260521 Electrical Wire.pdf

PDF 91 KB Posted

Attached to
Z2DA--Actionable: 666-24-127_B71N Cooling Tower Chemical Injection (VA-24-00006695)
Solicitation number
36C25924Q0057
Issued by

About this file

This document provides specifications for low-voltage electrical power conductors and cables to be installed at the VA Medical Center in Sheridan, Wyoming. Requirements include using copper conductors with THWN, THHN, XHHW, UF or USE insulation rated for voltages of 208/120V or 480/277V. Conductors must be color-coded according to size and phase. Splicing and termination methods are defined for branch and feeder circuits. Fireproofing materials, warning tape and testing procedures are also specified.

The related opportunity is a solicitation from the Department of Veterans Affairs for electrical work identified as Cooling Tower Chemical Injection at the VA Medical Center in Sheridan, Wyoming. The specifications provide requirements for the low-voltage wiring to be installed as part of this project.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12-05M

VA Medical Center, Sheridan, Wyoming 26 05 21 - 1

666-23-109 B71N Cooling Tower Chemical Injection Electrical Wire

SECTION 26 05 21

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

PART 1 - GENERAL

1.1 DESCRIPTION

This section specifies the furnishing, installation, and connection of the low voltage power wiring.

1.2 RELATED WORK

A. Sealing around penetrations to maintain the integrity of time rated construction: Section 07 84 00, FIRESTOPPING.

1.3 SUBMITTALS

A. In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND

SAMPLES, furnish the following:

1. Manufacturer's Literature and Data: Showing each cable type and rating.

2. Certificates: Two weeks prior to final inspection, deliver to the

COTR four copies of the certification that the material is in accordance with the drawings and specifications and has been properly installed.

1.4 APPLICABLE PUBLICATIONS

A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are reference in the text by the basic designation only.

B. American Society of Testing Material (ASTM):

D2301-04................Standard Specification for Vinyl Chloride

Plastic Pressure Sensitive Electrical

Insulating Tape

C. Federal Specifications (Fed. Spec.):

A-A-59544-00............Cable and Wire, Electrical (Power, Fixed

Installation)

C. National Fire Protection Association (NFPA):

70-05...................National Electrical Code (NEC)

D. Underwriters Laboratories, Inc. (UL):

44-02...................Thermoset-Insulated Wires and Cables

83-03...................Thermoplastic-Insulated Wires and Cables

467-01..................Electrical Grounding and Bonding Equipment

486A-01.................Wire Connectors and Soldering Lugs for Use with

Copper Conductors

VA Medical Center, Sheridan, Wyoming 26 05 21 - 2

666-23-109 B71N Cooling Tower Chemical Injection Electrical Wire

486C-02.................Splicing Wire Connectors

486D-02.................Insulated Wire Connector Systems for

Underground Use or in Damp or Wet Locations

486E-00.................Equipment Wiring Terminals for Use with

Aluminum and/or Copper Conductors

493-01..................Thermoplastic-Insulated Underground Feeder and

Branch Circuit Cable

514B-02.................Fittings for Cable and Conduit

1479-03.................Fire Tests of Through-Penetration Fire Stops

PART 2 - PRODUCTS

2.1 CABLE AND WIRE (POWER)

A. Cable and Wire shall be in accordance with Fed. Spec. A-A-59544, except as hereinafter specified.

B. Single Conductor:

1. Shall be annealed copper.

2. Shall be stranded for sizes No. 8 AWG and larger, solid for sizes

No. 10 AWG and smaller.

3. Shall be minimum size No. 12 AWG, except where smaller sizes are allowed herein.

C. Insulation:

1. THW, XHHW, or dual rated THHN-THWN shall be in accordance with UL

44, and 83.

2. Direct burial: UF or USE shall be in accordance with UL 493.

3. Isolated power system wiring: Type XHHW with a dielectric constant of 3.5 or less.

D. Color Code:

1. Secondary service, feeder and branch circuit conductors shall be color coded as follows:

208/120 volt Phase 480/277 volt

Black A Brown

Red B Orange

Blue C Yellow

White Neutral Gray *

* or white with colored (other than green) tracer.

2. Use solid color compound or solid color coating for No. 12 AWG and

No. 10 AWG branch circuit conductors and neutral sizes.

VA Medical Center, Sheridan, Wyoming 26 05 21 - 3

666-23-109 B71N Cooling Tower Chemical Injection Electrical Wire

3. Phase conductors No. 8 AWG and larger shall be color-coded using one of the following methods:

a. Solid color compound or solid color coating.

b. Stripes, bands, or hash marks of color specified above.

c. Color as specified using 19 mm (3/4 inch) wide tape. Apply tape in half overlapping turns for a minimum of 75 mm (three inches) for terminal points, and in junction boxes, pull boxes, troughs, manholes, and handholes. Apply the last two laps of tape with no tension to prevent possible unwinding. Where cable markings are covered by tape, apply tags to cable stating size and insulation type.

