22438 Drawings 5.pdf

PDF 2 MB Posted

Attached to
751/22438. ABG; Muskallonge Lake SP - Toilet and Shower Bldg.
Solicitation number
RFQ - 171 - 230000000616
Issued by
Luce County, Michigan

About this file

This document contains drawings and specifications for a mechanical and electrical systems upgrade project for the West Campground Toilet and Shower Building at Muskallonge Lake State Park in Newberry, Michigan. The project is being managed by the State of Michigan Design and Construction Division, Department of Technology, Management and Budget, and State Facilities Administration.

The mechanical scope includes installing a new gas-fired furnace, exhaust air ventilator, and associated ductwork and air distribution equipment. The electrical scope includes new power distribution, lighting, and control systems. The project has an estimated connected electrical load of 8.67 kVA. Bidders must upload their proposals to the SIGMA VSS system by the 2:00 PM deadline on the due date. The contract term and any renewal options are not specified in the provided documents.

View the file

Other files

File Type Posted
22438 Specs 2.pdf PDF
22438 Addendum 1 Part 1.pdf PDF
22438 Drawings 4.pdf PDF
22438 Advertisement.pdf PDF
22438 Specs 1.pdf PDF
22438 Addendum 4.pdf PDF
22438 Addendum 1 Part 2.pdf PDF
22438 Drawings 3.pdf PDF
22438 Drawings 1.pdf PDF
22438 Addendum 2.pdf PDF
22438 Specs 3.pdf PDF
22438 Addendum 3.pdf PDF
22438 Drawings 2.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PORCH A

PORCH B

MEN'S

WOMEN'S

STORAGE ROOM

SHOWER

SHOWER

SHOWER

SHOWER

LAVATORY

F-1

ERV-1

x8 x8

24x12

8x6 x1

6x

12x6 RA

12x6 RA

S A

EA

S A

12x6 RA

12x6 RA

24x14 RA

16x14 RA

6x10 SA

24x14 OA

105.2

104.2

104.4

275 105.4

105.1

104.3

105.3

104.1

111.2

111.1

107.1

107.2

108.1

108.2

109.2

109.1

110.2

110.1

106.1

300 CFM OED

W/DAMPER

M-101

M-101

3" FLUE AND COMBUSTION

AIR UP TO CONCENTRIC

ROOF TERMINAL

76" W X 26" H, 8" DEEP PLENUM.

CONNECT TO LOUVER PROVIDED BY

ARCH. COVER SECTIONS OF LOUVER

NOT COVERED BY PLENUM WITH

INSULATED PANEL. PROVIDE INSECT

SCREEN. PAINT INSIDE OF DUCT &

INSULATED PANEL BLACK.

8x8 SA 8x8 SA

106.2

8x8 SA

8x8 SA

6x6 RA

6x6 SA

8x4 RA 8x4 SA

6x6 RA

8x4 SA 8x4 SA6x6 RA

8x4 SA

T

F-1

82" W X 30" H, 8" DEEP PLENUM. CONNECT

TO LOUVER PROVIDED BY ARCH. COVER

SECTIONS OF LOUVER NOT COVERED BY

PLENUM WITH INSULATED PANEL.

PROVIDE INSECT SCREEN. PAINT INSIDE

OF DUCT & INSULATED PANEL BLACK.

THERMOSTAT WHITE

RODGERS MODEL

1F95E2-0671

REMOTE SENSOR

WHITE RODGERS

MODEL F145-1328-

S

24x22 SA

24x14 OA

12x10 SA

SEAL DUCTWORK AROUND COLUMN

3" FLUE AND COMBUSTION

AIR UP TO 4" CONCENTRIC

ROOF TERMINAL

R A

16x16

SA

ERV-1

F-1

6x6

16x16

12x24

6x6

EA

10x6SA

SA

SA

RA

STORAGE ROOM

PORCH B

3" CONCENTRIC VENT

3" VENT

WH-1 WH-1

MOUNT TO UNISTRUT, REFER TO

SHEET A-301 (TYP F-1 & ERV-1)

10x6 SA

12x18 SA

8x4 SA

8x4 SA

106.1

76" W X 26" H, 8" DEEP PLENUM CONNECT TO

LOUVER PROVIDED BY ARCH. COVER

SECTIONS OF LOUVER NOT COVERED BY

PLENUM WITH INSULATED PANEL. PROVIDE

INSECT SCREEN. PAINT INSIDE OF DUCT &

INSULATED PANEL BLACK.

4" CONCENTRIC VENT

3" COMBUSTION

AIR

CONCENTRIC VENTS TO BE MIN 3' ABOVE

ROOF, SPACED 2" APART, ALIGNED

14x16 RA

10x12 18x12SA

ERV-1

8x10

SA

109.2

STORAGE ROOM

SHOWER

RA

14x24 OA

106.2

82" W X 30" H X 8" DEEP PLENUM CONNECT

TO LOUVER PROVIDED BY ARCH. COVER

SECTIONS OF LOUVER NOT COVERED BY

PLENUM WITH INSULATED PANEL.

PROVIDE INSECT SCREEN. PAINT INSIDE

OF DUCT & INSULATED PANEL BLACK.

8x8 SA

16x16 SA

6x6 RA

12x16 EA

12x6 SA 12x6 SA

8x8 SA

8x8 SA

1. ALL DUCT SHALL BE MOUNTED AT LEAST 8'-0" A.F.F.

2. ERV / FURNACE / DUCTWORK SHALL BE SUPPORTED FROM UNI-STRUT ABOVE. ALL DUCT SHALL BE

MOUNTED AT LEAST 8'-0" A.F.F.

