260810_Drawings_Bid_Set.pdf
PDF 18 MB Posted
- Attached to
- Central Energy Plant Construction
- Solicitation number
- ITB 2026-0810
- Issued by
- Brevard County, Miramar Beach CDP, Florida
About this file
Summary of 260810_Drawings_Bid_Set.pdf
This is a bid set of architectural and engineering drawings for the Melbourne Orlando International Airport Terminal MEP/HVAC Renovations project, a multi-phase Central Energy Plant (CEP) replacement initiative undertaken by the Melbourne Airport Authority (MAA) in Melbourne, Florida. The project scope encompasses construction of a new enclosed Central Energy Plant structure with water-cooled chillers and cooling towers on the roof, installation of a new main electrical distribution panel, and installation of a pre-purchased generator, all while maintaining airport operations. The construction documents include comprehensive architectural, structural, mechanical, plumbing, electrical, and fire protection drawings with a drawing index containing 42 sheets organized by discipline, including cover sheets, floor plans, building elevations, wall sections, demolition plans, and detailed specifications. The project includes selective demolition of existing walls, mechanical systems, and equipment within designated areas, followed by installation of new 8-inch concrete masonry unit (CMU) walls with stucco finishes matching existing reveals, new concrete slabs with waterproofing membranes, and coordination of multiple mechanical, electrical, and plumbing systems.
The project documents establish comprehensive submittal and general requirements procedures, including a 14-day initial review period for submittals and up to 21 days for concurrent reviews involving multiple parties. The contractor is responsible for field verification of all dimensions governed by existing conditions, maintenance of traffic control, coordination with other contractors, and provision of full-time construction representation during all operating hours. The contractor must comply with the Florida Building Code, obtain all required permits, maintain the project area for one year following substantial completion, provide weekly progress reports with a CPM-type construction schedule using Primavera software, and furnish operation and maintenance manuals with record drawings upon project closeout. Specific requirements include provision of Energy Star-certified products where available, weekly coordination meetings with the owner and architect, and monthly payment submissions with approved schedules of values. The contract includes provisions for fire-rated construction, accessibility compliance with current Florida Building Code standards and ADA requirements, and coordination of materials testing as part of quality assurance.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING INDEX
NO. SHEET DESCRIPTION LATEST REVISION
ARCHITECTURAL
G001 COVER SHEET 5-26-2026
G002 GENERAL REQUIREMENTS AND SUBMITTAL PROCEDURES
G003 ACCESSIBILITY REQUIREMENTS
A100 LIFE SAFETY
D101 DEMOLITION PLANS
A201 FLOOR PLANS
A202 SLAB AND CEILING PLANS
A301 BUILDING ELEVATIONS
A401 WALL SECTIONS
A402 MISCELLANEOUS DETAILS
A501 DOOR AND FINISH SCHEDULES 5-26-2026
A502 DOOR DETAILS
STRUCTURAL
S1.0 STRUCTURAL NOTES
S2.0 FOUNDATION PLAN
S3.0 ROOF FRAMING PLAN
S4.0 PLATFORM FRAMING PLAN
S5.0 STRUCTURAL SECTIONS AND DETAILS
S6.0 STRUCTURAL SECTIONS AND DETAILS
S7.0 STRUCTURAL SECTIONS AND DETAILS
MECHANICAL
M-1 MECHANICAL SCHEDULES AND DETAILS
M-2 MECHANICAL SITE PLAN
M-3 MECHANICAL DEMOLITION PLAN
M-4 MECHANICAL PLANS
M-5 MECHANICAL PLAN - EEP
M-6 MECHANICAL ELEVATION
M-7 MECHANICAL SCHEDULES
M-8 MECHANICAL DETAILS
M-9 MECHANICAL CONTROLS - AIR SIDE
M-10 MECHANICAL CONTROLS - WATER SIDE
PLUMBING
P-1 PLUMBING LEGEND, NOTES, SPECS. & SCHEDULES
P-2 PLUMBING PLANS
FIRE PROTECTION
FP-1 FIRE PROTECTION PLAN
FP-2 FIRE PROTECTION PLAN
ELECTRICAL
E-1 ELECTRICAL SYMBOLS, LEGEND, ABB., NOTES
E-2 ELECTRICAL CHILLER TEMPORARY POWER
E-3 ELECTRICAL DEMOLITION PLAN
E-4 ELECTRICAL PARTIAL SITE POWER PLAN
E-5 ELECTRICAL POWER PLAN
E-6 ELECTRICAL LIGHTING PLAN
E-7 LIGHTNING PROTECTION PLAN
E-8 ELECTRICAL SCHEDULES
E-9 ELECTRICAL ONE-LINE DIAGRAM
E-10 ELECTRICAL ONE-LINE GROUNDING DIAGRAM
E-11 ELECTRICAL DETAILS
FIRE ALARM
FA-1 FIRE ALARM LEGEND, NOTES, & SPECIFICATIONS
FA-2 FIRE ALARM PLAN
PROJECT SCOPE
NEW SECOND FLOOR MECHANICAL MEZZANINE OVER
EXISTING CHILLER YARD.
COMPLIANCE STATEMENT
REVIEW AND APPROVAL BY THE AUTHORITY HAVING
JURISDICTION SHALL NOT RELIEVE THE APPLICANT OF
THE RESPONSIBILITY OF COMPLIANCE WITH THESE TO
THE BEST OF OUR KNOWLEDGE, THESE DOCUMENTS
COMPLY WITH THE APPLICABLE MINIMUM CODES AND
STANDARDS AS SET FORTH BY THE FLORIDA BUILDING
CODE AND GOVERNING FLORIDA STATUTES.
KEY PLAN
PROJECT INFORMATION
HVAC Modifications
PROJECT DIRECTORY
PROJECT MANAGER
JOHN WARRINGTON
TERMINAL OPERATIONS SUPERVISOR
MELBOURNE ORLANDO INTERNATIONAL AIRPORT
850 ED FOSTER ROAD
MELBOURNE, FLORIDA 32901
(321) 288-6891 jwarrington@mlbair.com
ARCHITECT
SHAD L. TRAYLOR, AIA
TSARK ARCHITECTURE, LLC
1600 SARNO ROAD, SUITE 212
MELBOURNE, FLORIDA 32935
(321) 241-6378 shad@tsarkarchitecture.com
STRUCTURAL ENGINEER
KIERAN JONES, P.E.
MK STRUCTURAL ENGINEERING
587 WEST EAU GALLIE BOULEVARD, SUITE 201
MELBOURNE, FLORIDA 32935
(321) 600-0672 kieran@mkstructural.com
MECHANICAL AND PLUMBING ENGINEER
DAVID DASILVA, P.E.
DDC ENGINEERING, LLC.
40863 US-1, SUITE 101
ROCKLEDGE, FLORIDA 32955
(321) 633-4522 dasilva.david@ddc-engineers.com
ELECTRICAL ENGINEER
RAMON REGALADO, P.E.
DDC ENGINEERING, LLC.
40863 US-1, SUITE 101
ROCKLEDGE, FLORIDA 32955
(321) 633-4522 regalado.ramon@ddc-engineers.com
KEY NOTE DESIGNATION
B
WINDOW DESIGNATION
101A
ACCESSORY DESIGNATION
DOOR NUMBER
PARTITION TYPE DESIGNATION
ROOM NUMBER
ROOM NAME
ON WHICH ELEVATION IS SHOWN
SURFACE SHOWN IN ELEVATION
ELEVATION NUMBER/SHEET NUMBER
DIRECTION OF CUTTING PLANE
SHEET ON WHICH SECTION IS SHOWN
SECTION NUMBER
EXTENT OF DETAIL
SHEET ON WHICH DRAWING IS SHOWN
DRAWING NUMBER
A
P1
ROOM
NAME
A101
DETAIL NUMBER/SHEET NUMBER ON
WHICH DETAIL IS SHOWN
GRAPHIC SYMBOLSABBREVIATIONS
A/C AIR CONDITIONING
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE, ALTERNATIVE
ALUM ALUMINUM
APPROX APPROXIMATE(LY)
ARCH ARCHITECT(URAL)
AV AUDIOVISUAL
BLDG BUILDING
BO BOTTOM OF
CLG CEILING
CLG HT CEILING HEIGHT
CLO CLOSET
CLR CLEAR(ANCE)
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUE, CONTINUOUS
CORR CORRIDOR
DEMO DEMOLISH
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIV DIVISION
E EAST
EA EACH
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXT EXTERIOR
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FIN FLR FINISHED FLOOR
FLR FLOOR
FT FOOT, FEET
FURN FURNITURE
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GYP BD GYPSUM BOARD
HC HANDICAP
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
HVAC HEATING, VENTILATION & AIR
CONDITIONING
INCL INCLUDE(D), (ING)
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
KIT KITCHEN
LAB LABOATORY
LAV LAVATORY
LF LINEAR FEET
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEZZ MEZZANINE
MFG MANUFACTURING
MFR MANUFACTURER
MIN MINUMUM
MISC MISCELLANEOUS
MR MOISTURE RESISTANT
MTG MOUNTING
N NORTH
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OPT OPTION(AL)
PLAM PLASTIC LAMINATE
PLF POUNDS PER LINEAR FEET
PLYWD PLYWOOD
PR PAIR
PREFAB PREFABRICATED
PREFIN PREFINISH
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFERENCE
REQD REQUIRED
RFG REFRIGERATOR
RM ROOM
RO ROUGH OPENING
S SOUTH
SC SOLID CORE
SD STORM DRAIN
SECT SECTION
SF SQUARE FEET
SIM SIMILAR
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STOR STORAGE
SUSP SUSPENDED
SYS SYSTEM
TEL TELEPHONE
TEMP TEMPORARY
THRU THROUGH
TO TOP OF
TRTD TREATED
TV TELEVISION
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
W WEST, WIDE
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WT WEIGHT
Tsark Architecture, LLC 1600 Sarno Rd., Suite 212
Melbourne, FL 32935
(321) 241-6378
Lic #: AA26003779
REVIEW SET
Shad L. Traylor
AR 93039
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
REVISIONS
4083 South U.S. Highway 1, Ste. 101 Rockledge, Florida 32955 Phone 321.633.4522 Fax 321.633.4528 www.ddc-engineers.com dasilva.david@ddc-engineers.com C.O.A.: 25988
DDC PROJECT NO.:
2026 by Tsark Architecture, LLC All rights reserved. No part of this work covered by the copyright hereon may be reproduced or used in any form or by any means - graphic, electronic or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without written permission of the copyright holder.ãCOPYRIGHT
26625A
DESCRIPTIONNO. DATE
26030.01
AUGUST 10, 2026
M
EL
BO
UR
NE
O
RL
AN
DO
IN
TE
RN
AT
IO
NA
L
AI
RP
OR
T
TE
RM
IN
AL
M
EP
/H
VA
C
RE
NO
VA
TI
ON
S
AI
R
TE
RM
IN
AL
P
AR
KW
AY
, M
EL
BO
UR
NE
, F
L
CL
IE
NT
P
RO
JE
CT
: 5
BID SET
NOT FOR
CONSTRUCTION
ST
ST
CW
G001
Melbourne Orlando International Airport
CO
VE
R
SH
EE
T
PROJECT AREA
AutoCAD SHX Text
KEY NOTE REFERENCE
AutoCAD SHX Text
OPENING REFERENCE
AutoCAD SHX Text
ACCESSORIES REFERENCE
AutoCAD SHX Text
OPENING REFERENCE
AutoCAD SHX Text
PARTITION REFERENCE
AutoCAD SHX Text
ELEVATION REFERENCE
AutoCAD SHX Text 1/A701
AutoCAD SHX Text
SECTION REFERENCE
AutoCAD SHX Text
DETAIL REFERENCE
AutoCAD SHX Text
AutoCAD SHX Text A601
AutoCAD SHX Text
ROOM REFERENCE
AutoCAD SHX Text
AutoCAD SHX Text A501
AutoCAD SHX Text
DETAIL REFERENCE
AutoCAD SHX Text 1/A302
PART 1 - GENERAL
1.1 SUMMARY
A. THIS SECTION INCLUDES ADMINISTRATIVE AND PROCEDURAL REQUIREMENTS FOR
SUBMITTING SHOP DRAWINGS, PRODUCT DATA, SAMPLES, AND OTHER MISCELLANEOUS
SUBMITTALS.
