This document is a set of construction drawings and specifications for the Ionia Correctional Facility HVAC Repair and Replacement project issued by the Michigan Department of Technology, Management and Budget for the Michigan Department of Corrections. The project involves demolishing existing air-cooled condensing units, cooling coils, and related piping and controls, and installing new condensing units, cooling coils, and associated piping and controls in three buildings on the Ionia Correctional Facility campus. The work is to be completed in multiple phases, with the administration building work done first, followed by the support service building and education/recreation building. The project requires the contractor to provide a construction schedule based on a start date of October 17, 2022, and prohibits construction on the air conditioning systems from June 1st through September 15th to ensure the systems remain fully operational during that period.
The procurement requires electronic bid submissions via the State of Michigan's SIGMA VSS system. Bidders must email questions to the project engineer rather than submitting them through the VSS system. The contract will be awarded by the Michigan Department of Technology, Management and Budget. No additional details are provided regarding pricing terms, set asides, incumbent contractors, funding sources, or other commercial aspects of the procurement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL DRAWING INDEX
1576 W. BLUEWATER HWY,
IONIA, MI 48846
FILE NUMBER: 472/21165.SMD
MATRIX PROJECT NUMBER: 22189.00
MECHANICAL DRAWING INDEX
MECHANICAL AND ELECTRICAL ENGINEER
SUPPORT SERVICE (BUILDING 200)
EDUCATION/RECREATION (BUILDING 300)
ADMINISTRATION (BUILDING 100)
N IONIA CORRECTIONAL FACILITY SITE MAP
STATE OF MICHIGAN
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
FOR DEPARTMENT OF CORRECTIONS
IONIA CORRECTIONAL FACILITY - HVAC REPAIR & REPLACEMENT
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
M-000
JLH
BRH
TITLE SHEET
GENERAL HVAC NOTES
1. ALL EXISTING SYSTEMS (INCLUDING AIR HANDLING UNITS) THAT SERVE AREAS BEING RENOVATED SHALL BE REBALANCED
AS REQUIRED.
2. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.
3. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY CONFLICT WITH NEW CONSTRUCTION AND RELOCATE AS
NEEDED.
4. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
5. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION, ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS
THAT MAY AFFECT THE WORK.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A
"NEW" CONDITION DURING CONSTRUCTION.
7. ALL WORK SHALL BE PERFORMED BY LICENSED CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.
8. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE, LATEST APPLICABLE EDITION.
9. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR SPECIFICATIONS THE MORE STRINGENT AND GREATER COST
ITEM SHALL BE USED.
10. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES. IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL NECESSARY OFFSETS. INSTALL WORK IN MANNER TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. DO NOT
SCALE FROM DRAWINGS.
11. CONTRACTOR TO NOTIFY THE FACILITY 3 DAYS IN ADVANCE FOR ANY HOT WORK TO ALLOW OWNER TO DISABLE THE FIRE
ALARM.
12. ALL ROOFING WORK SHALL MAINTAIN ALL EXISTING WARRANTIES. QUALITY ROOFING INC. (MIKE SZUMSKI, 734-550-9599)
CARRIES THE EXISTING CARLISLE ROOFING SYSTEMS WARRANTY.
13. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL USE TAMPERPROOF SCREWS.
14. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO OWNER OF THE AMOUNT OF MATERIAL BEING RECYCLED
THROUGHOUT THE PROJECT.
15. CONTRACTOR TO ATTEND A 6 MONTH AND AN 11 MONTH POST CONSTRUCTION MEETING WITH THE ENGINEER AND OWNER
TO REVIEW AND FIX ISSUES DURING THE WARRANTY PERIOD.
16. CONTRACTOR WILL HAVE 1 ESCORT TO WORK WITH THROUGHOUT THE PROJECT.
17. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER MANUFACTURER'S WRITTEN INSTRUCTIONS.
18. NO CONSTRUCTION ON THE AIR CONDITIONING SYSTEMS FROM JUNE 1ST THROUGH SEPTEMBER 15TH. ALL NEW AND EXISTING COOLING SYSTEMS TO BE FULLY OPERATIONAL DURING THE NO CONSTRUCTION PERIOD.
19. CONTRACTOR TO PROTECT ROOF AND MAINTAIN EXISTING CONDITION WHEN MOVING EQUIPMENT ON/OFF ROOF.
20. CONTRACTOR TO REPLACE CONDENSING UNITS ON BUILDING 100 FIRST, BUILDING 200 SECOND, AND BUILDING 300 LAST.
21. CONTRACTOR TO PROVIDE A CONSTRUCTION SCHEDULE FOR COMPLETION WITH THEIR BIDS BASED ON A START DATE OF
OCTOBER 17, 2022.
