220819-2218900-ICF HVAC Upgrades - CD set - prints-2.pdf
PDF 2 MB Posted
- Solicitation number
- RFQ - 171 - 220000000524
- Issued by
- Ionia County, Michigan
About this file
This document appears to be a set of design drawings and specifications for HVAC upgrades at various state and local facilities in Ionia County, Michigan. The key details are:
The project involves installing new condensing units, piping, cooling coils, and controls at the mechanical rooms of the Administration Building (Building 100), Support Service Building (Building 200), and Education/Recreation Building (Building 300). The work includes modifying existing air handling unit enclosures as needed, installing steel cross beams, connecting the new equipment to the existing Trane DDC control panels, and modifying the existing controls to match the new equipment requirements. The electrical drawings show demolition and new work to reconnect the mechanical equipment.
The contract is being administered by the Michigan Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division. The bid submission deadline is not provided, but the drawing issue date is August 19, 2022. The contract term and any renewal options are not specified. Pricing terms, funding sources, and other commercial details are also not included in the provided documentation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL KEY NOTES
INSTALL NEW CONDENSING UNIT, DX PIPING, COOLING COIL,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES PER
MANUFACTURE'S INSTALLATION INSTRUCTIONS AT LOCATION
SHOWN. MOUNT NEW CONDENSING UNIT ON EXISTING CURB
RAILS.
IF EXISTING PIPING SUPPORT ROOF CURB RAILS ARE
ABANDONED, SUPPORT REFRIGERANT PIPING WITH MIRO
24-BASE STRUT OR APPROVED EQUAL. SUPPORTS SHALL BE
CAPABLE OF BEING FIELD ADJUSTED BY CONTRACTOR TO
SUPPORT DX PIPING ON SLOPED ROOF WITH UP TO A 2%
SLOPE. SPACING AND QUANTITY OF PIPE SUPPORTS SHALL
BE DETERMINED BY PIPE SUPPORT MANUFACTURER, BUT NOT
TO EXCEED 8' SPACING. STRUT AND ALL HARDWARE FOR
SUPPORTS SHALL BE GALVANIZED AND BASES SHALL BE
POLYCARBONATE. INSTALL 1/8" THICK x 15.75" WIDE x 19.75"
LONG INJECTION MOLDED LOW DENSITY POLYETHYLENE PAD
BETWEEN DX PIPING CONDUIT SUPPORT AND ROOF, BASED
ON MIRO INDUSTRIES SUPPORT PAD. IF EXISTING PIPING
SUPPORT CURB RAILS ARE REUSUED, CONTRACTOR TO
PROVIDE NEW PIPING SUPPORT UNISTRUT FRAME AND ALL
ASSOCIATED ACCESSORIES TO MATCH EXISTING. TYPICAL
FOR ALL DX PIPING.
INSTALL NEW COOLING COIL AT LOCATION SHOWN PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
CONTRACTOR TO FIELD MEASURE NEW COOLING COIL SIZE
PRIOR TO ORDERING. MODIFY EXISTING AIR HANDLING UNIT
ENCLOSURE AS REQUIRED TO INSTALL NEW COOLING COIL.
INSTALL AND FASTEN W8x58 STEEL CROSS BEAMS ON TOP OF
EXISTING CURB RAILS AS NEEDED TO LINE UP WITH
CONDENSING UNIT MOUNTING POINTS AND PROVIDE PROPER
MOUNTING. PROVIDE AND COORDINATE NUMBER OF CROSS
BEAMS WITH CONDENSING UNIT MANUFACTURER.
CONNECT NEW CONDENSING UNIT AND COOLING COIL TO
EXISTING TRANE DDC CONTROL PANEL. EXISTING SEQUENCE
OF OPERATIONS TO REMAIN. MODIFY EXISTING CONTROLS AS
NEEDED TO MATCH NEW CONDENSING UNIT COMPRESSOR
STAGING AND MODULATION REQUIREMENTS.
