCHES) BETWEEN CENTERLINES OF SUPPORTS. (FOR
CANTILEVERS, L IS TWICE THE LENGTH OF THE CANTILEVER.)
5.2. MAXIMUM LATERAL INTER-STORY DRIFT DUE TO WIND LOADING (10-YEAR MEAN
RECURRENCE INTERVAL) ARE AS FOLLOWS:
H/400 AT THE CENTER OF MASS
MAXIMUM OF 0.6" AT THE EDGE OF THE BUILDING
6. SPECIAL INSPECTIONS ARE REQUIRED PER IBC CHAPTER 17 AND AS SPECIFIED IN THE
STRUCTURAL SPECIAL INSPECTION STATEMENT PROVIDED BY THE STRUCTURAL ENGINEER.
7. NO PROVISIONS HAVE BEEN MADE FOR FUTURE HORIZONTAL OR VERTICAL EXPANSION.
C. DEFERRED STRUCTURAL SUBMITTALS
1. DEFERRED SUBMITTALS, AS DEFINED BY THE BUILDING CODE, SHALL BE SUBMITTED TO THE
BUILDING OFFICIAL BY THE CONTRACTOR. THE DEFERRED SUBMITTALS SHALL BE SIGNED AND
SEALED BY A LICENSED ENGINEER IN THE PROJECT STATE.
2. THE STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR THE DESIGN OF THE DEFERRED
SUBMITTAL COMPONENTS OR THE CONNECTION TO THE STRUCTURE. THE STRUCTURAL DESIGN
OF THE COMPONENTS AND THE CONNECTION TO THE STRUCTURE IS DELEGATED TO A
SPECIALTY ENGINEER WHO SHALL BE ENGAGED BY THE CONTRACTOR, VENDOR, AND / OR
SUPPLIER OF THE COMPONENTS AS PART OF THE DEFERRED SUBMITTAL PROCESS.
3. THE CONTRACTOR SHALL SUBMIT THE DEFERRED SUBMITTAL TO THE ARCHITECT / STRUCTURAL
ENGINEER FOR REVIEW. AFTER REVIEW BY THE ARCHITECT / STRUCTURAL ENGINEER THE
CONTRACTOR SHALL SUBMIT THE REVIEWED SUBMITTAL TO THE BUILDING OFFICIAL PER SECTION
107.3 OF THE BUILDING CODE.
4. THE ITEMS LISTED BELOW ARE IDENTIFIED AS DEFERRED SUBMITTALS. REFER TO THE
ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND CIVIL DRAWINGS AND
SPECIFICATIONS FOR ADDITIONAL DEFERRED SUBMITTAL COMPONENTS. ALL COSTS ASSOCIATED WITH THE PREPARATION OF THE DEFERRED SUBMITTAL, INCLUDING THE SPECIALTY ENGINEER’S
DESIGN FEES, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
SPECIALTY FOUNDATION ELEMENTS
STRUCTURAL STEEL CONNECTIONS
HANDRAILS AND GUARDRAILS
COLD-FORMED METAL FRAMING
COLD-FORMED METAL TRUSSES
EXTERIOR BUILDING SIGNAGE
SEISMIC ANCHORAGE OF ARCHITECTURAL COMPONENTS
SEISMIC ANCHORAGE OF MECHANICAL, ELECTRICAL, AND PLUMBING COMPONENTS
ANCHORAGE OF EXTERIOR ARCHITECTURAL, MECH., ELEC., AND PLUMBING EQUIPMENT
ATTACHMENT OF ROOFTOP EQUIPMENT, PIPING, & DUCTWORK TO THE UNDERLYING STRUCTURE
GLAZING SYSTEMS (e.g., CURTAIN WALL, WINDOW WALL, AND STOREFRONT SYSTEMS)
PREFABRICATED / PRE-ENGINEERED ARCHITECTURAL ELEMENTS AND STRUCTURES
OTHER ELEMENTS SPECIFICALLY IDENTIFIED IN THE CONTRACT DOCUMENTS
WINDOW WASHING SYSTEMS
FALL PROTECTION SYSTEMS
BUILDING MAINTENANCE SYSTEMS
5. DEFERRED SUBMITTAL COMPONENTS SHALL BE DESIGNED FOR THE LOADS AS DEFINED BY THE APPLICABLE BUILDING CODE WITH DESIGN DATA DEFINED IN THE SECTION B OF THE STRUCTURAL
NOTES.
6. THE DESIGN OF ITEMS LISTED BELOW ARE THE RESPONSIBILITY OF THE CONTRACTOR BUT ARE
NOT CONSIDERED A DEFERRED SUBMITTAL AND ARE NOT TO BE SUBMITTED TO THE DESIGN
TEAM. ALL COSTS ASSOCIATED WITH THE DESIGN OF THESE ELEMENTS, INCLUDING THE
SPECIALTY ENGINEER’S DESIGN FEES, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
TEMPORARY SUPPORT OF EXCAVATION SYSTEMS
TEMPORARY BRACING / SHORING FOR STABILITY OF STRUCTURE DURING CONSTRUCTION
ALL OTHER ELEMENTS IDENTIFIED IN THE CONTRACT DOCUMENTS
D. FOUNDATION
1. FOUNDATION DESIGN IS BASED ON THE RECOMMENDATIONS IN THE GEOTECHNICAL REPORT
PREPARED BY _____________________________________, REPORT NUMBER ___________ DATED _______________. STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR SUBSURFACE CONDITIONS
ENCOUNTERED IN THE FIELD DIFFERENT FROM THOSE ASSUMED FOR DESIGN.
2. STRUCTURAL TESTING/INSPECTION AGENCY SHALL CERTIFY THE BEARING MEDIUM.
3. INDIVIDUAL SPREAD FOOTINGS AND CONTINUOUS FOOTINGS SHALL BEAR ON SOIL CAPABLE OF
SUPPORTING 2,000 PSF.
4. FOUNDATION WALLS ARE DESIGNED FOR LATERAL PRESSURES DUE TO THE FOLLOWING
EQUIVALENT FLUID DENSITIES:
WALLS SUPPORTED AT TOP (AT-REST CONDITION): PCF
WALLS FREE TO DISPLACE AT TOP (ACTIVE CONDITION): PCF
5. PROOFROLL BUILDING AREAS WITH TWO COMPLETE COVERAGES OF A LOADED DUMP-TRUCK OR
SCRAPER. REPLACE SOFT AREAS WITH COMPACTED STRUCTURAL FILL AS REQUIRED BY THE
SPECIFICATIONS.
6. UNDERCUT THE ENTIRE BUILDING AREA TO THE EXTENT SHOWN ON THE STRUCTURAL
DOCUMENTS AND REPLACE WITH COMPACTED STRUCTURAL FILL AS REQUIRED BY THE
SPECIFICATIONS.
E. REINFORCEMENT
1. REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, UNLESS NOTED OTHERWISE.
2. WELDED WIRE REINFORCING SHALL CONFORM TO ASTM A1064 AND HAVE MINIMUM SIDE AND END
LAPS OF ONE CROSS WIRE SPACING PLUS 2", BUT NOT LESS THAN 6”.
3. SUBMIT SHOP DRAWINGS WHICH ADEQUATELY DEPICT THE REINFORCING BAR SIZES AND
PLACEMENT. WRITTEN DESCRIPTION OF REINFORCEMENT WITHOUT ADEQUATE SECTIONS,
ELEVATIONS, AND DETAILS IS NOT ACCEPTABLE.
4. PROVIDE DOWELS FROM FOUNDATIONS THE SAME SIZE AND NUMBER AS THE VERTICAL WALL OR
COLUMN REINFORCING, UNLESS NOTED OTHERWISE.
5. PLACE REINFORCEMENT AS FOLLOWS, UNLESS NOTED OTHERWISE:
5.1. CAST-IN-PLACE CONCRETE REINFORCEMENT COVER
PERMANENTLY EXPOSED TO EARTH:
CAST AGAINST THE EARTH 3” CLEAR
EXPOSED TO EARTH OR WEATHER:
FOR BARS LARGER THAN A NO. 5 BAR 2” CLEAR
NO. 5 BARS OR SMALLER 1-1/2" CLEAR
NOT EXPOSED TO WEATHER OR IN CONTACT WITH EARTH:
WALLS (EXCEPT SHEAR WALLS) 3/4" CLEAR
SLABS 3/4” CLEAR
5.2. MASONRY CONCRETE REINFORCEMENT COVER
MASONRY REINFORCING STEEL SHALL BE PLACED IN THE CENTER OF CMU CELLS, UNLESS
NOTED OTHERWISE. IF REINFORCING STEEL IS NOTED TO BE PLACED OTHER THAN THE
CENTER OF THE CELL, PLACE BAR TO ACHIEVE 2" CLEAR COVER BETWEEN REINFORCING
AND OUTSIDE FACE OF CMU BLOCK.