GENERAL NOTES - MECHANICAL

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M D

IS

C

IP

LI

N E

L E

A D

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

7/ 5/

:3

5:

P M

B

IM

-2

2-

M us ka llo ng e S ta te

P ar k/

_F P

M E

_M S

P _A

2W es tC G

B ld g_

_C

E N

.rv t

M-101

F

IR

S T

F

LO

O R

M E

C H

A N

IC

A

L P

LA

N

C ou nt y R oa d

N ew be rr y, M

I 4

M U

S K

A

LL

O N

G E

L A

K E

S T

A T

E P

A R

K

W E

S T

C A

M P

G R

O U

N D

T O

IL

E

T S

H O

W E

R B

U

IL

D

IN

G

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

-2 2-

Z H

/0 7/

1.

8.

A

B G

D T

M B

F ile

N o.

LA

1/4" = 1'-0"1

FIRST FLOOR HVAC PLAN

1/4" = 1'-0"2

DUCTWORK SECTION 1

1/4" = 1'-0"3

DUCTWORK SECTION 2

FUSED

SWITCH

F-1

CONCENTRIC

COMBUSTION &

FLUE PIPING

ERV-1

EXHAUST AIR TO

OUTSIDE

SUPPLY AIR (CONNECT TO

FURNACE RETURN AIR)

FRESH AIR

FROM OUTSIDE

PROVIDE CLEARANCES

FOR DOORS TO FULLY OPEN

RETURN AIR

SUPPLY AIR TO ROOMS

GAS COCK

DIRT LEG

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M D

IS

C

IP

LI

N E

L E

A D

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

7/ 5/

:3

5:

P M

B

IM

-2

2-

M us ka llo ng e S ta te

P ar k/

_F P

M E

_M S

P _A

2W es tC G

B ld g_

_C

E N

.rv t

M-601

M E

C H

A N

IC

A

L S

C H

E D

U

LE

S

C ou nt y R oa d

N ew be rr y, M

I 4

M U

S K

A

LL

O N

G E

L A

K E

S T

A T

E P

A R

K

W E

S T

C A

M P

G R

O U

N D

T O

IL

E

T S

H O

W E

R B

U

IL

D

IN

G

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

-2 2-

Z H

/0 7/

1.

8.

A

B G

D T

M B

F ile

N o.

LA

AIR TERMINAL SCHEDULE

MARK CFM MANUFACTURER MODEL SUPPLY RETURN EXHAUST DIMENSIONS

104.1 225 PRICE 620 X 8X8

104.2 225 PRICE 620 X 8X8

104.3 275 PRICE 80 X 12X6

104.4 275 PRICE 80 X 12X6

105.1 225 PRICE 620 X 8X8

105.2 225 PRICE 620 X 8X8

105.3 275 PRICE 80 X 12X6

105.4 275 PRICE 80 X 12X6

106.1 300 PRICE 620 X 12X6

106.2 300 PRICE 80 X 12X6

107.1 75 PRICE 620 X 8X4

107.2 100 PRICE 80 X 6X6

108.1 75 PRICE 620 X 8X4

108.2 100 PRICE 80 X 6X6

109.1 75 PRICE 620 X 8X4

109.2 100 PRICE 80 X 6X6

110.1 75 PRICE 620 X 6X6

110.2 100 PRICE 80 X 6X6

111.1 100 PRICE 620 X 8X4

111.2 100 PRICE 80 X 6X6

NOTES 1. INTERLOCK TO FURNACE FAN

ERV-1 106 STORAGE 1600 84/71 77/67 -5 50 0.75 1900 0.75 2 230 1 2 230 1 2" MERV-8 RENEWAIRE HE2XINH 1

MARK LOCATION CFM SUMMER EAT (°F) (DB/WB) SUMMER LAT (°F) (DB/WB) WINTER EAT (°F) WINTER LAT (°F) ESP (IN-WG) CFM ESP (IN-WG) HP VOLTAGE PHASE HP VOLTAGE PHASE FILTERS MANUFACTURER MODEL NOTES

SUPPLY AIR EXHAUST AIR SUPPLY FAN EXHAUST FAN

ENERGY RECOVERY VENTILATOR SCHEDULE

3. PROVIDE LP GAS CONVERSION KIT, CONCENTRIC VENT KIT & LP GAS REGULATOR.

2. PROVIDE 7 DAY PROGRAMMABLE WALL MOUNTED THERMOSTAT.

NOTES: 1. FURNACE FAN TO RUN ON OCCUPANCY SCHEDULE SET BY OWNER.

F-1 106 STORAGE 120 117 2020 N/A 115/1/60 16.7 20 3 3 CARRIER 59SC5B120E24--22 1,2,3

MARK LOCATION INPUT OUTPUT HEATING COOLING V/PH/HZ MCA MOCP FLUE COMBINATION AIR MANUFACTURER MODEL NOTES

MBH CFM ELECTRICAL CONNECTION DIAMETER (IN)

GAS FIRED FURNACE SCHEDULE

N.T.S

FURNACE TO ERV DETAIL

FURNACE & ERV SEQUENCE OF OPERATION

OCCUPIED:

7 DAY PROGRAMMABLE THERMOSTAT SHALL RUN THE FURNACE SUPPLY FAN AND ERU SUPPLY AND EXHAUST FANS CONTINUOUSLY. THE FURNACE GAS FIRED

BURNER SHALL CYCLE TO MAINTAIN THE REMOTE SENSOR SETPOINT.

THIS SHALL BE COMPLETED BY USING A RELAY CONTROLLED BY THE THERMOSTATS “G” FAN WIRE TO CLOSE CONTACTS 1-4 AND 1-5 ON THE ERV TERMINAL BLOCK.

