25-8404_Attachment_2_IQ_GST_Tank_Information.pdf

PDF 138 KB Posted

Attached to
Water Ground Storage Tank Cleaning and Inspection
Solicitation number
25-8404
Issued by
Collier County, Florida

About this file

The document is a detailed tank information sheet for Collier County, Florida, prepared for the Public Utilities Department (PUD) Wastewater - Irrigation Quality Division's Ground Storage Tank (GST) Cleaning and Inspection project. The sheet provides comprehensive specifications for seven water storage tanks located at different sites, including Countryside, Foxfire, Glades, Royal Palm, and P-Bay locations. Each tank entry includes critical details such as storage capacity (ranging from 0.5 MG to 2.5 MG), dimensions, tank elevations, overflow levels, operational shutoff levels, and the year the tank was last painted.

The tanks vary in size and specifications, with dimensions ranging from 17' to 24' and storage capacities between 0.5 and 2.5 million gallons. The document notes that all tanks will trigger an alarm 0.5 feet over the Operational Shutoff Level, with a specific callout that GST 2 & 3 lack the redundancy of shutting down via float and can only be stopped via MOV (Motor Operated Valve). The most recent tank paintings occurred between 2019 and 2024, indicating ongoing maintenance and infrastructure upkeep. The document serves as a critical reference for understanding the physical characteristics and operational parameters of the county's ground storage tank infrastructure.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Site Dimensions Storage Capacity

Tank Elevations

Year Painted

Overflow 24.000 Area of top of tank High-High / Float Shut off Level 23.000 5,153 ft2

Countryside 0.925 MG High level 22.500 Circumference 4701 Santa Barbara BLVD Operation Shutoff Level 22.000 255 ft

Floor 0.000 Area of Walls 6,120 ft2

Overflow 19.000 Area of top of tank High-High / Float Shut off Level 18.000 8,012 ft2

Foxfire 1.1 MG High level 17.500 Circumference 5500 Radio RD Operation Shutoff Level 17.000 318 ft

Floor 0.000 Area of Walls 6,042 ft2

Overflow 18.500 Area of top of tank High-High / Float Shut off Level 17.500 14,103 ft2

Glades 2.000 MG High level 17.000 Circumference 105 Palm DR Operation Shutoff Level 16.500 421 ft

Floor 0.000 Area of Walls 6,947 ft2

Overflow 23.000 Area of top of tank High-High / Float Shut off Level 22.000 8,012 ft2

Royal Palm 1.3 MG High level 21.500 Circumference 5630 Warren ST Operation Shutoff Level 21.000 318 ft

Floor 0.000 Area of Walls 7,314 ft2

Overflow 20.000 Area of top of tank High-High / Float Shut off Level 19.000 16,742 ft2

P-Bay Gst - 1 20.5' 2.500 MG High level 18.500 Circumference 6200 Watergate WAY Operation Shutoff Level 18.000 459 ft

Floor 0.000 Area of Walls 9,410 ft2

Overflow 17.000 Area of top of tank High-High / Float Shut off Level 16.000 3,849 ft2

P-Bay Gst - 2 17' 0.500 MG High level 15.500 Circumference 6200 Watergate WAY Operation Shutoff Level 15.000 220 ft

Floor 0.000 Area of Walls 3,740 ft2

Overflow 17.000 Area of top of tank High-High / Float Shut off Level 16.000 3,849 ft2

P-Bay Gst - 3 17' 0.500 MG High level 15.500 Circumference 6200 Watergate WAY Operation Shutoff Level 15.000 220 ft

Floor 0.000 Area of Walls 3,740 ft2

Note: All tanks will Alarm .5 feet over Operational Shutoff Level GST 2 & 3 do not have the redundancy of shutting down via float-only via MOV

24' 81'

19'

16.5'

23'

101'

146'

70'

70'

GST Information

File details come from the government source that posted it. Updated .