6. REINFORCEMENT SHALL BE SPLICED ONLY AT LOCATIONS SHOWN OR NOTED IN THE
STRUCTURAL DOCUMENTS, EXCEPT REINFORCEMENT MARKED "CONTINUOUS" CAN BE SPLICED
AT LOCATIONS DETERMINED BY CONTRACTOR. SPLICES AT OTHER LOCATIONS SHALL BE
APPROVED IN WRITING BY THE STRUCTURAL ENGINEER. REINFORCING STEEL SPLICES SHALL BE
AS FOLLOWS, UNLESS NOTED OTHERWISE:
CONCRETE: CLASS B TENSION LAP - SEE REINFORCING LAP LENGTH SCHEDULE
MASONRY: SEE REINFORCING LAP LENGTH SCHEDULE
F. CAST-IN-PLACE CONCRETE
1. CONCRETE WORK SHALL CONFORM TO ACI 318 AND CRSI STANDARDS.
2. NORMAL WEIGHT STRUCTURAL CONCRETE SHALL HAVE THE FOLLOWING PROPERTIES:
EXPOSURE
CLASS
28-DAY MIN.
COMPRESSIVE
STRENGTH, ƒ’c
MAX.
w/cm
RATIO
MAX. NOM.
AGGREGATE
SIZE
FOOTINGS C1, W1 4,000 PSI 0.50 1-1/2”
INTERIOR FOUNDATION WALLS C1 4,500 PSI 0.45 1”
EXTERIOR FOUNDATION WALLS F2, C1 4,500 PSI 0.45 1”
INTERIOR SLABS-ON-GROUND C1 4,000 PSI 0.48 1”
EXTERIOR SLABS-ON-GROUND F2, C1 4,500 PSI 0.45 1”
ALL NORMAL WEIGHT CONCRETE SHALL BE CONSIDERED TO BE IN EXPOSURE CLASS F0, S0, W0, AND C0 ACCORDING TO ACI 318 UNLESS NOTED OTHERWISE ABOVE OR ELSEWHERE ON THE
STRUCTURAL DRAWINGS
3. CONCRETE MIX REQUIREMENTS
3.1. ALL CONCRETE SHALL BE PROPORTIONED TO COMPLY WITH ACI 318 CHAPTER 19 IN
ACCORDANCE WITH THE EXPOSURE CLASS INDICATED. WHERE REQUIREMENTS
INDICATED DIFFER FROM REQUIREMENTS OF CHAPTER 19, THE STRICTER REQUIREMENT
SHALL APPLY. REFER TO THE SPECIFICATIONS FOR OTHER REQUIREMENTS FOR VARIOUS
EXPOSURE CLASSES RELATIVE TO THE CEMENT TYPE, AIR ENTRAINMENT REQUIREMENTS,
CHLORIDE ION LIMITS, POZZOLAN LIMITS, AND SHRINKAGE LIMITS.
3.2. CONCRETE SHALL BE CONSIDERED EXTERIOR CONCRETE IF THE CONCRETE IS
PERMANENTLY EXPOSED TO THE WEATHER OR MOISTURE OR IF IT IS IN AN
UNCONDITIONED SPACE IN ITS COMPLETED CONFIGURATION.
3.3. ALL CONCRETE SHALL SATISFY BOTH THE SPECIFIED MAXIMUM WATER TO CEMENT RATIO
AND THE MINIMUM COMPRESSIVE STRENGTH, ƒ'c, REQUIREMENTS.
4. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATION OF SLEEVES, ACCESSORIES, ETC.
5. REFER TO ARCHITECTURAL DRAWINGS FOR MOLDS, GROOVES, ORNAMENTS, CLIPS OR GROUNDS
REQUIRED TO BE ENCASED IN CONCRETE AND FOR LOCATION OF ALL CONCRETE FINISHES AND
SLAB DEPRESSIONS.
6. CONSTRUCTION JOINT LOCATIONS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER. NO
HORIZONTAL JOINTS ARE PERMITTED EXCEPT THOSE SHOWN ON THE STRUCTURAL DRAWINGS.
7. DEFECTIVE AREAS IN CONCRETE INCLUDING BUT NOT LIMITED TO, HONEY-COMBING, SPALLS, AND
CRACKS WITH WIDTHS EXCEEDING 0.012" SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT / STRUCTURAL ENGINEER. REPAIR DEFECTIVE AREAS AS DIRECTED BY THE
STRUCTURAL ENGINEER.
G. CONCRETE MASONRY
1. CONCRETE MASONRY WORK SHALL CONFORM TO TMS 402/602, BUILDING CODE REQUIREMENTS
AND SPECIFICATIONS FOR MASONRY STRUCTURES.
2. MINIMUM COMPRESSIVE STRENGTH OF CONCRETE MASONRY SHALL BE ƒ’m = 2,000 PSI.
3. MORTAR SHALL BE TYPE S AND SHALL COMPLY WITH THE BUILDING CODE REQUIREMENTS FOR
CONCRETE MASONRY.
4. CONCRETE MASONRY UNITS SHALL BE GROUTED WITH 2,500 PSI COARSE GROUT AS SHOWN IN
THE STRUCTURAL DOCUMENTS. GROUT SHALL CONFORM TO ASTM C476.
5. PROVIDE HORIZONTAL JOINT REINFORCEMENT WITH NO. 9 GAGE LONGITUDINAL WIRES AT 16"
VERTICALLY, UNLESS NOTED OTHERWISE. PROVIDE SPECIAL ACCESSORIES FOR CORNERS,
INTERSECTIONS, ETC.
6. PROVIDE OPEN BOTTOM BEAM BLOCK UNITS WITH 3" DEEP MINIMUM WEB OPENINGS AT
HORIZONTAL REINFORCEMENT LOCATIONS. A MINIMUM CLEAR SPACE OF ONE BAR DIAMETER
SHALL BE PROVIDED BETWEEN THE REINFORCING BARS AND THE FACE OF MASONRY UNITS.
7. PROVIDE CONTRACTION (CONTROL) JOINTS IN ALL CONCRETE MASONRY WALLS AT LOCATIONS APPROVED BY THE ARCHITECT AT A MAXIMUM SPACING OF 1.5 TIMES THE WALL HEIGHT OR 25'-0", WHICHEVER IS LESS. THE DISTANCE TO THE FIRST CONTRACTION JOINT FROM CORNERS OR
INTERSECTING WALLS IS LIMITED TO HALF OF THE ABOVE VALUE.
8. PROVIDE DOVETAIL ANCHORS AT 16" C/C, UNLESS NOTED OTHERWISE, WHERE MASONRY WALLS
ABUT CONCRETE SURFACES OR STRUCTURAL STEEL MEMBERS.
9. SUBMIT WRITTEN CONSTRUCTION PROCEDURES PRIOR TO THE START OF MASONRY
CONSTRUCTION.
10. MINIMUM VERTICAL WALL REINFORCEMENT SHALL BE #4@48", FOR INTERIOR WALLS AND #5@32", FOR EXTERIOR WALLS, UNLESS NOTED OTHERWISE.
H. POST-INSTALLED ANCHORS AND REINFORCING STEEL
1. POST-INSTALLED ANCHORS AND REINFORCING STEEL SHALL ONLY BE USED WHERE SPECIFIED
ON THE CONSTRUCTION DOCUMENTS. CONTRACTOR SHALL OBTAIN APPROVAL FROM THE
STRUCTURAL ENGINEER PRIOR TO INSTALLING POST-INSTALLED ANCHORS OR REINFORCING
STEEL IN PLACE OF MISSING OR MISPLACED CAST-IN-PLACE ANCHORS OR REINFORCING STEEL.
2. CONTRACTOR SHALL ARRANGE ONSITE INSTALLATION TRAINING BY THE MANUFACTURER FOR
EACH PRODUCT TO BE INSTALLED. SUBMIT TO THE STRUCTURAL ENGINEER DOCUMENTATION
CONFIRMING TRAINING OF ALL PERSONNEL WHO WILL BE INSTALLING PRODUCTS. TRAINING AND
DOCUMENTATION SHALL OCCUR PRIOR TO THE COMMENCEMENT OF PRODUCT INSTALLATION.