1.2 DEFINITIONS
A. ACTION SUBMITTALS: WRITTEN AND GRAPHIC INFORMATION THAT REQUIRES
ARCHITECT'S/ENGINEER'S RESPONSIVE ACTION.
B. INFORMATIONAL SUBMITTALS: WRITTEN INFORMATION THAT DOES NOT REQUIRE
ARCHITECT'S/ENGINEER'S APPROVAL. SUBMITTALS MAY BE REJECTED FOR NOT
COMPLYING WITH REQUIREMENTS.
1.3 SUBMITTAL PROCEDURES
A. GENERAL: ELECTRONIC COPIES (.PDF ONLY) OF DRAWINGS OF THE CONTRACT
DRAWINGS WILL BE PROVIDED BY ARCHITECT/ENGINEER FOR CONTRACTOR'S USE IN
PREPARING SUBMITTALS.
B. CONTRACTOR SHALL SUBMIT SOFT COPIES OF PRODUCT DATA, SHOP DRAWINGS, AND
PHYSICAL COPIES OF SAMPLES.
C. ALL SUBMITTED SHOP DRAWINGS SHALL HAVE ENHANCEMENT OR ADDITIONAL DETAILS
THAN THAT OF THE ARCHITECT'S/ENGINEER'S, REFLECTING TYPES OF MATERIAL
ALREADY SUBMITTED FOR APPROVAL AND APPROVED BY THE
ARCHITECT/ENGINEER/OWNER AND REFLECTING ALL NECESSARY
EQUIPMENT, IF ANY, OR ELSE THE SUBMITTED SHOP DRAWING SHALL NOT BE
CONSIDERED AS COMPLETE.
D. COORDINATION: COORDINATE PREPARATION AND PROCESSING OF SUBMITTALS WITH
PERFORMANCE OF CONSTRUCTION ACTIVITIES.
E. PROCESSING TIME: ALLOW ENOUGH TIME FOR SUBMITTAL REVIEW, INCLUDING TIME FOR
RESUBMITTALS, AS FOLLOWS. TIME FOR REVIEW SHALL COMMENCE ON
ARCHITECT'S/ENGINEER'S RECEIPT OF SUBMITTAL.
1. INITIAL REVIEW: ALLOW UP TO 14 DAYS FOR INITIAL REVIEW OF EACH SUBMITTAL.
ALLOW ADDITIONAL TIME IF PROCESSING MUST BE DELAYED TO PERMIT
COORDINATION WITH SUBSEQUENT SUBMITTALS. ARCHITECT/ENGINEER WILL ADVISE
CONTRACTOR WHEN A SUBMITTAL BEING PROCESSED MUST BE DELAYED FOR
COORDINATION.
2. CONCURRENT REVIEW: WHERE CONCURRENT REVIEW OF SUBMITTALS BY
ARCHITECT'S/ENGINEER'S CONSULTANTS, OWNER, OR OTHER PARTIES IS REQUIRED,
ALLOW UP TO 21 DAYS FOR INITIAL REVIEW OF EACH SUBMITTAL.
3. NO EXTENSION OF THE CONTRACT TIME WILL BE AUTHORIZED BECAUSE OF FAILURE
TO TRANSMIT SUBMITTALS ENOUGH IN ADVANCE OF THE WORK TO PERMIT
PROCESSING.
F. IDENTIFICATION: PLACE A LABEL OR TITLE BLOCK ON EACH SUBMITTAL FOR
IDENTIFICATION.
1. INDICATE NAME OF FIRM OR ENTITY THAT PREPARED EACH SUBMITTAL ON LABEL OR
TITLE BLOCK.
2. PROVIDE A SPACE APPROXIMATELY 4 BY 5 INCHES (100 BY 125 MM) ON LABEL OR
BESIDE TITLE BLOCK TO RECORD CONTRACTOR'S REVIEW AND APPROVAL MARKINGS
AND ACTION TAKEN BY ARCHITECT/ENGINEER.
3. INCLUDE THE FOLLOWING INFORMATION ON LABEL FOR PROCESSING AND
RECORDING ACTION TAKEN:
a. PROJECT NAME.
b. DATE.
c. NAME OF ARCHITECT/ENGINEER.
d. NAME OF CONTRACTOR.
e. NAME OF SUBCONTRACTOR.
f. NAME OF SUPPLIER.
g. NAME OF MANUFACTURER.
h. UNIQUE IDENTIFIER, INCLUDING REVISION NUMBER.
i. NUMBER AND TITLE OF APPROPRIATE SPECIFICATION SECTION.
j. DRAWING NUMBER AND DETAIL REFERENCES, AS APPROPRIATE.
G. DEVIATIONS: HIGHLIGHT, ENCIRCLE, OR OTHERWISE IDENTIFY DEVIATIONS FROM THE
CONTRACT DOCUMENTS ON SUBMITTALS.
H. TRANSMITTAL: ARCHITECT/ENGINEER WILL RETURN SUBMITTALS, WITHOUT REVIEW,
RECEIVED FROM SOURCES OTHER THAN CONTRACTOR.
1. ON AN ATTACHED SEPARATE SHEET, PREPARED ON CONTRACTOR'S LETTERHEAD,
RECORD RELEVANT INFORMATION, REQUESTS FOR DATA, REVISIONS OTHER THAN
THOSE REQUESTED BY ARCHITECT/ENGINEER ON PREVIOUS SUBMITTALS, AND
DEVIATIONS FROM REQUIREMENTS OF THE CONTRACT DOCUMENTS, INCLUDING
MINOR VARIATIONS AND LIMITATIONS. INCLUDE THE SAME LABEL INFORMATION AS
THE RELATED SUBMITTAL.
2. INCLUDE CONTRACTOR'S CERTIFICATION STATING THAT INFORMATION SUBMITTED
COMPLIES WITH REQUIREMENTS OF THE CONTRACT DOCUMENTS.
I. DISTRIBUTION: FURNISH COPIES OF FINAL SUBMITTALS TO MANUFACTURERS,
SUBCONTRACTORS, SUPPLIERS, FABRICATORS, INSTALLERS, AUTHORITIES HAVING
JURISDICTION, AND OTHERS AS NECESSARY FOR PERFORMANCE OF CONSTRUCTION
ACTIVITIES.
J. ISSUED FOR CONSTRUCTION: USE ONLY FINAL SUBMITTALS WITH MARK INDICATING
ACTION TAKEN BY ARCHITECT/ENGINEER IN CONNECTION WITH CONSTRUCTION.
PART 2 - PRODUCTS
2.1 ACTION SUBMITTALS
A. GENERAL: PREPARE AND SUBMIT ACTION SUBMITTALS REQUIRED BY CONTRACT
DOCUMENTS.
1. NUMBER OF COPIES: SUBMIT COPIES OF EACH SUBMITTAL, AS FOLLOWS, UNLESS
OTHERWISE INDICATED:
a. INITIAL SUBMITTAL: SUBMIT A PRELIMINARY SINGLE COPY OF EACH SUBMITTAL
WHERE SELECTION OF OPTIONS, COLOR, PATTERN, TEXTURE, OR SIMILAR
CHARACTERISTICS IS REQUIRED. ARCHITECT/ENGINEER, WILL RETURN
SUBMITTAL WITH OPTIONS SELECTED.
b. FINAL SUBMITTAL: SUBMIT THREE COPIES, UNLESS COPIES ARE REQUIRED FOR
OPERATION AND MAINTENANCE MANUALS. SUBMIT FIVE COPIES WHERE COPIES
ARE REQUIRED FOR OPERATION AND MAINTENANCE MANUALS.
ARCHITECT/ENGINEER WILL RETAIN TWO COPIES; DIVISION 01 GENERAL
REQUIREMENTS TENDER DOCUMENTS-SPECIFICATIONS REMAINDER WILL BE
RETURNED. MARK UP AND RETAIN ONE RETURNED COPY AS A PROJECT RECORD
DOCUMENT.
B. PRODUCT DATA: COLLECT INFORMATION INTO A SINGLE SUBMITTAL FOR EACH ELEMENT
OF CONSTRUCTION AND TYPE OF PRODUCT OR EQUIPMENT.
1. IF INFORMATION MUST BE SPECIALLY PREPARED FOR SUBMITTAL BECAUSE
STANDARD PRINTED DATA ARE NOT SUITABLE FOR USE, SUBMIT AS SHOP DRAWINGS,
NOT AS PRODUCT DATA.
2. MARK EACH COPY OF EACH SUBMITTAL TO SHOW WHICH PRODUCTS AND OPTIONS
ARE APPLICABLE.