22. CONTRACTOR TO COORDINATE AIR HANDLING UNIT SHUTDOWNS WITH THE FACILITY 7 DAYS IN ADVANCE.
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLSHVAC PIPING
HVAC DUCTWORK
SD
F/S F/S s s
TEMPERATURE CONTROL SYMBOLS
M
P
M
H
S
T P T N
T
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
DIRECT EXPANSION
DEMOLITION
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)
FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
DXTAG CFM
NECK REMARKS
SIZE
SD-1 250
8"ø ---
ISOLATION
VALVES
FILTER DRYER
EXPANSION VALVE
(TYPICAL)
PITCH
EVAPORATOR COIL
L
CHARGING
VALVE
PITCH
CU
PITCH
S
SIGHT GLASS
NOTES:
1. PITCH ALL LINES MIN. 1/2" PER 10' IN
DIRECTION OF REFRIGERANT FLOW.
2. INSULATE SUCTION PIPING.
3. KEEP HORIZONTAL DISTANCE OF TRAPS TO
A MINIMUM.
4. PROVIDE TRAPS IF VERTICAL DISTANCE OF
PIPING EXCEEDS 8 FT.
EQUIPMENT MANUFACTURER TO PROVIDE
FACTORY APPROVED PIPING DETAIL VIA SHOP
DRAWINGS TO ENGINEER BEFORE CONSTRUCTION
BEGINS.
1 CONDENSING UNIT PIPING DIAGRAM
SCALE: NTS
TRAP
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O F
M
IC
H
IG
A N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
08/19/2022 CD SET
M-100
JLH
BRH
MECHANICAL SCHEDULES,
SYMBOLS, NOTES, AND
ABBREVIATIONS
DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING AIR
COOLED CONDENSING UNIT, DX PIPING, CONTROLS,
AND ALL ASSOCIATED ACCESSORIES IN THEIR
ENTIRETY. EXISTING CURB RAILS TO REMAIN AND
BE REUSED IN NEW DESIGN.
DISCONNECT, REMOVE, AND DEMO EXISTING DX
COOLING COILS, DX PIPING, AND ALL ASSOCIATED
ACCESSORIES IN THEIR ENTIRETY. MODIFY AIR
HANDLING UNIT ENCLOSURE AS REQUIRED TO
REMOVE EXISTING COOLING COILS.
DISCONNECT, REMOVE AND REINSTALL RETURN AIR
DUCTWORK AS REQUIRED TO REMOVE EXISTING DX
PIPING, REMOVE EXISTING COOLING COIL, INSTALL
NEW DX PIPING AND INSTALL NEW COOLING COIL.
DISCONNECT, REMOVE, AND RECONNECT EXISTING
HEATING SUPPLY AND RETURN PIPING AND ALL
ASSOCIATED ACCESSORIES AS REQUIRED TO
REPLACE COOLING COILS. REFER TO ENLARGED
HEATING COIL DETAIL ON SHEET M-300 FOR
EXTENTS OF HEATING SUPPLY AND RETURN PIPING
DEMOLITION. EXISTING HEATING COIL TO REMAIN.
DISCONNECT, REMOVE, AND DEMO EXISTING PIPING
SUPPORT UNISTRUT FRAME AND ALL ASSOCIATED
ACCESSORIES. EXISTING PIPING SUPPORT ROOF
CURB RAILS CAN BE REUSED IN NEW DESIGN WITH
THE ADDITION OF NEW PIPING SUPPORT UNITSTRUT
FRAME. ALTERNATIVELY, EXISTING PIPING SUPPORT
ROOF CURB RAILS CAN BE ABANDONED IN PLACE
AND REPLACED BY PIPING SUPPORTS CALLED OUT
ON NEW SHEET. IF PIPING SUPPORT CURB RAILS
ARE ABANDONED THE EXISTING PIPING SUPPORT
UNISTRUT FRAMES SHALL BE REMOVED AND CURB
RAILS SEALED WATER TIGHT.