INSTALLATION OF ADHESIVE ANCHOR PRODUCTS IN HORIZONTAL OR UPWARDLY INCLINED
ORIENTATION RESISTING SUSTAINED TENSION LOADS SHALL BE CONDUCTED BY AN INSTALLER
CERTIFIED IN ACCORDANCE WITH THE ACI/CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION
PROGRAM. PROOF OF CERTIFICATION SHALL BE MAINTAINED AT THE JOB SITE.
3. EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC
ANCHOR OR REINFORCING LOCATIONS. CONTRACTOR SHALL LOCATE THE POSITION OF
REINFORCING BARS AND P.T. TENDONS BY FERROSCAN, GPR, X-RAY, CHIPPING, OR OTHER
MEANS PRIOR TO ANCHOR INSTALLATION. THE CONTRACTOR SHALL NOT DAMAGE ANY
REINFORCING.
4. ADHESIVE ANCHOR INSERT SHALL BE ALL THREAD ROD OF THE FOLLOWING MATERIAL U.N.O.:
INTERIOR ENVIRONMENTS: ASTM F1554 Gr. 36 EXTERIOR ENVIRONMENTS: ASTM F1554 Gr. 36 GALV. PER ASTM B695, CLASS 65 TYPE I
CORROSIVE ENVIRONMENTS: ASTM A193 GR. B8M TYPE 316
5. MECHANICAL AND SCREW ANCHORS IN EXTERIOR AND CORROSIVE ENVIRONMENTS SHALL BE
GALVANIZED OR STAINLESS STEEL AND SHALL APPROVED BY THE MANUFACTURER FOR THE
EXPOSURE.
6. PROVIDE THE FOLLOWING INSTALLATION CONDITIONS FOR ADHESIVE ANCHORS; NOTIFY THE
STRUCTURAL ENGINEER IF THESE CONDITIONS DO NOT EXIST:
HOLES DRILLED WITH HAMMER DRILL WITH CARBIDE TIPPED DRILL BIT
DRY HOLE
CONCRETE CURED FOR A MINIMUM OF 21 DAYS
TEMPERATURE CATEGORY B (110° F LONG TERM AND 130° F SHORT TERM)
I. STRUCTURAL STEEL
1. STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED ACCORDING TO THE ANSI/AISC 360 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS" AND THE AISC 303 "CODE OF STANDARD
PRACTICE FOR STEEL BUILDINGS AND BRIDGES".
2. STRUCTURAL STEEL SHALL BE OF THE FOLLOWING GRADE UNLESS NOTED OTHERWISE ON
DRAWINGS:
W, WT, C, AND MC SHAPES ASTM A992
L, M, S, MT, AND ST SHAPES ASTM A572, GRADE 50
HSS SHAPES ASTM A500, GRADE C
STEEL PIPE SHAPES ASTM A53, GRADE B
PLATES AND BARS ASTM A572, GRADE 50
ROUND ROD ASTM A36
3. BOLTS, ANCHOR RODS, AND HEADED STUDS:
3.1. ALL BOLTS SHALL BE GROUP 120 OR GROUP 150 HIGH STRENGTH BOLTS WITH A 3/4"
MINIMUM DIAMETER UNLESS NOTED OTHERWISE. BOLT SHEAR STRENGTH SHALL BE
DETERMINED IN ACCORDANCE WITH TABLE 7-1 IN THE AISC "STEEL CONSTRUCTION
MANUAL".
3.2. ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 55, UNLESS NOTED OTHERWISE.
4. CONNECTIONS:
4.1. STEEL CONNECTIONS SHALL BE DETAILED BASED ON THE DESIGN INFORMATION
PROVIDED IN THE CONTRACT DOCUMENTS. DEVIATION FROM THE CONNECTION DETAILS
DEPICTED IN THE CONTRACT DOCUMENTS SHALL NOT BE PERMITTED WITHOUT ADVANCE
WRITTEN PERMISSION FROM THE STRUCTURAL ENGINEER.
4.2. THE SERVICES OF A CONNECTION DESIGN SPECIALTY ENGINEER (CDSE) SHALL BE
INCLUDED IN THE CONTRACTOR'S SCOPE OF SERVICES. THE CDSE SHALL BE LICENSED IN
THE PROJECT STATE. THE CDSE IS RESPONSIBLE FOR REVIEWING THE STEEL SHOP
DRAWINGS TO ENSURE THAT ALL CONNECTION DESIGN DETAILS HAVE BEEN CORRECTLY
SHOWN ON THE SHOP DRAWINGS; AND, THE CDSE SHALL SUBMIT A SIGNED AND SEALED
LETTER, WITH EACH SHOP DRAWING SUBMITTAL, CONFIRMING THE ABOVE REVIEW.
4.3. STANDARD SHEAR CONNECTIONS SHALL BE DETAILED AS DOUBLE-ANGLE, SINGLE-PLATE,
SINGLE-ANGLE, OR TEE CONNECTIONS IN ACCORDANCE WITH CONNECTION TABLES IN
PART 10 OF THE "STEEL CONSTRUCTION MANUAL". THE CDSE SHALL SUBMIT SIGNED AND
SEALED CALCULATIONS FOR ALL SHEAR CONNECTIONS THAT CANNOT BE DETAILED
COMPLETELY FROM THE ABOVE MANUAL FOR REVIEW BY THE STRUCTURAL ENGINEER.
4.4. FOR WELDED CONNECTIONS, USE PREQUALIFIED WELDED JOINTS IN ACCORDANCE WITH
AISC AND THE STRUCTURAL WELDING CODE OF THE AMERICAN WELDING SOCIETY. "NON-
PREQUALIFIED JOINTS" SHALL BE QUALIFIED PRIOR TO FABRICATION.
4.5. THE REQUIRED REACTION USING LRFD LOAD COMBINATIONS SHALL BE AS SHOWN ON THE
STRUCTURAL DRAWINGS.
4.6. STEEL CONNECTIONS NOT SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS
SHALL BE DESIGNED BY THE CDSE WITH THE EXCEPTION OF SIMPLE SHEAR CONNECTIONS
AS DESCRIBED IN SECTION 4.3. THE CDSE SHALL SUBMIT SIGNED AND SEALED
CALCULATIONS FOR ALL SUCH CONNECTIONS.
4.7. REVIEW OF THE SHOP DRAWINGS AND/OR CONNECTION CALCULATIONS BY THE
STRUCTURAL ENGINEER DOES NOT RELIEVE THE CONTRACTOR AND CDSE OF THE FULL
RESPONSIBILITY FOR THE DESIGN AND ADEQUACY OF SUCH CONNECTIONS.
5. THE STRUCTURAL STEEL MEMBERS HAVE NOT BEEN DESIGNED TO ACCOMMODATE THE TORSION
RESULTING FROM THE ECCENTRIC LOADING OF THE PRECAST PANELS, CURTAINWALL SYSTEMS,
LIGHT GAUGE METAL FRAMING, ETC. SUPPLEMENTAL SECONDARY BRACING SHALL BE DESIGNED
AND PROVIDED BY THE SUPPLIER TO ELIMINATE TORSION.
6. ALL STEEL EXPOSED TO WEATHER OR MOISTURE SHALL BE GALVANIZED, UNLESS OTHERWISE
DIRECTED BY THE ARCHITECT.
7. THE LATERAL LOAD RESISTING SYSTEM INCLUDES STRUCTURAL STEEL, NON-STRUCTURAL STEEL
ELEMENTS, AND THE DIAPHRAGM AS INDICATED BELOW. ALL ELEMENTS OF THE LATERAL LOAD
RESISTING SYSTEM AND DIAPHRAGM ARE REQUIRED TO BE COMPLETE AS INDICATED AND
DETAILED IN THE STRUCTURAL CONTRACT DOCUMENTS TO PROVIDE THE LATERAL STRENGTH
AND STABILITY OF THE STEEL STRUCTURE. THE STRUCTURE SHALL BE CONSIDERED UNSTABLE
UNTIL THESE SYSTEMS AND ELEMENTS ARE COMPLETE.