M
X-D
X-L
X-UH
M
X-D
MX-D
X-42x24 RAX-42x24 RA
X-42x24 RA
X-14x16 SA X-10x16 SA
X-14x16 SA X-12x16 SA
X-8x16 SA X-12x16 SA
X-12x16 SA
X-8x16 SA
X-1-1/4"
X-2"
X-HR
X-HS
X-HR
X-HS
X-HR
X-HS
X-CA
X-
HR
X-
HS
X-1"
X-3/4"
X-1"
X-
HR
X-
HS
X-STM X-STM
X-UH
X-UH
X-1/4"
X-CA
X-1-1/4"
X-1-1/2"
HS & HR
X-1-1/2"
X-2"
X-11'x8'x4' PLENUM
X-L
X-L
X-HR
X-HS
X-AHU-6
X-AHU
CONTROL
PANEL
X-EF DDC
CONTROL
PANEL
X-RAIL
X-RAIL
DX
CC-200-1
PIPING SUPPORTS
(TYP.)
CU-200-1
DX1
STEEL CROSS
BEAM (TYP.)5
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
M-401
BRH
SUPPORT SERVICE BUILDING
- (BLDG 200) - MECHANICAL
ROOM PLAN - HVAC NEW
N
SUPPORT SERVICE BUILDING - (BLDG 200) -
MECHANICAL ROOM PLAN - HVAC NEW
SCALE: 1/4" = 1'-0"
0 1 5 10
JLH
MECHANICAL KEY NOTES
INSTALL NEW CONDENSING UNIT, DX PIPING, COOLING COIL,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES PER
MANUFACTURE'S INSTALLATION INSTRUCTIONS AT LOCATION
SHOWN. MOUNT NEW CONDENSING UNIT ON EXISTING CURB
RAILS.
IF EXISTING PIPING SUPPORT ROOF CURB RAILS ARE
ABANDONED, SUPPORT REFRIGERANT PIPING WITH MIRO
24-BASE STRUT OR APPROVED EQUAL. SUPPORTS SHALL BE
CAPABLE OF BEING FIELD ADJUSTED BY CONTRACTOR TO
SUPPORT DX PIPING ON SLOPED ROOF WITH UP TO A 2%
SLOPE. SPACING AND QUANTITY OF PIPE SUPPORTS SHALL
BE DETERMINED BY PIPE SUPPORT MANUFACTURER, BUT
NOT TO EXCEED 8' SPACING. STRUT AND ALL HARDWARE FOR
SUPPORTS SHALL BE GALVANIZED AND BASES SHALL BE
POLYCARBONATE. INSTALL 1/8" THICK x 15.75" WIDE x 19.75"
LONG INJECTION MOLDED LOW DENSITY POLYETHYLENE PAD
BETWEEN DX PIPING CONDUIT SUPPORT AND ROOF, BASED
ON MIRO INDUSTRIES SUPPORT PAD. IF EXISTING PIPING
SUPPORT CURB RAILS ARE REUSUED, CONTRACTOR TO
PROVIDE NEW PIPING SUPPORT UNISTRUT FRAME AND ALL
ASSOCIATED ACCESSORIES TO MATCH EXISTING. TYPICAL
FOR ALL DX PIPING.
INSTALL NEW COOLING COIL AT LOCATION SHOWN PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
CONTRACTOR TO FIELD MEASURE NEW COOLING COIL SIZE
PRIOR TO ORDERING. MODIFY EXISTING AIR HANDLING UNIT
ENCLOSURE AS REQUIRED TO INSTALL NEW COOLING COIL.
INSTALL AND FASTEN W8x58 STEEL CROSS BEAMS ON TOP
OF EXISTING CURB RAILS AS NEEDED TO LINE UP WITH
CONDENSING UNIT MOUNTING POINTS AND PROVIDE PROPER
MOUNTING. PROVIDE AND COORDINATE NUMBER OF CROSS
BEAMS WITH CONDENSING UNIT MANUFACTURER.
CONNECT NEW CONDENSING UNIT AND COOLING COIL TO
EXISTING TRANE DDC CONTROL PANEL. EXISTING SEQUENCE
OF OPERATIONS TO REMAIN. MODIFY EXISTING CONTROLS
AS NEEDED TO MATCH NEW CONDENSING UNIT
COMPRESSOR STAGING AND MODULATION REQUIREMENTS.