UNOCCUPIED:

THE 7 DAY PROGRAMMABLE THERMOSTAT SHALL DISABLE THE FURNACE FAN AND THE ERV FANS DURING UNOCCUPIED TIMES. THE FURNACE GAS FIRED BURNER AND THUS THE FURNACE FAN SHALL CYCLE TO MAINTAIN REMOTE SENSOR SETPOINT. DURING TIMES OF CALL FOR HEAT THE ERU SUPPLY AND EXHAUST FANS

SHALL RUN.

THIS SHALL BE COMPLETED BY LETTING THE THERMOSTAT CONTROL THE FURNACE ON THE “W” HEATING TERMINAL. WHEN THE HEAT CALL IS ACTIVE THE “G” TERMINAL WILL ALSO BE ACTIVE AND THE RELAY WILL CLOSE CONTACTS 1-4 AND 1-5 ON THE ERV TERMINAL BLOCK.

CABLE TV, TELEPHONE,

DATA OR DUPLEX RECEPT

OUTLET (UNLESS NOTED)

TOP OF

COUNTER

BASEBOARD RADIATOR

FIRE ALARM

HORN/SPEAKER/STROBE

SWITCHES,

THERMOSTAT, WALL

OCCUPANCY SENSOR,

FIRE ALARM PULL

STATION

FLOOR

ELECTRIC WATER COOLER

CEILING

CL

7'

4'

6" M

IN

ELECTRICAL OUTLET

6"

6"

CL

/4

RECOMMENDATIONS

PER MANUFACTURERS

POWER CIRCUIT WIRING

UNDERGROUND WIRING

SWITCH LOOP WIRING

UN-SWITCHED HOT WIRING

LOW VOLTAGE WIRING

DATA WIRING

PROPOSED EXISTING DEMOLISH

TYPICAL 3⌀ 4-WIRE

DRY-TYPE UTILITY

TRANSFORMER

T-X

TYPICAL 3⌀ 4-WIRE

DRY-TYPE TRANSFORMER

SERVICE FROM SERVICE PANEL

T-X

BRANCH PANEL

CONNECTIONS BY

UTILITY

SUPPLY-SIDE

BONDING JUMPER

SERVICE

PANEL

G

NEU. NEU.

G

BRANCH PANEL

GROUNDED CONDUCTOR

GROUNDING ELECTRODE

CONDUCTOR

GROUNDING ELECTRODE

REFER TO NOTE 2

EQUIPMENT GROUNDING

CONDUCTOR

MAIN BUILDING JUMPER

GRADE

GROUNDED CONDUCTOR SYSTEM BONDING

JUMPER

SUPPLY-SIDE

BONDING

JUMPER

SEPARATELY DERIVED SYSTEM

G

NEU.

1. SIZE GROUNDING/BONDING CONDUCTORS PER NEC ARTICLE 250

2. GROUNDING ELECTRODE SYSTEM AS PER NEC ARTICLE 250 SECTION III.

NOTES

1. ALL ELECTRICAL INSTALLATIONS SHALL BE IN ACCORDANCE WITH THE CURRENT NATIONAL ELECTRICAL CODE AND ANY STATE/LOCAL AMENDMENTS.

2. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACQUISITION OF AN ELECTRICAL PERMIT AND SCHEDULING OF THE NECESSARY

INSPECTIONS. UPON COMPLETION OF THE WORK THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE OWNER EVIDENCE OF INSPECTION APPROVAL.

3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COORDINATION REQUIRED WITH THE ELECTRIC UTILITY SERVING THE FACILITY. UTILITY

COSTS SHALL BE PAID SEPARATELY BY THE OWNER.

GENERAL NOTES - ELECTRICAL

SURFACE / CEILING MOUNT

EMERGENCY SURFACE / CEILING

MOUNT

PENDANT / CHAIN MOUNT

EMERGENCY PENDANT / CHAIN

MOUNT

RECESSED MOUNT

EMERGENCY RECESSED MOUNT

COMBINATION FAN / LIGHT

TRACK STRIP

WALL MOUNT

EMERGENCY WALL MOUNT

EXTERIOR POLE MOUNT

EXTERIOR POST MOUNT

EMERGENCY WALL PACK

EXIT SIGN

CEILING FAN

DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

COMBINATION MOTOR STARTER

WITH DISCONNECT SWITCH

MOTOR STARTER

ELECTRICAL METER

DISTRIBUTION PANEL

ELECTRICAL POWER PANEL

SURFACE MOUNT

ELECTRICAL POWER PANEL

FLUSH MOUNT

LIGHITNG CONTROL PANEL

RELAY

ELECTRICAL TRANSFORMER

ELECTRICAL PULL BOX

JUNCTION BOX

SINGLE PHASE MOTOR

THREE PHASE MOTOR

VARIABLE FREQUENCY DRIVE

X = NUMBER AND TYPE OF PORTS

C COAXIAL PORT

D DATA PORT

H HDMI PORT

P PHONE PORT

W WIRELESS ACCESS POINT

X

X H Z

SENSORS

J J

PC

IC

PS

K

CR

DL

M

R

A

CO

HD

F F

F F

T

PB

1. MINIMUM SIZE OF RIGID CONDUIT SHALL BE 3/4".

2. MINIMUM SIZE OF FLEX CONDUIT SHALL BE 1/2".

3. MINIMUM SIZE WALL BOX IN CMU SHALL BE

4"X4".

