220819-2218900-ICF HVAC Upgrades - CD set - prints-2.pdf

PDF 2 MB Posted

Attached to
472/21165. SMD; Ionia CF - HVAC Repair and Replacement
Solicitation number
RFQ - 171 - 220000000524
Issued by
Ionia County, Michigan

About this file

This document appears to be a set of design drawings and specifications for HVAC upgrades at various state and local facilities in Ionia County, Michigan. The key details are:

The project involves installing new condensing units, piping, cooling coils, and controls at the mechanical rooms of the Administration Building (Building 100), Support Service Building (Building 200), and Education/Recreation Building (Building 300). The work includes modifying existing air handling unit enclosures as needed, installing steel cross beams, connecting the new equipment to the existing Trane DDC control panels, and modifying the existing controls to match the new equipment requirements. The electrical drawings show demolition and new work to reconnect the mechanical equipment.

The contract is being administered by the Michigan Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division. The bid submission deadline is not provided, but the drawing issue date is August 19, 2022. The contract term and any renewal options are not specified. Pricing terms, funding sources, and other commercial details are also not included in the provided documentation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MECHANICAL KEY NOTES

INSTALL NEW CONDENSING UNIT, DX PIPING, COOLING COIL,

CONTROLS, AND ALL ASSOCIATED ACCESSORIES PER

MANUFACTURE'S INSTALLATION INSTRUCTIONS AT LOCATION

SHOWN. MOUNT NEW CONDENSING UNIT ON EXISTING CURB

RAILS.

IF EXISTING PIPING SUPPORT ROOF CURB RAILS ARE

ABANDONED, SUPPORT REFRIGERANT PIPING WITH MIRO

24-BASE STRUT OR APPROVED EQUAL. SUPPORTS SHALL BE

CAPABLE OF BEING FIELD ADJUSTED BY CONTRACTOR TO

SUPPORT DX PIPING ON SLOPED ROOF WITH UP TO A 2%

SLOPE. SPACING AND QUANTITY OF PIPE SUPPORTS SHALL

BE DETERMINED BY PIPE SUPPORT MANUFACTURER, BUT NOT

TO EXCEED 8' SPACING. STRUT AND ALL HARDWARE FOR

SUPPORTS SHALL BE GALVANIZED AND BASES SHALL BE

POLYCARBONATE. INSTALL 1/8" THICK x 15.75" WIDE x 19.75"

LONG INJECTION MOLDED LOW DENSITY POLYETHYLENE PAD

BETWEEN DX PIPING CONDUIT SUPPORT AND ROOF, BASED

ON MIRO INDUSTRIES SUPPORT PAD. IF EXISTING PIPING

SUPPORT CURB RAILS ARE REUSUED, CONTRACTOR TO

PROVIDE NEW PIPING SUPPORT UNISTRUT FRAME AND ALL

ASSOCIATED ACCESSORIES TO MATCH EXISTING. TYPICAL

FOR ALL DX PIPING.

INSTALL NEW COOLING COIL AT LOCATION SHOWN PER

MANUFACTURER'S INSTALLATION INSTRUCTIONS.

CONTRACTOR TO FIELD MEASURE NEW COOLING COIL SIZE

PRIOR TO ORDERING. MODIFY EXISTING AIR HANDLING UNIT

ENCLOSURE AS REQUIRED TO INSTALL NEW COOLING COIL.

INSTALL AND FASTEN W8x58 STEEL CROSS BEAMS ON TOP OF

EXISTING CURB RAILS AS NEEDED TO LINE UP WITH

CONDENSING UNIT MOUNTING POINTS AND PROVIDE PROPER

MOUNTING. PROVIDE AND COORDINATE NUMBER OF CROSS

BEAMS WITH CONDENSING UNIT MANUFACTURER.

CONNECT NEW CONDENSING UNIT AND COOLING COIL TO

EXISTING TRANE DDC CONTROL PANEL. EXISTING SEQUENCE

OF OPERATIONS TO REMAIN. MODIFY EXISTING CONTROLS AS

NEEDED TO MATCH NEW CONDENSING UNIT COMPRESSOR

STAGING AND MODULATION REQUIREMENTS.