3. INCLUDE THE FOLLOWING INFORMATION, AS APPLICABLE:
a. MANUFACTURER'S WRITTEN RECOMMENDATIONS.
b. MANUFACTURER'S PRODUCT SPECIFICATIONS.
c. MANUFACTURER'S INSTALLATION INSTRUCTIONS.
d. STANDARD COLOR CHARTS.
e. MANUFACTURER'S CATALOG CUTS.
f. WIRING DIAGRAMS SHOWING FACTORY-INSTALLED WIRING.
g. PRINTED PERFORMANCE CURVES.
h. OPERATIONAL RANGE DIAGRAMS.
i. MILL REPORTS.
j. STANDARD PRODUCT OPERATING AND MAINTENANCE MANUALS.
k. COMPLIANCE WITH RECOGNIZED TRADE ASSOCIATION STANDARDS.
l. COMPLIANCE WITH RECOGNIZED TESTING AGENCY STANDARDS.
m. APPLICATION OF TESTING AGENCY LABELS AND SEALS.
n. NOTATION OF COORDINATION REQUIREMENTS.
C. SHOP DRAWINGS: PREPARE PROJECT-SPECIFIC INFORMATION, DRAWN ACCURATELY TO
SCALE. DO NOT BASE SHOP DRAWINGS ON REPRODUCTIONS OF THE CONTRACT
DOCUMENTS OR STANDARD PRINTED DATA.
D. SAMPLES: PREPARE PHYSICAL UNITS OF MATERIALS OR PRODUCTS, INCLUDING THE
FOLLOWING:
1. SAMPLES FOR INITIAL SELECTION: SUBMIT MANUFACTURER'S COLOR CHARTS
CONSISTING OF UNITS OR SECTIONS OF UNITS SHOWING THE FULL RANGE OF
COLORS, TEXTURES, AND PATTERNS AVAILABLE.
2. SAMPLES FOR VERIFICATION: SUBMIT FULL-SIZE UNITS OR SAMPLES OF SIZE
INDICATED, PREPARED FROM THE SAME MATERIAL TO BE USED FOR THE WORK,
CURED AND FINISHED IN MANNER SPECIFIED, AND PHYSICALLY IDENTICAL WITH THE
PRODUCT PROPOSED FOR USE, AND THAT SHOW FULL RANGE OF COLOR AND
TEXTURE VARIATIONS EXPECTED. SAMPLES INCLUDE, BUT ARE NOT LIMITED TO, THE
FOLLOWING: PARTIAL SECTIONS OF MANUFACTURED OR FABRICATED COMPONENTS;
SMALL CUTS OR CONTAINERS OF MATERIALS; COMPLETE UNITS OF REPETITIVELY
USED MATERIALS; SWATCHES SHOWING COLOR, TEXTURE, AND PATTERN; COLOR
RANGE SETS; AND COMPONENTS USED FOR INDEPENDENT TESTING AND
INSPECTION.
3. PREPARATION: MOUNT, DISPLAY, OR PACKAGE SAMPLES IN MANNER SPECIFIED TO
FACILITATE REVIEW OF QUALITIES INDICATED. PREPARE SAMPLES TO MATCH
ARCHITECT'S/ENGINEER'S SAMPLE WHERE SO INDICATED. ATTACH LABEL ON
UNEXPOSED SIDE THAT INCLUDES THE FOLLOWING:
a. GENERIC DESCRIPTION OF SAMPLE.
b. PRODUCT NAME OR NAME OF MANUFACTURER.
c. SAMPLE SOURCE.
4. ADDITIONAL INFORMATION: ON AN ATTACHED SEPARATE SHEET, PREPARED ON
CONTRACTOR'S LETTERHEAD, PROVIDE THE FOLLOWING, AS APPLICABLE:
a. SIZE LIMITATIONS.
b. COMPLIANCE WITH RECOGNIZED STANDARDS.
c. AVAILABILITY.
d. DELIVERY TIME.
5. SUBMIT SAMPLES FOR REVIEW OF KIND, COLOR, PATTERN, AND TEXTURE FOR A
FINAL CHECK OF THESE CHARACTERISTICS WITH OTHER ELEMENTS AND FOR A
COMPARISON OF THESE CHARACTERISTICS BETWEEN FINAL SUBMITTAL AND ACTUAL
COMPONENT AS DELIVERED AND INSTALLED.
6. NUMBER OF SAMPLES FOR INITIAL SELECTION: SUBMIT ONE FULL SET OF AVAILABLE
CHOICES WHERE COLOR, PATTERN, TEXTURE, OR SIMILAR CHARACTERISTICS ARE
REQUIRED TO BE SELECTED FROM MANUFACTURER'S PRODUCT LINE.
ARCHITECT/ENGINEER WILL RETURN SUBMITTAL WITH OPTIONS SELECTED.
7. DISPOSITION: MAINTAIN SETS OF APPROVED SAMPLES AT PROJECT SITE, AVAILABLE
FOR QUALITY- CONTROL COMPARISONS THROUGHOUT THE COURSE OF
CONSTRUCTION ACTIVITY. SAMPLE SETS MAY BE USED TO DETERMINE FINAL
ACCEPTANCE OF CONSTRUCTION ASSOCIATED WITH EACH SET.
2.2 INFORMATIONAL SUBMITTALS
A. GENERAL: PREPARE AND SUBMIT INFORMATIONAL SUBMITTALS REQUIRED BY OTHER
SPECIFICATION SECTIONS.
1. CERTIFICATES AND CERTIFICATIONS: PROVIDE A NOTARIZED STATEMENT THAT
INCLUDES SIGNATURE OF ENTITY RESPONSIBLE FOR PREPARING CERTIFICATION.
CERTIFICATES AND CERTIFICATIONS SHALL BE SIGNED BY AN OFFICER OR OTHER
INDIVIDUAL AUTHORIZED TO SIGN DOCUMENTS ON BEHALF OF THAT ENTITY.
2. TEST AND INSPECTION REPORTS: COMPLY WITH REQUIREMENTS IN CONTRACT
DOCUMENTS
B. CONTRACTOR'S CONSTRUCTION SCHEDULE:
C. MATERIAL TEST REPORTS: PREPARE REPORTS WRITTEN BY A QUALIFIED TESTING
AGENCY, ON TESTING AGENCY'S STANDARD FORM, INDICATING AND INTERPRETING TEST
RESULTS OF MATERIAL FOR COMPLIANCE WITH REQUIREMENTS.
D. MAINTENANCE DATA: PREPARE WRITTEN AND GRAPHIC INSTRUCTIONS AND
PROCEDURES FOR OPERATION AND NORMAL MAINTENANCE OF PRODUCTS AND
EQUIPMENT. COMPLY WITH GENERAL REQUIREMENTS.
E. MANUFACTURER'S INSTRUCTIONS: PREPARE WRITTEN OR PUBLISHED INFORMATION
THAT DOCUMENTS MANUFACTURER'S RECOMMENDATIONS, GUIDELINES, AND
PROCEDURES FOR INSTALLING ORZEZ E OPERATING A PRODUCT OR EQUIPMENT.
INCLUDE NAME OF PRODUCT AND NAME, ADDRESS, AND TELEPHONE NUMBER OF
MANUFACTURER. INCLUDE THE FOLLOWING, AS APPLICABLE:
1. PREPARATION OF SUBSTRATES.
2. RECOMMENDATIONS FOR CLEANING AND PROTECTION.
F. MANUFACTURER'S FIELD REPORTS: PREPARE WRITTEN INFORMATION DOCUMENTING
FACTORY-AUTHORIZED SERVICE REPRESENTATIVE'S TESTS AND INSPECTIONS. INCLUDE
THE FOLLOWING, AS APPLICABLE:
1. NAME, ADDRESS, AND TELEPHONE NUMBER OF FACTORY-AUTHORIZED SERVICE
REPRESENTATIVE MAKING REPORT.
2. STATEMENT ON CONDITION OF SUBSTRATES AND THEIR ACCEPTABILITY FOR
INSTALLATION OF PRODUCT.
3. STATEMENT THAT PRODUCTS AT PROJECT SITE COMPLY WITH REQUIREMENTS.
4. SUMMARY OF INSTALLATION PROCEDURES BEING FOLLOWED, WHETHER THEY
COMPLY WITH REQUIREMENTS AND, IF NOT, WHAT CORRECTIVE ACTION WAS TAKEN.
5. RESULTS OF OPERATIONAL AND OTHER TESTS AND A STATEMENT OF WHETHER
OBSERVED PERFORMANCE COMPLIES WITH REQUIREMENTS.
6. STATEMENT WHETHER CONDITIONS, PRODUCTS, AND INSTALLATION WILL AFFECT
WARRANTY.
G. INSURANCE CERTIFICATES AND BONDS: PREPARE WRITTEN INFORMATION INDICATING
CURRENT STATUS OF INSURANCE OR BONDING COVERAGE. INCLUDE NAME OF ENTITY
COVERED BY INSURANCE OR BOND, LIMITS OF COVERAGE, AMOUNTS OF DEDUCTIBLES,
IF ANY, AND TERM OF THE COVERAGE.
H. MONTHLY PROGRESS REPORT: REPORT SHALL INCLUDE THE FOLLOWING:
1. SCHEDULE OF PLANNING WITH UPDATES AND CURRENT SITUATION AT THE DATE OF
REPORT PREPARATION.
2. UPDATED CASHFLOW.
3. SUBMITTALS LOG.
4. CONSTRUCTION PROGRESS PHOTOGRAPHS
5. DAILY REPORTS
6. VARIATION ORDERS.
7. PAYMENT CERTIFICATES.
8. LIST OF PROBLEMS FACED ON SITE.
PART 3 - EXECUTION
3.1 CONTRACTOR'S REVIEW
A. REVIEW EACH SUBMITTAL AND CHECK FOR COMPLIANCE WITH THE CONTRACT
DOCUMENTS. NOTE CORRECTIONS AND FIELD DIMENSIONS. MARK WITH APPROVAL
STAMP BEFORE SUBMITTING TO ARCHITECT/ENGINEER.
B. APPROVAL STAMP: STAMP EACH SUBMITTAL WITH A UNIFORM, APPROVAL STAMP.
INCLUDE PROJECT NAME AND LOCATION, SUBMITTAL NUMBER, SPECIFICATION SECTION
TITLE AND NUMBER, NAME OF REVIEWER, DATE OF CONTRACTOR'S APPROVAL, AND
STATEMENT CERTIFYING THAT SUBMITTAL HAS BEEN REVIEWED, CHECKED, AND
APPROVED FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS.
3.2 ARCHITECT'S/ENGINEER'S ACTION
A. GENERAL: ARCHITECT/ENGINEER WILL NOT REVIEW SUBMITTALS THAT DO NOT BEAR
CONTRACTOR'S APPROVAL STAMP AND WILL RETURN THEM WITHOUT ACTION.
B. ACTION SUBMITTALS: ARCHITECT/ENGINEER WILL REVIEW EACH SUBMITTAL, MAKE
MARKS TO INDICATE CORRECTIONS OR MODIFICATIONS REQUIRED, AND RETURN IT.