X-CU-1 1
1X-CU-2
M
M
M
X-56x28 SA X-37x43 SA
X-FAN
SECTION
X-COIL SECTION
X-ACCESS SECTION
X-FILTER SECTION
X-MIXING PLENUM
X-D
X-L
X-L
X-56x28
RA DN
X-DX
X-DX
X-DX
X-54x48 RA X-72x48 RA
X-72x48 RA
X-72x48 RA
X-UH
X-2-1/2" HS
X-2-1/2" HR
X-2-1/2" HS
X-3/4" HS
X-3/4" HR
X-PP5
X-PP1
X-PP2
4" HS
X-4" HR
X-4" HSX-3" HS
X-3" HR
X-3" HR
X-2-1/2" HR
X-45x20 RA
X-1-1/2"
HS & HR
X-STACKED COOLING COILS
X-DDC TRANE
CONTROL
1 X-DX
X-PIPING SUPPORT
(TYP.)
X-DX
X-DX
M-300
X-RAIL
X-RAIL
HS
HR
X-RAIL
X-RAIL
X-STACKED COOLING COILS2
THERMOMETER (TYP.)
CIRC PUMP
HOSE END DRAIN VALVE
(TYP.)
HS
HR
COIL
MANUAL AIR
VENT
BALANCE (TYP.)
CHECK VALVE (TYP.)
CIRCUIT SETTERHS
HR
2-WAY MODULATING
CONTROL VALVE
SHUTOFF VALVE (TYP.)
M-300
BRH
ADMINISTRATION BUILDING -
(BLDG 100) - MECHANICAL
ROOM PLAN - HVAC
DEMOLITION
N
ADMINISTRATION BUILDING - (BLDG 100) -
MECHANICAL ROOM PLAN - HVAC DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10 file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
JLH
ENLARGED HEATING COIL DETAIL
SCALE: 1/8" = 1'-0"
0 1 5 10 20
COOLED CONDENSING UNIT, DX PIPING,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES
IN THEIR ENTIRETY. EXISTING CURB RAILS TO
REMAIN AND BE REUSED IN NEW DESIGN.
DISCONNECT, REMOVE, AND DEMO EXISTING DX
COOLING COILS, DX PIPING, AND ALL ASSOCIATED
ACCESSORIES IN THEIR ENTIRETY. MODIFY AIR
HANDLING UNIT ENCLOSURE AS REQUIRED TO
REMOVE EXISTING COOLING COILS.
DISCONNECT, REMOVE, AND DEMO EXISTING
PIPING SUPPORT UNISTRUT FRAME AND ALL
ASSOCIATED ACCESSORIES. EXISTING PIPING
SUPPORT ROOF CURB RAILS CAN BE REUSED IN
NEW DESIGN WITH THE ADDITION OF NEW PIPING
SUPPORT UNITSTRUT FRAME. ALTERNATIVELY,
EXISTING PIPING SUPPORT ROOF CURB RAILS
CAN BE ABANDONED IN PLACE AND REPLACED BY
PIPING SUPPORTS CALLED OUT ON NEW SHEET.
IF PIPING SUPPORT CURB RAILS ARE ABANDONED
THE EXISTING PIPING SUPPORT UNISTRUT
FRAMES SHALL BE REMOVED AND CURB RAILS
SEALED WATER TIGHT.
X-CU-1
M
X-D
X-L
X-UH
M
X-D
MX-D
X-42x24 RAX-42x24 RA
X-42x24 RA
X-14x16 SA X-10x16 SA
X-14x16 SA X-12x16 SA
X-8x16 SA X-12x16 SA
X-12x16 SA
X-8x16 SA
X-1-1/4"
X-2"
X-HR
X-HS
X-HR
X-HS
X-HR
X-HS
X-CA
X-
HR
X-
HS
X-1"
X-3/4"
X-1"
X-
HR
X-
HS
X-STM X-STM
X-UH
X-UH
X-1/4"
X-CA
X-1-1/4"
X-1-1/2"
HS & HR
X-1-1/2"
X-2"
X-11'x8'x4' PLENUM
X-L
X-CC
X-L
X-DX
X-HR
X-HS
X-AHU-6
X-AHU
CONTROL
PANEL
X-EF DDC
CONTROL
PANEL
X-PIPING SUPPORTS
(TYP.)X-DX1
X-RAIL 1
X-RAIL 1
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
M-301
BRH
SUPPORT SERVICE BUILDING
- (BLDG 200) - MECHANICAL
ROOM PLAN - HVAC
DEMOLITION
N
SUPPORT SERVICE BUILDING - (BLDG 200) -
MECHANICAL ROOM PLAN - HVAC DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10
JLH
COOLED CONDENSING UNIT, DX PIPING, DX
PIPING SUPPORTS, CONTROLS, AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
EXISTING CURB RAILS TO REMAIN AND BE
REUSED IN NEW DESIGN.