M

X-D

X-L

X-UH

M

X-D

MX-D

X-42x24 RAX-42x24 RA

X-42x24 RA

X-14x16 SA X-10x16 SA

X-14x16 SA X-12x16 SA

X-8x16 SA X-12x16 SA

X-12x16 SA

X-8x16 SA

X-1-1/4"

X-2"

X-HR

X-HS

X-HR

X-HS

X-HR

X-HS

X-CA

X-

HR

X-

HS

X-1"

X-3/4"

X-1"

X-

HR

X-

HS

X-STM X-STM

X-UH

X-UH

X-1/4"

X-CA

X-1-1/4"

X-1-1/2"

HS & HR

X-1-1/2"

X-2"

X-11'x8'x4' PLENUM

X-L

X-L

X-HR

X-HS

X-AHU-6

X-AHU

CONTROL

PANEL

X-EF DDC

CONTROL

PANEL

X-RAIL

X-RAIL

DX

CC-200-1

PIPING SUPPORTS

(TYP.)

CU-200-1

DX1

STEEL CROSS

BEAM (TYP.)5

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

22189.00

M a t r ix

472/21165.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

08/19/2022 CD SET

M-401

BRH

SUPPORT SERVICE BUILDING

- (BLDG 200) - MECHANICAL

ROOM PLAN - HVAC NEW

N

SUPPORT SERVICE BUILDING - (BLDG 200) -

MECHANICAL ROOM PLAN - HVAC NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

JLH

MECHANICAL KEY NOTES

INSTALL NEW CONDENSING UNIT, DX PIPING, COOLING COIL,

CONTROLS, AND ALL ASSOCIATED ACCESSORIES PER

MANUFACTURE'S INSTALLATION INSTRUCTIONS AT LOCATION

SHOWN. MOUNT NEW CONDENSING UNIT ON EXISTING CURB

RAILS.

IF EXISTING PIPING SUPPORT ROOF CURB RAILS ARE

ABANDONED, SUPPORT REFRIGERANT PIPING WITH MIRO

24-BASE STRUT OR APPROVED EQUAL. SUPPORTS SHALL BE

CAPABLE OF BEING FIELD ADJUSTED BY CONTRACTOR TO

SUPPORT DX PIPING ON SLOPED ROOF WITH UP TO A 2%

SLOPE. SPACING AND QUANTITY OF PIPE SUPPORTS SHALL

BE DETERMINED BY PIPE SUPPORT MANUFACTURER, BUT

NOT TO EXCEED 8' SPACING. STRUT AND ALL HARDWARE FOR

SUPPORTS SHALL BE GALVANIZED AND BASES SHALL BE

POLYCARBONATE. INSTALL 1/8" THICK x 15.75" WIDE x 19.75"

LONG INJECTION MOLDED LOW DENSITY POLYETHYLENE PAD

BETWEEN DX PIPING CONDUIT SUPPORT AND ROOF, BASED

ON MIRO INDUSTRIES SUPPORT PAD. IF EXISTING PIPING

SUPPORT CURB RAILS ARE REUSUED, CONTRACTOR TO

PROVIDE NEW PIPING SUPPORT UNISTRUT FRAME AND ALL

ASSOCIATED ACCESSORIES TO MATCH EXISTING. TYPICAL

FOR ALL DX PIPING.

INSTALL NEW COOLING COIL AT LOCATION SHOWN PER

MANUFACTURER'S INSTALLATION INSTRUCTIONS.

CONTRACTOR TO FIELD MEASURE NEW COOLING COIL SIZE

PRIOR TO ORDERING. MODIFY EXISTING AIR HANDLING UNIT

ENCLOSURE AS REQUIRED TO INSTALL NEW COOLING COIL.

INSTALL AND FASTEN W8x58 STEEL CROSS BEAMS ON TOP

OF EXISTING CURB RAILS AS NEEDED TO LINE UP WITH

CONDENSING UNIT MOUNTING POINTS AND PROVIDE PROPER

MOUNTING. PROVIDE AND COORDINATE NUMBER OF CROSS

BEAMS WITH CONDENSING UNIT MANUFACTURER.

CONNECT NEW CONDENSING UNIT AND COOLING COIL TO

EXISTING TRANE DDC CONTROL PANEL. EXISTING SEQUENCE

OF OPERATIONS TO REMAIN. MODIFY EXISTING CONTROLS

AS NEEDED TO MATCH NEW CONDENSING UNIT

COMPRESSOR STAGING AND MODULATION REQUIREMENTS.

X-DX

CU-300-1

M-402

REFER TO MECHANICAL

ROOM ENLARGEMENT PLAN

ON SHEET M-402 FOR DX

PIPING CONTINUATION

PIPING SUPPORTS

(TYP.) 2

1 CU-300-2 1

X-RAILS

X-RAILS

X-RAILS

X-RAILS

STEEL CROSS

BEAM (TYP.)