ARCHITECT/ENGINEER WILL ATTACH A COVER LETTER TO EACH SUBMITTAL INDICATING
AN ACTION TO BE TAKEN, AS FOLLOWS:
1. APPROVED
2. APPROVED AS NOTED
3. REVISE RESUBMIT
4. REJECTED - RESUBMIT
C. INFORMATIONAL SUBMITTALS: ARCHITECT/ENGINEER WILL REVIEW EACH SUBMITTAL
AND WILL NOT RETURN IT, OR WILL REJECT AND RETURN IT IF IT DOES NOT COMPLY WITH
REQUIREMENTS. ARCHITECT/ENGINEER WILL FORWARD EACH SUBMITTAL TO
APPROPRIATE PARTY.
D. SUBMITTALS NOT REQUIRED BY THE CONTRACT DOCUMENTS WILL NOT BE REVIEWED
AND MAY BE DISCARDED.
01 10 00 - GENERAL REQUIREMENTS 01 33 00 SUBMITTAL PROCEDURES
Tsark Architecture, LLC 1600 Sarno Rd., Suite 212
Melbourne, FL 32935
(321) 241-6378
Lic #: AA26003779
REVIEW SET
Shad L. Traylor
AR 93039
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
REVISIONS
4083 South U.S. Highway 1, Ste. 101 Rockledge, Florida 32955 Phone 321.633.4522 Fax 321.633.4528 www.ddc-engineers.com dasilva.david@ddc-engineers.com C.O.A.: 25988
DDC PROJECT NO.:
2026 by Tsark Architecture, LLC All rights reserved. No part of this work covered by the copyright hereon may be reproduced or used in any form or by any means - graphic, electronic or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without written permission of the copyright holder.ãCOPYRIGHT
26625A
DESCRIPTIONNO. DATE
26030.01
AUGUST 10, 2026
M
EL
BO
UR
NE
O
RL
AN
DO
IN
TE
RN
AT
IO
NA
L
AI
RP
OR
T
TE
RM
IN
AL
M
EP
/H
VA
C
RE
NO
VA
TI
ON
S
AI
R
TE
RM
IN
AL
P
AR
KW
AY
, M
EL
BO
UR
NE
, F
L
CL
IE
NT
P
RO
JE
CT
: 5
BID SET
NOT FOR
CONSTRUCTION
G002
CW
ST
ST
G
EN
ER
AL
R
EQ
U
IR
EM
EN
TS
S U
BM
IT
TA
LS
1. THE ENGINEER HAS PREPARED THIS SET OF CONTRACT DOCUMENTS BASED ON
VISUAL INSPECTION OF THE EXISTING PREMISES AND ON INFORMATION PROVIDED BY
THE OWNER.
2. IN THE EVENT OF A DISCREPANCY IN THE CONSTRUCTION DOCUMENTS, THE
PREVAILING ORDER SHALL BE:
A. CONTRACT FOR CONSTRUCTION
B. GENERAL REQUIREMENTS
C. SPECIAL REQUIREMENTS
D. OWNER'S PUBLISHED DESIGN STANDARDS, IF APPLICABLE
E. SPECIFICATIONS
F. DETAILS ON DRAWINGS
G. PLAN DRAWINGS
3. THE CONTRACTOR SHALL PROVIDE ALL WORK NECESSARY TO ENSURE A
FUNCTIONAL FACILITY UPON COMPLETION OF THE PROJECT.
4. ALL DIMENSIONS GOVERNED BY EXISTING CONDITIONS ARE APPROXIMATE. ALL SUCH
DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED BY THE GENERAL
CONTRACTOR PRIOR TO PROCEEDING WITH ANY WORK. SHOULD CONDITIONS OR
DIMENSIONS VARY FROM THOSE SHOWN, THE CONTRACTOR SHALL NOTIFY THE
ENGINEER BEFORE PROCEEDING. USE FIGURED DIMENSIONS. DO NOT SCALE
DRAWINGS. WHERE DIMENSIONS ARE SHOWN WITH A "±", ADJUSTMENTS MAY BE
MADE TO SUIT FIELD CONDITIONS.
5. TO ESTABLISH THE COMPREHENSIVE SCOPE OF WORK AND TO ASSURE
COORDINATION WITH OTHER TRADES, EACH SUBCONTRACTOR SHALL COMPLETELY
REVIEW THE PLANS, NOT ONLY FOR HIS OR HER RESPECTIVE TRADE, BUT FOR THE
WORK OF OTHER TRADES AS WELL. THE DOCUMENTS ARE INTERDEPENDENT. ONCE
THE CONTRACTOR OR SUBCONTRACTOR HAS COMMENCED WITH HIS WORK, IT SHALL
BE ASSUMED THAT HE HAS ACCEPTED THE CONDITIONS IN THE FIELD TO BE
CORRECT AND RIGHT FOR THE INSTALLATION OF HIS WORK.
6. ALL SUBCONTRACTORS FOR DEMOLITION AND REMEDIATION SHALL BE LICENSED TO
OPERATE IN BREVARD COUNTY, FLORIDA.
7. ALL SUBCONTRACTORS SHALL BE LICENSED TO OPERATE IN BREVARD COUNTY,
FLORIDA.
8. OWNER SHALL RETAIN ALL SAVAGE RIGHTS UNTIL THE RIGHTS ARE RELEASED BY
THE OWNER.
9. ALL WORK SHALL BE ACCOMPLISHED IN ACCORDANCE WITH THE ENVIRONMENTAL
PROTECTION AGENCY, STATE AND LOCAL ENVIRONMENTAL LAWS AND REGULATIONS.
THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS PRIOR TO CONSTRUCTION.
PERMITS SHALL BE POSTED AT THE JOBSITE.
10. CONSTRUCTION SHALL COMPLY WITH THE CURRENT EDITION OF THE FLORIDA
BUILDING CODE.
11. NO ASBESTOS CONTAINING BUILDING MATERIALS MAY BE USED DURING
CONSTRUCTION.
12. CONTRACTOR SHALL WARRANT THE PROJECT AREA FOR A TERM OF ONE YEAR FROM
THE DATE OF SUBSTANTIAL COMPLETION OF THE ENTIRE PROJECT, REGARDLESS OF
PARTIAL OCCUPANCY.
13. PROVIDE PRODUCTS HAVING "ENERGY STAR" CERTIFICATIONS WHEN AVAILABLE.
14. CONTRACTOR SHALL PROVIDE A CONSTRUCTION ACCESS AND STAGING AREA PLAN
FOR OWNER'S APPROVAL.
15. THE PROJECT SHALL HAVE FULL TIME, CONSTRUCTION REPRESENTATION DURING
ALL HOURS OF OPERATION. THIS REPRESENTATION CAN BE IN THE FORM OF A
PROJECT MANAGER OR SUPERINTENDENT.
16. CONTRACTOR SHALL PROVIDE A SAFETY BARRIER TO PREVENT INTERACTIONS
BETWEEN THE PUBLIC AND THE JOBSITE.
17. WORKING HOURS SHALL BE COORDINATED WITH, AND APPROVED BY, THE OWNER.
18. PROGRESS PAYMENTS ARE TO BE SUBMITTED MONTHLY.
19. A SCHEDULE OF VALUES SHALL BE SUBMITTED AND APPROVED PRIOR TO THE INITIAL
PAY REQUEST.
20. A DAILY REPORT IS TO BE KEPT BY THE CONTRACTOR AND A WEEKLY REPORT IS TO
BE SUBMITTED TO THE OWNER'S REPRESENTATIVE SHOWING THE CURRENT
PROJECT STATUS, TWO WEEK LOOK-AHEAD, ISSUES AND PROBLEMS, PERMIT STATUS
AND PERCENT COMPLETE.
21. ALL TRAINING VIDEOS SHALL BE DIGITALLY RECORDED AND SUBMITTED TO THE
OWNER.
22. COORDINATION MEETINGS SHALL HAVE AN AGENDA PREPARED BY AND MEETING
MINUTES TAKEN BY THE CONTRACTOR.
23. CONTRACTOR IS TO HOLD WEEKLY COORDINATION MEETINGS, INVITING BOTH THE
OWNER'S REPRESENTATIVE AND THE ARCHITECT.
24. THE CONSTRUCTION SCHEDULE WILL BE UPDATED MONTHLY AT EACH PAY REQUEST
AND BE REVIEWED AT THAT TIME AS A CONDITION OF THE PAY APPLICATION.
25. ALL SUBSTITUTION REQUESTS FROM THE CONTRACTOR SHALL BE REVIEWED BY THE
ARCHITECT AND ACCEPTED/REJECTED BY THE OWNER'S REPRESENTATIVE, BASED
ON THE ENGINEER'S RECOMMENDATION, PRIOR TO INCORPORATION IN THE WORK.
26. FLORIDA PRODUCT APPROVAL NUMBERS SHALL BE SUBMITTED BY THE CONTRACTOR
FOR BUILDING COMPONENTS SUCH AS EXTERIOR DOORS, WINDOWS, PANELS,
ROOFING PRODUCTS, SHUTTERS, SKYLIGHTS, LOUVERS, AND OTHER PRODUCTS
COMPRISING THE BUILDING ENVELOPE.
27. THROUGHOUT THE DURATION OF CONSTRUCTION, THE CONTRACTOR SHALL MAKE
EVERY EFFORT TO ENSURE THE BUILDING REMAIN IN DRIED-IN CONDITION AND
PREVENT UNLAWFUL ENTRY INTO THE CONSTRUCTION SITE.
28. CONTRACTOR TO PROVIDE FINAL CLEANING. THE OWNER RESERVES THE RIGHT TO
PROVIDE CLEANING SERVICES WHEN CLEAN-UP HAS NOT BEEN PROVIDED TO THE
SATISFACTION OF THE OWNER. ASSOCIATED COSTS WILL BE DEDUCTED FROM THE
CONTRACTOR'S FINAL PAYMENT.
29. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTING WITH AND
COORDINATION OF MATERIALS TESTING AS PART OF QUALITY ASSURANCE. THE
TESTING AGENCY IS TO COPY THE OWNER AND THE ARCHITECT ON ALL REPORTS.
30. THE CONTRACTOR'S CONSTRUCTION SCHEDULE SHALL BE IN THE FORM OF A CPM
TYPE SCHEDULE USING PRIMAVERA SOFTWARE (P3 OR SURETRACK). A LINEAR BAR
CHART SCHEDULE MAY BE ACCEPTABLE FOR SHORT DURATION PROJECTS AT THE
OWNER'S DISCRETION.
31. ALL MATERIAL SAFETY DATA SHEETS ON ANY HAZARDOUS PRODUCT SHALL BE KEPT
ON FILE AT JOBSITE, AND INCLUDED IN CLOSE-OUT DOCUMENTATION.
