231030 LANC 898-034 MX Bid Docs 2 of 5.pdf
PDF 7 MB Posted
- Solicitation number
- 36C78624B0023
About this file
This document appears to be a set of bid documents for a federal contract opportunity to replace a storage building at the Los Angeles National Cemetery. The documents include mechanical and plumbing drawings, equipment schedules, details, and specifications.
The key details are:
- The solicitation number is 36C78624B0023 and the name is "Y1EB--Los Angeles CA 898 -034 Maint, 036 FCA (VA-24-00060981)".
- The contract is for the replacement of a storage building at the Los Angeles National Cemetery, managed by the Department of Veterans Affairs National Cemetery Administration.
- The mechanical drawings show the new HVAC system, including a floor-mounted air handler, ductless AC units, heat pumps, and an energy recovery ventilator. Plumbing drawings detail the new domestic water, sanitary, and condensate drain systems.
- Equipment schedules are provided for mechanical and plumbing systems, including make, model, capacity, and electrical data.
- The bid documents provide details and specifications for the mechanical and plumbing installations.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
DUCTWORK SYMBOLS
ACU
AFF
AD
AHU
AL
BHP
BOD
BTU
BOP
BTUH
CA
CFM
CD
CONT.
COR
CU
D
DX
ENT
EXH
EMCS
FB
°F
FCU
F.G.
FD
FLEX
FPM
FS
FT.
FT
GPM
GPH
HB
HD
IN
HEPA
IU
KW
KWH
MA
MCC
NA
NO.
NIC
OBD
OA
PRV
PSIG
QTY
QUAD
Rh R.A.
RS
RL
ST
SP
RPM
SCD
SDVV
TOPT
TP
TYP.
V
VAC
VAV
VTR
VEL
QUANTITY
QUADRANT
RETURN AIR
REVOLUTIONS PER MINUTE
RELATIVE HUMIDITY
REFRIGERATION LIQUID
REFRIGERATION SUCTION
SMOKE CONTROL DAMPER
SINGLE DUCT VARIABLE VOLUME
STATIC PRESSURE (INCHES OF WATER)
SOUND TRAP
SIDEWALL SUPPLY REGISTER
TOP OF PIPE TRAPEZE
TOTAL PRESSURE (INCHES OF WATER)
TYPICAL
VOLTS
24"x12"
VOLTS, ALTERNATING CURRENT
VARIABLE AIR VOLUME
VENT THRU ROOF
VELOCITY
24"/12"
12"Ø
SD
24x12
12"Ø
24x12Ø
SD
EQUIPMENT SYMBOLS
DUCT MOUNTED SMOKE DETECTOR
XX-##
DUCT MOUNTED STATIC PRESSURE PROBE
ACCESS DOOR
SIDEWALL GRILLE DIMENSION WHERE
SHOWN ON PLANS
T
H
CO2
SEE CONTROL DRAWINGS FOR TYPE
ROOM THERMOSTAT/TEMP. TRANSMITTER LOCATION ONLY
ROOM HUMIDISTAT/HUMIDITY TRANSMITTER LOCATION ONLY
SEE CONTROL DRAWINGS FOR TYPE
ROOM CARBON DIOXIDE TRANSMITTER LOCATION ONLY
SEE CONTROL DRAWINGS FOR TYPE
##x##
XX-#
SYMBOL INDICATES GRILLE OR DIFFUSER
IDENTIFIED IN EQUIPMENT SCHEDULE
CFM
F. SEE SPECIFICATION SECTION 230593, TESTING, ADJUSTING, & BALANCING OR
MECHANICAL SYSTEMS FOR ADDITIONAL DESCRIPTION AND REQUIREMENTS.
G. ALL TEST AND MEASUREMENT TRAVERSE LOCATIONS SHALL BE CLEARLY NOTED ON
FLOOR PLANS WHICH SHALL BE INCLUDED WITH THE TEST AND MEASUREMENT DATA.
H. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL TRADES
INCLUDING MECHANICAL, PLUMBING, ELECTRICAL, FURNITURE, AND ARCHITECTURAL.
ANY DISCREPANCIES SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT PRIOR
TO START OF WORK.
I. ALL NEW TO EXISTING DUCT CONNECTIONS SHALL BE FIELD VERIFIED PRIOR TO
ORDERING AND FABRICATING NEW DUCTWORK OR DAMPERS
LETTERS REFER TO THE EQUIPMENT TYPE
NUMBERS REFER TO SPECIFIC EQUIPMENT
SYMBOL INDICATES EQUIPMENT IDENTIFIED
IN EQUIPMENT SCHEDULE
DUCT TRANSITION FROM RECTANGULAR TO ROUND
DUCT TRANSITION
INDICATES A 24"x12" RECTANGULAR DUCT (WIDTH x DEPTH)
INDICATES A 12" ROUND DUCT
INDICATES A 24"x12" FLAT OVAL DUCT (WIDTH x DEPTH)
DOWN DIRECTION PITCH
DIRECTION OF FLOW
DEMO
EXISTING
DETAIL NUMBER LOCATION
SECTION LETTER LOCATION A1
A1
SCALE
SECTION
A. THE DEMOLITION DRAWINGS REFLECT INFORMATION ON EXISTING BUILDING
SERVICES GATHERED BY SITE INSPECTION, DISCUSSIONS WITH MAINTENANCE
PERSONNEL AND PREVIOUS CONSTRUCTION DRAWINGS. THE EXACT LOCATION,
ARRANGEMENT, AND SIZES OF PIPE LINES AND DUCTWORK IN THE EXISTING BUILDING
MAY BE DIFFERENT FROM THAT SHOWN ON THESE DRAWINGS.
SCALE
DETAIL
B. THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OF EXISTING BUILDING
SERVICES FOR REMOVAL WITH OWNER AUTHORIZED REPRESENTATIVE AND SHALL
CONFORM TO THEIR REQUIREMENTS.
C. DISRUPTION OF NORMAL FACILITY ACTIVITIES ARE TO BE KEPT TO AN ABSOLUTE
MINIMUM. DUST, DEBRIS, AND FUMES SHALL BE CONTROLLED SO AS NOT TO AFFECT
THE HEALTH AND SAFETY OF OCCUPIED AREAS WITHIN THE FACILITY WHICH ARE
OUTSIDE THE AREA OF WORK. COORDINATE WITH THE ARCHITECT AND THE
OWNER'S REPRESENTATIVE WITH REGARD TO ALL ACTIVITIES TO BE CONDUCTED
OUTSIDE OF THE SUITE REMODEL AREA WHICH MAY AFFECT THE OPERATION OF THE
FACILITY.