STEEL CROSS

BEAM (TYP.)

DX

DX

DX

DX

DX

DX

REFER TO ROOF PLAN ON SHEET

M-402 FOR DX PIPING CONTINUATION

CC-300-2

X-L

X-30x30 UP

TO X-RH-3

X-2"

X-EF

X-HR

X-HS

X-UH-12

X-AHU-12

X-30x30 RA DN

X-60x24 RA

X-54x24 RA X-64x24 RA

X-60x24

X-

HR

X-

HS

X-HR

X-HS

X-20x14 SA X-16x16 RA

X-16x12 RA DN

X-20x20 SA DN

X-20x20 RA

X-24x24 EA

X-24x24 EA

UP TO X-RH-4

X-28"ø RA

X-28"ø SA

X-2"

X-AHU-11

X-3" X-3"

X-AHU-13

X-36x36 RA DN

X-1-1/2"

X-L

X-L

X-36x36 UP

TO X-RH-5

X-36x24 RA

X-50x20 SA

X-2"

X-24x24

SA DN

X-3/4"

X-36x36

SA DN

X-DDC CONTROL PANEL

X-DDC CONTROL PANEL

CC-300-1

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

22189.00

M a t r ix

472/21165.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

08/19/2022 CD SET

M-402

BRH

EDUCATION/RECREATION

BUILDING - (BLDG 300) -

MECHANICAL ROOM PLAN -

HVAC NEW

N

EDUCATION/RECREATION BUILDING - (BLDG 300) -

MECHANICAL ROOM PLAN - HVAC NEW

ENLARGED MECHANICAL ROOM

PLAN - HVAC NEW

SCALE: 1/2" = 1'-0"

0 1 5

SCALE: 1/4" = 1'-0"

JLH

X

X

X

TVSS

VFD

TRANSIENT VOLTAGE SURGE SUPPRESSION

VARIABLE FREQUENCY DRIVEDUPLEX RECEPTACLE

DOCK LIGHT FIXTURE

TELEPHONE / DATA OUTLET

ADDENDUM NOTE

PLAN NOTE

DEMOLITION NOTE

THREE PHASE MOTOR

ELECTRICAL SYMBOLS LEGEND

J

SINGLE RECEPTACLE (120 VOLT)

EMERGENCY RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

FLUSH FLOOR BOX

SURFACE FLOOR BOX

SPECIAL EQUIPMENT RECEPTACLE

TELEPHONE OUTLET

DATA OUTLET

POWER POLE

JUNCTION BOX

WALL JUNCTION BOX

PULL (JUNCTION) BOX

UNDERFLOOR JUNCTION BOX

OUTLETS

LIGHT FIXTURE

STRIP FIXTURE

IN-GRADE LIGHT FIXTURE

SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)

WALL MOUNT LIGHT FIXTURE

CEILING LIGHT FIXTURE

TRACK & FIXTURE

STREET TYPE POLE FIXTURE

POLE MOUNTED LIGHT FIXTURE

EXTERIOR WALL MOUNT LIGHT FIXTURE

WALLPACK LIGHT FIXTURE

SPECIAL PURPOSE LIGHT FIXTURE

HIGH BAY LIGHT FIXTURE

EMERGENCY EGRESS LIGHT FIXTURE

(number of heads shown)

EMERGENCY LIGHT FIXTURE

FIXTURES

SWITCHES

SINGLE-POLE SWITCH

DIMMER SWITCH

TIME SWITCH

KEY SWITCH

MANUAL MOTOR SWITCH

THERMAL OVERLOAD SWITCH

SWITCH WITH PILOT LIGHT

FOUR-WAY SWITCH

THREE-WAY SWITCH

CIRCUITRY and RACEWAYS

UNDERFLOOR DUCT

BUS DUCT

PLUGMOLD AS SPECIFIED

WIREMOLD AS SPECIFIED

FLEXIBLE PIGTAILS/CONNECTIONS

"CONDUIT RUN CONTINUES" INDICATION

END OF CONDUIT RUN, CAP AND STAKE

END OF CONDUIT RUN

HOME RUN (with circuit numbers)

CONDUIT STUB DOWN

CONDUIT STUB UP

CONDUIT INSTALLED

CONDUIT INSTALLED

MECHANICAL

ELECTRIC WATER HEATER

ELECTRIC UNIT HEATER

PIPE TRACE HEATER

RESISTANCE HEATER, KW SHOWN

SINGLE PHASE MOTOR

SERVICE and EQUIPMENT

THERMOSTAT

CAPACITOR

ENCLOSED CIRCUIT BREAKER

TRANSFER SWITCH

WIREWAY

GROUND CONNECTION PER N.E.C.

TELEPHONE TERMINAL BOARD

GENERATOR, KW SHOWN

CURRENT TRANSFORMERS

UTILITY METER, AS REQUIRED

WEATHERHEAD

PANELBOARD, FLUSH MOUNTED

PANELBOARD, SURFACE MOUNTED

COMB. STARTER (BY x/C U.O.N.)

MAGNETIC STARTER (BY x/C U.O.N.)

DISCONNECT SWITCH (fuse size shown)

TRANSFORMER

CONTROL

xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt

LIGHTING CONTACTOR

CONTROL TRANSFORMER

buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)

PHOTOCELL (voltage as required)

HUMIDISTAT

DESIGNATIONS

(by E.C.)

(by others)

TT

G

WW

PC

CT

TS

T

H

TC

IC

T

1,3

OR

PM

WM

BD

UFD

F S

J

J

D

WH

PP

J

CEILING MOUNTED WIFI

POLE

PUMP

PANEL

P

PNL

PVC

PRV-

P-

PB

POLY VINYL CLORIDE

POWER ROOF VENTILATOR

PULL BOX

GENERAL CONTRACTOR

GROUND

HUMIDIFIERH-

GND

GFI

GC

GROUND FAULT INTERUPTER

ABBREVIATIONS LEGEND

POWER

SWITCH

RECEPT

SF-

SWBD

TCC

SPEC

SW

RGC

RTU-

PWR

VOLTS

WATTS

UF

V

W

UL

VL

UNO

UH-

TS

TYP

TR

ROOF TOP UNIT

RECEPTACLE

SWITCHBOARD

UNDER FLOOR

SPECIFICATIONS

RIGID GALVANIZED STEEL CONDUIT

UNLESS NOTED OTHERWISE

UNDERWRITERS' LABORATORIES, INC.

TAMPER PROOF RECEPTACLE

TAMPER PROOF SWITCH

TEMPERATURE CONTROL CONTRACTOR

VERIFY LOCATION WITH OWNER

TYPICAL

UNIT HEATER

SUPPLY FAN

WITH

WITHOUT

W/

XFMR

W/O

WP

TRANSFORMER

WEATHER PROOF

HOUR

LIGHT

JUNCTION BOX

LIGHT CONTROL

ISOLATED GROUND

HORSEPOWER

MINIMUM

MOUNT

MAKE-UP AIR UNIT

MOTOR CONTROL CENTER

MAIN LUG ONLY

MOUNTED

MOUNTING

MAXIMUM

LIGHTING

LT FLEX

MTD

MUAU-

MTG

MLO

MIN

MT

MC

MAX

MCC

LTG

IG

LC

LT

IMC

JB

HR

HVAC

HOA

HP

NORMALLY CLOSED

NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

NIGHT LIGHTNL

NTS

NO

NIC

NC

HAND-OFF-AUTO SELECTOR SWITCH

HEATING/VENTILATING/AIR CONDITIONING

INTERMEDIATE METAL CONDUIT

LIQUID TIGHT FLEXIBLE METAL CONDUIT

MECHANICAL CONTRACTOR

HID HIGH INTENSITY DISCHARGE

A

AC

AFF

ACU-

AHJ

AHU-

AS

B-

BC

AIC

ATS

BLDG

CHLR-

CND (C)

CKT BKR

CKT

CUH-

CU-

DISC

DFU-

EF-

EC

DWH-

EBB-

DWG

CT-

EXIST (E)

EWC

FLEX

FLA

FLR

FSES

FLUOR

EMT

ABOVE FINISHED FLOOR

AIR CONDITIONING UNIT

AMPS

ABOVE COUNTER

AIR HANDLING UNIT

AUTOMATIC TRANSFER SWITCH

AMPS INTERUPTING CAPACITY

AUTHORITY HAVING JURISDICTION

ABOVE SHELF

BOILER

BUILDING

BELOW COUNTER

CHILLER

DOMESTIC WATER HEATER

CABINET UNIT HEATER

CIRCUIT

CIRCUIT BREAKER

CONDUIT

CONDENSING UNIT

COOLING TOWER

DUCT FURNACE

DRAWING

DISCONNECT

FOOD SERVICE EQUIP. SUPPLIER

ELECTRIC WATER COOLER

ELECTRICAL CONTRACTOR

ELECTRIC BASEBOARD

ELECTRICAL METALLIC TUBING

EXISTING

EXHAUST FAN

FLOOR

FLUORESCENT

FLEXIBLE CONDUIT

FULL LOAD AMPS

EM EMERGENCY

F/S FIRE/SMOKE

FU- FURNACE

GENERAL ELECTRICAL NOTES

1. ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED WITH LIKE MATERIAL TO

MAINTAIN ORIGINAL RATING.

2. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL

STEEL.

3. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID WALK THROUGH TO

DETERMINE THE EXACT EXTENT OF THE DEMOLITION WORK REQUIRED BEFORE

BIDDING THE PROJECT.

4. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT

WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.

5. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,

SURFACES SHALL BE PATCHED TO MATCH ADJACENT.

6. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN

CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED

NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH

SURFACE AND THEN PATCHED AND PAINTED TO MATCH, OR AS NOTED.

7. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED

TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND

PATCHING.

8. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO

MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.

9. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING

SERVICE TO EQUIPMENT.

10. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD

OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.

11. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. REFER TO SPECIFICATION 260533 -

RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.

12. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:

12.1. STRAP DISTANCE: 5 FEET.

12.2. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.

12.3. FITTINGS: COMPRESSION.

12.4. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.

13. ALL CONDUIT BELOW 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:

13.1. STRAP DISTANCE: 3 FEET.

13.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.

13.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.

13.4. FITTINGS: COMPRESSION.

13.5. BELL BOXES: FS TYPE.

13.6. NO KNOCKOUTS.

13.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES

14. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE

CEILINGS IS ACCEPTABLE.

15. CONDUITS SHALL BE INSTALLED STRAIGHT AND LEVEL AND SHALL BE PARALLEL OR

PERPENDICULAR TO THE BUILDING LINES.

16. CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.

17. ALL LOCATIONS WHERE THE WALLS CAN'T BE FISHED SHALL BE SURFACE MOUNTED

CONDUIT FOLLOWING NOTES 11 AND 12 ABOVE.

18. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.

19. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE

EPC-40-PVC

20. ANY ELECTRICAL OUTAGE SHALL NOT LAST OVER 2-HOURS. FOR OUTAGES OVER

PORTABLE GENERATORS SHALL BE USED TO REPLACE ANY ELECTRICAL SERVICE

EXCEEDING THAT DURATION.

21. UPON RELOCATING LIGHTS AND CAMERAS CONTRACTOR SHALL VERIFY THAT THE

LIGHTS AND CAMERAS ARE WORKING PROPERLY PRIOR TO LEAVING THE SITE.

22. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED COMPONENTS,

RACEWAYS, WIRE, AND HARDWARE, AS INDICATED ON DRAWINGS.

23. ALL WORK DONE WITHOUT APPROVED SHOP DRAWINGS IS AT CONTRACTORS RISK.

24. UPON RELOCATING LIGHTS AND CAMERAS CONTRACTOR SHALL VERIFY THAT THE

LIGHTS AND CAMERAS AREA WORKING PROPERLY PRIOR TO LEAVING THE SITE.

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

22189.00

M a t r ix

472/21165.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

08/19/2022 CD SET

E-100

JKB

JFS

ELECTRICAL

SYMBOLS

ABBREV.

+ NOTES

X-CU-2

X-CU-1

PNL "MPB"

CU-100-2

480V-3Ø, 140A

EX

CU-100-1

480V-3Ø, 140A

EXIST

PNL "MPB"

GFI/WP

EXISTING DEVICE TO REMAIN.

EXISTING EQUIPMENT TO REMAIN.

DISCONNECT EQUIPMENT FOR REMOVAL BY OTHERS. ALL ASSOCIATED

CONDUIT, WIRE, OVERCURRENT, AND CONTROL DEVICES ARE TO REMAIN.

DISCONNECT & RELOCATE EXISTING DEVICES. EXTEND EXISTING CONDUIT &

WIRE TO NEW LOCATION.

DEMOLITION NOTES

ELECTRICAL KEY NOTES

RECONNECT MECHANICAL EQUIPMENT TO ALL ASSOCIATED CONDUIT, WIRE,

OVERCURRENT, AND CONTROL DEVICES AT THIS LOCATION.

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

22189.00

M a t r ix

472/21165.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

08/19/2022 CD SET

E-500

JKB

JFS

ADMINISTRATION BUILDING -

(BLDG 100) - MECHANICAL

ROOM PLAN - ELECTRICAL

DEMOLITION & NEWN

ADMINISTRATION BUILDING - (BLDG 100) -

MECHANICAL ROOM PLAN - ELECTRICAL DEMOLITION

SCALE: 1/4" = 1'-0"

0 1 5 10 N

ADMINISTRATION BUILDING - (BLDG 100) -

MECHANICAL ROOM PLAN - ELECTRICAL NEW

SCALE: 1/4" = 1'-0"

PNL "DPB-C"

CU-200-1

480V-3Ø, 41.6A

EX

EXIST

PNL "DPB-C"

EXISTING DEVICE TO REMAIN.

EXISTING EQUIPMENT TO REMAIN.

DISCONNECT EQUIPMENT FOR REMOVAL BY OTHERS. ALL ASSOCIATED

CONDUIT, WIRE, OVERCURRENT, AND CONTROL DEVICES ARE TO REMAIN.

DISCONNECT & RELOCATE EXISTING DEVICES. EXTEND EXISTING CONDUIT &

WIRE TO NEW LOCATION.

DEMOLITION NOTES

ELECTRICAL KEY NOTES

RECONNECT MECHANICAL EQUIPMENT TO ALL ASSOCIATED CONDUIT, WIRE,

OVERCURRENT, AND CONTROL DEVICES AT THIS LOCATION.

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

22189.00

M a t r ix

472/21165.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

08/19/2022 CD SET

E-501

JKB

JFS

N

SUPPORT SERVICE BUILDING - (BLDG 200) -

MECHANICAL ROOM PLAN - ELECTRICAL DEMOLITION

SCALE: 1/4" = 1'-0"

0 1 5 10 N

SUPPORT SERVICE BUILDING - (BLDG 200) -

MECHANICAL ROOM PLAN - ELECTRICAL NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

SUPPORT SERVICE BUILDING -

(BLDG 200) - MECHANICAL

ROOM PLAN - ELECTRICAL

DEMOLITION & NEW

X-CU-2

CND TYP.

PNL "DPB-2"

PNL "DPB-1"

CU-300-2

480V-3Ø, 36FLA

CU-300-1

480V-3Ø, 36FLA

EXIST

PNL "DPB-2"

EXIST

PNL "DPB-1"

WP

WP

EXISTING DEVICE TO REMAIN.

EXISTING EQUIPMENT TO REMAIN.

DISCONNECT EQUIPMENT FOR REMOVAL BY OTHERS. ALL ASSOCIATED

CONDUIT, WIRE, OVERCURRENT, AND CONTROL DEVICES ARE TO REMAIN.

DISCONNECT & RELOCATE EXISTING DEVICES. EXTEND EXISTING CONDUIT &

WIRE TO NEW LOCATION.

DEMOLITION NOTES

ELECTRICAL KEY NOTES

NOT USED.

RELOCATED DEVICE EXTEND ALL ASSOCIATED CONDUIT,

WIRE, OVERCURRENT, AND CONTROL DEVICES AT THIS

LOCATION.

EXTEND ALL ASSOCIATED CONDUIT, AND WIRE, FOR NEW

DISCONNECT .

file no.

checked by drawn by consultant issue date contract order no.

consultant job no.

22189.00

M a t r ix

472/21165.SMD

funding code sheet description

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L

A C

H R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

08/19/2022 CD SET

E-502

JKB

JFS

N

EDUCATION/RECREATION BUILDING - (BLDG 300) -

MECHANICAL ROOM PLAN - ELECTRICAL DEMOLITION

SCALE: 1/4" = 1'-0"

0 1 5 10 N

EDUCATION/RECREATION BUILDING - (BLDG 300) -

MECHANICAL ROOM PLAN - ELECTRICAL NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

EDUCATION/RECREATION

BUILDING - (BLDG 300) -

MECHANICAL ROOM PLAN -

ELECTRICAL DEMOLITION &

NEW

Sheets and Views
M000-2218900-M000
M100 - 2218900-M100
M300 - 2218900-M300
M301 - 2218900-M301
M302 - 2218900-M302
M400 - 2218900-M400
M401 - 2218900-M401
M402 - 2218900-M402
CD Elec Set.pdf
E100-2218900-30x42
E500-2218900-30x42
E501-2218900-30x42
E502-2218900-30x42