32. CONTRACTOR IS TO PROVIDE A PROJECT CONSTRUCTION SIGN OF
WATER-RESISTANT CONSTRUCTION. COPY AND DESIGN OF THE CONSTRUCTION SIGN
SHALL BE REVIEWED AND APPROVED BY THE OWNER'S REPRESENTATIVE AND
ARCHITECT. NO OTHER MARKETING SIGNAGE WILL BE PERMITTED.
33. FINAL SUBMITTAL SHALL INCLUDE TWO PRINTED COPIES AND ONE ELECTRONIC COPY
OF THE OPERATION AND MAINTENANCE DATA BINDERS FOR THE OWNER'S USE THAT
NOTES CONTRACTOR LISTINGS, PRODUCTS, AND WARRANTY INFORMATION.
34. ALL SHELVING, CABINETRY AND CASEWORK SHALL HAVE 2x WOOD BLOCKING AND/OR
PLYWOOD BACKER BOARD SUPPORT AS REQUIRED
35. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING LADDERS OR OTHER MEANS OF
ACCESS TO THE AUTHORITY HAVING JURISDICTION (AHJ), ARCHITECT, ENGINEER,
AND OWNER FOR REQUIRED OBSERVATIONS AND INSPECTIONS.
36. THE QUANTITY OF SUBMITTALS THAT WILL BE REQUIRED FOR THE PROJECT
INCLUDING THE NUMBER OF SAMPLES, PRODUCT DATA AND SHOP DRAWINGS
REQUIRED TO BE DETERMINED.
37. ALL EXITS SHALL COMPLY WITH FLORIDA ACCESSIBILITY CODE FOR LEVEL ENTRY;
SEE FBC, ACCESSIBILITY, SECTION 303; CHANGES IN LEVEL.
38. CONTRACTORS SHALL INCLUDE FOUR PRINTED COPIES OF THE RECORD DRAWINGS
ALONG WITH ONE ELECTRONIC AUTOCAD COPY WITH CLOSE-OUT DOCUMENTATION.
39. CONSTRUCTION OF WORK INDICATED ON THE DRAWINGS AS (N.I.C.) IS NOT IN
CONTRACT.
40. ALL WORK SHALL BE OF BEST PRACTICE OF EACH TRADE.
41. WHERE GYPSUM BOARD LAYERS DIFFER BETWEEN TWO ADJOINING WALLS, MAINTAIN
A CONTINUOUS FINISH OF WALL.
42. ELECTROLYTIC PROTECTION SHALL BE PROVIDED BETWEEN DISSIMILAR METALS
WHENEVER THE TWO ARE IN CONTACT.
43. DETAILS NOT SHOWN ARE SIMILAR IN NATURE TO THOSE DETAILED. WHERE SPECIFIC
DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE DETERMINED, CONSULT
ENGINEER BEFORE PROCEEDING WITH THE WORK. TYPICAL DETAILS APPLY AT ALL
SIMILAR CONDITIONS WHETHER CROSS REFERENCED OR NOT.
44. OPEN EXTERIOR JOINTS AROUND WINDOW AND DOOR FRAMES, BETWEEN WALLS
AND FOUNDATIONS, BETWEEN WALL AND ROOF, BETWEEN WALL PANELS, AT
PENETRATIONS OF UTILITIES THROUGH THE BUILDING ENVELOPE SHALL BE SEALED
W/ BACKER ROD AND SEALANT IF REQUIRED, FLASHED OR WEATHER-STRIPPED AS
REQUIRED FOR COMPATIBILITY WITH ADJACENT MATERIALS TO ELIMINATE AIR
LEAKAGE AND WATER INFILTRATION, AND TO MEET THE REQUIREMENTS OF THE
FLORIDA MODEL ENERGY CODE AS APPLICABLE.
45. PROVIDE PROPER ANCHORAGE OF ESSENTIAL EQUIPMENT IN ACCORDANCE WITH
APPLICABLE CODES. WOOD BLOCKING IN CONTACT WITH CONCRETE OR MASONRY
SHALL BE PRESSURE TREATED.
46. CONTRACTOR TO INCLUDE FOUR PRINTED COPIES OF THE RECORD DRAWINGS
ALONG WITH ONE ELECTRONIC COPY ON CD ROM.
47. PROVIDE ACCESS PANELS FOR MECHANICAL AND ELECTRICAL EQUIPMENT AS
REQUIRED BY APPLICABLE CODES.
48. PROVIDE AND INSTALL ALL STIFFENERS, BRACINGS, BACK-UP PLATES AND
SUPPORTING BRACKETS REQUIRED FOR THE BEST POSSIBLE INSTALLATION AND
REQUIRED MINIMUM LATERAL FORCE OF ALL PARTITIONS AND ALL WALL MOUNTED
OR SUSPENDED MECHANICAL, ELECTRICAL OR MISCELLANEOUS EQUIPMENT IN
ACCORDANCE WITH APPLICABLE CODES.
49. CEILING HEIGHT DIMENSIONS ARE FROM DESIGNATED FINISHED FLOOR SURFACE TO
FINISHED CEILING SURFACES UNLESS NOTED OTHERWISE.
50. LIGHT FIXTURE COLOR SELECTIONS SHALL BE BY THE ARCHITECT, AND EXPRESSLY
RECEIVED IN WRITING FROM THE ARCHITECT. APPROVAL OF SUBMITTALS BY THE
ELECTRICAL ENGINEER IS NOT AN APPROVAL OF THE LIGHT FIXTURE COLOR
SELECTION.
51. THESE DRAWINGS, SPECIFICATIONS, AND ANY ADDENDA SHALL BE THE BASIS FOR
THE CONTRACT FOR CONSTRUCTION BETWEEN THE GENERAL CONTRACTOR AND
THE OWNER. THE RESPONSIBILITIES OF THE OWNER, ARCHITECT, AND GENERAL
CONTRACTOR SHALL BE AS DESCRIBED IN AIA DOCUMENT A201-2017 - GENERAL
CONDITIONS OF THE CONTRACT FOR CONSTRUCTION.
52. PROJECT TO BE COMPLIANT WITH ICD 705 AND TEMPEST RECOMMENDATIONS.
MISCELLANEOUS SPECIFICATIONS
DIVISION 6 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
PART 1 GENERAL
1.1 SUMMARY
A. SECTION INCLUDES:
1.FRAMING WITH DIMENSION LUMBER.
2.WOOD BLOCKING AND NAILERS.
1.2 ACTION SUBMITTALS
A. PRODUCT DATA: FOR EACH TYPE OF PROCESS AND FACTORY-FABRICATED PRODUCT.
1.INCLUDE DATA FOR WOOD-PRESERVATIVE TREATMENT FROM CHEMICAL TREATMENT MANUF. AND
CERTIFICATION BY TREATING PLANT THAT TREATED MATERIALS COMPLY WITH REQUIREMENTS
1.3 INFORMATIONAL SUBMITTALS
A. MATERIAL CERTIFICATES: FOR DIMENSION LUMBER SPECIFIED TO COMPLY WITH MINIMUM
ALLOWABLE UNIT STRESSES. INDICATE SPECIES AND GRADE SELECTED FOR EACH USE AND
DESIGN VALUES APPROVED BY THE ALSC BOARD OF REVIEW.
B. EVALUATION REPORTS: FOR THE FOLLOWING, FROM ICC-ES:
1.WOOD-PRESERVATIVE-TREATED WOOD.
2.POWER-DRIVEN FASTENERS.
3.POWDER-ACTUATED FASTENERS.
4. EXPANSION ANCHORS.
PART 2 PRODUCTS
2.1 WOOD-PRESERVATIVE-TREATED LUMBER
A. PRESERVATIVE TREATMENT BY PRESSURE PROCESS: AWPA U1; USE CATEGORY UC2 FOR INT.
CONSTRUCTION NOT IN CONTACT WITH THE GROUND, USE CATEGORY UC3B FOR EXT.
CONSTRUCTION NOT IN CONTACT WITH THE GROUND, AND USE CATEGORY UC4A FOR ITEMS IN
CONTACT W/ THE GROUND.
1.PRESERVATIVE CHEMICALS: ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION AND
CONTAINING NO ARSENIC OR CHROMIUM.
B. KILN-DRY LUMBER AFTER TREATMENT TO A MAXIMUM MOISTURE CONTENT OF 19 PERCENT. DO
NOT USE MATERIAL THAT IS WARPED OR THAT DOES NOT COMPLY W/ REQUIREMENTS FOR
UNTREATED MATERIAL.
C. MARK LUMBER WITH TREATMENT QUALITY MARK OF AN INSPECTION AGENCY APPROVED BY THE
ALSC BOARD OF REVIEW.
D. APPLICATION: TREAT ITEMS INDICATED ON DRAWINGS, AND THE FOLLOWING:
1.WOOD CANTS, NAILERS, CURBS, EQUIPMENT SUPPORT BASES, BLOCKING, STRIPPING, AND
SIMILAR MEMBERS IN CONNECTION WITH ROOFING, FLASHING, VAPOR BARRIERS, AND
WATERPROOFING.
2.5 FASTENERS
A. GENERAL: PROVIDE FASTENERS OF SIZE AND TYPE INDICATED THAT COMPLY WITH REQUIREMENTS
SPECIFIED IN THIS ARTICLE FOR MATERIAL AND MANUFACTURE.
1.WHERE ROUGH CARPENTRY IS EXPOSED TO WEATHER, IN GROUND CONTACT,
PRESSURE-PRESERVATIVE TREATED, OR IN AREA OF HIGH RELATIVE HUMIDITY, PROVIDE
FASTENERS WITH HOT-DIP ZINC COATING COMPLYING WITH ASTM A 153/A 153M.
B. POWER-DRIVEN FASTENERS: NES NER-272.
C. BOLTS: STEEL BOLTS COMPLYING WITH ASTM A 307, GRADE A; WITH ASTM A 563 HEX NUTS AND, WHERE INDICATED, FLAT WASHERS.
2.6 METAL FRAMING ANCHORS
A. BASIS-OF-DESIGN PRODUCT: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCT
INDICATED ON DRAWINGS OR COMPARABLE PRODUCT BY ONE OF THE FOLLOWING:
1.SIMPSON STRONG-TIE CO., INC.
2.OR EQUAL
B. ALLOWABLE DESIGN LOADS: PROVIDE PRODUCTS WITH ALLOWABLE DESIGN LOADS, AS PUBLISHED
BY MANUFACTURER, THAT MEET OR EXCEED THOSE OF BASIS-OF-DESIGN PRODUCTS.
MANUFACTURER'S PUBLISHED VALUES SHALL BE DETERMINED FROM EMPIRICAL DATA OR BY
RATIONAL ENGINEERING ANALYSIS AND DEMONSTRATED BY COMPREHENSIVE TESTING
PERFORMED BY A QUALIFIED INDEPENDENT TESTING AGENCY.
