22438 Drawings 5.pdf
PDF 2 MB Posted
- Solicitation number
- RFQ - 171 - 230000000616
- Issued by
- Luce County, Michigan
About this file
This document contains drawings and specifications for a mechanical and electrical systems upgrade project for the West Campground Toilet and Shower Building at Muskallonge Lake State Park in Newberry, Michigan. The project is being managed by the State of Michigan Design and Construction Division, Department of Technology, Management and Budget, and State Facilities Administration.
The mechanical scope includes installing a new gas-fired furnace, exhaust air ventilator, and associated ductwork and air distribution equipment. The electrical scope includes new power distribution, lighting, and control systems. The project has an estimated connected electrical load of 8.67 kVA. Bidders must upload their proposals to the SIGMA VSS system by the 2:00 PM deadline on the due date. The contract term and any renewal options are not specified in the provided documents.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 22438 Specs 2.pdf | ||
| 22438 Addendum 1 Part 1.pdf | ||
| 22438 Drawings 4.pdf | ||
| 22438 Advertisement.pdf | ||
| 22438 Specs 1.pdf | ||
| 22438 Addendum 4.pdf | ||
| 22438 Addendum 1 Part 2.pdf | ||
| 22438 Drawings 3.pdf | ||
| 22438 Drawings 1.pdf | ||
| 22438 Addendum 2.pdf | ||
| 22438 Specs 3.pdf | ||
| 22438 Addendum 3.pdf | ||
| 22438 Drawings 2.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PORCH A
PORCH B
MEN'S
WOMEN'S
STORAGE ROOM
SHOWER
SHOWER
SHOWER
SHOWER
LAVATORY
F-1
ERV-1
x8 x8
24x12
8x6 x1
6x
12x6 RA
12x6 RA
S A
EA
S A
12x6 RA
12x6 RA
24x14 RA
16x14 RA
6x10 SA
24x14 OA
105.2
104.2
104.4
275 105.4
105.1
104.3
105.3
104.1
111.2
111.1
107.1
107.2
108.1
108.2
109.2
109.1
110.2
110.1
106.1
300 CFM OED
W/DAMPER
M-101
M-101
3" FLUE AND COMBUSTION
AIR UP TO CONCENTRIC
ROOF TERMINAL
76" W X 26" H, 8" DEEP PLENUM.
CONNECT TO LOUVER PROVIDED BY
ARCH. COVER SECTIONS OF LOUVER
NOT COVERED BY PLENUM WITH
INSULATED PANEL. PROVIDE INSECT
SCREEN. PAINT INSIDE OF DUCT &
INSULATED PANEL BLACK.
8x8 SA 8x8 SA
106.2
8x8 SA
8x8 SA
6x6 RA
6x6 SA
8x4 RA 8x4 SA
6x6 RA
8x4 SA 8x4 SA6x6 RA
8x4 SA
T
F-1
82" W X 30" H, 8" DEEP PLENUM. CONNECT
TO LOUVER PROVIDED BY ARCH. COVER
SECTIONS OF LOUVER NOT COVERED BY
PLENUM WITH INSULATED PANEL.
PROVIDE INSECT SCREEN. PAINT INSIDE
OF DUCT & INSULATED PANEL BLACK.
THERMOSTAT WHITE
RODGERS MODEL
1F95E2-0671
REMOTE SENSOR
WHITE RODGERS
MODEL F145-1328-
S
24x22 SA
24x14 OA
12x10 SA
SEAL DUCTWORK AROUND COLUMN
3" FLUE AND COMBUSTION
AIR UP TO 4" CONCENTRIC
ROOF TERMINAL
R A
16x16
SA
ERV-1
F-1
6x6
16x16
12x24
6x6
EA
10x6SA
SA
SA
RA
STORAGE ROOM
PORCH B
3" CONCENTRIC VENT
3" VENT
WH-1 WH-1
MOUNT TO UNISTRUT, REFER TO
SHEET A-301 (TYP F-1 & ERV-1)
10x6 SA
12x18 SA
8x4 SA
8x4 SA
106.1
76" W X 26" H, 8" DEEP PLENUM CONNECT TO
LOUVER PROVIDED BY ARCH. COVER
SECTIONS OF LOUVER NOT COVERED BY
PLENUM WITH INSULATED PANEL. PROVIDE
INSECT SCREEN. PAINT INSIDE OF DUCT &
INSULATED PANEL BLACK.
4" CONCENTRIC VENT
3" COMBUSTION
AIR
CONCENTRIC VENTS TO BE MIN 3' ABOVE
ROOF, SPACED 2" APART, ALIGNED
14x16 RA
10x12 18x12SA
ERV-1
8x10
SA
109.2
STORAGE ROOM
SHOWER
RA
14x24 OA
106.2
82" W X 30" H X 8" DEEP PLENUM CONNECT
TO LOUVER PROVIDED BY ARCH. COVER
SECTIONS OF LOUVER NOT COVERED BY
PLENUM WITH INSULATED PANEL.
PROVIDE INSECT SCREEN. PAINT INSIDE
OF DUCT & INSULATED PANEL BLACK.
8x8 SA
16x16 SA
6x6 RA
12x16 EA
12x6 SA 12x6 SA
8x8 SA
8x8 SA
1. ALL DUCT SHALL BE MOUNTED AT LEAST 8'-0" A.F.F.
2. ERV / FURNACE / DUCTWORK SHALL BE SUPPORTED FROM UNI-STRUT ABOVE. ALL DUCT SHALL BE
MOUNTED AT LEAST 8'-0" A.F.F.