4. MINIMUM SIZE OF UNDERGROUND CONDUIT

SHALL BE 1 1/4"

J

(WALL) (CEILING)

NURSE

N

N

FACP

FAA

FS

TS

PS

DH

C

P

(LIGHT)(NO LIGHT)

CARD READER

MAGNETIC SWITCH (DOOR CONTACT)

ELECTRONIC DOOR LOCK

MOTORIZED DOOR OPERATOR

ELECTRIC STRIKE

KEYPAD ENTRY DEVICE

ENTRANCE CALL SYSTEM

SECURITY CAMERA

PANIC ALARM SPEAKER/STROBE

ES

DP##

PP##

PP##

(WALL)

(CLG)

(FLR)

B

M

WG

HSS

OUTDOOR BELL / CHIME

SMOKE DETECTOR

SMOKE DETECTOR WITH AUDIBLE BASE

SMOKE/CARBON MONOXIDE DETECTOR

DUCT SMOKE DETECTOR

HEAT DETECTOR

FIRE ALARM HORN/STROBE

FIRE ALARM STROBE

FIRE ALARM SPEAKER

FIRE ALARM SPEAKER/STROBE

FIRE ALARM PULL STATION

ELECTROMAGNETIC DOOR HOLD OPEN

END OF LINE RESISTOR

FIRE ALARM FLOW SWITCH

FIRE ALARM PRESSURE SWITCH

FIRE ALARM TAMPER SWITCH

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

HOOD SUPPRESSION SYSTEM FIRE ALARM

CONTACT

ELR

I/C

DC

DO

SWITCHES: X = DESIGNATION BELOW

H = HUB CONTROLLER

Z = LIGHTING ZONE

PUSH BUTTON

EMERGENCY STOP BUTTON

PHOTOCELL

CEILING MOUNTED PULL SWITCH

WIRELESS NETWORK LIGHTING CONTROLLER

(HUB) H# = CONTROLLER INDICATOR

LIGHTING CONTROL SCHEME NUMBER

SINGLE POLE

2 TWO POLE

3 THREE WAY

4 FOUR WAY

DM DIMMER

F FAN

K KEY OPERATED

LV LOW VOLTAGE

M MOTION DETECTION

O OCCUPANCY SENSOR

P PILOT LIGHT

T TIMER

F F

S S

X

X X

(FURN)

SPEAKER

INTERCOM CALL BOX

BELL

MICROPHONE JACK

POWER SUPPLY

REQUIRES WIRE GUARD

NURSE CALL MAIN PANEL

NURSE CALL PULL STATION

NURSE CALL LIGHT

CLOCK

SIMPLEX RECEPTACLE

DUPLEX GROUNDED RECEPTACLE

208/240/480V, 1ϕ STRAIGHT BLADE RECEPTACLE

QUADRUPLEX RECEPTACLE

DUPLEX RECEPTACLE ON EMERGENCY POWER

FLOOR BOX

CEILING BOX

SPECIALTY RECEPTACLE

CTR MOUNTED ABOVE COUNTER

G GROUND FAULT CIRCUIT INTERRUPTER

GC GFCI - MOUNTED ABOVE COUNTER

U DUAL USB PORTS

UC DUAL USB PORTS ABOVE COUNTER

WP WEATHERPROOF RECEPT & COVER, GFI

H##

D DAYLIGHT

M MOTION DETECTION

O OCCUPANCY

V VACANCY

H = HUB CONTROLLER

Z = LIGHTING ZONE

XS X

H Z

S X H Z

LP##

(CEILING) (WALL)

(CEILING) (WALL)

(CEILING)

(WALL)

(WALL)(CLG)

(CLG) (WALL) (FLR)

ELECTRICAL SYMBOLS LEGEND

VFD

XX-X EQUIPMENT INDICATOR

INDICATES EXISTING

e LF-1

H Z

LIGHT FIXTURE INDICATOR

HUB CONTROLLER

LIGHTING ZONE

e

RACEWAY NOTES

WIRES

OTHER SYMBOLS

TELEPHONE/COMMUNICATIONS

FIRE ALARM SYSTEMRECEPTACLE OUTLETS

SECURITY

POWER DISTRIBUTION

LIGHT FIXTURES

SWITCHES

(360 VIEW)

P P

SX

(W/ LIGHTS)

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M D

IS

C

IP

LI

N E

L E

A D

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

7/ 5/

2:

:1

P

M B

IM

-2 2-

M us ka llo ng e

S ta te P ar k/

_F

P M

E _M

S P

_A 2W es tC

G B ld g_

_C E

N .r vt

E-001

E

LE

C T

R

IC

A L

N O

T E

S A

N D

S Y

M B

O

LS

C ou nt y R oa d

N ew be rr y, M

I 4

M U

S K

A

LL

O N

G E

L A

K E

S T

A T

E P

A R

K

W E

S T

C A

M P

G R

O U

N D

T O

IL

E

T S

H O

W E

R B

U

IL

D

IN

G

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

-2 2-

Z H

/0 7/

1.

8.

A

B G

D T

M B

F ile

N o.