C. HOT-DIP, HEAVY-GALVANIZED STEEL SHEET: ASTM A 653/A 653M; STRUCTURAL STEEL (SS), HIGH-
STRENGTH LOW-ALLOY STEEL TYPE A (HSLAS TYPE A), OR HIGH-STRENGTH LOW-ALLOY STEEL
TYPE B (HSLAS TYPE B); G185 COATING DESIGNATION; AND NOT LESS THAN 0.036 INCH THICK.
1.USE FOR WOOD-PRESERVATIVE-TREATED LUMBER AND WHERE INDICATED.
PART 3 EXECUTION
3.1 INSTALLATION, GENERAL
A. SET ROUGH CARPENTRY TO REQUIRED LEVELS AND LINES, WITH MEMBERS PLUMB, TRUE TO LINE, CUT, AND FITTED. FIT ROUGH CARPENTRY TO OTHER CONSTRUCTION; SCRIBE AND COPE AS
NEEDED FOR ACCURATE FIT. LOCATE NAILERS, BLOCKING, AND SIMILAR SUPPORTS TO COMPLY
WITH REQUIREMENTS FOR ATTACHING OTHER CONSTRUCTION.
B. FRAMING STANDARD: COMPLY WITH AF&PA'S WCD 1, "DETAILS FOR CONVENTIONAL WOOD FRAME
CONSTRUCTION," UNLESS OTHERWISE INDICATED.
C. COMPLY WITH AWPA M4 FOR APPLYING FIELD TREATMENT TO CUT SURFACES OF
PRESERVATIVE-TREATED LUMBER.
D. WHERE WOOD-PRESERVATIVE-TREATED LUMBER IS INSTALLED ADJACENT TO METAL DECKING, INSTALL CONTINUOUS FLEXIBLE FLASHING SEPARATOR BETWEEN WOOD AND METAL DECKING.
DIVISION 7 - THERMAL PROTECTION
07 62 00 SHEET METAL FLASHING AND TRIM
1.METAL FLASHINGS: FURNISH AND INSTALL 0.0400" ALUMINUM OR 22 GAUGE STAINLESS STEEL
FLASHING MATERIALS WHERE NOTED OR DETAILED OR REQUIRED TO PROVIDE LEAK-FREE
TRANSITION OF MATERIALS.
2.FLASHING GAUGE AND ATTACHMENT SHALL COMPLY WITH FBC (LATEST EDITION) TEST PROTOCOL
MANUAL (RAS-111).
DIVISION 9 - FINISHES
09 21 16 INTERIOR FRAME WALLS
A. INSTALLATION OF GYPSUM WALL BOARD ASSEMBLIES AND PLASTERING PER ASTM C 840 & GA-216.
B. PRODUCTS FOR NON-LOAD BEARING PARTITION WALLS SHALL BE METAL FRAMING AS
MANUFACTURED BE CLARK DIETRICH OR APPROVED EQUAL.
C. FURNISH AND INSTALL NEW LIGHT GAUGE METAL FRAMING AS INDICATED ON PARTITION TYPES.
D. FURNISH AND INSTALL 5/8" THICK STANDARD, MOISTURE RESISTANT, FIRE RATED (TYPE X) OR
ABUSIVE RESISTANT GYPSUM WALLBOARD AND ACCESSORIES AS DETAILED AND REQUIRED TO
PROVIDE A COMPLETED WORK PRODUCT INCLUDING CORNER BEADS, 'J' BEAD EDGES, ETC.
E. TAPE AND MUD TO RECEIVE A LEVEL 4 FINISH FOR PAINTED GYPSUM WALLS.
09 65 13 VINYL WALL BASE
A. MANUFACTURERS: PROVIDE VINYL BASE AND ACCESSORIES AS PRODUCED BY A SINGLE
MANUFACTURER, INCLUDING RECOMMENDED PRIMERS, ADHESIVES, AND SEALANTS.
B. PROVIDE VINYL BASE COMPLYING WITH FS SS-W-40, TYPE II, WITH FILED FORMED CORNERS AND AS
FOLLOWS:
1.HEIGHT: 4" (UNLESS NOTED OTHERWISE)
2.THICKNESS: 1/8"
3.STYLE: STANDARD FIELD CUT CORNERS.
4. FINISH: MATTE
5.COLOR: TO BE SELECTED BY OWNER FROM MANUFACTURER'S STANDARD RANGE.
MANUFACTURERS WITH A LIMITED COLOR RANGE MAY BE SUBJECT TO REJECTION.
C. ADHESIVES (CEMENTS): WATERPROOF, STABILIZED TYPE AS RECOMMENDED BY FLOORING
MANUFACTURER TO SUIT MATERIAL AND SUBSTRATE CONDITIONS.
D. INSTALLATION: CLEAN ALL SURFACES AS RECOMMENDED BY VINYL BASE MANUFACTURER AND FILL
SMALL CRACKS, HOLES, AND DEPRESSIONS IN WALLS.
1.INSTALL VINYL BASE USING METHOD INDICATED IN STRICT COMPLIANCE WITH MANUFACTURER'S
PRINTED INSTRUCTIONS. EXTEND VINYL BASE INTO TOE SPACES, CLOSETS AND SIMILAR
OPENINGS. USE FIELD CUT CORNERS THROUGHOUT.
2.ADHERE TO WALL SUBSTRATES USING FULL SPREAD OF ADHESIVE APPLIED IN COMPLIANCE WITH
MANUFACTURER'S DIRECTIONS.
3.IN APPLICATIONS WHERE NO FLOOR BASE IS TO BE INSTALLED, PROVIDE A 1/8" UNIFORM BEAD OF
TRAFFIC RESISTANT CAULK/SEALANT ALONG THE PERIMETER OF THE INSTALLATION.
DIVISION 10 - SPECIALTIES
10 44 16 FIRE EXTINGUISHERS
A. PROVIDE THE FOLLOWING NEW EXTINGUISHERS, BRACKETS THROUGHOUT PROJECT WHERE
IDENTIFIED ON THE LIFE SAFETY PLAN.
B. BASIS OF DESIGN SHALL BE J.L. INDUSTRIES, 10 POUND, 2A:10B:C FOR MULTI-PURPOSE USE, CLASS A, B, AND C FIRES.
C. NEW BRACKETS SHALL BE A STRAP HELD LEDGER TYPE HANGER.
MISCELLANEOUS SPECIFICATIONS CONT.
6" MAX.8" MIN.
17" - 19"
48" MIN.
" M
IN
9" M
IN
" M
IN
" M
AX
5" MIN. 15" MIN.
(N)
10" MAX.
" M
AX
" M
AX
" M
AX
" M
AX
> 10"-24" MAX.
(A) (B)
10" MAX.
" M
AX
" M
IN
" M
AX
" M
AX
>20"-25" MAX.20" MAX.
(A) (B)
" M
IN
" M
AX
OBSTRUCTED HIGH SIDE REACH UNOBSTRUCTED
SIDE REACH
UNOBSTRUCTED
FORWARD REACH
OBSTRUCTED HIGH FORWARD REACH
(B)
PLAN
" M
IN
25" MAX.
11" MIN.
" M
IN
8" MIN.
9" MIN.
(A)
ELEVATION
6" MIN.
KNEE AND TOE CLEARANCE
(C)
(C)
RETURN RAILING TO WALL
SWITCHES / THERMOSTAT
RECEPTACLE
HOT WATER SUPPLY & DRAIN LINES SHALL BE FULLY
INSULATED OR COVERED W/ A REMOVABLE,
NON-METALLIC BAFFLE WHEN HOT WATER TEMP.
FLOOR LINE
DIRECTION OF TRAVEL
(30" C.F.S. PERP.
TO WALL)
48" MIN. CLEAR
VISIBLE HALL SIGNALS
MIN.
3'-0"
MIN.
2'-8"
(B)
T-SHAPED SPACE FOR 180° TURNS
30° MAX
RADIUS 1/2"
MAX.
(A)
RADIUS OF TREAD EDGE
(TYP. FOR ALL PROFILES)
1 1/2" MAX.
(B)
ANGLED RISER
1 1/2" MAX.
CL
(C)
CURVED NOSING
STAIR
PROTECT SHADED AREA
FROM CROSS
TRAFFIC
(D)
BEVELED NOSING
CL
B
A
CL
MIN.
2'-8"
MIN.
3'-0"
CANE DETECTION
AREA
6" 8"
17" MIN.
48" MIN. CLEAR
60" MIN.
(A)
60 INCH
DIAMETER
SPACE
12" MIN. 36" MIN.
SHADED AREA DENOTES KNEE & TOE
SPACE REQ'D. @ ACCESSIBLE LAV.
DIRECTION OF TRAVEL
FLOOR LINE
DASHED LINE DENOTES MAX. SIZE OF
MOUNTING BRACKETS FROM REMOVABLE
PROTECTION & APPEARANCCE PANEL
MIRROR
32" MIN.
FOLDING DOOR
32" MIN.
32" MIN.
4'-0"
2'-6"
(A)
WALL HUNG URINAL
GRAB BAR CROSS SECTION
(A) (B)
HINGED DOOR
12" MIN.
1 1/2" MIN.
12" MIN.
X X
12" MIN.
POCKET DOOR
2" MAX
13 1/2" MIN.
(A)
HANDRAILS & GRAB BARS
SIZING & SPACING
DIRECTION OF TRAVEL
DIRECTION
OF TRAVEL DIRECTION
OF TRAVEL
18" MIN.
36" MIN. 42" MIN. 24" MIN. 24" MIN.
DIRECTION
OF TRAVEL
DIRECTION
OF TRAVEL
6" MAX.
27" MAX.
CAN BE LOCATED ON ANY
WALL OF SHOWER
BACK WALL
27" MAX.
15" MAX.
5'-0"
15" MAX.
SIDE
WALL
BACK WALL
FRONT WALL
(A)
FRONT APPROACH, PULL SIDE
(B)
HINGE APPROACH, PULL SIDE
(C)
HINGE APPROACH, PULL SIDE
(D)
LATCH APPROACH, PULL SIDE
(E)
LATCH APPROACH, PULL SIDE
DOOR PROVIDED W/ CLOSER
(A)
WITHOUT SEAT
STANDARD ROLL-IN SHOWER
CONTROL LOCATION
DIRECTION OF TRAVEL
DIRECTION
OF TRAVEL
22" MIN. 22" MIN.
DIRECTION
OF TRAVEL
DIRECTION OF TRAVEL
DIRECTION
OF TRAVEL
12" MIN. 24" MIN.
