240130_Question and Answers.docx
DOCX document 14 KB Posted
- Solicitation number
- S-73000-00009217
- Issued by
- Douglas County, Oregon
About this file
This document contains the questions and answers from the pre-bid meeting for Bid S-73000-00009217 for the Shady Maintenance Station Fire Protection System project in Roseburg, Oregon. The project consists of the installation of a fire protection system in the north end of the ODOT Shady Maintenance Station Building 2. The bid document addresses several contractor questions, including whether rooms will be emptied for construction, the requirement for temporary toilet facilities, the availability of a contractor staging area, and the selection of fitting types for underground fire sprinkler service piping. The bid plans for the existing maintenance building are also noted to be available and posted on OregonBuys.
The related state and local contract opportunity is for the Shady MS Bldg 02 Fire Protection Installation REBID project, which is located in Douglas County, Oregon. No additional details on pricing, set asides, incumbents, funding, or other salient information are provided in the given materials.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AttE_COBID_CoachingSrvcs_Intproc~1.docx | DOCX document | |
| 35909 Attachments.docx | DOCX document | |
| Preliminary Results posted.xlsx | XLSX spreadsheet | |
| Reference Drawings Shady Crew Room Remodel.pdf | ||
| Prebid meeting sign in sheet.pdf | ||
| Reference Drawings Exisiting Shady_Shop_1984.pdf | ||
| Exhibit B Specifications.pdf | ||
| 35909 RFCQ.docx | DOCX document | |
| Exhibit A Plans.pdf | ||
| ADD 1 ODOT Shady Maintenance Station Install Fire Protection System.docx | DOCX document | |
| ADD 1 SHADY MS FIRE PROTECTION_ PLAN A101 REV1 012524.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BID S-73000-00009217
SHADY MAINTENANCE STATION FIRE PROTECTION SYSTEM PREBID MEETING
QUESTIONS AND ANSWERS
QUESTION: If existing ceilings in offices, restrooms, or enclosed spaces must be removed to install fire sprinklers, will rooms be emptied for construction?
ANSWER: Yes, ODOT will remove furniture and other items from rooms as required for construction to occur. Spaces will only be vacated during construction activities in the space directly. Contractor will need to coordinate schedule with the ODOT Construction Project Manager.
QUESTION: Is contractor required to provide temporary toilet facilities?
ANSWER: Yes, contractor is required to provide temporary toilet facilities.
QUESTION: Will a contractor staging area be available?
ANSWER: Yes, adequate area will be available for contractor staging. Contractor will need to coordinate specific area needs and location with the ODOT Construction Project Manager.
QUESTION: Can contractor select fitting types for underground fire sprinkler service piping?
ANSWER: Contractor may select fitting types for underground fire sprinkler service piping unless a specific type is noted on the drawings or in the specifications.
QUESTION: Are plans available for the existing maintenance building?
ANSWER: Yes, plans for the existing maintenance building are available and will be posted on OregonBuys.