260553 Identification for Electrical Systems Specifications.pdf

PDF 291 KB Posted

Attached to
ITB-SMCPS-2024-M-EGLHS - Emergency Generator Replacement at Leonardtown High School
Solicitation number
BPM039704
Issued by
St. Mary's County, La Plata Town, Maryland

About this file

This document is a solicitation for bids (ITB-SMCPS-2024-M-EGLHS) issued by the Board of Education of St. Mary's County on behalf of St. Mary's County Public Schools (SMCPS) for the emergency generator replacement at Leonardtown High School located in Leonardtown, Maryland. The project requires the supply and installation of a new emergency generator and automatic transfer switch to replace the existing generator installed in 1999. The work must be substantially completed by August 15, 2025, and the resulting contract will be awarded for 60 days after receipt of the generator from the manufacturer.

The solicitation does not provide details on pricing terms, set asides, incumbents, funding requirements and sources, or other salient commercial information. Contractors will be responsible for complying with all applicable laws and regulations of authorities having jurisdiction while meeting the project specifications and requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Spring Ridge Middle School Renovation and Addition IDENTIFICATION FOR ELECTRICAL SYSTEMS Renovation and Addition – 201305.1 260553 - 1 January 31, 2014 (FINAL BID DOC’S)

SECTION 260553 – IDENTIFICATION FOR ELECTRICAL SYSTEMS

PART 1 – GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Identification for raceways.

2. Identification of power and control cables.

3. Identification for conductors.

4. Underground-line warning tape.

5. Warning labels and signs.

6. Instruction signs.

7. Equipment identification labels.

8. Miscellaneous identification products.

1.3 SUBMITTALS

A. Product Data: For each electrical identification product indicated.

1.4 QUALITY ASSURANCE

A. Comply with ANSI A13.1 and IEEE C2.

B. Comply with NFPA 70.

C. Comply with 29 CFR 1910.144 and 29 CFR 1910.145.

D. Comply with ANSI Z535.4 for safety signs and labels.

1.5 COORDINATION

A. Coordinate identification names, abbreviations, colors, and other features with requirements in other Sections requiring identification applications, Drawings, Shop Drawings, manufacturer's wiring diagrams, and the Operation and Maintenance Manual; and with those required by codes, standards, and 29 CFR 1910.145. Use consistent designations throughout Project.

B. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied.

ATTACHMENT 1.2

Renovation and Addition – 201305.1 260553 - 2 January 31, 2014 (FINAL BID DOC’S)

C. Coordinate installation of identifying devices with location of access panels and doors.

D. Install identifying devices before installing acoustical ceilings and similar concealment.

PART 2 - PRODUCTS

2.1 POWER RACEWAY IDENTIFICATION MATERIALS

A. Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each raceway size.

B. Colors for Raceways Carrying Circuits at 600 V or Less:

1. Black letters on an orange field for normal feeders, black letters on a yellow field for emergency feeders.

2. Legend: Indicate voltage and system or service type.

C. Snap-Around Labels for Raceways Carrying Circuits at 600 V or Less: Slit, pretensioned, flexible, preprinted, color-coded acrylic sleeve, with diameter sized to suit diameter of raceway or cable it identifies and to stay in place by gripping action.

2.2 METAL-CLAD CABLE IDENTIFICATION MATERIALS

A. Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each raceway and cable size.

B. Colors for Raceways Carrying Circuits at 600 V and Less:

1. Black letters on an orange field for normal circuits, black letters on a yellow field for emergency circuits.

2. Legend: Indicate voltage and system or service type.

C. Self-Adhesive Vinyl Tape: Colored, heavy duty, waterproof, fade resistant; 2 inches (50 mm) wide; compounded for outdoor use.

2.3 CONDUCTOR IDENTIFICATION MATERIALS

A. Color-Coding Conductor Tape: Colored, self-adhesive vinyl tape not less than 3 mils (0.08 mm) thick by 1 to 2 inches (25 to 50 mm) wide.