7.1. THE LATERAL LOAD RESISTING SYSTEM FOR THE STEEL STRUCTURE INCLUDES THE
FOLLOWING ELEMENTS AS INDICATED AND DETAILED IN THE STRUCTURAL CONTRACT
DOCUMENTS:
MOMENT FRAMES
CONNECTIONS, BASEPLATES, ANCHOR RODS, AND GROUT
MASONRY SHEAR WALLS
7.2. THE LATERAL LOAD RESISTING DIAPHRAGM FOR THE STEEL STRUCTURE INCLUDES THE
FOLLOWING ELEMENTS AS INDICATED AND DETAILED IN THE STRUCTURAL CONTRACT
DOCUMENTS:
STEEL ROOF DECK
COLD-FORMED STEEL TRUSSES WITH PLYWOOD SHEATHING
8. STABILITY BRACING: THE STABILITY OF STRUCTURAL STEEL ELEMENTS, INCLUDING INDIVIDUAL
HOT-ROLLED STEEL SHAPES, IS PROVIDED BY THE FOLLOWING ELEMENTS AS INDICATED AND
DETAILED IN THE STRUCTURAL CONTRACT DOCUMENTS. THESE ELEMENTS SHALL BE COMPLETE
AS SHOWN IN THE STRUCTURAL CONTRACT DOCUMENTS BEFORE ANY TEMPORARY MEANS AND
METHODS REQUIRED FOR ERECTION ARE REMOVED.
STEEL ROOF DECK
COLD-FORMED METAL TRUSSES WITH PLYWOOD SHEETING
J. STEEL DECK
1. STEEL DECK SHALL BE PLACED OVER MULTIPLE SPANS WHEREVER POSSIBLE. WHERE SINGLE
SPAN DECK IS REQUIRED, THE CONTRACTOR SHALL DRAW SPECIFIC ATTENTION TO THOSE
LOCATIONS ON THE SHOP DRAWINGS.
2. SUBMIT SHOP DRAWINGS SHOWING THE STEEL DECK PROFILE, GAGE, PHYSICAL PROPERTIES, AND LAYOUT. THE SUBMITTAL SHALL INCLUDE ALL ACCESSORIES AND INSTALLATION DETAILS. IF DECK OTHER THAN THE BASIS OF DESIGN IS PROVIDED, THE SUBMITTAL SHALL INCLUDE LOAD
TABLES DEMONSTRATING THE DECK MEETS OR EXCEEDS THE BASIS OF DESIGN. THE LOAD
TABLES SHALL BE IN ACCORDANCE WITH THE STEEL DECK INSTITUTE (SDI) REQUIREMENTS
3. ROOF DECK:
3.1. THE 1 1/2" TYPE B ROOF DECK BASIS OF DESIGN IS 1.5B ROOF DECK PRODUCED BY
VULCRAFT (IAPMO UES ER-0652). OTHER DECK MANUFACTURERS ARE PERMITTED
PROVIDED THE FOLLOWING MINIMUM DECK PROPERTIES ARE MET OR EXCEEDED:
GAGE 22
YIELD STRESS 50 KSI
MOMENT OF INERTIA (POSITIVE BENDING), I(+) 0.155 IN4/FT
MOMENT OF INERTIA (NEGATIVE BENDING), I(-) 0.178 IN4/FT
SECTION MODULUS (POSITIVE MOMENT), S(+) 0.169 IN3/FT
SECTION MODULUS (NEGATIVE MOMENT), S(-) 0.179 IN3/FT
3.2. DECK FINISH SHALL BE GALVANIZED G60.
K. COLD-FORMED METAL FRAMING
1. COLD-FORMED METAL FRAMING DESIGN, FABRICATION, AND ERECTION SHALL BE IN
ACCORDANCE WITH AISI S100 AND AISI S202.
2. DESIGN OF COLD-FORMED METAL FRAMING MEMBERS AND THEIR CONNECTIONS IS A DEFERRED
SUBMITTAL AND SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. SUBMIT SHOP
DRAWINGS SEALED BY AN ENGINEER LICENSED IN THE PROJECT STATE. SHOP DRAWINGS SHALL
INCLUDE PLACING DRAWINGS FOR FRAMING MEMBERS SHOWING SIZE AND GAGE DESIGNATIONS,
NUMBER, TYPE, LOCATION, AND SPACING. INDICATE SUPPLEMENTAL STRAPPING, BRACING,
SPLICES, BRIDGING, ACCESSORIES, AND DETAILS REQUIRED FOR PROPER INSTALLATION. REVIEW
OF SHOP DRAWINGS SHALL BE FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS
REGARDING ARRANGEMENT AND SIZES OF MEMBERS AND THE CONTRACTOR'S INTERPRETATION
OF THE DESIGN LOADS AND CONTRACT DOCUMENT DETAILS. SUCH REVIEW SHALL NOT RELIEVE
THE CONTRACTOR OF FULL RESPONSIBILITY FOR THE DESIGN OF THE COLD-FORMED STEEL
STRUCTURAL MEMBERS AND THEIR CONNECTIONS.
L. COLD-FORMED METAL TRUSSES
1. COLD-FORMED METAL TRUSS DESIGN, FABRICATION AND ERECTION SHALL BE IN ACCORDANCE
WITH AISI S100, AISI 202, AND AISI 240.
2. DESIGN OF COLD-FORMED METAL TRUSSES AND BRACING IS A DEFERRED SUBMITTAL AND SHALL
BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. SUBMIT SHOP DRAWINGS TO THE
ARCHITECT/STRUCTURAL ENGINEER AND THE BUILDING OFFICIAL PRIOR TO TRUSS INSTALLATION.
3. COLD-FORMED METAL TRUSS PROFILES SHALL BE AS SHOWN IN THE STRUCTURAL DOCUMENTS.
4. COLD-FORMED METAL TRUSSES SHALL BE DESIGNED TO SUPPORT A TOTAL SUPERIMPOSED
LOAD OF 40 PSF, CONSISTING OF 20 PSF DEAD LOAD (10 PSF TOP CHORD AND 10 PSF BOTTOM
CHORD) AND 20 PSF ROOF LIVE LOAD, UNLESS NOTED OTHERWISE.
5. COLD-FORMED METAL TRUSSES SHALL BE DESIGNED TO SUPPORT SNOW AND DRIFT LOADS AS
REQUIRED BY THE BUILDING CODE.
6. COLD-FORMED METAL TRUSSES AND THEIR ANCHORAGE SHALL BE DESIGNED TO RESIST WIND
UPLIFT.
7. DEFLECTIONS SHALL BE LIMITED TO A MAXIMUM OF L/240 FOR TOTAL LOAD AND L/360 FOR LIVE
LOAD.
8. COLD-FORMED METAL TRUSSES SHALL BE DESIGNED TO BEAR ONLY ON BEAMS AND WALLS
SPECIFICALLY NOTED AS LOAD BEARING IN THE CONTRACT DOCUMENTS.
9. ANY ALTERATION OF TRUSS MEMBERS AND COMPONENTS (CUTTING, NOTCHING, DRILLING,
SPLICING, ETC.) REQUIRES APPROVAL OF THE COLD-FORMED METAL TRUSS SPECIALTY
ENGINEER.
M. WOOD
1. THE REQUIREMENTS OUTLINED IN THIS SECTION ARE THE MINIMUM MATERIAL REQUIREMENTS AND THEIR APPLICATION. CODE REQUIREMENTS, WHEN IN EXCESS OF MINIMUM REQUIREMENTS, SHALL CONTROL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REVIEW AND SUBMIT ALL SHOP
DRAWINGS AND REPORT ALL DOCUMENT DISCREPANCIES TO THE STRUCTURAL ENGINEER PRIOR
TO FABRICATION OR ERECTION.
2. STRUCTURAL GLUE-LAMINATED TIMBER
2.1. STRUCTURAL GLUE-LAMINATED TIMBER SHALL BE PRODUCED IN ACCORDANCE WITH THE
AMERICAN NATIONAL STANDARD ANSI/AITC A190.1.
2.2. STRUCTURAL GLUE-LAMINATED TIMBER SHALL MEET STRESS CLASS 16F-V2
REQUIREMENTS FROM THE AF&PA NATIONAL DESIGN SPECIFICATION (NDS) FOR WOOD
CONSTRUCTION.
2.3. REFER TO ARCHITECTURAL DRAWINGS FOR APPEARANCE GRADE AND FINISH
REQUIREMENTS.
