260519 Low Voltage Electrical Power Conductors and Cables Specifications.pdf

PDF 371 KB Posted

Attached to
ITB-SMCPS-2024-M-EGLHS - Emergency Generator Replacement at Leonardtown High School
Solicitation number
BPM039704
Issued by
St. Mary's County, La Plata Town, Maryland

About this file

This document contains specifications for a state and local contract opportunity related to the Emergency Generator Replacement at Leonardtown High School, issued by the Board of Education of St. Mary's County on behalf of St. Mary's County Public Schools (SMCPS). The contract seeks experienced and qualified vendors to supply and replace the existing emergency generator and automatic transfer switch at the school. The scope of work includes but is not limited to the services and supplies described in the "Specifications VI" section. SMCPS reserves the right to make multiple awards, and the resulting contract shall be awarded for a period of 60 days after receipt of the generator from the manufacturer, with all work required to be substantially completed by August 15, 2025.

The contract opportunity is open to vendors across the state of Maryland, specifically in the jurisdictions of St. Mary's County and La Plata Town. Contractors are responsible for complying with all applicable laws and regulations of the authorities having jurisdiction while meeting the project specifications and requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

260519 - 1

Leonardtown High School Emergency Generator Replacement

SECTION 260519 – LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 – GENERAL

1.1 RELATED DOCUMENTS

A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Building wires and cables rated 600 V and less.

2. Connectors, splices, and terminations rated 600 V and less.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Qualification Data: For testing agency.

C. Field quality-control test reports.

1.4 QUALITY ASSURANCE

A. Testing Agency: Engage a qualified independent testing agency to perform field quality-control testing.

B. Testing: On installation of wires and cables and before electrical circuitry has been energized, demonstrate product capability and compliance with requirements. Procedures: Perform each visual and mechanical inspection and electrical test state din NETA ATS Section 7.3.1. Certify compliance with test parameters.

C. Correct malfunctioning conductors and cables at Project site, where possible, and retest to demonstrate compliance;

otherwise, remove and replace with new units and retest.

D. Measure tightness of bolted connections and compare torque measurements with manufacturer’s recommended values.

E. Verify continuity of each branch circuit conductor.

F. Tests: Service Entrance Cables, Power & Lighting Distribution Feeders and Feeders to all major mechanical equipment at 60A and over (i.e., chillers, AHU’s, etc.).

1. Tests shall be performed with a 1000-volt megger, and conductors shall test free from short-circuits and grounds.

2. Conductors shall be tested phase-to-phase and phase-to-ground.

ATTACHMENT 1.1

260519 - 2

Leonardtown High School Emergency Generator Replacement

3. Furnish the instruments, materials, and labor required. Perform the tests in the presence of the Contracting Officer.

4. Test readings shall be recorded and delivered to Owner and Engineer in a report.

5. Copy of Test results shall be included in O&M Manuals.

G. Demonstration: Subsequent to wire and cable hook-ups, energize circuit and demonstrate functioning in accordance with requirements. Where necessary, correct malfunctioning units, and then retest to demonstrate compliance.

PART 2 - PRODUCTS

2.1 CONDUCTORS AND CABLES

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work are the following:

1. Wires and Cables:

a. American Insulated Wire Corp.; Leviton Manufacturing Co.

b. BICC Brand-Rex Company.

c. Carol Cable Co., Inc.

d. Senator Wire & Cable Company.

e. Southwire Company.

2. Connectors and Accessories for Wires and Cables:

a. AMP Incorporated.

b. Buchanan.

c. General Signal; O-Z/Gedney Unit.

d. Monogram Company; AFAC.

e. NSI Industries, Inc.

f. Square D Company; Anderson.

g. 3M Company; Electrical Products Division.

B. Copper and Aluminum Conductors: Comply with NEMA WC 70.

C. Conductor Insulation: Comply with NEMA WC 70 for Types THHN-THWN, and SO.

D. Multiconductor Cable: Comply with NEMA WC 70 for metal clad cable, Type MC and Type SO with ground wire.

2.2 CONNECTORS AND SPLICES

A. UL-listed, factory-fabricated wiring connectors of size, ampacity rating, material, type, and class for application and service indicated. Comply with Project's installation requirements and as specified in Part 3 "Wire and Insulation Applications" Article.

B. Split Bolt Connectors: Not Acceptable.

C. Solderless Pressure Connectors: High copper alloy terminal. May be used only for cable termination to equipment pads or terminals. Not approved for splicing.

D. Spring Wire Connectors: Solderless spring type pressure connector with insulating covers for copper wire splices and taps. Use for conductor sizes 10 AWG and smaller.

260519 - 3

Leonardtown High School Emergency Generator Replacement

E. All wire connectors used in underground or exterior pull boxes shall be gel-filled twist connectors or a connector designed for damp and wet locations.

F. Mechanical Connectors: Bolted type tin-plated; high conductivity copper alloy; spacer between conductors; beveled cable entrances.