GENERAL NOTES - MECHANICAL
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M D
IS
C
IP
LI
N E
L E
A D
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
7/ 5/
:3
5:
P M
B
IM
-2
2-
M us ka llo ng e S ta te
P ar k/
_F P
M E
_M S
P _A
2W es tC G
B ld g_
_C
E N
.rv t
M-101
F
IR
S T
F
LO
O R
M E
C H
A N
IC
A
L P
LA
N
C ou nt y R oa d
N ew be rr y, M
I 4
M U
S K
A
LL
O N
G E
L A
K E
S T
A T
E P
A R
K
W E
S T
C A
M P
G R
O U
N D
T O
IL
E
T S
H O
W E
R B
U
IL
D
IN
G
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 2-
Z H
/0 7/
1.
8.
A
B G
D T
M B
F ile
N o.
LA
1/4" = 1'-0"1
FIRST FLOOR HVAC PLAN
1/4" = 1'-0"2
DUCTWORK SECTION 1
1/4" = 1'-0"3
DUCTWORK SECTION 2
FUSED
SWITCH
F-1
CONCENTRIC
COMBUSTION &
FLUE PIPING
ERV-1
EXHAUST AIR TO
OUTSIDE
SUPPLY AIR (CONNECT TO
FURNACE RETURN AIR)
FRESH AIR
FROM OUTSIDE
PROVIDE CLEARANCES
FOR DOORS TO FULLY OPEN
RETURN AIR
SUPPLY AIR TO ROOMS
GAS COCK
DIRT LEG
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M D
IS
C
IP
LI
N E
L E
A D
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
7/ 5/
:3
5:
P M
B
IM
-2
2-
M us ka llo ng e S ta te
P ar k/
_F P
M E
_M S
P _A
2W es tC G
B ld g_
_C
E N
.rv t
M-601
M E
C H
A N
IC
A
L S
C H
E D
U
LE
S
C ou nt y R oa d
N ew be rr y, M
I 4
M U
S K
A
LL
O N
G E
L A
K E
S T
A T
E P
A R
K
W E
S T
C A
M P
G R
O U
N D
T O
IL
E
T S
H O
W E
R B
U
IL
D
IN
G
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 2-
Z H
/0 7/
1.
8.
A
B G
D T
M B
F ile
N o.
LA
AIR TERMINAL SCHEDULE
MARK CFM MANUFACTURER MODEL SUPPLY RETURN EXHAUST DIMENSIONS
104.1 225 PRICE 620 X 8X8
104.2 225 PRICE 620 X 8X8
104.3 275 PRICE 80 X 12X6
104.4 275 PRICE 80 X 12X6
105.1 225 PRICE 620 X 8X8
105.2 225 PRICE 620 X 8X8
105.3 275 PRICE 80 X 12X6
105.4 275 PRICE 80 X 12X6
106.1 300 PRICE 620 X 12X6
106.2 300 PRICE 80 X 12X6
107.1 75 PRICE 620 X 8X4
107.2 100 PRICE 80 X 6X6
108.1 75 PRICE 620 X 8X4
108.2 100 PRICE 80 X 6X6
109.1 75 PRICE 620 X 8X4
109.2 100 PRICE 80 X 6X6
110.1 75 PRICE 620 X 6X6
110.2 100 PRICE 80 X 6X6
111.1 100 PRICE 620 X 8X4
111.2 100 PRICE 80 X 6X6
NOTES 1. INTERLOCK TO FURNACE FAN
ERV-1 106 STORAGE 1600 84/71 77/67 -5 50 0.75 1900 0.75 2 230 1 2 230 1 2" MERV-8 RENEWAIRE HE2XINH 1
MARK LOCATION CFM SUMMER EAT (°F) (DB/WB) SUMMER LAT (°F) (DB/WB) WINTER EAT (°F) WINTER LAT (°F) ESP (IN-WG) CFM ESP (IN-WG) HP VOLTAGE PHASE HP VOLTAGE PHASE FILTERS MANUFACTURER MODEL NOTES
SUPPLY AIR EXHAUST AIR SUPPLY FAN EXHAUST FAN
ENERGY RECOVERY VENTILATOR SCHEDULE
3. PROVIDE LP GAS CONVERSION KIT, CONCENTRIC VENT KIT & LP GAS REGULATOR.
2. PROVIDE 7 DAY PROGRAMMABLE WALL MOUNTED THERMOSTAT.
NOTES: 1. FURNACE FAN TO RUN ON OCCUPANCY SCHEDULE SET BY OWNER.
F-1 106 STORAGE 120 117 2020 N/A 115/1/60 16.7 20 3 3 CARRIER 59SC5B120E24--22 1,2,3
MARK LOCATION INPUT OUTPUT HEATING COOLING V/PH/HZ MCA MOCP FLUE COMBINATION AIR MANUFACTURER MODEL NOTES
MBH CFM ELECTRICAL CONNECTION DIAMETER (IN)
GAS FIRED FURNACE SCHEDULE
N.T.S
FURNACE TO ERV DETAIL
FURNACE & ERV SEQUENCE OF OPERATION
OCCUPIED:
7 DAY PROGRAMMABLE THERMOSTAT SHALL RUN THE FURNACE SUPPLY FAN AND ERU SUPPLY AND EXHAUST FANS CONTINUOUSLY. THE FURNACE GAS FIRED
BURNER SHALL CYCLE TO MAINTAIN THE REMOTE SENSOR SETPOINT.
THIS SHALL BE COMPLETED BY USING A RELAY CONTROLLED BY THE THERMOSTATS “G” FAN WIRE TO CLOSE CONTACTS 1-4 AND 1-5 ON THE ERV TERMINAL BLOCK.