DISCONNECT, REMOVE, AND DEMO EXISTING DX
COOLING COILS, DX PIPING, AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
MODIFY AIR HANDLING UNIT ENCLOSURE AS
REQUIRED TO REMOVE EXISTING COOLING
COILS.
DISCONNECT, REMOVE, AND DEMO EXISTING
PIPING SUPPORT UNISTRUT FRAME AND ALL
ASSOCIATED ACCESSORIES. EXISTING PIPING
SUPPORT ROOF CURB RAILS CAN BE REUSED IN
NEW DESIGN WITH THE ADDITION OF NEW
PIPING SUPPORT UNITSTRUT FRAME.
ALTERNATIVELY, EXISTING PIPING SUPPORT
ROOF CURB RAILS CAN BE ABANDONED IN
PLACE AND REPLACED BY PIPING SUPPORTS
CALLED OUT ON NEW SHEET. IF PIPING
SUPPORT CURB RAILS ARE ABANDONED THE
EXISTING PIPING SUPPORT UNISTRUT FRAMES
SHALL BE REMOVED AND CURB RAILS SEALED
WATER TIGHT.
X-DX
X-CU-1 1
M-302
REFER TO MECHANICAL
ROOM ENLARGEMENT PLAN
ON SHEET M-302 FOR DX
PIPING CONTINUATION
X-RAILS 1
X-CU-2 1
X-RAILS 1
X-RAILS 1
X-RAILS 1
X-PIPE SUPPORT
(TYP.)
X-L
X-30x30 UP
TO X-RH-3
X-2"
X-EF
X-HR
X-HS
X-UH-12
X-AHU-12
X-30x30 RA DN
X-60x24 RA
X-54x24 RA X-64x24 RA
X-60x24
X-
HR
X-
HS
X-HR
X-HS
X-20x14 SA X-16x16 RA
X-16x12 RA DN
X-20x20 SA DN
X-20x20 RA
X-24x24 EA
X-24x24 EA
UP TO X-RH-4
X-28"ø RA
X-28"ø SA
X-2"
X-AHU-11
X-3" X-3"
X-AHU-13
X-36x36 RA DN
X-1-1/2"
X-L
X-L
X-36x36 UP
TO X-RH-5
X-36x24 RA
X-50x20 SA
X-2"
X-DX
X-DX
X-DX
X-DX
X-DX
X-DX
X-24x24
SA DN
X-3/4"
REFER TO ROOF PLAN ON SHEET
M-302 FOR DX PIPING CONTINUATION
X-36x36
SA DN
X-CC
X-CC
X-DXX-DX
X-DX
X-DDC CONTROL PANEL
X-DDC CONTROL PANEL
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
M-302
BRH
EDUCATION/RECREATION
BUILDING - (BLDG 300) -
MECHANICAL ROOM PLAN -
HVAC DEMOLITION
N
EDUCATION/RECREATION BUILDING - (BLDG 300) -
MECHANICAL ROOM PLAN - HVAC DEMOLITION
ENLARGED MECHANICAL ROOM
PLAN - HVAC DEMOLITION
SCALE: 1/2" = 1'-0"
0 1 5
SCALE: 1/4" = 1'-0"
M
M
M
X-56x28 SA X-37x43 SA
X-FAN
SECTION
X-COIL SECTION
X-ACCESS SECTION
X-FILTER SECTION
X-MIXING PLENUM
X-D
X-L
X-L
X-56x28
RA DN
X-54x48 RA X-72x48 RA
X-72x48 RA
X-72x48 RA
X-UH
X-2-1/2" HS
X-2-1/2" HR
X-2-1/2" HS
X-3/4" HS
X-3/4" HR
X-PP5
X-PP1
X-PP2
4" HS
X-4" HR
X-4" HSX-3" HS
X-3" HR
X-3" HR
X-2-1/2" HR
X-45x20 RA
X-1-1/2"
HS & HR
X-DDC TRANE
CONTROL
X-RAIL
X-RAIL
HS
HR
X-RAIL
X-RAIL
CU-100-1
CU-100-2
2 PIPING SUPPORTS
(TYP.)
DX
DX
DX
DX
CC-100-1 & CC-100-2 (STACKED)
31CC-100-3 & CC-100-4 (STACKED) 5
DX1
STEEL CROSS
BEAM (TYP.)