2.4 UNDERGROUND-LINE WARNING TAPE

A. Tape: Permanent, bright-colored, continuous-printed polyethylene tape.

1. Recommended by manufacturer for the method of installation and suitable to identify and locate underground electrical and communications utility lines.

2. Printing on tape shall be permanent and shall not be damaged by burial operations.

3. Tape material and ink shall be chemically inert, and not subject to degrading when exposed to acids, alkalis, and other destructive substances commonly found in soils.

4. Embedded continuous metallic strip or core.

Renovation and Addition – 201305.1 260553 - 3

B. Color and Printing:

1. Comply with ANSI Z535.1 through ANSI Z535.5.

2. Inscriptions for Red-Colored Tapes: ELECTRIC LINE, HIGH VOLTAGE.

3. Inscriptions for Orange-Colored Tapes: TELEPHONE CABLE, CATV CABLE, COMMUNICATIONS

CABLE, OPTICAL FIBER CABLE.

2.5 WARNING LABELS AND SIGNS

A. Comply with NFPA 70 and 29 CFR 1910.145.

B. Baked-Enamel Warning Signs:

1. Preprinted aluminum signs, punched or drilled for fasteners, with colors, legend, and size required for application.

2. 1/4-inch (6.4-mm) grommets in corners for mounting.

3. Nominal size, 7 by 10 inches (180 by 250 mm).

C. Metal-Backed, Butyrate Warning Signs:

1. Weather-resistant, nonfading, preprinted, cellulose-acetate butyrate signs with 0.0396-inch (1-mm) galvanized-steel backing; and with colors, legend, and size required for application.

2. 1/4-inch (6.4-mm) grommets in corners for mounting.

3. Nominal size, 10 by 14 inches (250 by 360 mm).

D. Warning label and sign shall include, but are not limited to, the following legends:

1. Multiple Power Source Warning: "DANGER - ELECTRICAL SHOCK HAZARD - EQUIPMENT HAS

MULTIPLE POWER SOURCES."

2. Workspace Clearance Warning: "WARNING - OSHA REGULATION - AREA IN FRONT OF

ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 36 INCHES (915 MM)."

2.6 EQUIPMENT IDENTIFICATION LABELS

A. Engraved, Laminated Acrylic or Melamine Label: Punched or drilled for screw mounting. White letters on a dark-gray background for equipment connected to normal power source, white letters on a red background for equipment connected to an emergency power source. Minimum letter height shall be 3/8 inch (10 mm).

B. Stenciled Legend: In nonfading, waterproof, black ink or paint. Minimum letter height shall be 1 inch (25 mm).

2.7 CABLE TIES

A. General-Purpose Cable Ties: Fungus inert, self extinguishing, one piece, self locking, Type 6/6 nylon.

1. Minimum Width: 3/16 inch (5 mm).

2. Tensile Strength at 73 deg F (23 deg C), According to ASTM D 638: 12,000 psi (82.7 MPa).

3. Temperature Range: Minus 40 to plus 185 deg F (Minus 40 to plus 85 deg C).

4. Color: Black except where used for color-coding.

B. UV-Stabilized Cable Ties: Fungus inert, designed for continuous exposure to exterior sunlight, self extinguishing, one piece, self locking, Type 6/6 nylon.

Renovation and Addition – 201305.1 260553 - 4

1. Minimum Width: 3/16 inch (5 mm).

2. Tensile Strength at 73 deg F (23 deg C), According to ASTM D 638: 12,000 psi (82.7 MPa).

3. Temperature Range: Minus 40 to plus 185 deg F (Minus 40 to plus 85 deg C).

4. Color: Black.

C. Plenum-Rated Cable Ties: Self extinguishing, UV stabilized, one piece, self locking.

1. Minimum Width: 3/16 inch (5 mm).

2. Tensile Strength at 73 deg F (23 deg C), According to ASTM D 638: 7000 psi (48.2 MPa).

3. UL 94 Flame Rating: 94V-0.

4. Temperature Range: Minus 50 to plus 284 deg F (Minus 46 to plus 140 deg C).

5. Color: Black.

2.8 MISCELLANEOUS IDENTIFICATION PRODUCTS

A. Paint: Comply with requirements in Division 09 painting Sections for paint materials and application requirements.

Select paint system applicable for surface material and location (exterior or interior).

B. Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine screws with nuts and flat and lock washers.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Verify identity of each item before installing identification products.

B. Location: Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment. In finished spaces, nameplates for panelboards shall be secured to the interior behind the door.

C. Apply identification devices to surfaces that require finish after completing finish work.

D. Attach signs and plastic labels with stainless screws.

E. System Identification Color-Coding Bands for Raceways and Cables: Each color-coding band shall completely encircle cable or conduit. Place adjacent bands of two-color markings in contact, side by side. Locate bands at changes in direction, at penetrations of walls and floors, at 50-foot (15-m) maximum intervals in straight runs, and at 25-foot (7.6-m) maximum intervals in congested areas.

F. Cable Ties: For attaching tags. Use general-purpose type, except as listed below:

1. Outdoors: UV-stabilized nylon.

2. In Spaces Handling Environmental Air: Plenum rated.

G. Underground-Line Warning Tape: During backfilling of trenches install continuous underground-line warning tape directly above line at 8 inches (200 mm) below finished grade. Use multiple tapes where width of multiple lines installed in a common trench or concrete envelope exceeds 16 inches (400 mm) overall.

H. Painted Identification: Comply with requirements in Division 09 painting Sections for surface preparation and paint application.

Renovation and Addition – 201305.1 260553 - 5

3.2 IDENTIFICATION SCHEDULE

A. Accessible Raceways, 600 V or Less, for Service, Feeder, and Branch Circuits More Than 20 A: Identify with snap-around label applied in bands. Install labels at 10-foot (3-m) maximum intervals.

B. Accessible Raceways and Cables within Buildings: Identify the covers of each junction and pull box of the following systems with self-adhesive vinyl labels with the wiring system legend and system voltage. System legends shall be as follows:

1. Emergency Power - Yellow.

2. Power - Orange.

3. Fire Alarm System – Red.

4. Security System – Blue and Yellow.

5. Mechanical and Electrical Supervisory System – Green and Blue.

6. Telecommunication Systems - Green and Yellow.

7. Control Wiring – Green and Red.

C. Power-Circuit Conductor Identification, 600 V or Less: For conductors in vaults, pull and junction boxes, manholes, and handholes, use color-coding conductor tape to identify the phase.

1. Color-Coding for Phase and Voltage Level Identification, 600 V or Less: Use colors listed below for ungrounded service, feeder and branch-circuit conductors.

a. Color shall be factory applied or field applied for sizes larger than No. 8 AWG, if authorities having jurisdiction permit.

b. Colors for 208/120-V Circuits:

1) Phase A: Black.

2) Phase B: Red.

3) Phase C: Blue.

4) Neutral: White.

5) Ground: Green.

c. Colors for 480/277-V Circuits:

1) Phase A: Brown.

2) Phase B: Orange.

3) Phase C: Yellow.

4) Neutral: Gray.

5) Ground: Green.

d. All control wiring shall be color-coded when using wires of different color from the type used to designate phase wires.

e. Field-Applied, Color-Coding Conductor Tape: Apply in half-lapped turns for a minimum distance of 6 inches (150 mm) from terminal points and in boxes where splices or taps are made. Apply last two turns of tape with no tension to prevent possible unwinding. Locate bands to avoid obscuring factory cable markings.

f. All emergency wiring shall have the same color-coding, but shall be clearly identified as emergency in all outlets, fixtures, etc.