UNOCCUPIED:
THE 7 DAY PROGRAMMABLE THERMOSTAT SHALL DISABLE THE FURNACE FAN AND THE ERV FANS DURING UNOCCUPIED TIMES. THE FURNACE GAS FIRED BURNER AND THUS THE FURNACE FAN SHALL CYCLE TO MAINTAIN REMOTE SENSOR SETPOINT. DURING TIMES OF CALL FOR HEAT THE ERU SUPPLY AND EXHAUST FANS
SHALL RUN.
THIS SHALL BE COMPLETED BY LETTING THE THERMOSTAT CONTROL THE FURNACE ON THE “W” HEATING TERMINAL. WHEN THE HEAT CALL IS ACTIVE THE “G” TERMINAL WILL ALSO BE ACTIVE AND THE RELAY WILL CLOSE CONTACTS 1-4 AND 1-5 ON THE ERV TERMINAL BLOCK.
CABLE TV, TELEPHONE,
DATA OR DUPLEX RECEPT
OUTLET (UNLESS NOTED)
TOP OF
COUNTER
BASEBOARD RADIATOR
FIRE ALARM
HORN/SPEAKER/STROBE
SWITCHES,
THERMOSTAT, WALL
OCCUPANCY SENSOR,
FIRE ALARM PULL
STATION
FLOOR
ELECTRIC WATER COOLER
CEILING
CL
7'
4'
6" M
IN
ELECTRICAL OUTLET
6"
6"
CL
/4
RECOMMENDATIONS
PER MANUFACTURERS
POWER CIRCUIT WIRING
UNDERGROUND WIRING
SWITCH LOOP WIRING
UN-SWITCHED HOT WIRING
LOW VOLTAGE WIRING
DATA WIRING
PROPOSED EXISTING DEMOLISH
TYPICAL 3⌀ 4-WIRE
DRY-TYPE UTILITY
TRANSFORMER
T-X
TYPICAL 3⌀ 4-WIRE
DRY-TYPE TRANSFORMER
SERVICE FROM SERVICE PANEL
T-X
BRANCH PANEL
CONNECTIONS BY
UTILITY
SUPPLY-SIDE
BONDING JUMPER
SERVICE
PANEL
G
NEU. NEU.
G
BRANCH PANEL
GROUNDED CONDUCTOR
GROUNDING ELECTRODE
CONDUCTOR
GROUNDING ELECTRODE
REFER TO NOTE 2
EQUIPMENT GROUNDING
CONDUCTOR
MAIN BUILDING JUMPER
GRADE
GROUNDED CONDUCTOR SYSTEM BONDING
JUMPER
SUPPLY-SIDE
BONDING
JUMPER
SEPARATELY DERIVED SYSTEM
G
NEU.
1. SIZE GROUNDING/BONDING CONDUCTORS PER NEC ARTICLE 250
2. GROUNDING ELECTRODE SYSTEM AS PER NEC ARTICLE 250 SECTION III.
NOTES
1. ALL ELECTRICAL INSTALLATIONS SHALL BE IN ACCORDANCE WITH THE CURRENT NATIONAL ELECTRICAL CODE AND ANY STATE/LOCAL AMENDMENTS.
2. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACQUISITION OF AN ELECTRICAL PERMIT AND SCHEDULING OF THE NECESSARY
INSPECTIONS. UPON COMPLETION OF THE WORK THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE OWNER EVIDENCE OF INSPECTION APPROVAL.
3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COORDINATION REQUIRED WITH THE ELECTRIC UTILITY SERVING THE FACILITY. UTILITY
COSTS SHALL BE PAID SEPARATELY BY THE OWNER.
GENERAL NOTES - ELECTRICAL
SURFACE / CEILING MOUNT
EMERGENCY SURFACE / CEILING
MOUNT
PENDANT / CHAIN MOUNT
EMERGENCY PENDANT / CHAIN
MOUNT
RECESSED MOUNT
EMERGENCY RECESSED MOUNT
COMBINATION FAN / LIGHT
TRACK STRIP
WALL MOUNT
EMERGENCY WALL MOUNT
EXTERIOR POLE MOUNT
EXTERIOR POST MOUNT
EMERGENCY WALL PACK
EXIT SIGN
CEILING FAN
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
COMBINATION MOTOR STARTER
WITH DISCONNECT SWITCH
MOTOR STARTER
ELECTRICAL METER
DISTRIBUTION PANEL
ELECTRICAL POWER PANEL
SURFACE MOUNT
ELECTRICAL POWER PANEL
FLUSH MOUNT
LIGHITNG CONTROL PANEL
RELAY
ELECTRICAL TRANSFORMER
ELECTRICAL PULL BOX
JUNCTION BOX
SINGLE PHASE MOTOR
THREE PHASE MOTOR
VARIABLE FREQUENCY DRIVE
X = NUMBER AND TYPE OF PORTS
C COAXIAL PORT
D DATA PORT
H HDMI PORT
P PHONE PORT
W WIRELESS ACCESS POINT
X
X H Z
SENSORS
J J
PC
IC
PS
K
CR
DL
M
R
A
CO
HD
F F
F F
T
PB
1. MINIMUM SIZE OF RIGID CONDUIT SHALL BE 3/4".
2. MINIMUM SIZE OF FLEX CONDUIT SHALL BE 1/2".
3. MINIMUM SIZE WALL BOX IN CMU SHALL BE
4"X4".