3. WOOD SHEATHING
3.1. ROOF SHEATHING SHALL BE 23/32" THICK STRUCTURAL PANELS, T&G EDGE TREATMENT,
EXPOSURE 1, PANEL INDEX 48/24, CONFORMING TO DOC PS-1 FOR PLYWOOD PANELS OR
TO DOC PS-2 FOR OSB PANELS AND STAMPED WITH APA GRADEMARK. LONG DIMENSION
SHALL BE PERPENDICULAR TO FRAMING, AND END JOINTS SHALL BE STAGGERED. PANELS
SHALL BE SCREWED TO SUPPORTS WITH SELF-TAPPING SCREWS. FASTENER SPACING
SHALL BE 6" AT PANEL EDGES AND 12" AT INTERMEDIATE SUPPORTS UNLESS NOTED
OTHERWISE. SPACE SCREWS AT 4" OVER GABLE ENDWALLS AND GABLE ENDWALL
TRUSSES.
4. ALL WOOD ELEMENTS EXPOSED TO WEATHER, IN CONTACT WITH CONCRETE OR MASONRY, OR
WITHIN 12" OF ADJACENT GRADE SHALL BE PRESERVATIVE-TREATED IN ACCORDANCE WITH
AMERICAN WOOD PROTECTION ASSOCIATION (AWPA) STANDARD U1 AND M4 FOR THE SPECIES,
PRODUCT, PRESERVATIVE AND END USE.
5. PROVIDE FIRE-TREATED WOOD AS INDICATED BY THE ARCHITECT.
Checked By:
Drawn By:
Date:
SDL Project Number:
Drawing No.:
SealSeal
Revisions
Date:No.
Drawing Title:
D R
A W
IN
G
F
IL
E
P
LO
TT
E D
O N
ANDERSON
COUNTY
ANIMAL
SHELTER
Blankenship & Partners, LLC
1112 Weisgarber Rd, Knoxville, TN 37909
Structural
C
Mechanical/Plumbing/Fire Protection
COPYRIGHT Blankenship & Partners, LLC
This drawing is the property of Blankenship & Partners, LLC and shall not be reproduced in whole or in part. It shall not be used for any other project. This drawing is an instrument of service only and shall be returned to the
Architect upon request.
Contact Name:
Contact Name:
Architects and Planners
Office: 865.251.2585
Project Name:
Owner:
100 N Main Street, Suite 208
Contact Name: Mayor Terry Franks
Contact Name: William R. Blankenship
Consultants:
Electrical
Contact Name: Chris Lay, P.E.
T [865] 745-4401
Knoxville, TN 37939
P.O. Box 10645
Vreeland Engineers, Inc.
Contact Name:
Civil
Anderson County
Clinton, Tennessee 37716
T [865] 457-6200
Randy Corlew, P.E.
T (423) 312.8371
Morristown, Tennessee 37814
376 Lochmere Drive
Welroc Enterprises, LLC
T (615) 320-1735
Brentwood, Tennessee 37027
750 Old Hickeory Blvd Building 1 Suite 175
Stanley D. Lindsey & Associates
T (865) 522-0393
Knoxville, Tennessee 37915
900 E Hill Ave. #350
Engineering Services Group
Rusty Whillock, P.E.
Jason D. Perry, P.E.
C
S D
L\ R
E V
IT
LO
C A
L_
FI
LE
S
-A n d e rs o n C n ty
A n im a l_
S h e lt e r- S D
L2 ja so n p e rr y .r v t
/4
/2
:2 :4
A
M
S0.2
Structural Notes
05/30/25
DP
GR & JDP
25021.00
DRAWING INDEX
Sheet Number Sheet Name
S0.1 Structural AXON Views
S0.2 Structural Notes
S0.3 Structural Notes (Continued)
S0.4 Structural Statement of Special Inspections
S2.1 Foundation Plan
S2.2 Roof Framing Plan
S3.1 Typical Foundation Sections and Details
S3.2 Typical Foundation Sections and Details
S3.3 Typical CMU Wall Framing Sections and Details
S4.1 Framing Sections and Details
S4.2 Framing Sections and Details
S5.1 Roof Truss Profiles and Loading
S5.2 Roof Truss Profiles and Loading
C
OM MERC
E
R
EE
NI
GNE DERETSI
G
E R
AGRICULTURE
E
ESSENNET FO E
T A
T S
Y R
REP .D NO
S
A J
502111 .o
NOTES:
1. LAP LENGTHS ARE CALCULATED PER ARTICLE 6 OF TMS 402 FOR GR. 60 REINFORCING AND ƒ'm = 2,000 PSI
WITH A MINIMUM LENGTH OF 40 BAR DIAMETERS.
2. EDGE BARS SHALL HAVE A MINIMUM 1/2" GROUT BETWEEN MASONRY AND REINFORCING BAR.
3. CENTERED BAR LAP LENGTHS SHALL ONLY BE USED WHEN THE MINIMUM REINFORCMENT SPACING IS 8"
(ONE PER CELL) AND THE LAP IS CENTERED WITHIN THE CELL.
4. LAP LENGTHS GIVEN IN THE ABOVE TABLE SHALL BE INCREASED BY 50% FOR EPOXY COATED REBAR.
5. CONTACT STRUCTURAL ENGINEER FOR REINFORCING AND CMU SIZES NOT SHOWN.
LAP LENGTH
8" CMU 12" & LARGER CMU
CENTER
BAR
SIZE
EDGE CENTER EDGE
#3
#4
#5
#6
#7
#8
#9
15"
20"
25"
38"
52"
79"
103"
15"
25"
39"
73"
100"
150"
191"
15"
20"
25"
30"
35"
50"
64"
15"
25"
39"
73"
100"
150"
191"
E Q
E Q
EQEQ
CENTER BAR
EDGE BAR 1
/2
M
IN
CONCRETE MASONRY UNIT LAP LENGTH SCHEDULE
LAP NOTES:
1. LAP SPLICE LENGTHS ARE BASED ON ACI 318 SECTION 25.4.2.
2. CATEGORY DEFINITIONS: (SEE ADJACENT FIGURES FOR ADDITIONAL INFORMATION)
CATEGORY 1 - OTHER CASES - DOES NOT MEET CATEGORY 2 OR 3.
CATEGORY 2 - CLEAR SPACING OF BARS BEING DEVELOPED OR
SPLICED NOT LESS THAN 2db AND CLEAR COVER NOT LESS THAN db.
CATEGORY 3 - CLEAR COVER NOT LESS THAN 2db AND THE CLEAR SPACING NOT LESS THAN 4db.
3. MINIMUM LAP SPLICE SHALL NOT BE LESS THAN 12 INCHES.
4. MULTIPLY ABOVE LAP LENGTHS BY 1.53 FOR GRADE 80 REINFORCING STEEL.
5. MULTIPLY ABOVE LAP LENGTHS BY 1.3 FOR LIGHTWEIGHT CONCRETE.
6. TOP BARS ARE DEFINED AS HORIZONTAL REINFORCEMENT SO PLACED THAT MORE THAN 12 INCHES OF FRESH
CONCRETE IS CAST IN THE MEMBER BELOW THE DEVELOPMENT LENGTH OR SPLICE.
7. COMPRESSION LAPS FOR GR. 60 UNCOATED BARS IN NORMAL WEIGHT CONCRETE WITH A MINIMUM STRENGTH OF
3,000 PSI SHALL BE 30db. USE 48db FOR GR. 80 COMPRESSION LAP.
8. IF BARS OF DIFFERENT SIZE ARE LAP SPLICED IN TENSION, SPLICE LENGTH SHALL BE THE GREATER OF A CLASS A
LAP OF THE LARGER BAR AND A CLASS B LAP OF THE SMALLER BAR.