0' - 2 1/2"
(F)
HINGE APPROACH, PUSH SIDE
(G)
HINGE APPROACH, PUSH SIDE
DOOR PROVIDED W/ BOTH CLOSER & LATCH
(H)
FRONT APPROACH, PUSH SIDE
(I)
FRONT APPROACH, PUSH SIDE
DOOR PROVIDED W/ BOTH CLOSER & LATCH
(G)
W SEAT/ GRAB BARS
(F)
TRANSFER TYPE SHOWER
CONTROL LOCATION
SIZE & CLEARANCE
(J)
LATCH APPROACH, PUSH SIDE
15" TO 16" MAX
60" MIN.
48" MIN.
(H)
SIZE & CLEARANCE
FRONT WALL
(I)
WITHOUT SEAT
ALTERNATE ROLL-IN SHOWER
CONTROL LOCATION
ACCESSIBLE 2'-3"
(J)
WITHOUT SEAT
GRAB BARS
SIDE
WALL
15" MAX. 36" MIN.
RANGE FOR
CONTROL
AREA
(B)
W/ SEAT
STANDARD ROLL-IN SHOWER
CONTROL LOCATION
6"
BACK WALL
1'-6"
60" HOSE
(C)
W/ SEAT
ALTERNATE ROLL-IN SHOWER
CONTROL LOCATION
BACK WALL
BACK WALL 6" MAX.
BACK WALL
6" MAX.
(D)
W/ SEAT
ALTERNATE ROLL-IN SHOWER
CONTROL LOCATION
3'-0" (E)
W SEAT/ GRAB BARS
ALTERNATE ROLL-IN SHOWER
CONTROL LOCATION
NOTE: INSIDE FINISHED DIMENSIONS MEASURED
AT THE CENTER POINTS OF OPPOSING SIDES.
SIZE & CLEARANCE
NON-ACCESSIBLE
SIDE WALL
RANGE FOR
CONTROL
AREA
6" MAX. CLEAR
(B)
STAIR HANDRAIL AT
BOTTOM
(C)
STAIR HANDRAIL AT TOP
(D)
RAMP HANDRAIL EXTENSIONS
" M
IN
" M
IN
1' -3
" M
AX
TO
P
O F
SW
IT
C H
M
AX
2'
-0
M
AX
4'
-0
M
AX
2'
-0
1/
2" M
IN
" M
IN
" M
IN
1/
2" M
IN
" M
IN
" M
IN
" M
IN
" M
IN
" M
AX
" M
IN
" M
IN
" M
IN
" M
IN
2' -6
" M
AX
" M
IN
4' -0
" M
IN
BA
C
K W
AL
L
" M
AX
9" M
IN
1/
2" M
IN
" M
IN
" M
AX
" M
AX
6"
SI
D E
W
AL
L
" M
IN
" M
IN
" M
AX
" M
AX
" T
.O . H
AN
D
R
AI
L
" M
AX
X
SI
D
E W
AL
L
" M
IN
0'
1/
2" M
AX
" M
AX
" M
AX
SE
AT
W
AL
L
C O
N
TR
O L
W
AL
L
" M
IN
" M
IN
5"
" T
.O . H
AN
D
R
AI
L
" 72
" M
IN
" M
AX
SI
D
E W
AL
L 6" M
AX
SI
D
E W
AL
L
SI
D
E W
AL
L
6" M
AX
SI
D
E W
AL
L
3' -0
SI
D
E W
AL
L
SI
D
E W
AL
L
6" M
AX
2' -6
1' -7
1' -6
" 38 " M
IN
" M
AX
. 6'
-6
" M
IN
" M
AX
.8"
.0°
2" M
AX
Ø 1 1/4" - 1 1/2"
NOTE: FBC 505.10.3 AT THE
BOTTOM OF A STAIR FLIGHT,
HANDRAILS EXTEND AT THE
SLOPE OF THE STAIR FLIGHT
FOR A HORIZONTAL
DISTANCE AT LEAST EQUAL
TO ONE TREAD DEPTH
BEYOND THE LAST RISER
NOSING.
NOTE: Y = MIN. HANDRAIL EXTENSION
OF 12" PLUS THE WIDTH OF ONE TREAD
THAT IS REQUIRED AT THE BOTTOM
RISER.
NOTE: INSIDE FINISHED DIMENSIONS
MEASURED AT THE CENTER POINTS OF
OPPOSING SIDES.
NOTE: PER FBC 1009.4.2., STAIR RISER HEIGHTS
SHALL BE 7" MAXIMUM & 4" MINIMUM. THE RISER
SHALL BE MEASURED VERTICALLY BETWEEN THE
LEADING EDGES OF ADJACENT TREADS.
RECTANGULAR TREAD DEPTHS SHALL BE 11" MIN. (12"
BBA STANDARD) MEASURED HORIZONTALLY
BETWEEN THE VERTICAL PLANES OF THE FOREMOST
PROJECTION OF ADJACENT TREADS & AT A RIGHT
ANGLE TO THE TREAD'S LEADING EDGE.
MANEUVERING CLEARANCE AT DOORS AND GATES
4" MAX
M
IN
. 2 7"
M
IN
. 8 0"
48" MIN. 48" MIN. 48" MIN.
(K) (L) (M)
HI-LO DRINKING FOUNTAIN
(SURFACE MOUNTED)
42" SPOUT
HEIGHT
36" SPOUT
HEIGHT
8" MIN.
11" MIN.
ELEVATION
" M
IN
9" M
IN
ADA ACCESSIBILITY GUIDELINES 3
SHOWERS
HANDRAILS DETAILS
STAIR DETAILS
EXCEEDS 120° F.
ALL WORK SHALL COMPLY WITH THE AMERICANS WITH DISABILITIES ACT (2010), THE
CURRENT VERSION OF FLORIDA BUILDING CODE - ACCESSIBILITY, AND LOCAL ACCESSIBILITY
REGULATIONS TO INCLUDE BUT NOT LIMITED TO THE FOLLOWING:
1. THE INTERNATIONAL SYMBOL FOR ACCESSIBILITY SHALL BE LOCATED ALONGSIDE THE
DOOR AT THE LATCH SIDE OF ALL ACCESSIBLE RESTROOM FACILITIES.
2. WATER CLOSETS SHALL BE POSITIONED WITH A WALL OR PARTITION TO THE REAR AND
ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO
18 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION. THE SEAT HEIGHT OF A
WATER CLOSET ABOVE THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19
INCHES MAXIMUM MEASURED FROM THE TOP OF THE SEAT. SEATS SHALL NOT BE
SPRUNG TO RETURN TO A LIFTED POSITION.
3. ACCESSIBLE URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG TYPE WITH THE
RIM 17 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. URINALS SHALL BE
13-1/2 INCHES DEEP MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM
TO THE BACK OF THE FIXTURE. PROVIDE A CLEAR FLOOR SPACE 30" X 48" IN FRONT OF
THE ACCESSIBLE URINAL.
4. LAVATORIES SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR WITH A
CLEARANCE OF 29" FROM THE FLOOR TO THE BOTTOM OF THE APRON. SPACE UNDER
A LAVATORY BETWEEN 9 INCHES AND 27 INCHES ABOVE THE FINISH FLOOR OR
GROUND SHALL BE CONSIDERED KNEE CLEARANCE. KNEE CLEARANCE SHALL EXTEND
25 INCHES MAXIMUM UNDER AN ELEMENT AT 9 INCHES ABOVE THE FINISH FLOOR AND 8
INCHES DEEP MINIMUM AT 27 INCHES ABOVE THE FINISH FLOOR. SPACE UNDER A
LAVATORY BETWEEN THE FINISH FLOOR OR GROUND AND 9 INCHES ABOVE THE FINISH
FLOOR OR GROUND SHALL BE CONSIDERED TOE CLEARANCE. TO CLEARANCE SHALL
EXTEND 25 INCHES MAXIMUM AND 17 INCHES MINIMUM UNDER A LAVATORY. KNEE
CLEARANCE SHALL BE 30 INCHES WIDE MINIMUM.
5. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE INSULATED
OR OTHERWISE CONFIGURED TO PROTECT AGAINST CONTACT. THERE SHALL BE NO
SHARP OR ABRASIVE SURFACES UNDER LAVATORIES AND SINKS.
6. CONTROLS FOR FAUCETS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT
REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
HAND-OPERATED METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS
MINIMUM.
7. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
THE BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
SURFACE 35 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
8. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED
FOR ANY FIXTURE. DOORS SHALL BE PERMITTED TO SWING INTO THE REQUIRED
TURNING SPACE.
9. GRAB BARS SHALL BE INSTALL IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
SURFACE. GRAB BARS AND ANY WALL OR OTHER SURFACES ADJACENT TO GRAB BARS
SHALL BE FREE OF SHARP OR ABRASIVE ELEMENTS AND SHALL HAVE ROUNDED
EDGES. GRAB BARS SHALL NOTE ROTATE WITHIN THEIR FITTINGS. ALLOWABLE
STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN A VERTICAL OR
HORIZONTAL FORCE OF 250 POUNDS IS APPLIED AT ANY POINT ON THE GRAB BAR,
FASTENER, MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
10. DRINKING FOUNTAINS SHALL BE PROVIDED WITH SPOUT OUTLETS AT 36 INCHES
MAXIMUM ABOVE THE FINISH FLOOR AND 38 INCHES MINIMUM AND 43 INCHES MAXIMUM
ABOVE THE FINISH FLOOR OR GROUND. THE SPOUT SHALL BE LOCATED 15 INCHES
MINIMUM FROM THE VERTICAL SUPPORT AND 5 INCHES MAXIMUM FROM THE FRONT
EDGE OF THE UNIT, INCLUDING BUMPERS. THE SPOUT SHALL PROVIDE A FLOW OF
WATER 4 INCHES HIGH MINIMUM AND SHALL BE LOCATED 5 INCHES MAXIMUM FROM
THE FRONT OF THE UNIT. THE ANGLE OF THE WATER STREAM SHALL BE MEASURED
HORIZONTALLY RELATIVE TO THE FRONT FACE OF THE UNIT. WHERE SPOUTS ARE
LOCATED LESS THAN 3 INCHES OF THE FRONT OF THE UNIT, THE ANGLE OF THE WATER
STREAM SHALL BE 30 DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED BETWEEN 3
INCHES AND 5 INCHES MAXIMUM FROM THE FRONT OF THE UNIT, THE ANGLE OF THE
WATER STREAM SHALL BE 15 DEGREES MAXIMUM.
11. DOOR CLOSERS SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 90
DEGREES, THE TIME REQUIRED TO MOVE THE DOOR TO A POSITION OF 12 DEGREES
FROM THE LATCH IS 5 SECONDS MINIMUM.
