26_05_19_Low-Voltage_Wires.pdf

PDF 123 KB Posted

Attached to
Portable Buildings - Maintenance & Repairs
Solicitation number
25/26-0045
Issued by
San Bernardino County, California

About this file

This is a specification document for low-voltage wires (600 volt AC) issued by the Fontana Unified School District (FUSD), a K-12 public school district serving approximately 32,000 students across 45 sites in San Bernardino County, California. The specification details requirements for single conductor THHN or THWN insulated wires rated at 600 volts, including materials, installation procedures, testing protocols, and color-coding standards for general wiring and signal systems. Installation must be performed by state-certified electricians under the supervision of the Project Inspector, with contractors required to demonstrate minimum five years of experience installing systems of similar scope and complexity, including completion of at least five equivalent projects. Prior to construction, manufacturers must provide certification that proposed products are qualified as low electromagnetic field products, and shop drawings with detailed material specifications must be submitted for approval. All components and materials must be listed and approved by Underwriter's Laboratories (UL) or another Nationally Recognized Testing Laboratory (NRTL) in compliance with applicable industry standards and California codes.

The specification requires comprehensive testing and quality assurance measures, including megger time-resistance insulation testing of all feeder and branch circuit conductors performed by approved independent testing laboratories or certified technicians, with insulation resistance not to be less than 100 mega-ohms. Contractors must provide a one-year labor warranty and a minimum 10-year material warranty beginning at substantial completion or project acceptance. Wire-pulling compounds must be UL-listed or NRTL-approved, with cable pull machines required for conductors of 2 AWG or larger on runs exceeding 50 feet. Pressure cable connectors for splices must be pre-insulated 3M Scotchlok, O-Z/Gedney, or approved equal products. The specification includes detailed color-coding requirements for phase conductors, neutral conductors, and signal systems including fire alarm, clocks, program bells, and door holding magnets. Installation of feeder cables requires notification to the Project Inspector at least two working days in advance, and all work must be completed in compliance with the California Electrical Code and applicable standards referenced throughout the document.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fontana Unified School District

LOW-VOLTAGE WIRES (600 VOLT AC)

26 05 19

Revised: 01/07/22 Page 1 of 8 Low-Voltage Wires 600 Volt AC Section 26 05 19

PART 1 - GENERAL

1.01 SUMMARY

A. Provisions of Division 01 apply to this section.

B. Section Includes: Low-voltage wire, splices, terminations and installation.

1.02 SUBMITTALS

A. Provide in accordance with Division 01.

B. List of Materials: Submit a complete list of proposed materials.

C. Shop Drawings: Provide detailed and dimensioned Shop Drawings indicating kind, weight and thickness of materials, insulation type, resistivity, conductivity, impedance, and conductance. Drawings shall contain sufficient information to assemble and install equipment at the Project site without further instructions.

D. Prior to start of construction; provide letter from wiring and electrical cables manufacturer certifying that the products are qualified/ listed as low electromagnetic field products.

1.03 SUBSTITUTIONS

A. Deviations/Substitutions from these requirements shall not be accepted without written approval from OWNER’S Design Standards Section and Maintenance and Operations Technical Unit. When deviating are proposed the following information shall be submitted:

1. Substitution request form stating reasons and benefits to OWNER.

2. OWNER’S approval shall be obtained for any equipment or materials substitutions.

3. Proposed substitutions requests shall provide proof of compliance with OWNER’S requirements and applicable standards.

B. Submittals must comply with contract general provisions.

1.04 QUALITY ASSURANCE

A. Components and materials shall be listed and approved for the intended application by Underwriter's Laboratories (UL), or other Nationally Recognized Testing Laboratory (NRTL), and in compliance with applicable industry standards and codes.

B. Wiring installation shall be performed under the supervision of state certified electricians. Contractor or Installer’s electricians shall be certified in accordance with Labor Code sections 3099, and 3099.2 and section

209.0 of the California Code of Regulations.

26 05 19

Revised: 01/07/22 Page 2 of 8 Low-Voltage Wires 600 Volt AC Section 26 05 19

C. Contractor shall have adequate experience installing systems of similar size and complexity.

1. Qualifications of Installer: Minimum five years of experience installing products and systems of similar scope and complexity.

2. Installer shall have completed at least five projects of equivalent scope and complexity.

3. Contractor shall have completed and commissioned a minimum of five service agreements that provide similar support services to those needed for this project.

4. System startup and testing shall be performed under direct observation of the Project Inspector and OAR.

D. The Project Inspector will observe installation of feeder cables. Notify the Project Inspector not less than two working days in advance of the proposed time of feeder installation.

1.05 WARRANTY

A. Provide a one year labor warranty.

B. Provide material warranty of no less than 10 years.

C. Warranty period begins at substantial completion or project acceptance for beneficial occupancy.

D. CONTRACTOR shall warranty all products and materials. Multiple warranty sources is not acceptable.

PART 2 - PRODUCTS

2.01 WIRES

A. Pressure cable connectors shall be pre-insulated 3M Scotchlok, O- Z/Gedney or equal.

B. Wires shall be single conductor type THHN or THWN insulated with polyvinyl chloride and covered with a protective sheath of nylon, rated at 600 volts.