CATEGORY 2 CLEAR SPACING AT
STAGGERED SPLICES
CATEGORY 3 CLEAR SPACING AT
OFFSET COLUMN BARS
FACE OF
CONCRETE
OFFSET BARS
FROM COLUMN
BELOW
BARS IN COLUMN
ABOVE
> = 2db d b
SPACING
CLEAR
≥ = 4db d b
FACE OF
CONCRETE
CLEAR SPACING
REINFORCING LAP LENGTH SCHEDULE
TENSION LAP SPLICE LENGTHS, (INCHES) FOR GRADE 60 (4)
UNCOATED BARS, f'c = 3,000psi; NORMAL-WEIGHT CONCRETE (5)
LAP LENGTH PER SPACING AND COVER CASE (3)
BAR
SIZE
LAP
CLASS
TOP BARS (6)
CATEGORY (2)
OTHER BARS
CATEGORY (2)
A B
#3 32
2 3 1 2 3
#4
#5
#6
#7
#8
#9
#10
#11
A B
A B
A B
A B
A B
A B
A B
A B
TENSION LAP SPLICE LENGTHS, (INCHES) FOR GRADE 60 (4)
UNCOATED BARS, f'c = 4,000psi; NORMAL-WEIGHT CONCRETE (5)
LAP LENGTH PER SPACING AND COVER CASE (3)
BAR
SIZE
LAP
CLASS
TOP BARS (6)
CATEGORY (2)
OTHER BARS
CATEGORY (2)
A B
#3 28
2 3 1 2 3
#4
#5
#6
#7
#8
#9
#10
#11
A B
A B
A B
A B
A B
A B
A B
A B
TENSION LAP SPLICE LENGTHS, (INCHES) FOR GRADE 60 (4)
UNCOATED BARS, f'c = 5,000psi; NORMAL-WEIGHT CONCRETE (5)
LAP LENGTH PER SPACING AND COVER CASE (3)
BAR
SIZE
LAP
CLASS
TOP BARS (6)
CATEGORY (2)
OTHER BARS
CATEGORY (2)
A B
#3 25
2 3 1 2 3
#4
#5
#6
#7
#8
#9
#10
#11
A B
A B
A B
A B
A B
A B
A B
A B
D E
P T
H h
E M
B E
D M
E N
T
D E
P T
H
B E
D M
E N
T
D E
P T
H
B E
D M
E N
T
C O
O R w
M
A N
U F
H O
L E
D E
P T
H
C O
O R w
M
A N
U F
H O
L E
D E
P T
H
C O
O R w
M
A N
U F
H O
L E
D E
P T
H
NOTES:
1. POST INSTALLED ANCHORS SHALL BE ONE OF THE PRODUCTS LISTED IN THE TABLE BELOW, UNLESS A SUBSTITUTION
IS APPROVED BY THE STRUCTURAL ENGINEER.
2. THE EMBEDMENT DEPTH SPECIFIED IS THE MINIMUM LENGTH OF THE ANCHOR INTO THE HOLE (NOMINAL EMBEDMENT
DEPTH, hnom).
3. COORDINATE THE ACTUAL ANCHOR LENGTH w/ THE SPECIFIED MINIMUM EMBEDMENT DEPTH, ATTACHMENT
THICKNESS, WASHERS, ETC.
4. ANCHORS AND REINFORCING STEEL SHALL BE INSTALLED PER THE MANUFACTURER’S PRINTED INSTALLATION
INSTRUCTIONS (MPII).
5. COORDINATE THE REQUIRED DRILL BIT TYPE, NOMINAL DIAMETER, AND HOLE DEPTH w/ THE ANCHOR
MANUFACTURER AND THE CODE EVALUATION REPORT. CLEAN THE HOLE AS REQUIRED BY THE MANUFACTURER AND
CODE EVALUATION REPORT REQUIREMENTS FOR THE SELECTED INSTALLATION METHOD.
6. DO NOT DAMAGE ANY EXISTING REINFORCING, INCLUDING PT TENDONS, DURING THE INSTALLATION PROCESS OF
POST-INSTALLED ANCHORS.
7. ANCHORS SHALL BE INSTALLED WITHIN 6° OF PERPENDICULAR TO THE CONCRETE OR MASONRY SURFACE, UNLESS
NOTED OTHERWISE.
8. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE CLEARANCES INDICATED ON THE DRAWINGS. IF NO SPACING OR EDGE DISTANCES ARE SPECIFIED ON THE STRUCTURAL DRAWINGS, REFER TO APPLICABLE EVALUATION
REPORT FOR CRITICAL SPACING AND EDGE DISTANCES.
9. REFERENCE THE STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS.
10. MINIMUM EMBEDMENT DEPTHS SHALL BE THE FOLLOWING, UNLESS NOTED OTHERWISE:
8 × ANCHOR DIAMETER FOR EXPANSION AND SCREW ANCHORS
12 × ANCHOR DIAMETER OR REINFORCING DIAMETER FOR ADHESIVE ANCHORS.
ADHESIVE
ANCHOR w/
REINFORCING
EXPANSION
ANCHOR
SCREW
ANCHOR
POST-INSTALLED ANCHOR INFORMATION
TABLE NOTES:
1. ANCHOR PRODUCT MUST HAVE AN EVALUATION REPORT LISTED TO BE USED IN THE APPLICABLE BASE MATERIAL. IF A "-" IS LISTED IN THE TABLE ABOVE, THEN THE ANCHOR PRODUCT IS NOT PERMITTED IN THAT BASE MATERIAL.
2. ANCHORS IN EXTERIOR AND CORROSIVE ENVIRONMENTS SHALL BE APPROVED BY THE MANUFACTURER FOR THE
EXPOSURE.
3. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE SPECIFIED IN THIS TABLE SHALL BE SUBMITTED BY THE CONTRACTOR TO THE STRUCTURAL ENGINEER ALONG WITH CALCULATIONS THAT ARE SIGNED AND SEALED BY A LICENSED PROFESSIONAL ENGINEER DEMONSTRATING THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING EQUIVALENT PERFORMANCE (MINIMUM) OF THE SPECIFIED PRODUCTS. THE SUBSTITUTION REQUEST SHALL INCLUDE CODE EVALUATION REPORTS STATING THAT THE PRODUCTS ARE APPROVED FOR THE INTENDED USE AND COMPLIANT WITH THE APPLICABLE BUILDING CODE. THE CALCULATIONS SHALL USE THE APPROPRIATE
DESIGN PROCEDURE AND/OR STANDARD(S) AS REQUIRED BY THE BUILDING CODE.
D E
P T
H
B E
D M
E N
T
C O
O R w
M
A N
U F
H O
L E
D E
P T
H
ADHESIVE
ANCHOR w/
THREADED ROD
h n o m h n o m h n o m h n o m
PERMISSIBLE POST-INSTALLED ANCHOR PRODUCTS
ANCHOR
TYPE
MANUFACTURER PRODUCT NAME
BASE MATERIAL
CONCRETE
SOLID GROUTED
CMU
HOLLOW CMU
EXPANSION
ANCHOR
SIMPSON STRONG-TIE STRONG-BOLT 2 ICC ESR-3037 IAPMO-UES ER-240 -
HILTI KWIK BOLT-TZ2 ICC ESR-4266 ICC ESR-4561 -
DEWALT
POWER-STUD+ SD2 ICC ESR-2502 - -
POWER-STUD+ SD1 - ICC ESR-2966 -
SCREW
ANCHOR
SIMPSON STRONG-TIE TITEN-HD ICC ESR-2713 ICC ESR-1056 ICC ESR-1056
HILTI
KWIK HUS-EZ ICC ESR-3027 ICC ESR-3056 -
KWIK-CON II - - NO REPORT
DEWALT
SCREW-BOLT+ ICC ESR-3889 ICC ESR-4042 -
TAPPER + - - ICC ESR-3196
SHALLOW
ANCHOR
HILTI HDI-P-TZ ICC ESR-4236 - -
DEWALT MINI-UNDERCUT+ ICC ESR-3912 - -
ADHESIVE
ANCHORS
SIMPSON STRONG-TIE
SET-3G ICC ESR-4057 ICC ESR-4844 ICC ESR-4844
AT-3G FAST-CURE ICC ESR-5026 - -
HILTI
HIT-RE 500 V3 SLOW CURE ICC ESR-3814 - -
HIT-HY 200 V3 FAST CURE ICC ESR-4868 - -
HIT-HY 200 V3 - ICC ESR-4878 -
HIT-HY 270 - ICC ESR-4143 ICC ESR-4143
DEWALT
PURE110+ ICC ESR-3298 - -
AC100+ GOLD - ICC ESR-3200 ICC ESR-3200
Checked By:
Drawn By:
Date:
SDL Project Number:
Drawing No.:
SealSeal
Revisions
Date:No.
Drawing Title:
D R
A W
IN
G
F
IL
E
P
LO
TT
E D
O N
ANDERSON
COUNTY
ANIMAL
SHELTER
Blankenship & Partners, LLC
1112 Weisgarber Rd, Knoxville, TN 37909
Structural
C
Mechanical/Plumbing/Fire Protection
COPYRIGHT Blankenship & Partners, LLC
This drawing is the property of Blankenship & Partners, LLC and shall not be reproduced in whole or in part. It shall not be used for any other project. This drawing is an instrument of service only and shall be returned to the
Architect upon request.
Contact Name:
Contact Name:
Architects and Planners
Office: 865.251.2585
Project Name:
Owner:
100 N Main Street, Suite 208
Contact Name: Mayor Terry Franks
Contact Name: William R. Blankenship
Consultants:
Electrical
Contact Name: Chris Lay, P.E.