S W

N.T.S

TYPICAL MOUNTING HEIGHTS

ABBREVIATIONS

_SPECIAL

Φ PHASE

A

A AMPERE

AFF ABOVE FINISHED FLOOR

C

C CONDUIT

CAT CATALOGUE

CB CIRCUIT BREAKER

CMU CONCRETE MASONRY UNIT

CO. COMPANY

CUH CABINET UNIT HEATER

E

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EWC ELECTRIC WATER COOLER

F

FA FIRE ALARM

G

G GROUND FAULT CIRCUIT

INTERRUPTER

GND EQUIPMENT GROUND

H

HID HIGH INTENSITY DISCHARGE

HPS HIGH PRESSURE SODIUM

HVAC HEATING VENTILATING & AIR

CONDITIONING

K

K KEY OPERATED DEVICE

KVA KILOVOLT-AMPERES

KW KILOWATTS

L

LED LIGHT EMITTING DIODE

M

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MH METAL HALIDE

MISC MISCELLANEOUS

MLO MAIN LUG ONLY

MTD MOUNTED

N

NEU NEUTRAL

No. NUMBER

P

PL PILOT

R

RECEPT RECEPTACLE

T

TEL TELEPHONE

TV TELEVISION

TYP TYPICAL

U

UGE UNDERGROUND ELECTRIC

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

V

V VOLT

VA VOLT-AMPERES

W

W WIRE

WNC WIRELESS NETWORK CONTROLLER

WP WEATHERPROOF

X

XFMR TRANSFORMER

N.T.S

GROUNDING BONDING DIAGRAM

WP

G

GC

GC

GC

GC

GC

GC

G

J

J

J

J

J

G G

J

J

J

J

J

J

J

J

J

J

GC

G

J J

JJ

J J

J

J

JJ

J J

A

F-1

ERV-1

RP-W

RP-W - 1

MOUNT RECEPTS 6' AFF

FOR POWER VENTING

POWER FOR HAND DRYERS. REFER

TO A-002 FOR TYPICAL MOUNTING

HEIGHTS (TYPICAL HAND DRYERS)

POWER FOR HAND DRYER

POWER FOR HAND DRYERS

4X4 J-BOX MOUNTED INTERIOR TO CMU FOR

AUTOMATIC FLUSH VALVES (TYPICAL WATER

CLOSET J-BOX). REFER TO DETAIL 1 ON

SHEET E-501 FOR MOUNTING HEIGHTS.

RECEPT BOX TO BE MOUNTED 3" FROM CORNER TO ALLOW

FOR PARTITION MOUNTING. SEE DETAILS 3 & 4 ON SHEET

A-452 FOR PROPER MIRROR AND OUTLET LOCATIONS

RP-W - 5

MEN'S

WOMEN'S

STORAGE ROOM

LAVATORY

SHOWER

SHOWER

SHOWER

SHOWER

PORCH B

PORCH A

RP-W - 3

RP-W - 3

RP-W - 7

RP-W - 8

RP-W - 6

RP-W - 9

MOUNT SINGLE TRANSFORMER FOR FLUSH

VALVES ABOVE CMU. FEED EACH SENSOR

J-BOX WITH 3/4" CONDUIT AND 2-#18AWG

THROUGH GROUTED CMU CAVITY.

RP-W - 20RP-W - 21

3/4" CONDUIT WITH 2-#12AWG + #12EG

3/4" CONDUIT WITH 2-#

10AWG + #10EG

3/4" CONDUIT WITH 2-#12AWG

+ #12EG

RP-W - 25

RP-W - 23

RP-W - 2,4

HH

2" CONDUIT WITH 3-#2/0AL AWG + #3 AL EG

EXISTING HANDHOLE TO BE DEMOLISHED AND A NEW HANDHOLE PLACED WITHIN GREEN

SPACE WITHIN EXISTING CONDUCTOR RUN. REMOVE EXISTING CONDUIT AND CONDUCTORS

APPROXIMATELY 8' FROM EXISTING BUILDING. SPLICE AND EXTEND CONDUIT AND

CONDUCTORS TO RP-W LOCATION FROM PROPOSED HAND HOLE. SEE SHEET C-201 FOR

PROPOSED LOCATION OF HAND HOLE.

STUB UP CONDUIT TO PANEL

WITH LOCKING COVER

RP-W - 22

RP-W - 18

RP-W - 10

RP-W - 11

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M D

IS

C

IP

LI

N E

L E

A D

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

7/ 5/

2:

:2

P

M B

IM

-2 2-

M us ka llo ng e

S ta te P ar k/

_F

P M

E _M

S P

_A 2W es tC

G B ld g_

_C E

N .r vt

EP101

F

IR

S T

F

LO

O R

P O

W E

R P

LA

N

C ou nt y R oa d

N ew be rr y, M

I 4

M U

S K

A

LL

O N

G E

L A

K E

S T

A T

E P

A R

K

W E

S T

C A

M P

G R

O U

N D

T O

IL

E

T S

H O

W E

R B

U

IL

D

IN

G

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

-2 2-

Z H

/0 7/

1.

8.

A

B G

D T

M B

F ile

N o.

S W

1/4" = 1'-0"1

FIRST FLOOR POWER PLAN

S O

S V S O

S O

S O

S O

S O S O S O S O

S V

S V

K K

A

A

B

C

E

D

F

G

1 2 3 54

SHOWER

SHOWER

SHOWER

SHOWER

MEN'S

WOMEN'S

STORAGE ROOM

PORCH B

PORCH A

LAVATORY

LA

LC LCLC

OA

LB LBLBLB

LB LB LB LB

LA

LA

LC

LA

LA

LA

LA

LA

LC

LC

LA

LA

LA

LA

LA

OA

OA

OA

OA OA

MOUNT TO HORIZONTAL BEAM

(TYPICAL OA FIXTURES)

MOUNT LB FIXTURES 6'10" AFF

(TYPICAL LB FIXTURES)

MOUNT EMA FIXTURES 7'6" AFF

(TYPICAL EMA FIXTURES IN TOILET AND STORAGE ROOMS)

MOUNT LA FIXTURES 9' AFF

(TYPICAL LA FIXTURES)

MOUNT LC & EMA FIXTURES 7' AFF

(TYPICAL FIXTURES ALONG WALL)

MOUNT EMA FIXTURES 8'4" AFF

(TYPICAL EMA FIXTURES IN SHOWERS)

MOUNT EMA FIXTURES 8'4" AFF

(TYPICAL EMA FIXTURES IN SHOWERS)

EMA EMA

EMA EMA

EMA

EMA

EMA

EMA

EMA

EMAEMA

CONCEAL CONDUIT TO QA FIXTURES ON TOP OF

STRUCTURAL BEAM FROM BUILDING. CONDUIT TO BE

SOLID CEDAR STAIN COLOR. COORDINATE COLOR WITH

ARCHITECT. (TYPICAL EXTERIOR CONDUIT)

CONCEAL CONDUIT TO QA FIXTURES ON TOP

OF STRUCTURAL BEAM FROM BUILDING.