G. Compression (crimp) Connectors: Long barrel; seamless, tin-plated electrolytic high conductivity copper tubing, internally beveled barrel ends. Connector shall be clearly marked with the wire size and type and proper number and location of crimps.

H. Heat shrinkable tubing shall meet the requirements of ANSI C119.1-1986 for buried connections to 90°C and shall be material flame-retarded per IEEE 383 “Vertical Tray Flame Test”. Motor connection kits shall consist of heat-shrinkable, polymeric insulating material over the connection area and a high dielectric strength mastic to seal the ends against ingress of moisture and contamination. Motor connection kits shall accommodate a range of cable sizes for both in-line and stub-type configurations. Connection kits shall be independent of cable manufacturer’s tolerances.

I. Wire Nut Connectors:

1. Wire nuts install in wet locations, exterior, etc., shall be self-contained, waterproof and corrosion-proof units incorporating prefilled silicone grease to block out moisture and air.

2. Connectors shall be UL listed appropriately sized according to manufacturer’s recommendation for the suitable wire sizes and voltage rating (600 volt minimum).

3. Connectors body shall have a color-coded outer shell.

4. Connectors shall be as manufactured by King Technology or approved equal.

PART 3 - EXECUTION

3.1 CONDUCTOR MATERIAL APPLICATIONS

A. Feeders: Soft Drawn Copper, 98% conductivity minimum, solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.

B. Branch Circuits: Soft Drawn Copper. 98% Conductivity minimum, Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.

3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRING METHODS

A. 600 volt, unless otherwise noted, #12 AWG minimum (except control cable may be #14 AWG).

B. Service Entrance: Type THHN-THWN, single conductors in raceway.

C. Exposed Feeders: Type THHN-THWN, single conductors in raceway.

D. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN-THWN, single conductors in raceway.

E. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN-THWN, single conductors in raceway.

F. Exposed Branch Circuits, Including in Crawlspaces: Type THHN-THWN, single conductors in raceway.

260519 - 4

Leonardtown High School Emergency Generator Replacement

G. Branch Circuits Concealed in Ceilings, Walls, and Partitions: THHN-THWN, single conductors in raceway, except Metal-clad cable, Type MC may be used for lighting branch circuits above accessible ceilings.

H. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN-THWN, single conductors in raceway.

I. Cord Drops and Portable Appliance Connections: Type SO, hard service cord with stainless-steel, wire-mesh, strain relief device at terminations to suit application.

J. Class 1 Control Circuits: Type THHN-THWN, in raceway.

K. Class 2 Control Circuits: Type THHN-THWN, in raceway.

L. Conductors shall be rated 75 deg C in wet locations and 90 deg C in dry locations.

3.3 INSTALLATION OF CONDUCTORS AND CABLES

A. Conceal cables in finished walls and ceilings unless otherwise indicated.

B. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

C. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.

D. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.

E. Support cables according to Section 16071, "Hangers and Supports for Electrical Systems."

F. Identify and color-code conductors and cables according to Section 16075, “Identification for Electrical Systems."

3.4 CONNECTIONS

A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.

B. Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.

C. Wiring at Outlets: Install conductor at each outlet, with at least 8 inches (200 mm) of slack.

D. Joints of #10 AWG and smaller shall be made with properly insulated solderless type pressure connectors. Where stranded conductors or multiple solid conductors are connected to terminals, solderless lugs manufactured by Thomas and Betts Company or equivalent shall be used.

E. Joints of #8 AWG and larger in power and lighting circuits shall be of the type indented into the conductor by means of a hand or hydraulic pressure tool. Connectors shall be Burndy “Hy-dent’, T&B “St-Kon”, or equivalent.

Connectors for control wiring shall be Burndy “Hy-Lug”, or equivalent.

260519 - 5

F. All circuits for exterior electric work shall be #10 AWG (minimum) and contain an extra #10 AWG (minimum) copper ground conductor. All exterior wiring shall be installed in conduit as specified above, unless otherwise noted as larger on the Drawings.

3.5 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS

A. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 07 Section "Sealants," Division 07 Section “Insulation” and Division 16 “Basic Electrical Materials and Methods”.

3.6 SLEEVE-SEAL INSTALLATION

A. Install to seal underground exterior-wall penetrations according to Division 16 Section, “Basic Electrical Materials and Methods”.

3.7 FIRESTOPPING

A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to Division 7 Section "Sealants" and Division 07 Section “Insulation.”

3.8 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified independent testing agency to perform field quality-control testing.

B. Testing: On installation of wires and cables and before electrical circuitry has been energized, demonstrate product capability and compliance with requirements. Procedures: Perform each visual and mechanical inspection and electrical test state din NETA ATS Section 7.3.1. Certify compliance with test parameters.

C. Correct malfunctioning conductors and cables at Project site, where possible, and retest to demonstrate compliance;

otherwise, remove and replace with new units and retest.