T [865] 745-4401
Knoxville, TN 37939
P.O. Box 10645
Vreeland Engineers, Inc.
Contact Name:
Civil
Anderson County
Clinton, Tennessee 37716
T [865] 457-6200
Randy Corlew, P.E.
T (423) 312.8371
Morristown, Tennessee 37814
376 Lochmere Drive
Welroc Enterprises, LLC
T (615) 320-1735
Brentwood, Tennessee 37027
750 Old Hickeory Blvd Building 1 Suite 175
Stanley D. Lindsey & Associates
T (865) 522-0393
Knoxville, Tennessee 37915
900 E Hill Ave. #350
Engineering Services Group
Rusty Whillock, P.E.
Jason D. Perry, P.E.
C
S D
L\ R
E V
IT
LO
C A
L_
FI
LE
S
-A n d e rs o n C n ty
A n im a l_
S h e lt e r- S D
L2 ja so n p e rr y .r v t
/4
/2
:2 :4
A
M
S0.3
Structural Notes (Continued)
05/30/25
DP
GR & JDP
25021.00
C
OM MERC
E
R
EE
NI
GNE DERETSI
G
E R
AGRICULTURE
E
ESSENNET FO E
T A
T S
Y R
REP .D NO
S
A J
502111 .o
X
X X
X
X - X -
X
- X
X
X
X
X-
X
X
X
X
X -
X
X
X
X
X
X
X
X - X
X
X
X
XX -
X
X-
-X
X - X
X X -
X
X-
X
X- -
X - X
X
X
X
X
X
X
X
X X
X
X
X
X
X
X X
X
X
X
X X
X X
X
X
X
X
X
X
X
X X
X
X
X - X
X X
X X
X X
X X -
- X -
X
X
X
X
X
X
X
X -
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
1704.2.5 INSPECTION OF FABRICATORS
PRE-CAST CONCRETE CONSTRUCTION
STRUCTURAL STEEL CONSTRUCTION
WOOD CONSTRUCTION
COLD FORMED METAL CONSTRUCTION
VERIFICATION OF WELDING CONSUMABLES, FILLER METALS, PROCEDURE SPECIFICATIONS,
PROCEDURE QUALIFICATION RECORDS, AND PERSONNEL PERFORMANCE QUALIFICATION
RECORDS
NONDESTRUCTIVE TESTING OF WELDING
INSPECTION OF WELDING
MATERIAL VERIFICATION OF WELD FILLER MATERIALS
VERIFICATION OF FABRICATOR AND ERECTOR DOCUMENTS AS LISTED IN AISC 360, CHAPTER N, PARAGRAPH 3.2
PRE-STRESSING STEEL INSTALLATION
ERECTION OF PRE-CAST CONCRETE MEMBERS
CONCRETE FIELD SAMPLING AND TESTING
REVIEW CERTIFIED MILL REPORTS
CONCRETE STRENGTH TESTING
REINFORCING PLACEMENT, CAST-IN-PLACE BOLTS, POST INSTALLED ANCHORS CONCRETE
AND SHOTCRETE PLACEMENT AND CURING OPERATIONS. INSPECTION OF FORMWORK FOR
SHAPE, LOCATION AND DIMENSIONS
VERIFICATION OF f'm AND f'ACC
MORTAR JOINT CONSTRUCTION, GROUT PROTECTION AND PLACEMENT, MATERIALS
PROPORTION, TYPE/SIZE/LOCATION OF REINFORCEMENT, STRUCTURAL ELEMENTS,
ANCHORAGE, AND CONNECTORS
SAMPLING/TESTING OF GROUT/MORTAR SPECIMENS
INSPECTION OF WELDING OF REINFORCING STEEL
OBSERVE PREPARATION OF MASONRY PRISMS FOR TESTING OF COMPRESSIVE STRENGTH
OF MASONRY, f'm AND f'ACC
TESTING OF WELDING OF REINFORCING STEEL
OBSERVE INSTALLATION
OBSERVE LOAD TESTS
OBSERVE STRUCTURAL PANEL SHEATHING, SIZE OF FRAMING MEMBERS, NAIL OR STAPLE
DIAMETER AND LENGTH, NUMBER OF FASTENER LINES, AND SPACING OF FASTENER LINES
AND FASTENERS FOR COMPLIANCE WITH CONSTRUCTION DOCUMENTS FOR THE PROJECT
WORK OF UNUSUAL OR SPECIAL NATURE
VERIFY USE OF REQUIRED DESIGN MIX
POST-TENSIONED CONCRETE FORCE APPLICATION
REINFORCING STEEL WELDABILITY, REINFORCING WELDING, WELD FILLER MATERIAL
TESTING OF WELDING OF REINFORCING STEEL
PRE-STRESSED (PRE-TENSIONED) CONCRETE FORCE APPLICATION
OBSERVE SITE PREPARATION, FILL PLACEMENT TESTING OF COMPACTION FOR COMPLIANCE
WITH THE CONSTRUCTION DOCUMENTS FOR THE PROJECT
OBSERVE TEST BEARING MATERIALS BELOW SHALLOW FOUNDATIONS FOR ABILITY TO ACHIEVE
DESIGN BEARING CAPACITY
REVIEW COMPACTION TESTING FOR COMPLIANCE WITH THE CONSTRUCTION DOCUMENTS FOR
THE PROJECT
KEY:
A. LICENSED PROFESSIONAL ENGINEER COMPETENT IN THE SPECIFIC TASK AREA.
B. REGISTERED ARCHITECT COMPETENT IN THE SPECIFIC TASK AREA.
C. ICC SPECIAL INSPECTOR CERTIFICATION SPECIFIC TO THE MATERIAL AND TESTING METHODOLOGY AS APPLICABLE.
D. PTI CERTIFICATION, LEVEL 2, BONDED OR UNBONDED AS APPLICABLE
E. PCI CERTIFIED INSPECTOR
F. AWS-CWI CERTIFIED WELDING INSPECTOR
G. ASNT NON-DESTRUCTIVE TESTING TECHNICIAN - LEVEL II OR III.
H. ACI CONCRETE CONSTRUCTION SPECIAL INSPECTOR
I. NICET TECHNICIAN - LEVELS II OR HIGHER SPECIFIC TO THE MATERIAL AND TESTING METHODOLOGY AS APPLICABLE.
J. ACI CONCRETE FIELD TESTING TECHNICIAN w/GRADE 1 CERTIFICATION.
K. NCMA CONCRETE MASONRY TESTING PROCEDURES CERTIFICATION
L. NICET CERTIFIED ENGINEERING TECHNOLOGISTS (CT).
M. ACI STRENGTH TESTING TECHNICIAN
N. OTHER QUALIFIED SPECIAL INSPECTOR AS APPROVED BY THE BUILDING OFFICIAL AND STRUCTURAL ENGINEER
ORGANIZATION ABBREVIATIONS:
ACI - AMERICAN CONCRETE INSTITUTE
AWS - AMERICAN WELDING SOCIETY
ASNT - AMERICAN SOCIETY OF NON-DESTRUCTIVE TESTING
ICC - INTERNATIONAL CODE COUNCIL
NCMA - NATIONAL CONCRETE MASONRY ASSOCIATION
NICET - NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES
PTI - POST-TENSIONING INSTITUTE
PCI - PRECAST/PRESTRESSED CONCRETE INSTITUTE
NOTES:
1. THE SPECIAL INSPECTOR SHALL MEET ONE OF THE MINIMUM QUALIFICATIONS LISTED FOR THE APPLICABLE CATEGORY OF TESTING AND
INSPECTION SUBJECT TO APPROVAL OF THE BUILDING OFFICIAL.
2. MATERIALS TESTING SHALL BE DONE BY AN APPROVED TESTING AGENCY MEETING THE REQUIREMENTS OF IBC SECTION 1703 AND ASTM
E 329.