4. For modifications and additions to existing wiring systems, color coding shall conform to the existing wiring system.

5. Color code for isolated power system wiring shall be in accordance with the NEC.

2.2 SPLICES AND JOINTS

A. In accordance with UL 486A, C, D, E and NEC.

B. Branch circuits (No. 10 AWG and smaller):

1. Connectors: Solderless, screw-on, reusable pressure cable type, 600 volt, 105 degree C with integral insulation, approved for copper and aluminum conductors.

2. The integral insulator shall have a skirt to completely cover the stripped wires.

3. The number, size, and combination of conductors, as listed on the manufacturers packaging shall be strictly complied with.

C. Feeder Circuits:

1. Connectors shall be indent, hex screw, or bolt clamp-type of high conductivity and corrosion-resistant material.

2. Field installed compression connectors for cable sizes 250 kcmil and larger shall have not less than two clamping elements or compression indents per wire.

3. Insulate splices and joints with materials approved for the particular use, location, voltage, and temperature. Insulate with not less than that of the conductor level that is being joined.

4. Plastic electrical insulating tape: ASTM D2304 shall apply, flame retardant, cold and weather resistant.

VA Medical Center, Sheridan, Wyoming 26 05 21 - 4

666-23-109 B71N Cooling Tower Chemical Injection Electrical Wire

2.3 WIRE LUBRICATING COMPOUND

A. Suitable for the wire insulation and conduit it is used with, and shall not harden or become adhesive.

B. Shall not be used on wire for isolated type electrical power systems.

2.4 FIREPROOFING TAPE

A. The tape shall consist of a flexible, conformable fabric of organic composition coated one side with flame-retardant elastomer.

B. The tape shall be self-extinguishing and shall not support combustion.

It shall be arc-proof and fireproof.

C. The tape shall not deteriorate when subjected to water, gases, salt water, sewage, or fungus and be resistant to sunlight and ultraviolet light.

D. The finished application shall withstand a 200-ampere arc for not less than 30 seconds.

E. Securing tape: Glass cloth electrical tape not less than 0.18 mm

(7 mils) thick, and 19 mm (3/4 inch) wide.

2.6 WARNING TAPE

A. The tape shall be standard, 76 mm (3 inch) wide, 4-Mil polyethylene non-detectable type.

B. The tape shall be red with black letters indicating “CAUTION BURIED

ELECTRIC LINE BELOW”.

PART 3 - EXECUTION

3.1 INSTALLATION, GENERAL

A. Install in accordance with the NEC, and as specified.

B. Install all wiring in raceway systems, except where direct burial or

HCF Type AC cables are used.

C. Splice cables and wires only in outlet boxes, junction boxes, pull boxes, manholes, or handholes.

D. Wires of different systems (i.e. 120V, 277V) shall not be installed in the same conduit or junction box system.

E. Install cable supports for all vertical feeders in accordance with the

NEC. Provide split wedge type which firmly clamps each individual cable and tightens due to cable weight.

F. For panelboards, cabinets, wireways, switches, and equipment assemblies, neatly form, train, and tie the cables in individual circuits.

VA Medical Center, Sheridan, Wyoming 26 05 21 - 5

666-23-109 B71N Cooling Tower Chemical Injection Electrical Wire

G. Seal cable and wire entering a building from underground, between the wire and conduit where the cable exits the conduit, with a non-hardening approved compound.

H. Wire Pulling:

1. Provide installation equipment that will prevent the cutting or abrasion of insulation during pulling of cables.

2. Use ropes made of nonmetallic material for pulling feeders.

3. Attach pulling lines for feeders by means of either woven basket grips or pulling eyes attached directly to the conductors, as approved by the Resident Engineer.

4. Pull in multiple cables together in a single conduit.

I. No more than (3) single-phase branch circuits shall be installed in any one conduit.

J. The wires shall be derated in accordance with NEC Article 310. Neutral wires, under conditions defined by the NEC, shall be considered current-carrying conductors.

3.2 SPLICE INSTALLATION

A. Splices and terminations shall be mechanically and electrically secure.

B. Where the Government determines that unsatisfactory splices or terminations have been installed, remove the devices and install approved devices at no additional cost to the Government.

3.3 EXISITNG WIRING

Unless specifically indicated on the plans, existing wiring shall not be reused for the new installation. Only wiring that conforms to the specifications and applicable codes may be reused. If existing wiring does not meet these requirements, existing wiring may not be reused and new wires shall be installed.

3.4 FIELD TESTING

A. Feeders and branch circuits shall have their insulation tested after installation and before connection to utilization devices such as fixtures, motors, or appliances.

B. Tests shall be performed by megger and conductors shall test free from short-circuits and grounds.

C. Test conductor phase-to-phase and phase-to-ground.

D. The Contractor shall furnish the instruments, materials, and labor for these tests.

- - - E N D - - -