RP-W - 12

RP-W - 13

RP-W - 15

RP-W - 16

RP-W - 17

RP-W - 19

RP-W - 19

CONCEAL CONDUIT TO QA FIXTURES ON TOP

OF STRUCTURAL BEAM FROM BUILDING

MOUNT LC FIXTURES TO UNISTRUT

COORDINATE WITH

ARCHITECTURAL/STRUCTURAL

MOUNT CONTROL DEVICES TO UNISTRUT

(TYPICAL STORAGE ROOM)

MOUNT SENSOR ON CEILING

(TYPICAL SENSORS IN SHOWER

AND TOILET RMS)

COORDINATE PLACEMENT OF

FIXTURES WITH PLUMBING PIPING

1 1

LC

RP-W - 14

1. PROVIDE TWO LABELED KEY SWITCHES FOR SUMMER-WINTER SWITCH TO INTERRUPT POWER TO MOTION SENSOR POWER PACKS (IN RETROOMS AND SHOWERS) IN ORDER TO DEACTIVATE SENSORS IN

"WINTER SHUTDOWN".

2. COORDINATE LIGHTING LAYOUT WITH ARCHITECTURAL ELEVATIONS, MECHANICAL FLOOR PLANS, AND

MECHANICAL DUCT WORK PRIOR TO ROUGH IN.

3. PROVIDE POWER PACKS AND ASSOCIATED WIRING FOR MULTIPLE SWITCH LEG LOCATIONS, SEE PLAN FOR EXACT SWITCH LEGS WITH-IN EACH AREA OR ROOM. ELECTRICAL CONTRACTOR SHALL SUPPLY

MANUFACTURER DEVICE LAYOUT AS PART OF SHOP DRAWINGS SUBMITTALS.

4. TO PREVENT FALSE ACTIVATION, CEILING MOUNT SENSORS SHALL BE MOUNTED AWAY FROM THE PATH OF STRONG AIR TURBULENCE A MINIMUM OF FOUR FEET FOR STANDARD SENSITIVITY AND SIX FEET

FOR MAXIMUM SENSITIVITY. FOR TYPICAL PLACEMENT, REFER TO LOCATION DIAGRAMS.

5. CONTRACTOR SHALL FOLLOW MANUFACTURER'S RECOMMENDED OF PLACEMENT, COVERAGE,

FREQUENCY AND VERIFY CIRCUITS WITH RESPECT TO POWER PACKS ETC,. NEEDED IN THE FIELD PER MANUFACTURER OF CHOICE, LOCATE AND AIM SENSORS IN THE CORRECT LOCATION REQUIRED FOR

COMPLETE AND PROPER VOLUMETRIC COVERAGE WITHIN THE RANGE OF COVERAGE(S) OF

CONTROLLED AREAS PER THE MANUFACTURER'S RECOMMENDATIONS. ROOMS SHALL HAVE ONE

HUNDRED (100%) PERCENT COVERAGE TO COMPLETELY COVER THE CONTROLLED AREA TO

ACCOMODATE ALL OCCUPANCY HABITS OF SINGLE OR MULTIPLE OCCUPANTS AT ANY LOCATION WITHIN THE ROOM(S). THE CONTRACTOR SHALL PROVIDE ADDITIONAL SENSORS IF REQUIRED TO PROPERLY

AND COMPLETELY COVER THE RESPECTIVE ROOM.

6. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF THE NUMBER OF POWER PACKS/ROOM

CONTROLLERS NEEDED. MAXIMUM NUMBER OF SENSORS PER POWER PACK/ROOM CONTROLLERS,

SLAVES, NETWORK BRIDGES, GATEWAYS, ETC, DEPENDENT ON SENSOR TYPE, SEE PRODUCT

INFORMATION. MULTIPLE CIRCUITS MAY BE CONTROLLED BY ONE SENSOR BY USING ADDITIONAL

POWER PACKS.

7. ELECTRICAL CONTRACTOR SHALL FIELD ADJUST EACH AREAS MOTION SENSOR'S TIME DELAY FROM 5 MINUTES TO 30 MINUTES PER OWNER'S DIRECTION. PRIOR TO INSTALLATION OF MOTION SENSORS, ELECTRICAL CONTRACTOR SHALL MEET WITH OWNER TO DETERMINE EACH AREAS TIME DELAY

SETTINGS.

8. AFTER 15 MINUTES OF NO MOTION DETECTED, SENSORS SHALL DIM FIXTURES TO 30%. 15 MINUTES AFTER BEING WITHIN DIMMED STATE OF NO MOTION DETECTED SENSOR SHALL TURN FIXTURE OFF.

ANY MOTION DURING THIS TIME WILL TURN FIXTURES ON TO 100%.

9. INTERIOR MOTION SENSOR, IN PUBLIC AREAS, TO BE DEACTIVATED DURING WINTER SHUTDOWN VIA

KEYED SWITCHES

GENERAL NOTES - ELECTRICAL

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M D

IS

C

IP

LI

N E

L E

A D

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

7/ 5/

2:

:2

P

M B

IM

-2 2-

M us ka llo ng e

S ta te P ar k/

_F

P M

E _M

S P

_A 2W es tC

G B ld g_

_C E

N .r vt

EL101

F

IR

S T

F

LO

O R

L

IG

H T

IN

G

P

LA

N

C ou nt y R oa d

N ew be rr y, M

I 4

M U

S K

A

LL

O N

G E

L A

K E

S T

A T

E P

A R

K

W E

S T

C A

M P

G R

O U

N D

T O

IL

E

T S

H O

W E

R B

U

IL

D

IN

G

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

-2 2-

Z H

/0 7/

1.

8.

A

B G

D T

M B

F ile

N o.

S W

1/4" = 1'-0"1

FIRST FLOOR LIGHTING PLAN

UTILITY

ELECTRICAL

DISTRIBUTION

PANEL BOARD PP1

UTILITY PROVIDED

TRANSFORMER. CONTRACTOR

TO COORDINATE WITH UTILITY

240V/120V

600 AMP 1ɸ

2-3" CONDUIT W/ 3-350KCMIL

MULTIPLE CIRCUITS

TO ELECTRICAL

PEDESTAL CIRCUITS

PANEL RP-W 120/240V

100A, MCB, 42CKT

2" CONDUIT W/ 3-#2/0 AL AWG + #3

ALUMINUM GND. GROUND AND NEUTRAL TO

BE SEPARATELY ISOLATED AT PANEL

ELECTRICAL HH

BOX SHALL BE CONCRETE OR COMPOSITE. METAL COVER IS ACCEPTABLE.

COVERS SHALL BE SECURED WITH 3/8" BOLTS, NUTS AND WASHERS. WHICH SHALL BE

BRASS, STAINLESS STEEL OR OTHER CORROSION RESISTANT MATERIAL. STAINLESS STEEL

SHALL HAVE A CHROMIUM CONTENT OF NOT LESS THAN 18% AND A NICKEL CONTENT OF

NOT LESS THAN 8%, NUTS SHALL BE RECESSED BELOW TOP SURFACE OF COVER.

COVER LETTERING SHALL BE 1/2" MINIMUM LETTERS CAST IN STANDARD MARKINGS:

(ELECTRICAL).

CONDUIT ENTERING THE BOX SHALL HAVE 90 DEGREE LONG RADIUS BEND (INSIDE THE

BOX). THE CONDUITS OPENING, IINSIDE THE BOX, SHALL BE AT LEAST 4" BELOW THE LID,

OPENING SHALL HAVE SMOOTH EDGE. IF THE CONDUIT IS P.V.C. A SLIP COUPLING MUST BE

USED. IF THE CONDUIT IS RIGID PIPE, A PROTECTIVE BUSHING SHALL BE USED.

CONDUCTORS SHALL HAVE A MINIMUM OF 24" SLACK FROM CONDUIT BELL END.

BACKFILL WITH EXCAVATED MATERIAL AND THOROUGHLY COMPACT.

WHERE PULLBOXES ARE INSTALLED IN CONCRETE AREAS, 1/2" PREMOLDED EXPANSION

JOINT SHALL BE INSTALLED AROUND THE BOX.

BOXES TO BE TIER 22 UNLESS OTHERWISE NOTED.

NOTE:

1.)

2.)

3.)

4.)

5.)

6.)

7.)

5/8" x4" LIFTING SLOTS

16" x 8" CONCRETE BRICK

COVER TO BE FLUSH WITH FINISH GRADE

ALL CONDUIT END BELLS SHALL BE

INSTALLED BEFORE PULLING WIRE

1" PVC CONDUIT FOR DRAINAGE

6A BACKFILL WITH MINIMUM

OF 5" DEPTH

5/8" DIAMETER (TYPICAL)

GROUND ROD (8' MIN. LENGTH)

23 3/4"

21 1/4"

15 9/16"

/2

/8

15 3/8"

ELECTRICAL

M

IN

8.)

C/L OF

ELECTRICAL BOX

C/L OF

WATER

SUPPLY

C/L OF

FIXTURE

TOP OF FIXTURE.

1/

2"

2 3/4"

4 3/4"

/2

3/4" CONDUIT FROM

VALVE TO SENSOR.

SLOAN EL-154

TRANSFORMER SUPPLIED BY

PLUMBING CONTRACTOR

MOUNTED AT HEIGHT IND

3/4" CONDUIT TO SENSOR.

ONE PER 10 FIXTURES.

WATER CLOSET

FLUSH VALVE.

4"x4"x2 1/2" SURFACE

MOUNTED JUNCTION BOX.

MOUNT AT 12' AFF

4"x4"x2 1/2" RECESSED

JUNCTION BOX. COVER

SUPPLIED BY OTHERS

4"x4"x2 1/2" RECESSED

JUNCTION BOX. COVER

SUPPLIED BY OTHERS

3/4" CONDUIT TO

NEXT SENSOR/SOLENOID

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M D

IS

C

IP

LI

N E

L E

A D

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

7/ 5/

2:

:1

P

M B

IM

-2 2-

M us ka llo ng e

S ta te P ar k/

_F

P M

E _M

S P

_A 2W es tC

G B ld g_

_C E

N .r vt

E-501

E

LE

C T

R

IC

A L

D E

T A

IL

S

C ou nt y R oa d

N ew be rr y, M

I 4

M U

S K

A

LL

O N

G E

L A

K E

S T

A T

E P

A R

K

W E

S T

C A

M P

G R

O U

N D

T O

IL

E

T S

H O

W E

R B

U

IL

D

IN

G

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

-2 2-

Z H

/0 7/

1.

8.

A

B G

D T

M B

F ile

N o.

S W

N.T.S2

ONE-LINE POWER DIAGRAM - PP1

N.T.S3

HANDHOLE DETAIL

N.T.S1

FLUSH VALVE MOUNTING HEIGHT DETAIL

1 1 X AUTOMATIC ON TO 100%, DIM FIXTURE TO 30% AFTER 15 MINUTES OF NO MOTION DETECTED.

AUTOMATIC OFF AFTER 15 MINUTES OF NO MOTION DETCTED WHILE IN DIMMED STATE.