4. MINIMUM SIZE OF UNDERGROUND CONDUIT
SHALL BE 1 1/4"
J
(WALL) (CEILING)
NURSE
N
N
FACP
FAA
FS
TS
PS
DH
C
P
(LIGHT)(NO LIGHT)
CARD READER
MAGNETIC SWITCH (DOOR CONTACT)
ELECTRONIC DOOR LOCK
MOTORIZED DOOR OPERATOR
ELECTRIC STRIKE
KEYPAD ENTRY DEVICE
ENTRANCE CALL SYSTEM
SECURITY CAMERA
PANIC ALARM SPEAKER/STROBE
ES
DP##
PP##
PP##
(WALL)
(CLG)
(FLR)
B
M
WG
HSS
OUTDOOR BELL / CHIME
SMOKE DETECTOR
SMOKE DETECTOR WITH AUDIBLE BASE
SMOKE/CARBON MONOXIDE DETECTOR
DUCT SMOKE DETECTOR
HEAT DETECTOR
FIRE ALARM HORN/STROBE
FIRE ALARM STROBE
FIRE ALARM SPEAKER
FIRE ALARM SPEAKER/STROBE
FIRE ALARM PULL STATION
ELECTROMAGNETIC DOOR HOLD OPEN
END OF LINE RESISTOR
FIRE ALARM FLOW SWITCH
FIRE ALARM PRESSURE SWITCH
FIRE ALARM TAMPER SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
HOOD SUPPRESSION SYSTEM FIRE ALARM
CONTACT
ELR
I/C
DC
DO
SWITCHES: X = DESIGNATION BELOW
H = HUB CONTROLLER
Z = LIGHTING ZONE
PUSH BUTTON
EMERGENCY STOP BUTTON
PHOTOCELL
CEILING MOUNTED PULL SWITCH
WIRELESS NETWORK LIGHTING CONTROLLER
(HUB) H# = CONTROLLER INDICATOR
LIGHTING CONTROL SCHEME NUMBER
SINGLE POLE
2 TWO POLE
3 THREE WAY
4 FOUR WAY
DM DIMMER
F FAN
K KEY OPERATED
LV LOW VOLTAGE
M MOTION DETECTION
O OCCUPANCY SENSOR
P PILOT LIGHT
T TIMER
F F
S S
X
X X
(FURN)
SPEAKER
INTERCOM CALL BOX
BELL
MICROPHONE JACK
POWER SUPPLY
REQUIRES WIRE GUARD
NURSE CALL MAIN PANEL
NURSE CALL PULL STATION
NURSE CALL LIGHT
CLOCK
SIMPLEX RECEPTACLE
DUPLEX GROUNDED RECEPTACLE
208/240/480V, 1ϕ STRAIGHT BLADE RECEPTACLE
QUADRUPLEX RECEPTACLE
DUPLEX RECEPTACLE ON EMERGENCY POWER
FLOOR BOX
CEILING BOX
SPECIALTY RECEPTACLE
CTR MOUNTED ABOVE COUNTER
G GROUND FAULT CIRCUIT INTERRUPTER
GC GFCI - MOUNTED ABOVE COUNTER
U DUAL USB PORTS
UC DUAL USB PORTS ABOVE COUNTER
WP WEATHERPROOF RECEPT & COVER, GFI
H##
D DAYLIGHT
M MOTION DETECTION
O OCCUPANCY
V VACANCY
H = HUB CONTROLLER
Z = LIGHTING ZONE
XS X
H Z
S X H Z
LP##
(CEILING) (WALL)
(CEILING) (WALL)
(CEILING)
(WALL)
(WALL)(CLG)
(CLG) (WALL) (FLR)
ELECTRICAL SYMBOLS LEGEND
VFD
XX-X EQUIPMENT INDICATOR
INDICATES EXISTING
e LF-1
H Z
LIGHT FIXTURE INDICATOR
HUB CONTROLLER
LIGHTING ZONE
e
RACEWAY NOTES
WIRES
OTHER SYMBOLS
TELEPHONE/COMMUNICATIONS
FIRE ALARM SYSTEMRECEPTACLE OUTLETS
SECURITY
POWER DISTRIBUTION
LIGHT FIXTURES
SWITCHES
(360 VIEW)
P P
SX
(W/ LIGHTS)
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M D
IS
C
IP
LI
N E
L E
A D
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
7/ 5/
2:
:1
P
M B
IM
-2 2-
M us ka llo ng e
S ta te P ar k/
_F
P M
E _M
S P
_A 2W es tC
G B ld g_
_C E
N .r vt
E-001
E
LE
C T
R
IC
A L
N O
T E
S A
N D
S Y
M B
O
LS
C ou nt y R oa d
N ew be rr y, M
I 4
M U
S K
A
LL
O N
G E
L A
K E
S T
A T
E P
A R
K
W E
S T
C A
M P
G R
O U
N D
T O
IL
E
T S
H O
W E
R B
U
IL
D
IN
G
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 2-
Z H
/0 7/
1.
8.
A
B G
D T
M B
F ile
N o.