Wires may be operated at a maximum continuous conductor temperature in dry locations of 90 degrees C. and 75 degrees C. in wet locations. Wires and cables shall be listed by Underwriter's Laboratories (UL) Standard 83 for thermoplastic insulated wires, and listed for installation in accordance with Article 310 of the California Electrical Code (CEC).

C. Conductors shall be solid copper for 12 AWG and smaller conductors, and stranded copper for 10 AWG and larger conductors.

D. Conductors shall be insulated with PVC and sheathed with nylon.

26 05 19

Revised: 01/07/22 Page 3 of 8 Low-Voltage Wires 600 Volt AC Section 26 05 19

E. Wires shall be identified by surface markings indicating manufacturer's identification, conductor size and metal, voltage rating, UL symbol, type designations and optional rating. Indentations for lettering are not permitted.

F. Wires shall be tested in accordance with the requirements of UL standard for types THWN and THHN.

G. Conductors shall be solid Class B or stranded Class C annealed uncoated copper in accordance with UL standards, or another Nationally Recognized Testing Laboratory (NRTL).

2.02 STANDARDS

A. THWN/THHN wires shall comply with the following standards:

1. UL 83 for thermoplastic insulated wires.

2. UL 1063 for machine tool wires and cables.

PART 3 - EXECUTION

3.01 INSTALLATION

A. Wires shall not be installed until debris and moisture is removed from conduits, boxes, and cabinets. Wires stored at site shall be protected from physical damage until they are installed, and walls are completed.

B. Wire-pulling compounds furnished as lubricants for installation of conductors in raceways shall be compounds approved and listed by UL, NRTL, or equal. Oil, grease, graphite, or similar substances are not permitted. Pulling of 2 AWG or larger conductors shall be performed with a cable pull machine. Any runs shorter than 50 feet are exempt. When pulling conductors, do not exceed manufacturer’s recommended values.

The project inspector will observe installation of feeder cables notify project inspector not less than two working days in advance of the proposed time of feeder installation.

C. At outlets for light, power, and signal equipment, pigtail splices with 8-inch circuit conductor leads for connection to fixtures, equipment, and devices.

D. Pressure cable connectors, pre-insulated Scotch Lok, 3m or equal, Yellow, Red, or Blue spring-loaded twist-on type, may be furnished in splicing number 8 AWG or smaller wires for wiring systems. Listed Push-in spring clamp wire connectors, Ideal In-Sure, or equal may be used in luminaires for fixture wiring. Except public address and telephone systems.

E. Joints, splices, taps, and connections to switchboard neutral, bonding or grounding conductors, conductors to ground busses, and transformer connections for wires 6 gage and larger shall be performed with high-

26 05 19

Revised: 01/07/22 Page 4 of 8 Low-Voltage Wires 600 Volt AC Section 26 05 19 pressure cable connectors approved for installation with copper conductors. Connectors shall be insulated with heavy wall heat shrink WCSM, or cold-applied roll-on sleeve RVS. Insulation level shall be a minimum of 600V and joints, splices, and taps shall be qualified to ANSI C 119.1, UL, NRTL, or equal listed mechanical pressure connections.

F. Connections to any bussing and high-press cable connectors shall be securely bolted together with corrosion-resistant plated carbon steel, minimum grade five machine screws secured with constant pressure-type locking devices.

G. Connection of any bonding or grounding conductors shall be securely bolted together with corrosion-resistant plated carbon steel, minimum grade five machine screws secured with constant pressure-type locking devices.

H. Wire switchboards, panel cabinets, pull boxes, and other cabinets except public address, shall be neatly grouped and tied in bundles with nylon ties at 10-inch intervals. In switchboards, panels and terminal blocks, wires shall be fanned out to terminals. If bundles are longer than 24 inches, a maximum of nine current carrying conductors may be bundled together.

I. Install conductor lengths with a minimum length within the wiring space.

Conductors must be long enough to reach the terminal location in a manner that avoids strain on the connecting lug.

J. Maintain the conductor required bending radius.

K. Neutral conductors larger than 6 gage, which are not color identified throughout their entire length, shall be taped, painted white or natural gray, or taped white where they appear in switchboards, cabinet, gutters or pull boxes. Neutral conductors 6 gage and smaller shall be white color identified throughout their entire length.

L. Fire alarm and clock wiring shall be continuous from terminal cabinets or from equipment to each device. Splices are not permitted between devices and/or terminal cabinets at junction and pull boxes. Wiring shall be terminated at terminal blocks or devices only.

M. Wiring systems shall be free from short circuits and grounds, other than required grounds. The contractor shall be responsible for the testing of feeder and branch circuit conductor’s insulation resistance. The insulation of the conductors shall be tested prior to connections to any panelboards, switchboards, variable frequency drives, lighting control systems, ballasts, and wiring devices such as but not limited to GFI receptacles, TVSS receptacles, or equipment. Insulation testing of panelboards and switchboards shall be independently performed from the insulation testing of any conductors as specified in other sections of this specification.