D. Install instructional sign including the color-code for grounded and ungrounded conductors using adhesive-film-type labels.

Renovation and Addition – 201305.1 260553 - 6

E. Conductors to Be Extended in the Future: Attach marker tape to conductors and list source.

F. Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm, control, and signal connections.

1. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, and pull points.

Identify by system and circuit designation.

2. Use system of marker tape designations that is uniform and consistent with system used by manufacturer for factory-installed connections.

3. Coordinate identification with Project Drawings, manufacturer's wiring diagrams, and the Operation and Maintenance Manual.

G. Locations of Underground Lines: Identify with underground-line warning tape for power, lighting, communication, and control wiring and optical fiber cable.

1. Install underground-line warning tape for both direct-buried cables and cables in raceway.

H. Workspace Indication: Install floor marking tape to show working clearances in the direction of access to live parts.

Workspace shall be as required by NFPA 70 and 29 CFR 1926.403 unless otherwise indicated. Do not install at flush-mounted panelboards and similar equipment in finished spaces.

I. Warning Labels for Indoor Cabinets, Boxes, and Enclosures for Power and Lighting: Baked-enamel warning signs and metal-backed, butyrate warning signs.

1. Comply with 29 CFR 1910.145.

2. Identify system voltage with black letters on an orange background.

3. Apply to exterior of door, cover, or other access.

4. For equipment with multiple power or control sources, apply to door or cover of equipment including, but not limited to, the following:

a. Power transfer switches.

b. Controls with external control power connections.

J. Operating Instruction Signs: Install instruction signs to facilitate proper operation and maintenance of electrical systems and items to which they connect. Install instruction signs with approved legend where instructions are needed for system or equipment operation.

K. Emergency Operating Instruction Signs: Install instruction signs with white legend on a red background with minimum 3/8-inch- (10-mm-) high letters for emergency instructions at equipment used for power transfer.

L. Equipment Identification Labels: On each unit of equipment, install unique designation label that is consistent with wiring diagrams, schedules, and the Operation and Maintenance Manual. Apply labels to disconnect switches and protection equipment, central or master units, control panels, control stations, terminal cabinets, and racks of each system. For electrical equipment such as disconnect switches, motor starters, contactors, relays, pushbutton stations, etc., the label shall have the same designation as the equipment it serves. Systems include power, lighting, control, communication, signal, monitoring, and alarm systems unless equipment is provided with its own identification.

1. Labeling Instructions:

a. Indoor Equipment: Engraved, laminated phenolic nameplates. Unless otherwise indicated, provide a single line of text with 1/2-inch- (13-mm-) high letters on 1-1/2-inch- (38-mm-) high label;

where two lines of text are required, use labels 2 inches (50 mm) high.

b. Outdoor Equipment: Engraved, laminated acrylic or melamine label.

c. Elevated Components: Increase sizes of labels and letters to those appropriate for viewing from the floor.

Renovation and Addition – 201305.1 260553 - 7

d. Fasten labels with appropriate mechanical fasteners that do not change the NEMA or NRTL rating of the enclosure.

2. Equipment to Be Labeled:

a. Panelboards: Typewritten directory of circuits in the location provided by panelboard manufacturer.

Panelboard identification shall be engraved, laminated phenolic nameplate, “Panel (designation)”, “Served from “(designation)”.

b. Enclosures and electrical cabinets.

c. Access doors and panels for concealed electrical items.

d. Switchboards.

e. Transformers.

f. Electrical rooms/closets.

g. Emergency system boxes and enclosures.

h. Motor-control centers.

i. Enclosed switches.

j. Enclosed circuit breakers.

k. Enclosed controllers.

l. Variable-speed controllers.

m. Push-button stations.

n. Power transfer equipment.

o. Contactors.

p. Remote-controlled switches, dimmer modules, and control devices.

q. Power-generating units.

r. Monitoring and control equipment.

s. UPS equipment.