12. FIRE DOORS SHALL HAVE A MINIMUM OPENING FORCE ALLOWABLE BY THE
APPROPRIATE ADMINISTRATIVE AUTHORITY. THE FORCE FOR PUSHING OR PULLING
OPEN A DOOR OR GATE OTHER THAN FIRE DOORS SHALL BE 5 POUNDS MAXIMUM.
THESE FORCES DO NOT APPLY TO THE FORCE REQUIRED TO RETRACT LATCH BOLTS
OR DISENGAGE OTHER DEVICES THAT HOLD THE DOOR OR GATE IN A CLOSED
POSITION.
13. FIRE ALARM SYSTEMS SHALL HAVE PERMANENTLY INSTALLED AUDIBLE AND VISIBLE
ALARMS COMPLYING WITH NFPA 72 AND ANSI A117.1, EXCEPT THAT THE MAXIMUM
ALLOWABLE SOUND LEVEL OF AUDIBLE NOTIFICATION APPLIANCES COMPLYING WITH
SECTION 4-3.2.1 OF NFPA 72 (1999 EDITION) SHALL HAVE A SOUND LEVEL NO MORE
THAN 110 DB AT THE MINIMUM HEARING DISTANCE FROM THE AUDIBLE APPLIANCE.
14. FLOOR AND GROUND SURFACES SHALL BE STABLE, FIRM, AND SLIP RESISTANT.
CHANGES IN LEVEL OF 1/4 INCH HIGH MAXIMUM SHALL BE PERMITTED TO BE VERTICAL.
CHANGES IN LEVEL BETWEEN 1/4 INCH HIGH MINIMUM AND 1/2 INCH HIGH MAXIMUM
SHALL BE BEVELED WITH A SLOPE NOT STEEPER THAN 1:2.
15. FLOOR OR GROUND SURFACE WITHIN REQUIRED MANEUVERING CLEARANCES AT
DOORS SHALL COMPLY WITH NOTE 15. CHANGES IN LEVEL ARE NOT PERMITTED, WITH
THE FOLLOWING EXCEPTIONS:
A. SLOPES NOT STEEPER THAN 1:48 SHALL BE PERMITTED.
B. CHANGES IN LEVEL AT THRESHOLDS COMPLYING WITH NOTE 16 SHALL BE
PERMITTED.
16. THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH HIGH MAXIMUM.
ACCESSIBILITY NOTES
Tsark Architecture, LLC 1600 Sarno Rd., Suite 212
Melbourne, FL 32935
(321) 241-6378
Lic #: AA26003779
REVIEW SET
Shad L. Traylor
AR 93039
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
REVISIONS
4083 South U.S. Highway 1, Ste. 101 Rockledge, Florida 32955 Phone 321.633.4522 Fax 321.633.4528 www.ddc-engineers.com dasilva.david@ddc-engineers.com C.O.A.: 25988
DDC PROJECT NO.:
2026 by Tsark Architecture, LLC All rights reserved. No part of this work covered by the copyright hereon may be reproduced or used in any form or by any means - graphic, electronic or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without written permission of the copyright holder.ãCOPYRIGHT
26625A
DESCRIPTIONNO. DATE
26030.01
AUGUST 10, 2026
M
EL
BO
UR
NE
O
RL
AN
DO
IN
TE
RN
AT
IO
NA
L
AI
RP
OR
T
TE
RM
IN
AL
M
EP
/H
VA
C
RE
NO
VA
TI
ON
S
AI
R
TE
RM
IN
AL
P
AR
KW
AY
, M
EL
BO
UR
NE
, F
L
CL
IE
NT
P
RO
JE
CT
: 5
BID SET
NOT FOR
CONSTRUCTION
G003
CW
ST
ST
AC
CE
SS
IB
IL
IT
Y
1 3
B
2 4
A
1H R
1H R
1H R
1H R
1H R
1H R
1H R
1HR 1HR 1HR 1HR 1HR 1HR 1HR 1HR 1HR
1HR 1HR 1HR 1HR 1HR
1HR
1HR
1HR
1HR
1HR
1H R
1H R
1H R
TR
AV
EL
D
IS
TA
N C
E:
0' -0
F.E
FD
CO
FDFD
FD
CO
REMOVE AND
REPLACE
LIFE SAFETY PLAN LEGEND
EXISTING CONSTRUCTION TO REMAIN
NEW CMU CONSTRUCTION
1-HOUR FIRE RATING
PRIMARY EXIT OR EXIT ACCESS
INDICATES EXIT ACCESS TRAVEL DISTANCE (FEET)
INDICATES EXIT SIGN (REFERENCE ELECTRICAL)
INDICATES EMERGENCY LIGHTS (REFERENCE ELECTRICAL)
1HR
Tsark Architecture, LLC 1600 Sarno Rd., Suite 212
Melbourne, FL 32935
(321) 241-6378
Lic #: AA26003779
REVIEW SET
Shad L. Traylor
AR 93039
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
REVISIONS
4083 South U.S. Highway 1, Ste. 101 Rockledge, Florida 32955 Phone 321.633.4522 Fax 321.633.4528 www.ddc-engineers.com dasilva.david@ddc-engineers.com C.O.A.: 25988
DDC PROJECT NO.:
2026 by Tsark Architecture, LLC All rights reserved. No part of this work covered by the copyright hereon may be reproduced or used in any form or by any means - graphic, electronic or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without written permission of the copyright holder.ãCOPYRIGHT
26625A
DESCRIPTIONNO. DATE
26030.01
AUGUST 10, 2026
M
EL
BO
UR
NE
O
RL
AN
DO
IN
TE
RN
AT
IO
NA
L
AI
RP
OR
T
TE
RM
IN
AL
M
EP
/H
VA
C
RE
NO
VA
TI
ON
S
AI
R
TE
RM
IN
AL
P
AR
KW
AY
, M
EL
BO
UR
NE
, F
L
CL
IE
NT
P
RO
JE
CT
: 5
BID SET
NOT FOR
CONSTRUCTION
ST
ST
CW
A100
LI
FE
S
AF
ET
Y
1/4" = 1'-0"
80 16
LIFE SAFETY PLAN1
D101
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
EXISTING JOCKEY PUMP
AutoCAD SHX Text
JOCKEY PUMP
AutoCAD SHX Text
EXISTING DIESEL FIRE PUMP
AutoCAD SHX Text
CONTROLLER
AutoCAD SHX Text
FIRE PUMP
AutoCAD SHX Text
CONTROLLER
AutoCAD SHX Text
DECOMMISSIONED U.G. SUPPLY LINE
AutoCAD SHX Text
TO EXISTING SYSTEMS
AutoCAD SHX Text
EXISTING BATTERY PACK
AutoCAD SHX Text
4" TO F.D.C.
AutoCAD SHX Text
8" PRESSURE RELIEF VALVE DRAIN ASSEMBLY
AutoCAD SHX Text
6" TO PUMP TEST HEADER
AutoCAD SHX Text
EXISTING 8" FIRE SUPPLY U.G.
AutoCAD SHX Text
EXISTING PRESSURE RELIEF VALVE
AutoCAD SHX Text
EXISTING O.S.&Y
AutoCAD SHX Text
DECOMMISSIONED U.G. SUPPLY LINE
AutoCAD SHX Text
FUEL SUPPLY LINE
AutoCAD SHX Text
FUEL RETURN LINE
AutoCAD SHX Text
4" VENT
AutoCAD SHX Text
EXIT
AutoCAD SHX Text
EXIT
EXIT
AREA OF SLAB
TO REMAIN
REMOVE AND
REPLACE
EXISTING DOOR
Tsark Architecture, LLC 1600 Sarno Rd., Suite 212
Melbourne, FL 32935
(321) 241-6378
Lic #: AA26003779
REVIEW SET
Shad L. Traylor
AR 93039
DATE
PERMIT SET
BID SET
CONSTRUCTION SET
AS BUILT
APPROVED:
SHEET NO.:
CHECKED:
DRAWN:
REVISIONS
4083 South U.S. Highway 1, Ste. 101 Rockledge, Florida 32955 Phone 321.633.4522 Fax 321.633.4528 www.ddc-engineers.com dasilva.david@ddc-engineers.com C.O.A.: 25988
DDC PROJECT NO.:
2026 by Tsark Architecture, LLC All rights reserved. No part of this work covered by the copyright hereon may be reproduced or used in any form or by any means - graphic, electronic or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without written permission of the copyright holder.ãCOPYRIGHT
26625A
DESCRIPTIONNO. DATE
26030.01
AUGUST 10, 2026
M
EL
BO
UR
NE
O
RL
AN
DO
IN
TE
RN
AT
IO
NA
L
AI
RP
OR
T
TE
RM
IN
AL
M
EP
/H
VA
C
RE
NO
VA
TI
ON
S
AI
R
TE
RM
IN
AL
P
AR
KW
AY
, M
EL
BO
UR
NE
, F
L
CL
IE
NT
P
RO
JE
CT
: 5
BID SET
NOT FOR
CONSTRUCTION
ST
ST
CW
D101
KEY PLAN
N.T.S.4
1/4" = 1'-0"
80 16
FIRST FLOOR DEMOLITION PLAN1
D101
DEMOLITION LEGEND
EXISTING CONSTRUCTION TO REMAIN
CONSTRUCTION TO BE REMOVED
DEMOLITION KEYNOTES
GENERAL NOTES
1. REFER TO BALANCE OF DRAWINGS FOR DETAILED DEMOLITION WORK NOT SHOWN ON
DEMOLITION PLANS.
2. DEMOLITION WORK SHOWN INDICATES MINIMUM OF WORK TO BE PERFORMED TO
ACCOMMODATE NEW CONSTRUCTION. COORDINATE LIMITS OF DEMOLITION WORK WITH
SCOPE OF NEW CONSTRUCTION.
3. PROVIDE DEMOLITION OF ITEMS REQUIRED TO FACILITATE NEW CONSTRUCTION.
4. REMOVE EXISTING WALLS AND PARTITIONS, WHERE INDICATED, IN THEIR ENTIRETY,
INCLUDING INCORPORATED DOORS, WINDOWS, BRACING, ACCESSORIES, ETC. AND
ATTACHED MISCELLANEOUS SIGNAGE, PLAQUES, CLOCKS, ETC.
5. REMOVE EXISTING DOORS, WINDOWS AND FRAMES, WHERE INDICATED, IN THEIR
ENTIRETY, INCLUDING ANCHORS AND ASSOCIATED HARDWARE. SEE SCHEDULE OF
OPENINGS FOR DOORS AND WINDOWS TO BE MODIFIED AND/OR RELOCATED.
6. SEE MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR SPECIFIC DEMOLITION
REQUIREMENTS RELATING TO THOSE TRADES.
7. PATCH AND REPAIR EXISTING CONSTRUCTION…
This is the start of the file's text. The full file is on GovTribe.