X-DX
CU-300-1
M-402
REFER TO MECHANICAL
ROOM ENLARGEMENT PLAN
ON SHEET M-402 FOR DX
PIPING CONTINUATION
PIPING SUPPORTS
(TYP.) 2
1 CU-300-2 1
X-RAILS
X-RAILS
X-RAILS
X-RAILS
STEEL CROSS
BEAM (TYP.)
STEEL CROSS
BEAM (TYP.)
DX
DX
DX
DX
DX
DX
REFER TO ROOF PLAN ON SHEET
M-402 FOR DX PIPING CONTINUATION
CC-300-2
X-L
X-30x30 UP
TO X-RH-3
X-2"
X-EF
X-HR
X-HS
X-UH-12
X-AHU-12
X-30x30 RA DN
X-60x24 RA
X-54x24 RA X-64x24 RA
X-60x24
X-
HR
X-
HS
X-HR
X-HS
X-20x14 SA X-16x16 RA
X-16x12 RA DN
X-20x20 SA DN
X-20x20 RA
X-24x24 EA
X-24x24 EA
UP TO X-RH-4
X-28"ø RA
X-28"ø SA
X-2"
X-AHU-11
X-3" X-3"
X-AHU-13
X-36x36 RA DN
X-1-1/2"
X-L
X-L
X-36x36 UP
TO X-RH-5
X-36x24 RA
X-50x20 SA
X-2"
X-24x24
SA DN
X-3/4"
X-36x36
SA DN
X-DDC CONTROL PANEL
X-DDC CONTROL PANEL
CC-300-1
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
M-402
BRH
EDUCATION/RECREATION
BUILDING - (BLDG 300) -
MECHANICAL ROOM PLAN -
HVAC NEW
N
EDUCATION/RECREATION BUILDING - (BLDG 300) -
MECHANICAL ROOM PLAN - HVAC NEW
ENLARGED MECHANICAL ROOM
PLAN - HVAC NEW
SCALE: 1/2" = 1'-0"
0 1 5
SCALE: 1/4" = 1'-0"
JLH
X
X
X
TVSS
VFD
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVEDUPLEX RECEPTACLE
DOCK LIGHT FIXTURE
TELEPHONE / DATA OUTLET
ADDENDUM NOTE
PLAN NOTE
DEMOLITION NOTE
THREE PHASE MOTOR
ELECTRICAL SYMBOLS LEGEND
J
SINGLE RECEPTACLE (120 VOLT)
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
OUTLETS
LIGHT FIXTURE
STRIP FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
EMERGENCY LIGHT FIXTURE
FIXTURES
SWITCHES
SINGLE-POLE SWITCH
DIMMER SWITCH
TIME SWITCH
KEY SWITCH
MANUAL MOTOR SWITCH
THERMAL OVERLOAD SWITCH
SWITCH WITH PILOT LIGHT
FOUR-WAY SWITCH
THREE-WAY SWITCH
CIRCUITRY and RACEWAYS
UNDERFLOOR DUCT
BUS DUCT
PLUGMOLD AS SPECIFIED
WIREMOLD AS SPECIFIED
FLEXIBLE PIGTAILS/CONNECTIONS
"CONDUIT RUN CONTINUES" INDICATION
END OF CONDUIT RUN, CAP AND STAKE
END OF CONDUIT RUN
HOME RUN (with circuit numbers)
CONDUIT STUB DOWN
CONDUIT STUB UP
CONDUIT INSTALLED
CONDUIT INSTALLED
MECHANICAL
ELECTRIC WATER HEATER
ELECTRIC UNIT HEATER
PIPE TRACE HEATER
RESISTANCE HEATER, KW SHOWN
SINGLE PHASE MOTOR
SERVICE and EQUIPMENT
THERMOSTAT
CAPACITOR
ENCLOSED CIRCUIT BREAKER
TRANSFER SWITCH
WIREWAY
GROUND CONNECTION PER N.E.C.
TELEPHONE TERMINAL BOARD
GENERATOR, KW SHOWN
CURRENT TRANSFORMERS
UTILITY METER, AS REQUIRED
WEATHERHEAD
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
COMB. STARTER (BY x/C U.O.N.)
MAGNETIC STARTER (BY x/C U.O.N.)
DISCONNECT SWITCH (fuse size shown)
TRANSFORMER
CONTROL
xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt
LIGHTING CONTACTOR
CONTROL TRANSFORMER
buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)
PHOTOCELL (voltage as required)
HUMIDISTAT
DESIGNATIONS
(by E.C.)
(by others)
TT
G
WW
PC
CT
TS
T
H
TC
IC
T
1,3
OR
PM
WM
BD
UFD
F S
J
J
D
WH
PP
J
CEILING MOUNTED WIFI
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST (E)
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
GENERAL ELECTRICAL NOTES
1. ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED WITH LIKE MATERIAL TO
MAINTAIN ORIGINAL RATING.
2. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL
STEEL.
3. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID WALK THROUGH TO
DETERMINE THE EXACT EXTENT OF THE DEMOLITION WORK REQUIRED BEFORE
BIDDING THE PROJECT.
4. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT
WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.
5. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,
SURFACES SHALL BE PATCHED TO MATCH ADJACENT.
6. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN
CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED
NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH
SURFACE AND THEN PATCHED AND PAINTED TO MATCH, OR AS NOTED.
7. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED
TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND
PATCHING.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO
MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.
9. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING
SERVICE TO EQUIPMENT.
10. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD
OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.
11. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. REFER TO SPECIFICATION 260533 -
RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.
12. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
12.1. STRAP DISTANCE: 5 FEET.
12.2. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.
12.3. FITTINGS: COMPRESSION.
12.4. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.
13. ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
13.1. STRAP DISTANCE: 3 FEET.
13.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
13.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.
13.4. FITTINGS: COMPRESSION.
13.5. BELL BOXES: FS TYPE.
13.6. NO KNOCKOUTS.
13.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES
14. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE
CEILINGS IS ACCEPTABLE.
15. CONDUITS SHALL BE INSTALLED STRAIGHT AND LEVEL AND SHALL BE PARALLEL OR
PERPENDICULAR TO THE BUILDING LINES.
16. CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.
17. ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE SURFACE MOUNTED
CONDUIT FOLLOWING NOTES 11 AND 12 ABOVE.
18. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.
19. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE
EPC-40-PVC
20. ANY ELECTRICAL OUTAGE SHALL NOT LAST OVER 2-HOURS. FOR OUTAGES OVER
PORTABLE GENERATORS SHALL BE USED TO REPLACE ANY ELECTRICAL SERVICE
EXCEEDING THAT DURATION.
21. UPON RELOCATING LIGHTS AND CAMERAS CONTRACTOR SHALL VERIFY THAT THE
LIGHTS AND CAMERAS ARE WORKING PROPERLY PRIOR TO LEAVING THE SITE.
22. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED COMPONENTS,
RACEWAYS, WIRE, AND HARDWARE, AS INDICATED ON DRAWINGS.
23. ALL WORK DONE WITHOUT APPROVED SHOP DRAWINGS IS AT CONTRACTORS RISK.
24. UPON RELOCATING LIGHTS AND CAMERAS CONTRACTOR SHALL VERIFY THAT THE
LIGHTS AND CAMERAS AREA WORKING PROPERLY PRIOR TO LEAVING THE SITE.
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
E-100
JKB
JFS
ELECTRICAL
SYMBOLS
ABBREV.
+ NOTES
X-CU-2
X-CU-1
PNL "MPB"
CU-100-2
480V-3Ø, 140A
EX
CU-100-1
480V-3Ø, 140A
EXIST
PNL "MPB"
GFI/WP
EXISTING DEVICE TO REMAIN.
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT EQUIPMENT FOR REMOVAL BY OTHERS. ALL ASSOCIATED
CONDUIT, WIRE, OVERCURRENT, AND CONTROL DEVICES ARE TO REMAIN.
DISCONNECT & RELOCATE EXISTING DEVICES. EXTEND EXISTING CONDUIT &
WIRE TO NEW LOCATION.
DEMOLITION NOTES
ELECTRICAL KEY NOTES
RECONNECT MECHANICAL EQUIPMENT TO ALL ASSOCIATED CONDUIT, WIRE,
OVERCURRENT, AND CONTROL DEVICES AT THIS LOCATION.
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
E-500
JKB
JFS
ADMINISTRATION BUILDING -
(BLDG 100) - MECHANICAL
ROOM PLAN - ELECTRICAL
DEMOLITION & NEWN
ADMINISTRATION BUILDING - (BLDG 100) -
MECHANICAL ROOM PLAN - ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10 N
ADMINISTRATION BUILDING - (BLDG 100) -
MECHANICAL ROOM PLAN - ELECTRICAL NEW
SCALE: 1/4" = 1'-0"
PNL "DPB-C"
CU-200-1
480V-3Ø, 41.6A
EX
EXIST
PNL "DPB-C"
EXISTING DEVICE TO REMAIN.
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT EQUIPMENT FOR REMOVAL BY OTHERS. ALL ASSOCIATED
CONDUIT, WIRE, OVERCURRENT, AND CONTROL DEVICES ARE TO REMAIN.
DISCONNECT & RELOCATE EXISTING DEVICES. EXTEND EXISTING CONDUIT &
WIRE TO NEW LOCATION.
DEMOLITION NOTES
ELECTRICAL KEY NOTES
RECONNECT MECHANICAL EQUIPMENT TO ALL ASSOCIATED CONDUIT, WIRE,
OVERCURRENT, AND CONTROL DEVICES AT THIS LOCATION.
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
E-501
JKB
JFS
N
SUPPORT SERVICE BUILDING - (BLDG 200) -
MECHANICAL ROOM PLAN - ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10 N
SUPPORT SERVICE BUILDING - (BLDG 200) -
MECHANICAL ROOM PLAN - ELECTRICAL NEW
SCALE: 1/4" = 1'-0"
0 1 5 10
SUPPORT SERVICE BUILDING -
(BLDG 200) - MECHANICAL
ROOM PLAN - ELECTRICAL
DEMOLITION & NEW
X-CU-2
CND TYP.
PNL "DPB-2"
PNL "DPB-1"
CU-300-2
480V-3Ø, 36FLA
CU-300-1
480V-3Ø, 36FLA
EXIST
PNL "DPB-2"
EXIST
PNL "DPB-1"
WP
WP
EXISTING DEVICE TO REMAIN.
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT EQUIPMENT FOR REMOVAL BY OTHERS. ALL ASSOCIATED
CONDUIT, WIRE, OVERCURRENT, AND CONTROL DEVICES ARE TO REMAIN.
DISCONNECT & RELOCATE EXISTING DEVICES. EXTEND EXISTING CONDUIT &
WIRE TO NEW LOCATION.
DEMOLITION NOTES
ELECTRICAL KEY NOTES
NOT USED.
RELOCATED DEVICE EXTEND ALL ASSOCIATED CONDUIT,
WIRE, OVERCURRENT, AND CONTROL DEVICES AT THIS
LOCATION.
EXTEND ALL ASSOCIATED CONDUIT, AND WIRE, FOR NEW
DISCONNECT .
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
E-502
JKB
JFS
N
EDUCATION/RECREATION BUILDING - (BLDG 300) -
MECHANICAL ROOM PLAN - ELECTRICAL DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10 N
EDUCATION/RECREATION BUILDING - (BLDG 300) -
MECHANICAL ROOM PLAN - ELECTRICAL NEW
SCALE: 1/4" = 1'-0"
0 1 5 10
EDUCATION/RECREATION
BUILDING - (BLDG 300) -
MECHANICAL ROOM PLAN -
ELECTRICAL DEMOLITION &
NEW
| Sheets and Views |
| M000-2218900-M000 |
| M100 - 2218900-M100 |
| M300 - 2218900-M300 |
| M301 - 2218900-M301 |
| M302 - 2218900-M302 |
| M400 - 2218900-M400 |
| M401 - 2218900-M401 |
| M402 - 2218900-M402 |
| CD Elec Set.pdf |
| E100-2218900-30x42 |
| E500-2218900-30x42 |
| E501-2218900-30x42 |
| E502-2218900-30x42 |
File details come from the government source that posted it. Updated .