S W
N.T.S
TYPICAL MOUNTING HEIGHTS
ABBREVIATIONS
_SPECIAL
Φ PHASE
A
A AMPERE
AFF ABOVE FINISHED FLOOR
C
C CONDUIT
CAT CATALOGUE
CB CIRCUIT BREAKER
CMU CONCRETE MASONRY UNIT
CO. COMPANY
CUH CABINET UNIT HEATER
E
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EWC ELECTRIC WATER COOLER
F
FA FIRE ALARM
G
G GROUND FAULT CIRCUIT
INTERRUPTER
GND EQUIPMENT GROUND
H
HID HIGH INTENSITY DISCHARGE
HPS HIGH PRESSURE SODIUM
HVAC HEATING VENTILATING & AIR
CONDITIONING
K
K KEY OPERATED DEVICE
KVA KILOVOLT-AMPERES
KW KILOWATTS
L
LED LIGHT EMITTING DIODE
M
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MH METAL HALIDE
MISC MISCELLANEOUS
MLO MAIN LUG ONLY
MTD MOUNTED
N
NEU NEUTRAL
No. NUMBER
P
PL PILOT
R
RECEPT RECEPTACLE
T
TEL TELEPHONE
TV TELEVISION
TYP TYPICAL
U
UGE UNDERGROUND ELECTRIC
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V
V VOLT
VA VOLT-AMPERES
W
W WIRE
WNC WIRELESS NETWORK CONTROLLER
WP WEATHERPROOF
X
XFMR TRANSFORMER
N.T.S
GROUNDING BONDING DIAGRAM
WP
G
GC
GC
GC
GC
GC
GC
G
J
J
J
J
J
G G
J
J
J
J
J
J
J
J
J
J
GC
G
J J
JJ
J J
J
J
JJ
J J
A
F-1
ERV-1
RP-W
RP-W - 1
MOUNT RECEPTS 6' AFF
FOR POWER VENTING
POWER FOR HAND DRYERS. REFER
TO A-002 FOR TYPICAL MOUNTING
HEIGHTS (TYPICAL HAND DRYERS)
POWER FOR HAND DRYER
POWER FOR HAND DRYERS
4X4 J-BOX MOUNTED INTERIOR TO CMU FOR
AUTOMATIC FLUSH VALVES (TYPICAL WATER
CLOSET J-BOX). REFER TO DETAIL 1 ON
SHEET E-501 FOR MOUNTING HEIGHTS.
RECEPT BOX TO BE MOUNTED 3" FROM CORNER TO ALLOW
FOR PARTITION MOUNTING. SEE DETAILS 3 & 4 ON SHEET
A-452 FOR PROPER MIRROR AND OUTLET LOCATIONS
RP-W - 5
MEN'S
WOMEN'S
STORAGE ROOM
LAVATORY
SHOWER
SHOWER
SHOWER
SHOWER
PORCH B
PORCH A
RP-W - 3
RP-W - 3
RP-W - 7
RP-W - 8
RP-W - 6
RP-W - 9
MOUNT SINGLE TRANSFORMER FOR FLUSH
VALVES ABOVE CMU. FEED EACH SENSOR
J-BOX WITH 3/4" CONDUIT AND 2-#18AWG
THROUGH GROUTED CMU CAVITY.
RP-W - 20RP-W - 21
3/4" CONDUIT WITH 2-#12AWG + #12EG
3/4" CONDUIT WITH 2-#
10AWG + #10EG
3/4" CONDUIT WITH 2-#12AWG
+ #12EG
RP-W - 25
RP-W - 23
RP-W - 2,4
HH
2" CONDUIT WITH 3-#2/0AL AWG + #3 AL EG
EXISTING HANDHOLE TO BE DEMOLISHED AND A NEW HANDHOLE PLACED WITHIN GREEN
SPACE WITHIN EXISTING CONDUCTOR RUN. REMOVE EXISTING CONDUIT AND CONDUCTORS
APPROXIMATELY 8' FROM EXISTING BUILDING. SPLICE AND EXTEND CONDUIT AND
CONDUCTORS TO RP-W LOCATION FROM PROPOSED HAND HOLE. SEE SHEET C-201 FOR
PROPOSED LOCATION OF HAND HOLE.
STUB UP CONDUIT TO PANEL
WITH LOCKING COVER
RP-W - 22
RP-W - 18
RP-W - 10
RP-W - 11
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M D
IS
C
IP
LI
N E
L E
A D
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
7/ 5/
2:
:2
P
M B
IM
-2 2-
M us ka llo ng e
S ta te P ar k/
_F
P M
E _M
S P
_A 2W es tC
G B ld g_
_C E
N .r vt
EP101
F
IR
S T
F
LO
O R
P O
W E
R P
LA
N
C ou nt y R oa d
N ew be rr y, M
I 4
M U
S K
A
LL
O N
G E
L A
K E
S T
A T
E P
A R
K
W E
S T
C A
M P
G R
O U
N D
T O
IL
E
T S
H O
W E
R B
U
IL
D
IN
G
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 2-
Z H
/0 7/
1.
8.
A
B G
D T
M B
F ile
N o.
S W
1/4" = 1'-0"1
FIRST FLOOR POWER PLAN
S O
S V S O
S O
S O
S O
S O S O S O S O
S V
S V
K K
A
A
B
C
E
D
F
G
1 2 3 54
SHOWER
SHOWER
SHOWER
SHOWER
MEN'S
WOMEN'S
STORAGE ROOM
PORCH B
PORCH A
LAVATORY
LA
LC LCLC
OA
LB LBLBLB
LB LB LB LB
LA
LA
LC
LA
LA
LA
LA
LA
LC
LC
LA
LA
LA
LA
LA
OA
OA
OA
OA OA
MOUNT TO HORIZONTAL BEAM
(TYPICAL OA FIXTURES)
MOUNT LB FIXTURES 6'10" AFF
(TYPICAL LB FIXTURES)
MOUNT EMA FIXTURES 7'6" AFF
(TYPICAL EMA FIXTURES IN TOILET AND STORAGE ROOMS)
MOUNT LA FIXTURES 9' AFF
(TYPICAL LA FIXTURES)
MOUNT LC & EMA FIXTURES 7' AFF
(TYPICAL FIXTURES ALONG WALL)
MOUNT EMA FIXTURES 8'4" AFF
(TYPICAL EMA FIXTURES IN SHOWERS)
MOUNT EMA FIXTURES 8'4" AFF
(TYPICAL EMA FIXTURES IN SHOWERS)
EMA EMA
EMA EMA
EMA
EMA
EMA
EMA
EMA
EMAEMA
CONCEAL CONDUIT TO QA FIXTURES ON TOP OF
STRUCTURAL BEAM FROM BUILDING. CONDUIT TO BE
SOLID CEDAR STAIN COLOR. COORDINATE COLOR WITH
ARCHITECT. (TYPICAL EXTERIOR CONDUIT)
CONCEAL CONDUIT TO QA FIXTURES ON TOP
OF STRUCTURAL BEAM FROM BUILDING.