SCHEME NO. MANUAL ON DIMMING NO. OF SCENES MULTIPLE ZONES DAYLIGHTING

OCCUPANCY

SENSOR

VACANCY SENSOR ORDER OF OPERATION

LIGHTING CONTROL SCHEDULE - MAIN BUILDING

X SCHEME NO.

2 1

MANUAL ON, AUTOMATIC OFF AFTER 15 MINUTES OF NO MOTION DETECTED.

• BUTTON TOGGLES LIGHTS ON TO 100% AND OFF.

X X

S T

A T

E O

F M

IC

H

IG

A

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

LO

G

Y , M

A N

A G

E M

E N

T A

D G

E T

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

ARCHITECTS ENGINEERS PLANNERS

OHM-ADVISORS.COM

R

C O

P Y

R

IG

H T

O

H M

A

LL

D R

A W

IN

G

S A

N D

W R

IT

T

E N

M A

T E

R

IA

LS

A

P P

E A

R

IN

G H

E R

E

IN

C O

N S

T

IT

U T

E T

H E

O R

IG

IN

A L

A N

D U

N P

U B

LI

S

H E

D W

O R

K O

F O

H M

A N

D T

H E

S A

M E

M A

Y N

O T

B E

D U

P

LI

C A

T E

D , D

IS

T

R

IB

U T

E D

, O R

D

IS

C

LO

S E

D W

IT

H

O U

T P

R

IO

R W

R

IT

T E

N C

O N

S E

N T

O F

O H

M

IS

S

U E

D F

O R

P

R O

JE

C

T N

U M

B E

R P

M D

IS

C

IP

LI

N E

L E

A D

A D

A M

P . L

A C

H , R

A , D

IR

E

C T

O R

7/ 5/

2:

:1

P

M B

IM

-2 2-

M us ka llo ng e

S ta te P ar k/

_F

P M

E _M

S P

_A 2W es tC

G B ld g_

_C E

N .r vt

E-601

E

LE

C T

R

IC

A L

S C

H E

D U

LE

S

C ou nt y R oa d

N ew be rr y, M

I 4

M U

S K

A

LL

O N

G E

L A

K E

S T

A T

E P

A R

K

W E

S T

C A

M P

G R

O U

N D

T O

IL

E

T S

H O

W E

R B

U

IL

D

IN

G

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

-2 2-

Z H

/0 7/

1.

8.

A

B G

D T

M B

F ile

N o.

S W

1. PROVIDE TWO LABELED KEY SWITCHES FOR SUMMER-WINTER SWITCH TO INTERRUPT POWER TO MOTION SENSOR POWER PACKS (IN RESTROOMS AND SHOWERS) IN

ORDER TO DEACTIVATE SENSORS IN "WINTER SHUTDOWN"

SCHEDULE NOTES:

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION MFR. CATALOG # LAMPS WATTS NOTES

EMA EMERGENCY BUG EYES DUAL LITE PG-W-HTR LED 15 REQUIRES UN-SWITCHED HOT

LA SURFACE LINEAR METALUX HVL8-(BR/MR/ER)-4-LD4-1STD-30-UNV-O-EDD1-SHVL8-4LEDCM LED 33 COORDINATE BR/MR/ER WITH

BEGINNING, MIDDLE AND END RUN

AS FIXTURES APPEAR ON SHEETS.

LB WALL MOUNT LUMINAIRE LITHONIA ARV13-MIN10-25W30K-120-OP-WHT LED 27

LC SURFACE LINEAR CREE LIGHTING LS4-40L-830-10V LED 31

OA WALL MOUNT LUMINAIRE LUMARK AXCS1A-W-PC1 LED 14

CONNECTED LOAD: (kVA) 8.67 6.22

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

WOMENS 105 HAND DRYER 12 1 20 25 1.00 26

MENS 104 HAND DRYER 12 1 20 23 1.00 24

MENS FLUSH VALVE POWER 12 1 20 21 0.05 1.00 22 20 1 12 LAV. 111 HAND DRYER

PORCH A AND B LITES 12 1 20 19 0.04 0.05 20 20 1 12 WOMEN FLUSH VALVE POWER

EMERGENCY LITES 12 1 20 17 0.08 0.18 18 20 1 12 LAV. 111 GFCI RECEPTACLE

STORAGE 105 LITES 12 1 20 15 0.21 0.30 16 20 1 12 SHOWER/LAV. 111 LITES

MENS 104 LITES 12 1 20 13 0.18 0.15 14 20 1 12 WOMENS 105

STORAGE 106 GFCI RECEPT 12 1 20 11 0.18 0.01 12 20 1 12 PORCH C OUTSIDE LITES

STORAGE 106 GFCI RECEPT 12 1 20 9 0.18 0.36 10 20 1 12 STORAGE 106 RECEPTS

WOMENS FAUCET RECEPTS 12 1 20 7 0.54 1.00 8 20 1 12 WOMENS 105 HAND DRYER

MENS 104 HAND DRYER 12 1 20 5 1.00 0.54 6 20 1 12 MENS FAUCET RECEPTS

STORAGE 106/OUTSIDE... 12 1 20 3 0.36 2.53 4

F-1 12 1 20 1 1.43 2.53 2

35 2 8 ERV-1

IDENTIFICATION

WIRE

SIZES POLE AMP CKT

A kVA

B kVA

A kVA

B kVA CKT AMP POLE

WIRE

SIZES IDENTIFICATION

FED FROM EXISTING PP1 THROUGH RELOCATED HANDHOLE

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 100 A

MOUNTING: SURFACE WIRES: 3 MAINS RATING: 100 A

SUPPLY FROM: PHASES: 1 MAINS TYPE: MCB

LOCATION: STORAGE ROOM 106 VOLTS: 120/240 Single SCCR RATING: 10 K

BRANCH PANEL: RP-W

File details come from the government source that posted it. Updated .