STRUCTURAL SPECIAL INSPECTION SCHEDULE:
FABRICATORS
STEEL CONSTRUCTION
CONCRETE CONSTRUCTION (REBAR FABRICATION)
WOOD CONSTRUCTION
COLD FORM METAL CONSTRUCTION
OTHER CONSTRUCTION
STRUCTURAL SPECIAL INSPECTION STATEMENT
THIS STATEMENT OF SPECIAL INSPECTIONS IS SUBMITTED AS A CONDITION FOR PERMIT ISSUANCE IN ACCORDANCE WITH THE SPECIAL INSPECTION AND STRUCTURAL TESTING REQUIREMENTS OF THE BUILDING CODE. IT INCLUDES A SCHEDULE
OF SPECIAL INSPECTION SERVICES APPLICABLE TO THIS PROJECT AS WELL AS THE NAME OF THE SPECIAL INSPECTION COORDINATOR AND THE IDENTITY OF OTHER APPROVED AGENCIES TO BE RETAINED FOR CONDUCTING THESE INSPECTIONS AND TESTS. THIS STATEMENT OF SPECIAL INSPECTIONS ENCOMPASSES THE STRUCTURAL DISCIPLINE.
THE SPECIAL INSPECTION COORDINATOR SHALL KEEP RECORDS OF ALL INSPECTIONS AND SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL AND THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
DISCOVERED DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF SUCH DISCREPANCIES ARE NOT CORRECTED, THE DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE SPECIAL INSPECTION PROGRAM DOES NOT RELIEVE THE CONTRACTOR OF HIS OR HER RESPONSIBILITIES.
INTERIM REPORTS SHALL BE SUBMITTED TO THE BUILDING OFFICIAL AND THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. INTERIM REPORTS SHALL BE SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN CHARGE
WEEKLY.
A FINAL REPORT OF SPECIAL INSPECTIONS DOCUMENTING COMPLETION OF ALL REQUIRED SPECIAL INSPECTIONS, TESTING AND CORRECTION OF ANY DISCREPANCIES NOTED IN THE INSPECTIONS SHALL BE SUBMITTED PRIOR TO
ISSUANCE OF A CERTIFICATE OF USE AND OCCUPANCY.
JOB SITE SAFETY AND MEANS AND METHODS OF CONSTRUCTION ARE SOLELY THE RESPONSIBILITY OF THE CONTRACTOR.
THIS STATEMENT OF SPECIAL INSPECTIONS IS NOT INTENDED TO INCORPORATE ALL ASPECTS OF THE SPECIAL INSPECTION PROGRAM AS DEFINED IN THE SPECIAL INSPECTION AND STRUCTURAL TESTING REQUIREMENTS OF THE BUILDING CODE. REFER TO OTHER DISCIPLINES FOR REMAINING SPECIAL INSPECTIONS THAT MAY BE REQUIRED.
THE STRUCTURAL ENGINEER OF RECORD IS NOT RESPONSIBLE FOR ENSURING THE SPECIAL INSPECTION PROGRAM IS
CONDUCTED IN ACCORDANCE WITH THIS PLAN.
THIS STATEMENT OF SPECIAL INSPECTIONS INCLUDES THE FOLLOWING INSPECTION CATEGORIES:
FABRICATORS
SOILS
DRIVEN DEEP FOUNDATIONS
CAST-IN-PLACE DEEP FOUNDATIONS
HELICAL PILE FOUNDATIONS
H-PILES
CONCRETE CONSTRUCTION
MASONRY CONSTRUCTION - LEVEL 1
MASONRY CONSTRUCTION - LEVEL 2
MASONRY CONSTRUCTION - LEVEL 3
STRUCTURAL STEEL CONSTRUCTION
STRUCTURAL STEEL SEISMIC FORCE-
RESISTING SYSTEM
OPEN-WEB STEEL JOISTS AND
JOIST GIRDERS
COLD-FORMED STEEL DECK
COLD-FORMED STEEL TRUSSES
COLD-FORMED STEEL LIGHT FRAME
CONSTRUCTION
WOOD CONSTRUCTION
CONFIGURATION AND FINISH OF ACCESS HOLES
FIT-UP OF FILLET WELDS
• DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
CONTROL AND HANDLING OF WELDING CONSUMABLES
• PACKAGING
• EXPOSURE CONTROL
NO WELDING OVER CRACKED TACK WELDS
ENVIRONMENTAL CONDITIONS
• WIND SPEED WITHIN LIMITS
• PRECIPITATION AND TEMPERATURE
WPS FOLLOWED
• SETTING OF WELDING EQUIPMENT
• TRAVEL SPEED
• SELECTED WELDING MATERIALS
• SHIELDING GAS TYPE / FLOW RATE
• PREHEAT APPLIED
• INTERPASS TEMPERATURE MAINTAINED (MIN. / MAX.)
• PROPER POSITION (F, V, H, OH)
WELDING TECHNIQUES
• INTERPASS AND FINAL CLEANING
• EACH PASS WITHIN PROFILE LIMITATIONS
• EACH PASS MEETS QUALITY REQUIREMENTS
AISC 360,
N5.4-2
AISC 360,
N5.4-3
WELDS MEET VISUAL ACCEPTANCE CRITERIA
• CRACK PROHIBITION
• WELD / BASE-METAL FUSION
• CRATER CROSS SECTION
• WELD PROFILES
• WELD SIZE
• UNDERCUT
• POROSITY
AISC 360,
N5.6
AISC 360,
N5.6
AISC 360,
N5.6
INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR
PROPER APPLICATION TECHNIQUES.
VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE
AND TECHNIQUES.
INSPECT PRESTRESSED CONCRETE FOR:
a. APPLICATION OF PRESTRESSING FORCES; AND
b. GROUTING OF BONDED PRESTRESSING TENDONS.
INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING
OF TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO
REMOVAL OF SHORES AND FORMS FROM BEAMS AND
STRUCTURAL SLABS.
INSPECT FORMWORK FOR SHAPE, LOCATION AND
DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED.
1908.6, 1908.7, 1908.8
ACI 318: 26.5
ACI 318:
26.5.3-26.5.5
1908.9
ACI 318: 26.10 -
ACI 318:
26.11.1.2(b)
AISC 360,
N5.5
FIT-UP OF CJP GROOVE WELDS OF HSS T-, Y- AND K-JOINTS WITHOUT
BACKING (INCLUDING JOINT GEOMETRY)
• JOINT PREPARATIONS
• DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS
VISUALLY INSPECT THE WELD ACCESS HOLE FOR CRACKS AFTER WELDING
ROLLED HEAVY SHAPES AND BUILT-UP HEAVY SHAPES
SPECIAL INSPECTION AGENCIES
SPECIAL INSPECTOR
TO BE DETERMINED -
ADDRESS AND TELEPHONE NUMBERFIRMRESPONSIBILITY
NOTES:
1.THE INSPECTORS AND TESTING AGENCIES SHALL BE ENGAGED BY THE OWNER OR THE OWNER'S AGENT, AND NOT BY THE
CONTRACTOR.
2.ANY CONFLICT OF INTEREST MUST BE DISCLOSED TO THE BUILDING OFFICIAL AND THE DESIGN PROFESSIONAL PRIOR TO
COMMENCING WORK.
3.THE MINIMUM QUALIFICATIONS OF THE SPECIAL INSPECTOR(S) AND/OR TESTING AGENCIES SHALL BE THOSE LISTED IN THE MINIMUM SPECIAL INSPECTOR QUALIFICATIONS TABLE. THE QUALIFICATIONS OF THE SPECIAL INSPECTOR(S) AND/OR
TESTING AGENCIES MAY BE SUBJECT TO THE APPROVAL OF THE BUILDING OFFICIAL.
4. INSPECTION OF FABRICATORS IS NOT REQUIRED WHERE THE FABRICATOR IS APPROVED IN ACCORDANCE WITH SECTION
1704.2.5.1 OF THE BUILDING CODE.
VERIFY FABRICATION AND IMPLEMENTATION PROCEDURES
- 1705.2
1705.3
1705.5
1705.2
1705.1.1
APPLICABLE
TO THIS
PROJECT?
VERIFICATION AND INSPECTION TASK
FREQUENCY
CONTINUOUS PERIODIC
REFERENCED
STANDARD
CODE
REFERENCE
APPLICABLE
TO THIS
PROJECT?
VERIFICATION AND INSPECTION TASK
FREQUENCY
CONTINUOUS PERIODIC
REFERENCED
STANDARD
CODE
REFERENCE
STRUCTURAL SPECIAL INSPECTION SCHEDULE:
SOILS
VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE
ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY.
VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH
AND HAVE REACHED PROPER MATERIAL.
PERFORM CLASSIFICATION AND TESTING OF COMPACTED
FILL MATERIALS.
VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT
THICKNESSES DURING PLACEMENT AND COMPACTION OF
COMPACTED FILL.
PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE
SUBGRADE AND VERIFY THAT SITE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .