231030 LANC 898-034 MX Bid Docs 2 of 5.pdf

PDF 7 MB Posted

Attached to
Y1EB--Los Angeles CA 898 -034 Maint, 036 FCA (VA-24-00060981)
Solicitation number
36C78624B0023
Issued by

About this file

This document appears to be a set of bid documents for a federal contract opportunity to replace a storage building at the Los Angeles National Cemetery. The documents include mechanical and plumbing drawings, equipment schedules, details, and specifications.

The key details are:

  • The solicitation number is 36C78624B0023 and the name is "Y1EB--Los Angeles CA 898 -034 Maint, 036 FCA (VA-24-00060981)".
  • The contract is for the replacement of a storage building at the Los Angeles National Cemetery, managed by the Department of Veterans Affairs National Cemetery Administration.
  • The mechanical drawings show the new HVAC system, including a floor-mounted air handler, ductless AC units, heat pumps, and an energy recovery ventilator. Plumbing drawings detail the new domestic water, sanitary, and condensate drain systems.
  • Equipment schedules are provided for mechanical and plumbing systems, including make, model, capacity, and electrical data.
  • The bid documents provide details and specifications for the mechanical and plumbing installations.

View the file

Other files

File Type Posted
LANC FCA Deficiencies Bid Package Ammended Drawings - Reduced - 5 of 6.pdf PDF
LANC FCA Deficiencies Bid Package Ammended Drawings - Reduced - 4 of 6.pdf PDF
RFIs -AE-COR.docx DOCX document
Amendment 0002.docx DOCX document
LANC Combined Specifications 4 of 4 Rev 001 6.20.24.pdf PDF
LANC Combined Specifications 3 of 4 Rev 001 6.20.24.pdf PDF
LANC Combined Specifications 2 of 4 Rev 001 6.20.24.pdf PDF
LANC FCA Deficiencies Bid Package Ammended Drawings - Reduced - 2 of 6.pdf PDF
LANC FCA Deficiencies Bid Package Ammended Drawings - Reduced - 1 of 6.pdf PDF
LANC FCA Deficiencies Bid Package Ammended Drawings - Reduced - 3 of 6.pdf PDF
LANC Combined Specifications 1 of 4 Rev 001 6.20.24.pdf PDF
LANC FCA Deficiencies Bid Package Ammended Drawings - Reduced - 6 of 6.pdf PDF
S04 LA Sign In Roster.pdf PDF
S01 LA 0001 Amendment.docx DOCX document
36C78624B0023.docx DOCX document
231030 LANC 898-Multi MX - FCA IFB Scope of Work.docx DOCX document
S02 Final LANC Combined Specifications -4 of 4.pdf PDF
231030 LANC 898-036 FCA Bid Docs 5 of 5.pdf PDF
231030 LANC 898-036 FCA Bid Docs 4 of 5.pdf PDF
231030 LANC 898-034 MX Bid Docs 3 of 5.pdf PDF
231030 LANC 898-036 FCA Bid Docs 2 of 5.pdf PDF
S02 Final LANC Combined Specifications-1 of 4.pdf PDF
P07 Wage Determination LA.pdf PDF
231030 LANC 898-036 FCA Bid Docs 3 of 5.pdf PDF
36C78624B0023_2.docx DOCX document
231030 LANC 898-034 MX Bid Docs 5 of 5.pdf PDF
231030 LANC 898-034 MX Bid Docs 4 of 5.pdf PDF
231030 LANC 898-036 FCA Bid Docs 1 of 5.pdf PDF
S02 Final LANC Combined Specifications -3 of 4.pdf PDF
S02 Final LANC Combined Specifications-2 of 4.pdf PDF
231030 LANC 898-034 MX Bid Docs 1 of 5.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

DUCTWORK SYMBOLS

ACU

AFF

AD

AHU

AL

BHP

BOD

BTU

BOP

BTUH

CA

CFM

CD

CONT.

COR

CU

D

DX

ENT

EXH

EMCS

FB

°F

FCU

F.G.

FD

FLEX

FPM

FS

FT.

FT

GPM

GPH

HB

HD

IN

HEPA

IU

KW

KWH

MA

MCC

NA

NO.

NIC

OBD

OA

PRV

PSIG

QTY

QUAD

Rh R.A.

RS

RL

ST

SP

RPM

SCD

SDVV

TOPT

TP

TYP.

V

VAC

VAV

VTR

VEL

QUANTITY

QUADRANT

RETURN AIR

REVOLUTIONS PER MINUTE

RELATIVE HUMIDITY

REFRIGERATION LIQUID

REFRIGERATION SUCTION

SMOKE CONTROL DAMPER

SINGLE DUCT VARIABLE VOLUME

STATIC PRESSURE (INCHES OF WATER)

SOUND TRAP

SIDEWALL SUPPLY REGISTER

TOP OF PIPE TRAPEZE

TOTAL PRESSURE (INCHES OF WATER)

TYPICAL

VOLTS

24"x12"

VOLTS, ALTERNATING CURRENT

VARIABLE AIR VOLUME

VENT THRU ROOF

VELOCITY

24"/12"

12"Ø

SD

24x12

12"Ø

24x12Ø

SD

EQUIPMENT SYMBOLS

DUCT MOUNTED SMOKE DETECTOR

XX-##

DUCT MOUNTED STATIC PRESSURE PROBE

ACCESS DOOR

SIDEWALL GRILLE DIMENSION WHERE

SHOWN ON PLANS

T

H

CO2

SEE CONTROL DRAWINGS FOR TYPE

ROOM THERMOSTAT/TEMP. TRANSMITTER LOCATION ONLY

ROOM HUMIDISTAT/HUMIDITY TRANSMITTER LOCATION ONLY

SEE CONTROL DRAWINGS FOR TYPE

ROOM CARBON DIOXIDE TRANSMITTER LOCATION ONLY

SEE CONTROL DRAWINGS FOR TYPE

##x##

XX-#

SYMBOL INDICATES GRILLE OR DIFFUSER

IDENTIFIED IN EQUIPMENT SCHEDULE

CFM

F. SEE SPECIFICATION SECTION 230593, TESTING, ADJUSTING, & BALANCING OR

MECHANICAL SYSTEMS FOR ADDITIONAL DESCRIPTION AND REQUIREMENTS.

G. ALL TEST AND MEASUREMENT TRAVERSE LOCATIONS SHALL BE CLEARLY NOTED ON

FLOOR PLANS WHICH SHALL BE INCLUDED WITH THE TEST AND MEASUREMENT DATA.

H. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL TRADES

INCLUDING MECHANICAL, PLUMBING, ELECTRICAL, FURNITURE, AND ARCHITECTURAL.

ANY DISCREPANCIES SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT PRIOR

TO START OF WORK.

I. ALL NEW TO EXISTING DUCT CONNECTIONS SHALL BE FIELD VERIFIED PRIOR TO

ORDERING AND FABRICATING NEW DUCTWORK OR DAMPERS

LETTERS REFER TO THE EQUIPMENT TYPE

NUMBERS REFER TO SPECIFIC EQUIPMENT

SYMBOL INDICATES EQUIPMENT IDENTIFIED

IN EQUIPMENT SCHEDULE

DUCT TRANSITION FROM RECTANGULAR TO ROUND

DUCT TRANSITION

INDICATES A 24"x12" RECTANGULAR DUCT (WIDTH x DEPTH)

INDICATES A 12" ROUND DUCT

INDICATES A 24"x12" FLAT OVAL DUCT (WIDTH x DEPTH)

DOWN DIRECTION PITCH

DIRECTION OF FLOW

DEMO

EXISTING

DETAIL NUMBER LOCATION

SECTION LETTER LOCATION A1

A1

SCALE

SECTION

A. THE DEMOLITION DRAWINGS REFLECT INFORMATION ON EXISTING BUILDING

SERVICES GATHERED BY SITE INSPECTION, DISCUSSIONS WITH MAINTENANCE

PERSONNEL AND PREVIOUS CONSTRUCTION DRAWINGS. THE EXACT LOCATION,

ARRANGEMENT, AND SIZES OF PIPE LINES AND DUCTWORK IN THE EXISTING BUILDING

MAY BE DIFFERENT FROM THAT SHOWN ON THESE DRAWINGS.

SCALE

DETAIL

B. THE CONTRACTOR SHALL COORDINATE THE SHUTDOWN OF EXISTING BUILDING

SERVICES FOR REMOVAL WITH OWNER AUTHORIZED REPRESENTATIVE AND SHALL

CONFORM TO THEIR REQUIREMENTS.

C. DISRUPTION OF NORMAL FACILITY ACTIVITIES ARE TO BE KEPT TO AN ABSOLUTE

MINIMUM. DUST, DEBRIS, AND FUMES SHALL BE CONTROLLED SO AS NOT TO AFFECT

THE HEALTH AND SAFETY OF OCCUPIED AREAS WITHIN THE FACILITY WHICH ARE

OUTSIDE THE AREA OF WORK. COORDINATE WITH THE ARCHITECT AND THE

OWNER'S REPRESENTATIVE WITH REGARD TO ALL ACTIVITIES TO BE CONDUCTED

OUTSIDE OF THE SUITE REMODEL AREA WHICH MAY AFFECT THE OPERATION OF THE

FACILITY.

D. THE CONTRACTOR SHALL PROVIDE TEMPORARY VENTILATION (MAINTAIN WORK ZONE

AT NEGATIVE PRESSURE), FILTRATION, AIR PURIFIERS, DUST SCREENS, ETC. FOR ALL

WORK AREAS AFFECTED BY DEMOLITION FOR NEW INSTALLATION TO MINIMIZE DUST

AND FUMES.

E. THE CONTRACTOR SHALL PRESENT AN AREA BY AREA WORK PLAN WELL IN ADVANCE

TO THE ARCHITECT AND THE OWNER'S AUTHORIZED REPRESENTATIVE FOR

APPROVAL PRIOR TO BEGINNING WORK. THE WORK PLAN SHALL INCLUDE AN

OUTLINE OF ALL ACTIVITIES OF ALL SUBCONTRACTORS. THE CONTRACTOR SHALL

COORDINATE WITH THE OWNER'S AUTHORIZED REPRESENTATIVE TO ESTABLISH

ACCEPTABLE ROUTING AND ACCESS WITHIN THE FACILITY FOR MATERIALS REQUIRED

FOR THE NEW INSTALLATION.

SIDEWALL EXHAUST OR RETURN AIR GRILLE

OR REGISTER

CEILING RETURN AIR REGISTER OR GRILLE

CEILING EXHAUST REGISTER

ENTERING

EXHAUST

ENERGY MANAGEMENT CONTROL SYSTEM

DEGREES FAHRENHEIT

FLAT BOTTOM

FLOOR DRAIN

FAN COIL UNIT

FILTER GAUGE

FLEXIBLE

FEET PER MINUTE

FLOOR SINK

FEET

FLAT TOP

GALLONS PER MINUTE

GALLONS PER HOUR

HOSE BIBB

HIGH EFFICIENCY PARTICULATE AIR (FILTER)

HAND DAMPER (VOLUME DAMPER)

INCHES

INDOOR UNIT

KILOWATT

MAIN AIR (CONTROLS)

KILOWATT HOUR

MOTOR CONTROL CENTER

NUMBER (QUANTITY)

NOT IN CONTRACT

NOT APPLICABLE

OPPOSED BLADE DAMPER

OUTSIDE AIR

PRESSURE REDUCING VALVE

POUNDS PER SQUARE INCH GAGE

PERFORATED FACE CEILING DIFFUSERS

HWS

HWR

CHS

CHR

STAMPED FACE CEILING DIFFUSERS

V

D

CD

MU

RS

RL

R

TWS

TWR

TWB

MPS

HPS

LPS

HPR

HPR

LPR

CND

PC

GWS

GWR

HEATING WATER RETURN

HEATING WATER SUPPLY

CHILLED WATER SUPPLY

CHILLED WATER RETURN

DRAIN

CONDENSATE DRAIN

MAKE-UP WATER

VENT

REFRIGERATION LIQUID

REFRIGERATION SUCTION

REFRIGERATION

TOWER WATER BYPASS

TOWER WATER RETURN

TOWER WATER RETURN

STEAM - HIGH PRESSURE SUPPLY

STEAM - HIGH PRESSURE RETURN

STEAM - MEDIUM PRESSURE SUPPLY

STEAM - LOW PRESSURE SUPPLY

CONDENSER WATER

PUMPED CONDENSATE

GEOTHERMAL SUPPLY

GEOTHERMAL RETURN

SECTION AND DETAIL TITLES

STEAM - MEDIUM PRESSURE RETURN

STEAM - LOW PRESSURE RETURN

DRAWING NUMBER WHERE DETAILED

SECTION LOCATION

DETAIL SYMBOL

DETAIL LOCATION

DRAWING NUMBER WHERE DETAILED

X#/X###

M301 A1

SECTION SYMBOL

B

M

RETURN DUCT

PIPING SYMBOLS

EXHAUST DUCT

MECHANICAL PIPING

SUPPLY DUCT

EXISTING DUCT TO BE REMOVED

FLEXIBLE CONNECTION

RISE IN DUCT

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES

EXCEPT TRANSFER AIR SOUND ELBOW)

SHORT RADIUS ELBOW (PROVIDE ALL

SQUARE OR RECTANGULAR ELBOWS WITH

VANES EXCEPT TRANSFER AIR SOUND

ELBOW)

STANDARD LONG RADIUS ELBOW

3/4" BALL VALVE WITH ADAPTER

TO 3/4" HOSE THREAD

DIAPHRAGM VALVE

BUTTERFLY VALVE

BALL VALVE

VALVE IN RISE

WATER FLOW MEASURING DEVICE

CIRCUIT SETTER

F

S

SOLENOID VALVE

POINT OF CONNECTION, NEW DUCT TO EXISTING DUCT

OR / POINT OF REMOVAL FROM EXISTING DUCT TO DEMO DUCT

AIR CONDITIONING UNIT

ABOVE FINISHED FLOOR

ACCESS DOOR

AIR HANDLING UNIT

ACOUSTIC LINING

BRAKE HORSEPOWER

BOTTOM OF DUCT

BOTTOM OF PIPE

BTU PER HOUR

BRITISH THERMAL UNIT

COMPRESSED AIR

CUBIC FEET PER MINUTE

CONDENSATE DRAIN

CONTINUATION

CONTRACTING OFFICER'S REPRESENTATIVE

CONDENSING UNIT

DRAIN

DIRECT EXPANSION

S.DPR

F.DPR

F/S DPR

COMBINATION FIRE/SMOKE DAMPER

PRESSURE REDUCING VALVE

2HR. SMOKE BARRIER

SMOKE BARRIER

2HR. FIRE BARRIER

1 HR. FIRE BARRIER

M

VERIFY WITH

ARCHITECTURAL

DRAWINGS

M

3-WAY

MODULATING

CONTROL VALVE

A

2-WAY CONTROL VALVE

SAFETY VALVE OR

PRESSURE RELIEF

VALVE

P

PS PS

GAUGE - DIFFERENTIAL

GAUGE - PRESSURE

GAUGE - PRESSURE WITH COCK

GAUGE - TEMPERATURE

HS

PS

TS

PIPE ANCHOR

PIPE EXPANSION JOINT

PIPE GUIDE

SENSOR - FLOW

SWITCH - FLOW

SWITCH HUMIDITY

SWITCH - PRESSURE

SWITCH - TEMPERATURE

TEMPERATURE - PRESSURE TEST FITTING

THERMOMETER

THERMOMETER WELL

BASKET STRAINER

STEAM TRAP INVERTED BUCKET

METER - TOTALIZING BTU

METER - TOTALIZING FLOW

AIR VENT - AUTOMATIC

AIR VENT - MANUAL

G. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF ALL FIRE

RATED AND/OR SMOKE RATED WALLS AND ASSEMBLIES. PROVIDE APPROVED

FIRE DAMPERS IN ALL REQUIRED PENETRATIONS FOR DUCTWORK, GRILLES,

REGISTERS AND DIFFUSERS. ALL PIPE AND DUCTWORK PENETRATIONS OF FIRE,

SMOKE AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT

STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL.

H. CONTRACTOR SHALL COORDINATE ALL DUCTWORK, PIPING, PLUMBING AND

FIRE PROTECTION PIPING WITH STRUCTURAL AND ELECTRICAL SYSTEMS AND

SHALL PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

EQUIPMENT ACCESS AND SERVICEABILITY.

I. CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS,

SLEEVES, AND HANGING DEVICES FOR INSTALLATION OF MECHANICAL AND

PLUMBING EQUIPMENT, DUCTWORK AND PIPING, ETC. CONTRACTOR SHALL

COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOID

CONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.

J. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY

MISCELLANEOUS ANGLES, CHANNELS, UNISTRUT, ETC., AS MAY BE REQUIRED TO

ADEQUATELY SUPPORT THE MECHANICAL PIPING, DUCTWORK, AND EQUIPMENT

IN A MANNER APPROVED BY THE ARCHITECT, WHICH WILL NOT OVERLOAD THE

BUILDING STRUCTURAL SYSTEM.

K. CONTRACTOR SHALL PROVIDE RETURN AIR OR TRANSFER AIR OPENINGS IN

FULL HEIGHT WALLS SIZED AT 350 FPM (UNLESS OTHERWISE SPECIFICALLY

SHOWN ON THE DRAWINGS) TO CREATE AND/OR MAINTAIN A RETURN AIR PATH AS

REQUIRED. FIRE DAMPERS AND/OR SMOKE DAMPERS SHALL BE PROVIDED IN

SUCH OPENINGS WHERE REQUIRED BY NOTE "J".

L. SEAL ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, DUCT WALL

PENETRATIONS AND FITTING CONNECTIONS ON ALL DUCT SYSTEMS.

M. MECHANICAL ITEMS SUCH AS ROOF DRAINS, FLOOR DRAINS, PLUMBING FIXTURES,

ETC. SHOWN ON THE ARCHITECTURAL DRAWINGS BUT NOT SHOWN ON THE

MECHANICAL DRAWINGS SHALL BE INCLUDED IN THE PROJECT. THESE ITEMS

SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR INCLUSION IN

ADDENDUM.

N. IT IS CRITICAL THAT THE CONTRACTOR PERFORM A COMPLETE REVIEW OF ALL

SUBMITTALS PRIOR TO SUBMISSION TO THE AE/COR. INCOMPLETE, INCORRECT

AND UNCLEAR SUBMITTALS WILL BE REJECTS AND MARKED AS "REVISE AND

RESUBMIT". ALL SUBMITTALS MUST CLEARLY INDICATE THE EQUIPMENT

SELECTIONS FOR THE PROJECT. TECHNICAL DRAWINGS OF COMPLETE

ASSEMBLIES, REFLECTING ACCURATE PROJECT CONDITIONS, SHALL BE

SUBMITTED WITH EQUIPMENT SELECTIONS TO ENSURE SPACE ALLOWANCES ARE

REFLECTED IN THE ACTUAL SPACE AVAILABLE. WHERE SIZE DEVIATIONS DIFFER

FROM THE BASIS OF DESIGN CONTRACTOR SHALL HIGHLIGHT THE DIFFERENCES

FOR AE/COR REVIEW WITHIN THE SUBMITTAL. CONTRACTOR SHALL PROVIDE

INSTALLATION ROUTE AND VERIFICATION THAT ACCESS POINTS, PLACEMENT

ROUTE, SUPPORTS, AND REQUIRED EQUIPMENT CLEARANCES ARE IDENTIFIED ON

THE ROUTE DRAWING. SAFETY PROTOCOLS FOR SUBJECT STATION SHALL BE

REFLECTED ON EQUIPMENT CLEARANCES. PLATFORMS AND INTERFACE AREAS

(FILTER, GAUGES, MONITORS, VALVES, ETC.) SHALL HAVE PROPER CLEARANCE AS

DEFINED BY THE MANUFACTURER, VA SAFETY PERSONNEL AND SERVICE

PERSONNEL. ACCESS POINTS OF USE SHALL BE CLEARLY IDENTIFIED ON THE

DRAWINGS.

GENERAL DEMO NOTES

PIPE REDUCER - ECCENTRIC

PIPE STRAINER

UNION - SCREWED

FIRE DAMPER

SMOKE DAMPER

CHECK VALVE

PLUG VALVE

ACOUSTICAL DUCT LINING

FLEXIBLE DUCT

MANUAL BALANCING DAMPER

GATE VALVE

MECHANICAL SYMBOL LEGEND

VALVE SYMBOLS

GLOBE VALVE

ELBOW - DROP TO TEE

TEE - DROP FROM TEE

END CAP

FLEX CONNECTION

PIPE REDUCER - CONCENTRIC

GENERAL NOTES

FITTING SYMBOLS

ELBOW - DOWN

ELBOW - UP

PIPE RISE-DROP

A. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN

FURRED CHASES OR SUSPENDED CEILINGS, UNLESS OTHERWISE NOTED.

B. PROVIDE ACCESS PANELS OR DOORS IN INACCESSIBLE CEILINGS AND/OR

CHASES FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS, COILS, FANS,

CONTROLS, ETC. THEY SHALL BE FURNISHED UNDER DIVISION 23 AND

INSTALLED UNDER THE ARCHITECTURAL SPECIFICATION. ACCESS DOOR RATING

SHALL MATCH CLASSIFICATION OF WALL AND CEILING FIRE RATING.

C. COORDINATE THE LOCATION OF ALL DIFFUSERS, GRILLES, REGISTERS, ACCESS

DOORS, ETC., WITH THE ARCHITECTURAL REFLECTED CEILING PLAN(S).

D. ALL ROUND RUNOUTS AND DROPS TO DIFFUSERS SHALL BE THE SAME NOMINAL

SIZE AS THE SCHEDULED DIFFUSER NECK SIZE.

E. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR

INDICATED. ALL DUCT SIZES SHOWN ON DRAWINGS ARE NET INSIDE DIMENSIONS.

PROVIDE ONE INCH ACOUSTICAL LINING (TYPE D3 INSULATION) IN LOW VELOCITY

RECTANGULAR DUCTWORK FOR THE FIRST 10 DIAMETERS OF DUCTWORK

CONNECTED TO DEVICE, OR AS INDICATED ON DRAWINGS, WHICHEVER IS

GREATER. FOR THE REMAINDER OF THIS DUCTWORK PROVIDE AS INDICATED IN

THE INSULATION SPECIFICATIONS.

F. PROVIDE 1/2" MANUAL AIR VENTS AT ALL HIGH POINTS OF CLOSED SYSTEM PIPING

AND 1/2" MANUAL DRAIN VALVES WITH HOSE CONNECTION AT LOW POINTS AS

REQUIRED TO PROVIDE COMPLETE SYSTEM DRAINAGE. WHERE DRAIN VALVES

OCCUR ABOVE CEILING AREAS AND IN AREAS OUTSIDE MECHANICAL RANGE

PROVIDE HOSE CONNECTION ON VALVE.

ELECTRICAL DISCONNECT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

M-001

MECHANICAL SYMBOLS &

Fridge

FD

FD

1. NEW FLOOR MOUNTED AIR HANDLER

2. NEW WALL MOUNTED DUCTLESS AC UNIT

(NOT ALL KEYED NOTES USED ON THIS SHEET)KEYED NOTES:

3. NEW HEAT PUMP OUTDOOR UNIT

4. NEW ERV UNIT

5. 12x10 TRANSFER DUCT WITH TITUS 350R (12x10)

6. ROOF MOUNTED INTAKE VENT 24"DIA.

7. UNIT HEATER, MOUNT MIN. 9FT ABOVE FINISHED FLOOR

8. 6"Ø WALL TERMINATION VENT WITH BIRD SCREEN AND BACKDRAFT

DAMPER

9. 8"Ø WALL TERMINATION VENT WITH BIRD SCREEN AND BACKDRAFT

DAMPER

10. CEILING TYPE EXHAUST FAN IN STORAGE AREA, PROVIDE WITH

WALL SWITCH.

11. REFRIGERANT LINE SET BUNDLED WITH 34" CONDENSATE DRAIN.

12. OUTDOOR AC UNIT, COOLING ONLY.

EF-01

HP-02

IU-01

EF-03

EF-01

AC-01

HP-01CU-01

AHU-01

ERV-01

EWH-01

EF-02

EF-04

EF-01

60E

60E 50E

450E 450E

EH-01

EH-01

EH-01

CD-02

CD-02 CD-02

CD-02

CD-02

CD-02

CD-01

CD-01

RG-01

EG-02

EG-02

EG-02

CD-01

EG-01 EG-01

8 9

8Ø

8Ø

8Ø

6Ø

4Ø

6Ø

4Ø

4Ø

4Ø

8Ø

16x1210x1210x10

8Ø

6Ø 8Ø

8Ø

8Ø 8Ø x1

MH101

HVAC FLOOR PLANS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

M-501

MECHANICAL DETAILS

PIPE CLAMP

SEE PLANS FOR

PIPE TYPE , SIZE,

AND LOCATION

ROOF

A6 ABOVE ROOF PIPE SUPPORT

NTS

4 4 10

1 3 3

PREPOSITIONED SLEEVE PREPOSITIONED SLEEVE

7 6

ROOF SUPPORT AS

MANUFACTURED BY C-PORT,

CB10, 28" LONG OR EQUIVALENT.

SEE SPECIFICATION FOR

SPACING

4 4 10

CORE DRILLED SLEEVE

FOR 1-1/4" AND LARGER

CORE DRILLED SLEEVE 12

C6 TYPICAL CONDENSATE DRAIN TRAP

NTS C8 PIPE PENETRATION DETAIL

NTS

1 2

E8

3 2

SPLIT SYSTEM DX REFRIGERANT PIPING

NTS

PAD MOUNTED CONDENSING UNIT, 4" CONCRETE PAD

INDOOR UNIT, DIRECT EXPANSION (DX) COIL.

DISTRIBUTION NOZZLE

GLOBE VALVES AT OUTDOOR UNIT.

SWING JOINT.

PIPE PENETRATION THROUGH ROOF, SEE PIPING THRU ROOF

DETAIL ON THIS SHEET.

REFRIGERANT SUCTION LINE

REFRIGERANT LIQUID LINE

SIGHT GLASS

REMOTE BULB

FILTER

LIQUID CHARGING VALVE

STRAINER

SOLENOID VALVE TO BE LOCATED AS CLOSE

TO EXPANSION VALVE AS POSSIBLE.

EXPANSION VALVE

CONCRETE STRUCTURE

PIPE SLEEVE SIZED FOR PIPE WITH INSULATION

WATERSTOP

EXTEND SLEEVE 4" ABOVE FINISHED FLOOR LEVEL

MINIMUM 18" LONG ALUMINUM INSULATION JACKET

INSULATION-SEE SPECS FOR THICKNESS

PIPE

SEAL WITH WATERPROOF CAULKING

MINIMUM 34" POURED LEAD

MULTI-COMPONENT PLASTIC CEMENT

PIPE SLEEVE (I.D. MIN 1" LARGER THAN O.D. OF

PIPE)

WATERPROOF GROUT

CORE DRILL MIN 1" LARGER HOLE THAN O.D.OF PIPE

SLEEVE

NOTES:

1. SEAL SLEEVE WITH UL RATED SEALANT TO MATCH

RATING OF WALL OR CEILING. MAINTAIN REQUIRED

MINIMUM CONTACT OF SEALANT AND CLEARANCES OF

PIPE IN PENETRATION.

2. PROVIDE ESCUTCHEON PLATES AT ALL EXPOSED

PENETRATIONS.

3"MIN TRAP

2% SLOPE

SPILL CONDENSATE

DRAIN PIPING TO

DRYWELL

SOLDER ALL JOINTS

AS REQUIRED, (TYP)

VENT OPEN TO

ATMOSPHERE LINE CLEANOUT, (TYP)

UNION,

(TYP)

DRAIN SIZE AT

LEAST SAME SIZE

AS NIPPLE

CONNECTION SIZE

NOTES:

1. SEE PLAN FOR PIPE SIZES

2. INTERIOR CONDENSATE DRAINS ABOVE CEILING

SHALL BE INSULATED

3. IF HORIZONTAL RUN IS GREATER THAN 15FT,

INSTALL VENT (same size as drain pipe)

4. CONDENSATE DRAIN CONNECTIONS SHALL

OCCUR ABOVE EQUIPMENT FRAMING TO ALLOW

FOR PROPER P-TRAP INSTALLATION

E3 EQUIPMENT SUPPORT RAIL DETAIL

NTSE1 TYPICAL GROUND MOUNTED CONDENSING UNIT

NTS

MIN. 4" CONCRETE PAD

MIN. 38" EXPANSION BOLT

INTO CONCRETE PAD.

22 GA. GALV.

STEEL FLASHING

COUNTER SUNK BOLTS

(4) MINIMUM AT 16" O.C.

2"x4" NAILER

(TREATED)

3/4" CLEARANCE

FOR ROOFING FELTS

ROOF SURFACE

ROOF INSULATION

6"

TYP.

8" DRIP EDGE

18 GA. GALV. STEEL

CURB. SOLDER ALL

SEAMS AND EDGES

WATER TIGHT.

FIBERBOARD CANT

C-CHANNEL ROOF DECK

TACK WELD TO STEEL

ROOF AND LAG TO

JOISTS (TYPICAL AT

EACH JOIST)

4"

MIN.

INDOOR UNIT

OUTDOOR UNIT

FRONT PANEL

AIR FILTER

GUIDE LOUVER

WALL PIPE

BIND TAPE

POWER CABLE

AIR IN

AIR OUT

AIR IN

AIR OUT

> 24 INCH CLEARANCE

C1 TYPICAL AC/HEAT PUMP SPLIT SYSTEM DETAIL

NTS

PROVIDE ISOLATOR

PADS

REFRIGERANT LINE SET

AND COMMUNICATION

CABLE

CONDENSATE DRAIN

PIPING

C3 FLEXIBLE AIR DUCT CONNECTOR DETAIL

NTS

E6 DUCT ELBOW DETAIL

NTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

M-502

MECHANICAL DETAILS

C6 ROOF MOUNTED EXHAUST FAN DETAIL

NTS

E3 CEILING EXHAUST DETAIL

NTSE1 ROOF INTAKE & RELIEF VENTILATOR DETAIL

NTS

C1 ELECTRIC UNIT HEATER DETAIL

NTS

C3 SPLIT SYSTEM HEAT PUMP DETAIL

NTS

SYMBOL

NO.

MANUFACTURER/MODEL

NO. TYPE

IU-01 MSZ-JP09WA * WALL MOUNTED 310

INDOOR UNIT SCHEDULE

SUPPLY

AIRFLOW

(CFM)

9,000

SOUND

(dBA)

ELECTRICAL DATA

VOLTS PHASE HZ MCA

120 1 60 1.0

WEIGHT

(LBS)

SYMBOL

NO.

MANUFACTURER/MODEL

NO. TYPE CFM

EF-01 GREENHECK SPB90 CEILING 60

EXHAUST FAN SCHEDULE

S.P.

INCH W.C.

0.3

SOUND

(SONES)

1.5

ELECTRICAL DATA

VOLTS PHASE HZ HP

120 1 60 1/25

WIDTH (IN)

14.5

HEIGHT

(IN)

7.25

WEIGHT

(LBS)

10.5

*BASED ON MITSUBISHI

SYMBOL

NO.

MANUFACTURER/MODEL

NO.

SENSIBLE

COOLING

CAPACITY

(BTU/H)

HP-01 SVZ-KP36NA * 33,400 33,400

HEAT PUMP OUTDOOR UNIT SCHEDULE

23,200

SOUND

(dBA)

ELECTRICAL DATA

VOLTS PHASE HZ MCA

208/230 1 60 17.0 31.0

DIM

(IN)

28x33x13

WEIGHT

(LBS)

*BASED ON MITSUBISHI

HEATING

CAPACITY

(BTU/H)

@47°F

HEATING

CAPACITY

(BTU/H)

@17°F MOCP

SYMBOL

NO.

MANUFACTURER/MODEL

NO.

ERV-01 RENEWAIRE EV300 175 78

ENERGY RECOVERY VENTILATOR (ERV) SCHEDULE

73/59

PORT DIA.

(IN.)

ELECTRICAL DATA

VOLTS PHASE HZ MCA

120 1 60 5.0 15

DIM

(IN)

34x44x34

WEIGHT

(LBS)

BLOWER

FAN

(CFM) MOCP

HP-02 MUZ-JP09WA* 9,000 10,900 6,700 49 120 1 60 12.0 15.0 31x12x22 75

SYMBOL

NO.

MANUFACTURER/MODEL

NO.

SENSIBLE

COOLING

CAPACITY

(BTU/H)

CU-01 MUY-GL24NA 22,400 8,200

COOLING ONLY OUTDOOR UNIT SCHEDULE

12.5

SOUND

(dBA)

ELECTRICAL DATA

VOLTS PHASE HZ MCA

208/230 1 60 17.1 20.0

DIM

(IN)

28x33x13

WEIGHT

(LBS)

*BASED ON MITSUBISHI

EER MOCP

SENSIBLE

COOLING

CAPACITY

(BTU/H)

HEATING

CAPACITY

@47degF

(BTU/H)

10,500

MINIMUM

COOLING

CAPACITY

(BTU/H)

AC-01 MSY-GL24NA* WALL MOUNTED 562 22,400 45208/230 1 60 1.0 35N/A

MOCP

1.0

AHU-01 SVZ-KP36NA2* AIR HANDLER 1010 33,400 45208/230 1 60 4.1 13033,400 15

TEMP

(EFF%)

TOTAL EFF%

WINT/SUM

EF-02 GREENHECK G-090-VG ROOF 600 0.35 6.5 120 1 60 1/10 17.0 7.25 18.0

EF-03 GREENHECK G-080-VG ROOF 350 0.35 6.5 120 1 60 1/10 17.0 7.25 18.0

EF-04 GREENHECK G-060-VG ROOF 120 0.25 6.5 120 1 60 1/15 17.0 7.25 18.0

SYMBOL

NO.

MANUFACTURER/MODEL

NO.

EH-01 MODINE HER 30C 380 3.0

ELECTRIC HEATER SCHEDULE

HEAT

THROW

(FT.)

ELECTRICAL DATA

VOLTS PHASE HZ AMPS

240 1 60 12.5 15

DIM

(IN)

14x17x18

WEIGHT

(LBS)

BLOWER

FAN

(CFM) MOCP

HEAT

CAPACITY TEMP RISE

(DEG.F)(KW)

EH-02 BERKO CZ1548T 50 1.5 12 5 240 1 60 6.2 15 9x12x5 10

SYMBOL MANUFACTURER/MODEL

NO.

LOCATION

TYPE

CD-01 TITUS MCD CEILING SUPPLY DIFF

AIR DEVICE SCHEDULE

PANEL

FRAME SIZE

24x24

NECK

SIZE

6Ø

AIR FLOW DATA

MIN MAX APD NC

0 120 0.01 25

OPPOSED

NO

FINISH

TBD

REMARKS

CD-02 TITUS MCD CEILING SUPPLY DIFF 24x24 8Ø 80 240 25 NO EG-01 TITUS 350R DUCT EXHAUST 18x8 18x8 120 550 25 YES EG-02 TITUS 350R CEILING EXHAUST 8x4 8x4 0 120 25 NO

BASIS OF DESIGN MOUNTING

IN x IN IN CFM CFM IN WC

BLADE

DAMPER

RG-01 TITUS 350R CEILING RETURN 30x16 30x16 0 1100

0.01 0.01 0.01

0.01 25 NO

TBD

TBD

TBD

TBD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

M-601

MECHANICAL SCHEDULES

MP

NG

NGMP

NPCW

X

XXX

OFL

OD

RWL

PSD

OFL

OD

RWL

PSD

SS

SD

SS

SSD

TP

TW

V

SINGLE LINE DOUBLE LINE

ABBREVIATION DESCRIPTION

SD

SS

SSD

TP

TW

V

NPHW

NPCW

NPHW

D

DI

DIWS

DIWR

SYMBOL

AV

AW

CA

CND

ABBREVIATION

AV

AW

CA

CW

CD

D

DI

DIWS

DIWR

HW

DHC

MP

NG

NGMP

DESCRIPTION SYMBOL ABBREVIATION DESCRIPTION

PLUMBING SYSTEMS LEGEND PLUMBING SYMBOLS LEGEND PLUMBING GENERAL NOTES

PLUMBING PIPE SYMBOLS LEGEND

HWR

DCW

SS

RAIN WATER OVERFLOW LEADER

OVERFLOW DRAIN

RAINWATER LEADER

PUMPED STORM DRAIN

SANITARY SEWER

STORM DRAIN

SANITARY SEWER

SUB-SOIL DRAIN

TRAP PRIMER WATER

TEMPERED OR TEPID WATER

VENT FOR SANITARY SEWER

NONE POTABLE COLD WATER

NONE POTABLE HOT WATER

ACID VENT

ACID WASTE

COMPRESSED AIR

COLD DOMESTIC WATER

CONDENSATE DRAIN

DRAIN

DEIONIZED WATER

DEIONIZED WATER SUPPLY

DIIONIZED WATER RETURN

HOT DOMESTIC WATER

HOT DOMESTIC WATER RECIRC

MEDICAL PRESSURE CONDENSATE

NATURAL GAS

NATURAL GAS MEDIUM PRESSURE

CIRCUIT SETTER VALVE

BALL VALVE

BALANCING VALVE

CHECK VALVE

GATE VALVE

PLAN VIEW

A.F.F. ABOVE FINISHED FLOOR--

ANCHOR

BACKFLOW PREVENTER, REDUCE PRESSURE TYPE

BALL VALVE

BOTTOM CONNECTION

CHECK VALVE

CALIBRATED BALANCING VALVE

CONDENSATION DRAIN & SECONDARY CONDENSATE DRAIN

CONNECT

ENERGY MANAGEMENT CONTROL SYSTEM

EXISTING

FROM ABOVE, FROM BELOW

FLOOR CLEANOUT

FLOOR DRAIN

FLOOR SINK

FLOW ARROW

GATE VALVE

GRADE CLEANOUT

HOSE BIBB

INVERT ELEVATION

LIMIT OF DEMOLITION

NON POTABLE

PIPE BREAK

PIPE CAP

PIPE DOWN

PIPE GUIDE

PIPE UP

POINT OF CONNECTION

ROOF DRAIN AND OVERFLOW

ROUGH-IN AND CONNECT

SHUT OFF VALVE

STRAINER

TO ABOVE, TO BELOW

TRAP PRIMER

VENT, VENT RISER, VENT THRU ROOF

WALL CLEANOUT OR END OF LINE CLEANOUT

WASTE DROP

WATER HAMMER ARRESTOR

WITH

UNDER GROUND

UNION

A.F.F.

A.F.F.

A.F.F.

A.F.F.

A.F.F.

A.F.F.

A.F.F.

A.F.F.

EMCS

(E)

FA,FB

FCO

FD

FS

GCO

HB

IE

POD

NP

POC

RD & OF

RICONN

SOV

TA,TB

TP

V, VR, VTR

WD

WHA

W

UG

TYPICALTYP.

XX

XXX

100-SP-1

DRAWING SYMBOLS

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DEMO KEY NOTE ITEM

DETAIL NUMBER

DETAIL NUMBER

DETAIL NUMBER

DETAIL NUMBER

DETAIL NUMBER

XX KEY NOTE ITEM

1. KEEP ALL VTR'S MINIMUM 25FT FROM FRESH AIR INTAKES, AND MINIMUM 4FT FROM EXTERIOR WALLS WHETHER SHOWN OR NOT.

2. ALL NEW PIPING SHOWN ON PLUMBING PLAN IS INDICATED AS BOLD LINE TYPE.

3. OFFSET ALL RISERS AND DROPS TO AVOID PENETRATIONS THROUGH TOP PLATES.

4. CONTRACTOR SHALL FIELD VERIFY EXACT SIZES, LOCATIONS AND ELEVATIONS OF ALL PIPING CONNECTIONS AND OTHER WORK PRIOR

TO TRENCHING OR INSTALLING NEW WORK.

5. ALL SHUT-OFF VALVES SHALL BE LINE SIZE UNLESS OTHER WISE NOTED.

6. CONNECT CONDENSATE DRAIN PIPING TO EQUIPMENT WITH P-TRAP. PROVIDE CLEANOUTS AT ALL CHANGE IN DIRECTION.

7. THE DRAWINGS ARE NOT INTENDED TO SHOW EVERY OFFSET OR FITTING OR EVERY STRUCTURAL DIFFICULTY THAT MAY BE ENCOUNTERED DURING INSTALLATION OF THE WORK. LOCATION OF ALL ITEMS NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY. EXACT LOCATIONS NECESSARY TO SECURE BEST CONDITIONS AND RESULTS MUST BE DETERMINED AT THE JOB SITE AND SHALL HAVE THE APPROVAL OF THE ARCHITECH BEFORE BEING INSTALLED. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING LOCATIONS OF ITEMS OF WORK. ADJUSTMENTS SHALL BE MADE AS REQUIRED AT NO ADDITIONAL COST TO OWNER.

8. HVAC EQUIPMENT IS SHOWN FOR THE COORDINATION OF UTILITIES ONLY, SEE "MH" SHEETS FOR MORE INFORMATION.

9. FOR APPLICABLE CODES REFER TO ARCHITECTURAL SHEETS.

10. FOR CONDENSATE DRAIN PIPING, DEPTH OF "P" TRAP SHALL BE GREATER THAN THE TTOAL SCHEDULED FAN PRESSURE FOR THE UNIT.

11. OFFSET ALL RISERS AND DROPS TO AVOID STRUCTURAL ELEMENTS. SEAL ALL PENETRATIONS THROUGH FLOOR WATER TIGHT.

12. FIELD VERIFY EXACT SIZES, LOCATIONS AND ELEVATIONS ALL EXISTING PIPING CONNECTIONS SITE AND CLOSELY COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO TRENCHING OR INSTALLING ANY NEW WORK. DRAWINGS ARE DIAGRAMMATIC ONLY.

13. PROVIDE SHUT-OFF VALVES ON DOMESTIC WATER PIPE BRANCHES EQUIPMENT AND ON BRANCHES SERVING TWO OR MORE PLUMBING FIXTURES. WATER PIPING SERVING MAJOR FIXTURE GROUPINGS SUCH AS TOILET ROOMS, SUITES AND THE LIKE SHALL ALSO BE PROVIDED WITH SECTIONALIZING VALVES TO PERMIT SERVICING OR REPLACEMENT OF PIPING, FIXTURES AND EQUIPMENT.

14. COORDINATION SHOP DRAWINGS ARE REQUIRED TO AMPLIFY, EXPAND AND COORDINATE THE INFORMATION CONTAINED IN THE CONTRACT DOCUMENTS. APPROVED SHOP DRAWINGS ARE REQUIRED PRIOR TO THE INSTALLATION OF ALL NEW WORK.

15. ACCESS PANELS SHALL BE PROVIDED WHERE NECESSARY TO PROPERLY ACCESS THE PLUMBING SYSTEM, INCLUDING VALVES.

16. IF APPLICABLE, PROVIDE FLOOR CLEANOUTS IN ALL UNDERGROUND SANITRAY SEWER WASTE AND STORM DRAINS LINES INSIDE THE BUILDING AT EVERY 50FEET AND AT CHANGE OF DIRECTION GRATER THAN 45 DEGREES ACCUMULATIVE, COORDINATE LOCATIONS WITH ARCH PRIOR TO INSTALLATION. ALSO PROVIDE CLEANOUTS AT TOP AND BOTTOM OF ALL STACKS. EXTEND ABOVE THE FLOOR RIM ELEVATION OF ANY FIXTURE LOCATED NEAR THE CLEANOUTS AND BE CONNECTED TO THE SAME WASTE LINE.

17. DOMESTIC HOT WATER UNCIRCULATED LINES BRANCH LINES TO FIXTURES SHALL BE A MAXIMUM OF F FEET TO ALL SENSOR ACTIVATED MIXING STYLE FAUCETS AND A MAXIMUM 15 FEET TO ANY FAUCET WITH CONVENTIONAL CONTROLS.

18. ALL PENETRATIONS OF PIPES, CONDUITS , ETC. THRU RATED ASSEMBLIES SHALL BE FIRE STOPPED. MATERIAL SHALL BE TESTED UL

LISTED ASSEMBLY APPROVED BY THE STATE FIRE MARSHALL.

19. PROVIDE WALL CLEANOUTS AT ALL SINKS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

P-001

PLUMBING SYMBOLS &

Fridge

FD

FD

1. 1" BACKFLOW PREVENTER

2. WALL MOUNTED 1" MIXING VALVE, PROVIDE WITH WALL MOUNTED CABINET.

(NOT ALL KEYED NOTES USED ON THIS SHEET)KEYED NOTES:

3. SEE CIVIL PLANS FOR CONTINUATION.

4. ROUTE NEW 1" WATER LINE UNDER SLAB INTO MECHANICAL ROOM.

5. ROUTE NEW 1" HOT WATER AND 12" HW RECIRC LINES BELOW GRADE, ROUTE

TO MAINTENANCE BUIDING FOR SAFETY SHOWER TEMPERING.

P-301

P-301

P-301

P-402

P-806

P-707

EWH-01

P-101

P-101

P-701

P-701

P-201

P-606

P-501

P-910

P-910

P-9101

WCO

WCO

WCO

WCO

CP-1

MV-1

P-910

FDP-701

P-101

P-606 P-402

P-301

P-910 P-501 P-701

P-101

P-910

P-201 P-301 P-301

FD FD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

P-101

PLUMBING FLOOR PLANS

1. WALL MOUNTED ELEC WATER HEATER

2. REMOVE EXISTING PLUMBING FIXTURES, INCLUDING EXPOSED SANITARY, VENT

AND WATER LINES. CAP SANITARY LINES BELOW SLAB, PATCH SLAB TO MATCH

EXISTING. CAP WATER LINES AT WALL.

3. CONNECT NEW SAFETY SHOWER TO 1" WATER LINE FROM MIXING VALVE, SEE CIVIL

PLANS FOR LOCATION FOR 1" WATER LINE TO BUILDING.

4. TAP 34" LINE FROM 1" COLD WATER LINE, CONNECT TO HOSE BIBB.

5. NEW 1" MIXING VALVE FOR SAFETY SHOWER.

6. NEW 1" HOT WATER LINE FROM ADMINISTRATION BUILDING BELOW GRADE. PEX

PIPING WITH 1" ARMAFLEX CLASS O NITRILE FOAM INSULATION OR EQUIVALENT.

7. INSTALL HEAVY DUTY FLOOR DRAIN WITH SEDIMENT BUCKET.

8. ROUTE 3" SANITARY LINE TO OIL INTERCEPTOR, SEE CIVIL PLANS FOR LOCATION.

9. NEW AIR COMPRESSOR

(NOT ALL KEYED NOTES USED ON THIS SHEET)KEYED NOTES:

P-806

P-707 1

MV-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

P-102

PLUMBING FLOOR PLANS

B1 EMER EYEWASH/SHPWER BOUNDARY DETAIL

NTS B3 EMER EYEWASH/SHOWER PIPING DETAIL

NTS

D1 WATER CLOSET AND URINAL DETAIL

NTS

B5 POINT OF USE MIXING VALVE DETAIL

NTS

LAVATORY/SINK

NEW POINT

OF USE

MIX-VALVE.

HOT COLD

STOP VALVES

STOP VALVES

1. INSTALL MIXING VALVE UNDER SINK.

2. INSULATE ALL NEW SUPPLY PIPING

CONNECTIONS.

3. PROVIDE REMOVABLE INSULATION PADS FOR

MIX-VALVE AND SHUT OFF VALVES.

4. INSTALL 38" ISOLATION VALVES AT EACH

CONNECTION TO MIXING VALVE.

NOTE:

D3 FLOOR DRAIN TRAP PRIMER DETAIL

NTS D5 AIR COMPRESSOR DETAIL

NTS

F1 ELECTRIC WATER HEATER DETAIL

NTS F3 PIPE SLEEVE THROUGH WALL DETAIL

NTS F5 WALL CLEANOUT DETAIL

NTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

P-501

PLUMBING DETAILS

RECIRCULATION PUMP SCHEDULE

MIXING VALVE SCHEDULE

ELECTRIC WATER HEATER SCHEDULE

SYMBOL SERVICE TYPE

CAPACITY

VOLTS/PHASE H.P. MFG. AND MODEL No. REMARKS

CP-1 DHW RECIRC CIRCULATOR

GPM HEAD(FT)

-- -- 120/1 1/40 TACO HLS-2 HOT LINK

SYMBOL DISCHARGE

TEMPERATURE

MAXIMUM

FLOW GPM

PRESURE DROP

@ MAX FLOW

CAPACITY

CW IN HW IN MIXED OUT MFG. AND MODEL No. REMARKS

SYMBOL STORAGE

CAPACITY

(GALLONS)

CAPACITY

@ 60°F RISE

(GPH)

POWER REQUIRMENTS

(KW)/VOLTAGE/PHASE MFG. AND MODEL No. LOCATION REMARKS

EWH-1 55 67 6.0KW/240V/1PH STATE WATER HEATER/ EE8-5-DFRS0 MECH RM.

2"3" - ZURN Z5615, WALL MOUNT, TOP SPUD, ABA COMPLIANT, ELONGATED BOWL. PROVIDE W/ ZURN Z5955SS-EL OPEN FRONT SEAT, SLOAN ROYAL 111-1.28ES 1.28 GPF SENSORY FLUSH VALVE, SLOAN EL-154

TRANSFORMER, JR SMITH 0417 CARRIER.

WATER CLOSET

(ADA)P101

-- WATTS #LF15M2, LEAD-FREE, 60 PSI AIR PRE-LOAD, PER PDI WH201. PROVIDE W/ ACCESS PANEL.

WATER

HAMMER

ARRESTER

P905

2"2"

ZURN Z5351, WALL MOUNTED, 19"x17", WHITE VITREOUS CHINA. PROVIDE W/ SLOAN OPTIMA SYSTEM FAUCET MODEL ETF-80 HARDWIRED SENSOR ACTIVATED, ZURN Z8743-1-PC GRID STRAINER DRAIN, Z8700-PC CHROME PLATED P-TRAP AND TRUEBRO LAV GUARD 2 E-Z MODEL #102E-Z; BRASSCRAFT REGULAR PART NUMBER SCR39 C REGULAR PATTERN COMPRESSION JOINT ANGLE VALVE WITH LOOSE

KEY, POLYMER BRAID CONNECTORS, AND ESCUTCHEON PLATES

P301 LAVATORY

(ADA)

PLUMBING FIXTURE SCHEDULE

ITEM DESCRIPTION

MINIMUM ROUGH-IN

CONNECTION (INCH) REMARKSELECTRICAL DATA

CWVW HW

2"11

2"2"

JUST MFG SLN-ADA-2122, LEDGE MOUNT, STAINLESS STEEL, 21"Lx22"Wx6"D. PROVIDE W/ CHICAGO FAUCET AGN8AE2805-5CP 0.5 GPM AERATOR GOOSENECK, DUAL WRIST BLADE HANDLE; JUST #J-ADA-35-FS PUNCH DRAIN AND REMOVABLE STRAINER; CHROME PLATED P-TRAP (HOT WATER SUPPLY AND P-TRAP SHALL BE TRUEBRO WRAPPED FOR ACCESSIBILITY PROTECTION; BRASSCRAFT COMPRESSION JOINT ANGLE VALVE, POLYMER BRAID CONNECTORS, AND ESCUTCHEON PLATES

2"P402 BREAKROOM

SINK

P606 DRINKING

FOUNTAIN

HAWS 1119.8, DUAL HIGH-LOW, WALL MOUNTED, 304 STAINLESS STEEL CONSTRUCTION. PROVIDE W/ HAWS

SK1 CANE SKIRT, HCR8 CHILLER, MTGFR.LG CARRIER AND 6426 WATER FILTER.2 1

2" -

2" 1

2"

P906 -TRAP PRIMER WATTS #WPIME-1, COMPLETE W/ QUARTER-TURN BRASS VALVE AND ENCLOSURE1 2"--

TRAP

INT

2"

2"

2"

2"

-1 2"

2"

115V, 60HZ, 370W,

5FLA

P806 -HOSE-BIB WATTS #SC8-6, HEX SHOULDER W/ TEE HANDLE AND VACUUM BREAKER--- -

P707 -

EMERGENCY

EYEWASH

SHOWER

HAWS 8336, SCHED 80 PVC GREEN EPOXY FINISH, 316 STAINLESS STEEL BALL VALVE, ANTI-CORROSIVE, AXION MSR SHOWERHEAD AND FACE BOWL W/ INTEGRAL FLOW CONTROL. PROVIDE W/ SP170 TEST CARD

AND SP178LG FIXTURE SIGNAGE.

P711 -EMERGENCY

ALARM

HAWS 9001TYPE4X, AUDIBLE 60dB, VISUAL FLASHING AMBER LIGHT, DOUBLE POLE FLOW SWITCH

ACTIVATED.- - 120VAC, 60HZ

- 11 4"

2"

4"

P701 SHOWER J.R. SMITH FIGURE 2005Y-A05-B-P050-CP, ROUND ADJUSTABLE STRAINER WITH SEDIMENT BUCKET, CHROME PLATED STRAINER AND TRAP PRIMER CONNECTION.2" 2" 1

2"2" -

(ADA)

2"

2"

MV-1 85F 20 10PSI 15 5.0 BRADLEY S19-210020

MV-2 110F 2.0 10PSI 0.75 0.75 WEBSTONE H-72202W1.5 POINT OF USE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENT

SUBMITTAL

N/A

National Cemetery Administration

Design and Construction Service

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

18300 East 71st Ave., Denver, CO, 80249 504.684.4408; Sean Fitzpatrick

LOS ANGELES NATIONAL CEMETERY

REPLACE STORAGE BUILDING

Los Angeles, CA

898CM3034

N/A Project Director

05/24/2023Revisions: Date:

Juan Kays Department of Veterans Affairs, NCA

Phone: 202.632.5057 Email: juan.kays@va.gov Sheet of 95

VCI Project Management Construction Management Engineering

BSTM

1331 17TH STREET SUITE 605

DENVER, COLORADO 80202

PHONE: (720) 439-4700

WEBSITE: www.dci-engineers.com

CIVIL / STRUCTURAL

5/24/23

P-601

PLUMBING SCHEDULES

File details come from the government source that posted it. Updated .