D. Measure tightness of bolted connections and compare torque measurements with manufacturer’s recommended values.

E. Verify continuity of each branch circuit conductor.

F. Tests: Service Entrance Cables, Power & Lighting Distribution Feeders and Feeders to all major mechanical equipment at 60A and over (i.e., chillers, AHU’s, etc.).

1. Tests shall be performed with a 1000-volt megger, and conductors shall test free from short-circuits and grounds.

2. Conductors shall be tested phase-to-phase and phase-to-ground.

3. Furnish the instruments, materials, and labor required. Perform the tests in the presence of the Contracting

Officer.

4. Test readings shall be recorded and delivered to Owner and Engineer in a report.

5. Copy of Test results shall be included in O&M Manuals.

G. Demonstration: Subsequent to wire and cable hook-ups, energize circuit and demonstrate functioning in accordance with requirements. Where necessary, correct malfunctioning units, and then retest to demonstrate compliance.

Leonardtown High School Emergency Generator Replacement

END OF SECTION 260519

000001 project manual - cover - volume 2
000002-Inside Cover
000002toc 2
Spring Ridge MS Specifications - Volume 2
230500_ComWorkResultsHVAC--8-5-09-JWA-FL
230513_ComMotorRequireHVAC-Equip--8-5--09-jwa-FL
230519_Meters&GaugesHVACPiping-8-5--09-jwa-FL
230523_GenDutyValvesHVACPiping-8-5--09-JWA-FL
230529_Hangers&SupportsHVAC-Piping&Equip-8-5--09-jwaFL
230548_Vibration&SeismicControlsHVACPiping&Equip-JWA-8-5--09fL
230553_ID-HVAC-Piping&Equip-8-5--09JWA
230593_TestingAdjustingBalancingHVAC-8-5--09FL
230700_hvacinsulation--fl
230900_Instrumentations&ControlHVAC-JWA-8-5-09--FL
231113 FL - FACILITY FUEL-OIL PIPING
232113_HydronicPiping-8-5--09-jwa-FL
232123_HydronicPumps8-5-09-jwa-FL
232300_RefrigerantPiping
233113_MetalDucts-8-5-09FL
233300_AirDuctAccessories-8-5--09-jwa-FL
233423_HVACPowerVentilators-8-5--09-jwa-FL
233600_AirTerminalUnits-JWA-8-6-09FL
233713_DiffusersRegisters&Grilles--8-5--09-jwa-FL
235223 FL - CAST-IRON BOILERS
237413 FL - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS
238126 FL - SPLIT-SYSTEM AIR-CONDITIONERS
238233_Convectors-8-5--09-jwa-FL
238239._UnitHeaters-8-5--09-jwa-FL
238239.13 FL__CABINET UNIT HEATERS
Division 26.pdf
260500-sleeves and sleeve seals for electrical raceways and cabling - Copy
260501-General Electrical Requirements - Copy
260501-General Electrical Requirements
260519-LowVoltageEPC&CablesFL - Copy
260526-grounding&bonding for electrical systems - Copy
260529-Hangers&Supports for electrical systems - Copy
260533-Raceway&Boxes for electrical systems - Copy
260543-UndergrdDuct and raceways for electrical systems - Copy
260548-Vibration&SeismicControls for electrical systems- - Copy
260553-identification for electrical systems - Copy
260573-overcurrent protective deivce coordination study - Copy
260923 FL - LightingControlDevices-12140-LPL - Copy
262200-low-voltage transformers - Copy
262413 Switchbds - Copy
262416 Panelbds - Copy
262713_electricitymetering - Copy
262726 - Wiring Devices - Copy
262813-Fuses - Copy
262816-EnclosedSwitches&CBs - Copy
262913-EnclosedControllers - Copy
262913-EnclosedControllers
263100 - PHOTOVOLTAIC SYSTEM
263213-EngineGenerators
263600-TRANSFER-SWITCHES
264113-LightningProtection for structures
264343-SurgeProtection for Low-voltage electrical power circuits
265100-16511-InteriorLtg-12140
265600-ExteriorLtg
Division 27.pdf
271500 Data Systems
275116 intercommunications system
275313 Clock System
Division 28.pdf
281300 - ACCESS CONTROL
281600 security system
282300 - VIDEO SURVEILLANCE
283111-Digiatal AddressableFAS
Binder2.pdf
31 20 00 - earth moving
31 22 19 - finish grading
31 23 19 - dewatering
31 50 00 - excavation support and protection
Binder3.pdf
32 11 60 - paving joint sealants
32 12 16 - asphalt paving
32 13 00 - rigid paving
32 92 00 - turfs and grasses
32 93 00 - plants
Binder4.pdf
33 00 00 - cast-in-place concrete
33 11 00 - water distribution
33 30 00 - sanitary sewerage
33 40 00 - storm drainage utilities

File details come from the government source that posted it. Updated .