26 05 19

Revised: 01/07/22 Page 5 of 8 Low-Voltage Wires 600 Volt AC Section 26 05 19

1. Utilize the services of an approved independent testing laboratory to perform megger time-resistance insulation testing of feeder conductors. Tests must be conducted with wires disconnected at both ends.

a. Provide calibration program records to assure the testing instrument to be within rated accuracy. The test equipment accuracy shall be in accord with the requirements stated by the National Institute of Standards and Technology (NIST).

b. Test equipment shall be provided with a label stating the date of last calibration. As a minimum the equipment shall have been calibrated within the past 12 months.

c. Test reports shall include the following:

1) Identification of the testing organization.

2) Equipment identification.

3) Ambient conditions.

4) Identification of the testing technician.

5) Summary of project.

6) Description of equipment being tested.

7) Description of tests.

8) Test results.

9) Analysis, interpretation and recommendations.

2. Utilize the services of an approved independent testing laboratory or a qualified contractor’s employee (Technician certified in accordance with ANSI/NETA ETT-2000 Standard for Certification of Electrical Testing Personnel) to perform megger time-resistance insulation testing of branch circuit conductors. Tests must be conducted with wires disconnected at both ends.

a. Test equipment and report requirements stipulated under paragraph 3.01.N.1 apply to branch circuit testing.

3. Tests shall be performed in the presence of the Project Inspector.

4. Insulation resistance shall not be less than 100 mega-ohms.

3.02 COLOR CODES

A. General Wiring:

26 05 19

Revised: 01/07/22 Page 6 of 8 Low-Voltage Wires 600 Volt AC Section 26 05 19

1. For phase and neutral conductors 6 gage or larger, permanent plastic-colored tape may be furnished to mark conductor end instead of coded insulation. Tape shall cover not less than 2 inches of conductor insulation within enclosure.

2. Color code conductor insulation as follows:

SYSTEM VOLTAGE

Conductor 208Y/120 480Y/277

Phase A Black Brown

Phase B Red Orange

Phase C Blue Yellow

Neutral White Natural Gray

Neutrals shall be colored-distinguished if circuits of two voltage systems are used in the same raceway.

3. Where two voltage systems are combined in an enclosure;

CONTRACTOR shall apply a permanent color code label where the circuits originate.

B. Signal Systems: Wires for signal systems shall be color-coded and installed under observation of the Project Inspector. Except where otherwise specified, color-coding shall be as follows:

EDIT NOTE: IN NEW SCHOOLS AND SOME EXISTING SCHOOLS THE PROGRAM

SIGNAL IS THROUGH THE PA SYSTEM; PROGRAM BELLS ARE NOT PRESENT.

DELETE REFERENCE TO PROGRAM BELLS AS NEEDED.

SYSTEM COLOR CODE

Clocks Pink, Gray and Orange

Program Bells (some existing elementary schools)

White (Common)Black

Initiating Devices (Non- Addressable)

Red (+) and Black (-)

Program Bells (some existing

White (120 volt, common) Black (C.R. program) Blue (Shop program) Brown (Gym program) Yellow (Auditorium fire alarm)

26 05 19

Revised: 01/07/22 Page 7 of 8 Low-Voltage Wires 600 Volt AC Section 26 05 19 secondary schools)

Fire Alarm Horns Pink (+) and Gray (-)

Fire Alarm Strobes Orange (+) and Blue (-)

Un-Interruptible 24 Volt Power (Annunciator, Water Flow, and Audible Device)

Yellow (+) and White (-)

Note: A single white wire may be common to both

Interruptible 24 Volt Power (4 wire smoke detectors, duct detectors)

Brown (+) and White (-)

Note: A single white wire may be common to both

Switch-Leg Sprinkler Bell (Between water flow and audible device)

Violet (+) and White (-)

Door Holding Magnets (Non Power Limited)

Black (+) and White (-)

3.03 FEEDER IDENTIFICATION

A. Feeder wires and cables shall be identified at each point the conduit run is broken by a cabinet, box, gutter, etc. Where terminal ends are available, identification shall be by means of heat shrink wire markers, which provide terminal strain relief. Markers shall be by Tyco Electronics, Panduit, Brady Perma-Sleeve, or equal. Identification in other areas shall be by means of wrap-around tape markers from E-Z Code, Brady Perma-Code or equal.

Markers shall include feeder designation, size, and description.

3.04 TAPE AND SPLICE KITS

A. Splices, joints, and connectors joining conductors in dry and wet locations shall be covered with insulation equivalent to that provided on conductors.

Free ends of conductors connected to energized sources shall be taped.

Voids in irregular connectors shall be filled with insulating compound before taping. Thermoplastic insulating tape approved by UL, NRTL, or equal for installation as sole insulation of splices shall be furnished and shall be installed according to manufacturer's printed specifications.

3.05 PROTECTION

A. Protect the Work of this section until Substantial Completion.

3.06 CLEANUP

26 05 19

Revised: 01/07/22 Page 8 of 8 Low-Voltage Wires 600 Volt AC Section 26 05 19

A. Remove rubbish, debris and waste materials and legally dispose of off the Project site.

END OF SECTION