END OF SECTION 260553

000001 project manual - cover - volume 2
000002-Inside Cover
000002toc 2
Spring Ridge MS Specifications - Volume 2
230500_ComWorkResultsHVAC--8-5-09-JWA-FL
230513_ComMotorRequireHVAC-Equip--8-5--09-jwa-FL
230519_Meters&GaugesHVACPiping-8-5--09-jwa-FL
230523_GenDutyValvesHVACPiping-8-5--09-JWA-FL
230529_Hangers&SupportsHVAC-Piping&Equip-8-5--09-jwaFL
230548_Vibration&SeismicControlsHVACPiping&Equip-JWA-8-5--09fL
230553_ID-HVAC-Piping&Equip-8-5--09JWA
230593_TestingAdjustingBalancingHVAC-8-5--09FL
230700_hvacinsulation--fl
230900_Instrumentations&ControlHVAC-JWA-8-5-09--FL
231113 FL - FACILITY FUEL-OIL PIPING
232113_HydronicPiping-8-5--09-jwa-FL
232123_HydronicPumps8-5-09-jwa-FL
232300_RefrigerantPiping
233113_MetalDucts-8-5-09FL
233300_AirDuctAccessories-8-5--09-jwa-FL
233423_HVACPowerVentilators-8-5--09-jwa-FL
233600_AirTerminalUnits-JWA-8-6-09FL
233713_DiffusersRegisters&Grilles--8-5--09-jwa-FL
235223 FL - CAST-IRON BOILERS
237413 FL - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS
238126 FL - SPLIT-SYSTEM AIR-CONDITIONERS
238233_Convectors-8-5--09-jwa-FL
238239._UnitHeaters-8-5--09-jwa-FL
238239.13 FL__CABINET UNIT HEATERS
Division 26.pdf
260500-sleeves and sleeve seals for electrical raceways and cabling - Copy
260501-General Electrical Requirements - Copy
260501-General Electrical Requirements
260519-LowVoltageEPC&CablesFL - Copy
260526-grounding&bonding for electrical systems - Copy
260529-Hangers&Supports for electrical systems - Copy
260533-Raceway&Boxes for electrical systems - Copy
260543-UndergrdDuct and raceways for electrical systems - Copy
260548-Vibration&SeismicControls for electrical systems- - Copy
260553-identification for electrical systems - Copy
260573-overcurrent protective deivce coordination study - Copy
260923 FL - LightingControlDevices-12140-LPL - Copy
262200-low-voltage transformers - Copy
262413 Switchbds - Copy
262416 Panelbds - Copy
262713_electricitymetering - Copy
262726 - Wiring Devices - Copy
262813-Fuses - Copy
262816-EnclosedSwitches&CBs - Copy
262913-EnclosedControllers - Copy
262913-EnclosedControllers
263100 - PHOTOVOLTAIC SYSTEM
263213-EngineGenerators
263600-TRANSFER-SWITCHES
264113-LightningProtection for structures
264343-SurgeProtection for Low-voltage electrical power circuits
265100-16511-InteriorLtg-12140
265600-ExteriorLtg
Division 27.pdf
271500 Data Systems
275116 intercommunications system
275313 Clock System
Division 28.pdf
281300 - ACCESS CONTROL
281600 security system
282300 - VIDEO SURVEILLANCE
283111-Digiatal AddressableFAS
Binder2.pdf
31 20 00 - earth moving
31 22 19 - finish grading
31 23 19 - dewatering
31 50 00 - excavation support and protection
Binder3.pdf
32 11 60 - paving joint sealants
32 12 16 - asphalt paving
32 13 00 - rigid paving
32 92 00 - turfs and grasses
32 93 00 - plants
Binder4.pdf
33 00 00 - cast-in-place concrete
33 11 00 - water distribution
33 30 00 - sanitary sewerage
33 40 00 - storm drainage utilities

File details come from the government source that posted it. Updated .