RP-W - 12
RP-W - 13
RP-W - 15
RP-W - 16
RP-W - 17
RP-W - 19
RP-W - 19
CONCEAL CONDUIT TO QA FIXTURES ON TOP
OF STRUCTURAL BEAM FROM BUILDING
MOUNT LC FIXTURES TO UNISTRUT
COORDINATE WITH
ARCHITECTURAL/STRUCTURAL
MOUNT CONTROL DEVICES TO UNISTRUT
(TYPICAL STORAGE ROOM)
MOUNT SENSOR ON CEILING
(TYPICAL SENSORS IN SHOWER
AND TOILET RMS)
COORDINATE PLACEMENT OF
FIXTURES WITH PLUMBING PIPING
1 1
LC
RP-W - 14
1. PROVIDE TWO LABELED KEY SWITCHES FOR SUMMER-WINTER SWITCH TO INTERRUPT POWER TO MOTION SENSOR POWER PACKS (IN RETROOMS AND SHOWERS) IN ORDER TO DEACTIVATE SENSORS IN
"WINTER SHUTDOWN".
2. COORDINATE LIGHTING LAYOUT WITH ARCHITECTURAL ELEVATIONS, MECHANICAL FLOOR PLANS, AND
MECHANICAL DUCT WORK PRIOR TO ROUGH IN.
3. PROVIDE POWER PACKS AND ASSOCIATED WIRING FOR MULTIPLE SWITCH LEG LOCATIONS, SEE PLAN FOR EXACT SWITCH LEGS WITH-IN EACH AREA OR ROOM. ELECTRICAL CONTRACTOR SHALL SUPPLY
MANUFACTURER DEVICE LAYOUT AS PART OF SHOP DRAWINGS SUBMITTALS.
4. TO PREVENT FALSE ACTIVATION, CEILING MOUNT SENSORS SHALL BE MOUNTED AWAY FROM THE PATH OF STRONG AIR TURBULENCE A MINIMUM OF FOUR FEET FOR STANDARD SENSITIVITY AND SIX FEET
FOR MAXIMUM SENSITIVITY. FOR TYPICAL PLACEMENT, REFER TO LOCATION DIAGRAMS.
5. CONTRACTOR SHALL FOLLOW MANUFACTURER'S RECOMMENDED OF PLACEMENT, COVERAGE,
FREQUENCY AND VERIFY CIRCUITS WITH RESPECT TO POWER PACKS ETC,. NEEDED IN THE FIELD PER MANUFACTURER OF CHOICE, LOCATE AND AIM SENSORS IN THE CORRECT LOCATION REQUIRED FOR
COMPLETE AND PROPER VOLUMETRIC COVERAGE WITHIN THE RANGE OF COVERAGE(S) OF
CONTROLLED AREAS PER THE MANUFACTURER'S RECOMMENDATIONS. ROOMS SHALL HAVE ONE
HUNDRED (100%) PERCENT COVERAGE TO COMPLETELY COVER THE CONTROLLED AREA TO
ACCOMODATE ALL OCCUPANCY HABITS OF SINGLE OR MULTIPLE OCCUPANTS AT ANY LOCATION WITHIN THE ROOM(S). THE CONTRACTOR SHALL PROVIDE ADDITIONAL SENSORS IF REQUIRED TO PROPERLY
AND COMPLETELY COVER THE RESPECTIVE ROOM.
6. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF THE NUMBER OF POWER PACKS/ROOM
CONTROLLERS NEEDED. MAXIMUM NUMBER OF SENSORS PER POWER PACK/ROOM CONTROLLERS,
SLAVES, NETWORK BRIDGES, GATEWAYS, ETC, DEPENDENT ON SENSOR TYPE, SEE PRODUCT
INFORMATION. MULTIPLE CIRCUITS MAY BE CONTROLLED BY ONE SENSOR BY USING ADDITIONAL
POWER PACKS.
7. ELECTRICAL CONTRACTOR SHALL FIELD ADJUST EACH AREAS MOTION SENSOR'S TIME DELAY FROM 5 MINUTES TO 30 MINUTES PER OWNER'S DIRECTION. PRIOR TO INSTALLATION OF MOTION SENSORS, ELECTRICAL CONTRACTOR SHALL MEET WITH OWNER TO DETERMINE EACH AREAS TIME DELAY
SETTINGS.
8. AFTER 15 MINUTES OF NO MOTION DETECTED, SENSORS SHALL DIM FIXTURES TO 30%. 15 MINUTES AFTER BEING WITHIN DIMMED STATE OF NO MOTION DETECTED SENSOR SHALL TURN FIXTURE OFF.
ANY MOTION DURING THIS TIME WILL TURN FIXTURES ON TO 100%.
9. INTERIOR MOTION SENSOR, IN PUBLIC AREAS, TO BE DEACTIVATED DURING WINTER SHUTDOWN VIA
KEYED SWITCHES
GENERAL NOTES - ELECTRICAL
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M D
IS
C
IP
LI
N E
L E
A D
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
7/ 5/
2:
:2
P
M B
IM
-2 2-
M us ka llo ng e
S ta te P ar k/
_F
P M
E _M
S P
_A 2W es tC
G B ld g_
_C E
N .r vt
EL101
F
IR
S T
F
LO
O R
L
IG
H T
IN
G
P
LA
N
C ou nt y R oa d
N ew be rr y, M
I 4
M U
S K
A
LL
O N
G E
L A
K E
S T
A T
E P
A R
K
W E
S T
C A
M P
G R
O U
N D
T O
IL
E
T S
H O
W E
R B
U
IL
D
IN
G
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 2-
Z H
/0 7/
1.