4STEEL CROSS
BEAM (TYP.)
1 DX
MECHANICAL KEY NOTES
INSTALL NEW CONDENSING UNIT, DX PIPING, COOLING COIL,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES PER
MANUFACTURE'S INSTALLATION INSTRUCTIONS AT LOCATION
SHOWN. MOUNT NEW CONDENSING UNIT ON EXISTING CURB
RAILS.
IF EXISTING PIPING SUPPORT ROOF CURB RAILS ARE
ABANDONED, SUPPORT REFRIGERANT PIPING WITH MIRO
24-BASE STRUT OR APPROVED EQUAL. SUPPORTS SHALL BE
CAPABLE OF BEING FIELD ADJUSTED BY CONTRACTOR TO
SUPPORT DX PIPING ON SLOPED ROOF WITH UP TO A 2% SLOPE.
SPACING AND QUANTITY OF PIPE SUPPORTS SHALL BE
DETERMINED BY PIPE SUPPORT MANUFACTURER, BUT NOT TO
EXCEED 8' SPACING. STRUT AND ALL HARDWARE FOR
SUPPORTS SHALL BE GALVANIZED AND BASES SHALL BE
POLYCARBONATE. INSTALL 1/8" THICK x 15.75" WIDE x 19.75"
LONG INJECTION MOLDED LOW DENSITY POLYETHYLENE PAD
BETWEEN DX PIPING CONDUIT SUPPORT AND ROOF, BASED ON
MIRO INDUSTRIES SUPPORT PAD. IF EXISTING PIPING SUPPORT
CURB RAILS ARE REUSUED, CONTRACTOR TO PROVIDE NEW
PIPING SUPPORT UNISTRUT FRAME AND ALL ASSOCIATED
ACCESSORIES TO MATCH EXISTING. TYPICAL FOR ALL DX PIPING.
INSTALL NEW COOLING COIL AT LOCATION SHOWN PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS. CONTRACTOR
TO FIELD MEASURE NEW COOLING COIL SIZE PRIOR TO
ORDERING. MODIFY EXISTING AIR HANDLING UNIT ENCLOSURE
AS REQUIRED TO INSTALL NEW COOLING COIL.
INSTALL AND FASTEN W8x58 STEEL CROSS BEAMS ON TOP OF
EXISTING CURB RAILS AS NEEDED TO LINE UP WITH
CONDENSING UNIT MOUNTING POINTS AND PROVIDE PROPER
MOUNTING. PROVIDE AND COORDINATE NUMBER OF CROSS
BEAMS WITH CONDENSING UNIT MANUFACTURE.
CU-100-1, CC-100-1, AND CC-100-2 ARE TO BE CIRCUITED
TOGETHER WITH DX PIPING AND BE INDEPENDENT OF CU-100-2,
CC-100-3, AND CC-100-4. CU-100-2, CC-100-3, AND CC-100-4 ARE
TO BE CIRCUITED TOGETHER WITH DX PIPING AND BE
INDEPENDENT OF CU-100-1, CC-100-1, AND CC-100-2 TO PROVIDE
100% COOLING CAPACITY REDUNDANCY.
CONNECT NEW CONDENSING UNIT AND COOLING COIL TO
EXISTING TRANE DDC CONTROL PANEL. EXISTING SEQUENCE OF
OPERATIONS TO REMAIN. MODIFY EXISTING CONTROLS AS
NEEDED TO MATCH NEW CONDENSING UNIT COMPRESSOR
STAGING AND MODULATION REQUIREMENTS.
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
22189.00
M a t r ix
472/21165.SMD
funding code sheet description
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
08/19/2022 CD SET
M-400
BRH
ADMINISTRATION BUILDING -
(BLDG 100) - MECHANICAL
ROOM PLAN - HVAC NEW
N
ADMINISTRATION BUILDING - (BLDG 100) -
MECHANICAL ROOM PLAN - HVAC NEW
SCALE: 1/4" = 1'-0"
| Sheets and Views |
| M000-2218900-M000 |
| M100 - 2218900-M100 |
| M300 - 2218900-M300 |
| M301 - 2218900-M301 |
| M302 - 2218900-M302 |
| M400 - 2218900-M400 |
| M401 - 2218900-M401 |
| M402 - 2218900-M402 |
| CD Elec Set.pdf |
| E100-2218900-30x42 |
| E500-2218900-30x42 |
| E501-2218900-30x42 |
| E502-2218900-30x42 |