D. THE CONTRACTOR SHALL PROVIDE TEMPORARY VENTILATION (MAINTAIN WORK ZONE
AT NEGATIVE PRESSURE), FILTRATION, AIR PURIFIERS, DUST SCREENS, ETC. FOR ALL
WORK AREAS AFFECTED BY DEMOLITION FOR NEW INSTALLATION TO MINIMIZE DUST
AND FUMES.
E. THE CONTRACTOR SHALL PRESENT AN AREA BY AREA WORK PLAN WELL IN ADVANCE
TO THE ARCHITECT AND THE OWNER'S AUTHORIZED REPRESENTATIVE FOR
APPROVAL PRIOR TO BEGINNING WORK. THE WORK PLAN SHALL INCLUDE AN
OUTLINE OF ALL ACTIVITIES OF ALL SUBCONTRACTORS. THE CONTRACTOR SHALL
COORDINATE WITH THE OWNER'S AUTHORIZED REPRESENTATIVE TO ESTABLISH
ACCEPTABLE ROUTING AND ACCESS WITHIN THE FACILITY FOR MATERIALS REQUIRED
FOR THE NEW INSTALLATION.
SIDEWALL EXHAUST OR RETURN AIR GRILLE
OR REGISTER
CEILING RETURN AIR REGISTER OR GRILLE
CEILING EXHAUST REGISTER
ENTERING
EXHAUST
ENERGY MANAGEMENT CONTROL SYSTEM
DEGREES FAHRENHEIT
FLAT BOTTOM
FLOOR DRAIN
FAN COIL UNIT
FILTER GAUGE
FLEXIBLE
FEET PER MINUTE
FLOOR SINK
FEET
FLAT TOP
GALLONS PER MINUTE
GALLONS PER HOUR
HOSE BIBB
HIGH EFFICIENCY PARTICULATE AIR (FILTER)
HAND DAMPER (VOLUME DAMPER)
INCHES
INDOOR UNIT
KILOWATT
MAIN AIR (CONTROLS)
KILOWATT HOUR
MOTOR CONTROL CENTER
NUMBER (QUANTITY)
NOT IN CONTRACT
NOT APPLICABLE
OPPOSED BLADE DAMPER
OUTSIDE AIR
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH GAGE
PERFORATED FACE CEILING DIFFUSERS
HWS
HWR
CHS
CHR
STAMPED FACE CEILING DIFFUSERS
V
D
CD
MU
RS
RL
R
TWS
TWR
TWB
MPS
HPS
LPS
HPR
HPR
LPR
CND
PC
GWS
GWR
HEATING WATER RETURN
HEATING WATER SUPPLY
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DRAIN
CONDENSATE DRAIN
MAKE-UP WATER
VENT
REFRIGERATION LIQUID
REFRIGERATION SUCTION
REFRIGERATION
TOWER WATER BYPASS
TOWER WATER RETURN
TOWER WATER RETURN
STEAM - HIGH PRESSURE SUPPLY
STEAM - HIGH PRESSURE RETURN
STEAM - MEDIUM PRESSURE SUPPLY
STEAM - LOW PRESSURE SUPPLY
CONDENSER WATER
PUMPED CONDENSATE
GEOTHERMAL SUPPLY
GEOTHERMAL RETURN
SECTION AND DETAIL TITLES
STEAM - MEDIUM PRESSURE RETURN
STEAM - LOW PRESSURE RETURN
DRAWING NUMBER WHERE DETAILED
SECTION LOCATION
DETAIL SYMBOL
DETAIL LOCATION
DRAWING NUMBER WHERE DETAILED
X#/X###
M301 A1
SECTION SYMBOL
B
M
RETURN DUCT
PIPING SYMBOLS
EXHAUST DUCT
MECHANICAL PIPING
SUPPLY DUCT
EXISTING DUCT TO BE REMOVED
FLEXIBLE CONNECTION
RISE IN DUCT
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES
EXCEPT TRANSFER AIR SOUND ELBOW)
SHORT RADIUS ELBOW (PROVIDE ALL
SQUARE OR RECTANGULAR ELBOWS WITH
VANES EXCEPT TRANSFER AIR SOUND
ELBOW)
STANDARD LONG RADIUS ELBOW
3/4" BALL VALVE WITH ADAPTER
TO 3/4" HOSE THREAD
DIAPHRAGM VALVE
BUTTERFLY VALVE
BALL VALVE
VALVE IN RISE
WATER FLOW MEASURING DEVICE
CIRCUIT SETTER
F
S
SOLENOID VALVE
POINT OF CONNECTION, NEW DUCT TO EXISTING DUCT
OR / POINT OF REMOVAL FROM EXISTING DUCT TO DEMO DUCT
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
ACCESS DOOR
AIR HANDLING UNIT
ACOUSTIC LINING
BRAKE HORSEPOWER
BOTTOM OF DUCT
BOTTOM OF PIPE
BTU PER HOUR
BRITISH THERMAL UNIT
COMPRESSED AIR
CUBIC FEET PER MINUTE
CONDENSATE DRAIN
CONTINUATION
CONTRACTING OFFICER'S REPRESENTATIVE
CONDENSING UNIT
DRAIN
DIRECT EXPANSION
S.DPR
F.DPR
F/S DPR
COMBINATION FIRE/SMOKE DAMPER
PRESSURE REDUCING VALVE
2HR. SMOKE BARRIER
SMOKE BARRIER
2HR. FIRE BARRIER
1 HR. FIRE BARRIER
M
VERIFY WITH
ARCHITECTURAL
DRAWINGS
M
3-WAY
MODULATING
CONTROL VALVE
A
2-WAY CONTROL VALVE
SAFETY VALVE OR
PRESSURE RELIEF
VALVE
P
PS PS
GAUGE - DIFFERENTIAL
GAUGE - PRESSURE
GAUGE - PRESSURE WITH COCK
GAUGE - TEMPERATURE
HS
PS
TS
PIPE ANCHOR
PIPE EXPANSION JOINT
PIPE GUIDE
SENSOR - FLOW
SWITCH - FLOW
SWITCH HUMIDITY
SWITCH - PRESSURE
SWITCH - TEMPERATURE
TEMPERATURE - PRESSURE TEST FITTING
THERMOMETER
THERMOMETER WELL
BASKET STRAINER
STEAM TRAP INVERTED BUCKET
METER - TOTALIZING BTU
METER - TOTALIZING FLOW
AIR VENT - AUTOMATIC
AIR VENT - MANUAL
G. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL FIRE
RATED AND/OR SMOKE RATED WALLS AND ASSEMBLIES. PROVIDE APPROVED
FIRE DAMPERS IN ALL REQUIRED PENETRATIONS FOR DUCTWORK, GRILLES,
REGISTERS AND DIFFUSERS. ALL PIPE AND DUCTWORK PENETRATIONS OF FIRE,
SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT
STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL.
H. CONTRACTOR SHALL COORDINATE ALL DUCTWORK, PIPING, PLUMBING AND
FIRE PROTECTION PIPING WITH STRUCTURAL AND ELECTRICAL SYSTEMS AND
SHALL PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
EQUIPMENT ACCESS AND SERVICEABILITY.
I. CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS,
SLEEVES, AND HANGING DEVICES FOR INSTALLATION OF MECHANICAL AND
PLUMBING EQUIPMENT, DUCTWORK AND PIPING, ETC. CONTRACTOR SHALL
COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOID
CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.
J. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY
MISCELLANEOUS ANGLES, CHANNELS, UNISTRUT, ETC., AS MAY BE REQUIRED TO
ADEQUATELY SUPPORT THE MECHANICAL PIPING, DUCTWORK, AND EQUIPMENT
IN A MANNER APPROVED BY THE ARCHITECT, WHICH WILL NOT OVERLOAD THE
BUILDING STRUCTURAL SYSTEM.
K. CONTRACTOR SHALL PROVIDE RETURN AIR OR TRANSFER AIR OPENINGS IN
FULL HEIGHT WALLS SIZED AT 350 FPM (UNLESS OTHERWISE SPECIFICALLY
SHOWN ON THE DRAWINGS) TO CREATE AND/OR MAINTAIN A RETURN AIR PATH AS
REQUIRED. FIRE DAMPERS AND/OR SMOKE DAMPERS SHALL BE PROVIDED IN
SUCH OPENINGS WHERE REQUIRED BY NOTE "J".
L. SEAL ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, DUCT WALL
PENETRATIONS AND FITTING CONNECTIONS ON ALL DUCT SYSTEMS.
M. MECHANICAL ITEMS SUCH AS ROOF DRAINS, FLOOR DRAINS, PLUMBING FIXTURES,
ETC. SHOWN ON THE ARCHITECTURAL DRAWINGS BUT NOT SHOWN ON THE
MECHANICAL DRAWINGS SHALL BE INCLUDED IN THE PROJECT. THESE ITEMS
SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR INCLUSION IN
ADDENDUM.
N. IT IS CRITICAL THAT THE CONTRACTOR PERFORM A COMPLETE REVIEW OF ALL
SUBMITTALS PRIOR TO SUBMISSION TO THE AE/COR. INCOMPLETE, INCORRECT
AND UNCLEAR SUBMITTALS WILL BE REJECTS AND MARKED AS "REVISE AND
RESUBMIT". ALL SUBMITTALS MUST CLEARLY INDICATE THE EQUIPMENT
SELECTIONS FOR THE PROJECT. TECHNICAL DRAWINGS OF COMPLETE
ASSEMBLIES, REFLECTING ACCURATE PROJECT CONDITIONS, SHALL BE
SUBMITTED WITH EQUIPMENT SELECTIONS TO ENSURE SPACE ALLOWANCES ARE
REFLECTED IN THE ACTUAL SPACE AVAILABLE. WHERE SIZE DEVIATIONS DIFFER
FROM THE BASIS OF DESIGN CONTRACTOR SHALL HIGHLIGHT THE DIFFERENCES
FOR AE/COR REVIEW WITHIN THE SUBMITTAL. CONTRACTOR SHALL PROVIDE
INSTALLATION ROUTE AND VERIFICATION THAT ACCESS POINTS, PLACEMENT
ROUTE, SUPPORTS, AND REQUIRED EQUIPMENT CLEARANCES ARE IDENTIFIED ON
THE ROUTE DRAWING. SAFETY PROTOCOLS FOR SUBJECT STATION SHALL BE
REFLECTED ON EQUIPMENT CLEARANCES. PLATFORMS AND INTERFACE AREAS
(FILTER, GAUGES, MONITORS, VALVES, ETC.) SHALL HAVE PROPER CLEARANCE AS
DEFINED BY THE MANUFACTURER, VA SAFETY PERSONNEL AND SERVICE
PERSONNEL. ACCESS POINTS OF USE SHALL BE CLEARLY IDENTIFIED ON THE
DRAWINGS.
GENERAL DEMO NOTES
PIPE REDUCER - ECCENTRIC
PIPE STRAINER
UNION - SCREWED
FIRE DAMPER
SMOKE DAMPER
CHECK VALVE
PLUG VALVE
ACOUSTICAL DUCT LINING
FLEXIBLE DUCT
MANUAL BALANCING DAMPER
GATE VALVE
MECHANICAL SYMBOL LEGEND
VALVE SYMBOLS
GLOBE VALVE
ELBOW - DROP TO TEE
TEE - DROP FROM TEE
END CAP
FLEX CONNECTION
PIPE REDUCER - CONCENTRIC
GENERAL NOTES
FITTING SYMBOLS
ELBOW - DOWN
ELBOW - UP
PIPE RISE-DROP
A. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN
FURRED CHASES OR SUSPENDED CEILINGS, UNLESS OTHERWISE NOTED.
B. PROVIDE ACCESS PANELS OR DOORS IN INACCESSIBLE CEILINGS AND/OR
CHASES FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS, COILS, FANS,
CONTROLS, ETC. THEY SHALL BE FURNISHED UNDER DIVISION 23 AND
INSTALLED UNDER THE ARCHITECTURAL SPECIFICATION. ACCESS DOOR RATING
SHALL MATCH CLASSIFICATION OF WALL AND CEILING FIRE RATING.
C. COORDINATE THE LOCATION OF ALL DIFFUSERS, GRILLES, REGISTERS, ACCESS
DOORS, ETC., WITH THE ARCHITECTURAL REFLECTED CEILING PLAN(S).
D. ALL ROUND RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL
SIZE AS THE SCHEDULED DIFFUSER NECK SIZE.
E. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR
INDICATED. ALL DUCT SIZES SHOWN ON DRAWINGS ARE NET INSIDE DIMENSIONS.
PROVIDE ONE INCH ACOUSTICAL LINING (TYPE D3 INSULATION) IN LOW VELOCITY
RECTANGULAR DUCTWORK FOR THE FIRST 10 DIAMETERS OF DUCTWORK
CONNECTED TO DEVICE, OR AS INDICATED ON DRAWINGS, WHICHEVER IS
GREATER. FOR THE REMAINDER OF THIS DUCTWORK PROVIDE AS INDICATED IN
THE INSULATION SPECIFICATIONS.
F. PROVIDE 1/2" MANUAL AIR VENTS AT ALL HIGH POINTS OF CLOSED SYSTEM PIPING
AND 1/2" MANUAL DRAIN VALVES WITH HOSE CONNECTION AT LOW POINTS AS
REQUIRED TO PROVIDE COMPLETE SYSTEM DRAINAGE. WHERE DRAIN VALVES
OCCUR ABOVE CEILING AREAS AND IN AREAS OUTSIDE MECHANICAL RANGE
PROVIDE HOSE CONNECTION ON VALVE.
ELECTRICAL DISCONNECT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
M-001
MECHANICAL SYMBOLS &
Fridge
FD
FD
1. NEW FLOOR MOUNTED AIR HANDLER
2. NEW WALL MOUNTED DUCTLESS AC UNIT
(NOT ALL KEYED NOTES USED ON THIS SHEET)KEYED NOTES:
3. NEW HEAT PUMP OUTDOOR UNIT
4. NEW ERV UNIT
5. 12x10 TRANSFER DUCT WITH TITUS 350R (12x10)
6. ROOF MOUNTED INTAKE VENT 24"DIA.
7. UNIT HEATER, MOUNT MIN. 9FT ABOVE FINISHED FLOOR
8. 6"Ø WALL TERMINATION VENT WITH BIRD SCREEN AND BACKDRAFT
DAMPER
9. 8"Ø WALL TERMINATION VENT WITH BIRD SCREEN AND BACKDRAFT
DAMPER
10. CEILING TYPE EXHAUST FAN IN STORAGE AREA, PROVIDE WITH
WALL SWITCH.
11. REFRIGERANT LINE SET BUNDLED WITH 34" CONDENSATE DRAIN.
12. OUTDOOR AC UNIT, COOLING ONLY.
EF-01
HP-02
IU-01
EF-03
EF-01
AC-01
HP-01CU-01
AHU-01
ERV-01
EWH-01
EF-02
EF-04
EF-01
60E
60E 50E
450E 450E
EH-01
EH-01
EH-01
CD-02
CD-02 CD-02
CD-02
CD-02
CD-02
CD-01
CD-01
RG-01
EG-02
EG-02
EG-02
CD-01
EG-01 EG-01
8 9
8Ø
8Ø
8Ø
6Ø
4Ø
6Ø
4Ø
4Ø
4Ø
8Ø
16x1210x1210x10
8Ø
6Ø 8Ø
8Ø
8Ø 8Ø x1
MH101
HVAC FLOOR PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
M-501
MECHANICAL DETAILS
PIPE CLAMP
SEE PLANS FOR
PIPE TYPE , SIZE,
AND LOCATION
ROOF
A6 ABOVE ROOF PIPE SUPPORT
NTS
4 4 10
1 3 3
PREPOSITIONED SLEEVE PREPOSITIONED SLEEVE
7 6
ROOF SUPPORT AS
MANUFACTURED BY C-PORT,
CB10, 28" LONG OR EQUIVALENT.
SEE SPECIFICATION FOR
SPACING
4 4 10
CORE DRILLED SLEEVE
FOR 1-1/4" AND LARGER
CORE DRILLED SLEEVE 12
C6 TYPICAL CONDENSATE DRAIN TRAP
NTS C8 PIPE PENETRATION DETAIL
NTS
1 2
E8
3 2
SPLIT SYSTEM DX REFRIGERANT PIPING
NTS
PAD MOUNTED CONDENSING UNIT, 4" CONCRETE PAD
INDOOR UNIT, DIRECT EXPANSION (DX) COIL.
DISTRIBUTION NOZZLE
GLOBE VALVES AT OUTDOOR UNIT.
SWING JOINT.
PIPE PENETRATION THROUGH ROOF, SEE PIPING THRU ROOF
DETAIL ON THIS SHEET.
REFRIGERANT SUCTION LINE
REFRIGERANT LIQUID LINE
SIGHT GLASS
REMOTE BULB
FILTER
LIQUID CHARGING VALVE
STRAINER
SOLENOID VALVE TO BE LOCATED AS CLOSE
TO EXPANSION VALVE AS POSSIBLE.
EXPANSION VALVE
CONCRETE STRUCTURE
PIPE SLEEVE SIZED FOR PIPE WITH INSULATION
WATERSTOP
EXTEND SLEEVE 4" ABOVE FINISHED FLOOR LEVEL
MINIMUM 18" LONG ALUMINUM INSULATION JACKET
INSULATION-SEE SPECS FOR THICKNESS
PIPE
SEAL WITH WATERPROOF CAULKING
MINIMUM 34" POURED LEAD
MULTI-COMPONENT PLASTIC CEMENT
PIPE SLEEVE (I.D. MIN 1" LARGER THAN O.D. OF
PIPE)
WATERPROOF GROUT
CORE DRILL MIN 1" LARGER HOLE THAN O.D.OF PIPE
SLEEVE
NOTES:
1. SEAL SLEEVE WITH UL RATED SEALANT TO MATCH
RATING OF WALL OR CEILING. MAINTAIN REQUIRED
MINIMUM CONTACT OF SEALANT AND CLEARANCES OF
PIPE IN PENETRATION.
2. PROVIDE ESCUTCHEON PLATES AT ALL EXPOSED
PENETRATIONS.
3"MIN TRAP
2% SLOPE
SPILL CONDENSATE
DRAIN PIPING TO
DRYWELL
SOLDER ALL JOINTS
AS REQUIRED, (TYP)
VENT OPEN TO
ATMOSPHERE LINE CLEANOUT, (TYP)
UNION,
(TYP)
DRAIN SIZE AT
LEAST SAME SIZE
AS NIPPLE
CONNECTION SIZE
NOTES:
1. SEE PLAN FOR PIPE SIZES
2. INTERIOR CONDENSATE DRAINS ABOVE CEILING
SHALL BE INSULATED
3. IF HORIZONTAL RUN IS GREATER THAN 15FT,
INSTALL VENT (same size as drain pipe)
4. CONDENSATE DRAIN CONNECTIONS SHALL
OCCUR ABOVE EQUIPMENT FRAMING TO ALLOW
FOR PROPER P-TRAP INSTALLATION
E3 EQUIPMENT SUPPORT RAIL DETAIL
NTSE1 TYPICAL GROUND MOUNTED CONDENSING UNIT
NTS
MIN. 4" CONCRETE PAD
MIN. 38" EXPANSION BOLT
INTO CONCRETE PAD.
22 GA. GALV.
STEEL FLASHING
COUNTER SUNK BOLTS
(4) MINIMUM AT 16" O.C.
2"x4" NAILER
(TREATED)
3/4" CLEARANCE
FOR ROOFING FELTS
ROOF SURFACE
ROOF INSULATION
6"
TYP.
8" DRIP EDGE
18 GA. GALV. STEEL
CURB. SOLDER ALL
SEAMS AND EDGES
WATER TIGHT.
FIBERBOARD CANT
C-CHANNEL ROOF DECK
TACK WELD TO STEEL
ROOF AND LAG TO
JOISTS (TYPICAL AT
EACH JOIST)
4"
MIN.
INDOOR UNIT
OUTDOOR UNIT
FRONT PANEL
AIR FILTER
GUIDE LOUVER
WALL PIPE
BIND TAPE
POWER CABLE
AIR IN
AIR OUT
AIR IN
AIR OUT
> 24 INCH CLEARANCE
C1 TYPICAL AC/HEAT PUMP SPLIT SYSTEM DETAIL
NTS
PROVIDE ISOLATOR
PADS
REFRIGERANT LINE SET
AND COMMUNICATION
CABLE
CONDENSATE DRAIN
PIPING
C3 FLEXIBLE AIR DUCT CONNECTOR DETAIL
NTS
E6 DUCT ELBOW DETAIL
NTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
M-502
MECHANICAL DETAILS
C6 ROOF MOUNTED EXHAUST FAN DETAIL
NTS
E3 CEILING EXHAUST DETAIL
NTSE1 ROOF INTAKE & RELIEF VENTILATOR DETAIL
NTS
C1 ELECTRIC UNIT HEATER DETAIL
NTS
C3 SPLIT SYSTEM HEAT PUMP DETAIL
NTS
SYMBOL
NO.
MANUFACTURER/MODEL
NO. TYPE
IU-01 MSZ-JP09WA * WALL MOUNTED 310
INDOOR UNIT SCHEDULE
SUPPLY
AIRFLOW
(CFM)
9,000
SOUND
(dBA)
ELECTRICAL DATA
VOLTS PHASE HZ MCA
120 1 60 1.0
WEIGHT
(LBS)
SYMBOL
NO.
MANUFACTURER/MODEL
NO. TYPE CFM
EF-01 GREENHECK SPB90 CEILING 60
EXHAUST FAN SCHEDULE
S.P.
INCH W.C.
0.3
SOUND
(SONES)
1.5
ELECTRICAL DATA
VOLTS PHASE HZ HP
120 1 60 1/25
WIDTH (IN)
14.5
HEIGHT
(IN)
7.25
WEIGHT
(LBS)
10.5
*BASED ON MITSUBISHI
SYMBOL
NO.
MANUFACTURER/MODEL
NO.
SENSIBLE
COOLING
CAPACITY
(BTU/H)
HP-01 SVZ-KP36NA * 33,400 33,400
HEAT PUMP OUTDOOR UNIT SCHEDULE
23,200
SOUND
(dBA)
ELECTRICAL DATA
VOLTS PHASE HZ MCA
208/230 1 60 17.0 31.0
DIM
(IN)
28x33x13
WEIGHT
(LBS)
*BASED ON MITSUBISHI
HEATING
CAPACITY
(BTU/H)
@47°F
HEATING
CAPACITY
(BTU/H)
@17°F MOCP
SYMBOL
NO.
MANUFACTURER/MODEL
NO.
ERV-01 RENEWAIRE EV300 175 78
ENERGY RECOVERY VENTILATOR (ERV) SCHEDULE
73/59
PORT DIA.
(IN.)
ELECTRICAL DATA
VOLTS PHASE HZ MCA
120 1 60 5.0 15
DIM
(IN)
34x44x34
WEIGHT
(LBS)
BLOWER
FAN
(CFM) MOCP
HP-02 MUZ-JP09WA* 9,000 10,900 6,700 49 120 1 60 12.0 15.0 31x12x22 75
SYMBOL
NO.
MANUFACTURER/MODEL
NO.
SENSIBLE
COOLING
CAPACITY
(BTU/H)
CU-01 MUY-GL24NA 22,400 8,200
COOLING ONLY OUTDOOR UNIT SCHEDULE
12.5
SOUND
(dBA)
ELECTRICAL DATA
VOLTS PHASE HZ MCA
208/230 1 60 17.1 20.0
DIM
(IN)
28x33x13
WEIGHT
(LBS)
*BASED ON MITSUBISHI
EER MOCP
SENSIBLE
COOLING
CAPACITY
(BTU/H)
HEATING
CAPACITY
@47degF
(BTU/H)
10,500
MINIMUM
COOLING
CAPACITY
(BTU/H)
AC-01 MSY-GL24NA* WALL MOUNTED 562 22,400 45208/230 1 60 1.0 35N/A
MOCP
1.0
AHU-01 SVZ-KP36NA2* AIR HANDLER 1010 33,400 45208/230 1 60 4.1 13033,400 15
TEMP
(EFF%)
TOTAL EFF%
WINT/SUM
EF-02 GREENHECK G-090-VG ROOF 600 0.35 6.5 120 1 60 1/10 17.0 7.25 18.0
EF-03 GREENHECK G-080-VG ROOF 350 0.35 6.5 120 1 60 1/10 17.0 7.25 18.0
EF-04 GREENHECK G-060-VG ROOF 120 0.25 6.5 120 1 60 1/15 17.0 7.25 18.0
SYMBOL
NO.
MANUFACTURER/MODEL
NO.
EH-01 MODINE HER 30C 380 3.0
ELECTRIC HEATER SCHEDULE
HEAT
THROW
(FT.)
ELECTRICAL DATA
VOLTS PHASE HZ AMPS
240 1 60 12.5 15
DIM
(IN)
14x17x18
WEIGHT
(LBS)
BLOWER
FAN
(CFM) MOCP
HEAT
CAPACITY TEMP RISE
(DEG.F)(KW)
EH-02 BERKO CZ1548T 50 1.5 12 5 240 1 60 6.2 15 9x12x5 10
SYMBOL MANUFACTURER/MODEL
NO.
LOCATION
TYPE
CD-01 TITUS MCD CEILING SUPPLY DIFF
AIR DEVICE SCHEDULE
PANEL
FRAME SIZE
24x24
NECK
SIZE
6Ø
AIR FLOW DATA
MIN MAX APD NC
0 120 0.01 25
OPPOSED
NO
FINISH
TBD
REMARKS
CD-02 TITUS MCD CEILING SUPPLY DIFF 24x24 8Ø 80 240 25 NO EG-01 TITUS 350R DUCT EXHAUST 18x8 18x8 120 550 25 YES EG-02 TITUS 350R CEILING EXHAUST 8x4 8x4 0 120 25 NO
BASIS OF DESIGN MOUNTING
IN x IN IN CFM CFM IN WC
BLADE
DAMPER
RG-01 TITUS 350R CEILING RETURN 30x16 30x16 0 1100
0.01 0.01 0.01
0.01 25 NO
TBD
TBD
TBD
TBD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
M-601
MECHANICAL SCHEDULES
MP
NG
NGMP
NPCW
X
XXX
OFL
OD
RWL
PSD
OFL
OD
RWL
PSD
SS
SD
SS
SSD
TP
TW
V
SINGLE LINE DOUBLE LINE
ABBREVIATION DESCRIPTION
SD
SS
SSD
TP
TW
V
NPHW
NPCW
NPHW
D
DI
DIWS
DIWR
SYMBOL
AV
AW
CA
CND
ABBREVIATION
AV
AW
CA
CW
CD
D
DI
DIWS
DIWR
HW
DHC
MP
NG
NGMP
DESCRIPTION SYMBOL ABBREVIATION DESCRIPTION
PLUMBING SYSTEMS LEGEND PLUMBING SYMBOLS LEGEND PLUMBING GENERAL NOTES
PLUMBING PIPE SYMBOLS LEGEND
HWR
DCW
SS
RAIN WATER OVERFLOW LEADER
OVERFLOW DRAIN
RAINWATER LEADER
PUMPED STORM DRAIN
SANITARY SEWER
STORM DRAIN
SANITARY SEWER
SUB-SOIL DRAIN
TRAP PRIMER WATER
TEMPERED OR TEPID WATER
VENT FOR SANITARY SEWER
NONE POTABLE COLD WATER
NONE POTABLE HOT WATER
ACID VENT
ACID WASTE
COMPRESSED AIR
COLD DOMESTIC WATER
CONDENSATE DRAIN
DRAIN
DEIONIZED WATER
DEIONIZED WATER SUPPLY
DIIONIZED WATER RETURN
HOT DOMESTIC WATER
HOT DOMESTIC WATER RECIRC
MEDICAL PRESSURE CONDENSATE
NATURAL GAS
NATURAL GAS MEDIUM PRESSURE
CIRCUIT SETTER VALVE
BALL VALVE
BALANCING VALVE
CHECK VALVE
GATE VALVE
PLAN VIEW
A.F.F. ABOVE FINISHED FLOOR--
ANCHOR
BACKFLOW PREVENTER, REDUCE PRESSURE TYPE
BALL VALVE
BOTTOM CONNECTION
CHECK VALVE
CALIBRATED BALANCING VALVE
CONDENSATION DRAIN & SECONDARY CONDENSATE DRAIN
CONNECT
ENERGY MANAGEMENT CONTROL SYSTEM
EXISTING
FROM ABOVE, FROM BELOW
FLOOR CLEANOUT
FLOOR DRAIN
FLOOR SINK
FLOW ARROW
GATE VALVE
GRADE CLEANOUT
HOSE BIBB
INVERT ELEVATION
LIMIT OF DEMOLITION
NON POTABLE
PIPE BREAK
PIPE CAP
PIPE DOWN
PIPE GUIDE
PIPE UP
POINT OF CONNECTION
ROOF DRAIN AND OVERFLOW
ROUGH-IN AND CONNECT
SHUT OFF VALVE
STRAINER
TO ABOVE, TO BELOW
TRAP PRIMER
VENT, VENT RISER, VENT THRU ROOF
WALL CLEANOUT OR END OF LINE CLEANOUT
WASTE DROP
WATER HAMMER ARRESTOR
WITH
UNDER GROUND
UNION
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
A.F.F.
EMCS
(E)
FA,FB
FCO
FD
FS
GCO
HB
IE
POD
NP
POC
RD & OF
RICONN
SOV
TA,TB
TP
V, VR, VTR
WD
WHA
W
UG
TYPICALTYP.
XX
XXX
100-SP-1
DRAWING SYMBOLS
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DEMO KEY NOTE ITEM
DETAIL NUMBER
DETAIL NUMBER
DETAIL NUMBER
DETAIL NUMBER
DETAIL NUMBER
XX KEY NOTE ITEM
1. KEEP ALL VTR'S MINIMUM 25FT FROM FRESH AIR INTAKES, AND MINIMUM 4FT FROM EXTERIOR WALLS WHETHER SHOWN OR NOT.
2. ALL NEW PIPING SHOWN ON PLUMBING PLAN IS INDICATED AS BOLD LINE TYPE.
3. OFFSET ALL RISERS AND DROPS TO AVOID PENETRATIONS THROUGH TOP PLATES.
4. CONTRACTOR SHALL FIELD VERIFY EXACT SIZES, LOCATIONS AND ELEVATIONS OF ALL PIPING CONNECTIONS AND OTHER WORK PRIOR
TO TRENCHING OR INSTALLING NEW WORK.
5. ALL SHUT-OFF VALVES SHALL BE LINE SIZE UNLESS OTHER WISE NOTED.
6. CONNECT CONDENSATE DRAIN PIPING TO EQUIPMENT WITH P-TRAP. PROVIDE CLEANOUTS AT ALL CHANGE IN DIRECTION.
7. THE DRAWINGS ARE NOT INTENDED TO SHOW EVERY OFFSET OR FITTING OR EVERY STRUCTURAL DIFFICULTY THAT MAY BE ENCOUNTERED DURING INSTALLATION OF THE WORK. LOCATION OF ALL ITEMS NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY. EXACT LOCATIONS NECESSARY TO SECURE BEST CONDITIONS AND RESULTS MUST BE DETERMINED AT THE JOB SITE AND SHALL HAVE THE APPROVAL OF THE ARCHITECH BEFORE BEING INSTALLED. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING LOCATIONS OF ITEMS OF WORK. ADJUSTMENTS SHALL BE MADE AS REQUIRED AT NO ADDITIONAL COST TO OWNER.
8. HVAC EQUIPMENT IS SHOWN FOR THE COORDINATION OF UTILITIES ONLY, SEE "MH" SHEETS FOR MORE INFORMATION.
9. FOR APPLICABLE CODES REFER TO ARCHITECTURAL SHEETS.
10. FOR CONDENSATE DRAIN PIPING, DEPTH OF "P" TRAP SHALL BE GREATER THAN THE TTOAL SCHEDULED FAN PRESSURE FOR THE UNIT.
11. OFFSET ALL RISERS AND DROPS TO AVOID STRUCTURAL ELEMENTS. SEAL ALL PENETRATIONS THROUGH FLOOR WATER TIGHT.
12. FIELD VERIFY EXACT SIZES, LOCATIONS AND ELEVATIONS ALL EXISTING PIPING CONNECTIONS SITE AND CLOSELY COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO TRENCHING OR INSTALLING ANY NEW WORK. DRAWINGS ARE DIAGRAMMATIC ONLY.
13. PROVIDE SHUT-OFF VALVES ON DOMESTIC WATER PIPE BRANCHES EQUIPMENT AND ON BRANCHES SERVING TWO OR MORE PLUMBING FIXTURES. WATER PIPING SERVING MAJOR FIXTURE GROUPINGS SUCH AS TOILET ROOMS, SUITES AND THE LIKE SHALL ALSO BE PROVIDED WITH SECTIONALIZING VALVES TO PERMIT SERVICING OR REPLACEMENT OF PIPING, FIXTURES AND EQUIPMENT.
14. COORDINATION SHOP DRAWINGS ARE REQUIRED TO AMPLIFY, EXPAND AND COORDINATE THE INFORMATION CONTAINED IN THE CONTRACT DOCUMENTS. APPROVED SHOP DRAWINGS ARE REQUIRED PRIOR TO THE INSTALLATION OF ALL NEW WORK.
15. ACCESS PANELS SHALL BE PROVIDED WHERE NECESSARY TO PROPERLY ACCESS THE PLUMBING SYSTEM, INCLUDING VALVES.
16. IF APPLICABLE, PROVIDE FLOOR CLEANOUTS IN ALL UNDERGROUND SANITRAY SEWER WASTE AND STORM DRAINS LINES INSIDE THE BUILDING AT EVERY 50FEET AND AT CHANGE OF DIRECTION GRATER THAN 45 DEGREES ACCUMULATIVE, COORDINATE LOCATIONS WITH ARCH PRIOR TO INSTALLATION. ALSO PROVIDE CLEANOUTS AT TOP AND BOTTOM OF ALL STACKS. EXTEND ABOVE THE FLOOR RIM ELEVATION OF ANY FIXTURE LOCATED NEAR THE CLEANOUTS AND BE CONNECTED TO THE SAME WASTE LINE.
17. DOMESTIC HOT WATER UNCIRCULATED LINES BRANCH LINES TO FIXTURES SHALL BE A MAXIMUM OF F FEET TO ALL SENSOR ACTIVATED MIXING STYLE FAUCETS AND A MAXIMUM 15 FEET TO ANY FAUCET WITH CONVENTIONAL CONTROLS.
18. ALL PENETRATIONS OF PIPES, CONDUITS , ETC. THRU RATED ASSEMBLIES SHALL BE FIRE STOPPED. MATERIAL SHALL BE TESTED UL
LISTED ASSEMBLY APPROVED BY THE STATE FIRE MARSHALL.
19. PROVIDE WALL CLEANOUTS AT ALL SINKS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
P-001
PLUMBING SYMBOLS &
Fridge
FD
FD
1. 1" BACKFLOW PREVENTER
2. WALL MOUNTED 1" MIXING VALVE, PROVIDE WITH WALL MOUNTED CABINET.
(NOT ALL KEYED NOTES USED ON THIS SHEET)KEYED NOTES:
3. SEE CIVIL PLANS FOR CONTINUATION.
4. ROUTE NEW 1" WATER LINE UNDER SLAB INTO MECHANICAL ROOM.
5. ROUTE NEW 1" HOT WATER AND 12" HW RECIRC LINES BELOW GRADE, ROUTE
TO MAINTENANCE BUIDING FOR SAFETY SHOWER TEMPERING.
P-301
P-301
P-301
P-402
P-806
P-707
EWH-01
P-101
P-101
P-701
P-701
P-201
P-606
P-501
P-910
P-910
P-9101
WCO
WCO
WCO
WCO
CP-1
MV-1
P-910
FDP-701
P-101
P-606 P-402
P-301
P-910 P-501 P-701
P-101
P-910
P-201 P-301 P-301
FD FD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
P-101
PLUMBING FLOOR PLANS
1. WALL MOUNTED ELEC WATER HEATER
2. REMOVE EXISTING PLUMBING FIXTURES, INCLUDING EXPOSED SANITARY, VENT
AND WATER LINES. CAP SANITARY LINES BELOW SLAB, PATCH SLAB TO MATCH
EXISTING. CAP WATER LINES AT WALL.
3. CONNECT NEW SAFETY SHOWER TO 1" WATER LINE FROM MIXING VALVE, SEE CIVIL
PLANS FOR LOCATION FOR 1" WATER LINE TO BUILDING.
4. TAP 34" LINE FROM 1" COLD WATER LINE, CONNECT TO HOSE BIBB.
5. NEW 1" MIXING VALVE FOR SAFETY SHOWER.
6. NEW 1" HOT WATER LINE FROM ADMINISTRATION BUILDING BELOW GRADE. PEX
PIPING WITH 1" ARMAFLEX CLASS O NITRILE FOAM INSULATION OR EQUIVALENT.
7. INSTALL HEAVY DUTY FLOOR DRAIN WITH SEDIMENT BUCKET.
8. ROUTE 3" SANITARY LINE TO OIL INTERCEPTOR, SEE CIVIL PLANS FOR LOCATION.
9. NEW AIR COMPRESSOR
(NOT ALL KEYED NOTES USED ON THIS SHEET)KEYED NOTES:
P-806
P-707 1
MV-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
P-102
PLUMBING FLOOR PLANS
B1 EMER EYEWASH/SHPWER BOUNDARY DETAIL
NTS B3 EMER EYEWASH/SHOWER PIPING DETAIL
NTS
D1 WATER CLOSET AND URINAL DETAIL
NTS
B5 POINT OF USE MIXING VALVE DETAIL
NTS
LAVATORY/SINK
NEW POINT
OF USE
MIX-VALVE.
HOT COLD
STOP VALVES
STOP VALVES
1. INSTALL MIXING VALVE UNDER SINK.
2. INSULATE ALL NEW SUPPLY PIPING
CONNECTIONS.
3. PROVIDE REMOVABLE INSULATION PADS FOR
MIX-VALVE AND SHUT OFF VALVES.
4. INSTALL 38" ISOLATION VALVES AT EACH
CONNECTION TO MIXING VALVE.
NOTE:
D3 FLOOR DRAIN TRAP PRIMER DETAIL
NTS D5 AIR COMPRESSOR DETAIL
NTS
F1 ELECTRIC WATER HEATER DETAIL
NTS F3 PIPE SLEEVE THROUGH WALL DETAIL
NTS F5 WALL CLEANOUT DETAIL
NTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
P-501
PLUMBING DETAILS
RECIRCULATION PUMP SCHEDULE
MIXING VALVE SCHEDULE
ELECTRIC WATER HEATER SCHEDULE
SYMBOL SERVICE TYPE
CAPACITY
VOLTS/PHASE H.P. MFG. AND MODEL No. REMARKS
CP-1 DHW RECIRC CIRCULATOR
GPM HEAD(FT)
-- -- 120/1 1/40 TACO HLS-2 HOT LINK
SYMBOL DISCHARGE
TEMPERATURE
MAXIMUM
FLOW GPM
PRESURE DROP
@ MAX FLOW
CAPACITY
CW IN HW IN MIXED OUT MFG. AND MODEL No. REMARKS
SYMBOL STORAGE
CAPACITY
(GALLONS)
CAPACITY
@ 60°F RISE
(GPH)
POWER REQUIRMENTS
(KW)/VOLTAGE/PHASE MFG. AND MODEL No. LOCATION REMARKS
EWH-1 55 67 6.0KW/240V/1PH STATE WATER HEATER/ EE8-5-DFRS0 MECH RM.
2"3" - ZURN Z5615, WALL MOUNT, TOP SPUD, ABA COMPLIANT, ELONGATED BOWL. PROVIDE W/ ZURN Z5955SS-EL OPEN FRONT SEAT, SLOAN ROYAL 111-1.28ES 1.28 GPF SENSORY FLUSH VALVE, SLOAN EL-154
TRANSFORMER, JR SMITH 0417 CARRIER.
WATER CLOSET
(ADA)P101
-- WATTS #LF15M2, LEAD-FREE, 60 PSI AIR PRE-LOAD, PER PDI WH201. PROVIDE W/ ACCESS PANEL.
WATER
HAMMER
ARRESTER
P905
2"2"
ZURN Z5351, WALL MOUNTED, 19"x17", WHITE VITREOUS CHINA. PROVIDE W/ SLOAN OPTIMA SYSTEM FAUCET MODEL ETF-80 HARDWIRED SENSOR ACTIVATED, ZURN Z8743-1-PC GRID STRAINER DRAIN, Z8700-PC CHROME PLATED P-TRAP AND TRUEBRO LAV GUARD 2 E-Z MODEL #102E-Z; BRASSCRAFT REGULAR PART NUMBER SCR39 C REGULAR PATTERN COMPRESSION JOINT ANGLE VALVE WITH LOOSE
KEY, POLYMER BRAID CONNECTORS, AND ESCUTCHEON PLATES
P301 LAVATORY
(ADA)
PLUMBING FIXTURE SCHEDULE
ITEM DESCRIPTION
MINIMUM ROUGH-IN
CONNECTION (INCH) REMARKSELECTRICAL DATA
CWVW HW
2"11
2"2"
JUST MFG SLN-ADA-2122, LEDGE MOUNT, STAINLESS STEEL, 21"Lx22"Wx6"D. PROVIDE W/ CHICAGO FAUCET AGN8AE2805-5CP 0.5 GPM AERATOR GOOSENECK, DUAL WRIST BLADE HANDLE; JUST #J-ADA-35-FS PUNCH DRAIN AND REMOVABLE STRAINER; CHROME PLATED P-TRAP (HOT WATER SUPPLY AND P-TRAP SHALL BE TRUEBRO WRAPPED FOR ACCESSIBILITY PROTECTION; BRASSCRAFT COMPRESSION JOINT ANGLE VALVE, POLYMER BRAID CONNECTORS, AND ESCUTCHEON PLATES
2"P402 BREAKROOM
SINK
P606 DRINKING
FOUNTAIN
HAWS 1119.8, DUAL HIGH-LOW, WALL MOUNTED, 304 STAINLESS STEEL CONSTRUCTION. PROVIDE W/ HAWS
SK1 CANE SKIRT, HCR8 CHILLER, MTGFR.LG CARRIER AND 6426 WATER FILTER.2 1
2" -
2" 1
2"
P906 -TRAP PRIMER WATTS #WPIME-1, COMPLETE W/ QUARTER-TURN BRASS VALVE AND ENCLOSURE1 2"--
TRAP
INT
2"
2"
2"
2"
-1 2"
2"
115V, 60HZ, 370W,
5FLA
P806 -HOSE-BIB WATTS #SC8-6, HEX SHOULDER W/ TEE HANDLE AND VACUUM BREAKER--- -
P707 -
EMERGENCY
EYEWASH
SHOWER
HAWS 8336, SCHED 80 PVC GREEN EPOXY FINISH, 316 STAINLESS STEEL BALL VALVE, ANTI-CORROSIVE, AXION MSR SHOWERHEAD AND FACE BOWL W/ INTEGRAL FLOW CONTROL. PROVIDE W/ SP170 TEST CARD
AND SP178LG FIXTURE SIGNAGE.
P711 -EMERGENCY
ALARM
HAWS 9001TYPE4X, AUDIBLE 60dB, VISUAL FLASHING AMBER LIGHT, DOUBLE POLE FLOW SWITCH
ACTIVATED.- - 120VAC, 60HZ
- 11 4"
2"
4"
P701 SHOWER J.R. SMITH FIGURE 2005Y-A05-B-P050-CP, ROUND ADJUSTABLE STRAINER WITH SEDIMENT BUCKET, CHROME PLATED STRAINER AND TRAP PRIMER CONNECTION.2" 2" 1
2"2" -
(ADA)
2"
2"
MV-1 85F 20 10PSI 15 5.0 BRADLEY S19-210020
MV-2 110F 2.0 10PSI 0.75 0.75 WEBSTONE H-72202W1.5 POINT OF USE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENT
SUBMITTAL
N/A
National Cemetery Administration
Design and Construction Service
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick
LOS ANGELES NATIONAL CEMETERY
REPLACE STORAGE BUILDING
Los Angeles, CA
898CM3034
N/A Project Director
05/24/2023Revisions: Date:
Juan Kays Department of Veterans Affairs, NCA
Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95
VCI Project Management Construction Management Engineering
BSTM
1331 17TH STREET SUITE 605
DENVER, COLORADO 80202
PHONE: (720) 439-4700
WEBSITE: www.dci-engineers.com
CIVIL / STRUCTURAL
5/24/23
P-601
PLUMBING SCHEDULES
File details come from the government source that posted it. Updated .