8.
A
B G
D T
M B
F ile
N o.
S W
1/4" = 1'-0"1
FIRST FLOOR LIGHTING PLAN
UTILITY
ELECTRICAL
DISTRIBUTION
PANEL BOARD PP1
UTILITY PROVIDED
TRANSFORMER. CONTRACTOR
TO COORDINATE WITH UTILITY
240V/120V
600 AMP 1ɸ
2-3" CONDUIT W/ 3-350KCMIL
MULTIPLE CIRCUITS
TO ELECTRICAL
PEDESTAL CIRCUITS
PANEL RP-W 120/240V
100A, MCB, 42CKT
2" CONDUIT W/ 3-#2/0 AL AWG + #3
ALUMINUM GND. GROUND AND NEUTRAL TO
BE SEPARATELY ISOLATED AT PANEL
ELECTRICAL HH
BOX SHALL BE CONCRETE OR COMPOSITE. METAL COVER IS ACCEPTABLE.
COVERS SHALL BE SECURED WITH 3/8" BOLTS, NUTS AND WASHERS. WHICH SHALL BE
BRASS, STAINLESS STEEL OR OTHER CORROSION RESISTANT MATERIAL. STAINLESS STEEL
SHALL HAVE A CHROMIUM CONTENT OF NOT LESS THAN 18% AND A NICKEL CONTENT OF
NOT LESS THAN 8%, NUTS SHALL BE RECESSED BELOW TOP SURFACE OF COVER.
COVER LETTERING SHALL BE 1/2" MINIMUM LETTERS CAST IN STANDARD MARKINGS:
(ELECTRICAL).
CONDUIT ENTERING THE BOX SHALL HAVE 90 DEGREE LONG RADIUS BEND (INSIDE THE
BOX). THE CONDUITS OPENING, IINSIDE THE BOX, SHALL BE AT LEAST 4" BELOW THE LID,
OPENING SHALL HAVE SMOOTH EDGE. IF THE CONDUIT IS P.V.C. A SLIP COUPLING MUST BE
USED. IF THE CONDUIT IS RIGID PIPE, A PROTECTIVE BUSHING SHALL BE USED.
CONDUCTORS SHALL HAVE A MINIMUM OF 24" SLACK FROM CONDUIT BELL END.
BACKFILL WITH EXCAVATED MATERIAL AND THOROUGHLY COMPACT.
WHERE PULLBOXES ARE INSTALLED IN CONCRETE AREAS, 1/2" PREMOLDED EXPANSION
JOINT SHALL BE INSTALLED AROUND THE BOX.
BOXES TO BE TIER 22 UNLESS OTHERWISE NOTED.
NOTE:
1.)
2.)
3.)
4.)
5.)
6.)
7.)
5/8" x4" LIFTING SLOTS
16" x 8" CONCRETE BRICK
COVER TO BE FLUSH WITH FINISH GRADE
ALL CONDUIT END BELLS SHALL BE
INSTALLED BEFORE PULLING WIRE
1" PVC CONDUIT FOR DRAINAGE
6A BACKFILL WITH MINIMUM
OF 5" DEPTH
5/8" DIAMETER (TYPICAL)
GROUND ROD (8' MIN. LENGTH)
23 3/4"
21 1/4"
15 9/16"
/2
/8
15 3/8"
ELECTRICAL
M
IN
8.)
C/L OF
ELECTRICAL BOX
C/L OF
WATER
SUPPLY
C/L OF
FIXTURE
TOP OF FIXTURE.
1/
2"
2 3/4"
4 3/4"
/2
3/4" CONDUIT FROM
VALVE TO SENSOR.
SLOAN EL-154
TRANSFORMER SUPPLIED BY
PLUMBING CONTRACTOR
MOUNTED AT HEIGHT IND
3/4" CONDUIT TO SENSOR.
ONE PER 10 FIXTURES.
WATER CLOSET
FLUSH VALVE.
4"x4"x2 1/2" SURFACE
MOUNTED JUNCTION BOX.
MOUNT AT 12' AFF
4"x4"x2 1/2" RECESSED
JUNCTION BOX. COVER
SUPPLIED BY OTHERS
4"x4"x2 1/2" RECESSED
JUNCTION BOX. COVER
SUPPLIED BY OTHERS
3/4" CONDUIT TO
NEXT SENSOR/SOLENOID
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M D
IS
C
IP
LI
N E
L E
A D
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
7/ 5/
2:
:1
P
M B
IM
-2 2-
M us ka llo ng e
S ta te P ar k/
_F
P M
E _M
S P
_A 2W es tC
G B ld g_
_C E
N .r vt
E-501
E
LE
C T
R
IC
A L
D E
T A
IL
S
C ou nt y R oa d
N ew be rr y, M
I 4
M U
S K
A
LL
O N
G E
L A
K E
S T
A T
E P
A R
K
W E
S T
C A
M P
G R
O U
N D
T O
IL
E
T S
H O
W E
R B
U
IL
D
IN
G
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 2-
Z H
/0 7/
1.
8.
A
B G
D T
M B
F ile
N o.
S W
N.T.S2
ONE-LINE POWER DIAGRAM - PP1
N.T.S3
HANDHOLE DETAIL
N.T.S1
FLUSH VALVE MOUNTING HEIGHT DETAIL
1 1 X AUTOMATIC ON TO 100%, DIM FIXTURE TO 30% AFTER 15 MINUTES OF NO MOTION DETECTED.
AUTOMATIC OFF AFTER 15 MINUTES OF NO MOTION DETCTED WHILE IN DIMMED STATE.
