251763_-_Collin_County_Generator_(JV_AS__Cluster_3)_-_Addendum_1.pdf

PDF 608 KB Posted

Attached to
Collin County New Generator Purchase, Generator Replacements and Installations
Solicitation number
2025-081
Issued by
Collin County, Texas

About this file

This document is Addendum #1 for the Collin County Generator Replacement project involving facilities at the Juvenile Center, Animal Shelter, and Cluster 3, issued by MD Engineering, LLP on June 6, 2025. The addendum addresses two key questions regarding generator specifications and equipment removal. For the generators at the Animal Shelter and Juvenile facility, the requirement is to have sufficient fuel to run 24 hours at 100% load, while the Cluster 3 Generator will have an 8-hour day tank replenished from a standalone 3,000-gallon tank installed in a separate project.

The addendum clarifies that all generators, except the temporary generator, are to be removed and disposed of by the contractor, who shall provide a trade-in value for the equipment. The Automatic Transfer Switches (ATS) will be handled differently at each location: the Cluster 3 ATS will be removed and replaced, the Juvenile facility's ATS will be disconnected and turned over to the County, and the Animal Shelter's existing manual ATS will remain in place. The contractor will be responsible for disconnecting and reconnecting fuel oil supply and return piping, and transferring current transformer (CT) components as specified in the contract documents.

View the file

Other files

File Type Posted
Collin_County_New_Generator_Purchase,_Generator_Replacements_and_Installations_(Addendum_#2_Revision).pdf PDF
Collin_County_New_Generator_Purchase,_Generator_Replacements_and_Installations_(Addendum_#2_Revision).pdf PDF
2025-081_Pre-Bid_Sign_In_Sheet_-_5.29.2025.pdf PDF
2025-081_Pre-Bid_Sign_In_Sheet_-_5.27.2025.pdf PDF
2025-081_Pre-Bid_Sign_In_Sheet_-_5.27.2025.pdf PDF
2025-081_Pre-Bid_Sign_In_Sheet_-_5.29.2025.pdf PDF
251763_-_Collin_County_Generator_(JV_AS__Cluster_3)_-_Addendum_1.pdf PDF
LEGAL_NOTICE_2025-081.pdf PDF
LEGAL_NOTICE_2025-081.pdf PDF
005213_Construction_Agreement_-_2025-081.pdf PDF
005213_Construction_Agreement_-_2025-081.pdf PDF
006119_Maintenance_Bond.pdf PDF
006119_Maintenance_Bond.pdf PDF
251763_CCADF_C3,_Juv,_&_AS_-_Generator_Replacement_BOOK_of_Specifications.pdf PDF
251763_CCADF_C3,_Juv,_&_AS_-_Generator_Replacement_BOOK_of_Specifications.pdf PDF
004313_Bid_Bond.pdf PDF
006111_Performance_Bond.pdf PDF
006113_Payment_Bond.pdf PDF
006111_Performance_Bond.pdf PDF
006113_Payment_Bond.pdf PDF
251763_CCADF_C3,_Juv,_&_AS_Generator_Replacements_-_Design_Drawings.pdf PDF
Form_W-9.pdf PDF
004325_Product_Substitution_Request_Form.pdf PDF
Conflict_of_Interest_Questionnaire.pdf PDF
Form_W-9.pdf PDF
004313_Bid_Bond.pdf PDF
Conflict_of_Interest_Questionnaire.pdf PDF
004325_Product_Substitution_Request_Form.pdf PDF
251763_CCADF_C3,_Juv,_&_AS_Generator_Replacements_-_Design_Drawings.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1255 W. 15th Street, Suite 300 Plano, Texas 75075 www.md-eng.com (TBPE F-7489) P:469.467.0200 F 469.467.0300

ADDENDUM #1

PROJECT TITLE: Collin County Generator Replacement – Juvenile, Animal Shelter, Cluster 3

MD PROJECT #: 251763

DATE: June 6, 2025

QUESTIONS

Question No.1 – What is the run time (or day tank size) for the generators to be furnished and installed on the project Response: The generators located at the Animal Shelter and Juvenile facility are to have enough fuel to run 24 hours at 100% load. Cluster 3 Generator shall have an 8-hour day tank that is replenished from the standalone 3,000-gallon tank installed as part of another project. This contractor shall disconnect the fuel oil supply and fuel oil return piping from the generator to be removed and modify/reconnect the fuel oil supply and return piping to the new generator.

Question No.2 – What equipment is to be turned over to the County Response: All Generators, except for the temporary generator, are to be removed and disposed by contractor. Bidders shall provide trade-in value for any generator and equipment being removed from site.

The Automatic Transfer Switches (ATS) at Cluster 3 is to be removed by the contractor and replaced with a new ATS. The ATS at Juvenile is to be disconnected and turned over to the County. As indicated in the document, the CT’s in the current ATS are to be removed and reinstalled in the new ATS as indicated in the contract documents. The existing ATS at the animal shelter is a manual ATS and is be left in place. The new ATS for the Animal Shelter will be installed near the new generator as indicated on the documents.

This concludes Addendum 1 items for the referenced project.

Sincerely, MD Engineering, LLP

Michael Smith, PE LEED®AP 6/6/25

President http://www.md-eng.com/

File details come from the government source that posted it. Updated .