SCHEME NO. MANUAL ON DIMMING NO. OF SCENES MULTIPLE ZONES DAYLIGHTING
OCCUPANCY
SENSOR
VACANCY SENSOR ORDER OF OPERATION
LIGHTING CONTROL SCHEDULE - MAIN BUILDING
X SCHEME NO.
2 1
MANUAL ON, AUTOMATIC OFF AFTER 15 MINUTES OF NO MOTION DETECTED.
• BUTTON TOGGLES LIGHTS ON TO 100% AND OFF.
X X
S T
A T
E O
F M
IC
H
IG
A
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
LO
G
Y , M
A N
A G
E M
E N
T A
D G
E T
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
ARCHITECTS ENGINEERS PLANNERS
OHM-ADVISORS.COM
R
C O
P Y
R
IG
H T
O
H M
A
LL
D R
A W
IN
G
S A
N D
W R
IT
T
E N
M A
T E
R
IA
LS
A
P P
E A
R
IN
G H
E R
E
IN
C O
N S
T
IT
U T
E T
H E
O R
IG
IN
A L
A N
D U
N P
U B
LI
S
H E
D W
O R
K O
F O
H M
A N
D T
H E
S A
M E
M A
Y N
O T
B E
D U
P
LI
C A
T E
D , D
IS
T
R
IB
U T
E D
, O R
D
IS
C
LO
S E
D W
IT
H
O U
T P
R
IO
R W
R
IT
T E
N C
O N
S E
N T
O F
O H
M
IS
S
U E
D F
O R
P
R O
JE
C
T N
U M
B E
R P
M D
IS
C
IP
LI
N E
L E
A D
A D
A M
P . L
A C
H , R
A , D
IR
E
C T
O R
7/ 5/
2:
:1
P
M B
IM
-2 2-
M us ka llo ng e
S ta te P ar k/
_F
P M
E _M
S P
_A 2W es tC
G B ld g_
_C E
N .r vt
E-601
E
LE
C T
R
IC
A L
S C
H E
D U
LE
S
C ou nt y R oa d
N ew be rr y, M
I 4
M U
S K
A
LL
O N
G E
L A
K E
S T
A T
E P
A R
K
W E
S T
C A
M P
G R
O U
N D
T O
IL
E
T S
H O
W E
R B
U
IL
D
IN
G
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
-2 2-
Z H
/0 7/
1.
8.
A
B G
D T
M B
F ile
N o.
S W
1. PROVIDE TWO LABELED KEY SWITCHES FOR SUMMER-WINTER SWITCH TO INTERRUPT POWER TO MOTION SENSOR POWER PACKS (IN RESTROOMS AND SHOWERS) IN
ORDER TO DEACTIVATE SENSORS IN "WINTER SHUTDOWN"
SCHEDULE NOTES:
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MFR. CATALOG # LAMPS WATTS NOTES
EMA EMERGENCY BUG EYES DUAL LITE PG-W-HTR LED 15 REQUIRES UN-SWITCHED HOT
LA SURFACE LINEAR METALUX HVL8-(BR/MR/ER)-4-LD4-1STD-30-UNV-O-EDD1-SHVL8-4LEDCM LED 33 COORDINATE BR/MR/ER WITH
BEGINNING, MIDDLE AND END RUN
AS FIXTURES APPEAR ON SHEETS.
LB WALL MOUNT LUMINAIRE LITHONIA ARV13-MIN10-25W30K-120-OP-WHT LED 27
LC SURFACE LINEAR CREE LIGHTING LS4-40L-830-10V LED 31
OA WALL MOUNT LUMINAIRE LUMARK AXCS1A-W-PC1 LED 14
CONNECTED LOAD: (kVA) 8.67 6.22
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
WOMENS 105 HAND DRYER 12 1 20 25 1.00 26
MENS 104 HAND DRYER 12 1 20 23 1.00 24
MENS FLUSH VALVE POWER 12 1 20 21 0.05 1.00 22 20 1 12 LAV. 111 HAND DRYER
PORCH A AND B LITES 12 1 20 19 0.04 0.05 20 20 1 12 WOMEN FLUSH VALVE POWER
EMERGENCY LITES 12 1 20 17 0.08 0.18 18 20 1 12 LAV. 111 GFCI RECEPTACLE
STORAGE 105 LITES 12 1 20 15 0.21 0.30 16 20 1 12 SHOWER/LAV. 111 LITES
MENS 104 LITES 12 1 20 13 0.18 0.15 14 20 1 12 WOMENS 105
STORAGE 106 GFCI RECEPT 12 1 20 11 0.18 0.01 12 20 1 12 PORCH C OUTSIDE LITES
STORAGE 106 GFCI RECEPT 12 1 20 9 0.18 0.36 10 20 1 12 STORAGE 106 RECEPTS
WOMENS FAUCET RECEPTS 12 1 20 7 0.54 1.00 8 20 1 12 WOMENS 105 HAND DRYER
MENS 104 HAND DRYER 12 1 20 5 1.00 0.54 6 20 1 12 MENS FAUCET RECEPTS
STORAGE 106/OUTSIDE... 12 1 20 3 0.36 2.53 4
F-1 12 1 20 1 1.43 2.53 2
35 2 8 ERV-1
IDENTIFICATION
WIRE
SIZES POLE AMP CKT
A kVA
B kVA
A kVA
B kVA CKT AMP POLE
WIRE
SIZES IDENTIFICATION
FED FROM EXISTING PP1 THROUGH RELOCATED HANDHOLE
NOTES:
ENCLOSURE: TYPE 1 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 3 MAINS RATING: 100 A
SUPPLY FROM: PHASES: 1 MAINS TYPE: MCB
LOCATION: STORAGE ROOM 106 VOLTS: 120/240 Single SCCR RATING: 10 K
BRANCH PANEL: RP-W